PSE FINAL 105093614 THE HUTCH APPROVED (5)Owner / Developer Contact Info
officeATTN:
MITCHELL DEVELOPMENT II, LLC
910 TRAFFIC AVE
SUMMER, WA 98390
SHERI GREENE 253.383.2422
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
GAS
PHONE
CABLE TV
508522870 105093614
N/A 108128860
N/A 105095336
N/A 593235644
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Removal
Streetlight
Fuse Upgrade
Temporary
Job Order
Distribution
Service Stubs
HP Svc/MSA
10.
9.
8.
7.
6.
5.
4.
3.
2.
1. THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, PER THE TRENCH
PROFILE, AND ALL EXCAVATIONS AT THE TRANSFORMER/HANDHOLE VAULT SITES
SUCH THAT PSE FACILITIES WILL MATCH FINAL GRADE. VAULT HOLES WILL HAVE
STABLE LEVEL BOTTOMS. CUSTOMER WILL PROVIDE 6" OF CRUSHED ROCK FOR
VAULT BEDDING. ALL TRENCHES WILL HAVE 6" OF WASHED SAND COVER AND 4"
BEDDING FOR ALL CONDUITS. THE CUSTOMER WILL PROVIDE SELECT BACKFILL, IF
REQUIRED, AND COMPACTION AS NECESSARY. THE CUSTOMER IS RESPONSIBLE FOR
DISPOSAL OF ALL NATIVE SPOILS NOT SUITABLE FOR USE AS BACKFILL. ALL
TRENCHES MAY BE JOINT WITH GAS, TELEPHONE AND TV CABLE.
ALL CABLES/CONDUITS TO BE INSTALLED IN CUSTOMER'S TRENCH AT THE DEPTH
INDICATED IN TRENCH DETAIL (DEPENDENT UPON SIZE OF CONDUIT BEING INSTALLED
TO MEET MIN 36" OF COVER). INSTALL CABLE ID TAGS AT EACH END OF THE PRIMARY
CABLES PER THE CIRCUIT ONE-LINE DIAGRAM.
UNLESS OTHERWISE SPECIFIED BY MUNICIPALITIES, INSTALL PVC (DB-120) ROAD
CROSSINGS AS INDICATED ON THE CROSSINGS CONDUIT TABLE & AS SHOWN ON
WORK SKETCH. CROSSINGS SHALL BE INSTALLED BY CUSTOMER/DEVELOPER PER
PUGET SOUND ENERGY STANDARDS.
AT SYMBOL: INSTALL UNDERGROUND PRIMARY CABLES IN
CONDUIT. CABLE LENGTH AND CONDUIT SIZE AS INDICATED ON PRIMARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL 600 VOLT UG SECONDARY CABLES IN
CONDUIT. CABLE/CONDUIT SIZE AND LENGTH AS INDICATED ON SECONDARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL MINI-PAD HANDHOLE & PADMOUNT TRANSFORMER.
ADDITIONAL EQUIPMENT AS INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY PEDESTAL/HANDHOLE W/ (3)
MULTI-CONNECTORS. SIZE AS INDICATED ON SECONDARY HH/PEDESTAL TABLE.
(EXCAVATION: 3' SQ.)
AT SYMBOL: INSTALL JUNCTION BOX HANDHOLE. ADDITIONAL EQUIPMENT AS
INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY CABLE & CONDUIT STUB-OUT.
AT SYMBOL: INSTALL STREET LIGHTING STANDARD. SIZE AND TYPE OF
STANDARD/LUMINARIE AS INDICATED ON STREET LIGHTING TABLE. (CUSTOMER TO
EXCAVATE & INSTALL CORRUGATED STREET LIGHT TUBES FOR PLACEMENT OF THE
STREET LIGHT STANDARDS. )
INCLEMENT WEATHER CONDITIONS MAY CAUSE DELAYS IN CONSTRUCTION TIMES
AND DATES.
POWER GENERAL NOTES - PLAT PROJECT
105093614 N/A
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
N/A 1 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
11.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:DON BETTENCOURT
206.445.5958
Don.Bettencourt@pse.com
x
x
x x
...
...
...
SGREENE@AHBL.COM
Excavation - 11-1/4 cubic yards
SIDE VIEW
Rock
Crushed
6"
4'-4"
2"
4'-0"
6'-0"
6"6'-7"
3'-6"
4'-0"
7'
10'
TOP VIEW
NOT TO SCALE
VAULT DETAIL @ V04
VAULT DETAIL @ V01-V03 & V05-V14
NOT TO SCALE
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
FRONT
FRONTTYPICAL NOTCH-OUT FOR TRANSFORMER,
NOT TO SCALE
& SECONDARY PEDESTAL/HANDHOLE
BACK OF EASEMENT
STANDARD
EASEMENT
LINE
ROW
10'
PL
1'
4' - 5'
Min.
1'
7'7'
TRANSFORMER
(WHEN PRESENT)
42"
45°42"
1'
45°Property LineRoad Side
Top View of Mainline Trench for
Single Stubout Location
4'Property LineRoad Side
Top View of Mainline Trench for Pedestal
or Double Stubout Location
42"45°
4'
45°
STUBOUT EXCAVATION DIMENSIONS
NOT TO SCALE
JOINT TRENCH DETAIL
NOT TO SCALE JOINT TRENCH DETAIL
NOTES:
1. If the final backfill contains rocks greater than 8 inches in diameter , install 12 inches compacted sand shading across the full width of the trench. *
If the final backfill contains rocks 8 inches in diameter or smaller , install 6 inches compacted sand shading across the full width of the trench. *
2. Rocks greater than 10 inches diameter are not permitted in the final backfill.
3. Sand bedding is required under PSE gas pipe. Bedding is not required for the full width of the trench; it shall extend from the
side of the trench nearest to where the gas main/service is installed to a minimum of 6 inches on the opposite side of the gas line.
4. Utilities shall not be stacked over the gas line in the trench.
5. If wet utilities will be included in the trench, please contact PSE or local power company directly for clearance requirements.
6. Reduced clearance of 4 inches between power and communication, must have approval of the communications companies.
* Alternatives to full-width trench shading require PSE approval.
Primary & Secondary-Mainline Gas & Communications (NTS)
ROAD SIDE
NATIVE
SECONDARY POWER
PEDESTAL
MATERIAL
P/L
Power
Secondary
Power
Primary
Conduit
Tel. & TV
12" Min
12" Sand
Cover when
gas line is in
trench
Sand
6" or 12"
4" Sand Bedding
1'
36"
Cover
42"
Gas
12"
18"
Lower 2"
10"
Pedestal
PSE 10' FRONTAGE
EASEMENT
1'
Cover
ROAD SIDE
MINIPAD
MINIPAD
FIELD SIDE
VAULT
6" of crushed rock
(base for vault)
P/L
Power
Secondary
Power
Primary
Gas
12" Min Horizontal Separation
Communications
42" Min
21"1'
Feeder
38"
2"
4" Sand Bedding
12" Sand
Cover
36"
Cover
4" Sand Bedding
42"
6" Additional depth when
Feeder is required
PSE 10' FRONTAGE EASEMENT
1'
TRANSFORMER
Final
Backfill
Initial
Backfill
Trench Depth
42" - 48"
Primary
Dirt Pile
Final Grade
24" Min
36"
Min Cover
Over Power
48"
Max
Depth
Final Backfill
Gas
4" Sand Bedding
Property Line
intercept (depth varies).
SidewalkCurb
Location of roof drain
48" Typical
Width may vary per
Number of Utilities
and Conduits
6" or 12" Min Sand Shading
Over Gas after Compaction
12" Min
R/W or
Excavated
12" Typical
Power
Secondary
Power
TV & TEL
12" Min
12" Min
Separation
4,5
1,2
1
3
6
6" or 12" Min Sand Shading
Over Power after Compaction1
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
3' MIN
@ H1A, H1B, H2A, H2B, H7A, H8A,
H9A, H10A, H11A, H12A, H12B,
H13A & H14A
SHALL BE STAGGERED
CONNECTOR BARS
IN THE FRONT
NEUTRALS SHALL BE 18"
16"
13"
12"10"
2"
10"
Pedestal will accept up to six 3" conduits
SEALED WITH FOAM
CONDUIT SHALL BE
120 PVC CONDUIT ELBOWS
TYPICAL 24" RADIUS DB
SIDE VIEW WITH CONDUIT
10"
18"
16"
13"
10"
2"
36"
FRONT VIEW WITH CONDUIT
SECONDARY PEDESTAL DETAIL
NOT TO SCALE
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED TRANSFORMER
TRANSFORMER
APPROVED
AREA
COMBUSTIBLE BUILDING WALLS & ROOF3'
3'
REDUCED FLAMMABILITY
3'
Oil-Filled Equipment Clearances per PSE Std 0700.1500
If the oil-filled equipment is adjacent to… Clearance
Requirement
Combustible walls or roof (including stucco).10 FT
Combustible walls using a reduced-flammability transformer. Gas
service meter relief vent.3 FT
Noncombustible walls, soffits, and roofs (including brick, concrete,
steel and stone) providing the side of the transformer facing the wall
does not have doors. Materials that pass UBC Std. 2-1 or ASTM
E136-79 are considered to be noncombustible.
3 FT
Generators, customer-owned transformers, fire sprinkler valves,
standpipes, and fire hydrants.6 FT
Doors, windows, vents, fire escapes, or other building openings.10 FT
The water's edge of a swimming pool or any body of water.15 FT
Facilities used to dispense or store LP, hazardous liquids, or fuel.20 FT
Individual domestic and irrigation wells. Clearance not required on
pole mounted transformers (pole placement still applies as stated in
6450.3000), TUT's installed in sealed vaults, 7200V single-phase
padmount transformers 50kva or less, and reduced flammability oil.
100 FT
N
Vicinity Map
46.9536, -122.6221
SITE
10
9
8
7
6
5
4
3
2
1
14 13
12 11
1516
1718
19
71 72
87
86
85
84
83
82 78
77
76
75
74
73
81 80 79
88
93
94
92
91
90
89
KILLION ROAD SE'B' LOOP SE'A' ROAD SE'E' ROAD SE
FUT: 1-2"
MON
TRACT 'B'
STORMWATER
56'
56'
R50'56'71'FEEDYEL
25
'A'
1" = 50'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
1" = 50' 2 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
SITE PLAN
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
YEL-25
12.21.20
303 306 278
19 26 36
322 332 314
...
...
...
SCHED.SQ. FT.
MAX LRC =
CIRCUIT FEET ADDED: 4,950 FT
17 2500
80 AMPS
CIRCUIT FEET REMOVED: 820 FT
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
CUSTOMER OWNED AND INSTALLED SECONDARY WIRE TABLE
BLDG.# OF
METERS SOURCE # OF RUNS WIRE SIZE REMARKS
-1 V01 1 1/0 MONUMENT
ALL CUSTOMER-OWNED WIRE MUST BE INSTALLED ACCORDING TO THIS TABLE
CROSSING CONDUIT TABLE
X-ING
#
LOCATION POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY
X01 'A'LOT 7 4 DB120 2 90 ( )' SCL PRIMARY
X02 LOT 7 LOT6 2 DB120 1 75 ( )' ECL PRIMARY
X03 LOT 6 LOT 76 3 DB120 1 65 ( )' NCL SECONDARY
X04 LOT 5 LOT 74 3 DB120 1 65 ( )' NCL SECONDARY
X05 LOT 4 LOT 73 3 DB120 1 65 ( )' NCL SECONDARY
X05A LOT 3 TRACT B 2 DB120 1 65 ( )' NCL STREETLIGHT
X06 LOT 7 LOT 78 3 DB120 1 75 ( )' SCL SECONDARY
X07 LOT 14 LOT 79 3 DB120 1 65 ( )' ECL SECONDARY
X08 LOT 15 LOT 80 3 DB120 2 65 ( )' ECL SECONDARY
X09 LOT 17 LOT 81 2 DB120 1 75 ( )' ECL PRIMARY
X10 LOT 81 LOT 93 3 DB120 1 65 ( )' NCL SECONDARY
X11 LOT 82 LOT 92 3 DB120 2 65 ( )' NCL SECONDARY
X12 LOT 83 LOT 91 3 DB120 1 65 ( )' NCL SECONDARY
X13 LOT 85 LOT 89 3 DB120 2 65 ( )' NCL SECONDARY
X14 LOT 86 LOT 88 3 DB120 1 65 ( )' NCL SECONDARY
X14A TRACT B LOT 88 2 DB120 1 65 ( )' NCL STREETLIGHT
X15 LOT 20 LOT 96 3 DB120 1 65 ( )' WCL SECONDARY
X16 LOT 20 LOT 95 3 DB120 1 65 ( )' WCL SECONDARY
X17 LOT 23 LOT 105
2 DB120 1 75 ( )' ECL PRIMARY
3 DB120 1 75 ( )' ECL SECONDARY
X18 LOT 105 LOT 106 3 DB120 2 65 ( )' NCL SECONDARY
X19 LOT 103 LOT 108 3 DB120 1 65 ( )' NCL SECONDARY
X20 LOT 101 LOT 109 3 DB120 2 65 ( )' NCL SECONDARY
X21 LOT 69 LOT 98 3 DB120 1 65 ( )' ECL SECONDARY
X22 LOT 69 LOT 97 3 DB120 1 65 ( )' ECL SECONDARY
X23 LOT 67 LOT 99 2 DB120 1 75 ( )' ECL PRIMARY
X24 LOT 64 LOT 112 3 DB120 2 65 ( )' WCL SECONDARY
X25 LOT 63 LOT 113 3 DB120 1 65 ( )' WCL SECONDARY
X25A LOT 61 LOT 113 2 DB120 1 65 ( )' WCL STREETLIGHT
X26 LOT 57 LOT 115 3 DB120 1 65 ( )' NCL SECONDARY
X27 LOT 56 LOT 116 3 DB120 2 65 ( )' NCL SECONDARY
X28 LOT 54 LOT 118 3 DB120 2 65 ( )' NCL SECONDARY
X29 LOT 38 LOT 52 3 DB120 2 65 ( )' SCL SECONDARY
X30 LOT 39 LOT 51 3 DB120 1 65 ( )' SCL SECONDARY
X31 LOT 40 LOT 50
3 DB120 1 65 ( )' SCL SECONDARY
2 DB120 1 65 ( )' SCL STREETLIGHT
X32 LOT 40 LOT 41 2 DB120 1 85 ( )' WCL PRIMARY
X33 LOT 41 LOT 49 3 DB120 1 65 ( )' NCL SECONDARY
X34 LOT 42 LOT 47 3 DB120 2 65 ( )' NCL SECONDARY
X35 LOT 43 LOT 46 3 DB120 1 65 ( )' NCL SECONDARY
X35A LOT 43 LOT 46 2 DB120 1 65 ( )' NCL STREETLIGHT
2" DB120 GREY PVC = 710 FT 2" PVC PLUG /CAPS = 20
3" DB120 GREY PVC = 2685 FT 3" PVC PLUG /CAPS = 84
4" DB120 GREY PVC = 180 FT 4" PVC PLUG /CAPS = 4
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING # MON
N/A
N/A
200A
N/A
0.5KW
80
2.2 @ V01
0.9 @ V01
CABLE/WIRE REMOVAL TABLE
SPAN ACTUAL LENGTH REMARKS
FROM TO CABLE TAG LENGTH CONDUIT WIRE
J03 J04
ADW306,ADW307
& ADW308 820 -
BREAKLINE~600'MATCHLINE A-A (SEE PAGE 3)MATCHLINE A-A (SEE PAGE 3)2"
Excavation - 19-1/2 cubic yards
SIDE VIEW
5'-4"Crushed
6"
Rock
TOP VIEW
9'
11'
7'-0"
4'-0"
1'
4'-8"
VAULT DETAIL @ J01 & J02
NOT TO SCALE
DEVELOPER TO COORDINATE WITH PSE
PROJECT MANGER & SERVICE PROVIDER
PRIOR TO EXCAVATING WITHIN 3' OF
LOCATE MARKS OF PSE ENERGIZED
FACILITIES
SITE SPECIFIC NOTES
AT IP1:
-INTERCEPT EXISTING 4" DB120 CONDUIT & RE-ROUTE TO J01
PER PRIMARY CABLE & CONDUIT TABLE (PAGE 6)
-REMOVE (3) EXISTING 1/0AL UG PRI CABLES AØADW306, BØADW307, CØADW308 FROM CONDUIT
AT IP2:
-INTERCEPT EXISTING 4" DB120 CONDUIT & RE-ROUTE TO J01
PER PRIMARY CABLE & CONDUIT TABLE (PAGE 6)
-REMOVE (3) EXISTING 1/0AL UG PRI CABLES AØADW306, BØADW307, CØADW308 FROM CONDUIT
IF SCH80 IS SUBSTITUTED FOR DB-120, A CHAMFER ON THE INSIDE OF THE
CONDUIT AT BOTH ENDS OF THE XING IS REQUIRED. FAILURE TO DO SO WILL
CAUSE DAMAGE TO THE TRIPLEX DURING CABLE PULL.
1920
21
22
23242526272829
3031
3233
34
35
36
37
38
40
41
42
43
44
45
46
47
48
49
50
51
52
53 54
55
56
57
58
59
60
61
63
64 65
66 6867
69 70
71
88
93
94
99
100
101
103
102
104
105
92
91
90
89
98
97
96
95
106
107117
118
108116
109115
110114
111112113
62
39MOUNTAIN VIEW ROAD SESPRAGUE ST NW #6CU#6CU#6CU#6CU#6CUBAN
BN
BN
BN
'D' ROAD SE 'A' ROAD SE'B' LOOP SE'C' ROAD SE'B' ROAD SE
'A' ROAD SEA#4 ACSR
BN
IRR
FUT: 1-2"
MON
DEVELOPER RESPONSIBLE
FOR CONDUIT/WIRE FROM
V02 TO METER LOCATION
FUT: 1-4"
TRACT 'A'
STORMWATER
56'56'56'
56'56'56'R50'
49'FEEDYEL
25
BN#6CU #6CUBAN
ABC3
9
7
.
5
A
A
C
3
9
7
.
5
A
A
C
FUSE @ 100T
70'45'
1" = 50'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
1" = 50' 3 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
SITE PLAN
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
CLEAR WORKING SPACE FOR VAULTS
NOT TO SCALE
FIELD SIDE (PREFERRED)
ROAD SIDE (PREFERRED)
6' MIN
3'
MIN
3'
MIN
3' MIN
J- BOX CABLE ENTRY DETAIL
NOT TO SCALE 12kV CABLE ROUTING
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
MATCHLINE A-A (SEE PAGE 2)MATCHLINE A-A (SEE PAGE 2)BREAKLINE~460'(SEE TOP RIGHT)
BREAKLINE~457'(SEE BOTTOM LEFT)
SITE SPECIFIC NOTES
AT P01 (559686-147034) 2008 CLASS 1 - 50'
-REMOVE EXISTING 65T FUSE FROM L/I CUTOUT (SW# Y115)
-REFUSE @ 100T (3412700), TAP AØ & BØ
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #IRR
N/A
N/A
200A
N/A
1KW
80
2.0 @ V02
0.9 @ V02
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #MON
N/A
N/A
200A
N/A
0.5KW
80
2.0 @ V14
0.9 @ V14
CUSTOMER OWNED AND INSTALLED SECONDARY WIRE TABLE
BLDG.# OF
METERS SOURCE # OF RUNS WIRE SIZE REMARKS
-1 V02 1 1/0 IRRIGATION
-1 V14 1 1/0 MONUMENT
ALL CUSTOMER-OWNED WIRE MUST BE INSTALLED ACCORDING TO THIS TABLE
DEDICATED FACILITIES (105093614) for RF Transformers
SITE SPAN ADDITIONAL REMARKS LABOR UNITS
# FROM TO FOOTAGE
V01-V14 --- REDUCED FLAMMABILITY -
- V06 89 25 DED. CONDUIT & WIRE
2-36, 2-54A
- V10 112 40 DED. CONDUIT & WIRE
2-36, 2-54A
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
AS SHOWN 4 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
EX OVERHEAD CIRCUIT MAP 1702E068
SCALE: 6" = 1 MILE
EX UNDERGROUND CIRCUIT MAP 1701E052
SCALE: NOT TO SCALE
SITE
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SITE
FUSE @ 100T
NEW 1/O AL
EIV878-AØ
EIV879-BØ
EIV880-CØ
AØADW306
BØADW307
CØADW308
NEW 1/O AL
EIV875-AØ
EIV876-BØ
EIV877-CØ
NEW 1/O AL
EIV884-CØ
NEW 1/O AL
EIV891CØ
NEW 1/O AL
EIV881-AØ
EIV882-BØ
EIV883-CØ
NEW 1/O AL
EIV890-CØ
NEW 1/O AL
EIV889-CØ
NEW 1/O AL
EIV886-CØ NEW 1/O AL
EIV887-CØ
NEW 1/O AL
EIV885-CØ
NEW 1/O AL
EIV892-BØ
NEW 1/O AL
EIV893-BØ
NEW 1/O AL
EIV894-BØNEW 1/O AL
EIV895-BØ
NEW 1/O AL
EIV896-AØ
NEW 1/O AL
EIV897-AØ
NEW 1/O AL
EIV898-AØ
AØADW309
BØADW310
CØADW311
CØADW316
AØADW318
BØADW315
AØAFC453
BØAFC454
CØAFC455 FEEDYEL
25
NEW 1/O AL
EIV888-CØ
'A'
AØADW306
BØADW307
CØADW308
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
N/A 5 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
NEW PRIMARY UNDERGROUND CIRCUIT ONE-LINE DIAGRAM
NOT TO SCALE
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
N/A 6 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT CABLE ASBUILT INFORMATION - FOREMAN COMPLETE CONDUIT TYPE (DB120, HDPE, SCH80), FEEDER CABLE TYPE (TAPE, CN, #4/O NEU)
FROM TO
SIZE
(IN)QTY.
DESIGN
LENGTH
(FT)
BENDS PULL
(LBS)
PULL
REV
(LBS)
CABLE
SIZE
DESIGN
LENGTH
(FT)
PHASE - ID TAG RECORD RECORD PHASE TAPPED & ACTUAL FOOTAGES & TYPES INSTALLED LUBRICANT (Gal.)
90° 45° 22° 11°A B C MANUFACTURER COMPOUND YEAR NOTES CONDUIT TYPE CABLE TYPE EST. ACTUAL
J01 IP1 4 1 20 1 CONDUIT ONLY ---
J01 J03 CABLE ONLY 383 347 1/0 AL JKT 400 EIV875 EIV876 EIV877
-2.8
J01 IP2 4 1 20 1 CONDUIT ONLY ----
J01 J04 CABLE ONLY 671 639 1/0 AL JKT 665 EIV878 EIV879 EIV880
-4.7
J01 J02 4 1 755 2 3 576 790 1/0 AL JKT 765 EIV881 EIV882 EIV883
-5.4
J01 V01 2 1 140 1 106 96 1/0 AL JKT 225 --EIV884 -0.9
V01 E01 2 1 200 CONDUIT ONLY -----
J02 V02 2 1 70 58 51 1/0 AL JKT 80 --EIV885 -0.3
V02 V03 2 1 180 93 93 1/0 AL JKT 190 --EIV886 -0.8
V03 V04 2 1 180 66 79 1/0 AL JKT 195 --EIV887 -0.8
V04 JMPR CABLE ONLY - -1/0 AL JKT 10 --EIV888 --
V04 V05 2 1 210 1 148 148 1/0 AL JKT 295 --EIV889 -1.2
V05 V06 2 1 150 87 87 1/0 AL JKT 160 --EIV890 -0.6
V04 V07 2 1 170 2 88 73 1/0 AL JKT 180 --EIV891 -0.7
J02 V08 2 1 220 1 2 133 127 1/0 AL JKT 305 -EIV892 --1.2
V08 V09 2 1 220 1 153 143 1/0 AL JKT 305 -EIV893 --1.2
V09 V10 2 1 250 106 106 1/0 AL JKT 260 -EIV894 --1.0
V10 V11 2 1 325 3 142 146 1/0 AL JKT 235 -EIV895 --0.9
J02 V12 2 1 275 96 78 1/0 AL JKT 285 EIV896 ---1.1
V12 V13 2 1 265 2 125 122 1/0 AL JKT 275 EIV897 ---1.1
V13 V14 2 1 195 1 117 120 1/0 AL JKT 290 EIV898 ---1.2
V14 E02 2 1 200 CONDUIT ONLY -----
J02 E03 4 1 770 2 3 CONDUIT ONLY -----
2" PVC (FT) & BENDS =3250 4 0 10 0
1Ø 1/0 AL JKT TOTAL (FT) =3290 TTL(Gal.)26
4" PVC (FT) & BENDS =1565 2 4 6 0
3Ø 1/0 AL JKT TOTAL (FT) =1830
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS TRANSFORMER ID NUMBERS
(COMPANY ID)
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
V01 559804
111169
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
1 1
MINU1SR 6045.1010 CØ
V02 559768
111117
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 CØ
V03 559768
111135
42"x48"x38"
Unistrut HH
Matid: 7663001
37.5KVA RF MP
120/240
Matid: 9995528
2 -
MINU1SL 6045.1010 CØ
V04 559767
111153
4'x6'x3'6"
Combo Vault
Matid: 7664000
Cover: 7665800
50kVA RF MP
120/240
Matid: 9995529
5 1
CMBO15LS 6045.1050 CØ
ELB10J 6041.1000
CAP (7630600)
V05 559787
111144
42"x48"x38"
Unistrut HH
Matid: 7663001
37.5KVA RF MP
120/240
Matid: 9995528
2 -
MINU1SL 6045.1010 CØ
V06 559802
111145
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
1 1
MINU1SR 6045.1010 CØ
V07 559776
111167
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
1 1
MINU1SR 6045.1010 CØ
V08 559795
111114
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 BØ
V09 559817
111122
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 BØ
V10 559818
111097
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 BØ
V11 559793
111083
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
1 1
MINU1SR 6045.1010 BØ
V12 559769
111082
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 AØ
V13 559780
111060
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
2 -
MINU1SL 6045.1010 AØ
V14 559808
111060
42"x48"x38"
Unistrut HH
Matid: 7663001
50kVA RF MP
120/240
Matid: 9995529
1 1
MINU1SR 6045.1010 AØ
J01 559787
111173
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
10 2 JBOX15L 6055.1030 3Ø
CAP (7630600)
J02 559769
111110
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
6 6
JBOX15L 6055.1030 3Ø
CAP (7630600)
Existing
J03
559762
147168
4'8"x7'x5'
w/2-3' Sq Doors
Matid: Existing
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: Existing
3 -
ELB10J 6041.1000 TAP 3Ø
Existing
J04
559840
147178
4'8"x7'x5'
w/2-3' Sq Doors
Matid: Existing
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: Existing
3 -
ELB10J 6041.1000 TAP 3Ø
SECONDARY HH/PEDESTAL TABLE
Site
Pedestal
or
Handhole
Number of
Positions
Required
Remarks
H1A PEDESTAL 5 - SEPL6 6050.1000
H1B PEDESTAL 3 - SEPS3 6050.1000
H2A PEDESTAL 4 - SEPS4 6050.1000
H2B PEDESTAL 5 - SEPL6 6050.1000
H7A PEDESTAL 4 - SEPS4 6050.1000
H8A PEDESTAL 3 - SEPS3 6050.1000
H9A PEDESTAL 3 - SEPS3 6050.1000
H10A PEDESTAL 5 - SEPL6 6050.1000
H11A PEDESTAL 5 - SEPL6 6050.1000
H12A PEDESTAL 3 - SEPS3 6050.1000
H12B PEDESTAL 4 - SEPS4 6050.1000
H13A PEDESTAL 6 - SEPL6 6050.1000
H14A PEDESTAL 5 - SEPL6 6050.1000
IRR
FUT: 1-2"
FUT: 1-2"
MON
DEVELOPER RESPONSIBLE
FOR CONDUIT/WIRE FROM
V02 TO METER LOCATION
MONFUT: 1-4"
10
9
8
7
6
5
4
3
2
1
14
13
12
11
1516
17181920212223242526272829303132
33
34
35
36
37
38
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
63 64 65
66 6867 69 70
71
72
87
86
85
84
83
82 78
77
76
75
74
73
81 80 79
88
93
94
99
100
101
103
102
104
105
92
91
90
89
9897
9695
106
107
117
118
108
116
109
115
110114
111112113
62
39
'A'
STREET LIGHT TABLE
SITE
#
POLE LUMINAIRE TUBE POLE BASE TYPE
(Direct Buried or
Basemount)
WO #BILLING
SCH.
TOTAL
CONN LOADGRID # TAG #TYPE MTG HT. ARM WATTS STYLE
TUBE
LENGTH
TUBE
DIAMETER
FL1 559775
111050
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
FL2 559804
111051
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
FL3 559823
111051
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
SL4 559817
111066
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL5 559795
111066
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL6 559775
111064
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL7 559771
111086
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL8 559811
111092
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
SL9 559817
111111
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
SL10 559770
111108
GREEN
CONCRETE 25' 6'47W LED CHFL T3
GREEN 5'18"DIRECT BURIED 105093516 51 120/240
SL11 559769
111141
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL12 559809
111138
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL13 559772
111163
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL14 559790
111162
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
SL15 559813
111163
GREEN
CONCRETE 25' 6' 47W
LED CHFL T3
GREEN 5'18" DIRECT BURIED 105093516 51 120/240
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
N/A 7 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
NOT TO SCALE
NEW CONDUIT DIAGRAM
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SECONDARY 2"
CUST. OWNED
SECONDARY 3"
PRIMARY 4"
PRIMARY 2"
ST. LT. CIC #6
CONDUIT LEGEND
ALL STREET LIGHTING POLES ARE TO BE INSTALLED PER STANDARD
6375.4800 (page #2) IN THE "LINE WORK PRACTICES MANUAL".
ALL POLES (WOOD, CONCRETE OR FIBERGLASS) ARE TO BE SET
PLUMB AND EMBEDDED TO THE GROUND LINE MARKED ON THE
POLE.
BACKFILL AROUND POLE WITH 5/8" MINUS GRAVEL AND COMPACT IN
6" LIFTS. (PEA GRAVEL AND NATIVE SOILS ARE NOT ACCEPTABLE.)
APPROXIMATELY 1 CU. YD. OF 5/8" MINUS CRUSHED ROCK WILL BE
REQUIRED.
THE DEVELOPER IS REQUIRED TO SUPPLY AND INSTALL PLASTIC
(NON PAPER) STREET LIGHT TUBES (MINIMUM 18" DIAMETER) TO
AID IN THE INSTALLATION OF THE STREET LIGHTING POLES. THE
DEVELOPER MUST ALSO SUPPLY THE REQUIRED 5/8" MINUS
GRAVEL AT EACH STREET LIGHT LOCATION.
IN ALL SHOEBOX AND COBRAHEAD INSTALLATIONS, THE LUMINAIRE
MUST BE LEVELED.
DEVELOPER MUST SUPPLY DURABLE LID/COVER AT EACH STREET
LIGHT TUBE.
NOT TO SCALE
STREET LIGHT TUBE DETAIL
Plan View Detail
of Street Light Tube
Wire Entrance
Slot
Street Light
Tube
Field
Side
Road
Side
Wire
Entrance Slot
45°
45°
Position 3" x 6" wire entrance slot 45 degrees
left or right from a line perpendicular to road-
way through center of tube.
Field Side
3" x 6" Wire
Entrance Slot
45°
45°
Street light tube
set 2" below grade.
Road Side
18" - 24" Minimum
Depending on
Pole Type
5'-0"
20"
26"
STREET LIGHT CIRCUITRY TABLE - 105095336
SITE
# FROM
CABLE INFO AS-BUILT
REMARKSTYPE LF TYPE LENGTH
FL1 - #6 CIC -- BY INTOLIGHT
FL2 - #6 CIC -- BY INTOLIGHT
FL3 - #6 CIC -- BY INTOLIGHT
SL4 H14A #6 CIC 75
SL5 H13A #6 CIC 110
SL6 V13 #6 CIC 70
SL7 V12 #6 CIC 45
SL8 H10A #6 CIC 80
SL9 V09 #6 CIC 120
SL10 H2A #6 CIC 50
SL11 V03 #6 CIC 70
SL12 V06 #6 CIC 160
SL13 V07 #6 CIC 65
SL14 H7A #6 CIC 45
SL15 H1A #6 CIC 70
TOTAL FT =960 TOTAL FT =
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ . 10.16.20
...
A. VASQUEZ . 10.16.20
REDT # ( RW-116593 )YELM
THE HUTCH
3Ø PRIMARY U/G LINE EXTENSION - 118 S/F LOTS
9306 MOUNTAIN VIEW ROAD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105093614
N/A 8 OF 8
THURSTON N/A N/A QSTHLE
13SE-T17N-R01E N/A N/A
1701E052 1702E068 1701E052 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
----
----
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER
Foreman - Complete
FROM TO
(1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in) Design (ft)90° 45°22° 11°
(Percent) (Percent)Actual Amount Installed Cable Conduit
V01 H1A 350 110 3 110 2 3.3 1.4
V01 H1B 350 90 3 90 2 3.0 1.3
V01 LOT 4 1/O 15 50 2 15 1 3.3 1.8
V01 LOT 5 1/O 15 50 2 15 1 3.3 1.8
V01 LOT 6 1/O 60 50 2 60 1 3.9 2.7
V01 LOT 73 4/O 115 50 3 50 2 3.8 2.7
V01 LOT 76 4/O 160 50 3 95 2 4.1 3.2
H1A LOT 1 1/O 55 50 2 55 1 4.7 3.4
H1A LOT 2 1/O 50 2 0 3.9 2.3
H1A LOT 3 1/O 50 2 0 3.9 2.3
H1B LOT 74 1/O 50 2 3.6 2.2
H1B LOT 75 1/O 50 2 3.6 2.2
V02 H2A 350 135 3 135 3 3.1 1.5
V02 H2B 350 170 3 95 3 3.8 1.7
V02 LOT 21 1/O 55 50 2 55 1 3.6 2.6
V02 LOT 22 1/O 15 50 2 15 1 3.1 1.8
V02 LOT 23 1/O 15 50 2 15 1 3.1 1.8
H2A LOT 24 1/O 50 2 3.7 2.5
H2A LOT 25 1/O 50 2 3.7 2.5
H2B LOT 104 1/O 50 2 4.5 2.7
H2B LOT 105 1/O 50 2 4.5 2.7
H2B LOT 106 4/O 85 50 3 85 2 4.7 3.1 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H2B LOT 107 4/O 85 50 3 85 2 4.7 3.7 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V03 LOT 17 1/O 55 50 2 55 1 3.8 2.9
V03 LOT 18 1/O 15 50 2 15 1 3.2 2.1
V03 LOT 19 1/O 15 50 2 15 1 3.2 2.1
V03 LOT 20 1/O 55 50 2 55 1 3.8 2.9
V03 LOT 95 4/O 165 50 3 100 3 4.1 3.5
V03 LOT 96 4/O 145 140 3 80 2 4.2 3.8 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V04 LOT 13 1/O 65 50 2 65 1 3.4 2.8
V04 LOT 14 1/O 25 50 2 25 1 2.8 2.0
V04 LOT 15 1/O 15 50 2 15 1 2.7 1.8
V04 LOT 16 1/O 50 50 2 50 1 3.2 2.5
V04 LOT 79 4/O 115 50 3 50 2 3.3 2.7
V04 LOT 80 1/O 105 50 3 40 2 3.9 3.6
V04 LOT 81 1/O 110 50 3 45 3 3.9 3.7
V05 LOT 82 1/O 15 50 2 15 1 3.2 2.1
V05 LOT 83 1/O 15 50 2 15 1 3.2 2.1
V05 LOT 91 4/O 105 50 3 40 2 3.7 2.9
V05 LOT 92 4/O 105 50 3 40 2 3.7 2.9
V05 LOT 93 4/O 115 50 3 50 3 3.8 3.0
V05 LOT 94 4/O 160 50 3 95 3 4.1 3.5
V06 LOT 84 1/O 60 50 2 60 1 3.3 2.7
V06 LOT 85 1/O 15 50 2 15 1 2.7 1.8
V06 LOT 86 1/O 15 50 2 15 1 2.7 1.8
V06 LOT 87 1/O 60 50 2 60 1 3.3 2.7
V06 LOT 88 1/O 95 50 3 30 2 3.7 3.4
V06 LOT 89 4/O 115 50 3 50 2 3.3 2.7
V06 LOT 90 4/O 120 50 3 55 3 3.3 2.8
V07 H7A 350 190 3 115 3 3.2 1.9
V07 LOT 7 1/O 65 50 2 65 1 3.6 2.8
V07 LOT 8 1/O 15 50 2 15 1 2.9 1.8
V07 LOT 9 1/O 15 50 2 15 1 2.9 1.8
V07 LOT 10 1/O 55 80 2 55 1 3.8 3.2
V07 LOT 11 4/O 75 125 2 75 1 3.4 3.6
LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V07 LOT 12 4/O 95 85 3 95 1 1 3.8 3.2
H7A LOT 77 1/O 50 2 3.9 2.9
H7A LOT 78 1/O 50 2 3.9 2.9
V08 H8A 350 110 3 110 2 2.7 1.4
V08 LOT 101 1/O 15 50 2 15 1 2.9 1.8
V08 LOT 102 1/O 15 50 2 15 1 2.9 1.8
V08 LOT 103 1/O 60 50 2 60 1 3.5 2.7
V08 LOT 108 4/O 135 50 3 70 2 3.6 3.0
V08 LOT 109 1/O 80 50 3 15 2 3.7 3.1
V08 LOT 110 1/O 95 50 3 30 3 3.9 3.4
H8A LOT 99 1/O 50 2 3.4 2.3
H8A LOT 100 1/O 50 2 3.4 2.3
CONTINUED AT RIGHT...
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER
Foreman - Complete
FROM TO
(1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in) Design (ft)90° 45° 22° 11°
(Percent) (Percent)Actual Amount Installed Cable Conduit
V09 H9A 350 160 3 160 2 1 3.2 1.7
V09 LOT 66 1/O 110 50 3 110 1 4.3 3.7
V09 LOT 67 1/O 60 50 2 60 1 3.7 2.7
V09 LOT 68 1/O 15 50 2 15 1 3.1 1.8
V09 LOT 69 1/O 15 50 2 15 1 3.1 1.8
V09 LOT 70 1/O 60 50 2 60 1 3.7 2.7
V09 LOT 97 4/O 90 140 3 25 2 3.7 3.0
LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V09 LOT 98 4/O 115 50 3 50 2 3.6 2.7
H9A LOT 71 1/O 50 2 3.8 2.7
H9A LOT 72 1/O 50 2 3.8 2.7
V10 H10A 350 145 3 145 2 1 3.6 1.6
V10 LOT 62 1/O 70 50 2 70 1 4.0 2.9
V10 LOT 63 1/O 15 50 2 15 1 3.3 1.8
V10 LOT 64 1/O 15 50 2 15 1 3.3 1.8
V10 LOT 65 1/O 70 50 2 70 1 4.0 2.9
V10 LOT 111 4/O 130 50 3 65 3 3.9 2.9
V10 LOT 112 4/O 125 50 3 60 2 3.9 2.8
V10 LOT 113 1/O 90 50 3 25 2 4.2 3.3
H10A LOT 59 4/O 55 50 2 55 1 4.6 3.1
H10A LOT 60 1/O 50 2 4.2 2.5
H10A LOT 61 1/O 50 2 4.2 2.5
V11 H11A 350 110 3 110 2 3.4 1.4
V11 LOT 56 1/O 15 50 2 15 1 3.3 1.8
V11 LOT 57 1/O 15 50 2 15 1 3.3 1.8
V11 LOT 58 1/O 60 50 2 60 1 3.9 2.7
V11 LOT 114 4/O 130 50 3 65 3 3.9 2.9
V11 LOT 115 1/O 95 50 3 30 3 4.3 3.4
V11 LOT 116 1/O 95 50 3 30 2 4.3 3.4
H11A LOT 54 1/O 50 2 4.1 2.3
H11A LOT 55 1/O 50 2 4.1 2.3
H11A LOT 117 4/O 95 50 3 30 3 4.7 3.3
H11A LOT 118 4/O 95 50 3 30 2 4.7 3.3
V12 H12A 350 145 3 145 2 3.1 1.6
V12 H12B 350 145 3 145 2 3.4 1.6
V12 LOT 28 1/O 55 50 2 55 1 3.6 2.6
V12 LOT 29 1/O 15 50 2 15 1 3.1 1.8
V12 LOT 30 1/O 15 50 2 15 1 3.1 1.8
V12 LOT 31 1/O 55 50 2 55 1 3.6 2.6
H12A LOT 26 1/O 50 2 3.8 2.5
H12A LOT 27 1/O 50 2 3.8 2.5
H12B LOT 32 1/O 50 2 4.0 2.5
H12B LOT 33 1/O 60 2 4.1 2.7
H12B LOT 34 4/O 35 95 2 35 1 4.2 2.9 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V13 H13A 350 110 3 110 2 1 3.4 1.4
V13 LOT 35 4/O 75 120 2 75 1 4.5 3.7
V13 LOT 36 1/O 55 80 2 55 1 4.2 3.2
V13 LOT 37 1/O 15 50 2 15 1 3.3 1.8
V13 LOT 38 1/O 15 50 2 15 1 3.3 1.8
V13 LOT 52 4/O 125 50 3 60 2 3.9 2.8
V13 LOT 53 4/O 120 50 3 55 2 3.9 2.8
H13A LOT 39 1/O 50 2 4.1 2.3
H13A LOT 40 1/O 50 2 4.1 2.3
H13A LOT 50 4/O 120 50 3 55 2 4.5 3.1
LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H13A LOT 51 4/O 85 50 3 20 2 4.6 3.2
V14 H14A 350 110 3 110 2 3.1 1.4
V14 LOT 41 1/O 15 50 2 15 1 3.1 1.8
V14 LOT 42 1/O 15 50 2 15 1 3.1 1.8
V14 LOT 46 4/O 145 50 3 80 2 3.8 3.1
V14 LOT 47 1/O 95 50 3 30 2 4.1 3.4
V14 LOT 48 1/O 95 50 3 30 3 4.1 3.4
V14 LOT 49 4/O 130 50 3 65 2 3.7 2.9
H14A LOT 43 1/O 50 2 3.7 2.3
H14A LOT 44 1/O 50 2 3.7 2.3
H14A LOT 45 1/O 55 50 2 55 1 4.5 3.4
1/O UG Triplex (ft) =2730 2" PVC & BENDS (ft)=1905 56 0 0 0 4.0
4/O UG Triplex (ft) =3565 3" PVC & BENDS (ft)=3630 116 0 4 0 12.1
350 UG Triplex (ft) =1730 TOTAL QTS OF GLUE 16.1