2021.0253.MP0060 204875 FSE Combined ME & SE 100% Drawings■ ^Mnstry ^Life Of Your Building McKINSTRY Co, LLC MECHANICAL INDEXGRILLE/REGISTER/DIFFUSERDUCTWORK ACCESSORIESPIPING IDENTIFICATIONABBREVIATIONS MeSHEET NAMESHEET NO PROJECT SPECIFICPROJECT SPECIFIC MECHANICAL LEGEND & ABBREVIATIONSM-001HVACGENERALHVAC MECHANICAL GENERAL NOTES, BASIS OF DESIGN, & RESPONSIBILTY MATRIXM-002 RETURN PIPING SUPPLY PIPING AIR CONDITIONING AIR HANDLING UNIT AD ACCESS DOOR ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AC MECHANICAL SPECIFICATIONSM-003SUPPLY GRILLE CEILING SUPPLY AIR DIFFUSERAHUAFF ForThMECHANICAL SPECIFICATIONSM-004AFC CONTROLS DIAGRAMSM-020BDDBACKDRAFT DAMPER BOTTOM OF DUCT CONTROLS DIAGRAMS & SEQUENCE OF OPERATIONSM-021RETURN OR EXHAUST GRILLEBRAKE HORSEPOWER BOTTOM OF PIPE BOTTOM BODBHP PIPING FITTINGS MECHANICAL DIAGRAMSM-030CEILING RETURN GRILLE OR TRANSFER AIR GRILLE BOP COOLING COIL COMPUTER ROOM UNIT COOLING TOWER CONSTANT VOLUME CCBOT MECHANICAL SCHEDULESM-060 CRU -e-TEE UP TEE DOWN MECHANICAL SCHEDULESM-061VOLUME DAMPER CTC/L CENTER LINE CEILING CUBIC FEET PER MINUTE CARBON MONOXIDE CARBON DIOXIDE CURRENT SENSING RELAY SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 LEVEL 1 - MECHANICAL PLAN - OVERALLM-100CVCLG LEVEL 1 - MECHANICAL DEMO PLAN - AREA AMD-101TEE DN W/ ELBOW TEE UP W/ELBOW 90° ELBOW UP 90° ELBOW DN CFM CEILING EXHAUST GRILLE_£ J,LEVEL 1 - MECHANICAL DEMO PLAN - AREA BMD-102DUCT BOARD DIFFUSER DAMPER SUPPLY AIR-DOAS DEDICATED OUTSIDE AIR SYSTEM CO DB MOTOR OPERATED DAMPERDIFFC02 LEVEL 1 - MECHANICAL DEMO PLAN - AREA CMD-103 OCSRDMPR LEVEL 1 - MECHANICAL DEMO PLAN - AREA DMD-104LINEAR DIFFUSER (CEILING)DOA £>LEVEL 1 - MECHANICAL DEMO PLAN - AREA EMD-105DOASDISCHDISCHARGE DOWN DISCONNECT SWITCH; DOOR SWITCH -]CAP LEVEL 1 - MECHANICAL PLAN - AREA AM-101LINEAR DIFFUSER (WALL)DN www.mckinstry.comAIRFLOW MONITOR LEVEL 1 - MECHANICAL PLAN - AREA BM-102UNION FLANGE FLEX HOSE CONNECTION DOUBLE BELLOWS FLEX CONNECTION SINGLE BELLOWS FLEX CONNECTION FLOW ARROW REDUCER EXHAUST AIR-GENERAL EXHAUST AIR-TYPE 2 ENTERING AIR TEMPERATURE EGGCRATE GRILLE EXHAUST FAN DS EA LEVEL 1 - MECHANICAL PLAN - AREA CM-103EA2LOUVER PLAN VIEW PROJECT:(E)EXISTING EAT M-104 LEVEL 1 - MECHANICAL PLAN - AREA D ECGEA EACH LEVEL 1 - MECHANICAL PLAN - AREA EM-105 YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE EC ELECTRICAL CONTRACTOR; END CAP ELECTRICAL PANEL; END PLUG EMERGENCY POWER OFF EXTERNAL STATIC PRESSURE EF REMOTELY OPERATED VOLUME DAMPER (YOUNG REGULATOR OR APPROVED)MECHANICAL DETAILSM-500■D-EP LOUVER (ELEVATION VIEW)FAN COIL UNIT FIRE DAMPER EXHAUST AIR-FUME FREQUENCY MODULATION FIRE PROTECTION; FAN POWERED COMBINATION FIRE/SMOKE DAMPER FAN TERMINAL UNIT FCUEPO FDESP ■>NORTHFE1% (F)FMFUTURE FIRE ALARM FIRE DEPARTMENT CONNECTION FOUNDATION FLEXIBLE FLOOR FIRE PROTECTION FOOTING SLOPE SYMBOL BREAK OR CONTINUATION SYMBOL DOWN SPOUT NOZZLE CLEANOUT BACK DRAFT DAMPER COORDINATE WITH CEILING APPURTENANCES.VICINITY MAPFA FP *FSDFDC CsOaFTUFDNCD 1 HVAC - ANNOTATIONFLEXFLEX CONNECTIONEXHAUST AIR-GREASE GRILLE, REGISTER, DIFFUSER EXHAUST AIR-GARAGE GDFLR GRDFP Olf EQUIPMENT/LOUVER TAGVALVES o.GXFTG Va n'SL ‘'o ■fFIRE DAMPER THROUGH WALL *r %XHEATING COIL HEATING, VENTILATION AND AIR CONDITIONING GA HCGAGE GALVANIZED GENERAL CONTRACTOR EQUIPMENT DESIGNATIONEFHVACGALVMOTORIZED 2-WAY VALVE MOTORIZED 3-WAY VALVE 2-1GCFIRE DAMPER THROUGH FLOOR lOGtii W„y $rCaY CiLEAVING AIR TEMPERATURE LINEAR DIFFUSER SUPPLY AIR - LOW PRESSURE LAT CONSECUTIVE EGUIPUIPMENT #HORSEPOWER; HIGH PRESSURE HEATING HEATER LDHP PRESSURE REDUCING VALVE CONTROL VALVE 9 Fort Stevens Elementary School V.5:LPSHTG 16525 100th WaySE Yelm, WA 98597 <?FIRE/SMOKE DAMPER THROUGH WALL HTR FLOOR OF EQUIP. LOCATIONMIXED AIR MOTOR OPERATED DAMPER; MODULATING MAKE-UP AIR UNIT SUPPLY AIR - MEDIUM PRESSURE SUPPLY AIR-MAKE-UP AIR MA SRELIEF VALVE BALL VALVE 3-WAY GATE VALVE BUTTERFLY VALVE DIAPHRAGM VALVE CHECK VALVE NEEDLE VALVE GLOBE VALVE GLOBE VALVE ANGLE GLOBE VALVE 3-WAY GATE VALVE PLUG VALVE BALANCING VALVE HOSE BIBB AUTO FLOW VALVE IN ACCORDANCE WITH INSIDE DIAMETER/DIMENSION INCHES WATER COLUMN MODIAW MAUID FIRE/SMOKE DAMPER THROUGH FLOOR$S GRILLE. REGISTER. OR DIFFUSER TAG -------------TYPE CODE I-----------WIDTH 1 •-------HEIGHT MPSIN WC CONSULTANTS:MUA MECHANICAL CONTRACTOR MANUFACTURER MANHOLE MOUNTED MC ACCESS DOORS uS-JYflm .IcKcr.n.s Rd SD>AD I +OUTSIDEAIR OPPOSED BLADE DAMPER OAMFR American Legion Post 164 4 OHY.'t McXc-maP-iSLtC Ave C;OBD s "SWG-WxH %ADMTD 52xCFMDollar Tree S v.•%SUPPLY AIR - PRESSURIZATIONPA ACOUSTICALLY LINED DUCT (X" THICK SOUND LINING)fN/A NOT APPLICABLE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN; NUMBER NOMINAL NOT TO SCALE 12x12 XSL CFMRETURN AIR RETURN AIR TEMPERATURE ROOFTOP UNIT RANC fMountain Lumber &• HardwareRATNICfIronic nabis eRUnited States Postal Service Dairy Queen Grill & Chill AutoZone Auto Paris Store 9RTUNOXI a CHANGE OF ELEVATION RISE(R) DROP(D)NOM SUPPLY AIR SUPPLY AIR TEMPERATURE SMOKE DAMPER; SMOKE DETECTOR EXHAUST AIR-SMOKE SUPPLY FAN SOUND LINED SOUND LINED SHEET METAL SHEET METAL SCREENED OPENING STATIC PRESSURE SANTS Walmart SupercenterotSATGENERAL INFORMATION SYMBOLS %-X -• xr I^ThVUPS 7vSDOCON CENTER OUTSIDE DIAMETER OVERHEAD r-7.?TURNING VANES *7‘fr.Yelm Liquor and BeverageODSE-th-Starbucks ^ Q / 5.County Line blmg Sports VSFOVHDfGravity'Coffeo.iYelm •SL fNEW MECHANICAL WORK mmmsiimmsm mmmRETURN / EXHAUST / OUTSIDE AIRSLSMPERFORATED POINT OF CONNECTION PERF ISSUE:PIPING ACCESSORIES FUTURE Tl SCOPE & NEW WORK OTHER THAN MECHANICAL SMPOC PROJECT SITESUPPLY/TRANSFER AIRSO PERMIT SUBMITTALSPQTYQUANTITY £PUMP POINT OF CONNECTION TRANSFER AIR TRANSFER GRILLE TOP OF DUCT (R)RELOCATED TA LEGAL DESCRIPTIONMVTGDUCTWORKaMANUAL AIR VENT POINT OF DEMOLITIONREFLECTED CEILING PLAN REQUIRED TODRCP AVREQD REGISTRATION:IN THE COUNTY OF THURSTON, STATE OF WASHINGTONAUTOMATIC AIR VENTVAVVARIABLE AIR VOLUME VOLUME DAMPER <L CENTERLINEHAVSECTION SIMILAR SPECIFICATION STANDARD VDSECT RECTANGULAR DUCT W/& LOTS 3,4, AND 5 IN BLOCK 36 OF MCKENNA IRRIGATED TRACTS AS RECORDED IN VOLUME 9 OF PLATS. PAGE 43: EXCEPTING THEREFROM THAT PART OF SAID LOT 3 LYING SOUTHERLY AND SOUTHEASTERLY OF A LINE DESCRIBED AS BEGINING AT A POINT ON THE EAST LINE OF SAID LOT 3,365.11 FEET NORTH OF ITS SOUTHEAST CORNER AND RUNNING THENCE WEST 520.87 FEET AND SOUTH 36° 20' WEST 409.7 FEET TO A POINT ON THE WESTERLY LINE OF SAID LOT, NORTH 39°05'44" WEST 121.67 FEET FROM ITS SOUTHWEST CORNER; AND EXCEPT THAT PORTION OF SAID LOTS 3 AND 4 DESCRIBED AS FOLLOWS: HIGH CAPACITY AIR VENTSIMPIPINGs SUPPLY AIR DUCT TURNING UP OR TOWARD KEY NOTE REFERENCESPECSTEAM BLOWDOWN BACKFLOW PREVENTER BDSTD SHOCK ARRESTORBP X PIPING RISER CALLOUT (CHW; HW) PIPING RISER# FS hiRECTANGULAR DUCTTBDTO BE DETERMINED TENANT IMPROVEMENTS TOP OF CONCRETE TOP OF STEEL TOTAL STATIC PRESSURE TYPICAL coFLOW SWITCH XCA COMPRESSED AIR CHILLED WATER RETURN CHILLED WATER SUPPLY CLEAN LOW PRESSURE STEAM CONDENSATE CONDENSER WATER RETURN CONDENSER WATER SUPPLY SUPPLY AIR DUCT TURNING DOWN OR AWAY tom\/Tl "3VB toCHWR CHWS /\TOC k.o 20106252VACUUM BREAKER XTOS PLAN NUMBER SHEET NUMBER WHERE PLAN SHOWN %£CLPS SrRECTANGULAR DUCTTSP XCNDS CNDWR CNDWS PRESSURE GAUGE THAT PORTION OF LOTS 3 AND 4 IN BLOCK 36 OF MCKENNA IRRIGATED TRACTS, ACCORDING TO THE PLAT THEREOF AS RECORDED IN VOLUME 9 OF THE PLATS, PAGE 44, RECORDS OF SAID COUNTY, DESCRIBED AS FOLLOWS: BEGINNING AT THE SOUTHEAST CORNER OF SAID LOT 3, THENCE NORTH 0°14;34" WEST ALONG THE EASTERLY LINE OF SIAD LOT 3 A DISTANCE OF 365.11 FEET; THENCE SOUTH S9°45'26" A WEST 290.78 FEET; THENCE SOUTH 53°25'26' WEST 30.88 FEET TO THE WESTERLY LINE OF { SECTION 20, TOWNSHIP 17 NORTH, RANGE 2 EAST, W.M.; THENCE NORTH 0°02'18" EAST ALONG THE WESTERLY LINE OF SAID SECTION 20 A DISTANCE OF 348.02 FEET; THENCE SOUTH 80°32'16" EAST 54.74 FEET; THENCE SOUTH 39°17'32" EAST 412.68 FEET MORE OR LESS TO THE TRUE POINT OF BEGINNING. RETURN AIR DUCT TURNING UP OR TOWARD TYP TEMPERATURE SENSORUNDERGROUND UNLESS NOTED OTHERWISE UG 0 X DETAIL OR DIAGRAM NUMBER SHEET NUMBER WHERE DETAIL/DIAGRAM SHOWN RECTANGULAR DUCTUNOTANK OVERFLOW & DRAINS DUAL TEMPERATURE RETURN DUAL TEMPERATURE SUPPLY DRAIN RETURN AIR DUCT TURNING DOWN OR AWAY X 7DTRTEMPERATURE INDICATOR ISSUES:VARIABLE FREQUENCY DRIVE VARIABLE SPEED DRIVE VFD DTS FM k.VSD NO DATE DESCRIPTIONIFLOW METER 1RECTANGULAR DUCT 04/29/2021 PERMIT SUBMITTALENTERING WATER TEMPERATUREEWTW/WITH X SECTION LETTER SHEET NUMBER WHERE SECTION SHOWN EXHAUST AIR DUCT TURNING UP OR TOWARD Y STRAINER W/BALL VALVEW/O WITHOUT WATER COLUMN WATER GAUGE FLUE CONDENSATE DRAIN BOILER FEED WATER FUEL OIL FILL FUELOIL RETURN FUEL OIL SUPPLY FUEL OIL VENT FCD XWCFEEDPIPE SLEEVEWGFOF RECTANGULAR DUCT FOR F REVISION NUMBER - DENOTES NUMBER AND DATE WHEN REVISION OR ISSUE OCCURED REVISION CLOUD - DENOTES AREA OF CHANGE EXHAUST AIR DUCT TURNING DOWN OR AWAY STEAM TRAP X FOS / k.FOV X PETES PLUG ROUND DUCTNATURAL GAS NATURAL GAS - LOW PRESSURE, 2 PSI NATURAL GAS - LOW PRESSURE, 5 PSI G SUCTION DIFFUSER W/ STRAINER SUPPLY AIR DUCT TURNING UP OR TOWARD 2# G 5#G f RPBP REDUCED PRESSURE BACKFLOW PREVENTOR X DETAIL REFERENCE OUTLINE WITH NUMBER AND SHEET LOCATION ROUND DUCTGENERATOR EXHAUST GEO-FIELD WATER RETURN GEO-FIELD WATER SUPPLY GROUND WATER RETURN GROUND WATER SUPPLY XGE A,GFWR GFWS SUPPLY AIR DUCT TURNING DOWN OR AWAY YINSTRUMENTATION AND CONTROLSGWR ROUND DUCTGWS /RETURN AIR DUCT TURNING UP OR TOWARD/HIGH PRESSURE CONDENSATE HIGH PRESSURE STEAM HEATING WATER RETURN HEATING WATER SUPPLY HPC T THERMOSTAT/HPS /HWR ROUND DUCTSENSORS HWS SR ENGINEER:/DLSRETURN AIR DUCT TURNING DOWN OR AWAY CARBON MONOXIDE SENSOR Y AP/SADRAWN BY:LOW PRESSURE CONDENSATE LIQUEFIED PROPANE GAS LOW PRESSURE STEAM LEAVING WATER TEMPERATURE LPC LPG CARBON DIOXIDE SENSOR ROUND DUCT QC BY:LHLPS EXHUAST AIR DUCT TURNING UP OR TOWARD LWT JOB NO:204875-003OCCUPANCY SENSOR,occ: 04/29/2021ISSUED ON:MEDIUM PRESSURE CONDENSATE MEDIUM PRESSURE STEAM MPC SMOKE DETECTOR ROUND DUCTMPS A EXHAUST AIR DUCT TURNING DOWN OR AWAY ( V SHEET TITLE:PROCESS COLD WATER PROCESS COOLING WATER RETURN PROCESS COOLING WATER SUPPLY PROCESS HOT WATER PROCESS HOT WATER RETURN PCW Y PCWR PCWS MECHANICAL LEGEND & ABBREVIATIONSPHW OVAL DUCTPHWR SUPPLY AIR DUCT TURNING UP OR TOWARDREFRIGERATION LIQUID REFRIGERATION SUCTION REFRIGERATION VENT RL RS RV OVAL DUCT f-SOFTENED COLD WATER STEAM RELIEF VENT SCW SUPPLY AIR DUCT TURNING DOWN OR AWAY x SRV TOP TOP OF PIPE SHEET NUMBER: FLEXIBLE DUCT M-001BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:03 AMS-001 SYMBOLS, GENERAL NOTES AND CONNECTION DETAILS S-101 PARTIAL PLAN S-102 PARTIAL PLAN S-103 PARTIAL PLAN ^tjlasky Wife Of Your Building McKINSTRY Co, LLC PIPING NOTESSUBMITTAL NOTESGENERAL NOTESFORT STEVENS ELEMENTARY SCHOOL HVAC BASIS OF DESIGN Me,DATE LAST MODIFIED CRITERIA SOURCEITEM# SYSTEM CRITERIA BACKFLOW DEVICES, CROSS CONTROL DEVICES, VACUUM BREAKER AND DOUBLE CHECK VALVES TO BE A TYPE APPROVED BY THE STATE OF WASHINGTON HEALTH SERVICES DIVISION. 1.PROVIDE A HVAC/PLUMBING EQUIPMENT AND COMPONENT SUBMITTAL PACKAGE. INCLUDE IN THE PACKAGE SUBMITTALS FOR ITEMS INCLUDED ON THE SCHEDULE AND/OR SPECIFICATION SHEETS. ALSO INCLUDE SUBMITTALS FOR VALVES, GAUGES, AND INSTRUMENTATION. PIECEMEAL SUBMITTALS ARE NOT ACCEPTABLE. 1.1. THE CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE AND DETERMINE THE EXACT EXTENT OF WORK, COORDINATION, DEMOLITION, TEMPORARY CONSTRUCTION, TEMPORARY FACILITIES, ETC., NECESSARY TO COMPLETE THE PROJECT AS INDICATED IN THE CONTRACT DOCUMENTS.CODE BASIS FOR PROJECT 2018 INTERNATIONAL BUILDING CODE WITH WA STATE AMENDMENTS1-1 4/1/2021 CODE INSTALL AIR VENTS AT HIGH POINTS IN HYDRONIC PIPING. INSTALL DRAIN VALVES IN LOW POINTS IN HYDRONIC PIPING. 2.ForTh2018 INTERNATIONAL EXISTING BUILDING CODE WITH WA STATE AMENDMENTS4/1/2021 CODE1-2 INTERRUPTIONS OF SERVICES (POWER, WATER, HVAC, ETC.) AND WORK IN OCCUPIED TENANT SPACES MUST BE SCHEDULED THRU THE MCKINSTRY CONSTRUCTION MANAGER A MINIMUM OF 24 HOURS IN ADVANCE. ANY INTERRUPTIONS OR CONSTRUCTION WHICH WILL AFFECT NORMAL OPERATION OF THE BUILDING OR TENANTS MUST BE SCHEDULED, WITH THE MCKINSTRY CONSTRUCTION MANAGER’S APPROVAL, ON AN AFTER-HOURS BASIS. 2. 2018 INTERNATIONAL MECHANICAL CODE WITH WA STATE AMENDMENTS1-3 4/1/2021 CODE PROVIDE CONTRACTOR PREPARED SHOP DRAWINGS OF CONTRACTOR FABRICATED SHEET METAL SYSTEMS. DRAWINGS SHALL BE PREPARED AT 1/4" SCALE USING COMPUTER AIDED DESIGN (CAD) SOFTWARE UNLESS INDICATED OTHERWISE. DRAWINGS SHALL SHOW EXACT LOCATION OF EQUIPMENT AND DUCTWORK, EACH SECTION OF SHOP FABRICATED DUCT AND LOCATION OF FIELD JOINTS, SUPPORTS, AND BUILDING ATTACHMENTS, AND SEISMIC RESTRAINT LOCATIONS. 2. 2018 NATIONAL FUEL GAS CODE (NFPA 54)1-4 4/1/2021 CODE PROVIDE FLANGES OR UNIONS AT PIPING CONNECTIONS TO EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER COMPONENTS TO ALLOW FOR MAINTENANCE. 3. 4/1/2021 CODE 2018 INTERNATIONAL FUEL GAS CODE1-5 CITY OF YELM, WA MUNICIPAL CODE2018 INTERNATIONAL FIRE CODE WITH WA STATE AMENDMENTS ENFORCED BY LOCAL JURISDICTION4/1/2021 CODE1-6 PROVIDE REDUCERS AS REQUIRED FROM LINE PIPE SIZE TO EQUIPMENT, TRAP, COIL, AND CONTROL VALVE CONNECTION SIZES.3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR TEMPORARY CONDITIONING DURING CONSTRUCTION. PERMANENT MECHANICAL EQUIPMENT SHALL NOT BE USED FOR TEMPORARY CONDITIONING WITHOUT PROTECTION FROM DUST ACCUMULATION, WRITTEN ACCEPTANCE OF DUST RELATED WARRANTY COSTS, AND PRIOR APPROVAL BY THE MECHANICAL ENGINEER. 2018 UNIFORM PLUMBING CODE WITH WA STATE AND CITY OF YELM AMENDMENTS 2018 WASHINGTON STATE ENERGY CODE ENFORCED BY LOCAL JURISDICTION 1-7 4/1/2021 CODE SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 PROVIDE CONTROLS SUBMITTAL PACKAGE. INCLUDE IN THE PACKAGE SUBMITTALS FOR SEQUENCE OF OPERATIONS, SYSTEM DIAGRAMS, ARCHITECTURE DIAGRAMS, PLANS, PLUS EQUIPMENT AND COMPONENTS. ALSO INCLUDE A BAS GRAPHICS DISPLAY SUBMITTAL SHOWING ALL CONTROLLABLE AND ADJUSTABLE POINTS AS WELL AS VIEWING POINTS. SEE 'CONTROLS SYSTEM AND GRAPHIC NOTES' FOR ALL ITEMS TO BE INCLUDED IN GRAPHICS. 3.4/1/2021 CODE PROVIDE OFFSETS FOR BRANCH LINES TO EQUIPMENT TO ALLOW FOR SERVICE AND MAINTENANCE OF EQUIPMENT. 5. 2020 NATIONAL ELECTRICAL CODE (NFPA 70)1-9 4/1/2021 CODE BASIS FOR LOAD CALCULATIONS PROVIDE DIELECTRIC UNIONS AT CONNECTIONS OF DISSIMILAR PIPE MATERIALS.6.4. FURNISH LABOR, MATERIALS, EQUIPMENT, APPARATUS AND APPURTENANCES REQUIRED FOR A COMPLETE WORKING AND COORDINATED SYSTEM. MATERIALS, EQUIPMENT, APPARATUS, AND APPURTENANCES SHALL MATCH EXISTING BUILDING STANDARDS IN QUALITY, TYPE AND FINISH, UNLESS OTHERWISE NOTED. 2018 WSEC RECOMMENDED OUTDOOR DESIGN TEMPS (OLYMPIA) OUTDOOR TEMPERATURE4/1/2021 WINTER OSA DESIGN TEMP = 17°F DB2-1 PIPE SUPPLY WATER LINES TO BOTTOM OF COILS LEAVING AIR SIDE TO OBTAIN COUNTERFLOW ARRANGEMENT. 7.SUBMITTALS FOR MECHANICAL EQUIPMENT REQUIRING LINE-VOLTAGE POWER SHALL INCLUDE THE FOLLOWING ITEMS: VOLTAGE, PHASE, HORSEPOWER, FLA (FULL LOAD AMPS), MCA (MINIMUM CIRCUIT AMPACITY), MOCP (MAXIMUM OVERCURRENT PROTECTIVE DEVICE), AND SCCR (SHORT CIRCUIT CURRENT RATING). SUBMITTALS SHALL ALSO INCLUDE AN ELECTRICAL WIRING SCHEMATIC, UNLESS THE EQUIPMENT CONSISTS SOLELY OF A THREE-PHASE INDUCTION MOTOR. 4.OUTDOOR TEMPERATURE 2018 WSEC/ASHRAE4/1/2021 SUMMER OSA DESIGN TEMP = 83°F DB, 66°F WB2-2 www.mckinstry.com COOLING MODE: CONDITIONED SPACES = 75°F DB, 50% RELATIVE HUMIDITY UNCONDITIONED SPACES = 80°F DB, 50% RELATIVE HUMIDITY PROVIDE REFRIGERANT LINE SIZING AND INSTALLATION IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. PIPE SIZES NOTED ARE FOR REFERENCE ONLY. 5. VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT. COORDINATE THE EXACT LOCATIONS OF NEW MECHANICAL AND PLUMBING EQUIPMENT WITH THE LOCATIONS OF LIGHTING FIXTURES, PIPING, AND OTHER CONSTRUCTION, TO ALLOW FOR PROPER ACCESS TO SERVICE AND MAINTAIN EQUIPMENT PRIOR TO START OF CONSTRUCTION. PROJECT: INDOOR DESIGN CRITERIA BASIS OF DESIGN / 2018 WSEC C302.12-3 4/1/2021 PROVIDE PRESSURE AND TEMPERATURE TEST PORTS AT SUPPLY AND RETURN PIPING CONNECTIONS TO EQUIPMENT. 9.CONTROLS SYSTEM AND GRAPHIC NOTES YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE HEATING MODE: CONDITIONED SPACES = 70°F DB, 50% RELATIVE HUMIDITY UNCONDITIONED SPACES = 65°F DB, 50% RELATIVE HUMIDITY 6. COORDINATE THE LOCATION OF DUCTWORK AND PIPING WITH OTHER TRADES. PROVIDE OFFSETS IN DUCTWORK AND PIPING AS REQUIRED AT NO ADDITIONAL COST TO OWNER.SIZE BALANCING/MEASURING VALVES IN ACCORDANCE WITH MANUFACTURER’S INSTRUCTIONS. DO NOT PROVIDE VALVES LARGER THAN LINE SIZE. 10.MAIN CONTROL PORTAL: ONE COMMON SCREEN PER BUILDING THAT DISPLAYS AND PROVIDES THE ABILITY TO MANIPULATE THE ASPECTS OF SCHEDULING AND SET POINTS FOR THE FACILITY ON A GLOBAL LEVEL SHALL BE INCORPORATED INTO THE CONTROLS DELIVERABLE. 1. CLASSROOM: 36 PEOPLE /1000 SF GYMNASIUM: 35 PEOPLE /1000 SF COMPUTER LAB: 33 PEOPLE /1000 SF LOUNGE: 33PEOPLE/1000SF OFFICE: 10 PEOPLE/1000 SF CORRIDOR: 10 PEOPLE /1000 SF 7. TRADES TO LEAVE 36” CLEARANCE IN FRONT OF MECHANICAL EQUIPMENT ACCESS PANELS FOR SERVICING.PLUMBING NOTESBASIS OF DESIGN / 2018 IMC, CHP 4, TBL 403.3.1.14/1/2021 OCCUPANT DENSITY2-5 GRAPHICS SHALL MIRROR THE BUILDING FLOOR PLANS, WITH IDENTIFIABLE ROOM AND EQUIPMENT/SYSTEM LOCATIONS. 2.8. INSTALL DUCTWORK AND PIPING TO ALLOW MINIMUM ACCESS OF 6" ABOVE AND TO THE SIDE OF THE ELECTRICAL CABLE TRAYS. 1. INSTALL PIPED UTILITIES ON WARM SIDE OF BUILDING INSULATION WHERE THE SERVICE IS SUBJECT TO FREEZING TEMPERATURES.GRAPHICS SHALL BE LINKABLE TO SPECIFIC EQUIPMENT, SYSTEM POINTS AND OPERATING PARAMETERS WHICH ALLOW FOR 'ONE CLICK’ DIAGNOSIS WHEN ISSUES ARE IDENTIFIED. 3.9. SUPPORT CONDUIT, PIPING, AND DUCTWORK INDEPENDENTLY. SUPPORTS ARE INDEPENDENT OF PARTITION AND CEIUNG SYSTEM SUPPORTS. CLASSROOM: 240 (SENS) /150 (LAT) BTU/H GYMNASIUM: 300 (SENS) / 350 (LAT) BTU/H COMPUTER LAB: 240 (SENS) /150 (LAT) BTU/H LOUNGE: 250 (SENS) / 200 (LAT) BTU/H OFFICE: 250 (SENS) / 200 (LAT) BTU/H CORRIDOR: 250 (SENS) / 200 (LAT) BTU/H BASIS OF DESIGN / 2017 ASHRAE FUNDAMENTALS RECOMMENDED OCCUPANT HEAT GAINS 2. PIPE COOLING COIL CONDENSATE DRAIN TRAP PER MANUFACTURER’S RECOMMENDATIONS AND ROUTE TO NEAREST APPROVED PLUMBING RECEPTACLE. OCCUPANT HEAT GRAPHICS SHALL HAVE DROP DOWN WINDOWS LINKING REFERENCES TO THE CONTROL DRAWINGS, SEQUENCES OF OPERATION, CONTROL PARAMETERS AND SPECIFIC EQUIPMENT/SYSTEM INFORMATION. 4.2-6 4/1/2021 10. IN NO INSTANCE SHALL OTHER TRADES HANG OR SUPPORT EQUIPMENT, CEILING WIRES, LIGHT FIXTURE HANGERS, ETC., FROM HVAC EQUIPMENT, DUCTWORK, OR PIPING. GAIN SHEETMETAL NOTES11. CUTTING, FRAMING, PATCHING, AND PAINTING OF WALL, CEILING, AND FLOOR OPENINGS SHALL BE BY THE GENERAL CONTRACTOR. THIS INCLUDES OPENINGS THROUGH AREA SEPARATION WALLS.THE CONTROL CONTRACTOR SHALL COORDINATE WITH OWNER ON THE PROPOSED GRAPHICS LAYOUT PRIOR TO SUBMITTALS. 5.CLASSROOM: 1.00 W/SF GYMNASIUM: 1.50 W/SF COMPUTER LAB: 1.00W/SF LOUNGE: 1.00 W/SF OFFICE: 1.00 W/SF CORRIDOR: 1.00 W/SF 16525 100th WaySE Yelm, WA 98597 BASIS OF DESIGN / 2018 WSEC TBL C405.4.2(2) 12. OBTAIN WRITTEN APPROVAL OF STRUCTURAL ENGINEER PRIOR TO INSTALLATION OF PENETRATIONS NOT PREVIOUSLY COORDINATED OR AGREED UPON, I.E. ANCHOR BOLT DEPTHS, ETC. PROVIDE DUCTWORK IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS, METALAND FLEXIBLE, SECOND EDITION, 2005 (SMACNA HVACDCS). 1.4/1/2021 LIGHTING LOADS2-7 CONTROLS CONTRACTOR SHALL REFERENCE MCKINSTRY CONTROL PROVIDER PERFORMANCE STANDARD FOR PROJECT EXPECTATIONS AND SHALL WORK WITH COMMISSIONING AGENT FOR ADHERENCE. 6. 13. REFER TO STRUCTURAL DRAWINGS FOR EQUIPMENT SUPPORTS. REFER TO THE SPECIFICATIONS MATRIX FOR ADDITIONAL SEISMIC INFORMATION. DUCT SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS.2. REFERENCE THE SEQUENCE OF OPERATION CONTAINED WITHIN THESE CONSTRUCTION DOCUMENTS FOR ADDITIONAL CONTROLS REQUIREMENTS. CLASSROOM: 1.00 W/SF GYMNASIUM: 1.00 W/SF COMPUTER LAB: 3.00 W/SF LOUNGE: 2.00W/SF OFFICE: 1.00 W/SF CORRIDOR: 0.25 W/SF 7.CONSULTANTS:PROVIDE A MANUAL VOLUME DAMPER FOR EACH SUPPLY, RETURN, AND EXHAUST OPENING EXCEPT WHERE PROHIBITED BY CODE. INSTALL AS FAR FROM INLET OR OUTLET AS POSSIBLE. 3. BASIS OF DESIGN / 2017 ASHRAE FUNDAMENTALS RECOMMENDED EQUIPMENT HEAT GAINS 14. UNIT WEIGHTS AND LOCATIONS HAVE BEEN COORDINATED TO DETERMINE BUILDING STRUCTURAL ADEQUACY. IF IT IS NECESSARY TO RELOCATE A UNIT, NOTIFY MCKINSTRY ENGINEERING DEPARTMENT FOR RE-COORDINATION. 4/1/2021 EQUIPMENT LOADS2-8 ELECTRICAL COORDINATION NOTES PROVIDE FLEXIBLE CONNECTION AT EACH DUCT CONNECTION TO FANS, AIR HANDLING UNITS, AND SIMILAR EQUIPMENT. DO NOT INSTALL ON EQUIPMENT LOCATED IN FIRE RATED CORRIDOR CEILING. 4. 15. PROVIDE SEISMIC RESTRAINTS AND ANCHORAGE PER SMACNA AND THE INTERNATIONAL BUILDING CODE FOR DUCTWORK, PIPING, AND EQUIPMENT.DUCT SMOKE DETECTORS: LOCATE DUCT SMOKE DETECTORS IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. COORDINATE LOCATION REQUIREMENTS WITH ELECTRICAL. 5.CLASSROOM: 10 CFM/PERSON AND 0.12 CFM/SF GYMNASIUM: 7.5 CFM/PERSON AND 0.06 CFM/SF COMPUTER LAB: 10 CFM/PERSON AND 0.12 CFM/SF LOUNGE: 5 CFM/PERSON AND 0.06 CFM/SF OFFICE: 5 CFM/PERSON AND 0.06 CFM/SF CORRIDOR: 5 CFM/PERSON AND 0.06 CFM/SF WHERE INDICATED ON THE EQUIPMENT SCHEDULES, THE EQUIPMENT COMES COMPLETE FROM THE FACTORY WITH MOTOR CONTROLS AS REQUIRED. ELECTRICIAN SHALL PROVIDE SERVICE AND A DISCONNECT PER CODE, AND POWER WIRING, INCLUDING CONNECTING TO EQUIPMENT. 1. 16. CONCRETE EQUIPMENT CURBS, FLASHINGS, SLEEPERS, PIPING, AND HOUSEKEEPING PADS ARE SHOWN FOR APPROXIMATE LOCATION AND SIZE AND WILL BE PROVIDED BY THE GENERAL CONTRACTOR. WHERE PROVIDED, REFER TO STRUCTURAL INFO FOR ADDITIONAL DETAILS. 2018 IMC, CHP 4, TBL 403.3.1.14/1/2021 VENTILATION RATES2-9 WASHINGTON STATE ENERGY CODE NOTESWHERE INDICATED ON EQUIPMENT SCHEDULES, THE EQUIPMENT REQUIRES FIELD INSTALLED MOTOR STARTERS. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL MOTOR STARTERS (OR CONTRACTORS WHERE INDICATED). PROVIDE SERVICE AND DISCONNECT PER CODE, AND POWER WIRING, INCLUDING CONNECTING TO EQUIPMENT. HOLDING COIL CIRCUIT SHALL BE POWERED BY ELECTRICAL CONTRACTOR (120V UNLESS INDICATED OTHERWISE). STARTERS SHALL BE PROVIDED WITH H-O-A SWITCH, EXCEPT SMOKE CONTROL FANS SHALL NOT HAVE HAND OFF POSITIONS ON THE STARTERS AS NOTED ABOVE. 2. 17. CUTTING AND PATCHING OF ROOF OPENINGS SHALL BE BY THE GENERAL CONTRACTOR. 2018 IMC, CHP 4, TBL 403.3.1.1RESTROOM: 2CFM/SF4/1/2021 EXHAUST RATES2-10 1. PROVIDE COMMISSIONING PLAN IN ACCORDANCE WITH 2018 WASHINGTON STATE ENERGY CODE SECTION C408. 18. VERIFY THAT ALL NECESSARY INFORMATION HAS BEEN PROVIDED PRIOR TO CONNECTION OF EQUIPMENT FURNISHED BY THE OWNER OR OTHERS.BASIS FOR BUILDING ENVELOPE USED IN HVAC LOADS BASIS OF DESIGNPERIMETER ZONE INFILTRATION AIRFLOW = 0.25 CFM PER SQUARE OF WALL AREAINFILTRATION3-1 4/1/2021 2. PROVIDE SYSTEMS TESTING AND BALANCING IN ACCORDANCE WITH 2018 WASHINGTON STATE ENERGY CODE SECTION C408.2.2. 19. PROVIDE ACCESS DOORS IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED MECHANICAL OR PLUMBING EQUIPMENT, VALVES, CONTROLS, AND OTHER DEVICES.ARCH DRAWINGS DATED 06/26/1989, INSULATION VALUE SOURCE (ie: 2018 WSEC APPENDIX A) ISSUE:SLANTED ROOF : U-VALUE=0.040 (3/4” PLYWOOD FRAMED SLANTED ROOF W/ R-30 COMPOSITE INSULATION BOARD) REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS OF THE MECHANICAL EQUIPMENT, UNLESS OTHERWISE NOTED. 3.4/1/2021 ROOF3-2 3. PROVIDE SYSTEMS, EQUIPMENT, AND CONTROLS FUNCTIONAL TESTING IN ACCORANCE WITH 2018 WASHINGTON STATE ENERGY CODE SECTIONS C408.2.3, C408.4.1, C408.5. 20. PROVIDE PIPE, EQUIPMENT, AND VALVE LABELING FOR IDENTIFICATION. MATCH OWNERS EXISTING LABELING SCHEME IF APPLICABLE.PERMIT SUBMITTALARCH DRAWINGS DATED 06/26/1989, INSULATION VALUE SOURCE (ie:2017 ASHRAE FUNDAMENTALS) EXTERIOR WALLS : U-VALUE=0.054 (2”x6" WOOD FRAMING W/ R-19 BATT INSULATION AND BRICK VENEER)DEMOLITION NOTES4/1/2021 WALL3-3 4. PROVIDE SUPPORTING DOCUMENTATION IN ACCORDANCE WITH 2018 WASHINGTON STATE ENERGY CODE C103.6 INCLUDING OPERATION AND MAINTENANCE MANUALS, HVAC CONTROL SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, HVAC CONTROL SEQUENCE OF OPERATIONS, COMMISSIONING REPORT, AND RECORD DRAWINGS. 21. SEAL CONNECTIONS TO AIR SHAFTS AIRTIGHT. PROVIDE AIRTIGHT SEAL AROUND PENETRATIONS IN AIR PLENUMS.ARCH DRAWINGS DATED 06/26/1989, INSULATION VALUE SOURCE (ie:2017 ASHRAE FUNDAMENTALS) VERTICAL GLAZING: U-VALUE=0.588 / 0.515 SUMMER / WINTER, SC=0.760 (DOUBLE PANE, GLAZED, ALUMINUM FRAME, NON-THERMALLY BROKEN, FIXED GLAZING)3-4 4/1/2021 WINDOW DEMOLITION DRAWINGS ARE INCLUDED TO GIVE A COMMON BASIS FOR BIDDING AND MAY NOT SHOW EVERY ITEM TO BE DEMOLISHED. VISIT SITE TO DETERMINE AND COORDINATE THE EXACT EXTENT OF DEMOLITION TO FACEPLATE WORK INDICATED BY THE CONTRACT DOCUMENTS. REWORK EXISTING TERMINATIONS, CONNECTIONS, ETC., TO ACCEPT NEW WORK. PRIOR TO START OF ANY DEMO WORK, VERIFY EXISTING CONDITIONS AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOR RESOLUTION. 1.REGISTRATION:22. LIGHT FIXTURE CLEARANCE: COORDINATE LOCATIONS OF MECHANICAL WORK TO PROVIDE CLEARANCES OVER LIGHTING FIXTURES FOR REMOVAL AND REPLACEMENT.ARCH DRAWINGS DATED 06/26/1989, INSULATION VALUE SOURCE (ie: 2018 WSEC APPENDIX A) 5. PROVIDE OWNER TRAINING FOR NECESSARY SYSTEMS PER 2018 WASHINGTON STATE ENERGY CODE SECTION C103.6.4.ASSUME STEEL EMERGENCY DOORS W/ INSULATION: U-VALUE =0.4554/1/2021 EXTERIOR DOORS3-5 23. PROVIDE MODIFICATIONS TO THE EXISTING SPRINKLER SYSTEM FOR ALL REMODEL AREAS. £ jQh 6. PROVIDE COMMISSIONING COMPLIANCE FORM IN ACCORDANCE WITH 2018 WASHINGTON STATE ENERGY CODE SECTION C408.1.3. ARCH DRAWINGS DATED 06/26/1989, INSULATION VALUE SOURCE (ie:2017 ASHRAE FUNDAMENTALS) 24. PROVIDE FIRE SAFE PENETRATIONS OF FIRE RATED CONSTRUCTION. ASSUME SLAB EDGES ARE UNINSULATED3-6 4/1/2021 SLAB ON GRADE REMOVE EXISTING HVAC EQUIPMENT AS INDICATED, INCLUDING ASSOCIATED PIPING, CONTROL SYSTEMS, AND APPURTENANCES. 2.25. MINIMUM VENTILATION QUANTITIES SHALL COMPLY WITH OR EXCEED THE 2018 INTERNATIONAL MECHANICAL CODE WITH THE WASHINGTON STATE AMENDMENTS. "v o7. MOTORS SHALL COMPLY WITH SECTION C403.2.13 OF THE 2018 WASHINGTON STATE ENERGY CODE. FOR ADDITIONAL DETAILS, SEE EQUIPMENT SCHEDULES CONTAINED WITHIN THIS DRAWING SET. 5«SCOPE OF WORK SUMMARY *O REMOVE EXISTING DUCTWORK AS INDICATED. CAP EXISTING OPENINGS NOT BEING REUSED.3.THE OFFICE AREA IS CURRENTLY SERVED USING THREE INDIVIDUAL AIR TO AIR HEAT PUMP SYSTEMS. THESE SYSTEMS WILL BE REPLACED AND EACH ZONE WILL BE CONNECTED TO A LARGER VRF OUTDOOR UNIT. 4rM26. VARIABLE PITCH SHEAVES TO BE USED FOR SYSTEM BALANCING. REPLACE WITH FIXED PITCH SHEAVES FOR NORMAL OPERATION.PROPOSED DESIGN4/1/2021 OFFICE AREA HVAC5-0 8. SYSTEMS SHALL BE INSULATED AS PRESCRIBED IN SECTIONS C403.2.8, C403.2.9 AND C404.6 OF THE 2018 WASHINGTON STATE ENERGY CODE. FOR ADDITIONAL DETAILS, SEE DUCTWORK AND PIPING SPECIFICATION MATRICES CONTAINED WITHIN THIS DRAWING SET. REMOVE EXISTING PIPING SERVING ITEMS TO BE REMOVED. CAP OR PLUG BRANCH LINES NOT BEING REUSED. 4. INDIVIDUAL HEATING ONLY FAN COIL UNITS WILL BE REPLACED WITH VRF TERMINAL BLOWER COILS TO PROVIDE BOTH HEATING AND COOLING TO THE SPACES. GROUPS OF INDOOR UNITS WILL BE CONNECTED TO AN OUTDOOR UNIT FOR ENERGY SAVINGS AND SIMULTANEOUS HEATING AND COOLING. REMAINDER OF THE SCHOOL PROPOSED DESIGN4/1/20215-1 GIVE OWNER THE OPPORTUNITY TO RETAIN ANY REMOVED ITEMS THAT ARE NOT BEING REUSED. DISPOSE OF OTHER ITEMS LEGALLY OR RELOCATE AS SHOWN ON THE DOCUMENTS. 5.9. HVAC EQUIPMENT SHALL NOT BE SIZED LARGER THAN THE NEXT LARGEST SIZE BASED ON LOAD CALCULATION, WSEC C403.2.2.ISSUES: THE EXISTING FAN COIL UNITS ARE CONNECTED TO A HEATING WATER SYSTEM TO PROVIDE HEATING TO THE SPACES. NEW DUCT MOUNTED HEATING WATER COILS ARE BEING PROVIDED IN THIS SYSTEM TO PROVIDE EMERGENCY HEAT FOR THE HEAT PUMP SYSTEM. CLEAN AND REFURBISH ITEMS INDICATED TO BE REMOVED AND REUSED PRIOR TO REUSE.6.NO DATE DESCRIPTIONHEATING WATER COILS 10. OCCUPIED SPACES ARE MECHANICALLY VENTILATED. SYSTEMS ARE DESIGNED TO PROVIDE MINIMUM OUTSIDE AIR PER MECHANICAL CODE AND SHALL NOT EXCEED 150% CALCULATED VALUE, WSEC 403.2.6 & 403.2.11.4. PROPOSED DESIGN4/1/20215-2 04/29/2021 PERMIT SUBMITTAL THESE TWO AIR HANDLING UNITS ARE BEING REPLACED WITH NEW UNITS WITH HEATING WATER COILS AND HEAT PUMP COILS AND DEDICATED OUTDOOR UNITS. THESE NEW AHU'S WILL NOW PROVIDE BOTH HEATING AND COOLING TO THE GYM. TWO AHU'S SERVING PROPOSED DESIGN4/1/20215-3 11. COMPLETION AND COMMISSIONING FOR MECHANICAL SYSTEMS:GYM THE GAS FIRED UNIT SERVING THE MULTIPURPOSE ROOM WILL HAVE A NEW HEAT PUMP COIL ADDED AND IT WILL BE CONNECTED TO A DEDICATED HEAT PUMP OUTDOOR UNIT. THIS UNIT WILL NOW PROVIDE BOTH HEATING AND COOLING TO THIS SPACE. AHU IN THE MULTIPURPOSE ROOM MECHANICAL SYSTEMS, EQUIPMENT AND CONTROL SHALL BE COMMISSIONED PER WSEC 408.2.A. PROPOSED DESIGN4/1/20215-4 COMMISSIONING PLAN IS REQUIRED TO BE PREPARED BY CERTIFIED COMMISSIONING PROFESSIONAL PRIOR TO FIRST MECHANICAL INSPECTION, PER WSEC 408.1.2. INCLUDE NARRATIVE OF ACTIVITIES, RESPONSIBILITIES OF Cx TEAM, SCHEDULE OF ACTIVITIES AND CONFLICT OF INTEREST PLAN. B. YELM SD - FORT STEVENS ES - RESPONSIBILITY MATRIX CONTROLS START-UPRECEIVE INSTALL WIREFURNISHEQUIPMENT a. PROVIDE SUMMARY OF REPORT OR COMPLIANCE CHECKLIST (SEE C408.1.4.2) AND PROVIDE TO OWNER PRIOR TO FINAL MECHANICAL INSPECTION.FACTORY/CC FACTORYMcKMCEC/CCMcKVRF INDOOR BLOWER COILS EC/CC FACTORY/CC FACTORYMCVRF OUTDOOR UNITS McK MC BALANCE SYSTEMS TO WITHIN TOLERANCES SPECIFIED. FIRST BALANCE TO MINIMIZE THROTTLING LOSSES THEN TO MEET DESIGN FLOW, WSEC 408.2.2. FACTORY C.EC/CC FACTORY/CCMC MCMCVRF ACCESSORIES MCMCVRF REFRIGERANT PIPING MC GCGCCONCRETE PADS FOR OUTDOOR UNITS PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION TO THE OWNER PER WSEC C103.6.D.CCccMcKMC/CC CCMcKCONTROL DAMPERS MINUS ACTUATOR CAMcK MC MCHEATING WATER COILS PROVIDE MAINTENANCE MANUALS FOR ALL MECHANICAL EQUIPMENT, WSEC C103.6.E. CCMC MC EC MCMcKVRF CONTROLS PROVIDE OWNERS OPERATING PERSONNEL TRAINING FOR MECHANICAL EQUIPMENT, WSEC C103.6. F.SR ENGINEER:DLSMCINSULATING PIPING, DUCTWORK, AND EQUIPMENT CC MC MCMC MCHOSE KITS FOR HEATING WATER COILS DRAWN BY:AP/SA MCMCMCNEW DUCTWORK AND TRANSITIONS MC PROVIDE WSEC COMPLIANCE FORMS AND CALCULATIONS, WSEC C103.6.G.QC BY: UHMCNEW CONDENSATE PIPING SYSTEM MC MINIMUM VENTILATION QUANTITIES WILL COMPLY WITH OR EXCEED THE 2018 INTERNATIONAL MECHANICAL CODE. CC H.204875-003CC CC EC (1) JOB NO: ISSUED ON: ACTUATORS FOR NEW DAMPERS CC COMMISSIONING AGENTCOMMISSIONING/TESTING/BALANCING 04/29/2021 ALL SYSTEMS WILL BE INSULATED AS PRESCRIBED IN WSEC C403.2.8.1.I.NOTES: 1. EC UNDER DIRECTION OF CC SHEET TITLE:FOR ADDITIONAL SYSTEM AND EQUIPMENT SEISMIC REQUIREMENTS, REFER TO STRUCTURAL SEISMIC TIE-DOWN INFORMATION AND BACK-UP CALCULATIONS PROVIDED SEPARATELY. J. MECHANICAL GENERAL NOTES, BASIS OF DESIGN, & RESPONSIBILTY MATRIX McK-McKINSTRY MC - MECHANICAL CONTRACTOR CC - CONTROLS CONTRACTOR GC - GENERAL CONTRACTOR SHEET NUMBER: M-002BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:04 AM ■ **Mnstry */7e Of Your Building McKINSTRY Co, LLC HVAC DUCT SPECIFICATION MeNOTESINSULATION (INDOOR, OUTDOOR) INT'L ENERGY CODE C403.2.7 ‘DETERMINED BY CLIMATE ZONE & ASHRAE 90.1 TABLES 6.8.2 & B-1 SEISMIC CRITERIA SEISMIC IMPORTANCE FACTOR IP LINING MATERIALSDUCT MATERIALS SPECIFICATION SPECIFCATION 233113 & 235100 FITTINGS CLEANLINESS DURING CONSTRUCTION SEAL CLASSFLEX CONNECTION / FLEX DUCT DUCT SYSTEM PRESSURE CLASS SPECIFCATION 233113 & 235100 NOTES 1,2,3,4,5IP = 1.0LINING WHERE INDICATED ON THE PLANS SEISMIC SUPPORT PER APPLICABLE CODE/LOCAL JURISDICTION. SEE MECHANICAL SEISMIC SHEET WHEN APPLICABLE. WITHIN CONDITIONED SPACE: R-3.3 (<55F OR >105F)FOLLOW INTERMEDIATE "LEVEL B* SMACNAELBOWS: PURCHASED ADJUSTABLE ELBOWS IN ACCORDANCE WITH SMACNA +1" STANDARDS SMACNA SEAL CLASS A per IEC 2012 C403.2.7 GALVANIZED DUCT; GAUGE AND REINFORCEMENT SHALL BE SMACNA OR BETTER 12-FOOT MAX. LENGTH WITH NO OFFSETS; USE JPL OR EQUAL SMACNA +1/2” OR +1* PRESSUREHVAC SUPPLY ForThIP = 1.5 (LAB PRESSURIZATION) ENGINEER TO CONSIDER LINING WHEN VELOCITY IS 1,400 FPM OR GREATER WHEN NOT IN A CONDITIONED SPACE: R-6 WITH APPROVED VAPOR BARRIERNOTE: MCKINSTRY BUILDS ALL LOW PRESSURE DUCTWORK IN ACCORDANCE WITH +1* SMACNA GUIDELINES TO MAXIMIZE PRODUCTION EFFICIENCY LOW PRESSURE CL RADIUS OF 1.0 DIA ON DUCTS LARGER THAN 24"RECTANGULAR MAY BE S+DRIVE WHEN OUTSIDE: R-8 EXTERIOR INSULATION WITH APPROVED VAPOR/WEATHER BARRIERTERMINALS TO DIFFUSERS FAN COIL UNITS TO DIFFUSERS HEAT PUMPS TO DIFFUSERS SPIN-IN / ATTO BRANCHES OKAYROUND MAY BE SNAPLOCK. IN CONCRETE OR GROUND: R-3.3 (HEATING ONLY)NO PRESSURE TEST REQUIRED PER IEC C403.2.7 SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 NOTES 1,2,3,4,5IP =1.0SEISMIC SUPPORT PER APPLICABLE CODE / LOCAL JURISDICTION. SEE MECHANICAL SEISMIC SHEET WHEN APPLICABLE. LINING WHERE INDICATED ON THE PLANSWITHIN CONDITIONED SPACE: R-7 (LESS THAN 2800 CFM)FOLLOW INTERMEDIATE "LEVEL B" SMACNASMACNA SEAL CLASS LEVEL C OKAY ENERGY CODE DOES NOT APPEAR TO HAVE REQUIREMENT FOR NEG. PRESS. ELBOWS: CENTERLINE RADIUS OF 1.5 DIA OR MITERED 90S WITH VANES OR PURCHASED ADJUSTABLE ELBOWS IN ACCORDANCE WITH SMACNA+1" FLEX AT EQUIP CONNECTIONS TO COMPLY WITH SMACNA APPLICABLE PRESSURE CLASS GALVANIZED DUCT; GAUGE AND REINFORCEMENT SHALL BE SMACNA OR BETTER SMACNA ±2’HVAC OA INTAKE IP = 1.5 (LAB PRESSURIZATION) ENGINEER TO CONSIDER LINING WHEN VELOCITY IS 1,400 FPM OR GREATER R4.4 per inch NOT WITHIN CONDITIONED SPACE: R-6 WITH APPROVED VAPOR BARRIERNO PRESSURE TEST REQUIRED PER IEC C403.2.7LOUVER CAN/PLENUMS UPSTREAM OF MOTORIZED DAMPER RECTANGULAR TO HAVE TDF CONNECTIONS OSA DUCT W/ GREATER THAN 2800 CFM UPSTREAM OF MOTORIZED DAMPER SHALL BE INSULATED TO BUILDING ENVELOPE R-VALUESCL RADIUS OF 1.0 DIA ON DUCTS LARGER THAN 24"ROUND MAY BE SNAPLOCK DIA www.mckinstry.com TAPS: CONICAL OR BOOT-STYLE PROJECT: NOTES 1,2,3,4,5SEISMIC SUPPORT PER APPLICABLE CODE / LOCAL JURISDICTION. SEE MECHANICAL SEISMIC SHEET WHEN APPLICABLE. IP= 1.01" LINING ONLY WHERE INDICATED ON PLANS R4.4 per inch WITHIN CONDITIONED SPACE: R-3.3FOLLOW INTERMEDIATE "LEVEL B" SMACNA3-FOOT MAX. LENGTH WITH NO OFFSETS; USE JPL OR EQUAL; SMACNA SEAL CLASS LEVEL C OKAY ENERGY CODE APPEARS TO NOT HAVE A REQUIREMENT FOR NEG. PRESS. GALVANIZED DUCT; GAUGE AND REINFORCEMENT SHALL BE SMACNA OR BETTER ELBOWS: CENTERLINE RADIUS OF 1.5 DIA OR MITERED 90S WITH VANES OR PURCHASED ADJUSTABLE ELBOWS IN ACCORDANCE WITH SMACNA +1" SMACNA -1/2” OR -1" PRESSUREHVAC RETURN YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE IP = 1.5 (LAB PRESSURIZATION) WHEN NOT IN A CONDITIONED SPACE: R-6 WITH APPROVED VAPOR BARRIERNOTE: MCKINSTRY BUILDS ALL LOW PRESSURE DUCTWORK IN ACCORDANCE WITH +1" SMACNA GUIDELINES TO MAXIMIZE PRODUCTION EFFICIENCY LOW PRESSURE FLEX AT EQUIP CONNECTIONS TO COMPLY WITH SMACNA APPLICABLE PRESSURE CLASS RECTANGULAR TO HAVE S&D CONNECTIONS, ROUND MAY BE SPIRAL CL RADIUS OF 1.0 DIA ON DUCTS LARGER THAN 24“SNAP LOCK PIPE STANDARD NO PRESSURE TEST REQUIRED PER IEC C403.2.7 DIA TAPS: CONICAL OR BOOT-STYLE SPIN-IN / ATTO BRANCHES OKAY NOTES 1,2,3,4,5IP = 1.01" LINING ONLY WHERE INDICATED ON PLANS R4.4 per inch SEISMIC SUPPORT PER APPLICABLE CODE / LOCAL JURISDICTION. SEE MECHANICAL SEISMIC SHEET WHEN APPLICABLE. FOLLOW INTERMEDIATE "LEVEL B" SMACNANOT REQUIRED,SMACNA SEAL CLASS LEVEL C OKAY ENERGY CODE APPEARS TO NOT HAVE A REQUIREMENT FOR NEG. PRESS. ELBOWS: PURCHASED ADJUSTABLE ELBOWS IN ACCORDANCE WITH SMACNA -1“ STANDARDS 12-FOOT MAX. LENGTH WITH NO OFFSETS; USE JPL OR EQUAL; GALVANIZED DUCT; SEE SUBMITTAL FOR GAUGE AND REINFORCEMENT. SMACNA -1/2" OR -1" PRESSUREHVAC EXHAUST IP = 1.5 (LAB PRESSURIZATION, CHEMICAL STORAGE, BATTERY, & REFRIGERATION EXHAUST) LOW PRESSURE NOTE: MCKINSTRY BUILDS ALL LOW PRESSURE DUCTWORK IN ACCORDANCE WITH +1" SMACNA GUIDELINES TO MAXIMIZE PRODUCTION EFFICIENCY FLEX AT EQUIP CONNECTIONS TO COMPLY WITH SMACNA APPLICABLE PRESSURE CLASS RECTANGULAR MAY BE S+D, ROUND MAY BE SNAPLOCK.CL RADIUS OF 1.0 DIA ON DUCTS LARGER THAN 24” SPIN-IN / ATTO BRANCHES OKAY NO PRESSURE TEST REQUIRED PER IEC C403.2.7 NOTES 1,2,3N/A N/AHORIZONTAL MOUNT, VERTICAL AIRFLOW - GREENHECK BR-10 OR APPROVED VERTICAL MOUNT, HORIZONTAL AIRFLOW - GREENHECK BR-30 OR APPROVED PER APPLICABLE DUCT SYSTEM N/APER APPLICABLE DUCT SYSTEM N/AN/A N/ABACKDRAFT DAMPERS LOW PRESSURE N/A 16525 100th Way SE Yelm, WA 98597 NOTES: 1. ALL DUCTWORK TO BE FABRICATED IN ACCORDANCE WITH McKINSTRY DUCT CONSTRUCTION STANDARDS / SUBMITTALS WHICH MEET OR EXCEED SMACNA GUIDELINES 2. ALL DIMENSIONS SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS 3. THE MECHANICAL ENGINEER RESERVES THE RIGHT TO AUTHORIZE DEVIATIONS TO THESE STANDARDS TO ACCOMMODATE UNIQUE SITUATIONS AS APPLICABLE 4. USE DOUBLE WIDTH VANES UNLESS OTHERWISE NOTED ON THE DRAWINGS 5. USE OF DUCTWORK FOR TEMPORARY HEATING / CONDITIONING DURING CONSTRUCTION NOT ALLOWED WITHOUT SPECIAL APPROVAL BY THE ENGINEER 6. REFERENCE DUCT CONSTRUCTION AND EXPOSED CLASSIFICATIONS MATRIX 7. LOW-VOLTAGE REMOTE DAMPERS STANDARD CONSULTANTS: HVAC PIPING SPECIFICATION PRESSURE TEST PROCEDURE CODETEST PRESSURE DURATIONMEDIAMANUFACTURER, PRODUCT OR EQUALMAXIMUM PRESSURE & TEMPSERVICE DESCRIPTIONCATEGORYID CONDENSATE DRAIN FROM EQUIPMENT COIL DRAIN PANSCONDENSATE DRAINCNDS HANPLY (HANSEN SUPPLY), MARKING SERVICES INC. MS-970 (INDOOR); MS-995 (OUTDOOR); DURALABELWHITE LETTERING ON GREEN BACKGROUND - ANSI/ASME A 13.1 - 2007PIPE IDENTIFICATION MARKER ISSUE:ATMOSHPHERICDESIGN OPERATING PRESS & TEMP MIN 15 MINUTES; VISUAL CHECKS FOR LEAKS PLUG OUTLET AND FILL SYSTEM FROM LOWEST TO HIGHEST POINT OF TEST SECTION PERMIT SUBMITTAL2018 UPC, SECTION 723.0 SIZES THRU 2'WATERVARIES ACCORDING TO TEMPERATURE (MAX 140F)PVC SCH 80PIPE MATERIAL SOLVENT CEMENT AND WELDING RODJOINTS VARIES ACCORDING TO TEMPERATURE (MAX 140F)PVC SCH 80FITTINGS VARIES ACCORDING TO TEMPERATURE (MAX 140F)PVC SCH 80FLANGES, UNIONS, & COUPLINGS REGISTRATION:GARLOCK STYLE BLUE-GAURD 3000SPIRAL WOUND GASKETFLANGED GASKETS - RAISED FACED HVAC HEATING WATERHEATING WATER SUPPLY AND RETURNHWS&R wSmHANPLY (HANSEN SUPPLY), MARKING SERVICES INC. MS-970 (INDOOR); MS-995 (OUTDOOR); DURALABELWHITE LETTERING ON GREEN BACKGROUND - ANSI/ASME A 13.1 - 2007PIPE IDENTIFICATION MARKER UP T0100 PSI; 140 F TO 200 FRATED OPERATING PRESS & TEMP 160 F TO 180F. SET PRV T015 PSIDESIGN OPERATING PRESS & TEMP T OcoZSEE PLUMBING SCHEDULE175 PSI, 140FDOUBLE CHECK-VALVE - CONFIRM ACCEPTABLE BY LOCAL JURISDICTIONBACKFLOW PREVENTION DEVICE 7?SEE PLUMBING SCHEDULE176 PSI, 140F 2RPBABACKFLOW PREVENTION DEVICE CMS22PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER, BOILER, STORAGE TANK.P&T RELIEF VALVE SEE SPECIALITES BELOWSPECIALTIES iMlLSIZES THRU 2' COPPER TUBE TYPE L ASTM B88______________________________ PRESS-FIT MECHANICAL COMPRESSION, THREADED AT SPECIALTIES AS APPLICABLE PIPE MATERIAL VIEGA PROPRESS; EPDM SEAL (BLACK), TYCO-GRINNELL G-PRESS EPDM SEAL (BLACK); APOLLO PRESS, EPDM SEAL (BLACK)300 PSIG @ 250F (Viega)JOINTS ( ISSUES:SWT, THREADED AT SPECIALTIES AS APPLICABLEJOINTS NO DESCRIPTIONDATEVIEGA PROPRESS; EPDM SEAL (BLACK), TYCO-GRINNELL G-PRESS EPDM SEAL (BLACK); APOLLO PRESS, EPDM SEAL (BUCK)300 PSIG @250F (Viega)PRESS-FIT MECHANICAL COMPRESSIONFITTINGS PERMIT SUBMITTAL04/29/2021WROT COPPER/BRONZE SWT JOINTCOUPLINGS 1.5 TIMES MAX OPERATING PRESSURE, BUT NOT LESS THAN 100 PSI 2018IMC, SECTION 120815 MINUTESWATERSWT OR THREADED; (WROT OR CAST COPPER) CLASS 150FLANGES GARLOCK STYLE BLUE-GAURD 3000TO1200FSPIRAL WOUND GASKET CARBON STEEL BOLTS AND STUDS - GRADE A - FOR FLANGED JOINTS IN PIPING SYSTEMS; NUTS: A536A HEX; WASHERS: F884 STANDARD BRONZE BODY - 20 MESH SS SCREEN - CLASS 125 - FPT FLANGED GASKETS - RAISED FACED FLANGED BOLTS (PLATED) KECKLEY F-150, TITAN YS 55, APOLLO YBS 59 SERIES;200 PSI@150FWQGWYE STRAINERS KECKLEY E-150, TITAN YS 56200 PSI @ 150FWQGCAST BRONZE BODY - 20 MESH SS SCREEN - CLASS 125 - SWTWYE STRAINERS ENGINEERED FLEXIBLE PRODUCTS (EFP)COMPENSATION FITTING AND/OR PIPING LOOPEXPANSION JOINTS MILWAUKEE BA-400, APOLLO 77CA-100;600 PSI @ 250 F2-PC BALL -CAST BRONZE BODY - FPT - 600 PSI WOGVALVES-ISOLATION 600 PSI @ 250 F MILWAUKEE BA-450, APOLLO 77C-2002-PC BALL -CAST BRONZE BODY - SWT - 600 PSI WOGVALVES - ISOLATION MILWAUKEE-510 / -1510-T , APOLLO 164T300 PSIHORIZONTAL SWING, BRONZE BODY - FLANGED -CLASS 150VALVES-CHECK MILWAUKEE 548BGLOBE SILENT CHECK CARBON STEEL CLASS 150 SWP - FLANGEDVALVES-CHECK GRISWOLD QUICK-SET; T/A - VICTAULIC TA SERIES 786/787 (STAD) TYCO-GRINNELL CB800 SERIES BELL & GOSSETT CIRCUIT SETTER PLUS MANUAL BALANCE ZONE VALVE WITH TEST PORTSVALVES - MANUAL BALANCE 2" & BELOW GRISWOLD ISOLATOR; T/A - VICTUALIC SERIES 76; BELL & GOSSETT CIRCUIT SENTRY [ALT WITH FLO-SETTER]PRESSURE INDEPENDENT AUTO-FLOW CONTROLVALVES - AUTO BALANCE - PRESSURE INDEPENDENT__ VALVES - BALANCE - DIFFERENTIAL PRESSURE CONTROLLERS (PART A) VALVES - BALANCE - DIFFERENTIAL PRESSURE CONTROLLERS (PART B) TOUR ANDERSON - VICTUALIC SERIES 76 (SPECIFY CONNECTION)PRESSURE INDEPENDENT DIFFERENTIAL PRESSURE CONTROLLER FOR HYDRONIC ZONES - STAP TOUR ANDERSON - VICTAULIC - SERIES 793 (THREADED, 794 (FLANGED)CIRCUIT BALANCING VALVE WITH TEST PORTS AND CAPILARY TUBE - STAD TOUR ANDERSON - BPV; TACO 3196-1 (3/4")BYPASS RELIEF VALVE TO MAINTAIN MINIUM FLOW THROUGH STAP 3/4" 2-PC BALL - HOSE END WITH CAP & CHAIN - T HANDLE - 600 PSI WOG/CWP - SWT VALVES - BALANCE - DIFFERENTIAL PRESSURE CONTROLLERS (PART C) MILWAUKEE BA-100H/150H; APOLLO 70-200-HC600 PSI @ 250 FVALVES - DRAINING REFRIGERANT PIPING FOR HEATING AND COOLINGREFRIGERANT LIQUID / REFRIGERANT SUCTIONRL/RS SR ENGINEER: DLS HANPLY (HANSEN SUPPLY), MARKING SERVICES INC. MS-970 (INDOOR); MS-995 (OUTDOOR); DURALABELBLACK LETTERING ON ORANGE BACKGROUND - ANSI/ASME A 13.1 - 2007PIPE IDENTIFICATION MARKER DRAWN BY: AP/SA PER ASTM B31.5 REFRIGERATION PIPING AND HEAT TRANSFER COMPONENTSRATED OPERATING PRESS & TEMP LHQC BY: 204875-003JOB NO: 1.5 TIMES PRESSURE RELIEF VALVE SETTING 2018 IMC, SECTION 1108 INERT GAS-NITROGEN OR CARBON DIOXIDE SIZES THRU 1 1/8"1 HOUR 04/29/2021ISSUED ON:PDM - GELCOPPER PRE-INSULATED COPPER ROLL (1/4”-1-1/8")PRE-INSULATED COPPER TUBING ON ROLLS, ASTM-B280 - SEALED AND CAPPED AT ENDSPIPE MATERIAL POLYETHYLENE CLOSED CELL FOAM - ASTM C 1427 COMPLIANT - UL94 & UL 723 (FLAME SPREAP<25 & SMOKE DEVELOPMENT <50)INSULATION SILVER BRAZED AND NITROGEN PURGE PER ASTM B828,JOINTS SHEET TITLE:WROT COPPER/BRONZE SWT JOINT PER ASTM B16.22;FITTINGS MECHANICAL SPECIFICATIONS PROJECT SPECIFIC REQUIREMENTS - SEE SPECIFICATION 232300" REFRIGERANT PIPING"MISC.SPECIALTIES SHEET NUMBER: M-003BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:05 AM i)instry Wife Of Your Building McKINSTRY Co, LLC MECHANICAL PIPE INSULATION SCHEDULE - WASHINGTON MeENERGY CODE: 2018 INTERNATIONAL ENERGY CODE WITH WASHINGTON AMENDMENTS TABLE C403.2 SPECIFICATION: 230700 HVAC INSULATION MEAN RATING TEMPERATURE INSULATION MATERIAL THERMAL COND. PIPING SYSTEM TEMP RANGE (Deg F)NOTESOVER 8’1" TO <1-1/2’ 1 1/2" TO 4'4" - 8"<1 SEE REFRIGERATION PIPING INSULATION MATRIXREFRIGERANT PIPING ForTh1,2,4,100.5 0.50.5 0.5 0.50,23-0.27 MPICOIL CONDENSATE DRAINS ALL 75 MPI: MINERAL WOOL PREFORMED PIPE INSULATION GENERAL NOTES: 1. INSTALLATION OF INSULATION SHALL BE PER THE MIDWEST INSULATION CONTRACTOR’S ASSOCIATION (MICA) STANDARDS MANUAL AND MANUFACTURER'S REQUIREMENT. THE INSULATION CONTRACTOR SHALL PROVIDE INSTALLATION DETAILS IF REQUESTED BY THE ENGINEER.SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 KEY NOTES: 1. FOR PIPING CLAMPED TO UNISTRUT SUPPORTS, UTILIZE RIGID INSERTS WITH SHEETMETAL SHIELDS CONTINUOUS THROUGH THE HANGER; UTILIZE STYRENE INSERTS 2, FOR PIPING SUPPORTED FROM CLEVIS HANGERS, IF RIGID INSERTS ARE NOT UTILIZED THE INSULATION SHALL FULLY ENCLOSE THE HANGER AND BE SEALED AT THE TOP AROUND THE SUPPORT ROD; IF RIGID INSERTS ARE UTILIZED THE INSULATION SHALL BE CONTINUOUS THROUGH THE HANGER; INSERT MATERIAL TO BE STYRENE INSERTS 3, JACKETING: ALUMINUM ROLLED JACKETING (ARJ) APPLIED TO EXTERIOR PIPING INSULATION EXPOSED TO WEATHER (I.E. ROOFTOP PIPING). SEE INSULATION SPEC FOR ALTERNATE JACKETING AND LOCATIONS. 4. ASTM E 84 AND UL 723 TESTED AND LISTED TO FLAME SPREAD INDEX OF 25 AND SMOKE DEVELOPED INDEX OF NOT EXCEEDING 50 www.mckinstry.com REFRIGERANT PIPE INSULATION SCHEDULE - WASHINGTON PROJECT; ENERGY CODE: 2018 INTERNATIONAL ENERGY CODE WITH WASHINGTON AMENDMENTS TABLE C403.2 YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE SPECIFICATION: 230700 HVAC INSULATION ACR TUBE SIZESINSULATION MATERIAL MEAN RATING TEMPERATURE TEMP RANGE THERMAL COND. PIPING SYSTEM NOTES1 5/8” TO 4-1/8” OD1-1/8” TO <1-5/8” OD<1-1/8“ OD(Deg F) VARIABLE REFRIGERANT FLOW - FROM OUTDOOR UNIT TO BRANCH SELECTOR SWITCHES (HARD PIPE ACR) 1,2, 3,4, 5,72.01.5 1.50.25-0.29 125 E/PFREFRIGERANT-HOT GAS 141-200 1,2, 3,4, 5, 71.0 1.00.5E/PF<40 0.20-0.26REFRIGERANT-SUCTION 75 1,2, 3,4, 5, 71.0 1.51.0E/PF105-140 0.21-0.28 100REFRIGERANT-LIQUID VARIABLE REFRIGERANT FLOW - FROM BRANCH SELECTOR SWITCHES TO FCU’s/CASSETTES (LINE SETS) 1,2,3,4, 5,6N/AN/AE/PF 1.50,25-0.29 125REFRIGERANT SUCTION (AC MODE) / HOT GAS (HEAT MODE)<40/141-200 1,2, 3,4, 5,6N/A1.0 N/AE/PF0.21-0.28 100105-140REFRIGERANT-LIQUID E: ELASTORMERIC CLOSED CELL INSULATION (WITH UV RETARDANT) PF: POLYURETHANE FOAM (UN RESISTANT) 16525 100th WaySE Yelm, WA 98597 GENERAL NOTES: 1. ACR TUBE AND UNESET SIZES BELOW 1*: 1/4", 3/8", 1/2", 5/8", 3/4", 7/8", 2. RECOMMENDED LINE-SET SIZE LIMIT TO 3/4* OD FOR EASE OF HANDLING. LARGER OD LINE-SETS ARE AVAILABLE BUT REQUIRE ADDITIONAL FIELD BURDEN DURING INSTALLATION. 3. INSTALLATION OF INSULATION SHALL BE PER THE MIDWEST INSULATION CONTRACTOR'S ASSOCIATION (MICA) STANDARDS MANUAL AND MANUFACTURER'S REQUIREMENT. THE INSULATION CONTRACTOR SHALL PROVIDE INSTALLATION DETAILS IF REQUESTED BY THE ENGINEER. CONSULTANTS: KEYNOTES: 1. PIPING SHOULD NOT BE CLAMPED DIRECTLY TO UNISTRUT SUPPORTS, UTILIZE SHEETMETAL SHIELDS CONTINUOUS THROUGH THE HANGER. INSULATION SHALL RUN CONTINUOUSLY THRU THE PIPE SUPPORT SHIELD. 2. FOR PIPING SUPPORTED FROM CLEVIS HANGERS, WHERE RIGID INSERTS ARE NOT UTILIZED THE INSULATION SHALL FULLY ENCLOSE THE HANGER AND BE SEALED AT THE TOP AROUND THE SUPPORT ROD; IF RIGID 3. EXTERIOR INSULATION SHALL BE COATED WITH TWO COATS OF WB FINISH FOR UV PROTECTION, OR PROVIDE WITH UV RATED COVERING. IN AREAS SUBJECT TO DAMAGE, PROVIDE JACKETING: ALUMINUM ROLLED JACKETING (ARJ) APPLIED TO EXTERIOR PIPING INSULATION OR FACTORY APPLIED ALUMINUM AND EXTERNAL PROTECTIVE LAYER. 4. FOR PIPING SMALLER THAN 11/2 INCH AND LOCATED IN PARTITIONS WITHIN A CONDITIONED SPACE, MAY REDUCE THICKNESSES BY 11NCH BUT TOTAL THICKNESS TO NOT BELOW 1" AS ALLOWED BY ENERGY CODE. 5. ASTM E 84 AND UL 723 TESTED AND LISTED TO FLAME SPREAD INDEX OF 25 AND SMOKE DEVELOPED INDEX OF NOT EXCEEDING 50 6. CONTRACTOR TO PROVIDE PRE-INSULATED SOFT COPPER LINE SETS WITH INSULATION THICKNESS VALUES AS INDICATED. 7. PIPING INSTALLED BELOW GROUND SHALL BE CONTAINED IN A PLASTIC DUCT COVER OR PIPING SHALL HAVE A FACTORY APPLIED ALUMINUM AND EXTERNAL PROTECTIVE LAYER TO PROTECT THE PIPE AND INSULATION. ISSUE: PERMIT SUBMITTAL REGISTRATION: w&m/KF Jk/dm ooo2 7s &&f^4/0m252 r ISSUES: NO DATE DESCRIPTION SR ENGINEER:DLS DRAWN BY:AP/SA QC BY: LH 204875-003JOB NO: ISSUED ON: 04/29/2021 SHEET TITLE: MECHANICAL SPECIFICATIONS SHEET NUMBER: M-004BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:05 AM ' ™Mnstry jWife Of Your Building McKINSTRY Co, LLC INDOOR BLOWER COIL (TYP) ZONE SENSOR (TYP)MeODU-02 REYQ120XATJ ODU-01 REYQ240XATJ £II • • BRC1E73BRC1E73BC-03 L FXSQ36TAVJU BCU-02 BSF4Q54TVJ BC-23 FXMQ54PBVJU BCU-01 BSF8Q54TVJ A REYQ120XATJA REYQ120XATJA INININ ForThHiINm• •BTOUTB*c*0 dt£♦♦ E • FOUTBGT H •REYQ120XATJA SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 • •REFRIGERANT BRANCH CONTROLLER (TYP) BRC1E73BRC1E73BC-04 L FXSQ36TAVJU BC-25 FXSQ18TAVJU OUTDOOR UNIT (TYP) www.mckinstry.com PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE • •BRC1E73BRC1E73BC-05 FXSQ36TAVJU BC-24 FXSQ48TAVJU Iml m BRC1E73BC-01 L FXMQ72MVJU 16525 100th WaySE Yelm, WA 98597 ♦ BRC1E73BC-02 FXSQ48TAVJU CONSULTANTS: • • ODU-04 REYQ216XATJ ODU-03 REYQ144XATJ£t£• •• •* •BRC1E73BRC1E73• •BC-10 FXMQ72MVJU BCU-04 BSF8Q54TVJ ABC-06 FXSQ36TAVJU BCU-03 BSF6Q54TVJREYQ144XATJA REYQ12QXATJA ININININAITATT♦BTmCTC ISSUE:DTOUT EE• •♦ OUTFB GT PERMIT SUBMITTALREYQ96XATJA ±l±L 00 0 BRC1E73BRC1E73BC-11 L FXSQ24TAVJU BC-07 FXSQ36TAVJU REGISTRATION: -TJTl 2 'p. 2lBRC1E73BRC1E73S/STEBC-12 FXSQ48TAVJU BC-08 FXSQ36TAVJU oQn •H ^2^ ISSUES: DESCRIPTIONNODATE PERMIT SUBMITTAL04/29/2021 • • BRC1E73• •BRC1E73 BC-13 ■- FXSQ36TAVJU BC-09 L FXSQ36TAVJU BRC1E73LEGEND:BC-14 L FXSQ36TAVJU------POWER WIRING ------CONTROL WIRING THESE DRAWINGS ARE PROVIDED BY THE EQUIPMENT MANUFACTURER AND PROVIDED TO THE CONTRACTORS FOR REFERENCE ONLY. FINAL CONNECTIONS SHALL BE COORDINATED WITH EQUIPMENT REQUIREMENTS.ODU-01 TO ODU-04 CONTROLS WIRING DIAGRAM1 SR ENGINEER:DLS SCALE: NTSM-020 AP/SADRAWN BY: QC BY: LH JOB NO: 204875-003 04/29/2021ISSUED ON: SHEET TITLE: CONTROLS DIAGRAMS SHEET NUMBER: M-020BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSE$-MCK-ENGR-MECH.rvt4/28/2021 11:57:06 AM ' ^tinstry fn.ifo Of Your Building McKiNSTRY Co, LLC INDOOR BLOWER COIL (TYP) CONTROL SEQUENCES FORT STEVENS ELEMENTARY SCHOOL ZONE SENSOR (TYP)MeODU-06 REYQ168XATJ, O DU-05 REYQ144XATJ VARIABLE REFRIGERANT FLOW /VRF) SYSTEM OVERVIEW THE VRF SYSTEM EQUIPMENT AND CONTROLS FOR THIS EQUIPMENT WILL BE PROVIDED BY DAIKIN, THE DAIKIN CONTROLS WILL INTERFACE TO THE NEW BAS SYSTEM VIA BACNET FROM A RIPTIDE HUB PROVIDED AS PART OF THE DAIKIN CONTROL PACKAGE. THE DAIKIN CONTROLS WILL CONTROL THE HEATING AND COOLING FUNCTIONS OF THE SPACES WHILE MANAGING THE MOST EFFICIENT OPERATION OF THE ENTIRE DAIKIN SYSTEM. £T • •# *• I • BRC1E73BRC1E73• I •• •BC-19 FXSQ48TAVJU BCU-06 BSF6G54TVJ BCU-05 BSF4Q54TVJ BC-18 FXSQ36TAVJU REYQ168XATJAREYQ144XATJA ININININ ForThAfTa*}m BTOUT cCi• • OUTD~i• •EOUTDOOR UNIT (TYP)F BAS SYSTEM OVERVIEW THE NEW BAS SYSTEM WILL PULL BACNET AVAILABLE CONTROL INFORMATION FROM THE DAIKIN SYSTEM, AND USE THIS DATA ON GRAPHIC SCREENS SET UP BY THE BAS CONTRACTOR FOR EACH SYSTEM AND ZONE. THE NEW BAS SYSTEM SHALL DUPLICATE THE EXISTING CONTROL FUNCTIONS NOT ASSOCIATED WITH THE REPLACED AIR SOURCE HEAT PUMPS. REFRIGERANT BRANCH CONTROLLER (TYP) SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 BRC1E73BRC1E73BC-20 FXSQ36TAVJU BC-15 L’ FXSQ24TAVJU ZONE BLOWER COIL UNITS EACH NEW VRF BLOWER COIL UNIT WILL HAVE A WALL MOUNTED BUTTON SENSOR ONLY WITH NO OCCUPANT CONTROL. THE CONTROL SET POINTS AND SCHEDULE WILL BE SET FROM THE MAIN CONTROL SYSTEM. EACH BLOWER COIL HAS A RETURN AIR DAMPER AND AN OUTSIDE AIR INTAKE DAMPER. THESE DAMPERS WILL BE CONTROLLED BY THE BAS SYSTEM. DURING UNOCCUPIED TIMES THE OUTSIDE AIR INTAKE DAMPER WILL REMAIN CLOSED AND THE RETURN AIR DAMPER WILL REMAIN OPEN. DURING OCCUPIED TIMES THE OUTDOOR TWO DAMPERS WILL MODULATE TO SUPPLY A PRESET AMOUNT OF OUTSIDE AIR TO THE BLOWER COIL. UPON A CALL FOR COOLING, AND WHEN OUTDOOR AIR TEMPERATURES AND HUMIDITY LEVELS ALLOW FOR ECONOMIZER COOLING, THE DAMPERS WILL MODULATE TO MAINTAIN A DISCHARGE AIR TEMPERATURE OF 60 DEGREES(ADJ). DURING ECONOMIZER CYCLE THE DX COOLING SYSTEM WILL BE OFF. EACH BLOWER COIL HAS A NEW DUCT MOUNTED HOT WATER HEATING COIL ASSOCIATED WITH IT. THESE COILS ARE TO BE UTILIZED WHEN THE DISCHARGE TEMPERATURE FROM THE VRF BLOWER COIL DROPS BELOW 90 DEGREES (ADJ) DURING A CALL FOR HEAT. ONCE THE SPACE TEMPERATURE SET POINT HAS BEEN SATISFIED THE HEATING WATER COIL WILL CYCLE OFF. www.mckinstry.com PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE BRC1E73BRC1E73BC-21 FXSQ36TAVJU BC-16 FXSQ48TAVJU as c• • BRC1E73• •BRC1E73 BC-22 L FXSQ36TAVJU BC-17 FXSQ24TAVJU BOILER SYSTEM CONTROL THE NEW BAS SYSTEM SHALL INTERFACE THE EXISTING BOILER SYSTEM AS IT IS CURRENTLY. WITH THE ADDITION OF THE HEAT PUMP SERVING EACH ZONE THE HEATING WATER SYSTEM WILL NOT BE UTILIZED AS HEAVILY FOR HEATING AS IT HAS IN THE PAST. THE NEW HEATING WATER COILS ARE SIZED USING 140 DEGREE ENTERING WATER TEMPERATURE TO ASSURE THAT THE BOILERS WILL BE OPERATING IN THE CONDENSING PORTION OF THEIR OPERATING RANGE MORE OFTEN IF NOT ALL THE TIME. THE HEATING WATER TEMPERATURE RESET SCHEDULE SHALL BE AS FOLLOWS; AT 20 DEGREES OUTDOOR AIR TEMPERATURE(ADJ) AND BELOW, THE HEATING WATER TEMPERATURE WILL BE 140 DEGREES - AT 50 DEGREE OUTDOOR AIR TEMPERATURE (ADJ) AND ABOVE THE HEATING WATER TEMPERATURE SHALL BE SET AT 110 DEGREES. AHU INTEGRATION KIT (TYP) ODU-09 RXYQ192XATJA, O DU-08 RXYQ168XATJ 16525 100th WaySE Yelm, WA 98597 • •BRC1E73BRC1E73* *A AHU 21EKEQ 0»AHU 11EKEQ 0*RXYQ168XATJA RXYQ120XATJA ININ •I* CONSULTANTS: * • B RXYQ72XATJAAHU COIL EXPANSION KIT (TYP)•I* THE EXISTING THREE-WAY VALVES SERVING THE TERMINAL UNITS WILL BE REUSED. PROVIDE A NEW THREE-WAY CONTROL VALVE WHICH IS PROPERLY SIZED FOR THE NEW AIR HANDLING UNITS SERVING THE GYMNASIUM. AHU 2 box 1 EKEXV400-US AHU 1 box 1 EKEXV400-US NEW GYMNASIUM AIR HANDLING UNITS - AHU-1 AND 2 THE NEW AIR HANDLING UNITS FOR THE GYMNASIUM WILL HAVE A HEAT PUMP COIL CONNECTED TO A DAIKIN OUTDOOR UNIT. EACH WILL BE PROVIDED WITH AN EXPANSION VALVE KIT AND AN AIR HANDLING INTEGRATION KIT. THERE IS ALSO A HEATING WATER COIL IN THESE UNITS. THESE UNITS ARE TO OPERATE AS A SINGLE ZONE VAV AIR HANDLING UNIT WITH A VFD ON THE SUPPLY FAN. THE HEAT PUMP COIL IS THE PRIMARY SOURCE OF HEAT DURING HEATING SEASON. THE HOT WATER COIL WILL BE THE BACK-UP OR AUXILIARY SOURCE OF HEAT. THE HEATING WATER COIL WILL BE UTILIZED, AND THE THREE-WAY HEATING WATER VALVE WILL MODULATE TO MAINTAIN SET POINT WHEN THE HEAT PUMP GOES INTO DEFROST OR THE HEAT PUMP CAN’T MAINTAIN SPACE TEMPERATURE. THESE UNITS SHALL FUNCTION AS A SINGLE ZONE VAV SYSTEM AND THE DAIKIN ODU’S WILL BE STEPPED CAPACITY BASED UPON LOAD. ISSUE:ODU-10 RXYQ120XATJ£PERMIT SUBMITTAL• • BRC1E73• • CC-011EKEQ 0*-RXYQ120XATJA IN • •• • REGISTRATION: EXISTING GAS FIRED UNIT FOR MULTI-PURPOSE SPACE A HEAT PUMP COIL IS BEING ADDED TO THE EXISTING GAS FIRED UNIT SERVING THE MULTI-PURPOSE SPACE. THE HEAT PUMP WILL BECOME THE FIRST STAGE OF HEAT AND THE GAS HEAT WILL BECOME THE BACK UP OR AUXILIARY HEAT SOURCE. THE GAS FIRED SECTION WILL BE UTILIZED TO MAINTAIN SET POINT WHEN THE HEAT PUMP GOES INTO DEFROST OR THE HEAT PUMP CAN’T MAINTAIN SPACE TEMPERATURE. OooMrz CC-01 box 1 EKEXV250-US 7$ O as MORNING WARM-UP WHEN A NIGHT SET BACK STRATEGY IS USED DURING HEATING SEASON, THE HEATING WATER COILS WILL BE UTILIZED BY EACH ZONE AND THE TWO GYM AIR HANDLING UNITS TO BRING THE SPACES UP TO SET POINT. DURING MORNING WARM-UP, THE HE, PUMPS WILL REMAIN OFF BUT THE FAN IN THE INDOOR BLOWER COILS WILL BE COMMANDED ON AND THE HEATING WATER COIL WILL BE USED TO HEAT THE SPACES. ONCE THE SPACES ARE AT SET POINT THEN THE HEAT PUMP WILL BE ENABLED AND USED TO MAINTAIN ZONE SET POINT. ODU-12 REYQ144XATJA ODU-11 REYQ120XATJ 7£££ISSUES:• • BRC1E73 DESCRIPTIONNODATEBRC1E73• •BC-29 FXSQ36TAVJU BCU-12 BSF4Q54TVJ BC-26 FXSQ36TAVJU BCU-11 BSF4Q54TVJ REYQ144XATJA 04/29/2021 PERMIT SUBMITTALREYQ120XATJA IN.INININ at;aaATT BT»OUTOUTC0 MISCELLANEOUS BAS CONTROL THE NEW BAS SYSTEM SHALL ALSO PICK UP CONTROL OF ALL THE EXITING DEVICES CURRENTLY CONTROLLED BY THE EXISTING BAS SYSTEM. THESE DEVICES TO INCLUDE BUT NOT LIMITED TO: • EXHAUST FANS • DOMESTIC WATER CIRCULATING PUMPS • PARKING LOT LIGHTING CONTROL • BUILDING MOUNTED LIGHTING CONTROL • SPACE TEMPERATURE MONITORING IN THE PORTABLE CLASSROOMS JZ• •• •BRC1E73BRC1E73«BC-30 FXSQ36TAVJU BC-27 L~ FXSQ36TAVJU JZ• •• •BRC1E73• •BRC1E73• •BC-31 FXSQ36TAVJU SR ENGINEER:BC-28 •- FXSQ36TAVJU DLS DRAWN BY:AP/SAaa QC BY:LH JOB NO:204875-003 ISSUED ON: 04/29/2021 SHEET TITLE: BRC1E73 CONTROLS DIAGRAMS & SEQUENCE OF OPERATIONS BC-32 FXSQ36TAVJU (*) for MORE DETAILS ABOUT WIRING TOWARDS AHU, PLEASE REFER TO THE INSTALLATION MANUAL NOTE: AHU INTEGRATION EXPANSION VALVE CONTROL BOXES AND VALVE KITS ARE NOT SHOWN ON PLANS NOTE: ODU-07 NOT USED LEGEND: ------POWER WIRING ------CONTROL WIRINGODU-05 TO ODU-10 CONTROLS WIRING DIAGRAM & CONTROL SEQUENCES THESE DRAWINGS ARE PROVIDED BY THE EQUIPMENT MANUFACTURER AND PROVIDED TO THE CONTRACTORS FOR REFERENCE ONLY. FINAL CONNECTIONS SHALL BE COORDINATED WITH EQUIPMENT REQUIREMENTS.1 SHEET NUMBER: SCALE: NTSM-021 M-021BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:06 AM \instry !Kite Of Your Building McKINSTRY Co, LLC BC-16 BC-22BC-21 BC-18 BC-20BC-17 BC-15BC-19 1" (15 TONS)1" (9 TONS) BC-31 BC-32BC-30BC-26 BC-27 BC-28 BC-29BC-6 BC-14 BC-11 BC-10 BC-13BC-4 BC-8 BC-12BC-25 BC-9 BC-7 BC-5 BC-3AHU-01 AHU-02 BC-24 BC-1 BC-23BC-2 1" (24 TONS) y® T T TT T3/4,r TT T J(TYP UNO)i_t_L 1" (16 TONS) f (40 TONS) 3/4” (12 TONS) 1" (21 TONS) 3/4" (9 TONS)3/4” (9 TONS) 1" (21 TONS) 3/4" (12 TONS)3/4" (16 TONS) iti SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 DRAIN TO MOP SINK IN OUST. N08 DRAIN TO MOP SINK IN OUST. 47 EXISTING OUTDOOR TERMINATION DRAIN TO MOP SINK IN OUST. 77 DRAIN TO OUTSIDE DRAIN TO OUTSIDE DRAIN TO OUTSIDE NOTE: ROUTE ALL CONDENSATE PIPING WITH A 1/8" /1' SLOPECONDENSATE RISER DIAGRAM1 SCALE: NTSM-030 www.mckinstry.com PROJECT:ODU-04 REYG216XATJ A ODU-01 REYQ240XATJA ODU-05 REYG144XATJA ODU-06 REYQ168XATJA ODU-02 REYQ120XATJA ODU-03 REYQ144XATJA YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE BAA B REYQ96XATJAREYG120XATJAREYQ120XATJAREYQ120XATJA 3/8x7/8x3/4'1/2x1 1/8x374”1/2x11/8x3/4"1/2x11/8x3/4* QnTTBHFP26P100UBHFP26P100U Q A AAA3/8 x 3/8 x3/8 x 5/8'5/8'5/8'BC-18 FXSQ36TAVJU BC-19 FXSQ48TAVJU BC-06 FXSQ36TAVJU 318x518' AA3/8 x 5/8"BC-23 BCU-05 BSF4Q54TVJ BCU-06 BSF6Q54TVJ BCU-03 BSF6G54TVJ BCU-02 BSF4Q54TVJFXMQ54PBVJU 16525 100th Way SE Yelm, WA 98597 T B BBB3/8 x 3/8 xBCU-01 BSF8Q54TVJ 3/8 x3/8 x3/8 x KHRP26A250T 5/8'5/8'3/4'5/8'5/8'BC-15 FXSQ24TAVJU BC-20 FXSQ36TAVJU BC-10 FXMQ72MVJU BC-07 FXSQ36TAVJU BC-03 FXSQ36TAVJU BCU-04 BSF8Q54TVJB1/4 x CONSULTANTS:1/2"B —BC-25 378x5/8FXSQ18TAVJU 1/2 x1/2 x 1 1/8 x1 1/8 x C CCC3/8 x7/8'3/8 x3/8 x3/4' 3/8 x 5/8'5/8'5/8'5/8"BC-16 FXSQ48TAVJU BC-21 FXSQ36TAVJU BC-08 FXSQ36TAVJU BC-04 FXSQ36TAVJU CC 3/8 x 5/8'BC-11 FXSQ24TAVJU 5/8 x1/2 x 1 1/8 x1 1/8 x D DDD3/8 x 3/8 x7/8'7/8'3/8 x3/8 x 5/8'5/8'5/8'5/8'BC-17 FXSQ24TAVJU BC-22 FXSQ36TAVJU BC-09 FXSQ36TAVJU BC-05 FXSQ36TAVJUD 3/8 x3/8 x 5/8'5/8"BC-12 FXSQ48TAVJU BC-24 FXSQ48TAVJU EE ISSUE:5/8 x 1 1/8 x 1 1/8" 5/8 x 3/8x5/8*1 3/8 x E PERMIT SUBMITTAL3/8 x11/8' 5/8'BC-13 FXSG36TAVJU T Fm1/2 xKHRP26A250T 3/4"BC-01 REGISTRATION:FXMQ72MVJU FF 3/8 x3/8x5/8" Ws&k 5/8'BC-14 FXSQ36TAVJU O«o "8 7*GG ODU-12 REYQ144XATJA ODU-11 REYQ120XATJA HH3/8 x ISSUES:5/8"BC-02 NO DATE DESCRIPTIONFXSQ48TAVJU 04/29/2021 PERMIT SUBMITTAL TTTTAA 3/8 x3/8 x 5/8'5/8'BC-29 FXSQ36TAVJU BC-26 FXSQ36TAVJU ODU-09 RXYQ192XATJA ODU-10 RXYQ120XATJA ODU-08 RXYQ168XATJA ODU-07 NOT USED BCU-12 BSF4Q54TVJ BCU-11 BSF4Q54TVJBA RXYQ120XATJA RXYQ72XATJA BB 3/8 x3/8 x 5/8'5/8'BC-30 FXSQ36TAVJU BC-27 FXSQ36TAVJU 1/2x1 1/8'378x3/4' 1/2 x <=>1/2 x SR ENGINEER:DLSs=s»1 1/8 X1 1/8 xrW ccBHFP22P100U 3/8 x7/8'3/4"3/8 x DRAWN BY: AP/SA5/8'5/8'BC-31 FXSQ36TAVJU BC-28 FXSQ36TAVJU QC BY: LHr111/2 x5/8 x JOB NO: 204875-0031 1/8'1 1/8'CC-01 box 1 EKEXV250-US AHU 1 box 1 EKEXV400-US 0 CC-01AHU 1 ISSUED ON:04/29/20215/8 x 1 1/8'AHU 2 box 1 EKEXV400-US AHU 2 DD SHEET TITLE:3/8 x MECHANICAL DIAGRAMS 5/8'BC-32 FXSQ36TAVJU NOTE: THESE REFRIGERANT PIPING DIAGRAMS ARE PROVIDED FOR REFERENCE ONLY BY THE MANUFACTURER OF THE SPECIFIED EQUIPMENT AND ARE BASED ON ESTIMATED LENGTHS FROM PLAN SHEETS.REFRIGERANT SYSTEM PIPING DIAGRAM2 SHEET NUMBER:SCALE: NTSM-030 M-030 IS a a is a IS a r IS a IS a Me ForTh BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:07 AMmmHO ' **tinstry */fe Of Your Building McKINSTRY Co, LLC M - VRF OUTDOOR CONDENSING UNIT SCHEDULE Me,SPECIFIC NOTES: 1. NOT USED GENERAL NOTES: 1. DISCONNECT PROVIDED BY EC ELECTRICAL ForThPERFORMANCEPHYSICAL DIMENSIONSDESCRIPTION FACTORY REFRIGERANT CHARGE SCCR RATING EQUIPMENT COP @ 17°F EQUIPMENT COP @ 47°F ADDITIONAL REFRIGERANT OPERATING WEIGHT TOTAL COOLING CAPACITY (BTU/H) HEATING CAPACITY (BTU/H) CONNECTION RATIO SPECIFIC NOTESMOCPPHASERLAVOLTAGE MCAEQUIPMENT IEER/EER REFRIGERANTHxWxDNUMBER OF UNITS EQUIPMENT CLASSIFICATION EQUIPMENT NOMINALAREA / SYSTEM SERVEDMANUFACTURER TYPELOCATIONMODEL (A) (A) (0)(A)(V)TYPE(IN)ID (kA)DB DB(LBS)(%)(LBS) TONS (LBS) 5.02083 43.0/43.0 50.0/50.0 28.2 / 28.23.68 2.3422.20/11.6R410A 51.6 32.5100221,458 208,24566.7 x 48.9 x 30.2 (TYP 2) 727 / 727 20OFFICE SPACES/KITCHEN REYQ240XATJA AIR COOLED HEAT RECOVERY 2ODUOUTDOORSDAIKIN-01 SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 5.03 43.0 50.0 28.23.81 20825.50/13.20 2.5415.5112,091 90.0 R410A 25.8102,92266.7x48.9x30.2 727 10REYQ120XATJA AIR COOLED HEAT RECOVERYODU -02 OUTDOORS CLASSROOMS DAIKIN 1 5.0370.0 42.620858.323.50/11.90 3.75 2.16R410A19.2100.0 25.8134,390 128,01566.7x48.9x30.2 727 12OUTDOORSREYQ144XATJA AIR COOLED HEAT RECOVERY 1ODUCLASSROOMS DAIKIN-03 5.043.0/38.1 50.0/45.0 28.2/23.3208323.10/12.40 3.75 2.3451.6 42.5100.0 R410A727 / 727 190,147 196,398266.7 x 48.9 x 30.2 (TYP 2) 18AIR COOLED HEAT RECOVERYODU -04 OUTDOORS LIBRARY/CLASSROOMS DAIKIN REYQ216XATJA 70.0 42.6 5.0208 3 58.323.50/11.90 3.75 2.1619.4R410A 25.8134,323 127,753 91.766.7x48.9x30.2 12727OUTDOORSCLASSROOMSDAIKIN REYQ144XATJA AIR COOLED HEAT RECOVERY 1ODU-05 70.0 5.049.0361.922.30/ 10.70 3.49 2.08 20820.792.9 R410A 25.8155,439 141,47566.7x48.9x30.2 793 14AIR COOLED HEAT RECOVERYOUTDOORSDAIKINREYQ168XATJA 1ODU -06 CLASSROOMS www.mckinsti^.conn1ODU-07 5.060.0 37.6208355.122.60/10.60 3.40 2.34N/AR410A151,250 121,578 17.266.7 x 48.9 x 30.2 14AIR COOLED HEAT PUMP 695RXYQ168XATJA1ODU -08 OUTDOORS AHU-01 HPC DAIKIN PROJECT: 45.0/35.0 5.03 36.3/27.6 26.2/15.73.68 20822.20/ 11.50 2.27N/A163,332 R410A 35.9172,031 75.72 66.7 x 48.9 x 30.2 / 66.7 x 36.7 x 30.2527/437 16AIRCOOLED HEAT PUMPOUTDOORSDAIKIN RXYQ192XATJAODU-09 AHU-02 HPC YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE 45.0 5.03 36.3 26.220825.40/12.40 2.25N/A80.4 R410A 22.9111,904 97,63366.7x48.9x30.2 10AIR COOLED HEAT PUMP 527DAIKINRXYQ120XATJA1ODU -10 OUTDOORS CC-1 5.050.0 28.22.54 208 3 43.03.8125.8 N/A 25.50/ 13.2090.0 R410A110,365 99,77572710AIR COOLED HEAT RECOVERY 66.7 x 48.9 x 30.2REYQ120XATJA1OUTDOORS CLASSROOMS DAIKINODU -11 5.070.0 42.63 58.33.75 2.16 20823.50/11.90R410A 25.8 N/A133,497 124,999 100.012166.7x48.9x30.2 727REYQ144XATJAAIR COOLED HEAT RECOVERYOUTDOORSCLASSROOMSDAIKINODU -12 M - VRF INDOOR UNIT SCHEDULE SPECIFIC NOTES:GENERAL NOTES: 1. DISCONNECT PROVIDED BY EC 2. UNIT CONTROLS ARE DDC ACOUSTICALELECTRICALPERFORMANCEPHYSICAL DIMENSIONSCONNECTIONSDESCRIPTION MAX SOUND PRESSURE MAX FAN SOUND POWER SUPPLY FAN AIRFLOW (CFM) COOLING HEATING REQUIRED VENTILATION (CFM) SENSIBLE COOLING CAPACITY (BTU/H) TOTAL COOLING CAPACITY (BTU/H) OPERATING WEIGHT TOTAL NOMINAL TONS OUTDOOR CONDENSING ZONE CHANGEOVER DEVICE SPECIFIC NOTES 16525 100th Way SE Yelm, WA 98597 MOCPVOLTAGE PHASE MCATOTAL HEATING CAPACITY (BTU/H) HxWxDEQUIPMENT CLASSIFICATION EQUIPMENT ESPEATEATTYPEAREA/SYSTEM SERVEDMANUFACTURER MODELLOCATION (A)(V)(0)(A)ID (DB)(DB)(IN. W.G.)(°F DB)(°F DB/WB)(LBS)UNIT 4919.0 15.02,048 0,95 20862078.8/65.5 84,000 68.053,20568,154YES 18.5x54.3x43.3 302 6MSP CONCEALED DUCTED UNIT ODU-01FXMQ72MVJUABOVE CEILING STAGE DAIKINBC-01 421 15.00.60 208 2.8 7055,959 68.0 620 1,30778.8/65.532,96210446,023ODU-01 YES 9.7x55.1x31.5 4MSP CONCEALED DUCTED UNITFXSQ48TAVJU-02 ABOVE CEILING KITCHEN/OFFICES DAIKINBC CONSULTANTS:3915.00.60 208 671,130 1 2.541,287 68.0 50078.8/65.534,461 24,705101ODU-02 YES 9.7x55.1x31.5 3FXSQ36TAVJU MSP CONCEALED DUCTED UNITABOVE CEILING CLASSROOM 82 DAIKINBC-03 392.5 15.0 671,130 0.60 208450 178.8/65.5 41,287 68.034,461 24,705YES 101 3MSP CONCEALED DUCTED UNIT ODU-02 9.7x55.1x31.5FXSQ36TAVJUCLASSROOM 83 DAIKINBC-04 ABOVE CEILING 392.5 15.00.60 208 671,130 141,287 68.0 53578.8/65.534,461 24,705101 3MSP CONCEALED DUCTED UNIT ODU-02 YES 9.7x55.1x31.5FXSQ36TAVJUCENTRAL ACTIVITIES 86 DAIKINBCABOVE CEILING-05 15.0 391 2.5 671,130 0.60 20845078.8/65.5 41,287 68.024,70534,461YES9.7x55.1 X31.5 101 3MSP CONCEALED DUCTED UNIT ODU-03CLASSROOM 84 DAIKIN FXSQ36TAVJUABOVE CEILINGBC -06 15.0 390.60 208 2.5 67168.0 470 1,13078.8/65.5 41,28724,705101 3 34,461YES9.7x55.1 x 31.5MSP CONCEALED DUCTED UNIT ODU-03CLASSROOM 76 DAIKIN FXSQ36TAVJUABOVE CEILINGBC-07 15.0 390.60 208 2.5 674601,130 141,287 68.078.8 / 65.524,705101 3 34,461ODU-03 YES 9.7x55.1x31.5MSP CONCEALED DUCTED UNITABOVE CEILING CLASSROOM 85 DAIKIN FXSQ36TAVJUBC-08 3915.0 671,130 0.60 208 2.568.0 178.8/65.5 41,287 425101 34,461 24,705YES 9.7x55.1x31.5 3MSP CONCEALED DUCTED UNIT ODU-03FXSQ36TAVJUABOVE CEILING CLASSROOM 75 DAIKINBC -09 15.0 490.95 208 9.02,048 184,000 68.0 35553,205 78.8/65.50DU-O4 18,5x54.3x43.3 302 6 68,154YESFXMQ72MVJUMSP CEILING MOUNTED DUCTED UNITLIBRARY 42 DAIKIN-10 ABOVE CEILINGBC 361 1.8 15.0 640.60 20831574278.8/65.5 27,98016,53082222,951ODU-04 YES 9.7x39.4x31.5MSP CONCEALED DUCTED UNITFXSQ24TAVJUABOVE CEILING TUTORIAL 73 DAIKINBC-11 15.0 420.60 208 2.8 701,307 168.0 43578.8/65.5104 46,023 32,962YES4MSP CONCEALED DUCTED UNIT ODU-04 9.7x55.1 x31.5ABOVE CEILING CLASSROOM 69 DAIKIN FXSQ48TAVJUBC-12 391 2.5 15.0 671,130 0.60 20868.0 37078.8/65.5 41,28724,705101 34,461ODU-04 YES 9.7x55.1 x 31.5 3FXSQ36TAVJUMSP CONCEALED DUCTED UNITABOVE CEILING OFFICE 41 DAIKINBC-13 15.0 390.60 2.5 671,130 208 178.8/65.5 41,287 68.0 50034,461 24,7051013ODU-04 YES 9.7x55.1x31.5MSP CONCEALED DUCTED UNITCLASSROOM 67 DAIKIN FXSQ36TAVJUABOVE CEILINGBC-14 15.0 64 36208 1.87420.60 127,980 68.0 30016,530 78.8/65.582 2 22,951ODU-G5 YES 9.7x39.4x31.5MSP CONCEALED DUCTED UNITDAIKIN FXSQ24TAVJUABOVE CEILING CHAPTER 1 48BC-15 15.0 421700.60 208 2.855,959 68.0 510 1,30778.8/65.532,9621044 46,023ODU-05 YES 9.7x55.1x31.5FXSQ48TAVJUMSP CONCEALED DUCTED UNITABOVE CEILING CLASSROOM 57 DAIKIN-16BC 3615.00.60 208 1.868.0 180 742 178.8/65.5 27,98016,53022,9519.7 x 39,4 x 31.5 82ODU-05 YES 2MSP CONCEALED DUCTED UNITFXSQ24TAVJUABOVE CEILING PRE-SCHOOL 49 DAIKINBC-17 ISSUE:15.0 392.5 675500.60 208 141,287 68.0 1,13078.8/65.524,7053 34,461YES9.7x55.1x31.5 101ODU-05MSP CONCEALED DUCTED UNITABOVE CEILING CENTRAL ACTIVITIES 58 DAIKIN FXSQ36TAVJU-18BC 4215.0 700.60 208 1 2.81,30755,959 44532,962 78.8/65.546,023104 4YES 9.7x55.1x31.5MSP CONCEALED DUCTED UNIT ODU-06FXSQ48TAVJUABOVE CEILING KINDERGARTEN 53 DAIKINBC-19 PERMIT SUBMITTAL391 2.5 15.0 670.60 20841,287 68.0 405 1,13078.8/65.524,70534,4611013ODU-06 YES 9.7x55.1x31.5MSP CONCEALED DUCTED UNITCLASSROOM 56 DAIKIN FXSQ36TAVJUABOVE CEILINGBC-20 392.5 15.0 671,130 0.60 208 168.0 38578.8 / 65.5 41,28724,70510134,4613ODU-06 YES 9.7x55.1x31.5MSP CONCEALED DUCTED UNITCLASSROOM 54 FXSQ36TAVJUABOVE CEILING DAIKINBC-21 15.0 391,130 0.60 208 2.5 67141,287 68.0 44578.8/65.534,461 24,705101YES9.7x55.1x31.5 3MSP CONCEALED DUCTED UNIT ODU-06FXSQ36TAVJUABOVE CEILING CLASSROOM 55 DAIKIN-22BC 453.4 15.00.56 208 1 7568.0 200 1,62462,20378.8 / 65.551,124 37,83611.8 x 55.1 x27.6 104 4.5ODU-01 YESMSP CEILING MOUNTED DUCTED UNITOFFICE SPACES FXMQ54PBVJUABOVE CEILING DAIKINBC-23 15.0 422.8 70208 155,959 68.0 120 1,30778.8/65.532,96246,0239.7x55.1x31.5 104 4QDU-01 YESMSP CONCEALED DUCTED UNITOFFICE SPACES DAIKIN FXSQ48TAVJU-24 ABOVE CEILINGBC REGISTRATION: 15.0 62 340.60 208 1.665120,814 41,287 68.0 60078.8/65.513,04017,170YES9.7x39.4x31.5 77ODU-01 1.5FXSQ18TAVJUMSP CONCEALED DUCTED UNITABOVE CEILING OFFICE SPACES DAIKIN-25BC 208 1 2.5 15.0 671,130 0.6068.0 50078.8/65.524,70534,4619.7x55.1x31.5 101 3ODU-11 YESMSP CONCEALED DUCTED UNITABOVE CEILING CLASSROOM N 01 DAIKIN FXSQ36TAVJUBC 15.0 67 391,130 0.60 208 2.5500141,287 68.078.8/65.534,461 24,7059.7x55.1 x 31.5 101 3ODU-11 YESMSP CONCEALED DUCTED UNITFXSQ36TAVJUCLASSROOM N 02 DAIKIN-27 ABOVE CEILINGBC 15.0 671,130 0.60 20868.0 500 1 2.578.8/65.5 41,28724,70534,4619.7x55.1 x 31.5 101 3YESMSP CONCEALED DUCTED UNIT ODU-11DAIKINFXSQ36TAVJUABOVE CEILING CLASSROOM N 03BC-28 3915.0 671,130 0.60 208 2.541,287 68.0 500 178.8/65.524,70510134,4619.7x55.1 x31.5 3ODU-12 YESMSP CONCEALED DUCTED UNITCLASSROOM N 04 DAIKIN FXSQ36TAVJUABOVE CEILINGBC O39208 2.5 15.0 6768.0 1,130 0.60 141,287 55078.8/65.534,461 24,7053YES9.7x55.1 x 31.5 101MSP CONCEALED DUCTED UNIT ODU-12FXSQ36TAVJU coCENTRAL ACTIVITIES N11 DAIKINBCABOVE CEILING-30 Z 391 15.0 671,130 0.60 208 2.541,287 68.0 50078.8/65.524,705101 3 34,4619.7x55.1 x 31.5ODU-12 YESFXSQ36TAVJUMSP CONCEALED DUCTED UNITABOVE CEILING CLASSROOM N 09 DAIKINBC-31 7?AT,3915.01,130 0.60 208 2.5 6768.0 500 178.8/65.5 41,28734,461 24,7059.7x55.1 x 31.5 3YES101MSP CONCEALED DUCTED UNIT ODU-12FXSQ36TAVJUABOVE CEILING CLASSROOM N 10 DAIKINBC-32 AW0106252 M - VRF AHU COIL SCHEDULE SPECIFIC NOTES: 1. PROVIDE WITH DAIKIN AHU INTEGRATION VALVE KITS TO MATCH COIL AND ODU. SEE CORRESPONDING SCHEDULE ON THIS SHEET. 2. NOT SHOWN ON PLANS. PROVIDE IN NEW AHU CABINET. SEE AHU SCHEDULE. GENERAL NOTES:ISSUES: NO DESCRIPTIONDATE 04/29/2021 PERMIT SUBMITTAL CONTROLSPERFORMANCEPHYSICAL DIMENSIONSCONNECTIONSDESCRIPTION HEATINGCOOLINGNOMINAL TOTAL HEATING CAPACITY (BTU/H) HEATINGNOMINAL TOTAL COOLING CAPACITY (BTU/H) NOMINAL SENSIBLE COOLING CAPACITY (BTU/H) COOLINGOPERATING WEIGHT FIN FINOUTDOOR CONDENSING SPECIFIC NOTESTOTAL NOMINAL TONS FINS PERLxWxDAREA / SYSTEM SERVED EQUIPMENT CLASSIFICATION EQUIPMENT CONTROLSEAT LATEATLATROWSHEIGHT LENGTHTYPEMANUFACTURERMODELLOCATION INID (°F DB/WB)(°F DB/WB)(°F DB)(°F DB)(LBS)UNIT DDC54.4 / 52.9 182,993 60.0 1,2102,761 78.0/63.5 101.8122,235115 10.145.1 x35.3x6.6 32.25 40 12 4DX COOLING COIL ODU-0812H31.25x40-12-4-W-Z-RRAEAHU-01 (GYMNASIUM)AHU-01 AHU-01HPC DDC60.0 100.6 1,2123,169 78.0/63.5 54.4 / 53.8 221,737141,42111811.831.25 13 445.1 x 35.3x6.6 40DX COOLING COIL ODU-0912H31.25x40-13-4-W-Z-RAHU-02 (GYMNASIUM)RAEAHU-02HPCAHU-02 60.0 DDC78.0/63.5 52.5/51.1 195,198 115.8 188,7159.4 112,2949148604ODU-10 64.8x36.5x6.6 32.50DX COOLING COILRAE12H32.5x60-9-4-W-H-RAHU-1 (EXISTING CABINET)AHU-1CC-01 M - VRF AHU INTEGRATION VALVE KIT SCHEDULE SPECIFIC NOTES:GENERAL NOTES: 1. NOT SHOWN ON PLANS 2. PROVIDE WITH EKEQMCBAV3-US CONTROL BOX CONTROLSELECTRICALPERFORMANCEPHYSICAL DIMENSIONSCONNECTIONSDESCRIPTION SR ENGINEER:DLS TOTAL HEATING CAPACITY (BTU/H) TOTAL COOLING CAPACITY (BTU/H) OPERATING WEIGHT TOTAL NOMINAL TONS OUTDOOR CONDENSING ZONE CHANGEOVER DEVICE DRAWN BY: AP/SASPECIFIC NOTESVOLTAGE PHASE DISCONNECT PROVIDED BY HxWxDEQUIPMENTAREA/SYSTEM SERVED EQUIPMENT CLASSIFICATION CONTROLSTYPEMANUFACTURERMODELLOCATION(V)(0)(IN)ID QC BY: LH(LBS)UNIT JOB NO: 204875-003DDC12 1 EC168,901 187,66815.8x8.5x3.1 12ODU-8 NO 7AHU INTEGRATION VALVE KITEKEXV400-USDAIKINAHU-01 AHU-01N/A N/A DDC187,668 12 EC ISSUED ON:04/29/2021168,901 115.8x8.5x3.1 12ODU-9 NO 7AHU INTEGRATION VALVE KITEKEXV400-USDAIKINAHU-02 AHU-02N/A N/A EC DDC168,901 118,401 12 115.8x8.5x3.1 7 8NOAHU INTEGRATION VALVE KIT ODU-10EKEXV250-USCC-01 DAIKINN/A AHU-1N/A SHEET TITLE: MECHANICAL SCHEDULES SHEET NUMBER: M-060BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:10 AM ' ^Mnstry W-ife Of Your Building McKINSTRY Co, LLC y - VRF BRANCH CONTROLLER SCHEDULE MCiSPECIFIC NOTES: 1. NOT USED GENERAL NOTES: ELECTRICALPERFORMANCEPHYSICAL DIMENSIONS ForThCONNECTIONSDESCRIPTION MAX CAPACITY PER PORT (BTU/H) MAX UNIT CAPACITY (BTU/H) OPERATING WEIGHT SPECIFIC NOTESVOLTAGE PHASE MCA MOCPHxWxDOUTDOOR CONDENSING UNIT EQUIPMENT CLASSIFICATION EQUIPMENT NUMBER OF PORTSAREA/SYSTEM SERVEDMANUFACTURER MODELLOCATION (0)(A)(V)(A)(IN)ID (LBS) 15.02080.8854,000 432,000 19.5 x 23.3 x 23.7ODU-01 82BSF8Q54TVJOFFICE SPACES/KITCHEN DAIKINABOVE CEILINGBCU-01 15.00.44 208 SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 54,000 216,000 149ODU-02 9.5x13.7x23.7BSF4Q54TVJABOVE CEILING CLASSROOMS DAIKINBCU -02 15.0208 1 0.6654,000 324,000ODU-03 73BSF6Q54TVJ9.5 x 23.3 x 23.7CLASSROOMS DAIKINABOVE CEILINGBCU -03 15.08 208 0.854,000 432000 1ODU-04 9.5 x 23.3 x 23.7 82BSF8Q54TVJLIBRARY/CLASSROOMS DAIKINABOVE CEILINGBCU -04 15.04208 1 0.454,000 216,000ODU-05 9.5x13.7x23.7 49BSF4Q54TVJCLASSROOMS DAIKINABOVE CEILINGBCU -05 208 0.6 15.0154,000 324,000ODU-06 9.5 x 23.3 x 23.7 73BSF6Q54TVJABOVE CEILING CLASSROOMS DAIKINBCU -06 BCU -07 15.04 208 0.454,000 216,000 19.5x13.7x23.7 49BS4Q54TVJODU-11CLASSROOMSDAIKINABOVE CEILINGBCU-11 www.mckinstry.com15.0208 0.44154,000 216000ODU-12 9.5x13.7x23.7 49BSF4Q54TVJABOVE CEILING CLASSROOMS DAIKINBCU -12 PROJECT: M - AIR HANDLING UNIT SCHEDULE YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE SPECIFIC NOTES:GENERAL NOTES: ELECTRICALHEATING COILDX COOLING COILPHYSICAL DIMENSIONS SUPPLY FANDESCRIPTION SPECIFIC NOTES REQUIRED SCCR MAX FACE VELOCITY FLUID FLOW (GPM) REF. MASS FLOW (LB/H) MAX FACE VELOCITY MAX FAN SPEED (RPM) BRAKE HORSEPOWER OPERATING WEIGHT UNIT DESIGN AIR FLOW (CFM) WHEEL DIA.MOCPPHASE FLA MCAFLUID PD (FT HEAD) VOLTAGEAIR PD (IN. W.C.) EAT LATLAT AIR PDMOTOR SIZE BLOW THRU/ DRAW THRU EATHxWxDTOTAL SP (IN. W.C.) AREA / SYSTEM SERVED EQUIPMENT CLASSIFICATION EQUIPMENT HEAT TYPECONTROLMANUF.MODELLOCATION (0)(A) (A)(A)(V)(°F DB)(°F DB)(°FDB/WB)(IN. W.C.)(HP)(°F DB / WB)(IN)ID (kA)(FPM)(FPM)(HP)(LBS) 20,0 5.039.20.20 459 208 11.50.17 6.51,504 HOT WATER 90.0 105.1SEE VRF AHU COIL SCHEDULE0.55 4653.8 ECM BLOW2,600 2.2CAH010GHCM78 x 54 x 54 1,160 4,000 2.42ABOVE CEILING GYMNASIUM 27 DAIKIN 17.71AHU -01 5.09.2 20.0545 208 3 11.50.30HOT WATER 90.0 105.1 0.24 8.11,741 576SEE VRF AHU COIL SCHEDULE0.78BLOW3.8 ECM78 x 56 x 56 5,000 2,600 3.2CAH010GHCM 1,200 2.76 17.71ABOVE CEILING GYMNASIUM 27 DAIKINAHU-02 M - HOT WATER HEATING COIL SCHEDULE SPECIFIC NOTES: 1. NOT USED GENERAL NOTES: 1. NOT SHOWN ON PLANS. INSTALL IN DUCT DOWNSTREAM OF BC UNIT IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.16525 100th WaySE Yelm, WA 98597HEATING COILPHYSICAL DIMENSIONSDESCRIPTION NOMINAL TOTAL HEATING CAPACITY (BTU/H) MAX FACE VELOCITY MAX FLUID PRESSURE DROP (FT W.C.) AIR PRESSURE DROP (IN. W.C.) OPERATING WEIGHT SPECIFIC NOTESLWT FLUID FLOW (GPM) EWTAIR FLOW (CFM) LATEAT CONSULTANTS:FIN HEIGHTFIN LENGTHLxWxDEQUIPMENT CLASSIFICATION FINS PER INROWSMODEL TYPELOCATION AREA/SYSTEM SERVEDMANUFACTUREREQUIPMENT ID (°F)(°F)(°F DB)(°F DB)(IN)(IN)(IN)(FPM)(LBS) 1.29 461117.5 4.0014090.1 0.0744,488 SEE BC SCHEDULE 70.0624552.3x17.5x4.9 13.5 47.558W13.5x47.5-6-2-F-Z-RHYDRONICABOVE CEILING BC-01 RAE-01HWC 0.07119.5 1.35 535140SEE BC SCHEDULE 79.6 0.0713,637 70.033451.8x11.5x4.9 47 258W7.5x47-4-2-F-F-RHYDRONIC 7.5ABOVE CEILING BC-02 RAE-02HWC 119.0 0.29 4622.7092.9 0.14 140SEE BC SCHEDULE 70.027,954103747258W7.5x47-10-2-W-F-RHYDRONIC 51.8x11.5x4.9 7.5-03 ABOVE CEILING BC-03 RAEHWC 0.29 462119.0140 2.7092.9 0.1427,954 SEE BC SCHEDULE 70.02103751.8x11.5x4.9 7.5 4758W7.5X47-10-2-W-F-RHYDRONIC-04 ABOVE CEILING BC-04 RAEHWC 119.0 0.29 4622.7092.9 140SEE BC SCHEDULE 0.1427,954 70.03710251.8x11.5x4.9 4758W7.5x47-10-2-W-F-RHYDRONIC 7.5ABOVE CEILING BC-05 RAE-05HWC 119.0 0.29 462140 2.7092.9 0.14SEE BC SCHEDULE 70.027,9541037258W7.5x47-10-2-W-F-RHYDRONIC 51.8x11.5x4.9 477.5-06 ABOVE CEILING BC-06 RAEHWC 0.29 462119.0140 2.7092.9 0.1427,954 SEE BC SCHEDULE 70.0210 3751.8x11.5x4.9 4758W7.5x47-10-2-W-F-RHYDRONIC 7.5ABOVE CEILING-07 BC-07 RAEHWC 119.0 0.29 4622.7092.9 0.14 14027,954 SEE BC SCHEDULE 70.02103751.8x11.5x4.9 4758W7.5x47-10-2-W-F-RHYDRONIC 7.5-08 ABOVE CEILING BC-08 RAEHWC 0.29119.0 462140 2.70SEE BC SCHEDULE 92.9 0.1427,954 70.0102 3751.8x11.5x4.9 7.5 4758W7.5x47-10-2-W-F-RHYDRONICBC-09-09 ABOVE CEILING RAEHWC 1.29 461117.50.07 14070.0 90.144,488 SEE BC SCHEDULE4562HYDRONIC 52.3x17.5x4.9 13.5 47.558W13.5x47.5-6-2-F-Z-RBC-10 RAE-10 ABOVE CEILINGHWC 0.35 447118.2 1.8094.0 140SEE BC SCHEDULE 70.0 0.0819,3282636.6x11.5x4.4 32 10 212W7.5x32-10-2-F-H-RHYDRONIC 7.5ABOVE CEILING BC-11 RAEHWC-11 0.29 536140119.1 2.700.1227,826 SEE BC SCHEDULE 70.0102377.5 4758W7.5X47-10-2-F-F-RHYDRONIC 51.8x11.5x4.9-12 ABOVE CEILING BC-12 RAEHWC 462119.2 1.3080.9 0.05 140 ISSUE:13,355 SEE BC SCHEDULE 70.0612950.9x11.5x3.6 4758W7.5X47-6-1-W-E-RHYDRONIC 7.5RAEABOVE CEILING BC-13HWC -13 462119.0 0.291402.7092.9 0.1427,954 SEE BC SCHEDULE 70.03710251.8x11.5x4.9 7,5 4758W7.5X47-10-2-W-F-RHYDRONICABOVE CEILING BC-14 RAEHWC-14 0.61 447118.0 0.8080.8 140SEE BC SCHEDULE 70.0 0.038,68422 PERMIT SUBMITTAL32 6 112W7.5x32-6-1-F-E-RHYDRONIC 35.7x11,5x3.4 7.5-15 ABOVE CEILING BC-15 RAEHWC 119.1 0.29 5361402.7089.7 0.1227,826 SEE BC SCHEDULE 70.01023751.8x11.5x4.9 4758W7.5x47-10-2-F-F-RHYDRONIC 7.5ABOVE CEILING BC-16 RAEHWC -16 0.61 447118.0 0.8080.8 14070.0 0.038,684 SEE BC SCHEDULE62212W7.5x32-6-1 -F-E-R 35.7x11.5x3.4 7.5 32HYDRONIC-17 ABOVE CEILING BC-17 RAEHWC 0.21 462119.7 2.301400.1023,008 SEE BC SCHEDULE 70.023558W7.5x47-7-2-W-F-R 51.8x11.5x4.9 47 7HYDRONIC7.5ABOVE CEILING BC-18 RAEHWC-18 536119.1 0.291402.700.1227,826 SEE BC SCHEDULE 70.02103751.8x11.5x4.9 4758W7.5x47-10-2-F-F-RHYDRONIC 7.5ABOVE CEILING BC-19 RAE-19HWC REGISTRATION:0.29 462119.0 2.7014070.0 92.9 0.1427,954 SEE BC SCHEDULE102 3751.8x11.5x4.9 4758W7.5x47-10-2-W-F-RHYDRONIC 7.5ABOVE CEILING BC-20 RAEHWC-20 119.0 0.29 4622.7092.9 0.14 140SEE BC SCHEDULE 70.027,954103747251.8x11.5x4.958W7.5x47-10-2-W-F-RHYDRONIC 7.5ABOVE CEILING BC-21 RAEHWC -21 462119.0 2.70 0.2914092.9 0.1427,954 SEE BC SCHEDULE 70.010 377.5 47 258W7.5x47-10-2-W-F-RHYDRONIC 51.8x11.5x4.9-22 ABOVE CEILING BC-22 RAEHWC mm®/v 1HWC-23 1-24HWC 1-25HWC oo O462119.0 0.291402.700.1427,954 SEE BC SCHEDULE 70.010 3751.8x11.5x4.9 47 258W7.5x47-10-2-W-F-RHYDRONIC 7.5ABOVE CEILING BC-26 RAEHWC-26 Z 7*0.29 462119.0 2.7092.9 1400.1427,954 SEE BC SCHEDULE 70.03710 251.8x11.5x4.9 7.5 4758W7.5x47-10-2-W-F-RHYDRONIC-27 ABOVE CEILING BC-27 RAEHWC WtOim.119.0 0.29 462140 2.7070.0 92.9 0.1427,954 SEE BC SCHEDULE1037258W7.5x47-10-2-W-F-RHYDRONIC 51.8x11.5x4.9 7.5 47-28 ABOVE CEILING BC-28 RAEHWC 119.0 2.70 0.29 46214070.0 92.9 0.1427,954 SEE BC SCHEDULE1037251.8x11.5x4.9 7.5 4758W7.5x47-10-2-W-F-RHYDRONICRAEABOVE CEILING BC-29HWC-29 Vi 119.0 0.29 4622.7092.9 0.14 140SEE BC SCHEDULE 70.027,95410372HYDRONIC 51.8x11.5x4.9 4758 W7.5x47-10-2-W-F-R 7.5BC-30 RAE-30 ABOVE CEILINGHWC 119.0 0.29 462140 2.7092.9 0.1427,954 SEE BC SCHEDULE 70.01023751.8x11.5x4.9 4758W7.5x47-10-2-W-F-RHYDRONIC 7.5-31 ABOVE CEILING BC-31 RAEHWC rX-119.0 462140SEE BC SCHEDULE 70.0 92.9 0.14 2.72795437102HYDRONIC 51.8x11.5x4.9 4758W7.5x47-10-2-W-F-R 7.5RAE-32 ABOVE CEILING BC-32HWC r ISSUES: NO DATE DESCRIPTION M - DAMPER SCHEDULE 04/29/2021 PERMIT SUBMITTAL SPECIFIC NOTES: 1. CONTRACTOR TO VERIFY DIMENSIONS OF EXISTING DUCT AND MATCH. GENERAL NOTES: PHYSICAL DIMENSIONSDESCRIPTION SPECIFIC NOTESHEIGHTWIDTHAREA/SYSTEM SERVED EQUIPMENT CLASSIFICATION TYPEMANUFACTURERMODELLOCATION (IN)(IN) VERTICAL 1RUSKINCD60SEE PLANS VARIESMD SR ENGINEER:DLS DRAWN BY:AP/SA QC BY:LH 204875-003JOB NO: ISSUED ON:04/29/2021 SHEET TITLE: MECHANICAL SCHEDULES SHEET NUMBER: M-061BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:11 AM **)instry fn.ifo Of Your Building McKINSTRY Co, LLC Me ForTh 2 0 3 7 4 :(.8 }i 1 (627)X 8 j 19) i;101>)16( 13 14 ,15( 5 )(12;SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 .v aBy www.mckinstry.comiii/ ]% iallS.C U:i. .7 (PROJECT: i! bT b i YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE i x ' \ - b j.......x...;a:sIxxxb xbxxx : Bl.XBa B Ij b . i,;tx;I :;:l ’J XX XX Lbxb 3):Lx.r t::)■b 1 !I :t B-s l- -•nsrctu;"1;-ibb B B''-BaccTC:---- •••• - ; - v-Lx:'Bxv B: —i 1 AREA A.j □I:; '•""0 v :! 6 / " ■ ■■■ ■ ■#T;" pr p: bBbr: N 0} :; 4\J 16525 100th Way SE Yelm, WA 98597 :r: :!X B:X- -j*B B->y wi !illWi- -I ,b a J 0LBlisyi r\C-,b yxxxx\1 / MD-101 DEMO 1 / M-101 ‘new ;7r iP;is XLXX;BT T V?ip CONSULTANTS:\/ \ \i i;lxB — 7 *.:0: «*r<- r ^;IB Si rx I LXLlb:...I1 / MD-102 demo 1 /M-102 new b rX;.d;i T‘ i.$\ 'V-VC b ;n BbI EAC-i y 0 x 7 bbBbir;bB 0 s:lb bb b.I b 1, I .............V"-' B’''';•bl \ ■rh"' ■Bli....i B........!\b '<1 v\.y L.a,..- 3! ~oibiy'■y /b sbIb-splpp!IL_ j■4/b ■31 ' ^ : s:blf □hx'*pbbbbbb: bLbba-bblb :bb- 4- >tb =< riTbbt"'(,:bbxxbb:\ ;:bblbl;x U Y L bifex X Ibri ,,,.bib : fX ID;■/bb■(bxD i..:-XX * X|!b ,•;Lxx/. I >b)AREAB r)'■ :: bbb I::.vI):bb*bb bbb.; - b.y bbxbbrcT bb lib 111)bb lx%;bb b”,;:: bb-r-va <- ’Jbly-bb ::b bxibQTbbbmr■ ■ bM.■r)b ISSUE:0...1:: ba-i...:..b:xr;;lb ::a bb' ''bb xiLx:fr b «b bbob ibxbbbX XB;bb /x bXS PERMIT SUBMITTAL£> Xlb g1:{bbSbibbbb k'-\' /■x xxr: p'X!bx-b r :is b -Vx y X (,1;...r-•yb 'Vx ,A/ #'b ;bbb bbbMbO\\/bx ■ aX . jIl bb , / b.: :>b rbbbxbbbbbi I'b b bxbb1\y b:\ ‘ y 1 / MD-105 demo - i r:xXa::xx:xxXy xb;>xix xxceP;:)bb b b AREA E b bx- ,x: X REGISTRATION:Obb XL:xb:b b b xiin;::zBxbbby l 5 b by yby-•X ;Yay;rT0 b yxbbbbxnxnX-/bb......1 / M-105 NEW >:.Xx.b)b::i;xb\c-;-\-".: X..1 / MD-103 demo bLX1 / M-103 new ^b—r-' 1/ MD-104 demo 1 / M-104 new .xx-. 3 11 x :x b i bx i..-I a' " T -V-1" a .ubxnr .yv .-..a ay x aa.L-aXi a'XX->-----<-:<> -/'X\XI \X........ /y>-.-r>:..............X Vbbr: i X X\f'M xb ps.„-lib )I Oj ITbbbxHib l xb...i CO/■'b,/21ter:>S-:..TLX;XX y.xx Abr -:B.....bb aXbe!X a 7?I 9<m. Sa:u£fiX;/;jb bbb oS'.XX bx \ X X a X X. a a Bxb V tooI'X ]jbL X. FbXb:(XISIXXEXX My.20 to!5$152u.XX moi:.:X:b l:l.......N-0/XYbbflaxxB : bib. x>% X. "■; X.a- V XX/Bb BbBbBb-IJb. bxxxb !m a B XB-.........“T bb(./[:. ,:b Ba0-Xsb 01bXb//'■1 rx;B?.nxxcXxy;.. $.0:; X;... f \■-aa-JbXX.;) nbxg XX;l...-0 b:.;:b B X■' Xx bb:X a ‘ ^aaarr.vR vajj Xa :::i l ixliLllXaa X BbaapcxxI XxxxmxX X■ISSUES::r33iIaXai"'../I11.b xbbb.f b lb lb:X :DESCRIPTIONx.DATE•r NObxxbba-i Ibll:\J....:i■b<,, !x\ a-Ba 04/29/2021 PERMIT SUBMITTALbbby-b,:bb ....G'V BbbxiI••X,b;b •by.i:fi b-■"XX;B .-'a U b b xb X'x 0 .bbbBjbbXBljlbl........n &bl B"-"BillIB ; b ill;Ix'\- lb I aaxxRXXIb^"0iB-> Cb...r B i...y rbba-a lap" x.., - - b b.BB 'B'ibi...!■B1..../rxj- 7- ;/ 0ab ‘V \ alxaxx 07* AREA D BB bbB ii. -• r.ri rX. X IIIbbblbbxx..c-:x:7}.xxvr:xx?n;:.xx-y -ByLB i.10IBBBGbbbB-x bBB " ■HI ixfxL BBC b'B:Ls-'■■Vi -a-. a b)iB ... u ) lbB !■b BIB L.B . ;BIB::ID*r:a...xXb.bX’x bx.,la X XXi ; 0BBllDBi l/V •:x :xt:■b•' B-...........j;B b■v blx:'Tr"i.5 ■XX'PxnC;b ;..:s %,0 i Bb .'V;B r fir"bf ,..b;yiXx-aRb"Xr:BBBB-C! b ■ b........Bi . .... ...; ...:b :b CB-'LL. _ y: >B..............x:.B' LX 1 X i"":: by “ b'-, |XL:.aj —;i -'■■'xx.'.x:.:;x.x. XX- TV'I B ;■ xxJi :.l 0 Bill''-xlbB b!BagibiBl%:BB ;;g-I x0Bb 1 B b B Bala : Ipxbrbxa;I xb2 0 3 ):LLIJ: 1 -.;: :XXI a r X ■ i...LbIIB : a :.....M :iBIB SR ENGINEER:DLS: BL-b-b DRAWN BY:AP/SAX,...XX ■■■XX: B !; «aaXaXB':X'.1 iaaaexXJaXXiSa:QC BY: LHi...i ■.bIb 204875-003JOB NO:XX KEYPLAN\ x S'04/29/2021ISSUED ON:'a.. :Xa-iaX i : SHEET TITLE:A;LEVEL 1 - MECHANICAL PLAN - OVERALL I C (16)(13)17 iX14 15 ;i 8 ((12 }10 |6 ? 7 XX 5 x4 X EB DLEVEL 1 - MECHANICAL PLAN - OVERALL1 0SCALE: 1/16" = 1’-0'M-100 %8’ 16*32*0 & SHEET NUMBER: M-100BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:17 AM ' ^tinstry m.ifo Of Your Building McKINSTRY Co, LLC MeDEMO KEYNOTES O 1. REMOVE EXISTING HEATING-ONLY FAN COIL UNIT AND CONTROLS. DEMO BACK ASSOCIATED DUCTWORK AS REQUIRED TO PROPERLY INSTALL NEW EQUIPMENT. 2. REMOVE EXISTING ZONE TEMPERATURE SENSOR. 3. REMOVE EXISTING OUTDOOR HEAT PUMP UNIT. 4. REMOVE EXISTING INDOOR BLOWER COIL UNITS. 5. DISCONNECT HEATING WATER PIPING. ForTh SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 DEMO GENERAL NOTES A. RECLAIM REFRIGERANT PER LOCAL REQUIREMENTS. B. PROPERLY DISPOSE OF ALL EQUIPMENT REMOVED FROM SERVICE. C. REMOVE ALL DISCONNECTED REFRIGERANT PIPING AND HANGERS.www.mckinstry.com PROJECT: YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE 16525 100th Way SE Yelm, WA 98597 ,86741 2 m3 5 CONSULTANTS:i : : :;;! 12/12 -! ::!210 CFM.210 CFM : WOMEN! io/8 ;raRCP-1 r "•~v: ; 10/8 i i!I iWt i j\*;; —vr—-! :i 14/14;iHALl ! ym; i:! w: }}• hF-1 iib ISSUE: i0a! !80 CFM!<Jhr \ PERMIT SUBMITTAL!10/8 r ?0SOCEM A.I J \MjsMENi j J................' A ;r ir EF-2 ;..i CUSTODIAN:ihIi 1 \A I<HA—I <J\A-;!l REGISTRATION:i ;jSTORAGE;: C I;WMm: Iff 20 x 12 DS 530 CFM 12" 0 (TYP. OF 6) 0 ! X II Tfi:ooo12/16 ---\-®\i *3: 'fi­ll«/o *2010625;x2" 0,,XI ■<s>|7 16/18 - AUX. ; ! GYMNASIUM!'® ill.i I 0 I ■g-M:;12" 0 i ISSUES:C 18/18 DATE DESCRIPTIONNO® lit.• | —VO 04/29/2021 PERMIT SUBMITTALi12" 0 i ! 20/20 I-12" .0;: ;> —'v*>Li 21/23 12" 03 > OCU-1 3 fin ri AHU-1f IREMOVE AHU-1 COOLING COIL. MAINTAIN EXISTING AHU-1 CASE. (II miD | 3E 32” X 32" HDR 3270 CFM I\;! <v\—i \ • fcrrJ?j; 3/4'i :: YJ,SR ENGINEER:DLSi1 / MD-103JA—V*>;! DRAWN BY:AP/SA "2 x 4' WPL'..! 1800 CFM 7"1 / MD-102 QC BY:LHS'jjpp: EF-11 204875-003JOB NO:l IIi 04/29/2021ISSUED ON: j i i ; SHEET TITLE:KEYPLAN: LEVEL 1 - MECHANICAL DEMO PLAN - AREA A j A C LEVEL 1 - MECHANICAL DEMO PLAN - AREA A1 EB SCALE: 1/8" = Y-0 itMD-101 D16'0 t 8'4 Q %& SHEET NUMBER: MD-101BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:25 AM ■ ^tinstry knife Of Your Building McKINSTRY Co, LLC DEMO KEYNOTES OI Me1. REMOVE EXISTING HEATING-ONLY FAN COIL UNIT AND CONTROLS. DEMO BACK ASSOCIATED DUCTWORK AS REQUIRED TO PROPERLY INSTALL NEW EQUIPMENT. 2. REMOVE EXISTING ZONE TEMPERATURE SENSOR. 3. REMOVE EXISTING OUTDOOR HEAT PUMP UNIT. 4. REMOVE EXISTING INDOOR BLOWER COIL UNITS. 5. DISCONNECT HEATING WATER PIPING. 1 / MD-101 j16" X 12" MOL. m -v J F 1F For ThL./B.D.M STORAGE ITTi|i I ;48” X 32" T.T.G. i MT. BTM. @ 18' A.F.F.T <L OVER DOOR : 48” X 32" W.P.L.I EF-11f 25 iwSTORAGEiCO12/8 lluif\CO 24 G? *VD " ‘2 DEMO GENERAL NOTES. 44" X 30" T.S.R. 2500 CFM SEATTLE; 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 //\ •8/6 A. RECLAIM REFRIGERANT PER LOCAL REQUIREMENTS. B. PROPERLY DISPOSE OF ALL EQUIPMENT REMOVED FROM SERVICE. C. REMOVE ALL DISCONNECTED REFRIGERANT PIPING AND HANGERS. o CM O CO I toH&V-2i---------T*rra \1 \/\!3|20” X 8" IT G/\\rr~ V-M'V L.www.mckinstry.coin STORAGE i PROJECT:23» .22" X 34” DN, TO RG. & FIR OFFiCE i It YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE GYMNASIUMfiii.’(j 27Cl.l 26/6r22iA, 36/6CM\\o I L. J L LCM CM /l I1COOO .J. •’CJ* sL,i CM ,( j 7" CO 1 *X \44" X 30" T.S.R, 2500 CFM. I "e WOMEN\/OO I /cd v;/\/,\/V Jtv7<J •i M Ix ! o r E.F.-1E.F-2 sIv.D.2 / .tTF]/\L._.r/cr 19/19 <[O l \ Xirippv.D.!vM"B.D.(MECHANICAL10/G 14/12B.D.-)8! f 1 CD f f V.D.■i—4I\ i 1 39I20/123I 16,fX16’i M' ^;/J\30i24 CMI !(:r ~i r," iiDNOFFICEB.DPJ 12/6521CM\\IZZQ- 1.. -s MENU112/10X I?< 219o\t~T y\\)\^ 40” X 30" T.S.R. 2000 CFM 37!W TIV D J ICOI_2U CO /.10/6Ik_/F.I.D.4/16525 100th Way SE Yelm, WA 98597 No.3 lKITCHENj!FID CO s ^ l CM I V.D. V . ;....• ;/Li (1YP)CO18 CM ,H-12/8\CO \ t /\&CO YdCMi1 1/4'wi>;V.D.• I. ..! t Li-i IDEMO H&V UNIT AND LEAVE SUPPLY AND RETURN AIR DUCTWORK IN PLACE FOR RECONNECTION TO NEW AHU (TYP 2) O r-CM A /STORAGE CONSULTANTS:I I V “718/10 H&V.-1v 40/. dtr-6/6IIt i-* -2O’ STORAGE>M)CM18” X18” EXH UP TO ROOF E.F-10 CO! I ID V I 20£22 l£j (T <x> ’ CO ^ l cm TZ XV.D.CCi(CT CO CORRIDORi I10/6QI—ih-X X XPv "i:i'./Y0"X30" TSR LCOI—(36AJ-4 M <CXL... 2 7 .oI/\22” X 26” DN TO R.G. @ FLR. ! i f 2000 CFM V.D.oiic —X \x:\i 8/6 :] 1 STOR.C536" X 36“ T.T.G\1 / MD-103\ \35 12/6\I \ .1 % ;3- - w. \MIE.F.-5 ID 36/36^4/1 / MD-104Ll_6/6/STAIR i|.ts!NNHIGH IN ......IT TRUSS SPACE X ....^>t/........HWS 2 1/2“ 1/4"34 10/6 oS1 1 1/2"ISSUE:36“ X 36“ W.P.L. H ISB.D.HWRHWR PERMIT SUBMITTAL2}'Ji2 G/—-.STAGE74 (F.I.D. V.D. W COMMUNITYH ICONFERENCEPLATFORMW4ftIV.D.I |32,wYT"i'Y'n12”012“0 4428CUSTODIAN/-v£ V.D QCOOC-%STORAGE 8/6STORAGECM REGISTRATION:8"0T T\T~:cV.D.c/c0/0 .......... W/B.D. 33}FOYER15oc ,nrm j j 6"0 I I QXu \\6/1010/14 i—f01i W s Q/sy Q_ Cl.ZD •w’3 j |:FA V.D Ii-4-10/8V.D.u14" X 8" TSR. 300 CFM.. Tx;_/8/12 O«I\ff iOFFICE 210090f 0 12/14;f18" X 12” TSR. 400 CFM >-d em317?I F.I.D. (TYP.) I FFF18" X12" TSR CORRIDOR RAMP<x 10 30CD 29r<6■Cv!-iCM kS rtf-(M)CN|I p. (Bi i hi p t co 0 I R Q CO ISSUES: HP- 3_ yS- n Hp-2 —<S311 /TZWJ-12Z -v-F RRLOUNGE-NO DATE DESCRIPTION•S'6/6rn-n /6/6 04/29/2021 PERMIT SUBMITTALRECEPTION113i£D <70 i6/6 1 (»Lcj<F®PATIO !i co 1:08 2W/B.D. S A.!As F14 COL- •FF I AY)I1.2 KHP-1 I3312»0 p COBCM 12"0i Sj CO iCSJso.\M'—-r—F 16/20[H.P-3J111 CM ,T-T /fcf V.D.3v.d. .aCO\•V I1 - xyr—r 1'C !i 1 CM I14/8MAM)1--HA2 ~J\\ 14/16p.T™F-24/8 1!H 12/10 \vCMHf n;r'v.dff.oj i F 1/2 cj j(H -J-j-CM ! O’ •: $ CNli * X i CO / r 1!j LJ WORK r~iCM 12M0ii[t111■ B.D. ____07 u!__Ii o 4* — "-J1 CF A T"?; CM r; — -f* LrL R--^•“'Tri ' ii "7“ ? 12"071.F— 8/6 ' V.D F>rrrnA— COND.STORAGE 1! -A -AM*14/12A x.O r"3! /COCM121Q CD-ff:I CM 10/6 CMCO03L~iz 10/6 W/B_D. | V ........ft —M —— mmmm i.u----------------------; FA F ------\—IF------—COND -f; lFc.--.„^h.p.1! l__J r r i3/4" COND. TERMINATE 6” ABV FIN. GRADE i. 20/6E.F-4 I L. 1 __!fVAH \L !! 20/6j3-,.< 2/r1/2 :\X f 0J Ii;I 1 7t7\26ol.i QCD CO!?Oi I f, CM .1 xXff- CO1 i 8/14CM20/6 12/6i6/14 \ ; A ~ 010/12,: ri- SR ENGINEER:DLSFF_20/6 I F VD' Ty Ff/dF? VD 16/16-----^VD 6/12J12"0 1O"0oor^W%:-v —j DRAWN BY: AP/SA1O"0 9"0 y ■73 OFFICE\ \ -i/oxcaGiiForij V-s LHQC BY:---x v"UxUi06A BD12/12 :AFF \ CO j I CO I 48" X 56“ W.P.L.r*“rED SUPPLY I EF-3 Q IPRINCIPAL 204875-003JOB NO:■ 'VDCO 10/12131NURSE6/68/6 --1 CM CM t|03 04/29/2021ISSUED ON:04 BD U24/6 24/6U yif)V rri i SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL DEMO PLAN - AREA B Q6; .5 !321 I A C LEVEL 1 - MECHANICAL DEMO PLAN - AREA B1 EB 16’4‘ 8*SCALE: 1/8"=1’-0 11 0MD-102 Da%& SHEET NUMBER: MD-102BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:27 AM ■ ^tinstry Wife Of Your Building McKINSTRY Co, LLC MgDEMO KEYNOTES O 1. REMOVE EXISTING HEATING-ONLY FAN COIL UNIT AND CONTROLS. DEMO BACK ASSOCIATED DUCTWORK AS REQUIRED TO PROPERLY INSTALL NEW EQUIPMENT. 2. REMOVE EXISTING ZONE TEMPERATURE SENSOR. 3. REMOVE EXISTING OUTDOOR HEAT PUMP UNIT. 4. REMOVE EXISTING INDOOR BLOWER COIL UNITS. 5. DISCONNECT HEATING WATER PIPING. ForTh 7161591113 DEMO GENERAL NOTES SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 A. RECLAIM REFRIGERANT PER LOCAL REQUIREMENTS. B. PROPERLY DISPOSE OF ALL EQUIPMENT REMOVED FROM SERVICE. C. REMOVE ALL DISCONNECTED REFRIGERANT PIPING AND HANGERS.I www.mckinstry.com CLASSROOM PROJECT: 26/6—asgfI YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE CLASSROOM i!T'ry 82-to 3Dt--ir t y-Ac1O”0i BOYSA26/8 M -<py 0<s>HCM V.D. (TYPY to.OCD 2 12/12’ CM ’10/6I.1/ ^<2)CORR to K ff >81G_CLV O V.D. '!A 1*0 vj'f f rr^<TL <o<TCM IRISOoSO\~7jr.rrr\r 73CDCD 79CM04VO\ DI a. A fSasl*J A CUS1L. )i A o %Pi/CDI\\to , " —y 610A'7704~\P //O' fTYn x( D }16525 100th WaySE Yelm, WA 98597 2 TO7 CO2620 26/?^CO\\VDEF-6 c-\3 3 i'7/\si l ; E )\toA s aCLASSROOf/v.FC.-811\12 10a& \i.I 84 —<nr ST/7v-i CONSULTANTS:\0-0 3 to o\............1's'to.0-2 CLASSROOM--- 26,27j--------vM'COCMCP'W0 20/12 i\\Vo1 / MD-101 76a Q\20 *2\o<\QCDCC a,VD(lYP}1CMI ^ u 1O’0L0r4CDCDp>\-o 04 o r*Cto16M2 I I 23 6\1 / MD-102 1 X 5 N o h3 a hr j ;Ya 5i,\rtn r.t r- !03\ \o.LL.1212_ _c-j i...3 3Y1O"0 \tT-1\x<2 2C3co vco CD V D (TYP )CO a 27’204 20,20/-•canj- -f3l> .-to(X r*OVoLQ to-<to 1Q'0/V 1C)~*M 1IM iQh /i s1\t. 3 _i0 !■i CD CO CO?—^I /1 Y /COCO1 vr _ __ - CENTALaCTF/TES Q„X /s\CX)i/7Tl20/10 0320/12 2012tIv 1U Ks\QV"s fJ-Lld: 3 CO\3\G ^/V2>ita i i 20 10\\ISSUE:s2010 \_vt 04 1/1x \2)J'IT 04 /O I 34I I /N f CO CDx^\^<77/7i\PERMIT SUBMITTALo r?oI*I I -i-x-rryrrTYY vYrYv 20'10 vi1 X 5 XVsY ,,Us J XJ4X5/>\VD \w 1 r I N ANAfr a y'/CO (TYP)IICO -----tOs.;26'S~r f uTIj/v•/I V vMs i'“Lc iJJsV/J.X-A..L I ' '' I REGISTRATION:\/a”1\MS *Mt-----s>s %CD CD1 ]8 /A? q\ 04 04L'U - J classroom NlBI °? L B4 <? I I 7- T I ; I NB-20<6 IOs,1 CLASSROOMiCOCDt28/6 85 CMO CM75!Ii\1X5 1X5 I\i 1COCDIoI! /' X .CO//2:Xc «ra1/a>'3 (3>4/ xV 4;K i"Y^O/7V/^ 'SV, < * ff vx-xj.Lxi j. xx/28/8 a fit,/26 6LQ1/<>>v JL KITCHEN O/x-/x'^20106252IB.D.V7 CORR,B.D,Y ,/I~>IOO i 26'8\ \00 JA/a>vcxoI20,12 87 iCM I.1/ViMVBD—sa_ x 7 V.D. (TYP.) Xio ,L>1C;I-ac/ :J3 *b77 I1O“0 w a7"0a:.!rQA20'12 Vd 1, sI L - NQo'TA j____,CO X 03 P 'o18/18 24/18 118/14/X 1V.D. (TYP.)12"0—n 710 3 C7 1-n-<T/(-2 /2 ISSUES: CO I I 'VI7212“014/14 x \x (rcco3niniiniiiTj~'i_l—|18/10TlLU 18,10 I‘4 6/6 | ■ \DESCRIPTIONNO DATE \X -J 3,.TC»C\UCL 10/6■C5 X I \V>! \n a-IT VDBy- 5"0 PERMIT SUBMITTAL04/29/2021\x 1 I CO Vo\II I6'6 ^ IIITUTORIALi aI 8/14, -xr I CMCO \CMT L h'I-M-73 AiI\0 iCMI a r,I VvI CM \CLASSROOM(T>®3 I ~RTI 1 10" X 8 1/2" DRYER VENT L CM \I^-6“0i 6;6i 04 "•'cr 69iw >1O!!0I CD 1--------iiLIBRARYCO a 12"0ji 10,14lii^ 6'8CO aoCM \!42 ’ CM ITEST1 1C"0 r~F;14/14________i1 . t I V-O 0.\-*XM;x71OFFICEiX 10/12 ,i r /! I CO iiwIu A 04 \COYV-1X rrrrrYrrrtj CO U.U._XMAX-Vleer <<f V >1P / v * ., ,At8, 14 V41xz12"0 YS.a i \\ Y I12"0 I ,, ,/V >—V IV V-D V )I I/ A !!2 4 ! a 1 i t A /,\A /1 20/14o//I/v 7/o 24/24 I! i l/Ito.2 /\/Liil!II 16/12 I/!I W.P.L.fl.Ai V.D.(TYP.)iif A 30/24(}v77, 'Via “ v.................*1 rv~x.‘ 1—/! I V.DV x -4 4 L F.C.-12I73-to VI\l1a 703 6"01O”0 20/12 A '7 1 1/2'3R. VD : 18/12 l 1, ITT3 1 1/2’to liTfC"aurail v4/8 12"0 1 X 5LV>12/8 FC.-13 HWS I}Ax l5AV-s 1HWR 3L*I 2’fir <a» (t *\1 ic T.iLJ \ 24/1668/CORRIDOR 1 / M-105FC.-140012/16.20/12 F,ito..CM A^to]N... no..SR ENGINEER:\DLSTNij1NN•: !FT ~il it fj j DRAWN BY:AP/SA1 / M-104 QC BY:LH 204875-003JOB NO: ISSUED ON:04/29/2021 N 1 SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL DEMO PLAN - AREA CA A 1 C r LEVEL 1 - MECHANICAL DEMO PLAN - AREA C1 I EB 7SCALE: 1/8” =1-0 11MD-103 D16’0 4’8’O. %& SHEET NUMBER: T MD-103BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:28 AM instry fn.ife Of Your Building McKINSTRY Co, LLC DEMO KEYNOTES O Me1. REMOVE EXISTING HEATING-ONLY FAN COIL UNIT AND CONTROLS. DEMO BACK ASSOCIATED DUCTWORK AS REQUIRED TO PROPERLY INSTALL NEW EQUIPMENT. 2. REMOVE EXISTING ZONE TEMPERATURE SENSOR. 3. REMOVE EXISTING OUTDOOR HEAT PUMP UNIT. 4. REMOVE EXISTING INDOOR BLOWER COIL UNITS. 5. DISCONNECT HEATING WATER PIPING. ForTh DEMO GENERAL NOTES SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 A. RECLAIM REFRIGERANT PER LOCAL REQUIREMENTS. B. PROPERLY DISPOSE OF ALL EQUIPMENT REMOVED FROM SERVICE. C. REMOVE ALL DISCONNECTED REFRIGERANT PIPING AND HANGERS. www.mckinstry.com PROJECT: 1 / MD-103 1 / M-105 YELM COMMUNITY SCHOOLS FORT STEVENS ELEM - HVAC UPGRADE 1 / MD-102 [_ '\iIi/N -/i j:8/6 24/16tk nI, \ !24/18iuddii_________________ |K-j\12-632”M l:HWS J { i an3CYS 16/10 [I i2" X12“ UP TO ROOF MID C3C _Q \HWR iVD4Lx ah*)2 1-'2‘l2 1/2“fv—i84 ARTloCORRIDOR ■i V,a I CMJ ( 5 i 1 CD I CO 65CO43106CMnzfr CMII I Faclassrooml ’ 8"0 a COVD 4* 10-10 r©48;6 CO67CMX I•m 1 VTJSL 17 V/D ov>'--1 OUST.i IK CQJ20/10\>2 \im 2/8ZH i DTrr.i______.f 2 Fr n C'A "•"DIRTS'22voffTu L-^ <o' t VD Oi Si 0VD47 V DBD Tf VDJi ~ 6/6 _CONF.L__Xla—/OJ! FI a-IDiqp3xcccocDr v D B Lf 3 o CD63COji-A-5a;a io T!7iT“20/10 i Lo1I ^ k ! ICOcoACM- 6/6 MX\ - •m,.wH-t . . '“Iw p-a1 LNj45ii\.6"0 i XX LU I JBD7"0 o12/6 u_id66 IiCOCHAPTER1aa&26/6 L 6'iO BDO COI 16525 100th Way SE Yelm, WA 98597 i.CM «0 ■I!CO20-12 EF-7 CMr:k-hnX,I o illDRAFT STOP IN ATTIC. IoSTOR.C3 DIo 1VD(1X5:aCONFERENCEa CMornronasL amiDiimiica V.D (TYP.) 60 a i14/10 I_l_O’ -10" AIR CUSHION 46 )dx 1! CM I <o26/6 CORRQ 3!: \12"0 !20/10a-i__j o'oCD 1O“003 CONSULTANTS:'N.62 aT d'FTl ILMi q rH' L 2: r 11 i i26/8 Ii\ S VD (TYP)V I\l i>I 2 >I X.D 14'1220/12*5*2^ V—-24/6- A j V- R *v i\t* 6; 6Tf “in |i 2i IJ oH !Is |L\'if\ii Il\|| i !16/8.a \\26/8j \\t fI 1O”0 <I r ~tr-' 0350 CLASSROOM51I a is3®PRE-SCHOOL oGUSTa 26; 8COIoI I 57MS A59 %71I'ri ! II 11 \COO 411to - $V D {PiV D reCD ■M 6/6 \CM.12”0 a —V L ur~~s — I ^ 6/6 VV/? CLy i6/6 f 3 adVD8/6 'TXrv r~r63BDW/B D i !10/14/:EF-852 i £1\2i>1 1/4"r~i ! 1 f M! l %]( l! 1 JIi II ISSUE:T - pp3 i I ?! : i errfsrr -npcaXi/ara\\in'20-'12El/ !-QTrnyiT s0 ST/ILQr liua%)CQ r V D (TYP )'58 CENTRAL ACTIVITIES PERMIT SUBMITTALo26/6 • !i\tr * <r tF~l I2u_ l/£ 4 1 l:1 iiCM 1Q"<2> —V W : " io < fM/u_o CM f L 4 i v 1 « 5 i i !SCLASSROOVtCM O26/6 CM 5626/8I-3 REGISTRATION: H7 PM,!dL 1O"0 a>i \yt — 1f N '4KINDERGARTEN d|0/12j 16,12ti u ' a®?1O”053rCM* S I ^ IS H X/fTf)Xixk)u>B D /,-o .a.CO TIIr- |N Hy)!i XL o20/12 RA-si \20#1212/12 20/12 coV\co R V.D.(TYP.)I IN TRUSS SPACE (I -JML-CO -TTv!CMCMI26,8 auCD16/12 8.D. I CM I l >r1Q"0 •Ura tH fI) \ Lx yst;f2 2/o\CD3a 1O“0§.1 LdTTta?1130/24Y/1R 10" X 31/2" RESIDENTIAL £ RANGE HOOD EXHAUST DUCT ia.i1L_ .L j____\jCM!Tvrb" 'CMJCO L_iI k0 fI8"0 XI ISSUES:26/6OCDfiSCMCLASSROOM DESCRIPTIONNODATE 26/6 1O"0- 04/29/2021 PERMIT SUBMITTAL5521wa 0\XK1 \12/12 Lx1\CMi; \\od-a CM V.DYTYP.1 CM CO L_48"X 36"= h 8.D.; WPI 48" X 38 W.P.L 2 10" 0ija 26/8 H •~aSS®■ 1O”0 iBs*-XTfT 1\B a pOOOODODODDODDOQOa® V.D.(TYP.)CLASSROOM 26/6 54 1 X " “1fal\ 1 x 1 \i___ !; i SR ENGINEER:DLSIi DRAWN BY:AP/SA (17)14) 11512 QC BY:LH JOB NO: 204875-003 04/29/2021ISSUED ON: SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL DEMO PLAN - AREA DA C LEVEL 1 - MECHANICAL DEMO PLAN - AREA D1 EB SCALE: 1 /8” = 1 ’-0’MD-104 16*D0 4*8*a* SHEET NUMBER: MD-104BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:32 AM PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE N 6N 3N 2H 1 I XI\\ N Af t i 26/6 TS ; i___1Q"01O“0 16525 100th WaySE Yelm, WA 98597 i i igmmmm !f.I (N B)l.I28/6 j u.__ BDDCLASSROOM r ii\26/6iA\ CONSULTANTS:0 N 02 28/6j CM rci ii cai:—i-'ex..; F=4 \[ <=> I ' CM i Jl26/6 l Z~BDD n/i IX* - 1O"0 10"0I/VTf %I i”*! 1 ©*!lS]zi 1 , 28/6 / & /i.c!?10 01O”0 T .12/12.1O"0 1O”0 I3DD r1;t8z10/10 M ©C5! \ |a0i _i_ I-1O”01G"0In xV-'/12/12 1 3ft /a/i pX ;~CLASSROOM !/CM CLASSROOMzV0 I /* <3 /CD N 01 '4V43 i /i CMCM10'0 NOS/W4C yZN /ISSUE:/z\I—I z ZS Z N/zz .yxB-ir-i Z \XZ Z 0zX 3ACKDRAFT DPR(BDD)Zz//r~Z ZZ x z z40/36A Z //I X //z z PERMIT SUBMITTALZz1Iz-7Z'Z \XT -rf-z x xz Xz Xz , \\z X Xz X __ L_N0^*- , , „ t rP—I 'nizO’/i!”-I i! -0 ;i ! ft Y/1Lx//z X 7Xz [ftzYX F ]i Z -(~TTZ//• 1O‘'0 Z \ XX \//jXz11Xzz"z 20/12//!z XzX 28 8 / Xy20/12 ru12’0 FC-3A ig LOCI | X I fii^aunnirD 26-'6XirxIDYI|i Uf\fife®® ci! iFC-2A Tr ! I£-- 3 0®3«Iany}! FC-4A ; -4-fi 2012 jL 41/! 1.1:REGISTRATION:!(Ju jsr-“-r 1O“0\1''(t*-CLASSRQOMV CMxX.I 1 1 X 5 >|mm« j !5 I0 N 04—4■HHWSI I 12/12,1 Vo !1 / MD-103 /H'A/R nI,1X51 1/2"“MlI I"I 3 3 i1-4"\2"M—'fcti' FC-5A TXHTJ> \ 2 o20/12'8/12 w<IT |Tr\ i » 2:sM4411 / MD-104 FC-6A co=tif \i xN b=?u L- X3 0/i/1R I I Z»(Wg> 3||ft)I7-1 !aFT-201062514/12 ‘1 %Lririi(eL so- 36/36a30/28 ^4?x \\■iri Xow26 ;G10 0ii i 2i \\ 1O:,0Y V BDD\<xV T\N‘C \INJ 1IU _L_ a- !\'\ !%S \'\CENTRAL ACT.ir\ 0]i___Y •TTI20/12 i/\\ii!h5BDD fe=\n ISSUES:10-0 N 11 1 j___ NC\s {CM}\\ fv\1O*‘0 >it CM !t 26/8 DESCRIPTIONNO DATE Ms \\i <F> ' CM§\MsO \ \N 04/29/2021 PERMIT SUBMinALIrCM j’ iX > CORRIDOR:am! J\ 1O“01O"0 N 05s ,5T “ < \X sV GIRLST.12/12.\ 1 a 1 n h N 07=fr-'- 10/10BDD '...10/10 8/8I j!26/8 BOYSCLASSROOM 1O”0 12/10BDDBDD1O”0 NOS7'N 09CLASSROOM -iiiI ~V\I ....20/12 k- 10/6t___at 10/6 10/8N 10 'n i i ^ 1|12/1026/8l1 I 'i i\\7\\ 2LM12/12-E3 kli X■®—26/8 h—BDDI26/6 ND 1O”0 tj26/6! .1 ">CUSTODIANIkIr— r woccf N 08[\J 1 I\\ I \2J 14N HP 18“ X 10'i 26/6 WPL. (NE) vH k-\ !\ SR ENGINEER: DLS DRAWN BY: AP/SAIQC BY: LH JOB NO: 204875-003 04/29/2021ISSUED ON: SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL DEMO PLAN - AREA EA C LEVEL 1 - MECHANICAL DEMO PLAN - AREA E1 EB16’4*8'0SCALE: 1/8" = f-O11MD-105 D % SHEET NUMBER: MD-105 ' ^Mnstry 5Wife Of Your Building McKINSTRY Co, LLC DEMO KEYNOTES O Me1. REMOVE EXISTING HEATING-ONLY FAN COIL UNIT AND CONTROLS. DEMO BACK ASSOCIATED DUCTWORK AS REQUIRED TO PROPERLY INSTALL NEW EQUIPMENT. 2. REMOVE EXISTING ZONE TEMPERATURE SENSOR. 3. REMOVE EXISTING OUTDOOR HEAT PUMP UNIT. 4. REMOVE EXISTING INDOOR BLOWER COIL UNITS. 5. DISCONNECT HEATING WATER PIPING. ForTh DEMO GENERAL NOTES A. RECLAIM REFRIGERANT PER LOCAL REQUIREMENTS. B. PROPERLY DISPOSE OF ALL EQUIPMENT REMOVED FROM SERVICE. C. REMOVE ALL DISCONNECTED REFRIGERANT PIPING AND HANGERS. SEATTLE; 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 www.mckinstry.com BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:36 AM '^jiinstry *ife Of Your Building McKINSTRY Co, LLC MeKEYNOTES O 1. INSTALL NEW BLOWER COIL UNIT AND ASSOCIATED APPURTENANCES. INSTALL NEW RA, OA, AND SA DUCTWORK AS REQUIRED TO CONNECT UNIT TO EXISTING DUCTWORK SYSTEMS. INSTALL NEW CONDENSATE PIPING TO NEAREST DRAIN. SEE DETAIL 2/M-500 FOR PIPING. 2. INSTALL NEW TEMPERATURE SENSOR. REUSE EXISTING LOCATION OF DEMOED SENSOR. 3. INSTALL NEW OUTDOOR HEAT PUMP. SEE DETAIL 2/M-500 FOR REFRIGERANT PIPING UP EXTERIOR WALL. 4. INSTALL NEW BRANCH CONTROLLER UNIT AND ASSOCIATED APPURTENANCES. 5. INSTALL NEW MOTORIZED DAMPER AND ASSOCIATED APPURTENANCES. 6. INSTALL NEW DUCT MOUNTED HEATING WATER COIL AND ASSOCIATED APPURTENANCES IN SUPPLY DUCT. CONNECT TO EXISTING HOT WATER PIPING. SEE DETAIL 4/M-500. 7. SET NEW UNIT ON 1/2” THICK RUBBER PADS. MOVE HEATING WATER PIPING AS REQUIRED TO ALLOW FOR THE INSTALLATION OF THE NEWAHU’S. ForTh SEATTLE: 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 www.mckinstry.com PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE 16525 100th WaySE Yelm, WA 98597 CONSULTANTS: 761235 i 12/12 WOMEN 210 CFM210 CFM 10/8RCP-1 10/8 9 !14/14HALL:;3 0 EF-1 ISSUE: 80 CFM 10/8 MEN PERMIT SUBMITTAL10/8 250 CFM A €5 j EF-2 j• CUSTODIAN REGISTRATION:STORAGE /fr AaA I20 x 12 DSis ! 530 CFM (TYP. OF 6)12“ 0 co:2!12/16 TJ 4•«7s.AT* .O &@ i$Sst‘J°1062$2B12" 0 I O 16/16 AUX. GYMNASIUM 12” 0 ISSUES:C 18/18 NO DESCRIPTIONDATE 04/29/2021 PERMIT SUBMITTAL12“ 0 I20/20 ODU '9310 12” 0 : I IODUi12" 03e9\AHU-1I ID \ ODUr CCSly :8 01 ■ , 1E II3/4"32”V 32RUN PIPING UP EXTERIOR WALL AND THROUGH OVERHANG OF ROOF —i—- RUN CONDENSATE DRAIN PIPES DOWN EXTERIOR WALL A in ;HDR l3270 CFM \1 / M-103il SR ENGINEER:DLS J II- n DRAWN BY:AP/SAr2’x ipi i1 / M-102 QC BY: LH1800 CFM II JOB NO: ISSUED ON: 204875-003 04/29/2021 SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL PLAN - AREA A/lcD LEVEL 1 - MECHANICAL PLAN - AREA A1 EB SCALE: 1/8" = 1-0'M-101 4'8*16*0 D'Ua% O' SHEET NUMBER: M-101BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:18AM ' ^tinstry *ife Of Your Building McKINSTRY Co, LLC 6z i MeKEYNOTES O16” X 12”1 / M-101 FF 1. INSTALL NEW BLOWER COIL UNIT AND ASSOCIATED APPURTENANCES. INSTALL NEW RA, OA, AND SA DUCTWORK AS REQUIRED TO CONNECT UNIT TO EXISTING DUCTWORK SYSTEMS. INSTALL NEW CONDENSATE PIPING TO NEAREST DRAIN. SEE DETAIL 2/M-500 FOR PIPING . 2. INSTALL NEW TEMPERATURE SENSOR. REUSE EXISTING LOCATION OF DEMOED SENSOR. 3. INSTALL NEW OUTDOOR HEAT PUMP. SEE DETAIL 2/M-500 FOR REFRIGERANT PIPING UP EXTERIOR WALL. 4. INSTALL NEW BRANCH CONTROLLER UNIT AND ASSOCIATED APPURTENANCES. 5. INSTALL NEW MOTORIZED DAMPER AND ASSOCIATED APPURTENANCES. 6. INSTALL NEW DUCT MOUNTED HEATING WATER COIL AND ASSOCIATED APPURTENANCES IN SUPPLY DUCT. CONNECT TO EXISTING HOT WATER PIPING. SEE DETAIL 4/M-500. 7. SET NEW UNIT ON 1/2” THICK RUBBER PADS. MOVE HEATING WATER PIPING AS REQUIRED TO ALLOW FOR THE INSTALLATION OFTHENEWAHU’S. 'I For TilB.D.QTHPA O l ©I 43” X 32" T.T.6. MT, BTM, @ 18' A.F.F. t OVER DOOR 43" X 32” W.P L.2!ISTORAGE: 12/8 CO I CO 24 Lp-VD y 44" X 30” T.S.R, 2500 CFtV! MT. BTM. § 18-0" A.F.F. SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 i RUN ABU-02 CONDENSATE LINE UNDER BC-2 AND AHU-01 LINES - 8/6 CD f CM O : CO V "I G( G i 20" X 8” T.T.G. AHU i V7081M. @ W-Q" A.F.F.www.mckinstry.com02 STORAGE PROJECT:23 34" DN, TO RG. & FLR OFFICE 22’VA II YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE GYMNASIUM 27Q_ i -26/622CMl; - 36/6 | L;O jCM CM CQCDCM CMX co ■h 44" X 30" T.S.R. 2500 CFtvl. WOMENICO!; CD 5 i - ii j jiJMT. BTM. @ 18’-0" -A.F.FI ILQ! • - E.F.-1E.F-2 5 V.D.19/19 r V.D. i:O I6/6 MECHANICALB.D.10/6 14/12 V.D.B.D.0 n 20/12 ■f <■39CO 16-X16" ^^ 30/24 CMIDMOFFICEB.D.12/6CDBC-2 < 2BC MEN I12/1019( 1 CO ©L02 o40" X 30" T.S.R. 2000 CFM 37ID©!:-I©I I 10/6MT. STM. @ 18'-0" A.F.F,-! 2 AHU-02 F.i.D 16525 100th Way SE Yelm, WA 98597 i —*3 ftKITCHENI RUN AHU-01 CONDENSATE LINE § ; UNDER BC-2 LINE I #V.D.i CO18 CM 12/8COIrCM11/4'I V.D.® CD I✓CM STORAGEI CONSULTANTS:AHU STORAGE718/10 4001ti1'20 o 6/6IA©2'y*CD M-CM *18" X 18" EXH. UP TO (l}AHU"°1CO \_^Q 03ROOF E.F-10 CO V.D.X ocCOCORRIDORCM Icr co <10/6CM ,<O IcXcoil 40" X 30" T.S.R. - MT. BTM. @ 18f~Q" A.F FCQCM X 36' co < : i O 22" X 26” DN TO R.G. @ FLR. V.D.I : j 2000 CFMi co © I8/6 STOR.o36" X 36“ T.T.G. MT. BTfvt. 17'-0“ A.F.F.I 35 1 / M-10312/6 3'I M :IB.D. ^E.F.-5 QX - 36/36 1 / M-1046/6ISTAIR N( N RUN HIGH IN TRUSS SPACE - 2 1/2” • 1/4*34I 10:6 1 1/2”■ISSUE:36" X 36“ W.P.L. HfSHWSIB.D.HWRBWR PERMIT SUBMITTAL2>BC-1(t), 2I RUNJIGH AS POSSIBLEGSTAGEF.i.D. V.DI COMMUNITY ICONFERENCEPLATFORM.4vAn 3212"0 12"0 4423CUSTODIAN/QCOSTORAGE 8/6STORAGECM REGISTRATION:8”0orV.D.o/o33 FOYER15cC 10/16/10W/B.D.10/14 x ox?- m 01 6!,0©Q Q_ A!!a. Z3 V.D.IV.D 10/8 T18'12° TSR.V 8” TSR,14”V OaA8/12 r CO ss400 CFM OFFICE 300 CFM©t 0(o)12/14 4IU-§T4 an31 (92^06252F.I.D. YTYP.) i ; '18° X 12" TSR _ [ BCU I £ 01 I CORRIDOR RAMPROUTE UP ALONG EXTERIOR WALL THROUGH ROOF OVERHANG-------- ------i I S- ‘0-A*3010O 2945CD<5jt.i CMCM £ Lg09MCNl I1 IU ss pVpnCO O OSET NEW UNIT ON EXISTING CONCRETE PAD a 6/6v.d. mV.D.ISSUES:|H y 12/12 R NO DATE DESCRIPTIONRBCLOUNGE |||p-= 5-fH ,|i 04/29/2021 PERMIT SUBMITTAL01RECEPTION11COPATIO53 08' \2j BC-25© 2 COODU12“0 O CD ICM3CD _ CM■; CM “01 12”0 SS16/20-o ^V.D.V.D.tc—U—u CN 8/4 14/1624/8 12/10 /g O •V.D..T a; ' qCNJCn;WORK -4 BCx04 12"0> B.D 1CO 243/4" CNDS 07I I4 STORAGE 6/6 ” V.D. -0 14/12 12"0 CO125aCD BC10/6 CNCQ10/6 W/B.D.1 233/4" COND. TERMINATE 6' ABV, FIN. GRADE............. 20/6.•es5-!E.F-4 BC-2455VT 20/62Q I0 BC-23 i ljCQ; V3/4” CNDS - 60L.Qco ““ 23 gO CQ8/14 CMCM 20/6 '12/66/14 5-FT 4 .5 10/12 SR ENGINEER:DLS20/6 V.D.i16/16 V, DI­VA V.D.:...6/12 .. OFFICE 12“01O"0 X DRAWN BY:AP/SA1O"0 9"0 »■i4 QC BY:LH•x 06B.D,12/12...’48" X 56" W.P.L,ED. SUPPLY a IEF-3 CO PRINCIPAL 204875-003JOB NO:> : I V.D.COco CO 10/1213 NURSE6/6CMCM 03 04/29/2021ISSUED ON: 04«-B.D,U24/6--»f- 24/6U VV SHEET TITLE:KEYPLAN'05 LEVEL 1 - MECHANICAL PLAN - AREA B 61 ; (2 1 3 I A C J 1 LEVEL 1 - MECHANICAL PLAN - AREA B1 EBI SCALE: 1/8” = 1-0’M-102 V D16’8'0 %& B SHEET NUMBER: M-102BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:20 AM ' **tinstry *ife Of Your Building McKINSTRY Co, LLC KEYNOTES O Me1. INSTALL NEW BLOWER COIL UNIT AND ASSOCIATED APPURTENANCES. INSTALL NEW RA, OA, AND SA DUCTWORK AS REQUIRED TO CONNECT UNIT TO EXISTING DUCTWORK SYSTEMS. INSTALL NEW CONDENSATE PIPING TO NEAREST DRAIN. SEE DETAIL 2/M-500 FOR PIPING . 2. INSTALL NEW TEMPERATURE SENSOR. REUSE EXISTING LOCATION OF DEMOED SENSOR. 3. INSTALL NEW OUTDOOR HEAT PUMP. SEE DETAIL 2/M-500 FOR REFRIGERANT PIPING UP EXTERIOR WALL. 4. INSTALL NEW BRANCH CONTROLLER UNIT AND ASSOCIATED APPURTENANCES. 5. INSTALL NEW MOTORIZED DAMPER AND ASSOCIATED APPURTENANCES. 6. INSTALL NEW DUCT MOUNTED HEATING WATER COIL AND ASSOCIATED APPURTENANCES IN SUPPLY DUCT. CONNECT TO EXISTING HOT WATER PIPING. SEE DETAIL 4/M-500. 7. SET NEW UNIT ON 1/2” THICK RUBBER PADS. MOVE HEATING WATER PIPING AS REQUIRED TO ALLOW FOR THE INSTALLATION OF THENEWAHU’S. ForTh 1715 16111 )139 . SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223ODU I/T 32j www.mckinstry.com! a .4■UUlVl PROJECT:i Q\ YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE ;Sbi m\U! >4 i C 1O"0 BOYS£<ji 80 iS$CM Oi CNi 10/6Af CORR. BC-04 < 2 ) —i .X81/T\10/8V.D.I t )V___7 8"0 o o/2d) BC-03 CM GIRLS C_79CM V.D.V.D.Ol!(—3/4" CNDS V OUST.oBC cd 1 Xq) .......................■ ■=* 8/10 77CM ■O X03CMD 16525 100th WaySE Yelm, WA 98597 N BCU :A ■r CNDS-CO CO< 4 V.D.E.F.-6 CO02*f u/Z‘RUN CONDENSATE DRAIN LINE DOWN TO MOP SINK--------D.E O ICLA('('DA/' »o oKU»/•..J 12/10 ■'X 84 V CONSULTANTS:5O CM 3/4" CNDS CLASSROOM- 26/24CO1O"0 20/12CM 76®2(>i I' On® VD(TYP.)1O"0BC£Q-1 • ^1 X 616/12 04 26/6VO CM ODU"D 3~\* CM 20/16v 12/12BC II <\ j 1O“0 26/81 X 6to[I 05 V.D.(TYP.)j XVCO20/12 7 - j central ACTivro 7CM20/20 c\ V Q ^3QQ H 1olof ?CQ ffl-i-.............10/14% CD CM 1 1/4 CO®20/10 V CM(2J/BC-O6Q 20/12I 20/12 o HQ BCU CD ?G TT)\©Xwf03 20/10 ISSUE:20/10 7 f I ©BC-p7<2)I BC BCH1 X 6 2 >BC-09(t1X6;ILL-PERMIT SUBMITTALODU0607!20/10 iA 47$i 0)tV.D.I NAiNA'-CMS.CO i ()« (TYP.)CO dShEDDCM 26/8iT5 REGISTRATION:5 5$Si 20/12CDCD ff A'i* CLASSROOMCM 'NlB<NB20/6IakSSROOMCO85BCr28/6 1 X 6 CM 0 i75OTP08CD CD OEX)1 CDBC co Z«r 09 7*earnx&XK 28/8 26/6-**33 KITCHENB.D.CORR.B.D.CO 26/874COffCO20/12 87CM B.D.x V.D. (TYP.)I1O!,0 7”020/12 ooCC ©)BC-12 (©)CO 18/18 CQ24/1818/14x x ^ 1LV.D. (TYP.)12“0BC-11 \ 2 B ISSUES:|CO 24/18 72T12"014/14x ®LU 18/10 6/6 NO DESCRIPTIONDATE x —1 o a-10/6 04/29/2021 PERMIT SUBMITTALV.D.x *4oBCU 5"0c6/6WB4 8/1404CO CM I-AT OTUTORIALCM CMBC CLASSROOMCDCM CM 10" X 8 1/2" DRYER VENT 1X6 6/6■a 6"07310vi-CO 69V5. 1O"0LIBRARY cX 12“00/14CO 42 CM TESTCM 14/141Q“0 ts»~ 20/1471OFFICE10/12 CO 8/14CMCO<741 -512"0 %CO IBCH-12"0 - 20/14 1 x 624/24 >'!12 16/12-0 W.P.L.<xrirD*30/24 V.D.(TYP,)I DBCV.D.1 x 6L13BC-13 < 2 16/12 BC70V1©20/12 1 / M-1051 1/2'7^ Jkf 14 I 1 1/2'V.D.BC3/4" CNDS12/8 ft14/8 1 X 6 WNS18/12 -CA[|OR FUTURE exfInsiqn.11©BC-IO©THWR £/ 2’•12"0' R8 ^CORRIDOR12"24/16.12/16:20/12 -vj-1 / M-104 N i1"SR ENGINEER:DSN V DRAWN BY:SACONT. TO CUSTODIAN 47 ON SHEET M-104.QCBY: LH JOB NO:204875-003 04/29/2021ISSUED ON: (N 1) SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL PLAN - AREA CLEVEL 1 - MECHANICAL PLAN - AREA C1 A 1SCALE: 1/8" = 1'-0'8' 16'4'0M-103 c 'U %& EB D SHEET NUMBER: M-103BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:21 AM KEYNOTES O ' **Mnstry S/fe Of Your Building McKINSTRY Co, LLC 1. INSTALL NEW BLOWER COIL UNIT AND ASSOCIATED APPURTENANCES, INSTALL NEW RA, Ok, AND SA DUCTWORK AS REQUIRED TO CONNECT UNIT TO EXISTING DUCTWORK SYSTEMS. INSTALL NEW CONDENSATE PIPING TO NEAREST DRAIN, SEE DETAIL 2/M-500 FOR PIPING , 2. INSTALL NEW TEMPERATURE SENSOR, REUSE EXISTING LOCATION OF DEMOED SENSOR. 3. INSTALL NEW OUTDOOR HEAT PUMP, SEE DETAIL 2/M-500 FOR REFRIGERANT PIPING UP EXTERIOR WALL. 4. INSTALL NEW BRANCH CONTROLLER UNIT AND ASSOCIATED APPURTENANCES. 5. INSTALL NEW MOTORIZED DAMPER AND ASSOCIATED APPURTENANCES. 6. INSTALL NEW DUCT MOUNTED HEATING WATER COIL AND ASSOCIATED APPURTENANCES IN SUPPLY DUCT. CONNECT TO EXISTING HOT WATER PIPING, SEE DETAIL 4/M-500. 7. SET NEW UNIT ON 1/2” THICK RUBBER PADS. MOVE HEATING WATER PIPING AS REQUIRED TO ALLOW FOR THE INSTALLATION OF THENEWAHU’S. Me ForTh SEATTLE; 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 www.mckinstry.com CONDENSATE DRAIN LINE CONT. ON SHEET M-103. PROJECT: 1 / M-103 1 / M-105 YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE 1 / M-102 LLL^IIN 4®-8/6 24/16M24/1612/16.;;; BOYS HWS 16/1012" X 12" UP TO ROOF MTD, HWR V.D, M'" 21/2" :0 M64ART CMCORRIDOREF.-9RUN CONDENSATE DRAIN PIPING DOWN TO MOP SINK --------- O04i65COCMfCNDSi> 10/6432^iCD104\ICLASSROOMI:H-~ 8"05 COV.D. 10/10 CO8/6 CO670404\-"e-■ 1 1/2"o i8/6 CUST.v/d;0320/109 12/s:t ¥', fi- if "GIRLSV.D.V.D.fiV 2 > BC-14 s471 V.D.B.D.V.D,R V.D,Y® 6/6CONF.04#©®LOo’:J 63CO CO8/10 20/10 :i COCOV.; ■ % 0445V.D.ro i6”0 B.D.T0 12/6 BC 664i1* 0 0 IICHAPTERS! 1 X6 i26/6 H«..6/1015 B.D.j CO 16525 100th Way SE Yelm, WA 98597\/ 0 -1 sO CO20/12 E.F.-7 04 OCO ( BCDRAFT STOP IN ATTIC....- CO /o■V.D.-------1" CNDS-104CONFERENCECNI STOR.14/10 O'-10" AIR ' CUSHION 46 I26/6 CORR.Q V.D. (TYP.)6012”0 20/103/4" CNDS g/6 Vm 1O“0 CONSULTANTS:62 0} ShBL-/t Q26/8 II>0 BC-15 <(©) ©4 VD.(TYP.)% L=BC-18 \ BCU j 4 \14/12.1 20/120: BC-17 (2)©24/6r*eIRW1 16/8|26/8 I 1O"0o5 > ° /4CQ50 CLASSROOM51IPRE-SCHOOL o QCUST..04 26/803 II|Ty-5/49S 59JC1 X 6©Ao0HLJCNIV.D.V.D.6/6 12“0 n i -16BC©18H*~6/6 W/ : B.D. T 6/6"V.D.8/6 ©n5W/B.D.110/14E.F.-852 1jk 1 1/4’CO J io>iI ISSUE:CM b.d.;520/12 BmQ©CQ '•V.D.(TYP.)58; I CENTRAL ACTIVITIES PERMIT SUBMITTAL26/6CNi4 BC:i X 6Ik 19 1O”0S7 ODUi0CLASSROOMI0405O 26/6 5 CM BC dXD 5626/8 I II REGISTRATION:n h 20 I ro-i1O"0 V $I lKINDERGARTEN 20/12 16/12 f.I IT53BCCM0®-..1O"0CM 21 0B.D 1 X 6 O20/12 R.A,s.12/12 25 09Ml ,COI.CO V.D.(TYP.)040426/8 20/12;©- <0U 16/12: "B.D. 1O"0 1O”0-.ygfc-f2 > BC-22I I _ 30/2410” X 3 1/2" RESIDENTIAL RANGE HOOD EXHAUST DUCT....-..... lCM&.IBCU% CMCO406 406"0 xI ISSUES:26/6OCLASSROOMo\\0BC-21(2CMa NO DATE DESCRIPTION 5526/6 1O"0 -4 04/29/2021 PERMIT SUBMITTAL & 12/12 CM O CM V.DiTYPT 48“ X 36" 0A/PI CM CO B.D. 1O"048’V 36"A 26/8W.P.L.\I1O”0—«s- ; CLASSROOM 26/6 V.D.fTYP.) 54 ! X 1ODU /©206} i SR ENGINEER:DLS AP/SADRAWN BY: 1715: 12 j QCBY: LH JOB NO: 204875-003 04/29/2021ISSUED ON: SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL PLAN - AREA DA C r LEVEL 1 - MECHANICAL PLAN - AREA D1 0 -UB SCALE: 1/8" = T-0'M-104 16'4’ 8'0 % O'SHEET NUMBER: M-104BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:22 AM PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE N 8)N 3N 2N 1 KEYNOTES Oi 1. INSTALL NEW BLOWER COIL UNIT AND ASSOCIATED APPURTENANCES. INSTALL NEW RA, OA, AND SA DUCTWORK AS REQUIRED TO CONNECT UNIT TO EXISTING DUCTWORK SYSTEMS. INSTALL NEW CONDENSATE PIPING TO NEAREST DRAIN. SEE DETAIL 2/M-500 FOR PIPING. 2. INSTALL NEW TEMPERATURE SENSOR. REUSE EXISTING LOCATION OF DEMOED SENSOR. 3. INSTALL NEW OUTDOOR HEAT PUMP. SEE DETAIL 2/M-500 FOR REFRIGERANT PIPING UP EXTERIOR WALL. 4. INSTALL NEW BRANCH CONTROLLER UNIT AND ASSOCIATED APPURTENANCES. 5. INSTALL NEW MOTORIZED DAMPER AND ASSOCIATED APPURTENANCES. 6. INSTALL NEW DUCT MOUNTED HEATING WATER COIL AND ASSOCIATED APPURTENANCES IN SUPPLY DUCT. CONNECT TO EXISTING HOT WATER PIPING. SEE DETAIL 4/M-500. 7. SET NEW UNIT ON 1/2” THICK RUBBER PADS. MOVE HEATING WATER PIPING AS REQUIRED TO ALLOW FOR THE INSTALLATION OFTHENEWAHU’S. I NA 26/8 1O"010" 0 16525 100th WaySE Yelm, WA 98597IN 8 28/6 8DDCLASSROOM 26/6 N 02 CONSULTANTS:; o CM O CM26/6 BDD * 1O’0 1O"0I2 ) BC-27 ©I j28/6 D'01O“0 : 12/12 ! RUN PIPING UP EXTERIOR WALL AND THROUGH .....10*0 OVERHANG OF ROOF----- -1O"0 1O”0 BDDA 10/10 0 8C-28 0 \/ n :1O"0:I n ODUvV'f-----12/12'311BC-26 < 2 l V / CLASSROOM 0/ ©CM Ci ASSROOM fIQON 01CM CM1O”0 ODUN 03 340/40l CO CO jEo: Q^Q-cl 12 ISSUE:i BACKDRAFT DPR(BDD).... wco2j CCOH CCn.n ??!40/36 V*. RUN SLOPED CONDENSATE LINES UNDER CATWALK PERMIT SUBMITTAL1IT20/12 isf? fW020/12-' z-4 JBCIAfi/T1BC5 28/8271BCBCU 26/6 '28 I1X64 <?26 fi~8./14 M11-\l 2*\REGISTRATION: 1O"0BC CLASSROOM1CM AT Jnf I o CM N 04I _HWS ...-12/121 / M-103 3/4" CNDSHV'/R “I r—‘20/12—1 --------------------X MD '0 .....^i2/i? .I "Ip ► > "1 1/4” ' 1 3/4" CNDS'f F) BC-29 <T>2’>rf O20/12-cr 218/12 co1 / M-104 i N -7?/20/12 /12”0 0.001^252BC© t -------rmr L 14/12BC(lXD-I 36/36 $OA/gO32'‘6 30UBCdXZ>y /26/61O”0311O”0 BDDBC-30 < 2 zv/-c /\BCU kr CNDSCENTRAL ACT12 F20/12 7BDD1O”0 ISSUES:N 11 NCCM10” 0 26/8 DESCRIPTIONCMNODATEO CMCD PERMIT SUBMITTAL04/29/2021CMCORRIDOR8/8 @ 1O”01O”0 N 05GIRLS12/12 :/N 0710/10 VBDD 10/10 26/8 BOYSCLASSROOM■&AW0■IP 12/10BDDBDD10” 0-jt**CLASSROOMI 20/12 j*r" 10/610/810/6N 10~«zg- 26/8 12/10 <T> BC-32 ©©.BC-31-- RUN CONDENSATE DRAIN PIPING ! DOWN TO MOP SINK 12/12:7-'26/8 BDD u.26/6 ND 1O”0 CUSTODIAN%I r 18” X 10” 26/6 WPL.NE SR ENGINEER:DLS DRAWN BY: AP/SAIQC BY:LH 204875-003JOB NO.- ISSUED ON:04/29/2021 SHEET TITLE:KEYPLAN LEVEL 1 - MECHANICAL PLAN - AREA EA C LEVEL 1 - MECHANICAL PLAN - AREA E1 EB'kSCALE: 1/8" = T-0‘M-105 Q D16'4'8'0 %* SHEET NUMBER: M-105 ™ijjnshy */fe Of Your Building McKINSTRY Co, LLC Mg ForTli SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 www.mckinstry.com BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:24 AM ^Sinstry ifc Of Your Building McKINSTRY Co, LLC PRIMER/VENT CONC. OR MASONRY WALLa Mg <7 u A /4 <7 4 <fA £4 /<7 “00°REMOVABLE CAP 3/8" DiA. x 2" LONG GALV. BOLTS & EXPANSION SHIELDS AT 24" O.C.6'ForThPLAN SIZE AS SCHEDULED18 GAUGE GALVANIZED STEEL WITH PAINT GRIP, \ 1/87FT SLOPE\OO 4/ /H SEATTLE; 5005 3RD AVENUES PO BOX 24567 SEATTLE, WA 98124 1-800-669-6223 r o o /X r AIR GAP PER PLUMBING CODE:www.mckinstry.com1-INCH MIN ORo o AHU 4 2X PIPE DIAMETER PROJECT: YELM COMMUNITY SCHOOLS - FORT STEVENS ELEM - HVAC UPGRADE P-TRAP INDIRECT CONN. TO WASTE WALL ELEVATION BLOW THRU FANS: H = 1/2” NOTE:X = FAN DISCHARGE PRESSURE, DIMENSION OF PIPING ENCLOSURE TO BE 2 INCHES WIDER AND 11NCH DEEPER THAN THE PIPING BEING COVERED. EXTEND ENCLOSURE TO A POINT ABOVE WALL PENETRATION AND COVER END OF ENCLOSURE AND SEAL THE JOINT. PROVIDE AN INSECT SCREEN AT THE BOTTOM OF THE ENCLOSURE FITTED AROUND THE PIPING. 1. DRAW THRU FANS: H = FAN INLET PRESSURE + 1-INCH X = FAN INLET PRESSURE 2. CONDENSATE TRAP DETAILPIPE GUARD DETAIL NEW 12 SCALE: NTSSCALE: NTS 16525 100th WaySE Yelm, WA 98597 CONSULTANTS: DISPOSABLE FLAT FILTER SECTION BLOWER COIL UNIT RETURN PLENUM ALL-THREAD SUPPORT FLEXIBLE CONNECTORBALL VALVE ISOLATION ISSUE:3-WAY VALVE SUPPLY PLENUM fSmm PERMIT SUBMITTALmmUNION WITH VENT AND TEST PORT ►x« STAINLESS STEEL BRAIDED EPDC COIL HOSE (TYP 2) WITH MALE THREAD END AND SWIVEL UNION (NO GASKET) RETURN /REGISTRATION: OPTION TO USE FLEX TO BOXRUBBER & SPRING VIBRATION ISOLATIONCOIL CONDENSATE DRAIN TO APPROVED DISCHARGE LOCATION------------- SUPPLY 3VZ.oSEE PLAN FOR CONTINUATION oo Z 7?PIPED BYPASS FLEXIBLE DUCT rSF f^>20106252 DIFFUSER BOOT COMBINATION ISOUTION VALVE/STRAINER/TEST PORTS NOTE:ISSUES:3-WAY BYPASS DATE DESCRIPTIONNO3-WAY CONTROL VALVE BY EITHER CONTROLS CONTRACTOR OR BY HOSE-KIT VENDOR. HEATING WATER COIL KITS ARE NOT INSULATED. NO VALVE HANDLE OR TEST PORT EXTENSIONS REQUIRED. COIL KITS TO HAVE EXTENDED VALVE HANDLES, EXTENDED TEST PORTS. VALVE KITS TO BE TAGGED BY MFR FOR VALVE NUMBER, GPM, CV, 1.04/29/2021 PERMIT SUBMITTAL2. 3. 4. BLOWER COIL (BC) DETAILHYDRONIC HEATING COIL 34 SCALE: NTSSCALE: NTS SR ENGINEER:DLS AP/SADRAWN BY: LHQC BY: JOB NO:204875-003 04/29/2021ISSUED ON: SHEET TITLE: MECHANICAL DETAILS SHEET NUMBER: M-500BIM 360://Yelm Schools - Fort Stevens Elementary/YSD-FSES-MCK-ENGR-MECH.rvt4/28/2021 11:57:24 AM McKINSTRY Co, LLC NOT FOR CONSTRUCTION CHECKED: DRAWN: JOB NO: DESIGNED: SHEET TITLE: SHEET NUMBER: REGISTRATION: PROJECT: CONSULTANTS: SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98134 1-800-669-6223 www.mckinstry.com ISSUES: NO DATE DESCRIPTION 202250-001 22150 NE 156TH PLACE WOODINVILLE, WA 98077 NORTHSHORE SCHOOL DISTRICT EAST RIDGE ELEMENTARY SCHOOL PH. 19 ENGINEERING MMR MMR JWG SYMBOLS, GENERAL NOTES AND CONNECTION DETAILS S-001 MISCELLANEOUS SYMBOLS GENERAL NOTES THE GENERAL NOTES SUPPLEMENT THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS. IF A CONFLICT IS NOTED, CONTACT THE ENGINEER PRIOR TO CONSTRUCTION. REFERENCE TO CODES, RULES, REGULATIONS, STANDARDS, OR REQUIREMENTS OF REGULATORY AGENCIES IS TO THE LATEST PRINTED EDITION OF EACH IN EFFECT AT THE DATE OF SUBMISSION. CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND FOR CHECKING DIMENSIONS. NOTIFY THE OWNER OF ANY DISCREPANCY AND RESOLVE CONFLICTS PRIOR TO CONSTRUCTION. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED, BUT ARE OF SIMILAR CHARACTER AS DETAILS INDICTED, USE SIMILAR DETAIL OF CONSTRUCTION, SUBJECT TO REVIEW BY THE ENGINEER OF RECORD. THE DRAWINGS INDICATE THE STRUCTURE IN ITS FINAL CONDITION. THE CONTRACTOR IS TO PROVIDE MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES INCLUDE, BUT MAY NOT LIMITED TO: BRACING, SHORING AND SEQUENCING TO MAINTAIN STABILITY DURING CONSTRUCTION. INFORMATION SHOWN ON THE DRAWINGS RELATED TO EXISTING CONDITIONS REPRESENT THE PRESENT KNOWLEDGE BUT WITHOUT CERTAINTY OF ACCURACY. CONTRACTOR IS TO REPORT ANY DISCREPANCY TO THE OWNER AND ENGINEER OF RECORD. CONTRACTOR SHALL NOT DEVIATE FROM THE CONTRACT DOCUMENTS WITHOUT WRITTEN DIRECTION FROM THE ENGINEER. THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EQUIPMENT, SUPPORTS, AND SEISMIC RESTRAINTS PRIOR TO FABRICATION. IDENTIFICATION OF EXISTING UTILITIES THAT INTERFERE WITH EQUIPMENT INSTALLATION IS ALSO THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR TO NOTIFY THE ENGINEER IF FIELD CONDITIONS RESTRICT THE INSTALLATION OF COMPONENTS OR RESTRAINTS SHOWN ON THE DRAWINGS. DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED, AND IN A MANNER SUITABLE TO, THE WORK SEQUENCES. EXISTING REINFORCING SHALL BE SAVED WHERE, AND AS NOTED, IN THE DRAWINGS. DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE. CONTRACTOR SHALL LIMIT CONSTRUCTION LOADING, INCLUDING DEMOLITION DEBRIS, TO 40 PSF ON EXISTING FLOOR SYSTEMS AND 25 PSF AT ROOF. SAW -CUTTING/CORE-DRILLING: SUBMIT ALL SAW -CUT LOCATIONS TO ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION. CONTRACTOR TO IMAGE WALL, LOCATE EXISTING REINFORCING, AND SUBMIT TO ENGINEER PRIOR TO SAW -CUT OR CORE. CONTRACTOR TO SHIFT PROPOSED OPENING AND/OR CORE DRILL LOCATION TO MINIMIZE CUTTING EXISTING REINFORCING. ALL NEW OPENINGS THROUGH EXISTING MASONRY WALLS, CONCRETE WALLS, SLABS, AND BEAMS SHALL BE SAW -CUT NEAT AND CLEAN; NO OVERCUTTING AS OPENING CORNER LOCATIONS IS ALLOWED. AS REQUIRED, CORE DRILL CORNER AND CHIP, GRIND, OR CUT THE CORNERS TO PROVIDE THE MINIMUM REQUIRED DIMENSIONS. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND COORDINATE OPENINGS WITH EXISTING STRUCTURE PRIOR TO CUTTING/CORING. SUBMITTALS SUBMITTALS FOR REVIEW: SUBMITTALS OF SHOP DRAWINGS, PRODUCT DATA, AND MILL TESTING ARE REQUIRED FOR ITEMS NOTED IN THE INDIVIDUAL MATERIALS SECTION AND FOR BIDDER DESIGNED ELEMENTS. SUBMITTAL REVIEW PERIOD: SUBMITTALS ARE TO BE MADE IN TIME TO PROVIDE A MINIMUM OF TW O WEEKS FOR REVIEW BY THE ARCHITECT/ENGINEER PRIOR TO THE ONSET OF FABRICATION. GENERAL CONTRACTOR’S PRIOR REVIEW: PRIOR TO SUBMISSION TO THE ARCHITECT/ENGINEER, THE CONTRACTOR MUST REVIEW THE SUBMITTAL FOR COMPLETENESS. DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE SEOR; THEREFORE, THEY MUST BE REVIEWED BY THE GENERAL CONTRACTOR. CONTRACTOR MUST PROVIDE ANY NECESSARY DIMENSIONAL DETAILS REQUESTED BY THE DETAILER AND PROVIDE THE CONTRACTOR’S REVIEW STAMP AND SIGNATURE BEFORE FORWARDING TO THE ARCHITECT/ENGINEER. SHOP DRAWING REVIEW: ONCE THE CONTRACTOR HAS COMPLETED THEIR REVIEW, THE EOR WILL REVIEW THE SUBMITTAL FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT AND THE CONTRACT DOCUMENTS OF THE BUILDING, AND WILL STAMP THE SUBMITTAL ACCORDINGLY. MARKINGS OR COMMENTS ARE NOT TO BE CONSTRUED AS RELIEVING THE CONTRACTOR FROM COMPLIANCE WITH THE PROJECT PLANS AND SPECIFICATION, NOR DEPARTURES THERE FROM. SHOP DRAWING DEVIATIONS: WHEN SHOP DRAWINGS (COMPONENT DESIGN DRAWINGS) DIFFER FROM, OR ADD TO, THE REQUIREMENTS OF THE STRUCTURAL DRAWINGS, THEY ARE TO BE STAMPED BY THE RESPONSIBLE EOR. 04/27/20 PERMIT SET 204875 ANCHORAGE TO HARDENED CONCRETE: ANCHORAGE TO HARDENED CONCRETE IS TO INCLUDE MECHANICAL AND ADHESIVE ANCHORS OF SIZE, NUMBER, AND SPACING AS SHOWN ON THE DRAWINGS. HOLES ARE TO BE DRILLED AND CLEANED, AND ANCHORS ARE TO BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S PUBLISHED INSTRUCTIONS AND AN APPROVED ICC_ES REPORT. INSPECTION AND TESTING IS TO BE CONDUCTED IN ACCORDANCE WITH THE GENERAL NOTES AND THE APPROVED ICC-ES REPORT. WHERE A SPECIFIC TYPE OF ANCHORAGE IS SPECIFIED ON THE DRAWINGS, SUBSTITUTION FOR A DIFFERENT TYPE OF ANCHORAGE, INCLUDING SUBSTITUTION FOR CAST-IN-PLACE ANCHORAGE, IS NOT PERMITTED WITHOUT PRIOR WRITTEN APPROVAL. ANCHORS ARE TO BE INSTALLED AND INSPECTED IN STRICT ACCORDANCE WITH THE APPLICABLE ICC-EVALUATION SERVICE REPORT (ESR). SPECIAL INSPECTION IS TO BE PER THE TESTS AND INSPECTIONS SECTION. REMOVE GREASE, OIL, RUST, AND OTHER FROM RODS AND DOWELS PRIOR TO INSTALLATION. PLACE ADHESIVE ANCHORS PER THE MANUFACTURER’S INSTRUCTIONS. IF REINFORCING IS ENCOUNTERED DURING DRILLING, ABANDON LOCATION AND SHIFT THE HOLE TO AVOID REINFORCING. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH (WHICHEVER IS LARGER) OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED, NOTIFY THE ENGINEER. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, AND OTHER ATTACHED STEEL ASSEMBLIES. SHOP DRAWINGS SHOP DRAWINGS FOR REINFORCING STEEL FOR MASONRY AND CONCRETE CONSTRUCTION SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION OF THESE ITEMS. CONTRACTOR SHALL SUBMIT CONCRETE WALL ELEVATION DRAWINGS OF AT LEAST 1/8" = 1'-0" SCALE INDICATING LOCATIONS OF CONNECTION EMBEDMENTS AND WALL OPENINGS FOR REVIEW PRIOR TO CONSTRUCTION. CONTRACTOR SHALL COORDINATE WITH REINFORCEMENT DRAWINGS. DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE EOR; THEREFORE, THEY SHALL BE VERIFIED BY THE CONTRACTOR. CONTRACTOR SHALL REVIEW AND STAMP DRAWINGS PRIOR TO REVIEW BY THE EOR. CONTRACTOR SHALL REVIEW DRAWINGS FOR CONFORMANCE WITH THE MEANS, METHODS, TECHNIQUES, SEQUENCES, AND OPERATIONS OF CONSTRUCTION, AND ALL SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO. SUBMITTALS SHALL INCLUDE ONE REPRODUCIBLE AND ONE COPY; REPRODUCIBLE WILL BE MARKED AND RETURNED. SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT BY INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED, AND BY DETAILING THE INTENDED FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWINGS SUBMITTALS AND THE CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED. MISCELLANEOUS REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, CIVIL, OR OTHER DRAWINGS FOR DIMENSIONS NOT SHOWN, INCLUDING INFORMATION SUCH AS: SIZE AND LOCATION OF CURBS, EQUIPMENT HOUSEKEEPING PADS, WALL AND FLOOR OPENINGS, BLOCK OUTS, FLOOR DEPRESSIONS, SUMPS, DRAINS, ANCHOR BOLTS, EMBEDDED ITEMS, ARCHITECTURAL TREATMENT, ETC. CONTRACTOR TO COORDINATE DIMENSIONS AND RESOLVE DISCREPANCIES OR CONFLICTS PRIOR TO CONSTRUCTION. MECHANICAL ANCHORS: PROVIDE ANCHORS SPECIFIED ON THE DRAWINGS. AT LOCATIONS WHERE ANCHORAGE IS NOT SPECIFIED, PROVIDE HILTI KWIK BOLT TYPE ‘TZ’ ANCHORS, INSTALLED PER CRITERIA DEFINED IN ICC ESR-1917. PROVIDE STAINLESS STEEL ANCHORS WHEN EXPOSED TO WEATHER OR IN A CLEAN ENVIRONMENT. PROVIDE GALVANIZED CARBON STEEL ANCHORS AT OTHER LOCATIONS, TYP UNO. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, AND OTHER ATTACHED STEEL ASSEMBLIES. YELM COMMUNITY SCHOOLS -FORT STEVENS ELEM - HVAC UPGRADE 16525 100th Way SE Yelm, WA 98597 SELECTION OF CONCRETE MIX PROPORTIONS ARE TO BE IN ACCORDANCE WITH ACI 301. MIX PROPORTIONS ARE TO MEET OR EXCEED THE REQUIREMENTS LISTED BELOW FOR THE LOCATIONS NOTED. THE MORE STRINGENT OF THE REQUIREMENTS LISTED WILL GOVERN. SEE MAXIMUM SIZE OF AGGREGATE PER ABOVE SCHEDULE. MAXIMUM FLY ASH AS PERCENTAGE OF TOTAL WEIGHT OF CEMENTITIOUS MATERIAL IS TO BE 30 PERCENT. FLY ASH IS TO BE CLASS C OR CLASS F AND MEET ASTM C618 REQUIREMENTS. WATER/CEMENT RATIO IS TO BE BASED ON TOTAL CEMENTITIOUS MATERIAL, INCLUDING FLY ASH AND OTHER POZZOLANIC MATERIAL. CONTRACTOR TO DETERMINE SLUMP. EACH CONCRETE MIX SUBMITTED IS TO HAVE THE SPECIFIED SLUMP. SLUMP IS TO BE MEASURED AT THE DISCHARGE OF THE TRUCK. IF CONCRETE IS PUMPED, SLUMP IS TO BE MEASURED AT THE DISCHARGE END OF THE PUMP LINE. SLUMPS ARE TO BE WITHIN + 1 INCH AND -2 INCHES OF THE SPECIFIED SLUMP. REINFORCING STEEL: ASTM A615 GRADE 60 IS TO BE USED. #3 AND #4 STIRRUPS, TIES, AND ELBOW BARS CAN BE GRADE 40. REINFORCING STEEL DETAILS SHALL BE PREPARED BY A QUALIFIED DETAILER TO CONFORM TO STANDARD PRACTICE PER ACI 315. ACCURATELY POSITION, SUPPORT, AND SECURE REINFORCEMENT FROM DISPLACEMENT DUE TO FORMWORK, CONSTRUCTION, AND CONCRETE PLACEMENT OPERATIONS. LOCATE AND SUPPORT REINFORCING BY METAL CHAIRS, RUNNERS, BOLSTERS, SPACERS, AND HANGERS AT A MAXIMUM OF 3’ OC SPACING. SHOP DRAWINGS, INCLUDING PLACING PLANS AND ELEVATIONS, ARE TO BE SUBMITTED TO, AND REVIEWED BY, THE ARCHITECT/ENGINEER BEFORE STARTING FABRICATION. CONCRETE COVER: 3” CONCRETE POURED AGAINST EARTH 2” FORMED CONCRETE WITH EARTH BACKFILL 1-1/2” BEAMS AND COLUMNS (STIRRUPS/TIES), OUTSIDE FACE OF W ALLS EXPOSED TO WEATHER SLABS ON MOISTURE BARRIER. 1” WALLS ALONG INSIDE FACE ¾” FORMED SLAB LAP SPLICES: CONFORM TO ACI 301, SECTION 3.3.2.7, SPLICES. REFER TO “TYPICAL LAP SPLICE AND DEVELOPMENT LENGTH SCHEDULE” FOR TYPICAL REINFORCEMENT SPLICES. SPLICES INDICATED ON INDIVIDUAL SHEETS ARE TO CONTROL OVER THE SCHEDULE. MECHANICA DEVICES MAY BE USED WHEN APPROVED BY THE EOR. FIELD BENDING: CONFORM TO ACI 301, SECTION 3.3.2.8.: “FIELD BENDING OR STRAIGHTENING.” BAR SIZES #3 THROUGH #5 MAY BE FIELD BENT COLD THE FIRST TIME. OTHER BARS REQUIRE PREHEATING. DO NOT TWIST BARS. BARS ARE NOT TO BE BENT PAST 45 DEGREES. TYPICAL CONCRETE REINFORCEMENT: UNLESS OTHERWISE NOTED ON THE PLANS, CONCRETE WALLS ARE TO HAVE THE FOLLOWING MINIMUM REINFORCEMENT. CONTRACTOR IS TO CONFIRM MINIMUM REINFORCEMENT OF THE WALLS WITH EOR PRIOR TO REBAR FABRICATION. 2 1/2" MIN 4d OR 90° TE : AND CROSSTIES FOR SHEAR WALL D D 45° 45° D D 180° D = 6d FOR #3 THRU #8 D = 8d FOR #9, #10 & #11 D = 10d FOR #14 & #18 ALL REINFORCING EXCEPT COLUMN TIES AND BEAM STIRRUPS STIRRUP STIRRUP OR TIE D = 4d FOR #3, #4 & #5 D = 6d FOR #6, #7 & #812dD D 180°3" MIN6d ORD D 135°3" MIN6d ORD D 90° 12d D D 90° 135° 3" MIN6d OR D D 90° 180° 3" MIN 6d OR 3" MIN6d ORBEAM OR COLUMN CROSSTIES BEAM STIRRUPS AND COLUMN TIES d = BAR DIAMETER, D = BEND DIAMETER3" MIN6d ORdd d d dSTANDARD HOOKS AND BENDS - BEAM STIRRUPS AND COLUMN TIES CONCRETE FORMWORK, SHORING, AND RE-SHORING TO BE CONSTRUCTED IN ACCORDANCE WITH ACI 301 “SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS” AND ACI 347 “RECOMMENDED PRACTICE FOR CONCRETE FORMW ORK. CONTRACTOR TO BE RESPONSIBLE FOR THE DESIGN AND CONSTRUCTION OF FORMWORK, SHORING, AND RESHORING. CONCRETE PLACEMENT AND CURING SHALL BE IN ACCORDANCE WITH ACI 301. ITEM F'C (PSI) MAX WATER TO CEMENT RATIO (NON AIRENT) MIN AIRENT CEMENT (SACK/CY) REMARKS FOOTINGS AND FOUNDATION WALLS 4,000 0.44 5% 5-1/2 MAX AGGREGATE SIZE = 1” 1. AIR-ENTRAINING AGENT (3% TO 6%) TO BE USED IN ALL CONCRETE FLATWORK EXPOSED TO WEATHER. 2. PER LEED AP, USE FLY ASH TO THE MAXIMUM EXTENT POSSIBLE EXTENT POSSIBLE IN ALL CONCRETE. 3. SUBMIT CONCRETE MIX DESIGNS TO SEOR FOR APPROVAL. 3,0002,500 X-X (N) MECH UNIT (N) 1/2" DIA HILTI TZ W/ 3-1/4" EFFECTIVE EMBED, TYP @ (6) - LOCATIONS, NOTE 1 (N) CONC SLAB (N) VENDOR PROVIDED CLIP X-XPLAN ODU CONN DETAIL SCALE: NOT TO SCALE 2 SUSPENDED EQUIPMENT SEISMIC DETAILS SCALE: NTS 4 SPECIAL INSPECTION THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION AND TESTING PER IBC SECTION 1705. THIS WORK SHALL BE PERFORMED BY A SPECIAL INSPECTOR CERTIFIED BY THE APPROPRIATE JURISDICTION TO PERFORM THE TYPES OF INSPECTIONS AND TESTS SPECIFIED. THE FREQUENCY OF INSPECTIONS AND TESTING SHALL BE AS OUTLINED IN THE IBC TABLE. DEFICIENCIES ARE TO BE REPORTED DAILY TO THE CONTRACTOR. SUMMARY REPORTS SHALL BE DISTRIBUTED WEEKLY TO THE OWNER, ARCHITECT, CONTRACTOR, BUILDING OFFICIAL, AND STRUCTURAL ENGINEER. SEE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR SPECIAL INSPECTIONS AND TESTING. SEE IBC SECTION 1705 FOR ADDITIONAL INFORMATION: SPECIAL CASES: 1. EXPANSION CONCRETE ANCHORS SPECIAL PERIODIC INSPECTION CONCRETE EXPANSION FOUNDATIONS ENGINEERING VALUES FOR THE FOUNDATION ARE BASED ON ASSUMED MINIMUM ALLOWABLE BEARING VALUES PER IBC 2015. NET ALLOWABLE BEARING: 2000 PSF (BEARING FOR FIRM, UNDISTURBED NATIVE MATERIALS) COEFF OF SLIDING FRICTION: 0.3 (MINIMUM) SOG ALLOWABLE SUBGRADE MODULUS: K = 100 PSI/IN FOOTINGS SHALL BE EMBEDDED A MINIMUM OF -1’-6” BELOW FINISH GRADE (FROST). CONTRACTOR TO LOCATE AND PROTECT EXISTING UTILITIES TO REMAIN INTACT DURING AND/OR AFTER CONSTRUCTION. NOTIFY THE OWNER OF THE PRESENCE OF ANY BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS, FOUNDATIONS, AND UTILITIES. COMPACT ALL SUBGRADE AND STRUCTURAL FILL TO 95% - 100% MAXIMUM DENSITY PER (ASTM MODIFIED PROCTOR TEST). OPEN CHANNEL STRUT ALL SECTIONS SHALL BE 12 GAGE STRUT WITH ELECTRO-GALVANIZED FINISH (EG) TYP UNO. PROVIDE ½ INCH DIAMETER A307 BOLTS FOR ALL CONNECTIONS TYP UNO. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING PROTECTIVE CAPS ON ENDS OF ALL EXPOSED UNISTRUT SUPPORTS. DESIGN CRITERIA CODES: IBC 2018 EDITION ALONG WITH WASHINGTON AMENDMENTS, ASCE 7-16, ACI 318-14. SCOPE OF WORK: MCK SCOPE INCLUDES STRUCT DESIGN OF THE SEISMIC AND WIND CONNECTION OF REPLACEMENT MECH EQUIPMENTS, CONCRETE FOOTING AND CONFIRM EXISTING ROOF FRAMING FOR MECHANICAL EQUIPMENT INCOMING LOADS. REFERENCE DRAWINGS: STRUCTURAL DRAWINGS: EXISTING DRAWING WAS ISSUED BY CHALKER ENGINEERS, STAMPED BY LYMAN F. BUSH; DATED: 06/26/89, DRAWINGS S0.1 - S4.5. MECH DRAWINGS: MCK MECHANICAL PERMIT SET; DATED 04/23/2021. DRAWINGS M-001 -- M- 500. LOADING: DEAD LOADS: SELF WT (SEE MECH EQUIP SCHEDULE) SNOW LOADS: Pg = 25 PSF, Is=1.0 SEISMIC: RISK CAT: II RISK CATEGORY SDC: D SEISMIC DESIGN CATEGORY SDS: 0.855 g DESIGN SHORT PERIOD ACCELERATION IE: 1.0 SEISMIC IMPORTANCE FACTOR WIND: V3SEC: 95 MPH ULTIMATE, 3-SEC GUST EXPOSURE: C IW: 1.0 CONC PAD/FOOTING DETAIL SCALE: NOT TO SCALE 1 GRAVITY HANGER WITH 1-5/8" STRUT CHANNEL WITH ROD STIFFENER AND CLAMPS IF LENGTH IS > 4'-0"; MIN (3) STIFFENER CABLE BRACE NOTE 3 SWAY ATTACHMENT FROM CABLE PROVIDER NUT & WASH EA SIDE OF HANGER OR TRAPEZE EQUIPMENT WT 310# (MAX) SEE NOTE 1 45˚±15˚ ROD STIFFENER CONN (3 MIN PER SCHED EQUIPMENT INSTALLED WITH HANGER BRACKETS. FOR TRAPEZE SUPPORT INFO SEE NOTE 2 3/8" DIA THREDED ROD, TYP ROD COUPLING DET-1 ELEVATION TYP NOTES: 1. MAX WT 310# FOR RIGID AND 200# FOR SPRING-ISSOLATED MECH EQUIPMENT. 2. IF EQUIPMENT LACKS HANGER BRACKETS, INSTALL P1000 STRUT TOP AND BOT AND ATTACH WITH #10 TEK @ 12" OC. 3. PROVIDE CABLE AT EACH CORNER OF UNIT WITH HORIZONTAL ANGLE SET TO 45˚±15˚ 4. PROVIDE ½ INCH DIAMETER A307 BOLTS AND STRUT NUTS FOR ALL CONNECTIONS TYP UNO. 5. IF AIRCRAFT CABLE IS USED IN LIEU OF GRIPPLE, PROVIDE THIMBLE AT AT DOUBLE SWAGE OR DOUBLE CABLE CLAMP (TYP). 6. CONTRACTOR REQ'D TO X-RAY EXISTING PT SLAB TO AVOID CLASH WITH PT TENDONS PRIOR TO ANCHOR INSTALL AND RELOCATE ACNHOR LOCATION IF NEEDED. DET-1 TYP (N) 1/4"x2-3/4" CWSD 15 SAMMY WOOD SCREW (N) 3/8" DIA THREADED GRAVITY ROD (N) GRIPPLE GS-12 CABLE BRACE CONN DETAIL @ MEB-1 SCALE: NTS DET-1 2X BLOCKING W/ 10d @ 4" O.C MAX 2X6 W/ SIMPSON U26 EA. END PLYWOOD 2X BLOCKING (E) TJI JOIST AHU CONN DETAIL SCALE: NOT TO SCALE 5 AHU X-X X--XPLAN (E) CONC SLAB MECH UNIT PER PLAN L3x3x14GAx0'-5" TOC (4) 1/4" DIA TEK SCREW (1) 3/8" DIA HUS SCREW ANCHOR WITH 2" MINIMUM EFFECTIVE EMBED1-1/2"SHEET TITLE PERMIT 05/03/21 S-001 SYMBOLS, GENERAL NOTES AND CONNECTION DETAILS X S-101 PARTIAL PLAN X S-102 PARTIAL PLAN X S-103 PARTIAL PLAN X DRAWING INDEX 1 1 #4 SOG REINF BOTH WAY @ 12" O.C MAX #4x @ TOP AT 18" OC 2'-6" #4 CLOSED TIES AT 12" OC, ALL-AROUND (2) #6 CONT TOP & BOTPER PLANPER PLAN X-X X-XPLAN D = 12" B = 10" 5" CONC SOGPER PLAN PER PLANEXPIRES: 9-23-22 McKINSTRY Co, LLC NOT FOR CONSTRUCTION CHECKED: DRAWN: JOB NO: DESIGNED: SHEET TITLE: SHEET NUMBER: REGISTRATION: PROJECT: CONSULTANTS: SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98134 1-800-669-6223 www.mckinstry.com ISSUES: NO DATE DESCRIPTION 202675-001 22150 NE 156TH PLACE WOODINVILLE, WA 98077 NORTHSHORE SOOL DISTRICT EAST RIDGE ELEMENTARY MMR MMR JWG PARTIAL PLAN S-101 04/27/20 PERMIT SET 204875 SCALE: 1/8" = 1'-0" 1 N LEVEL-1 SECTION A PARTIAL PLAN NOTES: 1. (N) DENOTES "NEW"; (E) DENOTES "EXISTING". 2. SEE MECH EQUIPMENT CONN SCHEDULE FOR ADDED INFO INCLUDING CONNECTION DETAIL AND WEIGHTS. 3. SEE GENERAL NOTES FOR ADDITIONAL INFO AND SPECIAL INSPECTION FOR CONCRETE AND POST-INSTALLED ANCHORS. 4. COORDINATE WITH MECH DRAWING FOR ADDITIONAL INFO INCLUDING EXTERIOR CONC PADS LOCATION AND DIMENSIONS. 5. PLAN INFO OBTAINED FROM EXISTING DRAWING ISSUED BY CHALKER ENGINEERS, STAMPED BY LYMAN F. BUSH; REF DRAWING S3.1. YELM COMMUNITY SCHOOLS -FORT STEVENS ELEM - HVAC UPGRADE 16525 100th Way SE Yelm, WA 98597 N A B C D E A B C D E EQUIPMENT TAG DESCRPITION NEW UNIT WT (LBS)L X W X H (IN)CONN DETAIL ODU-08 VRF OUTDOOR CONDENSING UNIT 695 49 X 30 X 67 2/S-001 ODU-09,10 VRF OUTDOOR CONDENSING UNIT 527 49 X 30 X 67 2/S-001 MECHANICAL EQUIPMENT CONNECTION SCHEDULE EQUIPMENT TAG DESCRPITION NEW UNIT WT (LBS)L X W X H (IN)CONN DETAIL ODU-01 VRF OUTDOOR CONDENSING UNIT 727 49 X 30 X 67 2/S-001 BC-01 VRF INDOOR UNIT 302 54 X 43 X 19 4/S-001 BC-02,23,24 VRF INDOOR UNIT 104 55 X 32 X 10 4/S-001 BC-25 VRF INDOOR UNIT 77 39 X 32 X 10 4/S-001 BCU-01 VRF BRANCH CONTROLLER 82 24 X 23 X 10 4/S-001 AHU-01 AIR HANDLING UNIT 1,160 54 X 54 X 78 3/S-001 AHU-02 AIR HANDLING UNIT 1,200 56 X 56 X 78 3/S-001 MECHANICAL EQUIPMENT CONNECTION SCHEDULE SCALE: 1/8" = 1'-0" 1 SECTION B ROOF PARTIAL PLAN NOTES: 1. (N) DENOTES "NEW"; (E) DENOTES "EXISTING". 2. SEE MECH EQUIPMENT CONN SCHEDULE FOR ADDED INFO INCLUDING CONNECTION DETAIL AND WEIGHTS. 3. SEE GENERAL NOTES FOR ADDITIONAL INFO AND SPECIAL INSPECTION FOR CONCRETE AND POST-INSTALLED ANCHORS. 4. COORDINATE WITH MECH DRAWING FOR ADDITIONAL INFO INCLUDING EXTERIOR CONC PADS LOCATION AND DIMENSIONS. 5. PLAN INFO OBTAINED FROM EXISTING DRAWING ISSUED BY CHALKER ENGINEERS, STAMPED BY LYMAN F. BUSH; REF DRAWING S1.1. KEY PLAN (N) ODU-10 NOTE 2 (N) ODU-9 NOTE 2 (N) ODU-8 NOTE 2 2'-0" MIN NOTE 3VIF NOTE 3(N) CONC SOG FOOTING PER DETAIL 1/S-001 10'-0"4'-0" (N) BC-2 NOTE 2 (N) AHU-02 AT LEVEL - 1 NOTE 2 (N) AHU-01 AT LEVEL - 1 NOTE 2 (N) ODU-1 NOTE 2 (N) BC-25 NOTE 2 (N) BC-24 NOTE 2 (N) BC-23 NOTE 2 (N) BCU-1 NOTE 2 (N) BC-1 NOTE 2 (E) CONCRETE PAD/FOOTING AT GROUND LEVEL GS-12 CABLE BRACE, TYP EXPIRES: 9-23-22 McKINSTRY Co, LLC NOT FOR CONSTRUCTION CHECKED: DRAWN: JOB NO: DESIGNED: SHEET TITLE: SHEET NUMBER: REGISTRATION: PROJECT: CONSULTANTS: SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98134 1-800-669-6223 www.mckinstry.com ISSUES: NO DATE DESCRIPTION 202675-001 22150 NE 156TH PLACE WOODINVILLE, WA 98077 NORTHSHORE SOOL DISTRICT EAST RIDGE ELEMENTARY MMR MMR JWG PARTIAL PLAN S-101 04/27/20 PERMIT SET 204875 N YELM COMMUNITY SCHOOLS -FORT STEVENS ELEM - HVAC UPGRADE 16525 100th Way SE Yelm, WA 98597 A B C D E SCALE: 1/8" = 1'-0" 1 SECTION C ROOF PARTIAL PLAN NOTES: 1. (N) DENOTES "NEW"; (E) DENOTES "EXISTING". 2. SEE MECH EQUIPMENT CONN SCHEDULE FOR ADDED INFO INCLUDING CONNECTION DETAIL AND WEIGHTS. 3. SEE GENERAL NOTES FOR ADDITIONAL INFO AND SPECIAL INSPECTION FOR CONCRETE AND POST-INSTALLED ANCHORS. 4. COORDINATE WITH MECH DRAWING FOR ADDITIONAL INFO INCLUDING EXTERIOR CONC PADS LOCATION AND DIMENSIONS. 5. PLAN INFO OBTAINED FROM EXISTING DRAWING ISSUED BY CHALKER ENGINEERS, STAMPED BY LYMAN F. BUSH; REF DRAWING S3.2. EQUIPMENT TAG DESCRPITION NEW UNIT WT (LBS)L X W X H (IN)CONN DETAIL ODU-02,03, 04 VRF OUTDOOR CONDENSING UNIT 727 49 X 30 X 67 2/S-001 BC-10 VRF INDOOR UNIT 302 54 X 43 X 19 4/S-001 BC-12 VRF INDOOR UNIT 104 55 X 32 X 10 4/S-001 BC- 03,04,05,06,07,08,09,13,14 VRF INDOOR UNIT 101 55 X 32 X 10 4/S-001 BC-11 VRF INDOOR UNIT 82 39 X 32 X 10 4/S-001 BCU-04 VRF BRANCH CONTROLLER 82 24 X 23 X 10 4/S-001 BCU-02 VRF BRANCH CONTROLLER 49 24 X 14 X 10 4/S-001 BCU-03 VRF BRANCH CONTROLLER 73 24 X 23 X 10 4/S-001 MECHANICAL EQUIPMENT CONNECTION SCHEDULE (N) ODU-2 NOTE 2 (N) BC-3 NOTE 2 (N) BCU-2 NOTE 2 (N) BC-4 NOTE 2 (N) BC-5 NOTE 2 (N) BCU-3 NOTE 2 (N) BC-7 NOTE 2 (N) BC-6 NOTE 2 (N) BC-9 NOTE 2 (N) BC-8 NOTE 2 (N) BCU-4 NOTE 2 (N) BC-10 NOTE 2 (N) BC-13 NOTE 2 (N) BC-11 NOTE 2 (N) BC-12 NOTE 2 (N) BC-14 NOTE 2 (N) CONC SOG FOOTING PER DETAIL 1/S-001 5'-0"4'-0"5'-0"4'-0" (N) ODU-4 NOTE 2 2'-0" MIN NOTE 3 (N) ODU-3 NOTE 2 GS-12 CABLE BRACE, TYP EXPIRES: 9-23-22 S-102 McKINSTRY Co, LLC NOT FOR CONSTRUCTION CHECKED: DRAWN: JOB NO: DESIGNED: SHEET TITLE: SHEET NUMBER: REGISTRATION: PROJECT: CONSULTANTS: SEATTLE: 5005 3RD AVENUE S PO BOX 24567 SEATTLE, WA 98134 1-800-669-6223 www.mckinstry.com ISSUES: NO DATE DESCRIPTION 202675-001 22150 NE 156TH PLACE WOODINVILLE, WA 98077 NORTHSHORE SOOL DISTRICT EAST RIDGE ELEMENTARY MMR MMR JWG PARTIAL PLAN S-101 04/27/20 PERMIT SET 204875 N YELM COMMUNITY SCHOOLS -FORT STEVENS ELEM - HVAC UPGRADE 16525 100th Way SE Yelm, WA 98597 A B C D E SCALE: 1/8" = 1'-0" 1 SECTION D ROOF PARTIAL PLAN NOTES: 1. (N) DENOTES "NEW"; (E) DENOTES "EXISTING". 2. SEE MECH EQUIPMENT CONN SCHEDULE FOR ADDED INFO INCLUDING CONNECTION DETAIL AND WEIGHTS. 3. SEE GENERAL NOTES FOR ADDITIONAL INFO AND SPECIAL INSPECTION FOR CONCRETE AND POST-INSTALLED ANCHORS. 4. COORDINATE WITH MECH DRAWING FOR ADDITIONAL INFO INCLUDING EXTERIOR CONC PADS LOCATION AND DIMENSIONS. 5. PLAN INFO OBTAINED FROM EXISTING DRAWING ISSUED BY CHALKER ENGINEERS, STAMPED BY LYMAN F. BUSH; REF DRAWING S3.3. EQUIPMENT TAG DESCRPITION NEW UNIT WT (LBS)L X W X H (IN)CONN DETAIL ODU-05 VRF OUTDOOR CONDENSING UNIT 727 49 X 30 X 67 2/S-001 ODU-06 VRF OUTDOOR CONDENSING UNIT 793 49 X 30 X 67 2/S-001 BC-16,19 VRF INDOOR UNIT 104 55 X 32 X 10 4/S-001 BC-18,20,21,22 VRF INDOOR UNIT 101 55 X 32 X 10 4/S-001 BC-15,17 VRF INDOOR UNIT 82 39 X 32 X 10 4/S-001 BCU-05 VRF BRANCH CONTROLLER 49 24 X 14 X 10 4/S-001 BCU-06 VRF BRANCH CONTROLLER 73 24 X 23 X 10 4/S-001 MECHANICAL EQUIPMENT CONNECTION SCHEDULE (N) BC-22 NOTE 2 (N) BC-21 NOTE 2 (N) BC-20 NOTE 2 (N) BC-19 NOTE 2 (N) BC-18 NOTE 2 (N) BC-17 NOTE 2 (N) BCU-5 NOTE 2 (N) BC-16 NOTE 2 (N) BC-15 NOTE 2 GS-12 CABLE BRACE (N) ODU-5 NOTE 2 (N) CONC SOG FOOTING PER DETAIL 1/S-001 5'-0"4'-0" 2'-0" MIN NOTE 3 5'-0"4'-0"2'-0" MIN NOTE 3 (N) ODU-6 NOTE 2 (N) BCU-6 NOTE 2 GS-12 CABLE BRACE, TYP EXPIRES: 9-23-22 S-103