1063-FA MRCSBCEILING MOUNTEDAUDIO/VISUALSEE NOTE 2CEILING MOUNTEDHEAT/SMOKESEE NOTE 16'-8"(80")CEILING MOUNTEDAUDIO/VISUAL SEE NOTE 3MAX 30'-0"(360")CEILING MOUNTEDHEAT/SMOKESEE NOTE 1MAX 6'-0"(72") &MIN 5'-6"(66")TYP.5'-0"(60")TYP.MAX 4'-0"(48")MIN 3'-6"(42")NOTES:1.LOCATE CEILING MOUNTED HEAT/SMOKE DETECTORS ON THE BOTTOM OF THE DECK/SUSPENDED CEILING (NOT ON BOTTOM OF STRUCTURALMEMBERS), AND AS INDICATED IN NFPA 72.2.LOCATE CEILING MOUNTED NOTIFICATION DEVICES ON BOTTOM OF BEAMS OR JOISTS; WITH CLEAR LINE OF SITE IN ALL DIRECTIONS; NO GREATERTHAN THIRTY (30) FEET ABOVE THE FINISHED FLOOR; AND AS INDICATED IN NFPA 72.3.LOCATE CEILING MOUNTED NOTIFICATION DEVICES FLUSH WITH THE SUSPENDED CEILING; ALIGNED WITH LIGHTING, SPRINKLERS, AND OTHERARCHITECTURAL FIXTURES; WITH CLEAR LINE OF SITE IN ALL DIRECTIONS; NO GREATER THAN THIRTY (30) FEET A.F.F. ; AND AS INDICATED INNFPA 72.4.LOCATE WALL MOUNTED NOTIFICATION DEVICES AT 80" A.F.F TO BOTTOM OF BACK BOX.5.COORDINATE EXACT MOUNTING HEIGHT OF CONTROL PANELS, ANNUNCIATORS, AND POWER SUPPLIES WITH THE GENERAL CONTRACTOR,ELECTRICAL CONTRACTOR AND AHJ PRIOR TO INSTALLATION.6.MEASURED TO THE OPERABLE PART OF THE PULL STATION.N.T.S.FAAWALL MOUNTEDAUDIO/VISUALPULL STATIONFACUFAPSB2A,B###cdAFACPFAPSFFIRE ALARM POWER SUPPLY - SILENT KNIGHT SK-5496XXcdWPFADEOLFAAAESHTBDFIRE ALARM CONTROL UNIT- FARENHYT IFP-75bAES RADIO -FIRE ALARM ANNUNCIATOR - FARENHYT RA-100FIRE ALARM DOCUMENT BOXMANUAL PULL STATION - FARENHYT IDP-PULL-SASMOKE DETECTOR - FARENHYT IDP-SMOKE-WHEAT DETECTOR -CEILING MOUNT STROBE - SYSTEM SENSOR - SS-SCRLCEILING MOUNT HORN STROBE - SYSTEM SENSOR - SS-PC2RLWALL MOUNT STROBE -WALL MOUNT WEATHER PROOF/OUTDOOR HORN STROBE -SS-P2RKWALL MOUNT MAGNETIC DOOR HOLDERINDICATES WEATHER RESISTANT DESIGNINDICATES CANDELA RATING OF STROBE LIGHTDENOTES END OF CIRCUIT FOR THAT NAC LOOP11010110105312INDICATES THE CANDELA SETTING OF THE STROBE.INDICATES 1x OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE WIRE TYPE, IN THE WIRE LEGEND.INDICATES 1x EACH OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE WIRE TYPE, IN THE WIRE LEGEND.INDICATES 2 OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE TYPE, THE EXPONENT IS THE NUMBER OF THAT WIRE.DESCRIPTIONWIRE LEGEND SYMBOLSSEE NOTE 6SEE NOTE 5SEE NOTE 4SUSPENDED CEILINGSEE NOTE 5FINISHED FLOORTYPICAL DEVICE MOUNTING HEIGHTCEILING/DECKSYMBOL LEGENDRUNNER SERVICE PROVIDED BYMONITORING SERVICE PROVIDED BY:EXISTINGMITRMONITOR MODULE - FARENHYT IDP-MONITORISOLATION MODULE -RELAY MODULE - FARENHYT IDP-RELAYSPRINKLER TAMPER CONNECTION030FIXED HEAT DETECTOR -0WALL MOUNT HORN STROBE - SYSTEM SENSOR SS-P2RL0THE PURPOSE OF THIS DESIGN IS SPRINKLER MONITORING, AND OCCUPANT NOTIFICATION THROUGHOUTTHE BUILDING, WITH RELAYS PROVIDED FOR CEILING FAN SHUNT.WE ACHIEVE THIS BY SYSTEM SENSOR NOTIFICATION DEVICES THROUGHOUT. AMBIENT SOUND PRESSURELEVELS ARE SPECIFIED IN TABLE A.18.3.2 FROM NFPA 72 2013 HANDBOOK. ANTICIPATED AUDIBILITY ISFIGURED BY THE "6DB RULE OF THUMB" METHOD REFERENCED IN NFPA 72 2013 HANDBOOK.MONITORING IS PROVIDED VIA THE INTEGRATED ONBOARD IP COMMUNICATOR.THE IFP-75B ADDRESSABLE FIRE ALARM PANEL IS POWERED FROM A 20 AMP DEDICATED CIRCUIT. THEBATTERIES ARE SIZED TO PROVIDE 24 HOUR STANDBY WITH 5 MINUTES OF ALARM. COMPLETECALCULATIONS ARE INCLUDED WITH CUT SHEETS.DESIGN NARRATIVESHEET INDEXSHEET NUMBERDISCRIPTIONFA01PROJECT DETAILSFA02FIRE ALARM DEVCE AND WIRE LAYOUTFA03FIRE ALARM RISER DIAGRAMFA04FIRE ALARM ESTIMATED AUDIBILITYGRAPHIC MAPGRAPHIC MAPMODULE DEVICE LISTDEVICE ADD.TYPELOCATION DESCRIPTIONM33:M001MANUAL PULLSTATIONMECH/ELEC RM 108M33:M002SPRINKLER SUPERVISORYMECH/ELEC RM 108M33:M003SPRINKLER SUPERVISORYMECH/ELEC RM 108M33:M004RELAY HVAC SHUTDOWN/CEILING FAN SHUNTWORKSHOP 101M33:M005RELAY HVAC SHUTDOWN/CEILING FAN SHUNTWORKSHOP 102M33:M005RELAY HVAC SHUTDOWN/CEILING FAN SHUNTWORKSHOP 102DETECTOR DEVICE LISTDEVICE ADD.TYPELOCATION DESCRIPTIONM33:S001SMOKE DETECTORMECH/ELEC RM 108 FACP SMOKE DETECTORBUILDING DATAADDRESS:PARCEL #:AREA:TYPE OF CONST:OCCUPANCY:1002 and 1102 RHOTON RD SEYELM, WA. 9859764300800301 and 6430080030219,654 FT²VBF-11FUNCTION 4 KEYFUNCTION 3 KEYFUNCTION 2 KEYFUNCTION 1 KEYDRILL BUTTONAC / BATTERYNOTIFICATTION CUIRCITDEVICE OR MODULESYSTEM COMPONITELEVATOR SHUNT HEAT DETECTORELEVATOR SUPERVISORY CONDITIONSHVAC SUPERVISORY CONDITIONSSPRINKER SUPERVISORY SWITCHESELEVATOR MACHINE ROOM SMOKE DETECTORELEVATOR ALTERNATE LOBBY SMOKE DETECTORSELEVATOR MAIN LOBBY SMOKE DETECTORPULLSTATIONSMOKE DETECTORWATERFLOW SWITCHALARM LED ACTIVATES
SUPERVISORY LED ACTIVATES
TROUBLE LED ACTIVATES
PIEZO ACTIVATES
ALARM WITH POINT ID TRANSMITTED
SUP. WITH POINT ID TRANSMITTED
TROUBLE WITH POINT ID TRANSMITTED
GENERAL ALARM NOTIFICATION
EXTERIOR STROBE ONLY
WATERFLOW BELL
HVAC SHUT DOWN
FIRE DAMPERS CLOSE
ELEVATOR RECALL MAIN
ELEVATOR RECALL ALTERNATE
ELEVATOR RECALL MACHINE ROOM
ELEVATOR SHUNT ACTIVATEDINPUTE DEVICES OR ACTIONS(TYP)OUTPUT DEVICES OR ACTIONS
(TYP)ALARM INITIATING DEVICESFACP DISPLAY / KEYPADAUXILIARY CONTROLS
NOTIFICATION CIRCUITS
AES COMMUNICATOR
FACP FARAP DISPLAYSUPERVISORY INITIATING DEVICESTROUBLE CONDITIONSFACP NAC #1-C WIREFACP NAC #2-D WIRE14 GAUGE 2 CONDUCTOR - FPLP14 GAUGE 2 CONDUCTOR - FPLPHORNS & STROBES.1ST FLOORSLC18 GAUGE 2 CONDUCTOR - FPLPAUSETYPESBUSSBCDDESCRIPTIONDATA CIRCUIT TO SMOKES, PULLS AND SPRINKLER MODULES.HORNS & STROBES. 2ND FLOOR18 GAUGE 4 CONDUCTOR - FPLPDATA CIRCUIT TO ANNUNCIATOR. FUTURE 1ST FLOOR.GFAPS #1-NAC #1-G WIRE14 GAUGE 2 CONDUCTOR - FPLPHORNS & STROBES. 3RD FLOORHFAPS #1-NAC #2-H WIRE14 GAUGE 2 CONDUCTOR - FPLPHORNS & STROBES. 3RD FLOORWIREWIRE LEGENDRev:Date:Description:Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
FIRE ALARM
AutoCAD LT 2021
KLM
KARA@FIRETEKOLYMPIA.COMFA01YELM, WA.
1002 and 1102 RHOTONRD SE
1ST FLOOR
MODERN RESOURCES CABINET SHOP
09/14/2021
09/14/2021
1063
FA-MRCSB
12345678910111234567891011ABB.1CDEE.1FGABB.1CDEE.1FGOFFICE111OFFICE111RR110WORKSHOP103WORKSHOP102WORKSHOP101BREAK RM104MECH/ELEC108RR106RR107COMPRESSOR RM109LOADING DOCK10395cd95cd95cd95cd95cd95cd75cd75cd15cdR15cd75cdFAA30cd30cd75cd75cd15cd15cd15cdFACP FMM FAPSA,B,C,D,G,HBH2A,C,D,G,HA,C,D,G,HA,C,D,G,HA,C,D,G,HA,C,DAA,DA,DA,DA,DA,DDDEOL EOLG,HG,HG,HG,HGHHHEOLEOLAM97:M001M97:S001M97:M002M97:M003M97:M006115cdD2WPRAM97:M005RAM97:M004MODERN RESOURCES CABINET SHOP -- DEVICE AND WIRE LAYOUT04'8'16'SCALE: 1/8"=1'-0"(IN FEET)Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
FIRE ALARM
AutoCAD LT 2021
KLM
KARA@FIRETEKOLYMPIA.COMFA02YELM, WA.
1002 and 1102 RHOTONRD SE
1ST FLOOR
MODERN RESOURCES CABINET SHOP
09/14/2021
09/14/2021
1063
FA-MRCSB
Rev:Date:Description:
FARENHYTIFP-75BUL LISTEDFIRE ALARMCONTROLPANELCIRCUITSA,C,DC-WIRE (NAC #1) HORN STROBES/STROBES(6 DEVICES)EOLSMOKE ABOVE FACPISOLATIONMODULERISER ROOMPULLSTATIONIFIMODERN RESOURCES CABINET SHOP - CIRCUITS A,B,C,D,H,IACDAISOLATIONMODULEAANNUNCIATORRA-100CIRCUIT BSBUSSD-WIRE (NAC #2) HORN STROBES/STROBES(5 DEVICES)EOLAWFTSACDAMMRRRSILENTKNIGHTSK-5496 FIRE ALARMPOWERSUPPLYCIRCUITSH,IGHH-WIRE (FAPS NAC #1) HORN STROBES/STROBES(4 DEVICES)EOLI-WIRE (FAPS NAC #2) HORN STROBES/STROBES(4 DEVICES)EOLHVAC SHUT-DOWNANDCEILING FAN SHUNTBFIRE RISER DIAGRAMN.T.S.Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
FIRE ALARM
AutoCAD LT 2021
KLM
KARA@FIRETEKOLYMPIA.COMFA03YELM, WA.
1002 and 1102 RHOTONRD SE
1ST FLOOR
MODERN RESOURCES CABINET SHOP
09/14/2021
09/14/2021
1063
FA-MRCSB
Rev:Date:Description:
TYPICAL ESTIMATED AUDIBILITY - F-1 OCCUPANCYBASED ON THE TABLE FROM NPFA 72, A.18.4.3, THE EXPECTED AMBIENT AUDIBLE LEVEL IS 40 IN THE RESIDENTIAL UNITS.CODE REQUIRES OUR DEVICES MAINTAIN 15 DB OVER AMBIENT PRESSURE LEVEL. OR A MINIMUM OF 65 DBA IN THERESIDENTIAL UNITS.SYSTEM SENSOR HORN STROBES GENERATE 89DB MEASURED ON THE CENTER LINE 10 FEET FROM THE DEVICE 5 FEET ABOVEFINISHED FLOOR.USING THE 6DB RULE OF THUMB METHOD PUBLISHED IN EXHIBIT 18.11 2013 NFPA72 HANDBOOK, IN THE EXAMPLE ABOVE ALLAREAS EXCEED THE CODE REQUIREMENTSTYPICAL AREA OF AUDIBILITY89DBAWORKSHOP101BREAK RM104MECH/ELEC108RR106RR10775cdFAA75cd75cd15cd15cd15cdFACP
FMM FAPS
EOL83DBA89DBA83DBA77DBA77DBA83DBA77DBA77DBA73DBAESTIMATED AUDIBILITYN.T.S.Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
FIRE ALARM
AutoCAD LT 2021
KLM
KARA@FIRETEKOLYMPIA.COMFA04YELM, WA.
1002 and 1102 RHOTONRD SE
1ST FLOOR
MODERN RESOURCES CABINET SHOP
09/14/2021
09/14/2021
1063
FA-MRCSB
Rev:Date:Description:
OFFICE111RR110WORKSHOP103WORKSHOP102WORKSHOP101BREAK RM104MECH/ELEC108RR106RR107COMPRESSOR RM109LOADING DOCK103EOLEOLEOLEOL
M97:M002M97:M003FAASDPullM97:S001M97:M001MMM97:M004RRRM97:M005M97:M006FACPIFP-75BYOUAREHERESDMFACPIFP-75BFAAPullWALL MOUNT HORN STROBESMOKE DETECTORMONITOR MODULEFIRE ALARM CONTROL PANELFIRE ALARM ANNUNCIATORFIRE ALARM PULL STATIONCEILING MOUNT HORN STROBECEILING MOUNT STROBESYMBOLLEGENDFAPSSK-5496FIRE ALARM POWER SUPPLYRRELAY MODULEFIRE ALARM GRAPHIC MAPMODERN RESOURCESCABINET SHOPYELM, WA.