2021.0295.BP0022 Walmart 3705 Remodel Electrical Drawing SetEXISTING LIGHTING FIXTURES NOT SHOWN ARE EXISTING TO REMAIN AND ARE NOT AFFECTED BY THE SCOPE OF WORK ON THIS PROJECT. THIS INCLUDES ALL GENERAL LIGHTING, EGRESS LIGHTING, AND EXIT LIGHTING.PROVIDE LISTED HANDLE-TIE BETWEEN CIRCUIT BREAKERS SHARING COMMON NEUTRAL FOR SIMULTANEOUS TRIP. TYP OF ALL CIRCUITS SHOWN ON ALL ELECTRICAL SHEETS.STOCKROOMEMERGENCY LIGHTING AND EXIT SIGNAGE MUST BE CONNECTED TO THE UNSWITCH LINE SIDE OF THE LIGHTING CIRCUIT. TYP OF ALL CIRCUITS SHOWN ON ALL ELECTRICAL SHEETS.EDC1SALESEDC4ABCDEFGHIJ12345678910111213EDC2E1.11E1.12architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONEXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. TYPICAL OF ALL ELECTRICAL SHEETS.EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. TYPICAL OF ALL ELECTRICAL SHEETS.DOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E1LIGHTINGPLANKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PN 1" = 20'-0" 1LIGHTING PLAN1.A.B.C.D.E.F.2.A.B.C.D.E.3.4.5.6.EXIT SIGN MOUNTINGWALL FIXTURE: CENTER 12" ABOVE DOOR OPENING.CEILING FIXTURE: ON CEILING OR AT HEIGHT SPECIFIED ON DRAWINGS.PENDANT FIXTURE: MATCH HEIGHT OF EXISTING PENDANT MOUNTED EXIT SIGNS. IF STORE DOES NOT HAVE PENDANT MOUNTED EXIT SIGNS, THEN PENDANT MOUNT SIGN 24" BELOW BOTTOM OF BAR JOIST. VERIFY MOUNTING HEIGHT WITH AHJ.COORDINATE LOCATIONS OF EXIT SIGNS TO ENSURE STORE SIGNAGE DOES NOT OBSTRUCT THEIR VIEW.THE USE OF TRITIUM BASED RADIOACTIVE EXIT SIGNAGE IS PROHIBITED.EMERGENCY LIGHT FIXTURE INSTALLATION WALL FIXTURE: 12" BELOW FINISHED CEILING OR +10'-0" IN AREAS OF EXPOSED STRUCTURE, UNLESS NOTED OTHERWISE.PENDANT FIXTURE: BOTTOM CHORD OF BAR JOIST OR AT HEIGHT SPECIFIED ON DRAWINGS.REMOTE HEAD FIXTURE: HEADS CENTERED ABOVE DOOR OPENING +9'-0", UNLESS NOTED OTHERWISE AND BATTERY PACK MOUNTED ON INTERIOR SIDE OF WALL 12" BELOW FINISHED CEILING OR AT BAR JOIST IN AREAS OF EXPOSED STRUCTURE.REFER TO MANUFACTURER'S WRITTEN INSTRUCTIONS. ALLOW BATTERY TO CHARGE CONTINUOUSLY FOR A MINIMUM OF 24 HOURS BEFORE INITIAL TESTING.AFTER EMERGENCY LIGHT HAS BEEN POWERED DO NOT TURN OFF FOR EXTENDED PERIODS OF TIME.EXIT SIGNS, EMERGENCY LIGHTS AND NIGHT LIGHTS SHALL NOT BE SWITCHED.IN AREAS OF OPEN STRUCTURE, MOUNT STRIP FIXTURE TO BOTTOM CHORD OF BAR JOIST, UNLESS NOTED OTHERWISE.PROVIDE SEPARATE BOXES FOR GANGED SWITCHES ON SEPARATE BRANCH CIRCUITS.FIXTURES DENOTED WITH "ABJ" ARE TO BE FASTENED ON UNISTRUT CHANNELS MOUNTED TO THE BOTTOM SIDE OF THE TOP CHORD OF BAR JOISTS. LOCATE THE FIXTURES RUNNING PERPENDICULAR TO BAR JOISTS WITHIN BAR JOISTS WEBBING SPACES. DO NOT FASTEN FIXTURE OR UNISTRUT CHANNELS TO ROOF DECK.GENERAL LIGHTING NOTES01.31.201.2.3.4.5.6.7.OCCUPANCY SENSORS IN RESTROOMS SHALL BE PROGRAMMED FOR AUTOMATIC ON AND MAXIMUM AVAILABLE TIME DELAY SETTINGS.OCCUPANCY SENSORS IN DELI, PRODUCE, AND BAKERY PREP AREAS SHALL BE PROGRAMMED WITH MAXIMUM AVAILABLE TIME DELAY SETTINGS.OCCUPANCY SENSORS IN WALK-IN COOLERS/FREEZERS SHALL BE LOW TEMPERATURE RATED, WALL MOUNTED 6" ABOVE DOOR. ADJUST AIMING FOR MAXIMUM COVERAGE, 10 MINUTE TIME DELAY.ALL OTHER OCCUPANCY SENSORS SHALL BE PROGRAMMED WITH THE MINIMUM AVAILABLE TIME DELAY SETTING UNLESS NOTED OTHERWISE.ALL SINGLE-POLE OCCUPANCY SENSORS SHALL BE PROGRAMMED FOR MANUAL ON LIGHTING CONTROL UNLESS NOTED OTHERWISE.ALL BI-LEVEL OCCUPANCY SENSORS SHALL BE PROGRAMMED FOR AUTOMATIC ON LIGHTING CONTROL FOR 50% OF FIXTURES AND WITH MANUAL ON MODE FOR REMAINING FIXTURES.WHERE TWO OCCUPANCY SENSORS ARE SHOWN IN THE SAME LOCATION WIRE FOR PARALLEL OPERATION.OCCUPANCY SENSOR NOTES01.31.20ISSUE BLOCK
OSOSOSOSAAH6PICKUP FREEZERPICKUP COOLERREFRIGERATION EVAPORATIVE COIL, TYPaba abLPU-1350 TYPG1TYP16.12516.125PICKUP CANOPY LIGHT FIXTURE FURNISHED WITH CANOPY, INSTALLED BY G.C.RELOCATE EXISTING EMERGENCY LIGHT TO BELOW NEW CANOPY ROOFEXISTING WALL PACK16.131HALLWAY16.12516.133architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E1.1ENLARGEDLIGHTINGPLANSKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PN"OW" FIXTURES AND LAMPS ARE FURNISHED BY THE OWNER FOR INSTALLATION BY THE CONTRACTOR. "GC" FIXTURES AND LAMPS ARE FURNISHED AND INSTALLED BY THE CONTRACTOR.LIGHT FIXTURE SCHEDULETYPESUPPLIEDBYDESCRIPTIONVENDOR /MANUFACTURERMODEL VOLTAGEINPUTVACOLORTEMPLIGHT SOURCELAMPQTYMOUNTING COUNT50 OW 4' SEALED STRIP LSI INDUSTRIES INC W/M EG3 4 LED 6L DA S UNV DIM 40 980 SL 120/277 50 VA 4000K INTEGRAL LED - SURFACE 4 1/4" = 1'-0" 1OGP COOLER/FREEZER LIGHTING PLANISSUE BLOCK 1/4" = 1'-0" 2OGP DOOR LIGHTING PLANKEYNOTES16.125 EXISTING LIGHT FIXTURES TO REMAIN UNLESSNOTED OTHERWISE.16.131 CONNECT TO EXISTING CIRCUIT.16.133 EXISTING LIGHT FIXTURES TO BE RELOCATED TONEW LOCATION AS SHOWN.
BADBADAAAA AAAA A A A A A A A A A A A AAAAAAAAAAAAAAAAAAAAAAAAAAA A A A A A A A A A AAAAAAAAAAAAAAAAAAAAAAAAAAADD DD DD DD DD DD DD DD DD DD DD DD DDA A A AA A AA AACLCLCLCLCLCLCLYAAAAAAAAAAAAAA A A AAAAAAADDDDDDDDDDCLDD DD DD WWWWDD DD DD DD DD DD DDAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AAAAAFFFSSLASSLSSLSSL SSLSSLSSLSSLAAAAFFFDD DDAAAT1 T1T1T1T1 T1T1 T1T1T1T1 T1T1T1T1 T1T1 T1T1T1T1T1T1T1T1T1T1T1T1T1D1UUUUUUUUUUA2TLL92DDE42E44E43SALESEDC4EDC2ABCDEFGHIJ12345678910111213ROOFTOPREFRIGERATIONRACK AROOFTOPREFRIGERATIONRACK DROOFTOPREFRIGERATIONRACK BROOFTOPREFRIGERATIONRACK EPANELCHFAPANELCHFDPANELCHFBPANELCHFEPANELCHLROOFTOPREFRIGERATIONRACK FPANELCHFFROOFTOPREFRIGERATIONRACK CPANELCHFCEDC1PANELLVCPANELLHCPANEL L2UEXISTING UPSPANELLTS1VISION CENTER HAIRCAREEQUIPMENTROOMTENANTSPACEPHARMACYPANELLRXGARDEN CENTERPANELHGCPANELLGCPANEL H3BTRANSFORMERT3DPANEL L3DSTORAGETLEPANELLFSFOODTENANTE2.11E2.12E2.14E2.13architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E2POWER PLANKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PN 1" = 20'-0" 1POWER PLAN1.2.3.4.A.B.C.5.A.B.C.TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO TOP SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL FURNISHED POWER POLE AND TERMINATE WIRING TO JUNCTION BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO SECURE TELEPOWER POLE PLUMB TO BUILDING STRUCTURE. REF POWER POLE CONNECTION DETAIL.PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT AND WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION POINT.WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE RATING DIFFERS FROM SIZE PROVIDED, NOTIFY WALMART CONSTRUCTION MANAGER IMMEDIATELY TO COORDINATE RESOLUTION.ELECTRONIC FIRE PROTECTION/SECURITY ALARM BOXES AND CONDUITS SHOWN ON POWER PLANS SHALL BE PROVIDED UNDER THIS CONTRACT. IN ADDITION, UNLESS NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES APPLY:ALL ALARM JUNCTION BOXES SHALL BE 4"X4"X2-1/8" MINIMUM.ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH PULL WIRE AND INSULATING BUSHINGS AT END OF VERTICAL RACEWAY RUN.VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE EITHER CONCEALED INSIDE WALL OR SURFACE MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL VERTICAL RUNS SHALL BE TURNED 90-DEGREES AT TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE BY VERTICAL FLOOR TYPE LIFT.UPON COMPLETION OF ELECTRICAL INSTALLATION AND PRIOR TO ENERGIZING CIRCUIT:INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.PERFORM CONTINUITY TEST.VERIFY PROPER PHASING CONNECTION TO ALL THREE PHASE MOTOR LOADS.GENERAL POWER NOTES07.26.19ISSUE BLOCK
AAAAAAJJJJJJJJJAJJJJAJJJAAH45OGP STORAGE16.492ELECTRICAL DEVICES AND UNUSED CIRCUITRYDEMO'ED PANEL L1R, XFMR T1R, DISCONNECT-REF1E417' - 3"16.492H456NEW XFMR TPU(AT STRUCTURE)-REF1E4NEWPANELLPUNEWPANELHPU-REF1E41E3MANAGER,STATION, +54"PRINTER16.71516.715OGP COOLEROGP FREEZERAIR DOOR AND CONTROL PANEL:PROVIDE POWER FROM DISCONNECT TO AIR DOOR CONTROL PANEL. PROVIDE AND INSTALL ALL INTERCONNECT WIRING BETWEEN THE CONTROL PANEL, AIR DOOR, AND DOOR INTERLOCK SWITCH PER MANUFACTURER'S INSTRUCTIONS.30A/3P/NF, +60"E.C. SHALL FIELD DETERMINE AND COORDINATE EXACT LOCATION OF TRANSFORMER (AND SECONDARY BREAKER, IF APPLICABLE) WITH EXISTING OBSTRUCTIONS AND GC. ENSURE ALL NEC REQUIREMENTS ARE MET AND CLEARANCES ARE MAINTAINED. PROVIDE LABEL THAT XFMR TPU IS FED FROM PANELBOARD HPU.AIR DOOR AND CONTROL PANEL:PROVIDE POWER FROM DISCONNECT TO AIR DOOR CONTROL PANEL. PROVIDE AND INSTALL ALL INTERCONNECT WIRING BETWEEN THE CONTROL PANEL, AIR DOOR, AND DOOR INTERLOCK SWITCH PER MANUFACTURER'S INSTRUCTIONS.-HPU 2,4,630A/3P/NF, +60"16.6202E3TYPHPU-8,10,1216.62016.609LPU-9LPU-11WPWP WP16.71216.71216.71216.712LPU-7WPLPU-15+10'-0",WASTE PUMP P11G116.14516.232-L4D1 7616.508+54"+102" AFF3/4"CE.C. TO INSTALL J-BOX AT +3'-8" TO BOTTOM OF J-BOX ON BOTH SIDES OF WALL FOR CARD SWIPE AND RUN 3/4" CONDUIT ABOVE CEILING.HALLWAYG1HALLWAY16.492ELECTRICAL DEVICES AND UNUSED CIRCUITRYarchitecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E2.1ENLARGEDPOWER PLANSKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PNKEYNOTES16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCHCIRCUITRY. MINIMUM WIRE SIZE ANDPANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE,RATING AND CONDITION OF EXISTING BRANCHCIRCUIT CONDUIT AND WIRE PRIOR TO USE TOENSURE THAT THEY MEET REQUIRED SIZE, ANDALL U.L. RATINGS AND REPLACE AS REQUIRED.16.232 AUTOMATIC DOOR OPERATOR: VERIFYLOCATION WITH MANUFACTURER'SRECOMMENDATIONS PRIOR TO INSTALLATION.ALL DOOR CONTROLS INCLUDING LOW VOLTAGEROUGH-IN CONDUIT, BACKBOXES AND WIRINGBY OTHERS.16.492 E.C. SHALL COORDINATE WITH GENERALCONTRACTOR AND ARCHITECTURALDEMOLITION PLANS THE EXTENT OF ELECTRICALDEMOLITION. REMOVE UNUSED DEVICES,BOXES, CONDUITS, AND WIRING BACK TOORIGINATING JUNCTION BOXES ORPANELBOARDS. REFERENCE POWER PLANS FORCIRCUITRY TO BE REUSED. DEMOLITION SHALLNOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT ISDEMOLISHED ALL THE WAY TO PANELBOARD,REMOVE CIRCUIT BREAKER AND REPLACE WITHFILLER PLATER. UPDATE TYPEWRITTEN CIRCUITDIRECTORY IDENTIFYING CIRCUIT AS "SPACE".COORDINATE EXACT REQUIREMENTS WITHEXISTING CONDITIONS PRIOR TO BID.16.508 INSECT CONTROL: PROVIDE BROWN DEVICE ANDMATCHING COVERPLATE.16.609 INSTALL FURNISHED ALARM JUNCTION BOX AT+80”, PENETRATE COOLER WALL, AND ROUTEVERTICAL RACEWAY UP EXTERIOR SIDE OFCOOLER WALL TO STRUCTURE. MINIMIZEEXPOSED CONDUIT ROUTED INSIDE COOLERBOXES. COORDINATE EXACT LOCATION WITHFIRE ALARM INSTALLER PRIOR TO ROUGH-IN.16.620 INVENTORY MANAGEMENT SYSTEM: PROVIDE3/4" CONDUIT FROM JUNCTION BOX TOSTRUCTURE AND TERMINATE WITH BUSHINGS.PROVIDE 1" CONDUIT SLEEVE THRUCOOLER/FREEZER WALL ADJACENT TOJUNCTION BOX. SEAL CONDUIT SLEEVEPENETRATION WITH SILICONE SEALANT.COORDINATE EXACT LOCATION AND MOUNTINGHEIGHT WITH ISD CABLE VENDOR PRIOR TOINSTALLATION16.712 SURFACE MOUNT WP JUNCTION BOX ON WALL24" BELOW COOLER/FREEZER BOX CEILING FORCONDENSATE DRAIN HEAT TRACE TAPE.PROVIDE LIQUID-TIGHT FLEXIBLE METALCONDUIT CONNECTION TO HEAT TAPE.16.715 JUNCTION BOX PROVIDED WITHCOOLER/FREEZER PANEL FOR CONNECTION TOLIGHTS, DOOR HEATERS AND/OR HEATEDVENTS. PROVIDE WEATHERPROOF EXTENSIONAND COVERPLATE FOR RECESSED JUNCTIONBOXES AS REQUIRED. FINAL TERMINATIONS BYR.C. 1/8" = 1'-0" 1OGP AREA DEMO POWER PLAN 1/4" = 1'-0" 2OGP AREA POWER PLAN 1/4" = 1'-0" 4PICKUP DOOR POWER PLANISSUE BLOCK 1/8" = 1'-0" 3PICKUP DOOR AREA DEMO POWER PLAN
TRANSFORMERCEILING MOUNTING BRACKETS AS FURNISHED BY TRANSFORMER MANUFACTURER OR USE 2"x2"x1/4" ANGLES. BOLT TRANSFORMER TO BRACKETS OR ANGLESBAR JOIST3"x2"x1/4" STEEL ANGLES BETWEEN BAR JOIST ON EACH SIDE OF TRANSFORMER. MOUNT ANGLE WITHIN 4" OF PANEL POINT (WHERE WEB BRACING ATTACHES TO BOTTOM CHORD). BOLT OR CLAMP ANGLES TO BAR JOIST. DO NOT CUT OR DRILL HOLES IN BAR JOIST1/2" THREADED STEEL ROD. DRILL 5/8" HOLES THROUGH ANGLES AND INSTALL LOCK WASHERS AND NUTS ON EACH SIDE TYPROOF DECK.6" MININSTALL TRANSFORMER AS HIGH AS POSSIBLE WITHIN JOIST SPACE. MAINTAIN A MINIMUM OF 6" CLEARANCE FROM ROOF DECK6' - 0" MAXIMUM SPACINGPROVIDE SEISMIC BRACINGAS REQUIRED BY STATE ORLOCAL ORDINANCES.JUNCTION BOXFRONTSIDE3/4" CONDUIT CLAMP WITH PURLIN CLIP3/4" CONDUIT CLAMPAS NEEDED 3/4" CONDUIT CLAMPAS NEEDED JUNCTION BOX3/4" CONDUIT CLAMP WITH PURLIN CLIPTERMINATE WITH THREADED BUSHINGTERMINATE WITH THREADED BUSHINGEXTEND SLEEVE 2" INTO BOX AND TERMINATE WITH THREADED BUSHING12"12"architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E3ELECTRICALDETAILSKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PNARSOSBDHJSSOS2SOSS3S4SDSMSVSSKSS SINGLE POLE SWITCH CIRCUIT, CONCEALED IN WALLS ORCEILING, E INDICATES EXISTING WIRINGSMOKE DETECTORSAIL SWITCHJUNCTION BOXHORN / STROBEABBREVIATIONSBUZZERCIRCUIT, CONCEALED IN SLAB FLOOR,E INDICATES EXISTING WIRINGCONDUIT SLEEVESURFACE MOUNTED PANELBOARDFLUSH MOUNTED PANELBOARDCIRCUIT, EXPOSED,E INDICATES EXISTING WIRINGLOW VOLTAGE WIRINGTELEPOWER POLETELEPHONE / DATA BOX FOR ISDTELEPHONE, FLUSH FLOORPUSH BUTTONMOTORALARM JUNCTION BOX,FOR REMOTE TEST/RESET(WALL MOUNTED/CEILING MOUNTED)EQUIPMENT CONNECTION POINT(PROVIDED WITH EQUIPMENT)NON-FUSED DISCONNECTRECEPTACLE, PLUG-MOLDRECEPTACLE, SIMPLEXRECEPTACLE, SPECIALJUNCTION BOX(WALL MOUNTED/CEILING MOUNTED)ALARM JUNCTION BOX,(WALL MOUNTED/CEILING MOUNTED)RECEPTACLE, DOUBLE DUPLEX,ISOLATED GROUNDFUSED DISCONNECT4-WAY SWITCHRECEPTACLE, DUPLEX ISOLATEDGROUND FLUSH FLOORRECEPTACLE, DOUBLE DUPLEXRECEPTACLE, DUPLEX FLUSH FLOORVARIABLE SPEED SWITCHKEYED SWITCHDIMMER SWITCHRECEPTACLE, DUPLEX,MOUNTED HORIZONTALLYRECEPTACLE, DUPLEXMANUAL MOTOR SWITCH3-WAY SWITCHRECEPTACLE, DUPLEXISOLATED GROUNDLIGHT FIXTURE,NIGHT LIGHTVOLUMETRIC LIGHT FIXTURELIGHT FIXTURE(WALL MOUNTED/CEILING MOUNTED)LIGHT FIXTURE(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)SYMBOL DESCRIPTIONRECEPTACLE, DUPLEX TWIST LOCK,ISOLATED GROUND, L5-15R, UNOSINGLE POLE OCCUPANCY SENSOR SWITCHLOW VOLTAGE CABLEBOX FOR OTHERDOOR HOLD OPENRECEPTACLE, DUPLEX TWIST LOCK,L5-15R, UNORECEPTACLE, SIMPLEX TWIST LOCK,ISOLATED GROUND, L5-15R, UNORECEPTACLE, SIMPLEX TWIST LOCK,L5-15R, UNOCEILING MOUNTED OCCUPANCY SENSOR SWITCHRECEPTACLE, GFIDOUBLE POLE OCCUPANCY SENSOR SWITCHTTHERMOSTAT(WALL MOUNTED/CEILING MOUNTED)EXIT FIXTURE(WALL MOUNTED/CEILING MOUNTED)EMERGENCY LIGHT(WALL MOUNTED/CEILING MOUNTED)EMERGENCY LIGHT REMOTE HEADS(WALL MOUNTED/CEILING MOUNTED)a, b, c LOWER CASE LETTERS INDICATE SWITCHING CONFIGURATIONAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEC CONDUITCCT CIRCUITCF CEILING FANCW CASH WRAPEC ELECTRICAL CONTRACTOREF EXHAUST FANETR EXISTING TO REMAINEWC ELECTRIC WATER COOLERG GROUNDGC GENERAL CONTRACTORGFEP GROUND FAULT EQUIPMENT PROTECTIONGFI GROUND FAULT CIRCUIT INTERRUPTERHD HAND DRYER IG ISOLATED GROUNDLCU LIGHTING CONTROL UNITNL NIGHT LIGHTNTS NOT TO SCALEREC REFRIGERATION ELECTRICAL CONTRACTORRC REFRIGERATION CONTRACTORRH RADIANT HEATERSC SECURITY CAMERATR TAMPER RESISTANTTYP TYPICALUH UNIT HEATERUNO UNLESS NOTED OTHERWISEWH WATER HEATERWP WEATHER PROOFWR WEATHER RESISTANTELECTRICAL SYMBOLS LEGENDTIME CLOCKTCTRACK LIGHTING03.29.191.A.B.C.D.E.2.A.B.C.D.3.4.A.B.C.5.6.7.8.9.10.11.12.13.14.15.16.A.B.C.D.17.A.B.C.D.E.F.18.19.A.B.C.D.FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS, READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURER'S RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR WALLS.ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE OPERATIONS. COORDINATE ALL DISRUPTIONS WITH WALMART CONSTRUCTION MANAGER AND STORE MANAGER.CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS BEFORE INSTALLING BOXES. FURNISH AND INSTALL EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED.CONTRACTOR SHALL VERIFY THAT ALL AFFECTED PANELBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS PROPERLY COVERED ANDTHAT ALL TRIM IS IN GOOD CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE STOPPING.NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM SEALANT.EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY PENETRATIONS.PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE PER NEC) IN PVC TYPE CONDUIT, POWER AND LIGHTING CIRCUITS, ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600 VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT GROUNDING CONDUCTOR.WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH MASONRY:SWITCHES +44"RECEPTACLES +20"VOICE/DATA +20"WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS.CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS AFFECTED BY REMODEL.NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT PROTECTIVE DEVICES.BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION (15-FT MAXIMUM).WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND DERATE CURRENT CARRYING CONDUCTORS PER NEC.PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH CIRCUITS PER NEC REQUIREMENTS.SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE SURFACE MOUNTED UNLESS NOTED OTHERWISE. SEAL DEVICES TO COOLER/FREEZER PANELS WITH SILICONE SEALANT.SURFACE MOUNTED CONDUIT ON COOLER/FREEZER PANELS OR IN FOOD PREP AREAS SHALL BE INSTALLED WITH GALVANIZED 1/2" STANDOFF CONDUIT HANGERS TO ALLOW FOR CLEANING.ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE INSTALLED UNDER SLAB. PROVIDE EXTERIOR COATED GRC BENDS ON ALL CONDUIT RUNS THAT HAVE 45 DEGREE BENDS OR GREATER. REFER TO SPECIFICATION SECTION 16.100 FOR UNDER SLAB.SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY LOCAL CODES.EXISTING ELECTRICAL AND ALARM:WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING OPERATION.IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT EXISTING UNDERGROUND SERVICES (ELECTRICAL, TELEPHONE, PARKING LOTLIGHTING CIRCUITRY, ETC.) PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES TO MAINTAIN THEIR EXISTING OPERATION.EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO THAT SYSTEMS REMAIN OPERATIONAL AT ALL TIMES.DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE NOTED.EXISTING ELECTRICAL DEMOLITION:GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL EQUIPMENT, CONDUIT AND CONDUCTORS AS INDICATED ON THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION. REMOVE ALL PANELBOARDS, DISCONNECT SWITCHES, BOXES, RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH WILL NOT BE REUSED.SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT, CONDUCTORS AND RELATED DEVICES SERVING SALES AREA GONDOLAS BEING RELOCATED OR REMOVED. EXISTING CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET REQUIREMENTS INDICATED ON PLANS AND ALL U.L. RATINGS. REMOVE ALL UNUSED CONDUIT AND CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SPACE". REMOVE CIRCUIT BREAKER AND REPLACE WITH FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT DIRECTORY IDENTIFYING CIRCUIT AS "SPACE".CONDUIT AND WIRING TO BE ABANDONED IN CEILING SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROUGH STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE. CONDUIT TO BE ABANDONED IN WALLS OR FLOORS SHALL BE REMOVED BACK TO FINISHED SURFACE AND CAPPED INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT.ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE REMOVED SHALL ALSO BE REMOVED. REMOVE CIRCUIT BREAKER AND REPLACE WITH FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT DIRECTORY IDENTIFYING CIRCUIT AS "SPACE".DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO SELECTIVE SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF LIGHT FIXTURE.BUILDING COMPONENTS ABANDONED BY THE SCOPE OF WORK SHALL BE SECURED TO PREVENT FALLING, LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE FUTURE.DATA AND PHONE CONDUIT INSTALLATION MILESTONE DATE:ALL RACEWAY AND CONDUIT SLEEVES FOR DATA AND PHONE CABLING TO BE INSTALLED 3 WEEKS PRIOR TO CONTRACT SUBSTANTIAL COMPLETION DATE.ETHERNET CABLE:FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON PLANS. PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES AND/OR ORDINANCES.ETHERNET CABLE IS FURNISHED BY OTHERS.ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER POLES.ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS DIRECTED BY WALMART CONSTRUCTION MANAGER.GENERAL NOTES08.02.19SCHEDULE GENERAL NOTES:ROUGH-IN NOTES:DROPcbaSURFACE MOUNT JUNCTION BOX AT +66" (UNO) WITH (1) 3/4" CONDUIT STUBBED TO ACCESSIBLE CEILING SPACE.FLUSH MOUNT JUNCTION BOX AT +20" (UNO) WITH (1) 3/4" CONDUIT ROUTED TO NEAREST ACCESSIBLE CEILING SPACE.FLUSH MOUNT JUNCTION BOX AT +20" (UNO) WITH (1) 3/4" CONDUIT STUBBED 12" ABOVE LAY-IN CEILING.1.2.3.4.5.6.7.8.ALL JUNCTION BOXES SHALL BE DOUBLE GANG WITH SINGLE GANG PLASTER RING UNLESS NOTED OTHERWISE ON SCHEDULE.ALL JUNCTION BOXES TO BE ROUGHED IN AT SCHEDULED HEIGHT UNLESS NOTED OTHERWISE ON DRAWINGS.ALL CONDUITS SHALL BE TERMINATED WITH BUSHINGS.PROVIDE PULL WIRE WITH EACH EMPTY RACEWAY (JUNCTION BOX/CONDUIT) INSTALLED.CONDUIT RUNS SHALL HAVE NO MORE THAN 90 DEGREES OF TRANSITION BETWEEN PULL BOXES.WHERE CONDUIT(S) TRAVERSE AREAS WITH CEILINGS OPEN TO STRUCTURE, CONDUIT(S) SHALL BE CONCEALED AS WELL AS POSSIBLE FROM VIEW FROM CUSTOMER AREA.FOR CONDUIT RUNS SCHEDULED WITH 1-1/2" OR LARGER CONDUIT UTILIZE LARGE RADIUS SWEEPS AT POINTS OF TRANSITION.ACCESSIBLE CEILING SPACE SHALL BE CONSIDERED 12 INCHES ABOVE A LAY-IN CEILING OR ABOVE BAR JOIST ACCESSIBLE BY A SCISSOR LIFT FOR AREAS OPEN TO STRUCTURE.VOICE/DATA ROUGH-IN SCHEDULE09.27.19NTS1SUSPENDED TRANSFORMER DETAILNTS2AP REPEATERISSUE BLOCK
CONNECTED LOADS TABLELOAD BREAKDOWN LOAD*NECDEMANDTOTAL KVA TOTAL AMPSHEATING/COOLING (DOMINANT LOAD ONLY)0.00 1.00 0.00 KVA 0.00 ALIGHTING 0.20 1.25 0.25 KVA 0.30 ARECEPTACLES 0.54 1.0 / 0.5 0.54 KVA 0.65 AKITCHEN EQUIPMENT 0.00 1.00 0.00 KVA 0.00 AREFRIGERATION / MISCELLANEOUS 27.79 1.00 27.79 KVA 33.43 ACONTINUOUS 0.00 1.25 0.00 KVA 0.00 ALARGEST MOTOR LOAD 0.00 1.25 0.00 KVA 0.00 AMOTOR LOADS 0.00 1.00 0.00 KVA 0.00 AEXISTING LOAD TO BE DELETED 9.85 1.00 9.85 KVA 11.85 A**EXISTING PEAK DEMAND 613.2 1.25 766.50 KVA 921.98 A***TOTAL - - - - - - 785.23 KVA 944.51 ASERVICE ENTRANCE CAPACITY 3325.44 KVA 4000.00 ASPARE SERVICE CAPACITY 2540.21 KVA 3055.49 A* IN ACCORDANCE WITH NEC 220-35 (FOR INFORMATION ONLY)** PEAK DEMAND BASED ON 12 MONTH DEMAND HISTORY FROM OWNER*** POWER COMPANY SHALL APPLY PROPER DEMAND FACTORS TO CALCULATE NEW ESTIMATED TOTALMAXIMUM DEMANDCLUTILITY TRANSFORMER480Y/277V, 3P, 4W SEC(EXISTING)MSB - 4000 AMP BUS - 480/277V, 3PH, 4W (EXISTING)600A3PA-1L-O"QC" BREAKERSHUNT TRIPGFRST1600A -3P MAIN1600A -3P MAIN800A3P400A3P600A3P300A3P600A3PA|1L-OSHUNT TRIPGFRSTBREAKER4000A -3P MAINKWH"QC" BREAKER SECTIONMAIN BREAKER SECTIONDISTRIBUTION SECTION500A3PCT CABINETBY CONTRACTORCTEXISTPNLBDH1A480VEXISTPNLBDH1B480/277VEXISTPNLBDH1P1480/277VEXISTPNLBDH1P2480/277VT1D150KVA480V-208Y/120V(EXISTING)T1D325KVA480V-240/120V(EXISTING)150A2PEXISTINGEXISTPNLBDL1D3240/120VEXISTPNLBDL1D1208/120VEXISTPNLBDL1D2208/120VEXISTPNLBDL1U240/120VEXISTUPSSYSTEMUPS ROOMEDC1EXISTPNLBDH2B480/277VEXISTPNLBDH2A480VEXISTPNLBDH2P480/277VEXISTPNLBDL2P208/120VEXISTPNLBDL2D1208/120VEXISTPNLBDL2B208/120VEXISTPNLBDLVC208/120VVISIONCENTEREXISTPNLBDLRX208/120VPHARMACYEXISTPNLBDLHC208/120VHAIRCAREEXISTPNLBDLTS1208/120VTENANTEXISTPNLBDL2D3208/120VEDC2EXISTPNLBDL2D2208/120VEQUIPMENTROOMEXISTPNLBDL2U240/120VEXISTUPSSYSTEMEXISTPNLBDH3B480/277VT3D112.5KVA480V-208Y/120V(EXISTING)EXISTPNLBDL3D208/120VT2D225KVA480V-208Y/120V(EXISTING)175A3PEXISTINGEXISTPNLBDLGC208/120VEXISTPNLBDHGC480/277VGARDEN CENTER400A3PEXISTPNLBDH4B1480/277VEXISTPNLBDH4B2480VEXISTPNLBDH4B3480VEXISTPNLBDH4C480/277VT4D150KVA480V-208Y/120V(EXISTING)TFS75KVA480V-208Y/120V(EXISTING)225A3PEXISTINGEXISTPNLBDL4D1208/120VEXISTPNLBDL4D2208/120VEDC4EXISTDIESELGENERATORTLE STORAGEKWHPLMEXISTPNLBDLFS208/120VFOOD TENANT200A, 3P200A, 3PEXISTFIREPUMPCTRLEXISTFIREPUMP100HPSPRINKLER ROOMT1R30KVA480V-208/120V(DEMO)DEMOPNLBDL1R208/120VPICKUPSTORAGETPU45KVA480V-208Y/120V(NEW)NEWPNLBDLPU208/120V1-1/4"C, (4)#2 CU, (1)#6 CU GREXISTPNLBDHPU480/277V3,8462,602#6 CU GND PER NEC2,2791-1/2"C, (4)#1/0 CU, (1)#6 CU GR1"C, (3)#4 CU, (1)#8 CU GR100A3P16.472(100A-3P)MSB-2,4,61E3(70A-3P)H1B-13,15,1716.47232,54532,198DISCONNECT(DEMO)IF IT IS NECESSARY TO REMOVE A METER, RTU SERVER, CT OR DISRUPT THE COMMUNICATION OF THE SYSTEM, THE CONTRACTOR IS RESPONSIBLE TO RESTORE THE SYSTEM TO THE SAME LEVEL OF OPERATION THAT EXISTED PRIOR TO THE WORK BEING INITIATED. THE EXISTENCE AND FUNCTIONALITY OF THE SYSTEM SHALL BE VERIFIED BY CALLING WALMART BUILDING PERFORMANCE TEAM AT 479-204-0432 BETWEEN THE HOURS OF 7 AM UNTIL 5 PM CT.EXISTING DISTRIBUTION SYSTEM IS SERIES RATED. E.C. SHALL PROVIDE CIRCUIT BREAKER(S) THAT WILL MAINTAIN EXISTING MANUFACTURER'S U.L. LISTED SERIES RATED SYSTEM. REPRESENTS THE AVAILABLE FAULT CURRENT IN RMS SYMMETRICAL AMPERES AT THE RESPECTIVE TRANSFORMER, PANEL OR EQUIPMENT. FAULT CURRENT CALCULATIONS ARE BASED ON AVAILABLE FAULT CURRENT OF 32,545 AMPS AT SECONDARY TERMINALS OF THE UTILITY TRANSFORMER AS PROVIDED BY TEH POWER COMPANY.XX,XXXFURNISH AND INSTALL A TYPED CIRCUIT DIRECTORY IN EACH NEW PANELBOARD AND EACH EXISTING PANELBOARD AFFECTED BY CHANGE.16.49216.49216.49216.49216.492I11MSB1MSB2MSB3ALARM BOARDTELEPHONEBOARDALARM BOARDH1BH1AH1P2 H1P1T1DL1D1L1D2TPLLPL BRKRL1ULPLEMS BOARDB9T2DL2BL2D1/L2D2STACKEDL2D3/SPACESTACKEDL2PH2PH2BH2A1H4B3H4B2H4B1H4CTFS/T4DSTACKEDL4D2L4D1LEAK DETECTIONNOVAREDC4L4D1-7816.72316.72316.470LDPES1 BAS CONTROLLERGROUND WIRE SIZING CHARTBREAKER AMPACITYWIRE WIRE SIZE15-2025-3035-50607080-90100PHASEGROUNDPHASEGROUNDPHASEGROUNDPHASEGROUNDPHASEGROUNDPHASEGROUNDPHASEGROUND#12#12#10#10#8#10#6#10#6#8#4#8#3#8#10#10#8#8#6#8#4#6#4#4#3#6#2#6#8#8#6#6#4#4#3#6#3#4#2#4#1#4#6#6#4#4#3#4#2#4#2#3#1#4#1/0#4#4#4#3#3#2#4#1#4#1#2#1/0#3#2/0#3WIRE SIZES PER NEC 250.122 (B)DRY TYPE TRANSFORMER SCHEDULETRANS.KVAPRIMARYSECONDARYMOUNTING LOCATIONVOLTS PHASE WIRESVOLTS PHASE WIRESTPU45480V 3PH 3W208/120V 3PH 4WSUSPENDED, NEMA-1WITH TAPSNOTES A,B, REFDRY TYPE TRANSFORMER NOTES:A.GROUND IN ACCORDANCE WITH NEC 250-30.B.CLEARANCE FOR VENTILATING OPENINGS SHALL BE NO LESS THAN THATREQUIRED ON MANUFACTURER'S NAMEPLATE. NEC 110-13(B),450-9 AND 450-11.architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E4ELECTRICALONE-LINEDETAILS ANDSCHEDULESKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PNNTS1ONE-LINE DIAGRAMCOORDINATE ALL CHANGES TO EXISTING ELECTRICAL SERVICE AND METERING WITH UTILITY COMPANY. STORE ADDRESS: WALMART SUPERCENTER #3705 GENERAL REMODEL 17100 WA-507 YELM, WA, 98597 UTILITY COMPANY: PUGET SOUND ENTERGY CONTACT: TRISHA STRIL EMAIL: PATRICIA.STRIL@PSE.COM PHONE: (425) 766-2961ARC FLASH HAZARD WARNING LABELING REQUIREMENTS PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE CONTRACT.ARC FLASHCOORDINATE ALL WORK THAT REQUIRES POWER INTERRUPTIONS TO THE STORE WITH THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES NOT HAVE A MAIN SERVICE DISCONNECTING MEANS, COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF TWO WEEKS IN ADVANCE OF THE STORE POWER INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE ACCOMPLISHED AFTER NORMAL STORE BUSINESS HOURS. PROVIDE TEMPORARY POWER AS REQUIRED PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND THE POWER SYSTEM TESTED AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER.POWER INTERRUPTION NOTE11.30.18NOTE:ALL OF THE ELECTRICAL DEVICES SHOWN ON THE RISER DIAGRAM ARE EXISTING AND ARE BASED UPON AS-BUILT DRAWINGS. E.C. SHALL VERIFY THE EXACT EXISTING CONDITIONS, SIZES AND LOCATIONS OF EQUIPMENT PRIOR TO ROUGH-IN. THIS RISER IS SHOWN FOR INFORMATIONAL PURPOSES ONLY AND ANY NEW DEVICES ARE SHOWN IN BOLD AND ARE NOTED. DURING CONSTRUCTION, THE STORE SHALL STAY OPEN FOR BUSINESS. ANY NECESSARY POWER DOWNTIME SHALL BE SCHEDULED AND APPROVED BY WALMART CONSTRUCTION MANAGER.NEW EQUIPMENTEXISTING EQUIPMENTEQUIPMENT TO BE DEMOLISHEDONE-LINE DIAGRAM LEGEND11.19.1020A WIRE SIZING SCHEDULE385 FT.770 FT.930 FT.620 FT.1865 FT.255 FT.ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE.THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM.6-10 AMPS1-5 AMPS120 VOLT11-15 AMPS6-10 AMPS1-5 AMPS277 VOLT11-15 AMPS#8#12#10380 FT.760 FT.250 FT.240 FT.480 FT.160 FT.585 FT.1170 FT.390 FT.325 FT.110 FT.160 FT.#12200 FT.70 FT.100 FT.490 FT.165 FT.245 FT.#10#8#6#6 1/4" = 1'-0" 2EDC1 POWER PLAN 1/4" = 1'-0" 3EDC2 POWER PLAN 1/4" = 1'-0" 4EDC4 POWER PLANKEYNOTES16.470 FURNISH AND INSTALL NEW 20 AMP, 120 VOLTCIRCUIT(S). FEED FROM PANELBOARD ASINDICATED. PROVIDE 20A-1P CIRCUIT BREAKERIF NEEDED. E.C. SHALL MATCH MANUFACTURER,TYPE AND AIC RATINGS OF EXISTING CIRCUITBREAKERS.16.472 FURNISH AND INSTALL NEW CIRCUIT BREAKER(##A-#P) IN EXISTING PANELBOARD INDICATED.E.C. SHALL MATCH MANUFACTURER, TYPE ANDAIC RATINGS OF EXISTING CIRCUIT BREAKERS.16.492 E.C. SHALL COORDINATE WITH GENERALCONTRACTOR AND ARCHITECTURALDEMOLITION PLANS THE EXTENT OF ELECTRICALDEMOLITION. REMOVE UNUSED DEVICES,BOXES, CONDUITS, AND WIRING BACK TOORIGINATING JUNCTION BOXES ORPANELBOARDS. REFERENCE POWER PLANS FORCIRCUITRY TO BE REUSED. DEMOLITION SHALLNOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT ISDEMOLISHED ALL THE WAY TO PANELBOARD,REMOVE CIRCUIT BREAKER AND REPLACE WITHFILLER PLATER. UPDATE TYPEWRITTEN CIRCUITDIRECTORY IDENTIFYING CIRCUIT AS "SPACE".COORDINATE EXACT REQUIREMENTS WITHEXISTING CONDITIONS PRIOR TO BID.16.723 REFRIGERATION BUILDING AUTOMATIONSYSTEM CONTROLLER INSTALLED BY BASCONTRACTOR. ALL 120VAC FINAL TERMINATIONSAT ENCLOSURE BY R.C. VERIFY EXACTLOCATION OF ENCLOSURE WITH BASCONTRACTOR.1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20.21.22.23.24.25.1.2.3.TERMINATE GROUND ON ISOLATED GROUND BUS.INSTALL LOCKING DEVICE (LOCK-OFF FOR MAINTENANCE). LOCKING DEVICE SHALL BE UL LISTED. MANUFACTURER SHALL MATCH EXISTING PANELBOARD MANUFACTURER.INSTALL LOCKING DEVICE (LOCK-ON FOR CRITICAL LOAD).GFI BREAKER FOR PERSONNEL PROTECTION (5MA).GFI BREAKER FOR EQUIPMENT PROTECTION (30MA).CONDUCTOR SIZE HAS BEEN INCREASED FOR VOLTAGE DROP. SIZE EQUIPMENT GROUNDING CONDUCTOR PROPORTIONATELY PER NEC.REFER TO ONE-LINE DIAGRAM FOR AVAILABLE FAULT CURRENT FOR INTERRUPT RATINGS.REFER TO ONE-LINE DIAGRAMS FOR WIRE SIZES.FACTORY WIRED TO LOAD.BREAKER SHALL BE HIGH MAGNETIC TYPE.BREAKER REMOVAL - FIELD VERIFY CIRCUIT BREAKER IS NOT SERVING AN EXISTING LOAD. IF NO EXISTING LOAD, REMOVE CIRCUIT BREAKER AND PROVIDE FILLER PLATE. IF BREAKER IS SERVING A LOAD, IDENTIFY LOAD SERVED. UPDATE CIRCUIT IDENTIFICATION SCHEDULE AS "SPACE" OR INDICATE LOAD SERVED.DUAL TAP SOLENOID OPERATED BREAKER. CONNECT EMERGENCY/NIGHT LIGHTING TO UNSWITCHED TERMINATION.EXISTING CIRCUIT AND/OR CIRCUIT BREAKER.ROUTE CIRCUIT THROUGH CONTACTOR.PROVIDE INTERLOCK WIRING WITH EXHAUST HOOD ANSUL SYSTEM.RELOCATED CIRCUIT FROM EXISTING PANELBOARD.PROVIDE BLANK CIRCUIT BREAKER FILLER PLATE FOR EXPOSED SPACE IN PANELBOARD.PROVIDE U.L. LISTED OVERCURRENT DEVICE TO COORDINATE AND MAINTAIN MANUFACTURER'S SERIES RATED SYSTEM.EXISTING CIRCUIT BREAKER TO REMAIN. VERIFY CONDITION OF CIRCUIT BREAKER TO ENSURE THAT IT IS OPERATIONAL AND MEETS ALL U.L. RATINGS.ROUTE CIRCUIT THROUGH EXISTING LCU CABINET UTILIZING EXISTING RELAY AND CONTROLS. UPDATE LCU IDENTIFICATION SCHEDULE WITH LOAD IDENTIFICATION.SOLENOID OPERATED CIRCUIT BREAKER. REFER TO ENERGY MANAGEMENT PLANS FOR CIRCUIT BREAKER CONTROL.EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY LOAD AND UPDATE CIRCUIT IDENTIFICATION SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN USE, REFER TO PANELBOARD NOTE (11).ROUTE CIRCUIT THROUGH ENCLOSED GFI BREAKER FOR PERSONNEL PROTECTION (5MA).SPARE - FIELD VERIFY CIRCUIT BREAKER IS NOT SERVING AN EXISTING LOAD. IF NO EXISTING LOAD, PROVIDE LOCK OFF DEVICE TO LOCK SPARE BREAKER IN THE OFF POSITION. IF BREAKER IS SERVING A LOAD, IDENTIFY LOAD SERVED. UPDATE CIRCUIT IDENTIFICATION SCHEDULE AS "SPARE" OR INDICATE LOAD SERVED.EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY LOAD AND UPDATE CIRCUIT IDENTIFICATION SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN USE, REFER TO PANELBOARD NOTE (24).GENERAL NOTES:NEW OVERCURRENT PROTECTIVE DEVICES PLACE IN EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT PROTECTION DEVICES IN SAID BOARD.E.C. SHALL TRACE ALL ELECTRICAL CIRCUITS FOR EVERY EXISTING PANELBOARD AFFECTED BY THIS PROJECT. IDENTIFY LOADS ON EACH CIRCUIT. PROVIDE A COMPLETE TYPEWRITTEN CIRCUIT IDENTIFICATION SCHEDULE FOR EVERY AFFECTED PANELBOARD.ALL OVERCURRENT DEVICES ARE NEW UNLESS NOTED OTHERWISE.PANELBOARD NOTES ()08.28.20PER NEC ARTICLE 220 FEEDER LOAD 2950.34 KVA 3548.71 AMPSTOTAL LOAD 2925.33 KVA 3518.62 AMPSTOTAL CONNECTED 3589.94 3544.38 3451.29 AMPSTOTAL CONNECTED 990.97 978.35 956.01 KVA53 45.19 0.00 -- -- -- dedicated space 5451 52.44 0.00 -- -- -- dedicated space 5249panel h3b (13) 300 A 351.08 0.00 -- -- -- dedicated space 5047 105.02 0.00 -- -- -- dedicated space 4845 105.02 0.00 -- -- -- dedicated space 4643panel h2a (13) 400 A 3105.02 0.00 -- -- -- dedicated space 4441 132.58 0.00 -- -- -- dedicated space 4239 131.90 0.00 -- -- -- dedicated space 4037panel h4b1 (13) 600 A 3139.18 0.00 -- -- -- dedicated space 3835 110.98 0.00 -- -- -- dedicated space 3633 110.98 0.00 -- -- -- dedicated space 3431panel h1a (13) 600 A 3110.98 0.00 -- -- -- dedicated space 3229 190.46 0.00 -- -- -- dedicated space 3027 201.34 0.00 -- -- -- dedicated space 2825panel h1b (13) 800 A 3209.41 0.00 -- -- -- dedicated space 2623 119.71 0.00 -- -- -- dedicated space 2421 124.60 0.00 -- -- -- dedicated space 2219panel h2b (13) 600 A 3123.23 0.00 -- -- -- dedicated space 2017 127.62 0.00 -- -- -- dedicated space 1815 127.62 0.00 -- -- -- dedicated space 1613panel h4b2 (13) 500 A 3127.62 0.00 -- -- -- dedicated space 1411 102.46 0.00 -- -- -- dedicated space 129 102.46 0.00 -- -- -- dedicated space 107panel h4b3 (13) 400 A 3102.46 0.00 -- -- -- dedicated space 85 0.10 21.89 63 0.10 21.89 41phase loss monitor (13) 15 A 30.10 21.893 100 A PANEL HPU (2,8)2DESCRIPTION WIRE BRKR PL A B C PL BRKR WIRE DESCRIPTIONLOCATION: EDC1SERVES: MAIN SERVICE(EXISTING)4000 A, M.C.B.MSB PANELBOARD480Y/277 V, 3PH, 4WISSUE BLOCK
architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021E4.1PANELBOARDSCHEDULESKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PN20A WIRE SIZING SCHEDULE385 FT.770 FT.930 FT.620 FT.1865 FT.255 FT.ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE.THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM.6-10 AMPS1-5 AMPS120 VOLT11-15 AMPS6-10 AMPS1-5 AMPS277 VOLT11-15 AMPS#8#12#10380 FT.760 FT.250 FT.240 FT.480 FT.160 FT.585 FT.1170 FT.390 FT.325 FT.110 FT.160 FT.#12200 FT.70 FT.100 FT.490 FT.165 FT.245 FT.#10#8#6#61.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20.21.22.23.24.25.1.2.3.TERMINATE GROUND ON ISOLATED GROUND BUS.INSTALL LOCKING DEVICE (LOCK-OFF FOR MAINTENANCE). LOCKING DEVICE SHALL BE UL LISTED. MANUFACTURER SHALL MATCH EXISTING PANELBOARD MANUFACTURER.INSTALL LOCKING DEVICE (LOCK-ON FOR CRITICAL LOAD).GFI BREAKER FOR PERSONNEL PROTECTION (5MA).GFI BREAKER FOR EQUIPMENT PROTECTION (30MA).CONDUCTOR SIZE HAS BEEN INCREASED FOR VOLTAGE DROP. SIZE EQUIPMENT GROUNDING CONDUCTOR PROPORTIONATELY PER NEC.REFER TO ONE-LINE DIAGRAM FOR AVAILABLE FAULT CURRENT FOR INTERRUPT RATINGS.REFER TO ONE-LINE DIAGRAMS FOR WIRE SIZES.FACTORY WIRED TO LOAD.BREAKER SHALL BE HIGH MAGNETIC TYPE.BREAKER REMOVAL - FIELD VERIFY CIRCUIT BREAKER IS NOT SERVING AN EXISTING LOAD. IF NO EXISTING LOAD, REMOVE CIRCUIT BREAKER AND PROVIDE FILLER PLATE. IF BREAKER IS SERVING A LOAD, IDENTIFY LOAD SERVED. UPDATE CIRCUIT IDENTIFICATION SCHEDULE AS "SPACE" OR INDICATE LOAD SERVED.DUAL TAP SOLENOID OPERATED BREAKER. CONNECT EMERGENCY/NIGHT LIGHTING TO UNSWITCHED TERMINATION.EXISTING CIRCUIT AND/OR CIRCUIT BREAKER.ROUTE CIRCUIT THROUGH CONTACTOR.PROVIDE INTERLOCK WIRING WITH EXHAUST HOOD ANSUL SYSTEM.RELOCATED CIRCUIT FROM EXISTING PANELBOARD.PROVIDE BLANK CIRCUIT BREAKER FILLER PLATE FOR EXPOSED SPACE IN PANELBOARD.PROVIDE U.L. LISTED OVERCURRENT DEVICE TO COORDINATE AND MAINTAIN MANUFACTURER'S SERIES RATED SYSTEM.EXISTING CIRCUIT BREAKER TO REMAIN. VERIFY CONDITION OF CIRCUIT BREAKER TO ENSURE THAT IT IS OPERATIONAL AND MEETS ALL U.L. RATINGS.ROUTE CIRCUIT THROUGH EXISTING LCU CABINET UTILIZING EXISTING RELAY AND CONTROLS. UPDATE LCU IDENTIFICATION SCHEDULE WITH LOAD IDENTIFICATION.SOLENOID OPERATED CIRCUIT BREAKER. REFER TO ENERGY MANAGEMENT PLANS FOR CIRCUIT BREAKER CONTROL.EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY LOAD AND UPDATE CIRCUIT IDENTIFICATION SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN USE, REFER TO PANELBOARD NOTE (11).ROUTE CIRCUIT THROUGH ENCLOSED GFI BREAKER FOR PERSONNEL PROTECTION (5MA).SPARE - FIELD VERIFY CIRCUIT BREAKER IS NOT SERVING AN EXISTING LOAD. IF NO EXISTING LOAD, PROVIDE LOCK OFF DEVICE TO LOCK SPARE BREAKER IN THE OFF POSITION. IF BREAKER IS SERVING A LOAD, IDENTIFY LOAD SERVED. UPDATE CIRCUIT IDENTIFICATION SCHEDULE AS "SPARE" OR INDICATE LOAD SERVED.EXISTING LOAD - TRACE EXISTING CIRCUIT, IDENTIFY LOAD AND UPDATE CIRCUIT IDENTIFICATION SCHEDULE FOR LOAD SERVED. IF CIRCUIT IS NOT IN USE, REFER TO PANELBOARD NOTE (24).GENERAL NOTES:NEW OVERCURRENT PROTECTIVE DEVICES PLACE IN EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT PROTECTION DEVICES IN SAID BOARD.E.C. SHALL TRACE ALL ELECTRICAL CIRCUITS FOR EVERY EXISTING PANELBOARD AFFECTED BY THIS PROJECT. IDENTIFY LOADS ON EACH CIRCUIT. PROVIDE A COMPLETE TYPEWRITTEN CIRCUIT IDENTIFICATION SCHEDULE FOR EVERY AFFECTED PANELBOARD.ALL OVERCURRENT DEVICES ARE NEW UNLESS NOTED OTHERWISE.PANELBOARD NOTES ()08.28.20PER NEC ARTICLE 220 FEEDER LOAD 65.68 KVA 79.00 AMPSTOTAL LOAD 65.68 KVA 79.00 AMPSTOTAL CONNECTED 79.03 79.03 79.03 AMPSTOTAL CONNECTED 21.89 21.89 21.89 KVA41 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 4239 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 4037 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3835 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3633 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3431 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3229 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3027 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2825 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2623 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2421 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2219 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2017 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 1815 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 1613 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 1411 3.60 3.60 129 3.60 3.60 107RCU-4 (2) 15 A 33.60 3.603 20 A HCR AIR DOOR85 11.08 3.60 63 11.08 3.60 41RCU-3 (2) 6 60 A 311.08 3.603 20 A HCR AIR DOOR2DESCRIPTION WIRE BRKR PL A B C PL BRKR WIRE DESCRIPTIONPANELBOARD FURNISHED AND INSTALLED BY E.C.LOCATION: OGP AREASERVES: OGP AREA EQUIPMENT GROUND BUS14,000 AIC(NEW) SURFACE MOUNTED225 A, M.L.O.HPU PANELBOARD480Y/277 V, 3PH, 4WPER NEC ARTICLE 220 FEEDER LOAD 28.15 KVA 78.13 AMPSTOTAL LOAD 28.10 KVA 77.99 AMPSTOTAL CONNECTED 74.38 82.56 78.23 AMPSTOTAL CONNECTED 8.93 9.85 9.33 KVA41 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 4239 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 4037 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3835 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3633 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3431 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3229 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 3027 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2825 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2623 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2421 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2219 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 2017 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 1815 WASTE PUMP P11 20 A 1 0.60 0.00 -- -- -- SPACE 1613 COOLER / FREEZER LTG 20 A 1 0.20 0.00 -- -- -- SPACE 1411 OGP PRINTER 20 A 1 0.80 0.00 -- -- -- SPACE 129 OGP MANAGER STATION 20 A 1 0.72 0.00 -- -- -- SPACE 107 OGP CLR / FRZR HTRS (2,5) 20 A 1 0.20 0.00 -- -- -- SPACE 85 4.18 4.35 63 4.18 4.35 41RCU-3 DEFROST / FANS (2) 8 50 A 34.18 4.353 50 A 8 RCU-4 DEFROST / FANS (2)2DESCRIPTION WIRE BRKR PL A B C PL BRKR WIRE DESCRIPTIONPANELBOARD FURNISHED AND INSTALLED BY E.C.LOCATION: OGP AREASERVES: OGP AREA EQUIPMENT GROUND BUS10,000 AIC(NEW) SURFACE MOUNTED150 A, M.C.B.LPU PANELBOARD208Y/120 V, 3PH, 4WPER NEC ARTICLE 220 FEEDER LOAD 58.63 KVA 162.74 AMPSTOTAL LOAD 58.63 KVA 162.74 AMPSTOTAL CONNECTED 185.46 140.67 170.38 AMPSTOTAL CONNECTED 21.78 16.88 19.97 KVA83 space -- -- -- 0.00 0.00 -- -- -- space 8481 space -- -- -- 0.00 0.00 -- -- -- space 8279 space -- -- -- 0.00 0.00 -- -- -- space 8077 rubi micro cafe (13) 20 A 1 0.18 0.00 1 20 A ES1 GATEWAY CONTROLLER (3) 7875 air curtain fans (13) 20 A 1 1.48 0.68 1 20 A PICKUP DOOR (2,13) 7673 air curtain fans (13) 20 A 1 1.48 0.18 1 20 A existing load (13) 7471 door operators (13) 20 A 1 0.60 0.60 7269 door operators (13) 20 A 1 0.60 0.602 20 A produce cooler (13)7067 vending machines (13) 20 A 1 1.50 0.18 1 20 A existing load (13) 6865 vending machines (13) 20 A 1 0.75 0.10 1 20 A rfid scanners (13) 6663 vending machines (13) 20 A 1 1.50 0.10 1 20 A rfid scanners (13) 6461 motorized carts (13) 20 A 1 0.96 1.67 1 20 A front cash wraps (13) 6259 vending machines (13) 20 A 1 0.96 1.67 1 20 A front cash wraps (13) 6057 eas (13) 20 A 1 0.75 1.67 1 20 A front cash wraps (13) 5855 vending machines (13) 20 A 1 0.90 1.44 1 20 A idf cabinet (13) 5653 ice merchandiser (13) 20 A 1 1.56 0.18 1 20 A self scan checkouts (13) 5451 ice bagger (13) 20 A 1 0.24 0.18 1 20 A pay station (13)5249 1.87 1.67 1 20 A front cash wrap (13) 5047ice maker (13) 30 A 21.87 1.67 1 20 A front cash wrap (13) 4845 1.87 0.87 1 20 A front cash wrap (13) 4643ice maker (13) 30 A 21.87 0.87 1 20 A front cash wrap (13) 4441 space -- -- -- 0.00 0.00 -- -- -- space 4239 space -- -- -- 0.00 0.00 -- -- -- space 4037 space -- -- -- 0.00 0.00 -- -- -- space 3835 space -- -- -- 0.00 0.00 -- -- -- space 3633 space -- -- -- 0.00 0.00 -- -- -- space 3431 space -- -- -- 0.00 0.00 -- -- -- space 3229 space -- -- -- 0.00 0.00 -- -- -- space 3027 space -- -- -- 0.00 0.00 -- -- -- space 2825 2.77 0.00 -- -- -- space 2623 2.77 0.00 -- -- -- space 2421s14 lobster steamer (13) 30 A 32.77 0.00 -- -- -- space 2219 s13 lobster tank (13) 20 A 1 0.72 0.00 -- -- -- space 2017 rollseal door (13) 20 A 1 1.20 1.44 1 20 A idf cabinet (13) 1815 ice cream frzr htrs (13) 20 A 1 0.60 0.36 1 20 A pharm drive-thru recept (13) 1613 grocery frzr htrs (13) 20 A 1 0.60 1.08 1 20 A rtu's 4-8, 15 (13) 1411 waste oil tank (13) 20 A 1 1.82 0.72 1 20 A rtu's 1,2,3, ahu 1 (13) 129 stockrm recept/pump (13) 20 A 1 0.60 0.18 1 20 A exterior recept (13) 107 meater cooler htrs (13) 20 A 1 0.60 0.96 1 20 A 92a coffee grinder (13) 85 seafood frzr htrs (13) 20 A 1 0.60 1.28 1 20 A 94a pastry/prod./pics (13) 63 m04 scale/m11 wrapper (13) 20 A 1 1.32 0.51 1 20 A i.c./grocery frzr ltg (13) 41 seafood recept (13) 20 A 1 0.37 0.09 1 20 A seafood freezer ltg (13) 2DESCRIPTION WIRE BRKR PL A B C PL BRKR WIRE DESCRIPTIONLOCATION: EDC4SERVES: GROCERY EQUIPMENT(EXISTING)225 A, M.C.B.L4D1 PANELBOARD208Y/120 V, 3PH, 4WISSUE BLOCKPER NEC ARTICLE 220 FEEDER LOAD 643.82 KVA 774.39 AMPSTOTAL LOAD 601.20 KVA 723.13 AMPSTOTAL CONNECTED 762.03 732.90 687.57 AMPSTOTAL CONNECTED 209.41 201.34 190.46 KVA47 space -- -- -- 0.00 0.00 -- -- -- space 4845 space -- -- -- 0.00 0.00 -- -- -- space 4643 space -- -- -- 0.00 3.36 1 20 A fan powered terminal (13)4441 3.88 0.00 -- -- -- space 4239 3.88 0.00 -- -- -- space 4037compactor (13) 30 A 33.88 0.00 -- -- -- space 3835 3.88 0.83 3633 3.88 0.83 3431baler (13) 30 A 33.88 0.833 20 A jockey pump (13)3229 3.88 0.00 3027 3.88 0.00 2825baler (13) 30 A 33.88 0.003 50 A SPARE (24)2623 5.00 0.00 -- -- -- dedicated space 2421 5.00 4.32 2219wh-gr receiving (13) 30 A 35.00 4.322 70 A transformer tpl (13)2017 9.33 44.89 1815 9.85 49.40 1613TRANSFORMER TPU (2,8) 70 A 38.93 48.743 225 A transformer t1d (13)1411 33.85 33.60 129 33.85 35.17 107lift station pump 5 (13) 150 A 333.85 37.633 200 A panel h1p2 (13)85 22.67 28.65 63 22.67 28.61 41ahu2 (13) 110 A 322.67 32.443 200 A panel h1p1 (13)2DESCRIPTION WIRE BRKR PL A B C PL BRKR WIRE DESCRIPTIONLOCATION: EDC1SERVES: 480V DISTRIBUTION(EXISTING)800 A, M.L.O.H1B PANELBOARD480Y/277 V, 3PH, 4W
A A A A A A A A A A AAAAADD DD DD DD DD DD DD DD DD DDJ JJ JCCHI456PICKUPFREEZERPICKUPCOOLERCFEDREFRIGERATIONEVAPORATOR COIL, TYP2RE1TYPRCU-3CFEDCF CFEDRCU-4(50A-3P)WR, WP, GFI, MOUNT TO FRAMING OR NON-REMOVABLE ACCESS PANEL60A/3P/NF, NEMA 3RRCU-3(ON ROOF)(15A-3P) #12W30A/3P/NF, NEMA 3R22PROVIDE 3/4"C FROM LOW VOLTAGE WIRING COMPARTMENT TO ACCESSIBLE INTERIOR JOIST SPACE AND TERMINATE WITH BUSHING, TYP.ED53(CF)(ED)(60A-3P) #6WHPU-7,9,11 HPU-1,3,52253(CF)(ED)RCU-3RCU-4#8W(50A-3P)#8W2253(CF)(ED)2253(CF)(ED)RCU-4(ON ROOF)NOTE: CONDUITS SHALL BE ROUTED WITH REFRIGERATION LINES. ROUTING CONDUITS ON THE ROOF IS NOT ALLOWED, TYPPICKUPSTOCKROOMTYP16.725LPU-1,3,5LPU-2,4,616.249PROVIDE CEILING MOUNTED MANUAL SWITCH 'SQUARE D' CLASS 2510 (OR EQUAL), TYPE M, WITH NEMA 4 WATERTIGHT DIE CAST ZINC ENCLOSURE FOR CONNECTION OF EVAPORATOR COIL FANS (CF) AND/OR ELECTRIC DEFROST (ED), (WHERE SHOWN ON DRAWINGS). PROVIDE PLACARD ON CEILING DETAILING PURPOSE OF EACH MANUAL SWITCH AND THE ELECTRICAL SOURCE (PANEL AND CIRCUIT NUMBER).NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.TYPICAL COILEMT CONDUIT AND WIRING TO NEXT COIL POWER JUNCTION BOX ON SAME SYSTEM WHEN MULTIPLE COILS ARE IN SAME COOLER/FREEZER BOX. POWER CONDUIT AND WIRING SAME SIZE AND QUANTITY AS WIRING TO PANEL.1" EMT CONDUIT PENETRATION SEALED WITH SILICONE SEALANT.NOTE: TAP DEFROST CIRCUIT IN JUNCTION BOX WITH #10 AWG FOR CONNECTION TO UNIT. MAXIMUM LENGTH OF TAP CONDUCTOR 18"CONDULET AT CEILING PENETRATION FILLED WITH SILICONECOIL FAN/DEFROST POWER EMT CONDUIT AND WIRING TO DESIGNATED PANEL VIA WALK-IN FAN/DEFROST CONTROL DEVICE. FINAL CONNECTION BY RC.COOLER/FREEZER BOX CEILINGCEILING MOUNTED WP JUNCTION BOX WITH THREADED HUBS AND GASKETED COVERPLATE. SEAL TOP OF JUNCTION BOX TO COOLER/FREEZER CEILING WITH SILICONE SEALANT.1" LIQUID-TIGHT FLEXIBLE METAL CONDUIT TO KNOCKOUT ON UNIT. FINAL CONNECTION TO COIL BY RC.architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17604-30-202105-28-2021RE1REFRIGERATIONELECTRICALPLANSKMYELM, WASHINGTON2021-0111YELM, WASHINGTON03/11/2020STORE NO: 3705-235176PNNOTE: REFRIGERATION CONTRACTOR IS RESPONSIBLE FOR ALL FINAL REFRIGERATION ELECTRICAL TERMINATIONS TO REFRIGERATION EQUIPMENTKEYNOTES16.249 E.C. TO PROVIDE MAINTENANCE RECEPTACLE.ROUTE CIRCUIT TO NEAREST RTU RECEPTACLE.16.725 ROUTE COIL FAN AND/OR ELECTRIC DEFROSTCIRCUITS VIA CONTROL DEVICES PROVIDEDWITH WALK-IN BAS CONTROLLER. FINALTERMINATIONS AT ENCLOSURE BY R.C.1.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.COORDINATE ALL WORK WITH REFRIGERATION CONTRACTOR (R.C.) PRIOR TO INSTALLATION.REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE) ELECTRICAL DEFROST. PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT CASE BY R.C. REF CASE CONNECTION WIRING DETAIL.NEW CASES ARE PROVIDED WITH A FACTORY INSTALLED TERMINAL STRIP AND JUMPERS FOR CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE LOADS. RC SHALL REMOVE FACTORY INSTALLED JUMPERS AS REQUIRED TO UTILIZE EXISTING SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS INDICATED ON PLANS AND/OR PANELBOARD SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL (SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING ELECTRICAL DEFROST WILL BE PROVIDED WITH SEPARATE 208V TERMINATIONS AT THE TERMINAL STRIP FOR CONNECTION TO THE 208V ELECTRIC DEFROST CIRCUIT. RC SHALL MAKE FINAL TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S) AT CASE TERMINAL STRIP. REFER TO CASE CONNECTION SCHEMATIC ON REFRIGERATION SHEETS.WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE) ELECTRIC DEFROST (ED). PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT COIL BY R.C. REF EVAPORATOR COIL WIRING DETAIL.ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH CIRCUITS TO WIREWAYS PROVIDED AT REFRIGERATION EQUIPMENT AND/OR PANELBOARDS AS REQUIRED. REFRIGERATED CASE WIRING COMPARTMENT REPRESENTED ON DRAWING BY JUNCTION BOX.KEEP PENETRATIONS THROUGH WALK-IN UNITS TO A MINIMUM. ROUTE ALL CONDUITS SERVING FREEZERS AND COOLERS ON INSIDE OF BOX.ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF ARCH.UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE REFRIGERANT LINES WHERE THEY CROSS.CIRCUITS FOR REFRIGERATED CASES SERVED BY UNDERSLAB REFRIGERATION PIPING ARE TO BE ROUTED UNDERSLAB AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY R.C. REFER TO UNDERSLAB CASE CONNECTION WIRING DETAIL.ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.CIRCUITS FOR REFRIGERATED CASES SERVED BY OVERHEAD REFRIGERATION PIPING ARE TO BE ROUTED DOWN FROM STRUCTURE AT THE SAME LOCATION AS THE REFRIGERATION PIPING AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY THE R.C. REFER TO OVERHEAD CASE CONNECTION WIRING DETAIL. ON GROUPS OF THREE OR MORE REFRIGERATED CASES WITH ELECTRIC DEFROST, R.C. SHALL CONNECT CASES TO CREATE A THREE-PHASE HEATER CIRCUIT. HEATER LOADS SHALL BE BALANCED BETWEEN PHASES AS EVENLY AS POSSIBLE. REF CASE DEFROST WIRING DETAIL.PROVIDE A SEPARATE NEUTRAL FOR EACH BRANCH CIRCUIT SERVING REFRIGERATED CASES OR WALK-IN UNITS AS INDICATED ON PLANS.PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING CIRCUIT BREAKERS SERVING REFRIGERATED CASE ANTI-SWEAT HEATERS OR DRAIN HEATERS. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR FULL EXTENT OF DEMOLITION WORK REQUIRED.GENERAL REFRIGERATION ELECTRICAL NOTES12.21.18FEEDER OR GROUND SIZEALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40%FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION.FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPESRATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC.FEEDER SCHEDULE22 (2)#12, (1)#12 G, 1/2" C53 (3)#8, (1)#10 G, 3/4" CNOTE: ALL CONDUITS INSTALLED ON TOP OF WALK-IN COOLERS AND FREEZERS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF. ARCH. 1/4" = 1'-0" 1PICKUP REFRIGERATION POWER PLAN 12" = 1'-0" 2EVAPORATOR COIL WIRINGISSUE BLOCK