Packaged Rooftop Builder 1.58 Page 2 of 21
5t Unit
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Unit Report For 5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 3 of 21
Unit Parameters
Unit Model: ....................... 48GCEM06A2A5-0A0A0
Unit Size: ................................................06 (5 Tons)
Volts-Phase-Hertz: ..................................... 208-3-60
Heating Type: ..................................................... Gas
Duct Cfg: ............ Vertical Supply / Vertical Return
Medium Heat
Two Stage Cooling Models
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: ......................................... 6' 2.375''
Unit Width:......................................... 3' 10.625''
Unit Height: ......................................... 3' 5.375''
*** Total Operating Weight: ...................... 618 lb
*** Weights and Dimensions are approximate. Weight
does not include unit packaging. Approximate
dimensions are provided primarily for shipping purposes.
For exact dimensions and weights, refer to appropriate
product data catalog.
Lines and Filters
Gas Line Size: ..................................................... 1/2
Condensate Drain Line Size: .............................. 3/4
Return Air Filter Type: ........................... Throwaway
Return Air Filter Quantity: ....................................... 4
Return Air Filter Size: ..............................16 x 16 x 2
Unit Configuration
Direct Drive - EcoBlue - Medium Static
Al/Cu - Al/Cu
Base controls set up for field installed air management devices
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger - Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48GCEM06A2A5-0A0A0 Rooftop Unit 2
Base Unit
Direct Drive - EcoBlue - Medium Static
Electromechanical control, No intake or exhaust option.
Accessories
CRECOMZR067A01 Ultra LOW LEAK - Vertical EconoMi$er X with solid-state W7220
controller
2
--HH--57AC-081 Enthalpy Control for W7220 Controller 2
Certified Drawing for 5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 4 of 21
Certified Drawing for 5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 5 of 21
Certified Drawing for 5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 6 of 21
Performance Summary For 5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 7 of 21
Part Number:48GCEM06A2A5-0A0A0
ARI SEER: ................................................................................................................................................... 16.10
Base Unit Dimensions
Unit Length: ............................................................................................................................................. 74.4 in
Unit Width: .............................................................................................................................................. 46.6 in
Unit Height: ............................................................................................................................................. 41.4 in
Operating Weight
Base Unit Weight: .................................................................................................................................... 555 lb
Medium Heat: ............................................................................................................................................. 63 lb
Total Operating Weight: ........................................................................................................................... 618 lb
Unit
Unit Voltage-Phase-Hertz: ............................................................................................................... 208-3-60
Air Discharge:.................................................................................................................................... Vertical
Fan Drive Type:.................................................................................................................................... Direct
Actual Airflow: ........................................................................................................................................ 2000 CFM
Site Altitude: ................................................................................................................................................. 0 ft
Cooling Performance
Condenser Entering Air DB: .................................................................................................................... 95.0 F
Evaporator Entering Air DB: .................................................................................................................... 80.0 F
Evaporator Entering Air WB: ................................................................................................................... 67.0 F
Entering Air Enthalpy: ........................................................................................................................... 31.44 BTU/lb
Evaporator Leaving Air DB: ..................................................................................................................... 57.6 F
Evaporator Leaving Air WB: .................................................................................................................... 57.1 F
Evaporator Leaving Air Enthalpy: .......................................................................................................... 24.44 BTU/lb
Gross Cooling Capacity: ....................................................................................................................... 63.00 MBH
Gross Sensible Capacity: ...................................................................................................................... 48.32 MBH
Compressor Power Input: ....................................................................................................................... 4.11 kW
Coil Bypass Factor: ............................................................................................................................... 0.047
Heating Performance
Heating Airflow: ...................................................................................................................................... 2000 CFM
Entering Air Temp: .................................................................................................................................. 70.0 F
Leaving Air Temp: ................................................................................................................................. 110.7 F
Gas Heating Input Capacity: ....................................................................................................... 82.0 / 110.0 MBH
Gas Heating Output Capacity: ...................................................................................................... 65.0 / 88.0 MBH
Temperature Rise: .................................................................................................................................. 40.7 F
Thermal Efficiency (%): ........................................................................................................................... 80.0
Supply Fan
External Static Pressure: ......................................................................................................................... 0.50 in wg
Options / Accessories Static Pressure
Economizer: ...................................................................................................................................... 0.12 in wg
Total Application Static (ESP + Unit Opts/Acc.): ..................................................................................... 0.62 in wg
Fan RPM: ............................................................................................................................................... 2024
Fan Power: .............................................................................................................................................. 0.88 BHP
NOTE: ............................................................................................ Selected IFM RPM Range: 1387 - 2390
Electrical Data
Voltage Range: ............................................................................................................................... 187 - 253
Compressor #1 RLA: ............................................................................................................................... 16.2
Compressor #1 LRA: ................................................................................................................................ 110
Indoor Fan Motor Type: .......................................................................................................................... MED
Indoor Fan Motor FLA: .............................................................................................................................. 8.6
Combustion Fan Motor FLA (ea): ............................................................................................................ 0.48
Power Supply MCA: ................................................................................................................................... 31
Performance Summary For 5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 8 of 21
Power Supply MOCP (Fuse or HACR): ...................................................................................................... 45
Disconnect Size FLA: ................................................................................................................................. 30
Disconnect Size LRA: .............................................................................................................................. 126
Electrical Convenience Outlet: .............................................................................................................. None
Outdoor Fan [Qty / FLA (ea)]: .............................................................................................................. 1 / 1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.6 89.0 85.6
125 Hz 82.7 78.7 84.7
250 Hz 76.7 71.5 80.5
500 Hz 73.4 65.4 76.0
1000 Hz 70.0 67.7 72.4
2000 Hz 67.4 58.9 68.0
4000 Hz 63.7 52.2 62.8
8000 Hz 59.9 46.5 59.3
A-Weighted 76.6 71.6 79.0
Advanced Acoustics
Advanced Accoustics Parameters
1. Unit height above ground: .................................. 30.0 ft
2. Horizontal distance from unit to receiver: ........... 50.0 ft
3. Receiver height above ground: ............................ 5.7 ft
4. Height of obstruction: ........................................... 0.0 ft
5. Horizontal distance from obstruction to receiver: . 0.0 ft
6. Horizontal distance from unit to obstruction: ........ 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
Performance Summary For 5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 9 of 21
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM 2500 RPM
2700 RPM
2900 RPM
0.50 BHP 0.75 BHP 1.00 BHP
1.50 BHP
2.00 BHP
3.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2024 BHP = 0.88 Maximum RPM = 2836 Maximum BHP = 5.00Static Pressure (in. wg.)Airflow (CFM - thousands)
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Unit Feature Sheet for 5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 10 of 21
7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 12 of 21
7.5t Unit
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Unit Report For 7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 13 of 21
Unit Parameters
Unit Model: ........................ 48TCED08A2A5-0A0G0
Unit Size: ............................................. 08 (7.5 Tons)
Volts-Phase-Hertz: ..................................... 208-3-60
Heating Type: ..................................................... Gas
Duct Cfg: ............ Vertical Supply / Vertical Return
Medium Heat
Round Tube Plate Fin Coils
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: ......................................... 7' 4.125''
Unit Width:............................................. 4' 11.5''
Unit Height: ........................................... 3' 5.25''
*** Total Operating Weight: ...................... 960 lb
*** Weights and Dimensions are approximate. Weight
does not include unit packaging. Approximate
dimensions are provided primarily for shipping purposes.
For exact dimensions and weights, refer to appropriate
product data catalog.
Lines and Filters
Gas Line Size: ..................................................... 3/4
Condensate Drain Line Size: .............................. 3/4
Return Air Filter Type: ........................... Throwaway
Return Air Filter Quantity: ....................................... 4
Return Air Filter Size: ..............................16 x 20 x 2
Unit Configuration
Medium Static Option (Belt Drive)
Al/Cu - Al/Cu
Base Electromechanical Controls
Standard Packaging
2-Speed indoor fan motor controlled by VFD
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger - Aluminized(std.)
15-Year heat exchanger - Stainless Steel(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48TCED08A2A5-0A0G0 Rooftop Unit 1
Base Unit
Medium Static Option (Belt Drive)
Electromechanical control, No intake or exhaust option.
2 Speed Fan Controller (VFD)
Accessories
CRECOMZR069A01 Ultra LOW LEAK - Vertical EconoMi$er 1
Certified Drawing for 7.5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 14 of 21
Certified Drawing for 7.5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 15 of 21
Certified Drawing for 7.5t Unit Project: Rosemont Retirement 04/13/2021 Prepared By: 07:32AM Packaged Rooftop Builder 1.58 Page 16 of 21
Performance Summary For 7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 17 of 21
Part Number:48TCED08A2A5-0A0G0
ARI EER: ..................................................................................................................................................... 11.00
IEER: ............................................................................................................................................................. 12.8
Base Unit Dimensions
Unit Length: ............................................................................................................................................. 88.1 in
Unit Width: .............................................................................................................................................. 59.5 in
Unit Height: ............................................................................................................................................. 41.3 in
Operating Weight
Base Unit Weight: .................................................................................................................................... 835 lb
Medium Heat: ............................................................................................................................................. 15 lb
Medium Static Option (Belt Drive): ............................................................................................................. 15 lb
2 Speed Fan Controller (VFD): ................................................................................................................ 20 lb
Accessories
Ultra LOW LEAK - Vertical EconoMi$er: ................................................................................................. 75 lb
Total Operating Weight: ........................................................................................................................... 960 lb
Unit
Unit Voltage-Phase-Hertz: ............................................................................................................... 208-3-60
Air Discharge:.................................................................................................................................... Vertical
Fan Drive Type:....................................................................................................................................... Belt
Actual Airflow: ........................................................................................................................................ 3000 CFM
Site Altitude: ................................................................................................................................................. 0 ft
Cooling Performance
Condenser Entering Air DB: .................................................................................................................... 95.0 F
Evaporator Entering Air DB: .................................................................................................................... 80.0 F
Evaporator Entering Air WB: ................................................................................................................... 67.0 F
Entering Air Enthalpy: ........................................................................................................................... 31.44 BTU/lb
Evaporator Leaving Air DB: ..................................................................................................................... 58.7 F
Evaporator Leaving Air WB: .................................................................................................................... 57.6 F
Evaporator Leaving Air Enthalpy: .......................................................................................................... 24.76 BTU/lb
Gross Cooling Capacity: ....................................................................................................................... 90.10 MBH
Gross Sensible Capacity: ...................................................................................................................... 68.90 MBH
Compressor Power Input: ....................................................................................................................... 6.40 kW
Coil Bypass Factor: ............................................................................................................................... 0.092
Heating Performance
Heating Airflow: ...................................................................................................................................... 3000 CFM
Entering Air Temp: .................................................................................................................................. 70.0 F
Leaving Air Temp: ................................................................................................................................. 115.7 F
Gas Heating Input Capacity: ..................................................................................................... 120.0 / 180.0 MBH
Gas Heating Output Capacity: .................................................................................................... 98.0 / 148.0 MBH
Temperature Rise: .................................................................................................................................. 45.7 F
Thermal Efficiency (%): ........................................................................................................................... 82.0
Supply Fan
External Static Pressure: ......................................................................................................................... 0.50 in wg
Options / Accessories Static Pressure
Economizer: ...................................................................................................................................... 0.11 in wg
Total Application Static (ESP + Unit Opts/Acc.): ..................................................................................... 0.61 in wg
Fan RPM: ................................................................................................................................................. 763
Fan Power: .............................................................................................................................................. 1.65 BHP
NOTE: ................................................................................................ Selected IFM RPM Range: 733 - 949
Electrical Data
Voltage Range: ............................................................................................................................... 187 - 253
Compressor #1 RLA: ............................................................................................................................... 13.6
Performance Summary For 7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 18 of 21
Compressor #1 LRA: .................................................................................................................................. 83
Compressor #2 RLA: ............................................................................................................................... 13.6
Compressor #2 LRA: .................................................................................................................................. 83
Indoor Fan Motor Type: .......................................................................................................................... MED
Indoor Fan Motor FLA: .............................................................................................................................. 8.4
Combustion Fan Motor FLA (ea): ............................................................................................................ 0.48
Power Supply MCA: ................................................................................................................................... 43
Power Supply MOCP (Fuse or HACR): ...................................................................................................... 50
Disconnect Size FLA: ................................................................................................................................. 45
Disconnect Size LRA: .............................................................................................................................. 227
Electrical Convenience Outlet: .............................................................................................................. None
Outdoor Fan [Qty / FLA (ea)]: .............................................................................................................. 2 / 1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 98.2 95.2 85.8
125 Hz 91.4 86.1 84.3
250 Hz 78.0 73.0 80.5
500 Hz 70.8 66.3 78.7
1000 Hz 67.2 63.4 76.4
2000 Hz 65.7 58.5 72.7
4000 Hz 67.1 57.8 68.3
8000 Hz 69.4 57.5 65.1
A-Weighted 79.4 74.3 82.0
Advanced Acoustics
Advanced Accoustics Parameters
1. Unit height above ground: .................................. 30.0 ft
2. Horizontal distance from unit to receiver: ........... 50.0 ft
3. Receiver height above ground: ............................ 5.7 ft
4. Height of obstruction: ........................................... 0.0 ft
5. Horizontal distance from obstruction to receiver: . 0.0 ft
6. Horizontal distance from unit to obstruction: ........ 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
A 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1 89.6 Lw
B 59.6 68.2 71.9 75.5 76.4 73.9 69.3 64.0 81.4 LwA
Performance Summary For 7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 19 of 21
C 53.4 51.9 48.1 46.3 44.0 40.3 35.9 32.7 57.2 Lp
D 27.2 35.8 39.5 43.1 44.0 41.5 36.9 31.6 49.0 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user
is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation.
This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to
the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate
sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical
Engineer or a person with sound prediction expertise should be consulted.
400 RPM
500 RPM
600 RPM
700 RPM
800 RPM
900 RPM 1000 RPM 1100 RPM 1200 RPM
0.50 BHP
0.75 BHP
1.00 BHP
1.50 BHP
2.00 BHP
3.00 BHP
5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
Note: Please contact application engineering for selections outside the shaded region.
RPM = 763 BHP = 1.65 Maximum RPM = 1400 Maximum BHP = 4.70Static Pressure (in. wg.)Airflow (CFM - thousands)
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Unit Feature Sheet for 7.5t Unit
Project: Rosemont Retirement 04/13/2021
Prepared By: 07:32AM
Packaged Rooftop Builder 1.58 Page 20 of 21