Part Number 15040 System Design Page 3A-12
3A.3.2 Module Perimeter Coverage, Total Flood (continued)
LOCATE NOZZLE AT MIDPOINT 6" MAXIMUM FROM
OF ADJACENT MODULE EDGE ENTRY POINT
8' MAXIMUM I
TO LATERAL
MODULE
EDGE
HEIGHT
TFP NOZZLE AS VIEWED DIRECTLY FROM BELOW:
UL EX 5208
November 15, 2007
Part Number 15040 System Design Page 3A-14
3A.3.2 Module Perimeter Coverage, Total Flood [continued}
Module Perimeter Total Floodina. IS45ABC Two TFP Nozzles:
The maximum nozzle height above the agent cylinder is 12.5 feet.
UL EX 5208
November 15, 2007
Maximum
Maximum
# of Tees
Pipe Size, in
Length, ft
# of Elbows
Allowed
1
36
4
1
C linder to Tl
1
10
2
0
T 1 to Nozzle
--
56
--
--
Total I' Pi e
The maximum nozzle height above the agent cylinder is 12.5 feet.
UL EX 5208
November 15, 2007
12.5'
12.5'
Part Number 15040 System Design Page 3A-15
3A.3.2 Module Perimeter Coverage, Total Flood 1eyntinued)
Below are Examples of Module Perimeter Total Flood Coverage Using the UP Nozzle:
12.5'
�r
25'
Note: When "stacking" modules vertically, the maximum nozzle height above the cylinder is 12.5
feet.
UL EX 5208
November 15, 2007
Part Number 15040 System Design Page 3A-17
3A.4 Vehicle Paint Spray Booths (continued):
Piping Requirements: Piping diagrams include limitations on pipe length and fittings. System piping must be
balanced. Balanced piping is that in which the difference between the shortest actual pipe length from any%" TEE
to nozzle and the longest actual pipe length from any W TEE to nozzle does not exceed 10% of the longest actual
pipe length from any %" TEE to nozzle. Piping runs from the 1" TEE to each of the 3/" TEE's must be equal in
length. The number and type of fittings for all TEE to nozzle sections must be equal.
All piping must be Schedule 40, hot -dipped galvanized steel pipe, and all fittings must be 150 Ib. class, minimum.
Examples of acceptable fitting materials include hot -dipped galvanized malleable iron, ductile iron, or steel.
Couplings and unions may be used where necessary, and reducing bushings or reducing tees can be used for
changes in pipe diameter. Note: Black steel pipe and fittings can be used in relatively noncorrosive atmospheres.
3A.4.1 Work Area Coverage, VPSB
There are two distinctly different nozzle and piping arrangements for protecting the Work Area using the IS45ABC
cylinder. The first arrangement is "Standard Work Area Coverage", and the second is "Module Perimeter
Work Area Coverage" outlined as follows:
3A.4.1.1 Standard Work Area Coverage, VPSB
The Amerex Vehicle Paint Spray Booth System is flexible enough to protect a wide variety of Vehicle Booths of
various dimensions. The maximum booth height is 23'4". As noted, the IS45 cylinder is used with two or four
nozzles, and each of the nozzles has been tested to protect a Work Area Module. A Work Area can be thought of
as a series of 'boxes', or Modules, stacked together, each protected with a nozzle. The maximum parameters for
each Module are given as follows:
Module Volume: 1,050 ft.3 per nozzle, two or four TF nozzles per IS45ABC
Maximum Module Area: 105 ft.2 per nozzle for booths up to 10 ft. in height;*
45 ft.2 for booths at 23 ft., 4 in. height."
Maximum Module Height: 23 ft., 4 in.
Maximum Module Side Length:
Module Center: 14 ft. for booths up to 10 ft. tall*
9 ft for booths at 234' tall*
Booth Edge: 14 ft for booths up to 10 ft tall
Centerline: 15 ft. (widthwise); booth height limited to 10' tall with this option
*Note: For Module Center Installations with booth heights between 10' and 23'4", reference table 3A-1
Maximum Nozzle Offset — Module Center Entrv: Within a 2.5 ft. radius semicircle from center of module,
no less than 12" from any side of the module (booth); the curved portion of the semicircle must curve
away from the centerline of the booth; the tip of the nozzle within 6" of ceiling.
Maximum Nozzle Offset — Booth Edge Entry: Entry into the module at the closest point to the intersection
of the booth wall and ceiling. The nozzle location, horizontally, is at the midpoint of the longest side of
the module, +/- 2 feet. The tip of the nozzle must be within 6" of its entry point. This option is
allowable only for booths 10 feet or less in height.
Maximum Nozzle Offset — Booth Centerline Entry: This option is available where nozzle entry is only
possible along the centerline of the booth ceiling. Maximum booth height for this option is 10 feet.
This installation configuration allows for a maximum module side length of 15', which is the width of
the Work Area, in this case. There is no allowable nozzle offset for this option. The first and fourth
nozzles are to be located at 12" from the front and back of the booth, respectively. The second and
third nozzles are to be spaced equally between the first and fourth nozzles. The tip of the nozzle must
be within 6" of the ceiling.
UL EX 5208
November 15, 2007
Part Number 15040 System Design Page 3A-29
3A.4.1.2 Module Perimeter Work Area Coverage, VPSB (continued)
*Example 1: a booth of dimensions 16' wide x 12.5' tall x 27-2'long
Module Dimensions: 16'x 13.6'x 12.5' tall;
Use one IS45 with two TFP nozzles, two possible piping options are shown.
12.5'
12
FRO
OF
BOC
NOTE: As in the figures above, the nozzle must either be located on the side of the module (booth) or with
one nozzle located at the edge of the module over the front end of the booth.
UL EX 5208
November 15, 2007
Part Number 15040 System Design Page 3A-41
3A.4.4 Piping Limitations, Plenum and Duct, VPSB (continued)
Zie
Vehicle Paint Spray Boot
DUCT. STANDARD or EXPANDED Plenum Coveraaes. IS35ABC. Two Nozzles:
Cylinder
Nozzle
Nozzle Type
Piping
Maximum
Maximum
Size
Quantity
Section
Pipe
Length, ft.
# of
Size,
Elbows
in.
2
Either of the following
Cylinder
3/4
36
4
IS35ABC
combinations:
to Tl
- one 3 -Way and one D/P;
- two D/P's;
- two 3 -Way's;
T1 to
3/4
16
3
Nozzle
The maximum elevation of the D/P, TF and 3 -way nozzles above cylinder is 23'4".
UL EX 5208
November 15, 2007
_
Fp.-.
■
(9
Z
�
�
D
Z
0
< w
_U /
J CO
O
a.
< g
F-
�
�
W
a.
'a E w
8$ e§
QO§ao
�•-0- -
CC �)-,c)CL0
mme
S{ A§�ƒ$
ul
.O.r-
s"
�8-BUJ[
mama
�2�RkLU&
k§010 2>\k
a&®§E%%
E■uco3a)
aeuo
. R_
£f2�/]2k
kt:11\£o`0
§�§» E2k(D
9/EEILuE-
e§- Lu2m
ƒk;EE15 E
mac-�f®�
cm MR m a g
�ceo'ME 5M
�£ CLacov- (D
E£'2a#2V)
/
w 0
§ k
k
kE
)
� }/
0 of
>
Ix
S8
fG
r
!
It
(9
Z
�
�
D
Z
0
< w
_U /
J CO
O
a.
< g
F-
�
�
W
a.
'a E w
8$ e§
QO§ao
�•-0- -
CC �)-,c)CL0
mme
S{ A§�ƒ$
ul
.O.r-
s"
�8-BUJ[
mama
�2�RkLU&
k§010 2>\k
a&®§E%%
E■uco3a)
aeuo
. R_
£f2�/]2k
kt:11\£o`0
§�§» E2k(D
9/EEILuE-
e§- Lu2m
ƒk;EE15 E
mac-�f®�
cm MR m a g
�ceo'ME 5M
�£ CLacov- (D
E£'2a#2V)
Part Number 15040 System Design Page 3A-40
3A.4.4 ,Piping Limitations, Plenum and Duct, VPSB [continued]
Vehicle Paint SnraY Booths,
DUCT and STANDARD Plenum Coveraaes. IS18ABC. Two Nozzles:
7ZIe
Cylinder
Nozzle
Nozzle Type
Piping
Maximum
Maximum
Size
Quantity
Section
Pipe
Length, ft.
# of
Size,
Elbows
in.
Any of the following
Cylinder
3/4
36
4
ISI8ABC
2
combinations:
to T1
- one 3 -Way and one D/P;
- two D/P's;
- two TF's;
- one TF and one D/P
TI to
3/4
16
3
Nozzle
The maximum elevation of the D/P, TF and 3 -way nozzles above cylinder is 23'4".
UL EX 5208
November 15, 2007