Loading...
21-005 Stevens 4-Plex Hyd Calc 10-12 - stamped "ON GUARD 24 HOURS A DAY" KNIGHT FIRE PROTECTION, INC. 9702 Lathrop Industrial Dr. SW OLYMPIA, WA 98512 (360) 786-8606 FAX 786-8722 LICENSE NO. KNIGHFP044LK "QUALITY IS REMEMBERED... LONG AFTER PRICE IS FORGOTTEN!" FIRE SPRINKLER HYDRAULIC CALCULATIONS FOR Stevens 4-Plex 314 Stevens Ave. NE Yelm, WA KFP Contract No. 21-005 • Calc Area 111-1 (Wet System) • Calc Area 211-1 (Wet System) • Calc Area 311-1 (Wet System) • Calc Area 411-1 (Wet System) Certificate of Competency Stamp For Entire Set of Calculations. Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :314 Stevens Ave. NE System :111 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 111-3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 10-12-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:314 Stevens Ave. NE Drawing no:2 of 2 Date:10-12-21 Design Remote area number:111 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 33 - Psi Type of system:Wet Flow-Through Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 10-12-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.012 D2 - System Pressure : 32.613 Hose ( Demand ):_______ D3 - System Demand :26.012 Safety Margin : 23.385 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 10-12-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 10-12-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 111H 17.0 4.9 7.09 na 13.05 0.05 256 7.0 112H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 111 17.5 7.34 na 112 17.5 7.25 na A1 17.5 7.6 na B1 8.5 13.05 na C1 8.5 14.03 na D1 8.5 14.71 na TOR1 8.5 15.68 na BOR1 3.0 21.67 na FLG1 0.5 23.51 na MTR1 -3.0 31.9 na SRC 1.0 32.61 na The maximum velocity is 8.77 and it occurs in the pipe between nodes A1 and B1 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 111H 13.05 1.101 N 7.0 3.170 7.090 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 111 13.05 0.0309 0.0 15.170 0.469 Vel = 4.40 0.0 13.05 7.342 K Factor = 4.82 112H 12.96 1.101 N 7.0 3.170 7.000 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 112 12.96 0.0305 0.0 15.170 0.463 Vel = 4.37 0.0 12.96 7.246 K Factor = 4.81 *MAIN 111 14.78 1.101 O 5.0 1.670 7.342 to 150.0 0.0 5.000 0.0 A1 14.78 0.0388 0.0 6.670 0.259 Vel = 4.98 0.0 14.78 7.601 K Factor = 5.36 112 11.24 1.101 O 5.0 10.170 7.246 to 150.0 0.0 5.000 0.0 A1 11.24 0.0234 0.0 15.170 0.355 Vel = 3.79 0.0 11.24 7.601 K Factor = 4.08 111 -1.73 1.101 6N 42.0 78.670 7.342 to 150.0 2O 10.0 52.000 0.0 112 -1.73 -0.0007 0.0 130.670 -0.096 Vel = 0.58 0.0 -1.73 7.246 K Factor = -0.64 * A1 26.01 1.101 O 5.0 9.000 7.601 to 150.0 0.0 5.000 3.898 B1 26.01 0.1106 0.0 14.000 1.549 Vel = 8.77 B1 -12.69 1.101 2N 14.0 27.670 13.048 to 150.0 2O 10.0 24.000 0.0 D1 13.32 0.0321 0.0 51.670 1.658 Vel = 4.49 0.0 13.32 14.706 K Factor = 3.47 B1 12.69 1.101 2O 10.0 23.580 13.048 to 150.0 0.0 10.000 0.0 C1 12.69 0.0293 0.0 33.580 0.985 Vel = 4.28 C1 0.0 1.101 O 5.0 17.920 14.033 to 150.0 0.0 5.000 0.0 D1 12.69 0.0294 0.0 22.920 0.673 Vel = 4.28 D1 13.32 1.101 N 7.0 1.830 14.706 to 150.0 0.0 7.000 0.0 TOR1 26.01 0.1106 0.0 8.830 0.977 Vel = 8.77 0.0 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 6 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn 26.01 15.683 K Factor = 6.57 * TOR1 26.01 1.101 Fsp 0.0 5.500 15.683 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR1 26.01 0.1105 0.0 5.500 0.608 Vel = 8.77 BOR1 0.0 1.101 Ball 4.303 2.500 21.673 to 150.0 0.0 4.303 1.083 FLG1 26.01 0.1107 0.0 6.803 0.753 Vel = 8.77 FLG1 0.0 1.314 0.0 40.000 23.509 to 150.0 0.0 0.0 6.516 * * Fixed Loss = 5 MTR1 26.01 0.0468 0.0 40.000 1.870 Vel = 6.15 MTR1 0.0 1.314 Ball 1.405 35.000 31.895 to 150.0 2O 16.0 17.405 -1.732 SRC 26.01 0.0468 0.0 52.405 2.450 Vel = 6.15 0.0 26.01 32.613 K Factor = 4.55 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :314 Stevens Ave. NE System :211 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 211-3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 10-12-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:314 Stevens Ave. NE Drawing no:2 of 2 Date:10-12-21 Design Remote area number:211 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:648 - SqFt Coverage per sprinkler:324 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):35 - GPM @ 45 - Psi Type of system:Wet Flow-Through Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 10-12-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :34.514 D2 - System Pressure : 45.195 Hose ( Demand ):_______ D3 - System Demand :34.514 Safety Margin : 10.802 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 10-12-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 10-12-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 211H 17.0 4.9 12.81 na 17.54 0.05 324 12.0 212H 17.0 4.9 12.0 na 16.97 0.05 324 12.0 211 17.5 12.89 na 212 17.5 12.51 na A2 17.5 14.15 na B2 8.5 20.66 na C2 8.5 21.08 na D2 8.5 22.08 na TOR2 8.5 23.73 na BOR2 3.0 30.14 na FLG2 0.5 32.49 na MTR2 -3.0 42.16 na SRC 1.0 45.2 na The maximum velocity is 11.63 and it occurs in the pipe between nodes A2 and B2 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 211H 17.54 1.101 O 5.0 0.500 12.813 K Factor = 4.90 to 150.0 0.0 5.000 -0.217 211 17.54 0.0535 0.0 5.500 0.294 Vel = 5.91 0.0 17.54 12.890 K Factor = 4.89 212H 16.97 1.101 N 7.0 2.500 12.000 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 212 16.97 0.0503 0.0 14.500 0.729 Vel = 5.72 0.0 16.97 12.512 K Factor = 4.80 *MAIN 211 22.66 1.101 O 5.0 9.670 12.890 to 150.0 0.0 5.000 0.0 A2 22.66 0.0858 0.0 14.670 1.258 Vel = 7.64 0.0 22.66 14.148 K Factor = 6.02 212 11.86 1.101 3N 21.0 32.250 12.512 to 150.0 2O 10.0 31.000 0.0 A2 11.86 0.0259 0.0 63.250 1.636 Vel = 4.00 0.0 11.86 14.148 K Factor = 3.15 211 -5.12 1.101 3N 21.0 43.250 12.890 to 150.0 O 5.0 26.000 0.0 212 -5.12 -0.0055 0.0 69.250 -0.378 Vel = 1.73 0.0 -5.12 12.512 K Factor = -1.45 * A2 34.51 1.101 O 5.0 9.000 14.148 to 150.0 0.0 5.000 3.898 B2 34.51 0.1866 0.0 14.000 2.613 Vel = 11.63 B2 -9.03 1.101 O 5.0 8.330 20.659 to 150.0 0.0 5.000 0.0 D2 25.48 0.1065 0.0 13.330 1.420 Vel = 8.59 0.0 25.48 22.079 K Factor = 5.42 B2 9.03 1.101 2O 10.0 16.750 20.659 to 150.0 0.0 10.000 0.0 C2 9.03 0.0156 0.0 26.750 0.418 Vel = 3.04 C2 0.0 1.101 2N 14.0 45.080 21.077 to 150.0 O 5.0 19.000 0.0 D2 9.03 0.0156 0.0 64.080 1.002 Vel = 3.04 D2 25.48 1.101 N 7.0 1.830 22.079 to 150.0 0.0 7.000 0.0 TOR2 34.51 0.1867 0.0 8.830 1.649 Vel = 11.63 0.0 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 6 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn 34.51 23.728 K Factor = 7.08 * TOR2 34.51 1.101 Fsp 0.0 5.500 23.728 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR2 34.51 0.1867 0.0 5.500 1.027 Vel = 11.63 BOR2 0.0 1.101 Ball 4.303 2.500 30.137 to 150.0 0.0 4.303 1.083 FLG2 34.51 0.1867 0.0 6.803 1.270 Vel = 11.63 FLG2 0.0 1.314 0.0 40.000 32.490 to 150.0 0.0 0.0 6.516 * * Fixed Loss = 5 MTR2 34.51 0.0789 0.0 40.000 3.156 Vel = 8.16 MTR2 0.0 1.314 Ball 1.405 35.000 42.162 to 150.0 3O 24.0 25.405 -1.732 SRC 34.51 0.0789 0.0 60.405 4.765 Vel = 8.16 0.0 34.51 45.195 K Factor = 5.13 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :314 Stevens Ave. NE System :311 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 311-3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 10-12-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:314 Stevens Ave. NE Drawing no:2 of 2 Date:10-12-21 Design Remote area number:311 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:648 - SqFt Coverage per sprinkler:324 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):35 - GPM @ 45 - Psi Type of system:Wet Flow-Through Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 10-12-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :34.514 D2 - System Pressure : 45.195 Hose ( Demand ):_______ D3 - System Demand :34.514 Safety Margin : 10.802 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 10-12-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 10-12-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 311H 17.0 4.9 12.81 na 17.54 0.05 324 12.0 312H 17.0 4.9 12.0 na 16.97 0.05 324 12.0 311 17.5 12.89 na 312 17.5 12.51 na A3 17.5 14.15 na B3 8.5 20.66 na C3 8.5 21.08 na D3 8.5 22.08 na TOR3 8.5 23.73 na BOR3 3.0 30.14 na FLG3 0.5 32.49 na MTR3 -3.0 42.16 na SRC 1.0 45.2 na The maximum velocity is 11.63 and it occurs in the pipe between nodes A3 and B3 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 311H 17.54 1.101 O 5.0 0.500 12.813 K Factor = 4.90 to 150.0 0.0 5.000 -0.217 311 17.54 0.0535 0.0 5.500 0.294 Vel = 5.91 0.0 17.54 12.890 K Factor = 4.89 312H 16.97 1.101 N 7.0 2.500 12.000 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 312 16.97 0.0503 0.0 14.500 0.729 Vel = 5.72 0.0 16.97 12.512 K Factor = 4.80 *MAIN 311 22.66 1.101 O 5.0 9.670 12.890 to 150.0 0.0 5.000 0.0 A3 22.66 0.0858 0.0 14.670 1.258 Vel = 7.64 0.0 22.66 14.148 K Factor = 6.02 312 11.86 1.101 3N 21.0 32.250 12.512 to 150.0 2O 10.0 31.000 0.0 A3 11.86 0.0259 0.0 63.250 1.636 Vel = 4.00 0.0 11.86 14.148 K Factor = 3.15 311 -5.12 1.101 3N 21.0 43.250 12.890 to 150.0 O 5.0 26.000 0.0 312 -5.12 -0.0055 0.0 69.250 -0.378 Vel = 1.73 0.0 -5.12 12.512 K Factor = -1.45 * A3 34.51 1.101 O 5.0 9.000 14.148 to 150.0 0.0 5.000 3.898 B3 34.51 0.1866 0.0 14.000 2.613 Vel = 11.63 B3 -9.03 1.101 O 5.0 8.330 20.659 to 150.0 0.0 5.000 0.0 D3 25.48 0.1065 0.0 13.330 1.420 Vel = 8.59 0.0 25.48 22.079 K Factor = 5.42 B3 9.03 1.101 2O 10.0 16.750 20.659 to 150.0 0.0 10.000 0.0 C3 9.03 0.0156 0.0 26.750 0.418 Vel = 3.04 C3 0.0 1.101 2N 14.0 45.080 21.077 to 150.0 O 5.0 19.000 0.0 D3 9.03 0.0156 0.0 64.080 1.002 Vel = 3.04 D3 25.48 1.101 N 7.0 1.830 22.079 to 150.0 0.0 7.000 0.0 TOR3 34.51 0.1867 0.0 8.830 1.649 Vel = 11.63 0.0 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 6 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn 34.51 23.728 K Factor = 7.08 * TOR3 34.51 1.101 Fsp 0.0 5.500 23.728 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR3 34.51 0.1867 0.0 5.500 1.027 Vel = 11.63 BOR3 0.0 1.101 Ball 4.303 2.500 30.137 to 150.0 0.0 4.303 1.083 FLG3 34.51 0.1867 0.0 6.803 1.270 Vel = 11.63 FLG3 0.0 1.314 0.0 40.000 32.490 to 150.0 0.0 0.0 6.516 * * Fixed Loss = 5 MTR3 34.51 0.0789 0.0 40.000 3.156 Vel = 8.16 MTR3 0.0 1.314 Ball 1.405 35.000 42.162 to 150.0 3O 24.0 25.405 -1.732 SRC 34.51 0.0789 0.0 60.405 4.765 Vel = 8.16 0.0 34.51 45.195 K Factor = 5.13 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :314 Stevens Ave. NE System :411 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 411-3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 10-12-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:314 Stevens Ave. NE Drawing no:2 of 2 Date:10-12-21 Design Remote area number:411 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 33 - Psi Type of system:Wet Flow-Through Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 10-12-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.012 D2 - System Pressure : 32.613 Hose ( Demand ):_______ D3 - System Demand :26.012 Safety Margin : 23.385 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 10-12-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 10-12-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 411H 17.0 4.9 7.09 na 13.05 0.05 256 7.0 412H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 411 17.5 7.34 na 412 17.5 7.25 na A4 17.5 7.6 na B4 8.5 13.05 na C4 8.5 14.03 na D4 8.5 14.71 na TOR4 8.5 15.68 na BOR4 3.0 21.67 na FLG4 0.5 23.51 na MTR4 -3.0 31.9 na SRC 1.0 32.61 na The maximum velocity is 8.77 and it occurs in the pipe between nodes A4 and B4 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 411H 13.05 1.101 N 7.0 3.170 7.090 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 411 13.05 0.0309 0.0 15.170 0.469 Vel = 4.40 0.0 13.05 7.342 K Factor = 4.82 412H 12.96 1.101 N 7.0 3.170 7.000 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 412 12.96 0.0305 0.0 15.170 0.463 Vel = 4.37 0.0 12.96 7.246 K Factor = 4.81 *MAIN 411 14.78 1.101 O 5.0 1.670 7.342 to 150.0 0.0 5.000 0.0 A4 14.78 0.0388 0.0 6.670 0.259 Vel = 4.98 0.0 14.78 7.601 K Factor = 5.36 412 11.24 1.101 O 5.0 10.170 7.246 to 150.0 0.0 5.000 0.0 A4 11.24 0.0234 0.0 15.170 0.355 Vel = 3.79 0.0 11.24 7.601 K Factor = 4.08 411 -1.73 1.101 6N 42.0 78.670 7.342 to 150.0 2O 10.0 52.000 0.0 412 -1.73 -0.0007 0.0 130.670 -0.096 Vel = 0.58 0.0 -1.73 7.246 K Factor = -0.64 * A4 26.01 1.101 O 5.0 9.000 7.601 to 150.0 0.0 5.000 3.898 B4 26.01 0.1106 0.0 14.000 1.549 Vel = 8.77 B4 -12.69 1.101 2N 14.0 27.670 13.048 to 150.0 2O 10.0 24.000 0.0 D4 13.32 0.0321 0.0 51.670 1.658 Vel = 4.49 0.0 13.32 14.706 K Factor = 3.47 B4 12.69 1.101 2O 10.0 23.580 13.048 to 150.0 0.0 10.000 0.0 C4 12.69 0.0293 0.0 33.580 0.985 Vel = 4.28 C4 0.0 1.101 O 5.0 17.920 14.033 to 150.0 0.0 5.000 0.0 D4 12.69 0.0294 0.0 22.920 0.673 Vel = 4.28 D4 13.32 1.101 N 7.0 1.830 14.706 to 150.0 0.0 7.000 0.0 TOR4 26.01 0.1106 0.0 8.830 0.977 Vel = 8.77 0.0 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 6 Stevens 4-Plex Date 10-12-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn 26.01 15.683 K Factor = 6.57 * TOR4 26.01 1.101 Fsp 0.0 5.500 15.683 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR4 26.01 0.1105 0.0 5.500 0.608 Vel = 8.77 BOR4 0.0 1.101 Ball 4.303 2.500 21.673 to 150.0 0.0 4.303 1.083 FLG4 26.01 0.1107 0.0 6.803 0.753 Vel = 8.77 FLG4 0.0 1.314 0.0 40.000 23.509 to 150.0 0.0 0.0 6.516 * * Fixed Loss = 5 MTR4 26.01 0.0468 0.0 40.000 1.870 Vel = 6.15 MTR4 0.0 1.314 Ball 1.405 35.000 31.895 to 150.0 2O 16.0 17.405 -1.732 SRC 26.01 0.0468 0.0 52.405 2.450 Vel = 6.15 0.0 26.01 32.613 K Factor = 4.55 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087