Yelm Creek Estates Lot 2 Plan 2126-2 Final StampedGENE fRAL COTE 5 BUILDING CODE. 2016 INTERNATIONAL BLDG. CODE (IBC), AND BY REFERENCE WHERE APPLICABLE THE 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) AS AMENDED BY LOCAL JURISDICTION. ROOF LIVE LOAD = 25 PSF (SNOW) ROOF DEAD LOAD = 15 PSF FLOOR LIVE LOAD = 40 PSF (REDUCIBLE) FLOOR DEAD LOAD = 15 PSF WIND LOAD = 85 MPH WIND SPEED, EXPOSURE "B" WIND LOAD = 110 MPH WIND SPEED, EXPOSURE "B" PER IBC SOIL SITE CLASS "D" CONSTRUCTION TYPE: VB OCCUPANCY GROUP: R-3 CONTRACTOR SHALL VERIFY ALL NOTES, DIMENSIONS 4 CONDITIONS PRIOR TO CONSTRUCTION, IT IS THE CONTRACTOR'S RESPONSIBILITY TO IDENTIFY ALL OMISSIONS AND/OR DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING WITH WORK. DIMENSIONS TAKE PRECEDENT OVER SCALED DRAWINGS. DEFERRED SUBMITTAL ITEMS THE FOLLOWING IS A LIST OF ITEMS THAT ARE NOT INCLUDED IN THIS PLAN AND SHOULD BE PROVIDED BY THE BUILDER AT TIME OF APPLICATION FOR PERMIT OR AS A DEFERRED SUBMITTAL ITEM: - ALTERNATIVE I-JOIST/BEAM 1" IANUFACTURER PLANS. - MANUFACTURED TRUSS DESIGNS AND LAYOUTS - HVAC SYSTEMS DESIGN - ELECTRICAL PLANS 4 SPECIFICATIONS (IF REQUIRED) 5 I T GENERAL UNLESS A SOILS INVESTIGATION BY A QUALIFIED SOILS ENGINEER IS PROVIDED, FOUNDATION DESIGN IS BASED ON AN ASSUMED AVERAGE SOIL BEARING OF 1500 PSF. EXTERIOR FOOTINGS SHALL BEA R18 (MINIMUM) BELOW FINISHED G ADEALLFOOTINGS TO BEAR ON FIRM UNDISTURBED EARTH BELOW ORGANIC SURFACE SOILS. BACKFILL TO BE THOROUGHLY COMPACTED. BOLT HEADS AND NUTS BEARING AGAINST WOOD TO BE PROVIDED WITH 1/4"x3"x3" PLATE WASHERS. WOOD BEARING ON OR INSTALLED WITHIN I" OF MASONRY OR CONCRETE TO BE PRESSURE TREATED WITH AN APPROVED PRESERVATIVE. FOUNDATION SILL BOLTS TO BE 5/8" DIAMETER AT 6'-0" O.G. U.N.O. WITH MIN. 1" EMBEDMENT METAL FRAMING CONNECTORS TO BE MANUFACTURED BY 5IMP50N STRONG -TIE OR USP STRUCTURAL CONNECTORS IN5ULATICN AND �1015TURE FRCTEC;TICN GENERAL MAINTAIN I" CLEARANCE ABOVE INSULATION FOR FREE AIR FLOW. INSULATION BAFFLES TO EXTEND &" ABOVE BATT INSULATION INSULATION BAFFLES TO EXTEND 12" ABOVE LOOSE FILL INSULATION INSULATE BEHIND TUBS/SHOWERS, PARTITIONS AND CORNERS FACE -STAPLE FACED BATTS FRICTION -FIT UNFACED BATTS USE 4 MIL POLY VAPOR RETARDER AT EXTERIOR WALLS R-10 INSULATION UNDER ELECTRIC WATER HEATERS. INSULATION MATERIALS INSULATION MATERIAL, INCLUDING FACINGS, SUCH AS VAPOR RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN FLOOR -CEILING ASSEMBLIES, ROOF -CEILING ASSEMBLIES, WALL ASSEMBLIES, CRAWL SPACES, AND ATTICS SHALL NAVE A FLAME -SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING SMOKE -DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 EXCEPTIONS: 1. WHEN SUCH MATERIAL ARE INSTALLED IN CONCEALED PAGES, THE FLAME -SPREAD AND SMOKE-DEVELO EM NT LIMITATIONS DO NOT APPLY TO THE FACINGS, PROVIDED THAT THE FACING IS INSTALLED IN SUBSTANTIAL CONTACT WITH THE UNEXPOSED SURFACE OF THE CEILING, FLOOR, OR WALL FINISH. 2, CELLULOSE LOOSE -FILL INSULATION, WHICH IS NOT SPRAY APPLIED, COMPLYING WITH THE REQUIREMENTS OF IRC 8302.1.10.3, SHALL ONLY BE REQUIRED TO MEET THE SMOKE -DEVELOPED INDEX OF NOT MORE THAN 450. INFILTRATION CONTROL EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, PENETRATIONS IN FLOORS, ROOFS AND WALLS AND ALL SIMILAR OPENINGS SHALL BE SEALED, CAULKED, GASKETED OR WEATHERSTRIPPED TO LIMIT AIR LEAKAGE. VAPOR BARRIERS / GROUND COVERS AN APPROVED VAPOR BARRIER SHALL BE PROPERLY INSTALLED IN ROOF DECKS, IN ENCLOSED CEILING SPACES AND AT EXTERIOR WALLS. A GROUND COVER OF 6 MIL (0.006") BLACK POLYETHYLENE OR EQUIVALENT SHALL BE LAID OVER THE GROUND IN ALL CRAWL SPACES. THE GROUND COVER SHALL BE OVERLAPPED ONE FOOT AT EACH JOINT AND SHALL EXTEND TO THE FOUNDATION WALL. WALL FLA&HING APPROVED CORROSION -RESISTANT FLASHING SHALL BE PROVIDED IN THE EXTERIOR WALL ENVELOPE IN SUCH A MANNER AS TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH AND SHALL BE INSTALLED TO PREVENT WATER FROM REENTERING THE EXTERIOR WALL ENVELOPE. APPROVED CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: 1. AT TOP OF ALL EXTERIOR WINDOW AND DOOR OPENINGS IN SUCH A MANNER AS TO BE LEAKPROOF, EXCEPT THAT SELF -FLASHING WINDOWS HAVING A CONTINUOUS LAP OF NOT LESS THAN 1-1/8" (26 mm) OVER THE SHEATHING MATERIAL AROUND THE PERIMETER OF THE OPENING, INCLUDING CORNERS, DOC NOT REQUIRE ADDITIONAL FLASHING± JAMB FLASHING MAY ALSO BE OMITTED WHEN SPECIFICALLY APPROVED BY THE BUILDING OFFICIAL. 2, AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH PROJECTING LIPS ON BOTH SIDES UNDER STUCCO OPENINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD, OR METAL COPINGS AND SILLS. 4. CONTINUOUSLY ABOVE ALLPROJECTING WOOD TRIM. 5, WHERE EXTERIOR PORCHES, DECKS, OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD CONSTRUCTION. 6. AT WALL AND ROOF INTERSECTIONS. T. AT BUILT-IN GUTTERS. FONDATION IJAT lRfROOF INS 4 DA�lf fROOF ING DAMPROOF ING EXCEPT WHERE REQUIRED BY 2018 IRC 84062 TO BE WATERPROOFED, FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE DAMPROOFED FROM THE TOP OF THE FOOTING TO THE FINISHED GRADE. MASONRY WALLS SHALL HAVE NOT LASS THAN $" PORTLAND CEMENT PARGING APPLIED TO THE EXTERIOR OF THE WALL. PARGING SHALL BE DAMPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. 1. BITUMINOUS COATING 2.3 POUNDS PER SQ, YD. OF ACRYLIC MODIFIED CEMENT 3. $' COAT OF SURFACE BONDING CEMENT COMPLYING WITH ASTN C 581 4, ANY MATERIAL APPROVED FOR WATERPFOORING IN 2018 IRC 8406.2 5. OTHER APPROVED METHODS OR MATERIALS. EXCEPTION: PARGING OF UNIT MASONRY WALLS IS NOT REQUIRED WHERE A MATERIAL IS APPROVED FOR DIRECT APPLICATION TO THE MASONRY. FOUI [D AT I ON UJAT R=ROOF IN 4 E)A�IFROOF ING (CONTINUED) WATERPROOFING IN AREAS WHERE HIGH WATER TABLE OR OTHER SEVERE SOIL -WATER CONDITIONS ARE KNOWN TO EXIST, EXTERIOR FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE WATERPROOFED FROM THE TOP OF FOOTING TO FINISHED GRADE. WALLS SHALL BE WATERPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. I. 2 -PLY HOT MOPPED FELT 2.55 POUND ROOF ROLLING 3. 6 -MIL POLYVINYL CHLORIDE 4. 6 -MIL POLYETHYLENE 5. 40 -MIL POLYMER -MODIFIED ASPHALT 6. 6O -MIL FLEXIBLE POLYMER CEMENT 1 8" CEMENT -BASED, FIBER -REINFORCED, WATERPROOF COATING 8. 60 -MIL SOLVANT-FREE, LIQUID -APPLIED SYNTHETIC RUBBER EXCEPTION: ORGANIC -SOLVANT-BASED PRODUCTS SUCH AS HYDROCARBONS, CHLORINATED HYDROCARBONS, KETONS AND ESTERS SHALL NOT BE USED FOR ICF WALLS WITH EXPANDED POLYSTYRENE FOAM MATERIAL. USE OF PLASTIC ROOFING CEMENTS, ACRYLIC COATINGS, LATEX COATINGS, MORTARS AND PARGING5 TO SEAL IGF WALLS IS PERMITTED. COLD -SETTING ASPHALT OR HOT ASPHALT SHALL CONFORM TO TYPE C OF ASTM D 449. HOT ASPHALT SHALL BE APPLIED AT A TEMPERATURE OF LESS THAN 200 DEG, F. ALL JOINTS IN MEMBRANE WATERPROOFING SHALL BE LAPPED AND SEALED WITH AN ADHESIVE COMPATIBLE WITH THE MEMBRANE. DOORS, UJINDOUJS SND 5K1'�1��4TS GENERAL ALL SKYLIGHTS AND SKY WALLS TO BE LAMINATED GLASS UNLESS NOTED OTHERWISE. BEDROOM EMERGENCY EGRESS WINDOWS SHALL HAVE MINIMUM NET CLEAR OPENING OF 5.1 SQ. FT. WITH MINIMUM NET CLEAR OPENING WIDTH OF 20" AND MINIMUM NET CLEAR OPENING HEIGHT OF 24" FINISHED SILL HEIGHT SHALL BE MAXIMUM 44' ABOVE FLOOR, MEASURED FROM THE FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING WINDOW FLASHING TO BE FASTENED PER 2018 IRC 8103.4 WINDOW GUARDS ARE REQUIRED PER 2016 IRC 8312.1 SAFETY GLAZING SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS OR AS OTHERWISE REQUIRED PER 2018 IRC 8308.4.3 SIDE HINGED DOORS EXCEPT JALOUSIES SLIDING GLASS DOORS AND PANELS IN SLIDING 4 51 -FOLD CLOSET DOOR ASSEMBLIES OF A DOOR IN THE CLOSED POSITION 4 BOTTOM EDGE IS LESS THAN 60" ABOVE 1. SHOWER AND BATH TUB, HOT TUB, WHIRLPOOL, SAUNA, STEAM ENCLOSURES 2. GLAZING W/ THE EXPOSED EDGE WITHIN A 24" ARG OF EITHER VERTICAL EDGE 3, STORM DOORS 4 THE WALKING SURFACE 5. GLAZING GREATER THAN 9 S.F. AND LESS THAN 18" ABOVE FINISHED FLOOR GLAZING IN GUARDRAILS �. GLAZING LESS THAN 10" ABOVE FINISHED FLOOR 8, STAIRS AND RAMPS ADJACENT WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 36" ABOVE THE PLANE OF ADJACENT WALKWAY SURFACE OF STAIRWAYS LANDINGS BETWEEN FLIGHTS OF STAIRS AND RAMPS SHALL BE CONSIDER A HAZARDOUS LOCATION. PER 2018 IRC 8308.4.6 MECHANICAL HEATING EQUIPMENT ALL WARM -AIR FURNACES SHALL BE LISTED AND LABELED BY AN APPROVED AGENCY AND INSTALLED TO LISTED SPECIFICATIONS, NO WARM -AIR FURNACES SHALL BE INSTALLED IN A ROOM USED OR DESIGNED TO BE USED AS A BEDROOM, BATHROOM, CLOSET OR IN ANY ENCLOSED SPACE WITH AGGESS ONLY THROUGH SUCH ROOM OR SPACE, EXCEPT DIRECT VENT FURNACE, ENCLOSED FURNAGES AN ELECTRIC HEATING FURNACES. LIQUEFIED PETROLEUM GAS -BURNING APPLIANCES SHALL NOT BE INSTALLED IN A PIT. BASEMENT OR SIMILAR LOCATION WHERE HEAVIER THAN AIR GAS MIGHT COLLECT. APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH AN APPROVED MEANS FOR REMOVAL OF UNBURNED GAS. HEATING AND COOLING EQUIPMENT LOCATED IN A GARAGE AND WHICH GENERATES A GLOW, SPARK OR FLAME CAPABLE OF IGNITING FLAMMABLE VAPORS SHALL BE INSTALLED WITH THE PILOTS AND BURNERS OR HEATING ELEMENTS AND SWITCHES AT LEAST 10 INCHES ABOVE THE FLOOR LEVEL. VENTILATION: SOU1G SPEC IF I C EXH4US7' VENT FAN EFFC NGT REQUIRED IN EACH KITCHEN, BATHROOM, WATER CL05ET COMPARTMENT, LAUNDRY ROOM, INDOOR SWIMMING POOL, 5PA AND OTHER ROOMS WHERE WATER VAPOR OR COOKING ODOR IS PRODUCED. (2018 IRC M1505.IJ FAN EFFICIENCY FROM 2018 WSEC TABLE R403.6.1 MINIMUM SOURCE SPECIFIC VENTILATION CAPACITY REQUIREMENTS: EVERY FACTORY BUILT CHIMNEY, TYPE L VENT, TYPE B GAS VENT OR TYPE BW GAS VENT SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF ITS LISTING, MFR'S INSTALLATION INSTRUCTIONS AND APPLICABLE CODE REQUIREMENTS, A TYPE L VENTING SYSTEM SHALL TERMINATE NOT LESS THAN 2 FEET ABOVE THE HIGHEST POINT WHERE THE VENT PASSES THROUGH THE ROOF OF THE BUILDING AND AT LEAST 2' HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10' OF THE VENT. INTEGRATED WHOLE HOUSE VENT SYSTEM INTEGRATED 24 HR WHOLE HOUSE VENTILATION SYSTEM. • USING A SUPPLY FAN U/ MANUAL 4 MOTORIZED DAMPER. * FAN TIMER EXTERNALLY LOCATED ON THE SIDE OF FURNACE OR GARAGE WALL. 220 GFM REQUIRED U/ A RUN TIME OF S NRS, MIN. FAN MUST OPERATE AT LEAST ONCE EVERY THREE HOURS SO VENTILATION EFFECTIVENESS CAN BE 1.0 * 8" SMOOTH WALL PIPE (OPERATION DESCRIPTION TO BE PROVIDED PER M1505.4) SYSTEM TO BE TESTED AT FINAL INSPECTION 4 LABELED DUCT LEAKAGE TESTING: DUCTS SHALL BE LEAK TESTED IN ACCORDANCE WITH R6-33, USING THE MAXIMUM DUCT LEAKAGE RATES SPECIFIED IN 2018 USEC. 8402.4.1.2 BUILDING AIR LEAKAGE TESTING 2010 USEC 8402.4.1.2 TESTING SHALL OCCUR AT ANY TIME AFTER ROUGH IN AND AFTER INSTALLATION OF PENETRATIONS OF THE BUILDING ENVELOPE. WHEN REQUIRED BY THE BUILDING OFFICIAL, THE TEST SHALL BE CONDUCTED IN THE PRESENCE OF DEPARTMENT STAFF. THE BLOWER DOOR TEST RESULTS SHALL BE RECORDED ON THE CERTIFICATE REQUIRED PER WSEC 8401.3 2018 W,45HINGTON STATE ENERGY CODE - TABLE 402.1.1 INSULATION AND FENESTRATION REQUIRMENT BY COMPONET CLIMATE ZONE 5 4 MARINE 4 - HEATING BY OTHER FUELS FENESTRATION U -FACTOR BATHROOM - UTILITY ROOMS KITCHENS IN-LINE FAN INTERMITTENTLY OPERATING 50 CFM 100 CFM VERTICAL CONTINUOUS OPERATIONS 20 GFM 25 CFM R-49 AIR FLOW RATE MINIMUM (CM) 10 90 ANY ANY MINIMUM EFFICACY (CFM/WATT) 1.4 CFM/WATT 1.4 CFM/WATT 2.8 CFM/WATT 2.8 M/WATT AIR FLOW RATE MAXIMUM (CFM) >90 ANY ANY ANY EVERY FACTORY BUILT CHIMNEY, TYPE L VENT, TYPE B GAS VENT OR TYPE BW GAS VENT SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF ITS LISTING, MFR'S INSTALLATION INSTRUCTIONS AND APPLICABLE CODE REQUIREMENTS, A TYPE L VENTING SYSTEM SHALL TERMINATE NOT LESS THAN 2 FEET ABOVE THE HIGHEST POINT WHERE THE VENT PASSES THROUGH THE ROOF OF THE BUILDING AND AT LEAST 2' HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10' OF THE VENT. INTEGRATED WHOLE HOUSE VENT SYSTEM INTEGRATED 24 HR WHOLE HOUSE VENTILATION SYSTEM. • USING A SUPPLY FAN U/ MANUAL 4 MOTORIZED DAMPER. * FAN TIMER EXTERNALLY LOCATED ON THE SIDE OF FURNACE OR GARAGE WALL. 220 GFM REQUIRED U/ A RUN TIME OF S NRS, MIN. FAN MUST OPERATE AT LEAST ONCE EVERY THREE HOURS SO VENTILATION EFFECTIVENESS CAN BE 1.0 * 8" SMOOTH WALL PIPE (OPERATION DESCRIPTION TO BE PROVIDED PER M1505.4) SYSTEM TO BE TESTED AT FINAL INSPECTION 4 LABELED DUCT LEAKAGE TESTING: DUCTS SHALL BE LEAK TESTED IN ACCORDANCE WITH R6-33, USING THE MAXIMUM DUCT LEAKAGE RATES SPECIFIED IN 2018 USEC. 8402.4.1.2 BUILDING AIR LEAKAGE TESTING 2010 USEC 8402.4.1.2 TESTING SHALL OCCUR AT ANY TIME AFTER ROUGH IN AND AFTER INSTALLATION OF PENETRATIONS OF THE BUILDING ENVELOPE. WHEN REQUIRED BY THE BUILDING OFFICIAL, THE TEST SHALL BE CONDUCTED IN THE PRESENCE OF DEPARTMENT STAFF. THE BLOWER DOOR TEST RESULTS SHALL BE RECORDED ON THE CERTIFICATE REQUIRED PER WSEC 8401.3 2018 W,45HINGTON STATE ENERGY CODE - TABLE 402.1.1 INSULATION AND FENESTRATION REQUIRMENT BY COMPONET CLIMATE ZONE 5 4 MARINE 4 - HEATING BY OTHER FUELS FENESTRATION U -FACTOR CEILING WALL ABOVE GRADE WALL BELOW GRADE MASS WALL FLOOR SLAB ON GRADE VERTICAL OVERHEAD 0.28 0.50 R-49 R-21 R-10/15/21 R -21/21H R-38 R-10 15 90 105 3001-4500 TB 15 90 2' fiE�IPERAfi�RE CONTROL THE PRIMARY SPACE CONDITIONING SYSTEM WITHIN EACH DWELLING UNIT SHALL BE PROVIDED WITH AT LEAST ONE PROGRAMMABLE THERMOSTAT FOR THE REGULATION OF TEMPERATURE 2018 WSEC 8403.1 D1RAFT5TOf f I G 4 FIRE 5LOOT'110�"ING DRAFTSTOPPING WHEN THERE IS USABLE SPACE BOTH ABOVE 4 BELOW THE CONCEALED SPACE OF A FLOOR/CEILING A55EM5LEY, DRAFT5TOP8 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE ABOVE E A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES: I. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS -TYPE OPEN -WEB OR PERFORATED MEMBERS. DRAFTSTOPPING SHALL CONSIST OF MATERIALS LISTED IN 2018 IRC 8302.12 FIREBLOCKING FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO FORM AN EFFECTIVE BARRIER BETWEEN STORIES, AND BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING SHALL BE PROVIDED IN WOOD -FRAME CONSTRUCTION IN THE FOLLOWING LOCATIONS: 1. IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS AS FOLLOWS: 1.1. VERTICALLY AT THE CEILING AND FLOOR LEVELS. U. HORIZONTALLY AT INTERVALS NOT EXCEEDING (Oft 2. AT ALL INTERCONNECTIONS BETWEEN CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR AT SOFFITS DRO C I INGS AND COVE C I INGS. 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER STAIRS SHALL COMPLY WITH 2018 IRC 8302.1 4. AT OPENINGS AROUND VENTS, PIPES, AND DUCTS AT CEILING AND FLOOR LEVEL, WITH AN APPROVED MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND PRODUCTS OF COMBUSTION. 5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES, SEE 2018 IRC 81003.19. 6. FIREBLOCKING OF CORNICES OF A TWO-FAMILY DWELLING IS REQUIRED AT THE LINE OF DWELLING UNIT SEPERATION. FIREBLOCKING SHALL CONSIST OF MATERIALS LISTED IN 2018 IRC SECTION 8302.11.1.3 LOOSE -FILL INSULATION MATERIAL SHALL NOT BE USED AS A FIREBLOGK UNLESS SPECIFICALLY TESTED IN THE FORM AND MANNER INTENDED. THE INTEGRITY OF ALL FIREBLOCKS SHALL BE MAINTAINED. L IGHT ING 2018 WSEC SECTION R404- LIGHTING EQUIPMENT R404.1 LIGHTING EQUIPMENT: NOT LESS THAN 90 PERCENT OF LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH EFFICACY LAMPS R404.1.1 LIGHTING EQUIPMENT. -FUEL GAS LIGHTING SYSTEMS SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. 2018 LUSECR401.3 CERTIFICATE (MANDATORY). A PERMANENT CERTIFICATE SHALL BE COMPLETED BY THE BUILDER OR REGISTERED DESIGN PROFESSIONAL AND POSTED ON A WALL IN THE SPACE WHERE THE FURNACE 15 LOCATED A UTILITY ROOM OR APPROVEDLOCATION INSIDE THE BUILDING. WHEN LOCATED ON AN ELECTRICAL PANEL THE CERTIFICATED SHALL NOT COVER OR OBSTRUCT THE VISIBILITY OF THE CIRCUIT DIRECTORY LABEL, SERVICE DISCONNECT LABEL, OR OTHER REQUIRED LABELS. THE CERTIFICATE SHALL LIST THE PREDOMINANT R -VALUES OF INSULATION INSTALLED IN OR ON CEILING/ROOF, WALL, FOUNDATION (SLAB, BELOW -GRADE WALL, AND/OR FLOOR) AND DUCTS OUTSIDE CONDITIONED SPACES± U -FACTORS FOR FENESTRATION AND THE SOLAR HEAT GAIN COEFFICIENT (SHGC) OF FENESTRATION, AND THE RESULTS FROM ANY REQUIRED DUCT SYSTEM AND BUILDING ENVELOPE AIR LEAKAGE TESTING DONE ON THE BUILDING. WHERE THERE IS MORE THAN ONE VALUE FOR EACH COMPONENT, THE CERTIFICATE SHALL LIST THE VALUE COVERING THE LARGEST AREA, THE CERTIFICATE SHALL LIST THE TYPES AND EFFICIENCIES OF HEATING, COOLING AND SERVICE WATER HEATING EQUIPMENT. WHERE A GAS-FIRED UNVENTED ROOM HEATER, ELECTRIC FURNACE, OR BASEBOARD ELECTRIC HEATER IS INSTALLED IN THE RESIDENCE, THE CERTIFICATE SHALL LIST "GAS-FIRED UNVENTED ROOM HEATER,' 'ELECTRIC FURNACE" OR BASEBOARD ELECTRIC HEATER, 'AS APPROPRIATE. AN EFFICIENCY SHALL NOT BE LISTED FOR GAS-FIRED UNVENTED ROOM HEATER, ELECTRIC FURNACES OR ELECTRIC BASEBOARD HEATER. �T I T"� f;�00�1 NOTE & 1. WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING CONSTRUCTION, THE EQUIVALENT LENGHT OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR TAG SHALL BE LOCATED WITHIN ro FEET OF THE EXHAUST DUCT CONNECTION. 2, INSTALLATIONS EXHAUSTING MORE THAN 200 CFM SHALL BE PROVIDED WITH MAKE UP AIR. WHERE A CLOSET IS DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN OPENING HAVING AN AREA OF NOT LESS THAN 100 SQ, INCHES FOR MAKE UP AIR SHALL BE PROVIDED IN THE CLOSET ENCLOSURE, OR MAKE UP AIR SHALL BE PROVIDED BY OTHER APPR. MEANS, 2018 IRC TABLE M1505.4.3(U CONTINUOUS WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS FLOOR AREA BEDROOMS (FT2) 0-1 2-3 4-5 6-1 > 1 < 1500 30 45 60 15 90 1500-3000 45 60 15 90 105 3001-4500 60 15 90 105 120 4501-6000 15 90 105 120 135 6001-1500 90 105 120 1 135 1 150 > 1500 105 120 135 1 150 165 f=OSTING OF CEIRTIFICATE 84013 CERTIFICATE. A PERMANENT CERTIFICATE SHALL BE COMPLETED BY THE BUILDER OR OTHER APPROVED PARTY AND POSTED ON A WALL IN THE SPACE WHERE THE FURNACE IS LOCATED, A UTILITY ROOM, OR AN APPROVED LOCATION INSIDE THE BUILDING. WHEN LOCATED ON AN ELECTRICAL PANEL, THE CERTIFICATE SHALL NOT COVER OR OBSTRUCT THE VISIBILITY Of THE CIRCUIT DIRECTORY LABEL, SERVICE DISCONNECT LABEL, OR OTHER REQUIRED LABELS. THE CERTIFICATE SHALL LIST THE PREDOMINANT R -VALUES OF INSULATION INSTALLED IN OR ON CEILING/ROOF, WALLS, FOUNDATION (SLAB, BELOW -GRADE WALL, AND/OR FLOOR) AND DUCTS OUTSIDE CONDITIONED SPACES± U -FACTORS FOR FENESTRATION AND THE SOLAR HEAT GAIN COEFFICIENT (SHGC) OF FENESTRATION± THE RESULTS FROM ANY REQUIRED DUCT SYSTEM AND BUILDING ENVELOPE AIR LEAKAGE TESTING DONE ON THE BUILDING*- AND THE RESULTS FROM THE WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FLOW RATE TEST. WHERE THERE IS MORE THAN ONE VALUE FOR EACH COMPONENT, THE CERTIFICATE SHALL LIST THE VALUE COVERING THE LARGEST AREA. THE CERTIFICATE SHALL LIST THE TYPES AND EFFICIENCIES OF HEATING, COOLING, WHOLEHOUSE MECHANICAL VENTILATION, AND SERVICE WATER HEATING APPLIANCES. WHERE A GAS-FIRED UNVENTED ROOM HEATER, ELECTRIC FURNACE, OR BASEBOARD ELECTRIC HEATER IS INSTALLED IN THE RESIDENCE, THE CERTIFICATE SHALL LIS" 'GAS-FIRED UNVENTED ROOM HEATER," "ELECTRIC FURNACE' OR "BASEBOARD ELECTRIC HEATER," AS APPROPRIATE. AN EFFICIENCY SHALL NOT BE LISTED FOR GAS-FIRED UNVENTED ROOM HEATERS, ELECTRIC FURNACES OR ELECTRIC BASEBOARD HEATERS R602.6 DRILLING AND NOTCHING STUDS. DRILLING AND NOTCHING OF STUDS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: 1. NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING PARTITION MAY BE CUT OR NOTHCED TO A DEPTH NOT EXCEEDING 25 PERCENT 2. DRILLING. ANY STUD MAY BE BORED OR DRILLED, PROVIDED THAT OF ITS WIDTH, STUDS IN NONBEARING PARTITIONS MAY BE NOTCHED TO A DEPTH NOT TO EXCEED 40 PERCENT OF A SINGLE STUD WIDTH. THE DIAMETER OF THE RESULTING HOLE IS NO MORE THAN 60 PERCENT THE HOLE IS NO MORE THAN 5/a INCH (1(omm) OF THE STUD WIDTH, THE EDGE OF TO THE EDGE OF THE STUD, AND THE HOLE IS NOT LOCATED IN THE SAME SECTION AS A CUT OR NOTCH. STUDS LOCATED IN EXTERIOR WALLS OR BEARING PARTITIONS DRILLED OVER 40 PERCENT AND UP TO (00 PERCENT SHALL ALSO BE DOUBLED WITH NO MORE THAN TWO SUCCESSIVE DOUBLED STUDS BORED. SEE 2018 IRC FIGURES 8602.6(1) AND 8602.6(2). -EXCEPTION. USE OF APPROVED STUD SHOES IS PERMITTED WHEN THEY ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. R602.6.1 DRILLING AND NOTCHING OF TOP PLATE. WHEN PIPING OR DUCTWORK. IS PLACED IN ORPARTLY IN AN EXTERIOR WALL OR INTERIOR LOAD BEARING WALL, NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A GALVANIZED METAL TIE OF NOT LESS THAN 0.054 INCH THICK (1.31mm) (1(o ea) AND 11/2 INCHES (38mm) WIDE SHALL BE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE OPENING WITH NOT LESS THAN EIGHT 16d NAILS AT EACH SIDE OF EQUIVALENT, SEE 2018 IRC FIGURE R602.6.1. -EXCEPTION: WHEN THE ENTIRE SIDE OF THE WALL WITH THE NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL SHEATHING. 2:018 W,45HINGTON STATE ENERG�' CREDIT-T,45LE R40(o.3 ENERGY CREDIT& ICREDITIOPTIONI DESCRIPTION PRESCRIPTIVE COMPLIANCE 15 BASED ON TABLE 8402.1.1 WITH THE FOLLOWING MODIFICATIONS: VERTICAL FENESTRATION U = 0.28 FLOOR R-38 0.5 1.3 SLAB ON GRADE R-10 PERIMETER AND UNDER ENTIRE SLAB BELOW GRADE SLAB R-10 PERIMETER AND UNDER ENTIRE SLAB OR COMPLIANCE BASED ON SECTION 8402.1.4: REDUCE THE TOTAL CONDUCTIVE UA BY 5%. COMPLIANCE BASED ON R402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 3.0 AIR CHANGES PER HOUR MAXIMUM AT 50 PASCALS OR FOR R-2 OCCUPANCIES, OPTIONAL COMPLIANCE BASED ON SECTION R402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 0.3 CFM/FT2 MAXIMUM AT 50 PASCALS AND ALL WHOLE HOUSE VENTILATION REQUIREMENTS AS DETERMINED BY SECTION 0.5 2.1 MI501.3 OF THE INTERNATIONAL RESIDENTIAL CODE OR SECTION 403.8 OF THE INTERNATIONAL MECHANICAL CODE SHALL BE MET WITH A HIGH EFFICIENCY FAN(S) (MAXIMUM 0.35 WATTS/CFM), NOT INTERLOCKED WITH THE FURNACE FAN (IF PRESENT). VENTILATION SYSTEMS USING A FURNACE INCLUDING AN ECM MOTOR ARE ALLOWED, PROVIDED THAT THEY ARE CONTROLLED TO OPERATE AT LOW SPEED IN VENTILATION ONLY MODE. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED, THE MAXIMUM TESTED BUILDING AIR LEAKAGE, AND SHALL SHOW THE QUALIFYING VENTILATION SYSTEM AND ITS CONTROL SEQUENCE OF OPERATION. AIR -SOURCE CENTRALLY DUCTED HEAT PUMP WITH MINIMUM HSPF OF 9.5. 1.0 3.2 TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE HEATING EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL SUPPLY AND RETURN DUCTS LOCATED IN AN UNCONDITIONED ATTIC SHALL BE DEEPLY BURIED IN CEILING INSULATION IN ACCORDANCE WITH SECTION 8403.3.1. FOR MECHANICAL EQUIPMENT LOCATED OUTSIDE THE CONDITIONED SPACE, A MAXIMUM OF 10 LINEAR FEET OF RETURN DUCT AND 5 LINEAR FEET OF SUPPLY DUCT CONNECTIONS TO THE EQUIPMENT MAY BE OUTSIDE THE DEEPLY BURIED INSULATION. 05 41 ALL METALLIC DUCTS LOCATED OUTSIDE THE CONDITIONED SPACE MUST HAVE BOTH TRANSVERSE AND LONGITUDINAL JOINTS SEALED WITH MASTIC, IF FLEX DUCTS ARE USED, THEY CANNOT CONTAIN SPLICES, DUCT LEAKAGE SHALL BE LIMITED TO 3 CFM PER 100 SQUARE FEET OF CONDITIONED FLOOR AREA. AIR HANDLER(S) SHALL BE LOCATED WITHIN THE CONDITIONED SPACE. WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWING: ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION OR FOR R-2 OCCUPANCY, ELECTRIC HEAT PUMP WATER HEATER(S), MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION, SHALL 2.0 5.5 SUPPLY DOMESTIC HOT WATER TO ALL UNITS. IF ONE WATER HEATER IS SERVING MORE THAN ONE DWELLING UNIT, ALL HOT WATER SUPPLY AND RECIRCULATION PIPING SHALL BE INSULATED WITH R-6 MINIMUM PIPE INSULATION. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE WATER HEATER EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL OF THE FOLLOWING APPLIANCES SHALL BE NEW AND INSTALLED IN THE DWELLING UNIT AND SHALL MEET THE FOLLOWING STANDARDS: DISHWASHER -ENERGY STAR RATED REFRIGERATOR (IF PROVIDED) -ENERGY STAR RATED WASHING MACHINE -ENERGY STAR RATED 0.5 1.1 DRYER -ENERGY STAR RATED, VENTLE55 DRYER WITH A MINIMUM GEF RATING OF 5.2. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SHOW THE APPLIANCE TYPE AND PROVIDE DOCUMENTATION OF ENERGY STAR COMPLIANCE. AT THE TIME OF INSPECTION, ALL APPLIANCES SHALL BE INSTALLED AND CONNECTED TO UTILITIES. DRYER DUCTS AND EXTERIOR DRYER VENT CAPS ARE NOT PERMITTED TO BE INSTALLED IN THE DWELLING UNIT. SYSTEM TABLE R406.2 TYPE FUEL NORMALIZATION CREDITS FOR AN INITIAL HEATING SYSTEM USING A HEAT PUMP THAT MEETS FEDERAL STANDARDS FOR THE EQUIPMENT LISTED IN TABLE C403.3.2(UC OR C403.3.2(2) 0 2 OR AIR TO WATER HEAT PUMP UNITS THAT ARE CONFIGURED TO PROVIDE BOTH HEATING AND COOLING AND ARE RATED IN ACCORDANCE WITH AHRI 550/590 6.0 I TOTAL: c6c: c:o aa) a � J E � 3 cn � c a) 0cl 0 ami a) o-8 o aa>i 2 c= �3�""-M�,owu� aso � Q 0 O 0 E c o .H U L cn -0 a.., Q L �o o� �0 w o x E'cn a-2 aa) m0 a) o"� a)io o6 .� 2 m c0i >.� � m >.L_ L_U a`)i m > IIS �aU 0 > QJIH J 0) 70 Ln co 0% cC 0 V co o H M M Q co 00 M N -.q: lie N N co M W LnN cn Z �o o a U - `REVISION DATE: I INIT: I PROJECT #: VATE: 09/13/2021 1 IN1T: J.K. 5 PROJECT #: R3023 DUELLING -GARAGE OPENING AND PENETRATION PROTECTION, OPENINGS AND PENETRATIONS THROUGH THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SMALL BE IN ACCORDANCE WITH SECTIONS 8302.5.1 THROUGH 8302.5.3, 8302.5.1 OPENING PROTECTION. OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SMALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LE55 THAN 1 a INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB -CORE STEEL DOORS NOT LESS THAN 1 a INCHES (35 MM) THICK, OR 20 -MINUTE FIRE -RATED DOORS, EQUIPPED WITH A SELF-CLOSING DEVICE. 8302.5.2 DUCT PENETRATION. DUCTS IN THE GARAGE AND DUCTS PENETRATING TITE WALLS OR CEILINGS SEPARATING TITE DWELLING FROM TITE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO, 26 GAGE (0.48 MM) SHEET STEEL OR OTITEB APPROVED MATERIAL AND SHALL NOT HAVE OPENINGS INTO THE GARAGE, R302.5.3 OTHER PENETRATIONS. PENETRATIONS THROUGH THE SEPARATION REQUIRED IN SECTION 8302.6 SHALL BE PROTECTED AS REQUIRED BY SECTION 8302.11, ITEM 4 8302.6 DWELLING -GARAGE FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE R302.6 OPENINGS IN GARAGE WALLS SHALL COMPLY WITH SECTION R302.5 ATTACHMENT OF GYPSUM BOARD SHALL COMPLY WITH TABLE 8702.3.5. THE WALL SEPARATION PROVISIONS OF TABLE 8302.6 SHALL NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR THE THE ADJACENT DWELLING UNIT WALL. 8302.7 UNDER -STAIR PROTECTION. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER -STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH z INCH (12.7 MM) GYPSUM BOARD, TA5LE 302.6 DWELL ING-GARAGR SEPARATION *DRYER VENT* PROVIDE PERMANENT LABEL IDENTIFYING ALLOWABLE LENGTH OF DRYER VENT DUCK (LOCATE WITHIN (o FEET OF DUCT CONNECTION) PER M1502.4.5 *NOTE* BUILDING AIR LEAKAGE TEST REQUIRED AS PER W5EC 8402.4.1.2 DUCTS -DUCTS SHALL BE LEAK TESTED IN ACCORDANCE WITH R5-33 PER W5EC R403.2.2 -DUCTS, AIR ITANDLERS, FILTER BOXES SHALL BE SEALED AS PER M1601.4.1 -R403.2.3 SEPARATION MATERIAL INSTALL SMOf<E DETECTORS UJIHERE INDICATED NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM THE RESIDENCE AND ATTICS APPLIED TO THE GARAGE SIDE FROM HABITABLE ROOM ABOVE THE GARAGE NOT LESS 5/a INCH TYPE X GYPSUM 51-, BOARD OR EQUIVALENT STRUCTURES) SUPPORTING FLOOR/CEILIING ASSEMBLIES SF, USED FOR SEPARATION REQUIRED BY THIS SECTION NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT GARAGE LOCATION LESS 3 FEET NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM A DWELLING UNIT ON THE SAME LOT APPLIED TO THE INTERIOR SIDE OF EXTERIOR PATIO: WALLS THAT ARE WITHIN THIS AREA FOR SI : 1 INCH = 25.4 MMJ FOOT =3043 MM. AREA SUMMARY VENTILATION REG- I: EMENTS OF IRC TABLE M1507.4 INSTALL SMOf<E DETECTORS UJIHERE INDICATED MAIN FLOOR: 902 SF, UPPER 1 -LOOK: 122-4 51-, TOTAL: 212ro SF, GARAGE: 380 SF. ENTRY: aro SF. PATIO: 1ro0 SF. SMOKE DETECTORS VENTILATION REG- I: EMENTS OF IRC TABLE M1507.4 INSTALL SMOf<E DETECTORS UJIHERE INDICATED OSD ALL SMOKE DETECTOR DECEIVE TIHERE POUJER FROM TIHE PRIMARY KITCHENS 100 CFM INTERMITTENT OR AND INTERCONNECTED PER 8314 $41-4.ro.4 CARBON MONOXIDE ALARMS 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 2O) FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND, WHERE PRIMARY POWER IS INTERRUPED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL O C/M BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH, OTHER THAN THOSE REQUIRED FOR OVERCURRENT PROTECTION. EXCEPTIONS: I. CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED WHERE INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER. VENTILATION SCHEDULE VENTILATION REG- I: EMENTS OF IRC TABLE M1507.4 SYMBOL KITCHENS 100 CFM INTERMITTENT OR 1 (V.T.0) 25 C1 -M CONTINUOUS IHROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACITY 2O) EEv-TOF 50 CFM MIN. INTERMITTENT OR 20 C1 -M CONTINUOUS VENTILATION RATE FOR UJIHOLE HOUSE FAN TO BE 75 CFM PER TABLE M1507.3.3(1) INDOOR AIR QUALITY HVAC CONTRACTOR TO SPECIFY LOCATION, OPTION WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWING: 5.5 ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'5 ADVANCED WATER HEATING SPECIFICATION. 2x STUDS a 16" c/c 2x4 CLEAT SEISMIC STRAPPING PER — MANUFACTURERS SPECIFICATI (UPC SEC .507.2) SECURE SHAPED 2xIO SPACER TO 2x4 CLEATS WITH (5)-16d NAILS SHAPED 2xIO SPACERS WILL BE CUT TO INSURE A TIGHT FIT TO WATER HEATER WATER HEATER STRAPS WILL RESIST LATERAL FORCES EQUAL TO 100% OF GRAVITY LOADING z PLATFORM MUST f BE ANCHORED SO TO WALL FINISHED FLOOR VENT FLUE UP THRU ROOF MIN. 1/2" DRYWALL 2x STUDS 16" o/c TYI=IC:AL WATER HEATER DETAIL SCALE: N.T.S. W5EC 2018 8403.5.3 HOT WATER PIPE INSULATION (PRESCRIPTIVE) INSULATION FOR HOT WATER PIPE,BOTH WITHIN AND OUTSIDE THE CONDITIONED SPACE, SHALL HAVE A MINIMUM THERMAL RESISTANCE (R -VALUE) OF R-3 2018 UPC 312.6 FREEZING PROTECTION, NO WATER,SOIL,OR WASTE PIPE SHALL BE INSTALLED OR PERMITTED OUTSIDE OF A BUILDING, IN ATTICS OR DRAWL SPACE, OR IN AN EXTERIOR WALL UNLESS, WHERE NECESSARY, ADEQUATE PROVISION IS MADE TO PROTECT SUCH PIPE FROM FREEZING. ALL HOT AND COLD WATER PIPES INSTALLED OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED TO A MINIMUM R-3 -PROVIDE ONE LAYER Sia° GWB TYPE "X" AT CEILINGS COMMON WITH HABITABLE AREAS -WHERE THE SEPARATION 15 A FLOOR - CEILING ASSEMBLY, CLAD ALL SUPPORT COLUMNS, BEAMS AND WALLS WITH ONE LAYER '/211 GWB. -THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ATTIC AREA WITH NO LE55 THAN 11/2" GWB ON THE GARAGE SIDE, LANDING AT EXTERIOR DOORWAY SHALL NOT BE MORE THAN 73/4" BELOW THE TOP OF THRESHOLD PROVIDED THE DOOR, OTHER THAN EXTERIOR STORM OR SCREEN DOORS DOES NOT SWING OVER THE LANDING, IRC 8311.3.2 604.10.1 TRACER WIRE, PLASTIC MATERIALS FOR BUILDING SUPPLY PIPING OUTSIDE UNDERGROUND SHALL HAVE A BLUE INSULATED COPPER TRACER WIRE OF OTHER APPROVED CONDUCTOR INSTALLED ADJACENT TO THE PIPING. ACCESS SHALL BE PROVIDED TO THE TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE GROUND AT EACH END OF THE NONMETALLIC PIPING. THE TRACER WIRE 51ZE SHALL BE NOT LESS THAN IS AWG AND THE INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL, 2x4 CLEAT 2x4 CLEAT MAIN FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" ALL DOOR/UJINDOUJ N1=AD1=R5 TO 5E 4x1O DP*22 AT 2xro 5EAiRINCs UJALLS , U.N.O., (c' -O' MAX. SPAN ALL DOOR/UJINDOUJ HEADERS TO BE 4x10 DF*12 AT 2x4 BEARING UJAL.L.5, U.N.O., (o' -O" MAX. SPAN UJINDOUJ HEADERS AT ro'-a" e a'-0" PLATE & a' -O" HDR e 9'-0" PLATE ABOVE SUB FLOOR, U.N.O. PROVIDE FIREBLOCKING AS REQUIRED (SEE NOTES ON SHEET 1) EXTERIOR UJALLS TO BE 2Xro AT fro" (M,4X.) O.C. U.N.O. INTERIOR PARTITIONS TO BE 2x4 AT fro" O.C. (2Xro e PLUMBING UJALLS, U.N.O.) - DUCTS THROUGH UJALL OR CEILING COMMON TO HOUSE MIN, 2ro GAGE STEEL - NO DUCT OPENINGS IN GARAGE PROVIDE SOLID FRAMING EQUAL TO THE UJIDTH 01= THE MEMBER BEING SUPPORTED PLE>45E REFER TO 5NEET 1/5 FOR ENERGY CREDIT PROPOSED UNDER THE 2010 WA5HINGTON &TATE ENERGY CREDIT -TABLE 8406.3 N (D lr� �I `n c = 0 o m ) 0 -0 � ' CO (D oo��ma�iao � a p U o O Q— Q >+ N m U a ca N� CIS N O N N O N U�,a) N 0— -1 0- CO �U w CD W� :wao oo�NCE� �Uo��c0NOQ� N a... J (� X i CL a� o CO) w N o 0 co o f •N 2) OR) co E w N N Ln 0 co o% E 0 V Co o M M Q co 00 M N -.q: 1 N N co M W LnN cn Z O o a u- ;�EVI510N DATE: I INIT: I PROJECT #: DATE: 09/13/2021 2/1 INIT: J.K. 51PROJEC7 0: * NO FIELD ALTERATIONS WILL BE AUTHORIZED UNLESS ACCOMPANIED BY REVISED DRAWINGS. NOTE: REFER TO STRUCTURAL SHEETS FOR SHEAR WALL SCHEDULE AND ENGINEERING PLAN WHICH CONTAIN DETAIL REFERENCES AND/OR INSTRUCTIONS PERTAINING TO EACH SHEAR WALL INDICATED IN THIS PLAN. NOTE: CONTRACTOR TO VERIFY ALL DIMENSIONS AND CONDITIONS OF PROJECT AND REPORT ANY OMISSIONS/ DISCREPANCIES TO DESIGNER PRIOR TO COMMENCING WORK. DESIGNER SHALL NOT BE RESPONSIBLE FOR DISCREPANT CONDITIONS RESULTING FROM UNAUTHORIZED WORK PERFORMED BY THE CONTRACTOR. CONCRETE CANNOT BE POURED DIRECTLY AGAINST WOOD. WOOD SIDINGS, OR MANUFACTURED SIDING PRODUCTS. CONCRETE CAN BE POURED AGAINST WOOD IN 5UCH A MANOR 45 TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR 571RUC7URAL FRAMING COMPONENTS WHEN FLASHING AND FELT PAPER HAVE BEEN APPLIED OVER THE WOOD, LITH WOOD SIDING A 2" VERTICAL CLEARANCE HAS TO BE MAINTAINED BETWEEN THE WOOD SIDING AND THE CONCRETE SLAB, R17.1 15, MANUFACTURED SIDING, THE MINIMUM VERTICAL DISTANCE OF I" HAS TO BE MAINTAINED OR AS STATED IN THE MANUFACTURE'S INSTALLATION GUIDE. 51DING PRODUCT TUCK CORROSION RESISTANT METAL FLASHING UNDER 51DING GAP (VARIES) PER TYPE OF SIDING 2" MIN. SEE SIDING SPECIFICATIONS RI7.1 05 SLOPE CONCRETE AWAY FROM BUILDING (1/4" PER FOOT MAX. SLOPE FOR LANDINGS) WOOD TO CONCRETE FLASHING DETAIL scALE T 8312.2 WINDOW SILLS IN DWELLING UNITS, WILEIRE THE OPENING OF AN OPERABLE WINDOW IS LOCATED MORE THAN 72 INCH ABOVE THE FINISHED GRADE OR SURFACE BELOW, THE LOUDEST PART OF THE CLEAR OPENING OF THE WINDOW SHALL BE A MINIMUM OF 24 INCHES ABOVE THE FINISHED FLOOR OF THE ROOM IN WHICH THE WINDOW 16 LOCATED. OPERABLE SECTION OF WINDOW SHALL NOT PERMIT OPENINGS THAT ALLOW PA55AGE OF A 4 INCH DIAMETER SPHERE WHERE SUCH OPENING5 ARE LOCATED WITHIN 24 INCHES OF THE FINISHED FLOOR. *DRYER VENT* M1502.4.ro LENGTH IDENTIFICATION. WHERE THE EXHAUST DUCT EQUIVALENT LENGTH EXCEEDS 35 FEET (10 l (oS MM), THE EQUIVALENT LENGTH OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEE (1829 MM) OF THE EXHAUST DUCT CONNECTION VENTILATION SCHEDULE VENTILATION REG= It E1„IENTS OF IRC T,45LE M1507.4 5�'M50L 3 KITCHENS 100 CFM INTERMITTENT OR 1 (V.T.0) 25 CFM CONTINUOUS HROOMS-TOILET ROOMS MECHANICAL EXHAUST CAPACIT'' -�- 2O) EEv-TOF 50 CFM MIN. INTERMITTENT OR 20 5 CFM CONTINUOUS 351-011 UPPER FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/411 " =1'-0 - PROVIDE FIRE5LOC ING AS REQUIRED (SEE NOTES ON SHEET 1) WINDOW HEADERS AT &'=8" o) 8'=0" PLATE 4 8'=0" HDR 9'=0" PLATE 450VE SUIS 1=LOOK, U.N.O. - EXTERIOR I,JALLS TO 5E 2Xro AT 1(o" O.C., U.N.O. - INTERIOR PARTITIONS TO 5E 2X4 AT 1G " O.C. (2XG 15) PLUM5ING JJALLS) U.N.O. - PROVIDE SUPPLEMENTAL JOI375/5LOCKING BELOUJ SHEAR UJALLS AS INDICATED ON FRAMING PLAN - PROVIDE SOLID FRAMING EQUAL TO THE JJIDTH OF THE MEM5ER SEING SUPPORTED (U.N.O.) PLEASE REFER TO SHEET 1/5 FOR ENERGY CREDIT PROPOSED UNDER THE 2018 WASHINGTON STATE ENERGY CREDIT-T,45LE R406.3 N lr� C6c �-J mL �m a 4- -Fn m0 �ai�, o -- ' Q- -:03 o ami m 2-0 o �3 ami 0 —J 0- co rU wQ O N E O m c vo��coNoaco N 4— X i w co E •4) 0N N (� E w N N �� w> QJH +- J REVISION DATE E O V � O H M 00M Q 00 M N -.q: 1 N N coLn cYi W N t!f Z O o a INIT: I PROJECT ": DATE: 3 09/13/2021 INIT: J.K. 5 FROJECT: R-402,4.1.2 TESTING. THE BUILDING OR DWELLING UNIT SHALL BE TESTED AND VERIFIED A5 HAVING AN AIR LEAKAGE RATE OF NOT EXCEEDING 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A BLOWER DOOR AT A PRESSURE OF 0.2 INCHES W.G. (50 PA5CAL5W). WHERE REQUIRED BY THE CODE OFFICIAL, TESTING SHALL BE CONDUCTED BY AN APPROVED THIRD PARTY -4 WRITTEN REPORT OF THE RESULTS OF THE TEST SHALL BE SIGNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE CODE OFFICIAL. TESTING SHALL BE PERFORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF THE BUILDING THERMAL ENVELOPE. ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE 8402.4.1.1), OPERABLE WINDOWS AND DOORS MANUFACTURED BY SMALL BUSINESS SHALL BE PERMITTED TO BE SEALED OFF AT THE FRAME PRIOR TO THE TEST. 3/4" T $ G PLYUUD WEATHER5TRIPPED SIDING PRODUCT 2X BLOCKING TYP. R-38 HD INSULATION IV X 24" MIN CRAWL SPACE ACCESS FLOOR JOISTS AS PER PLAN CRAWL SPACE ACCESS DETAIL SCA= N.T.`- 4" SPHERE NOT P,455, M1 10" MIN. 4,4NDR,41L TO SE PRESENT ON ON AT LEAST ONE SIDE OF STAIR. 44NDGRIP PORTION OF HANDRAILS SHALL HAVE CIRCULAR GROSS SECTION OF 11/4" MIN. $ 2" MAX. ALL REQUIRED GUARDRAILS TO BE aro" 4" MIN, IN 4EIGH7. OPENINGS FOR REQUIRED GUARDS ON THE SIDES OF STAIR TREADS 5N,41 1 NOT ALLOW 4 SPHERE 43/a INCHES (101mm) TO PASS THROUGH MIN. -11/4" MAX NOSING 2X4 THRUST BLOCK 51MPSON LSC ORI5IMUL,4R BRACKET ro" SP4ERE UNABLE TO PASS THROUG4 OPENING BELODU STAIR INSTALL /2" GUUB 'a CEILING, AND WALLS (3) 2X12 STRINGERS FIRE BLOCKING e MID -SPAN AND IN STUD WALLS ALONG AND IN LINE WITH STRINGERS IF AREA UNDER STAIRS IS UNFINISHED INTERIOR/GUARDRAIL STAIR NOTES: - HANDRAILS MUST NOT PROJECT MORE THAN 41/2" INTO THE STAIRWAY AND MUST BE ABLE TO RESIST A 200 Ib. POINT LOAD FROM ANY DIRECTION. IRG SECTIONS 8311.1.1 - LIGHTING IS REQUIRED AT THE TOP, BOTTOM, AND ANY LANDINGS WITH GONTROLS AT THE TOP AND BOTTOM OF STAIRS WITH 6 OR MORE RISERS, IRC SECTION 8303.1 - THE SPACING BETWEEN INTERMEDIATE HANDRAIL MEMBERS MUST NOT ALLOW A 4" SPHERE TO PASS THROUGH ANY OPENING. IRC. SECTION 8312.1.3 - MINIMUM STAIRWAY WIDTH ABOVE HANDRAIL SHALL BE NO LE55 THAN 36 INCHES. IRC SECTION 8311.1.1 - STAIR S STAIR LANDING MINIMUM WIDTH SHALL BE NO LE56 THAN 36" (31/2" CLEAR IF ONE HANDRAIL, S 21" CLEAR IF 2 HANDRAILS. RG SECTION 8311.1.1 - THE TREADS LEADING EDGE CURVATURE CAN HAVE A MAX. RADIUS OF 9/16". THE MAX. BEVELING OF THE NOSING SHALL BE NO MORE THAN 1/2" IRC SECTION 8311.1.5.3 - RISER OR TREAD MAXIMUM DIFFERENTIAL SHALL BE NO MORE THAN 3/a" IRC SECTION 8311.1.5.1 - NOSING IS NOT REQUIRED FOR STAIRS WITH TREADS GREATER THAN II" RC SECTION 8311.1.5.3 EXTERIOR STAIR NOTES: - EXTERIOR STAIR LIGHTING AT TOP LANDING WITH CONTROLS IN51DE THE DWELLING. IRC SECTION 83033 - A MAXIMUM SLOPE OF 1:48 (2%)15 REQUIRED AT EXTERIOR LANDINGS AND TREADS FOR DRAINAGE, IRC SECTION 8311.3 INTERIOR WINDER 57AIR NOTES: - WINDER TREADS ARE REQUIRED TO HAVE A MINIMUM OF 6" DEPTH AT INNER EDGE. RG SECTION 8311.7.5.2.1 - WINDER TREAD DEPTH OF 10" WITH IN 12" OF THE INSIDE, RG SECTION 8311.1.5.2.1 LAND ING NOTES: - LANDING WIDTH SHALL NOT BE LE55 THAN THAT OF STAIR SERVED IRC R311.1.6 - LANDING SHALL NOT BE LE56 THAN 36 INGHE5 IN DIRECTION OF TRAVEL IRC 8311.1.6 STAIR DETAIL z 0 w > m 4C m 11/2 " 4A1RDUJOOD HANDRAIL SOLID BLOCKING AS REQUIRED PRE FINISH METAL BRACKET TYP. T�T' f . 14 4NE) fRA f L R402.4.1.2 TESTING. THE BUILDING C LEAKAGE RATE OF NOT EXCEEDIN BLOWER DOOR AT A PRESSURE 01 OFFICIAL, TESTING SHALL BE CONE RESULTS OF THE TEST SHALL BE S CODE OFFICIAL. TESTING SHALL BE THE BUILDING THERMAL ENVELOPE R402.411), OPERABLE WINDOWS ANI BE SEALED OFF AT THE FRAME PF 2X4 BLOCKING T' 2/2 HIGH 5/8 (-2/211 47 ALL SIDE SCALE: N.T.S. SIDING PER ELEVATIONS ON TYVEK WRAP ON 1/16" PLY OR 055 5HEATI• TOP PLATI COMPOSITION ROOFING ON 15 a FELT UNDERLAYMENT ON 1/16" PLY OR OSB 5HEATHING TYPICAL. MFR, TRUSSES PER PLAN 'a 24" O.C. PER MFG, SPECS. TYP. TOP PLATF TOP PLATE 6' 2 x (o 5TUD5 l6 "o.c. W/ R-21 INSULATION F �R DWELLING UNIT SHALL BE TESTED AND VERIFIED AS HAVING AN AIR 3 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A 0.2 INCHES W.G. (50 PA5CAL5W). WHERE REQUIRED BY THE CODE UCTED BY AN APPROVED THIRD PARTY, A WRITTEN REPORT OF THE GNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE PERFORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF . ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE ) DOORS MANUFACTURED BY SMALL BUSINESS SHALL BE PERMITTED TO OR TO THE TEST. 'P. GWB TYPE "X" 3 WEATHER5TRIPPED TRU55 BOTTOM CHORD GWB TYPE °X° 5/8° G.W.B. TYPE °X° G ACCE55 HATCH- INSULATE FULL DEPTH CEILING CCESS DETAIL FO�ER 3/4" T & G PLYUJD GLUED S NAILED TYP. R -3a INSULATION IS" MIN. CRAWL SPACE W/ 6 MIL VAPOR BARRIER TYPICAL. SECTION "A" R-38 INSULATION J FLOOR TRUSSES A5 PER PLAN GARAGE 4" CONC. SLAB ON------' 4" COMP, FILL TYP, SLOPE 3/16" / FT TOWARD DOORS TnP PI ATF I_I I- ` • -1 _I �I II III -1I II 4" 4 C. TIGHTLINE To STORM SEWER 4" 0 PERF. PLASTIC FTG. DRAIN SET IN WASHED GRAVEL W/ FILTER FABRIC OVER © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" TYPICAL ROOF CONSTRUCTION - COMPOSITION ROOF SHING=, - 151* ROOFING F ELT COMPOSITION RC -- - 1/1(o" SHEATHING RATED 24/1( 1511 FELT PAPER - STRUCTURAL" S'T'STEM AS NOTED ON F=RAMING PLAN 1/16" SHEATHING - R-41:� INSULATION ROOF FRAMING F - 5/8" GUJ5CEILING N6ULA710N BAFF - 1/8" TO 1/4" MESH SCREEN OVER OPENINGS VENTED BLOCKY - MINIMUM NET F=REE VENTILATING AREA SHAT .L. E3E 1/150 5/4 x 8 FASCIA OF: VENTED AREA SPACE OR 1/300 IF- 40-50% CONTINUOUS MET, VENTING IN UPPER ATTIC OR RAF=TER SPACE, PER IRC RBO(o.2 - PROVIDE 1" MINIMUM CLEARANCE SETLUEEN INSULATION R-10 RIGID IN5UL AND SHEATHING AT VENTS PER IRC SECTION RBO(o.3 TYPICAL WALL CONSTRUCTION - SIDING AND/OR VENEER PER ELEVATION - T/1(®" PLS' OR OSB SHTG.( U.N.O ) - TT'VEK BUILDING UURAP OR EO. - 2Xro STUDS �@ Fro" O.C. EXTERIOR LALLS U.N.O. EXTERIOR UJALL NOTCH 25%, BORING 40io G O% 5ORING IF= DOU15LED S NOT MORE THAN TWO SUCCESSIVE STUDS. - 2x4 STUDS -z Fro" O.C., INTERIOR PARTITIONS (2Xro s PLUM5ING UJAI 1 S) NON-15EARING UJ,4LL MAXIMUM NOTCH 40io, 5ORING G o% HOLES NO CLOSER THE 5/B INCH TO FACE OF STUD - R-21 INSULATION UJITH VAPOR 5ARRIER - 1/2" GLUM INTERIOR SHEATHING TYPICAL FLOOR CONSTRUCTION - FINISHED FLOOR PER PLANS - 3/4" TSG PL T LUOOD SU5F=LOOR (GLUE AND NAIL) - FLOOR JOISTS PER PLAN - R-38 INSULATION OVER UNHEATED AREAS SEE NOTE ON SHEET 1 2x6 5TUD5 16" R-21 INSULATION 1/16" SHEATHING TYVEK WRAP - T' SIDING PER ELE\ 3/4" TSG PLYWOOE FLOOR JOISTS PE WINDOW HDR, PEf 5/4 TRIM 5URROU WINDOW W/ INS. Gl 3/4" TSG PLYWOOL FLOOR JOISTS PE R -38C INSULATIC 5/4 X 10 TRIM B< 2X P.T. WOOD SIL 4" GO TO STOP 4" PE SET IN l W/ FILTE 7, 5UBFL SUB w TYPICAL WALL SECTION SCALE : N.T.S. NOTE: T/16" 514EATl4INU NOT REOI IRED ON EXT. �JALL5 aUI ERE 71=11 51DING 15 5PECIFIED (UNLE55 N07ED 07I4ERUJIH IN file 514EAR JALL 5PEC;IFIC;A710N5) (D N rmN c6c o a N U W N S J i EC � � N-6 �cna) ;oo�}.00Qo -CD o i o oma — a �,a) co 0--5 -a co� a)� `a m o ate) a) o� o a� ami o c� o o- — ,— J Qca cU ti co § MaC oo2�cRE Q oQ N c o o a� N cd C a+ J Q ca c Q N 0O "c) N- p a) -2 QcnoE-�a)� cc$E co)T 0) .Fn 70 �n 00 O, Q E 0 V � O H M 00M Q 00 M N -.q: 1 N N co cYi LnZ N O o a ;�E:VI510N DATE: I INIT: I PROJECT : DATE: 09/13/202 4 INIT: J.K. 5 PROJECT �: R-49 INSULATION__) UT I L. E34TH. //LOFT /' T S G PLYWD A \ / GLUED $ NAILED TYP. \ SUB FLOORf, t A I �, — SUB FLOOR TOP PLATE 6' 2 x (o 5TUD5 l6 "o.c. W/ R-21 INSULATION F �R DWELLING UNIT SHALL BE TESTED AND VERIFIED AS HAVING AN AIR 3 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A 0.2 INCHES W.G. (50 PA5CAL5W). WHERE REQUIRED BY THE CODE UCTED BY AN APPROVED THIRD PARTY, A WRITTEN REPORT OF THE GNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE PERFORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF . ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE ) DOORS MANUFACTURED BY SMALL BUSINESS SHALL BE PERMITTED TO OR TO THE TEST. 'P. GWB TYPE "X" 3 WEATHER5TRIPPED TRU55 BOTTOM CHORD GWB TYPE °X° 5/8° G.W.B. TYPE °X° G ACCE55 HATCH- INSULATE FULL DEPTH CEILING CCESS DETAIL FO�ER 3/4" T & G PLYUJD GLUED S NAILED TYP. R -3a INSULATION IS" MIN. CRAWL SPACE W/ 6 MIL VAPOR BARRIER TYPICAL. SECTION "A" R-38 INSULATION J FLOOR TRUSSES A5 PER PLAN GARAGE 4" CONC. SLAB ON------' 4" COMP, FILL TYP, SLOPE 3/16" / FT TOWARD DOORS TnP PI ATF I_I I- ` • -1 _I �I II III -1I II 4" 4 C. TIGHTLINE To STORM SEWER 4" 0 PERF. PLASTIC FTG. DRAIN SET IN WASHED GRAVEL W/ FILTER FABRIC OVER © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" TYPICAL ROOF CONSTRUCTION - COMPOSITION ROOF SHING=, - 151* ROOFING F ELT COMPOSITION RC -- - 1/1(o" SHEATHING RATED 24/1( 1511 FELT PAPER - STRUCTURAL" S'T'STEM AS NOTED ON F=RAMING PLAN 1/16" SHEATHING - R-41:� INSULATION ROOF FRAMING F - 5/8" GUJ5CEILING N6ULA710N BAFF - 1/8" TO 1/4" MESH SCREEN OVER OPENINGS VENTED BLOCKY - MINIMUM NET F=REE VENTILATING AREA SHAT .L. E3E 1/150 5/4 x 8 FASCIA OF: VENTED AREA SPACE OR 1/300 IF- 40-50% CONTINUOUS MET, VENTING IN UPPER ATTIC OR RAF=TER SPACE, PER IRC RBO(o.2 - PROVIDE 1" MINIMUM CLEARANCE SETLUEEN INSULATION R-10 RIGID IN5UL AND SHEATHING AT VENTS PER IRC SECTION RBO(o.3 TYPICAL WALL CONSTRUCTION - SIDING AND/OR VENEER PER ELEVATION - T/1(®" PLS' OR OSB SHTG.( U.N.O ) - TT'VEK BUILDING UURAP OR EO. - 2Xro STUDS �@ Fro" O.C. EXTERIOR LALLS U.N.O. EXTERIOR UJALL NOTCH 25%, BORING 40io G O% 5ORING IF= DOU15LED S NOT MORE THAN TWO SUCCESSIVE STUDS. - 2x4 STUDS -z Fro" O.C., INTERIOR PARTITIONS (2Xro s PLUM5ING UJAI 1 S) NON-15EARING UJ,4LL MAXIMUM NOTCH 40io, 5ORING G o% HOLES NO CLOSER THE 5/B INCH TO FACE OF STUD - R-21 INSULATION UJITH VAPOR 5ARRIER - 1/2" GLUM INTERIOR SHEATHING TYPICAL FLOOR CONSTRUCTION - FINISHED FLOOR PER PLANS - 3/4" TSG PL T LUOOD SU5F=LOOR (GLUE AND NAIL) - FLOOR JOISTS PER PLAN - R-38 INSULATION OVER UNHEATED AREAS SEE NOTE ON SHEET 1 2x6 5TUD5 16" R-21 INSULATION 1/16" SHEATHING TYVEK WRAP - T' SIDING PER ELE\ 3/4" TSG PLYWOOE FLOOR JOISTS PE WINDOW HDR, PEf 5/4 TRIM 5URROU WINDOW W/ INS. Gl 3/4" TSG PLYWOOL FLOOR JOISTS PE R -38C INSULATIC 5/4 X 10 TRIM B< 2X P.T. WOOD SIL 4" GO TO STOP 4" PE SET IN l W/ FILTE 7, 5UBFL SUB w TYPICAL WALL SECTION SCALE : N.T.S. NOTE: T/16" 514EATl4INU NOT REOI IRED ON EXT. �JALL5 aUI ERE 71=11 51DING 15 5PECIFIED (UNLE55 N07ED 07I4ERUJIH IN file 514EAR JALL 5PEC;IFIC;A710N5) (D N rmN c6c o a N U W N S J i EC � � N-6 �cna) ;oo�}.00Qo -CD o i o oma — a �,a) co 0--5 -a co� a)� `a m o ate) a) o� o a� ami o c� o o- — ,— J Qca cU ti co § MaC oo2�cRE Q oQ N c o o a� N cd C a+ J Q ca c Q N 0O "c) N- p a) -2 QcnoE-�a)� cc$E co)T 0) .Fn 70 �n 00 O, Q E 0 V � O H M 00M Q 00 M N -.q: 1 N N co cYi LnZ N O o a ;�E:VI510N DATE: I INIT: I PROJECT : DATE: 09/13/202 4 INIT: J.K. 5 PROJECT �: * NO FIELD ALTERATIONS WILL BE AUTHORIZED UNLESS ACCOMPANIED BY REVISED DRAWINGS, NOTE: REFER TO STRUCTURAL SHEETS FOR SHEAR WALL SCHEDULE AND ENGINEERING PLAN WHICH CONTAIN DETAIL REFERENCES AND/OR INSTRUCTIONS PERTAINING TO EACH SHEAR WALL INDICATED IN THIS PLAN. NOTE: CONTRACTOR TO VERIFY ALL DIMENSIONS AND CONDITIONS OF PROJECT AND REPORT ANY OMISSIONS/ DISCREPANCIES TO DESIGNER PRIOR TO COMMENCING WORK. DESIGNER SHALL NOT BE RESPONSIBLE FOR DISCREPANT CONDITIONS RESULTING FROM UNAUTHORIZED WORK PERFORMED BY THE CONTRACTOR. RIGHT ELEVATION SCALE: 1/4" =1'-0" LEFT ELEVATION 0 N FRIEZE BOARD AT REAR ELEVATION SCALE: 1/4" =1'-0" _ ADE A 6" GRADE FALL AUJA1' FROM STRUCTURE IN FIRST 10'. 1 x 3 TRIM BD, ON 12 12 5/4 X S BARGE BD. T1'P. �g �9 DONT. METAL GUTTER ON 5/4 X 8 F,45GIA BD, T1'P. UJRAP P.T. POST TO --� 12" SQUARE COLUMN w/ Ix CEDAR OR UJKITE WOOD FRONT ELEVATION IS" e RAKE lT1'PJ 5/4 X 4 WINDOW TRIM lTl'PJ BOARD 8 BATT 5IDING- 3x BATT& a 16" O.G. 5/4 X 10 BAND 5D, 8" BEVEL SIDING 5/4 X 4 TRIM 5D NOTE: APPROVED NUM5ER& OR ADDRESSES &L4ALL 13E PROVIDED FOR ALL NEW 5UILDING6 IN &UCL4 A POSITION A& TO 13E PLAINLY VleI5LE AND LEG15LE FROM THE STREET OR ROAD FRONTING THE PROPERTY. ADDRESS NUMSER& ARE REQUIRED TO BE 4" NIGH WITH A 1/2" STROKE. N (D lr� �I C6 c O 0 J L oo��ma-6iao .CD ao iOoma —Q O N N O a'- N 0---.r2J Qco �U a O N O w c E 0cc -j coNoa"'EN +� J (� )( i a) cis a 0 a) o w� N o 0 O O E •N N O (Z O N H colo is w> QJ -HE IJ a E O V O M M 00 Q 00 M ca N -.q: Ln00 N N cv; ca > W N t!f Z O o a SCALE: 1/4" =1'-0" © 2021 Level Design, LLC. SCALE: 1/411 =1'-0" REVISION DATE: INIT: PROJECT - VERIFY &N€AR WALL NAILING AND 1-IOLDOWN& ARE PER PLAN AND SCHEDULE PRIOR TO INSTALLING SIDING - MASONRY AND WOOD FRAME CNIMNE''r'S ARE TO 5E CONSTRUCTED PER I.R.C. - PROVIDE GALVANIZED SHEET METAL FLASHING AND COUNTERFLA&NING AT ALL ROOF / WALL INTERSECTIONS, CLANNEX&, AND SKYLIGHTS - PROvID€ W€ATN€RSTRIPPING AND FLA&NING AT ALL DOORS AND WINDOWS AS R€QUIR€D - CAULK ALL €XT€RIOR JOINTS AND P€N€TRATION& - POST ADDRESS ON 5LDG, PRIOR TO FINAL INSPECTION - LOTS SI -TALL 5E GRADED AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALL. SLOPE SHALL 5E (o" IN FIRST 10 FT, OR DRAINS OR &WALES SHALL BE PROVIDED TO ENSURE DRAINAGE AWAY FROM STRUCTURE - FA&TENER& TO 5E NOT -DIPPED GALv. STEEL, STAINLESS OR ALUM. (CORRO&ION RE&ISTANT) NOTE: PROVIDE CONTINUOS PRE -PAINTED G.I. "Z" FLASKING AT ALL EXT. DOOR & WINDOW KEADERS, DATE: 09/13/202 5/1 INIT: J.K. 51FROJEC7 0: CI � ISI CI UJRAP P.T. POST TO --� 12" SQUARE COLUMN w/ Ix CEDAR OR UJKITE WOOD FRONT ELEVATION IS" e RAKE lT1'PJ 5/4 X 4 WINDOW TRIM lTl'PJ BOARD 8 BATT 5IDING- 3x BATT& a 16" O.G. 5/4 X 10 BAND 5D, 8" BEVEL SIDING 5/4 X 4 TRIM 5D NOTE: APPROVED NUM5ER& OR ADDRESSES &L4ALL 13E PROVIDED FOR ALL NEW 5UILDING6 IN &UCL4 A POSITION A& TO 13E PLAINLY VleI5LE AND LEG15LE FROM THE STREET OR ROAD FRONTING THE PROPERTY. ADDRESS NUMSER& ARE REQUIRED TO BE 4" NIGH WITH A 1/2" STROKE. N (D lr� �I C6 c O 0 J L oo��ma-6iao .CD ao iOoma —Q O N N O a'- N 0---.r2J Qco �U a O N O w c E 0cc -j coNoa"'EN +� J (� )( i a) cis a 0 a) o w� N o 0 O O E •N N O (Z O N H colo is w> QJ -HE IJ a E O V O M M 00 Q 00 M ca N -.q: Ln00 N N cv; ca > W N t!f Z O o a SCALE: 1/4" =1'-0" © 2021 Level Design, LLC. SCALE: 1/411 =1'-0" REVISION DATE: INIT: PROJECT - VERIFY &N€AR WALL NAILING AND 1-IOLDOWN& ARE PER PLAN AND SCHEDULE PRIOR TO INSTALLING SIDING - MASONRY AND WOOD FRAME CNIMNE''r'S ARE TO 5E CONSTRUCTED PER I.R.C. - PROVIDE GALVANIZED SHEET METAL FLASHING AND COUNTERFLA&NING AT ALL ROOF / WALL INTERSECTIONS, CLANNEX&, AND SKYLIGHTS - PROvID€ W€ATN€RSTRIPPING AND FLA&NING AT ALL DOORS AND WINDOWS AS R€QUIR€D - CAULK ALL €XT€RIOR JOINTS AND P€N€TRATION& - POST ADDRESS ON 5LDG, PRIOR TO FINAL INSPECTION - LOTS SI -TALL 5E GRADED AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALL. SLOPE SHALL 5E (o" IN FIRST 10 FT, OR DRAINS OR &WALES SHALL BE PROVIDED TO ENSURE DRAINAGE AWAY FROM STRUCTURE - FA&TENER& TO 5E NOT -DIPPED GALv. STEEL, STAINLESS OR ALUM. (CORRO&ION RE&ISTANT) NOTE: PROVIDE CONTINUOS PRE -PAINTED G.I. "Z" FLASKING AT ALL EXT. DOOR & WINDOW KEADERS, DATE: 09/13/202 5/1 INIT: J.K. 51FROJEC7 0: 9/27/2021 SHEAR WALLSMARK CALLOUTTYPICAL SHEARWALL NOTESTYPICAL HOLDDOWN NOTES*TYPEDESCRIPTIONTYPICAL SHEARWALL NOTES9/27/2021 ” ’’’9/27/2021 9/27/2021 9/27/2021