Building Comments 902 RhotonContainer storage of Div. 1.4G fireworks
Storage of consumer fireworks (Division 1.4G) will be governed by NFPA 1124 and WAC 212-440. As part of site development the City of Yelm adopts the appendix (WAC 212-17-900) per WAC
212-17-440. Plans conforming to the appendix will be supplied during site plan review. The site shall also conform to the International Building Code Chapter 11 for Accessibility,
Chapter 17 for structural design and Chapter 34 plumbing code for onsite sanitation. The City of Yelm development standards for fire lanes and fire hydrants. A 20 foot fire lane
shall be within 150 feet of any container cluster. If the fire lane is not looped it shall meet IFC standards for a fire truck turn around as a hammer head or cul de sac.
The number of fire hydrants shall be based on required fire flow. One hydrant shall be placed within 250 of the street frontage.
Sanitation facilities, office area and refuse containers shall meet the design standards of the City of Yelm Design Guidelines. Containers intended for permanent storage shall be designed
to appear as permanent buildings. Design of all on site required structures shall be submitted as elevations during site plan review.