Pal W 10 NHD #I-949-O Eng.STRUCTURAL NOTES DESIGN CRITERIA: 1. BUILDING CODE: 2018 INTERNATIONAL BUILDING CODE 2. VERTICAL LOADS: ROOF FLOOR DECK LIVE LOAD 0 psf 40 psf 60 psf SNOW LOAD 20 psf 0 psf 25 psf DEAD LOAD 15 psf 10 psf 10 psf 3. LATERAL LOAD FORCES TRANSMITTED BY DIAPHRAGM ACTION TO WOOD SHEARWALLS AND THENCE TO FOUNDATION WHERE DISPLACEMENT IS RESISTED BY PASSIVE PRESSURE AND SLIDING FRICTION OF EARTH. 4. SNOW DESIGN DATA (ASCE 7-16) FLAT SNOW LOAD, pf: 20 psf SNOW EXPOSURE FACTORY, Cc: 1.0 SNOW IMPORTANCE FACTOR, is: 1.0 THERMAL FACTOR, ct: 1.0 5. WIND DESIGN DATA (ASCE 7-16) WIND SPEED: Vult=110 mph RISK CATEGORY: II EXPOSURE CATEGORY: B 6. SEISMIC DESIGN DATA (ASCE 7-16) SEISMIC FORCE RESISTING SYSTEM: WOOD SHEARWALLS RISK CATEGORY: II SEISMIC IMPORTANCE FACTOR, Ie:=1 MAPPED SPECTRAL RESPONSE ACCELERATION: Ss=1.29, S 1=.466 DESIGN SPECTRAL RESPONSE ACCELERATION: Sds=1.029, Shc=.528 SITE CLASS: D SEISMIC DESIGN CATEGORY: D SEISMIC RESPONSE COEFFICIENT, Cs: .158 RESPONSE MODIFICATION COEFFICIENT, R: 6.5 EQUIVALENT LATERAL FORCE PROCEDURE (ASCE 7 12.8. 1) DESIGN BASE SHEAR: 12.68k 7. SOIL PROPERTIES BEARING CAPACITIES: 1500 psf LATERAL CAPACITY: 250 psf/ft GENERAL THE STRUCTURAL CONSTRUCTION DOCUMENT REPRESENTS THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTORS MEANS, METHODS, TECHNIQUES, SEQUENCES OF PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR MATERIALS, SUCH STANDARDS SHALL BE THE LATEST ADDITION AND/OR ADDENDA. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. OPTIONS FOR CONTRACTOR'S CONVENIENCE. IF AN OPTION IS CHOSEN, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CHANGES AND SHALL COORDINATE ALL DETAILS. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO START OF CONSTRUCTION. RESOLVE ANY DISCREPANCIES WITH ARCHITECT. TYPICAL DETAILS MAY NOT NECESSARILY BE CUT ON PLANS, BUT APPLY UNLESS NOTED OTHERWISE. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN. ANY ENGINEERING DESIGN, PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF A REGISTERED ENGINEER RECOGNIZED BY THE BUILDING CODE JURISDICTION OF THIS PROJECT. ALL GRAVITY LOADS RESISTING AND LATERAL LOAD RESISTING STRUCTURAL MEMBERS ARE SHOWN ON THE ENGINEERING S PAGES. THE ENGINEERING CALCULATIONS ARE NOT REQUIRED TO BE REFERENCED FOR CONSTRUCTION, AND DON'T NEED TO BE ONSITE. CONTRACTOR SHALL VERIFY ALL NOTES, DIMENSIONS AND CONDITIONS PRIOR TO CONSTRUCTION. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AS REQUIRED UNTIL ALL PERMANENT CONNECTIONS HAVE BEEN INSTALLED. ENGINEER AND DESIGNER SHALL BE NOTIFIED BY THE CONTRACTOR OF ANY DISCREPANCIES AT THE TIME THEY ARE NOTED. CONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING UTILITY LINES. CALL 1-800-424-5555 48 HOURS BEFORE DIGGING. INFORM ENGINEER OF ALL CHANGES PROPOSED ON THE DRAWINGS OR SPECIFICATIONS BY THE ARCHITECT -NOTES PRIOR TO CONSTRUCTION OF THE CHANGE. CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION MEANS, METHOD, TECHNIQUES, SEQUENCES, PROCEDURES, SAFETY OF THE WORKERS AND STABILITY OF THE STRUCTURE DURING CONSTRUCTION AND FOR COORDINATING ALL PORTIONS OF THE WORK. DRAWINGS SHALL BE USED FOR ONLY ONE CONSTRUCTION AND FOR LOCATIONS INDICATED HEREIN. PLYWOOD WEB JOISTS DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST EDITION I.C.C. REPORT ESR -1305. CONNECTIONS AND BEARING MATERIAL TO BE SHOP CONNECTED TO JOISTS AND DESIGNED AND FURNISHED BY JOIST FABRICATOR. MANUFACTURED I -JOISTS SHALL CONFORM TO ASTM505. CALCULATIONS SHALL INCLUDE DEFLECTION AND CAMBER REQUIREMENTS. DEFLECTION SHALL BE LIMITED AS FOLLOWS: FLOOR LIVE LOAD MAXIMUM = L/480. FLOOR TOTAL LOAD MAXIMUM = L/240. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WITH DESIGN CALCULATIONS SEALED BY A REGISTERED ENGINEER FOR REVIEW PRIOR TO MANUFACTURE. ADDITIONAL JOISTS SHALL BE SUPPLIED AS REQUIRED TO SUPPORT MECHANICAL EQUIPMENT. FOUNDATIONS ALL FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED SOIL OR APPROVED FILL 12" MINIMUM BELOW FINISHED GRADE. FINISHED GRADE IS DEFINED AS TOP OF SLAB FOR INTERIOR FOOTINGS AND LOWEST ADJACENT GRADE EXTENDING UP TO 5 FEET FROM WALL FOR PERIMETER FOOTINGS. DESIGN SOIL BEARING VALUE = 1500 PSF. WHERE REQUIRED BY THE BUILDING OFFICIAL, THE CLASSIFICATION AND INVESTIGATION OF THE SOIL SHALL BE PERFORMED BY A REGISTERED DESIGN PROFESSIONAL (1806.2) UNLESS A SOIL INVESTIGATION IS PROVIDED. FOUNDATION DESIGN IS BASED ON AN ASSUMED AVERAGE SOIL BEARING OF 1500 PSF. ORGANIC SILT, ORGANIC CLAYS, PEAT OR UNPREPARED FILL SHALL NOT BE ASSUMED TO HAVE BEARING CAPACITY (1806.2) THIS ENGINEERING IS BASED ON SITE CLASS D SOILS IN ACCORDANCE WITH TABLE 1806.2 OF THE 2018 IBC. SITE GRADING: THE GROUND IMMEDIATELY ADJACENT TO THE FOUNDATION SHALL BE SLOPED AWAY FROM THE BUILDING AT A SLOPE OF NOT LESS THAN 5 PERCENT FOR A MINIMUM OF 10 FEET. COMPACTED FILL MATERIAL SHALL NOT BE USED UNLESS ALLOWED BY A SOILS ENGINEERING REPORT. CONCRETE MINIMUM 28 DAY STRENGTH 2,500 PSI (fc = 2,500 PSI), 52 SACK U.N.O. ALL CONCRETE CONSTRUCTION SHALL CONFORM TO A.C.I. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT SLABS ON GRADE NEED ONLY BE VIBRATED AT TRENCHES, FLOOR DUCTS, TURNDOWNS, ETC. MINIMUM SLUMP 412" FOR CONCRETE WITHOUT PLASTICIZER. IF PLASTICIZER IS USED, A HIGHER FINAL SLUMP MAY BE ALLOWED UPON STRUCTURAL ENGINEER'S APPROVAL. UNLESS APPROVED OTHERWISE IN WRITING BY THE ARCHITEC, ALL CONCRETE SLABS ON GRADE SHALL BE BOUND BY CONTROL JOINTS (KEYED OR SAW CUT), AS SHOWN ON THE FOUNDATION PLAN, SUCH THAT THE ENCLOSED AREA DOES NOT EXCEED 225 SQUARE FEET. KEYED CONTROL JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING POURING, ALL OTHER JOINTS MAY BE SAW CUT. FLY ASH - IF PERMITTED BY ARCHITECTURAL SPECIFICATIONS - SHALL BE LIMITED TO 18% OF CEMENTITIOUS MATERIALS AND SHALL HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT REPLACED. NO FLY ASH ADDITIVES SHALL BE USED IN FLATWORK OR ARCHITECTURALLY EXPOSED CONCRETE. CONCRETE MINIMUM REINFORCEMENT THE FOLLOWING MINIMUM REINFORCEMENT SHALL BE PROVIDED U.N.O. ON THE DRAWING: 1. PROVIDE HORIZONTAL CORNER BARS AT ALL FOOTINGS AND WALL CORNERS AND HOOK BARS FOR T INTERSECTIONS WITH EQUAL SIZE AND SPACING OF THE HORIZONTAL REINFORCING USING THE INDICATED DETAILS OF SIMILAR SECTIONS AND DETAILS AS TYPICAL. 2. PROVIDE ONE #4 VERTICAL BAR - FULL HEIGHT OF WALL AT THE CORNER OR T INTERSECTION. 3. PROVIDE A MINIMUM OF 0.2% REINFORCEMENT OF GROSS CONCRETE AREA OF WALL IN HORIZONTAL DIRECTION AND 0.12% IN VERTICAL DIRECTION. MAXIMUM REBAR SPACING IS 18" O.C. IN EACH DIRECTION. 4. PROVIDE A MINIMUM #4 BARS AT 12" ON CENTER IN ISOLATED FOOTINGS. 5. PROVIDE REINFORCING CHAIRS IN ACCORDANCE WITH CRSI PLACING MANUAL. 6. PROVIDE WWF 6X6X1OX10 FOR 4" SLAB. 7. PROVIDE CONSTRUCTION JOINT AT 20' MAXIMUM UNLESS NOTED OTHERWISE (SAW CUT 25% OF SLAB THICKNESS). NAILS: USE COMMON NAIL ONLY. IF BOX OR OTHER TYPE OF NAILS ARE USED, SIZE ADJUSTMENTS ARE REQUIRED. PROVIDE NAIL PER IBC TABLE 2304. 10.1 GALVANIZE NAIL WHEN EXPOSED TO WEATHER. SIMPSON ZMAX AND HOT DIPPED ZINC NAILS SHALL BE USED FOR ALL PRESSURE TREATED WOODS OTHER THAN CHROMATED COPPER ARSENATE AND SODUIM BORATE. PREFABRICATED WOOD TRUSSES PREFABRICATED WOOD TRUSSES SHALL BE DESIGNED TO SUPPORT SELF WEIGHT PLUS LIVE LOAD AND SUPERIMPOSED DEAD LOADS STATED IN THE GENERAL STRUCTURE NOTES OR AS LOCATED ON PLANS. BRIDGING SIZE AND SPACING SHALL BE BY TRUSS MANUFACTURER/TRUSS DESIGNER UNLESS NOTED OTHERWISE. CONTRACTOR SHALL SUBMIT A TRUSS SUBMITTAL PACKAGE AS DEFINED IN IBC SECTION 2303.4.1.4, INCLUDING, BUT NOT LIMITED TO, INDIVIDUAL TRUSS DESIGN DRAWINGS, TRUSS PLACEMENT DIAGRAM AND TRUSS MEMBER PERMANENT BRACING REQUIREMENTS. TRUSS DOCUMENTS SHALL BE SEALED BY A REGISTERED DESIGN PROFESSIONAL AS REQUIRED BY IBC SECTION 2303.4.1.3. CALCULATIONS AND SHOT DRAWINGS SHALL SHOW ANY SPECIAL DETAILS REQUIRED AT BEARING POINTS. ALL CONTRACTORS SHALL HAVE CURRENT I.C.C. APPROVAL. CALCULATIONS SHALL INCLUDE DEFLECTION AND CAMBER REQUIREMENTS. DEFLECTION SHALL BE LIMITED AS FOLLOWS: ROOF TOTAL LOAD MAXIMUM= L/240. ROOF LIVE LOAD MAXIMUM= L/360. TRUSS TOP CHORD MATERIAL SHALL HAVE A SPECIFIC GRAVITY OF NOT LESS THAN 0.43. MULTIPLE TRUSS MEMBERS SHALL BE FASTENED TOGETHER TO ALLOW TRANSFER OF SHEAR AND TENSION FORCES (MINIMUM 200 PLF) AT PLYWOOD SHEATHING JOINTS AND TO PREVENT CROSS GRAIN BENDING OF TOP CHORDS. ATTACHMENT SHALL BE A CONTINUOUS 20 GAGE METAL PLATE OR OTHER APPROVED MEANS. METHOD OF ATTACHMENT SHALL BE INDICATED ON SHOP DRAWINGS FOR REVIEW. TRUSS MANUFACTURER SHALL HAVE LCC APPROVAL OR BE AN APPROVED FABRICATOR ACCORDING TO THE BUILDING JURISDICTION. TRUSS MANUFACTURER SHALL PERMANENTLY IDENTIFY EACH TRUSS. GLUE -LAMINATED BEAMS (GLULAM GLUED - LAMINATED BEAMS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES: Fb= 240OPSI, Fv= 265PSI, Fc (PERPENDICULAR)= 650 PSI, E= 1,800,000 PSI. CONTINUOUS BEAMS OR BEAMS CANTILEVERING OVER SUPPORTS SHALL HAVE THE SPECIFIED MINIMUM PROPERTIES TOP AND BOTTOM. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE. FABRICATION AND HANDLING PER LATEST AITC AND WCLA STANDARDS. BEAM TO BEAR GRADE STAMP AND AITC STAMP AND CERTIFICATE. CAMBER AS SHOWN ON DRAWINGS. STRUCTURAL GLUED -LAMINATED TIMBER SHALL CONFORM TO AITC A190.1 AND ASTM D 3737. kJOTAKelm LUMBER SHALL CONFORM TO DOC PS 20. MANUFACTURED LUMBER SHALL BE AS SPECIFIED ON THE PLAN SET. DESIGN OF THE MANUFACTURED LUMBER IS THE RESPONSIBILITY OF THE SUPPLIER. JOISTS: WOOD TYPE: 2X4 H.F. #2 2X6 OR LARGER H.F. #2 BEAMS: RATIO WIDTH 4" OR LESS D.F. #2 WIDTH GREATER THAN 4" D.F. #2 LEDGERS AND TOP PLATES: H.F. #2 STUDS: B.O.F .............................BOTTOM OF FOOTING 2X4 H.F. #2 2X6 OR LARGER H.F. #2 POSTS: 3/4" T&G 4X4 H.F. #2 4X6 OR LARGER D.F. #2 6X6 OR LARGER D.F. #2 CONNECTORS: METAL CONNECTORS, ANCHORS, AND FASTENERS WILL CORRODE AND LOSE LOAD CARRYING CAPACITY WHEN INSTALLED IN CORROSIVE ENVIRONMENTS OR EXPOSED TO CORROSIVE MATERIALS. THERE ARE MANY ENVIRONMENTS AND MATERIALS WHICH MAY CAUSE CORROSION INCLUDING: OCEAN SALT WATER, PRESERVATIVE -TREATED WOOD, FUMES, FIRE -RETARDANTS, DISSIMILAR METALS, FERTILIZERS. F2XW V,161 101 ALL PLYWOOD SHALL BE AMERICAN PLYWOOD ASSOCIATION CDX-RATED SHEATHING OR BETTER, AND SHALL BEAR THE STAMP OF AN APPROVED TESTING AGENCY. LAY UP PLYWOOD WITH FACE GRAIN PERPENDICULAR TO SUPPORTS (ON ROOFS WHERE PLYWOOD IS LAID UP WITH FACE GRAIN PARALLEL TO SUPPORTS, USE MINIMUM OF 5 -PLY PLYWOOD). STAGGER JOINTS. ALL NAILING SHALL BE WITH COMMON NAILS. WHERE SCREWS ARE INDICATED FOR WOOD -TO -WOOD ATTACHMENTS, USE WOOD SCREWS MEETING THE REQUIREMENTS OF A.N.S.I/A.S.M.E. B18.6.1 OF GRADE ASTM A584, GRADE 1013 TO 1022 STEEL (FY=193,60OPSI). HORIZONTAL DIAPHRAGM AND SHEARWALL CAPACITIES SHALL BE PER THE LATEST EDITION OF I.C.C. REPOST ESR -1539. ALL PLYWOOD SHALL BE OF THE FOLLOWING NORMAL THICKNESS, SHALL HAVE THE FOLLOWING SPANANDEX RATIO, AND SHALL BE ATTACHED AS FOLLOWS, UNLESS OTHERWISE NOTED. USE: THICKNESS SPAN/INDEX EDGE INTERMEDIATE A.B ................................ANCHOR BOLT RATIO ATTACHMENT ATTACHMENT F B.O.B .............................BOTTOM OF BEAM B.O.D .............................BOTTOM OF DECK B.O.F .............................BOTTOM OF FOOTING B.O.P .............................BOTTOM OF PLATE B.O.S .............................BOTTOM OF STEEL 6" O.C. 12" O.C. FLOOR 3/4" T&G 40/20 SCREWS @ SCREWS @ OF BEAM C.L.0 .............................CENTERLINE OF COLUMN 6" O.C. 12" O.C. SHEAR 1/2" 24(0 8d NAILS 8d NAILS WALL CONTROL JOINT CONC. S.J .....................CONCRETE SAWCUT JOINT @ 6" O.C. @ 12" O.C. SCREWS AT FLOOR SHEATHING SHALL BE #8 x 22" LONG FOR SHEATHING LESS THAN 1" NORMAL THICKNESS, AND SHALL HAVE CURRENT I.C.C. APPROVAL AS A REPLACEMENT FOR IOd NAILS IN WOOD PANEL DIAPHRAGMS. SCREWS PER I.C.C. ER -5280 OR APPROVAL EQUAL. ALL FLOOR SHEATHING SHALL BE GLUED TO SUPPORT MEMBERS WITH AN A.P.A. AFG-01 OR ASTM D3498 QUALIFIED GLUE IN ACCORDANCE WITH A.P.A. FORM E30. ALTERNATE SHEATHING AMERICAN PLYWOOD ASSOCIATION PERFORMANCE RATED SHEATHING MAY BE USED AS AN ALTERNATE TO PLYWOOD WITH PRIOR APPROVAL OF OWNER, ARCHITECT AND ROOFING CONTRACTOR. RATED SHEATHING SHALL COMPLY WITH I.C.C. ESR -1301, EXPOSURE 1, AND SHALL HAVE A SPAN RATING AND SHEAR VALUE EQUIVALENT TO OR BETTER THAN THE PLYWOOD IT REPLACES. ATTACHMENT AND THICKNESS (WITHIN i") SHALL BE THE SAME AS THE PLYWOOD IT REPLACES. INSTALL PLYWOOD PER MANUFACTURES RECOMMENDATIONS. PROTECTION AGAINST DECAY (2304.11): PRESERVATIVE -TREATED WOOD SHALL CONFORM TO APPLICABLE AWPA STANDARDS. TRUSSES, TRUSS DRAWINGS AND TRUSS ENGINEERING SHALL BE PROVIDED BY THE MANUFACTURER. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR WITHOUT JOISTS SHALL NOT BE CLOSER THAN 18 INCHES, OR WOOD GIRDERS CLOSER THAN 12 INCHES TO THE EXPOSED GROUND IN CRAWL SPACES. WOOD FRAMING MEMBERS, INCLUDING WOOD SHEATHING, WHICH REST ON EXTERIOR FOUNDATION WALLS SHALL NOT BE LESS THAN 8 INCHES FROM EXPOSED EARTH. SILLS IN CONTACT WITH CONCRETE SHALL BE PRESERVATIVE -TREATED WOOD. CLEARANCE BETWEEN WOOD SIDING AND EARTH SHALL NOT BE LESS THAN 6 INCHES. POSTS SHALL BE PRESERVATIVE -TREATED UNLESS SUPPORTED BY A PEDESTAL GREATER THAN 8 INCHES FROM EXPOSED GROUND. AS A MINIMUM CONTRACTORS SHALL USE SIMPSON ZMAX GALVANIZED FASTENERS OR AN APPROVED BARRIER WHEN A CORROSIVE ENVIRONMENT EXISTS. SHOP DRAWINGS SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS IN ADDITION TO ITEMS REQUIRED BY ARCHITECTURAL SPECIFICATIONS. THE CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS ARE NOT IN ACCORDANCE WITH CONTRACT DOCUMENTS SHALL BE FLAGGED UPON CONTRACTOR'S REVIEW. VERIFY ALL DIMENSIONS WITH ARCHITECT ANY CHANGES, SUBSTITUTIONS, OR DRAWINGS FROM CONTRACT DOCUMENTS SHALL BE CLOUDED BY MANUFACTURER OR FABRICATOR. ANY OF THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY SUBMITTING PARTIES SHALL NOT BE CONSIDERED APPROVED AFTER ENGINEER'S REVIEW, UNLESS NOTED ACCORDINGLY. THE ENGINEER HAS THE RIGHT TO APPROVE OR DISAPPROVE ANY CHANGES TO CONTRACT DOCUMENTS AT ANY TIME BEFORE OR AFTER SHOP DRAWING REVIEW. THE SHOP DRAWINGS DO NOT REPLACE THE CONTRACT DOCUMENTS. ITEMS OMITTED OR SHOWN INCORRECTLY AND NOT FLAGGED BY THE STRUCTURAL ENGINEER OR ARCHITECT SHALL NOT BE CONSIDERED CHANGES TO CONTRACT DOCUMENTS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSURE ITEMS ITEMS ARE CONSTRUCTED TO CONTRACT DOCUMENTS. THE ADEQUACY OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY OTHERS RESTS WITH THE DESIGNING OR SUBMITTING AUTHORITY. REVIEW BY THE E.O.R. IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR CORRECTNESS SHALL REST WITH THE CONTRACTOR. ABBREVIATIONS A.B.0 ............................AGGREGATE BASE COURSE A.F.F .............................ABOVE FINISHED FLOOR ALT ...............................ALTERNATE aF, A.B ................................ANCHOR BOLT BM .................................BEAM �¢ B.F.F ..............................BELOW FINISHED FLOOR B.O.B .............................BOTTOM OF BEAM B.O.D .............................BOTTOM OF DECK B.O.F .............................BOTTOM OF FOOTING B.O.P .............................BOTTOM OF PLATE B.O.S .............................BOTTOM OF STEEL BRG ...............................BEARING C.I.P ...............................CAST -IN-PLACE C.L .................................CENTERLINE C.L.B .............................CENTERLINE OF BEAM C.L.0 .............................CENTERLINE OF COLUMN C.L.F ..............................CENTERLINE OF FOOTING C.L.W ............................CENTER LINE OF WALL CLR ...............................CLEAR CONC ............................CONCRETE CONC. C.J ....................CONCRETE CONTROL JOINT CONC. S.J .....................CONCRETE SAWCUT JOINT C.M.0 ............................CONCRETE MASONRY UNIT CONN ............................CONNECTION CONT ............................CONTINUOUS D.L .................................DEAD LOAD DIA ................................DIAMETER DN .................................DOWN DWG(S).........................DRAWING(S) E.O.S ..............................EDGE OF SLAB EL ..................................ELEVATION EQ..................................EQUAL EQUIP ...........................EQUIPMENT EXP ................................EXPANSION BOLT EXP. JT. (E.J.) ...............EXPANSION JOINT E.W ................................EACH WAY F.F ..................................FINISHED FLOOR F.O.M ............................FACE OF MEMBER F.O.S. ............................FACE OF STEEL F.O.W ............................FACE OF WALL GA .................................GAUGE GALV ............................GALVANIZED GLB (GLULAM) ..........GLUE -LAMINATED BEAM H/C ................................HOLLOW CORE HORIZ ...........................HORIZONTAL LEW ..............................INSIDE FACE OF WALL I.E ..................................INVERT ELEVATION K (KIP) ..........................1000 POUNDS L.L .................................LIVE LOAD LBS (#) ..........................POUNDS L.L.H .............................LONG LEG HORIZONTAL L.L.V .............................LONG LEG VERTICAL MFR('S).........................MANUFACTURE('S) MAS. C.J .......................MASONRY CONTROL JOINT MECH'L ........................MECHANICAL N/A ................................NOT APPLICABLE N.T.S .............................NOT TO SCALE O.0................................ON CENTER O.F.W ............................OUTSIDE FACE OF WALL OPP ................................OPPOSITE P.0 .................................PRE CAST CONCRETE P.L.F ..............................POUNDS PER LINEAR FOOT PREFAB ........................PREFABRICATED P.S.F ..............................POUNDS PER SQUARE FOOT P.S.I ...............................POUNDS PER SQUARE INCH REINF...........................REINFORCING S.L.H .............................SHORT LEG HORIZONTAL S.L.V .............................SHORT LEG VERTICAL SIM ................................SIMILAR SQ ..................................SQUARE STD ...............................STANDARD T.L .................................TOTAL LENGTH T.O.B .............................TOP OF BEAM T.O.D .............................TOP OF DECK T.O.F .............................TOP OF FOOTING T.O.G .............................TOP OF GRADE T.O.L .............................TOP OF LEDGER T.O.M ............................TOP OF MASONRY T.O.P .............................TOP OF PLATE T.O.S .............................TOP OF STEEL T.O.W ............................TOP OF WALL TYP ...............................TYPICAL U.N.O ............................UNLESS NOTED OTHERWISE VERT ............................VERTICAL WTSP............................WATERSTOP W.W.R ..........................WELDED WIRE REINFORCEMENT SPECIAL INSPECTIONS THE FOLLOWING SPECIAL INSPECTIONS ARE REQUIRED PER CHAPTER 17 OF THE 2018 INTERNATIONAL BUILDING CODE TO BE PERFORMED BY AN INDEPENDENT THIRD PARTY INSPECTION. ANCHORAGE 1) PERIODIC INSPECTION OF POST INSTALLED (EPDXY) ANCHORAGE FOR USE WITH HOLDOWNS AND TENSION APPLICATIONS. CONCRETE 1) VERIFICATION OF HIGH STRENGTH ANCHORAGE PRIOR TO POUR. 2) VERIFICATION OF CONCRETE STRENGTH >2500psi WOOD CONSTRUCTION 1) PERIODIC VERIFICATION OF SHEATHING/ NAILS, AND NAIL PATTERN FOR SHEAR WALLS W/ 3" OR TIGHTER EDGE NAIL SPACING. N N N min A °z O LL_ SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET SI p aF, �¢ d min A °z O LL_ SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET SI C�1 m 22' 15'-9' STHD1 10'-3' CHANGE IN STEM/F❑❑TING SIZE STHD14J 1-101. FOUNDATION AND MAIN FLOOR FRAMING PLAN 1/4'=1'-0' ALL S❑LID SAWN BEAMS TO BE HF #2 OR BETTER VERIFY L❑CATI❑N OF STEMWALL/F❑❑TING STEP DOWN WITH SITE STHD14 /-STHD14 10' 1 1. �.•--16'•-� NOTES; 1, %'0 ANCHOR BOLTS @ 36'o/c U,N,❑ 2, 2x6 PT SILL PLATE 3. SHEARWALL EDGE NAILING 4, FINISH GRADE 5, #4 BAR CONT, @ 18'o/c HORIZ, 6, #4 BAR @ 18'o/c VERT, (ALT, BENDS) 7, (2)#4 BAR CONT. IN FTG, TYPICAL FOUNDATION STEM WALL SLAB SCALE: N,T,S, ALL PER PLAN ;'0x10' TITENHD SCREW ANCHORS @ 48'o/c PT SILL PLATE TYPICAL THICKENED SLAB SCALE: N.T.S. 4 BAR CONT.(AS NOTED) ' COMP. SAND UBGRADE ko 2' MI //--POST PER PLAN ABU BASE (OR PER PLAN) 5/6' 0 ANCHOR0 0o o a o O 00 a a TYPICAL THICKENED EDGE SLAB SCALE: N.T.S. '-L TOP PLATE STUD <6' @ 16'o/c P❑NYWALL 7/16' SHEATHING w/ 8d @ 3'o/c GE NAILING ANCHOR BOLTS 36'(MIN 2 PER STEP) )2x OR 3x PT SILL PLATE Q 20' Q�Q 12' 8' 6x6 POST W/ ABW66Z M 6x6 POST W/ ABW66 POST BASE POST BASE � � 24'x24'xl2' F❑❑TING 00 N PAD W/ (3) #4 E.W. o P-, 4" THK C❑NC SLAB w/ THKND EDGE C@ c BASEMENT LEVEL) co )ON r W � 4' C❑NC, SLAB OVER 4" COMP, SAND/GRAVEL BASE & ,006 VISA, VAPOR BARRIER & R-10 X 24" RIGID INSL, BD, @ SLAB INSIDE PERIMETER (TYP,) 12'-114' 3'-52' 3'-74' 20` 12" WIDE x 12' THICK F❑❑TING W/ (2) #4 C❑NTINU❑US M3 4- 4" CONC. SLAB ON 4" COMP, FILL f --TOP OF STEM SLOPED 3" TOWARDS DOOR ELEVATI❑N TO HANG C@ MAIN FLOOR LEVEL) JOISTS 6' STEM W/ STUB #4 BARS OUT 15'x6' FOOTING 18' INT❑ CONC, @ 24' ❑,C, AS PER ENG'S CALCS CTYPJ CHANGE IN STEM/FOOTING—t SIZE 4" THK C❑NC SLAB 30x30x10 F❑❑TING PAD w/ THKND EDGE (@ 6x6 POST W/ (3) #4 E.W. (UNDER MAIN FLOOR LEVEL) ABW66Z BASE GIRDER TRUSS) EDGE OF SLAB (2)#4 BARS C❑NT, IN-a,,,_ FTG, @ DOOR OPENING 30x30x10 F❑❑TING PAD W/ (3) #4 E,W, (UNDER 24'x24'xl2' FOOTING PAD W/ (3) #4 E,W. GIRDER TRUSS) lj7--F R.O. 5'-10' 14'-2' 20' 20, 40' FOUNDATION AND MAIN FLOOR FRAMING PLAN 1/4'=1'-0' ALL S❑LID SAWN BEAMS TO BE HF #2 OR BETTER VERIFY L❑CATI❑N OF STEMWALL/F❑❑TING STEP DOWN WITH SITE STHD14 /-STHD14 10' 1 1. �.•--16'•-� NOTES; 1, %'0 ANCHOR BOLTS @ 36'o/c U,N,❑ 2, 2x6 PT SILL PLATE 3. SHEARWALL EDGE NAILING 4, FINISH GRADE 5, #4 BAR CONT, @ 18'o/c HORIZ, 6, #4 BAR @ 18'o/c VERT, (ALT, BENDS) 7, (2)#4 BAR CONT. IN FTG, TYPICAL FOUNDATION STEM WALL SLAB SCALE: N,T,S, ALL PER PLAN ;'0x10' TITENHD SCREW ANCHORS @ 48'o/c PT SILL PLATE TYPICAL THICKENED SLAB SCALE: N.T.S. 4 BAR CONT.(AS NOTED) ' COMP. SAND UBGRADE ko 2' MI //--POST PER PLAN ABU BASE (OR PER PLAN) 5/6' 0 ANCHOR0 0o o a o O 00 a a TYPICAL THICKENED EDGE SLAB SCALE: N.T.S. '-L TOP PLATE STUD <6' @ 16'o/c P❑NYWALL 7/16' SHEATHING w/ 8d @ 3'o/c GE NAILING ANCHOR BOLTS 36'(MIN 2 PER STEP) )2x OR 3x PT SILL PLATE Q Q�Q cn M aA A EM WALL PER PLAN O ❑TING PER PLAN —T. FTG, BAR 24' FOOTING/STEMWALL STEP SCALE: N.T,S. 2'-6" NOTES: 1. 2. �) 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. SHEATHING AND ATTACHMENT PER SHEARWALL SCHEDULE EDGE NAILING RIM JOIST BY JOIST MANUFACTURER -ATTACH WITH (2) 10d NAILS PER JOIST 16d TOENAILS AT 6" O.C. 5/8" DIAMETER ANCHOR BOLTS PER SHEARWALL SCHEDULE, EMBEDMENT PER GSN DO NOT BACKFILL UNTIL FLOOR IS FRAMED 8" THICK CONCRETE WALL #4 BARS AT 12" O.C. VERTICAL AND HORIZONTAL DOWELS TO MATCH AND LAP VERTICAL REINFORCEMENT, ALTERNATE BENDS 4" PERFORMED DRAIN PIPE, SURROUNDED WITH FREE DRAINING GRAVEL -SLOPE TO APPROVED DISCHARGE BASE PLATE NAILING PER SHEARWALL SCHEDULE PLYWOOD SHEATHING CONNECT EACH JOIST TO BASE PLATE WITH SIMPSON A35, EACH SIDE PLYWOOD WEB JOISTS PER PLAN 2x8 TREATED BASE PLATE PER SHEARWALL SCHEDULE CONCRETE SLAB ON GRADE (2) #4 BARS CONTINUOUS #4 BARS AT 10" O.C. CENTER VERTICAL STEEL IN 8" WALL BASEMENT RETAINING WALL SCALE: N,T,S, W t— M SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEAT s2 cn M aA 00 � � 3 00 N o P-, c co r W � M SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEAT s2 STH STH UPPER FLOOR FRAMING PLAN 1/4"=1'-0" NOTE: ALL C❑NNECTI❑NS TO BE VERIFIED BY J❑IST MANUFACTURE ALL S❑LID SAWN BEAMS TO BE HF #2 OR BETTER = BEARING WALL ALL HEADERS TO BE 4X10 U.N.O. am Q z Q Q > Q �~ z 0 0. z o t O 1 SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET S3 M oc n Q b �N U N 0oc O rin m O O O o r an � W � M SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET S3 :'DST W/ CAP ROOF FRAMING PLAN 1/4'=l'-0' NOTE: ALL ❑VERFRAMED RAFTERS TO BE 2X6-24" Of, FOR SPANS UP TO 8'-0", 2X8-24" ❑,C. FOR SPANS UP TO 11'-0" 2X10-24" D.C. FOR SPANS UP TO 14'-0" = BEARING WALL ALL C❑NNECTI❑NS TO SPECIFIED AND OR VERIFIED BY TRUSS MANUFACTURER Rm NOTE: ALL S❑LID SAWN BEAMS TO BE HF #2 OR BETTER ALL HEADERS TO BE 4x8 U,N,❑ = ❑VERFRAMING Q z Q �QQ o a Q x ¢ 0 1 � t v= � �4• 3 O� a SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET S4 V � M n •�i% CI N U p a t?Q � o cd t/1 a O •~ O • N M V'1 SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET S4 r==TT I I I I II it II II TF =I T- IT==1' II II II III II II II II 11 II II I II II II II ==�-1===F---ff II II III II i II TT -1 II I II I II I II I 4. 2X BLOCKING WITH 5) 5. II II II II II WITH (2) lOd PER TRUSS 6. II II I I I II II II II II II II II II II � PER SHEARWALL II II II II I F==14==1T= I II 1 II II II II II II TRUSS I; II II 11 1 II I I I II II II II II II __II II IF=9F :91 II II II II 8d © 4"o.c. 8d ® 12"o.c. II 1F II I1 1 =`1F --I II I I I II II II II II II II E II II II 8. BOTTOM PLATE (2)16d © 8"o/c II II II I II I I� 1 II -ll II 11 11 til J1 -ILS-II-u '.di.. w/ 3x BTM. PLATE II LiI �I 1 1j n II q p n II 21 21 h II 11 IIS it u E it AO DOUBLE TOP PLATE w/ EDGE NAILING (STAGGER) OF TOP PLATE SPLICE AND NAILING PER PLANS. SEE SHEARWALL SCHEDULE FOR LUMBER GRADE). LAP 4'-0" MINIMUM. CENTER SPLICE ON STUD. ©EDGE NAILING AT ALL PANEL EDGES. BACK w/ © HOLDOWN PER SCHEDULE AND PLAN 2x BLOCKING OR BACKING C EDGE NAILING TO HOEDOWN POST FULL HEIGHT @ COORDINATE ALL STUD AND PLATE SIZES O ( ) w/ SHEARWALL SCHEDULE REQUIREMENTS O STUDS ® 16" o.c. OJ EDGE NAILING TO POSTS. TRIM STUDS OE P.T. SILL PLATE w/ EDGE NAILING & ANCHOR AND KING STUDS BOLTS PER SHEARWALL SCHEDULE (PROVIDE A MINIMUM OF 5/8 dia. ANCHOR BOLTS ® KO BEARING STUD FOR HEADER 48" o.c.) TYPICAL WOOD SHEARWALL ELEVATION. NTS 801/10d @ 6'o/c SOLE PLATE NAILI 801/10d @ 6'o 8d/l0d @ 6'o -'o/c 6'o/c TYPE 3/4/5 SHEAR WALL EDGE NAILING SCALE: N.T.S. NOTES: 1. WOOD TRUSS 2. PLYWOOD SHEATHING 3. EDGE NAILING 4. 2X BLOCKING WITH 5) 5. CONTINU❑US FASCIA NAILING WITH (2) lOd PER TRUSS 6. SHEAR PANEL EDGE TO (2) STUDS NAILING 7. SHEATHING AND NAILING (14) SDS/4'x2Y2" PER SHEARWALL 8d @ 6"o.c. SCHEDULE 8, SIMPS❑N H2,5 AT EACH 5, 16d TOENAILS @ 6'0/c (4) TRUSS TYPICAL TRUSS CONNECTION SCALE: N.T.S, SHEARWALL SCHEDULE STHD8 STHD14 MINIMUM EDGE FIELD SOLE PLATE SILL PLATE MARK SHEATHING NAILING NAILING NAILING CONN. @ FND, A 7/16" OSB16"o/c TO (2) STUDS NONE (2)1601 5/8dia. @ 48" o.c. (14) SDS/4'x2Y2" ONE FACE 8d @ 6"o.c. 8d © 12"o.c. TO 4x MEMBERS w/ 2x BTM. PLATE 5, 16d TOENAILS @ 6'0/c (4) 7/16" OSB" I; BOLT W/ 10' EMBEDMENT (2)1601 @ 12 o/c 5/8"dia. @ 36" O.C. (20) SDS Y'4'x2Y2' ONE FACE 8d © 4"o.c. 8d ® 12"o.c. TO 6x MEMBERS w/ 2x BTM. PLATE 0 7/16" OSB REBAR 8. BOTTOM PLATE (2)16d © 8"o/c 5/8"dia. @ 30" o.c. LENGTH ONE FACE 8d © 3"o.c. 8d @ 12"o.c. '.di.. w/ 3x BTM. PLATE ® 7/16" OSB (2)1\ 1 MIN. (2)16d @ 8"o/c 5/8"dia. © 18" ox . ONE FACE 8d © 2"o.c. 8d @ 12"o.c. w/ 3x BTM. PLATE 19/32" OSB C cmtNER (2)16d 0 8"o/c 5/8"dia. @ 18" o.c. STHD CONNECTIONS ONE FACE 10d @ 2"o.c. 10d © 12"o.c. w/ 3x BTM. PLATE SHEARWALL N❑TES1 L ALL STUDS AND BLOCKING SHALL BE HF#2 ALL TOP AND BOTTOM PLATES SHALL BE HF#2. ALL SHEATHING EDGES SHALL BE BACKED WITH 2x OR WIDER FRAMING UNLESS OTHERWISE NOTED (SEE NOTE#2). SHEATHING MAY BE INSTALLED EITHER HORIZONTALLY OR VERTICALLY. 2. WHERE SHEATHING NAILING IS A & OR GREATER, FOUNDATION SILL PLATES AND ALL FRAMING MEMBERS RECEIVING EDGE NAILING FROM ABUTTING PANELS SHALL NOT BE LESS THAN A SINGLE 3 -INCH NOMINAL MEMBER AND SILL PLATES NOT BE LESS THAN A SINGLE 3 -INCH NOMINAL MEMBER. 3. NAILING CRITERIA IS BASED ON IBC 23063 AND AF&PA SPDWS TABLE 4.3A FOR CD PLYWOOD AND HF#2 FRAMING. WIRE STAPLES MAY BE SUBSTITUTED AS OUTLINED IN THE STRUCTURAL NOTES, OTHER SUBSTITUTIONS MUST BE VERIFIED IN WRITING BY THE STRL, ENGINEER. 4. H❑LDOWNS AND OTHER CONNECTIONS MAY BE REQUIRED AT THE ENDS OF MANY SHEARWALLS, SIZES AND L❑CATIONS OF THESE CONNECTORS ARE INDICATED ON THE PLANS. REFER TO THE APPROPRIATE CONNECTOR DETAILS FOR ADDITIONAL INFORMATI❑N REGARDING ANCHOR BOLTS, EMBEDMENT LENGTH, ETC, 5 ANCHOR BOLTS MUST BE EMBEDDED INT❑ CONCRETE OR GROUTED CMU A MINIMUM OF 7', AND SHALL BE PLACED TO PR❑VIDE A MINIMUM OF 2' GROUTED CLEAR TO THE FACE OF FORMED CONCRETE (PROVIDED 3" CLEAR FOR CONCRETE CAST AGAINST S❑IL). 6. EDGE OF ANCHOR BOLT WASHER SHALL BE WITHIN 1/2" OF SHEAR WALL SHEATHING 4) 1 �"(MTM 2 GARAGE PORTAL FRAME SCALE: N.T.S. TRUSS GABLE END DETAIL SCALE: N.T.S, HOLD DOWN SCHEDULE STHD8 STHD14 SIMPSON (PRODUCT) HDU5 ANCHOR MARK CAPACITY ATTACHMENTS BOLTS STHD14 STHD14 OR STHD14RJ W/ 30x1601 NA LED PORION 7. (❑R PHD 2 SUBSTITUTION) TO (2) STUDS NONE HDU5 HDU5 - SDS 2.5 (14) SDS/4'x2Y2" s/e" DIA. ANCHOR SSTB 0 TO 4x MEMBERS PER SIMPS❑N OR 'J' 5, 16d TOENAILS @ 6'0/c (4) I; BOLT W/ 10' EMBEDMENT HDQ8 HDU8 - SDS 2.5 (20) SDS Y'4'x2Y2' %' DIA. ANCHOR SB OR 0 TO 6x MEMBERS SSTB PER SIMPSON HOLD DOWN NOTES; 1. ALL THREAD BOLTS SHALL CONFORM TO ASTM A307. 2. CONCRETE COMPRESSIVE STRENGTH f'c=2,500 psi, 3. HD11/8 REQUIRES A 6x6 MIN. POST SIZE, HDU2/4/5 REQUIRES (2)2x MIN. POST SIZE, HD19 REQUIRED MIN. 6x8 POST SIZE U.N.❑ 4. MINIMUM EDGE DISTANCE SHOWN IS FOR FORMED CONCRETE EXPOSED TO SOIL OR WEATHER, FOR CONCRETE CAST AGAINST S❑IL PROVIDE 3' CLEAR TO ANCHOR BOLT, 5. NAILS TO HOLDOWN POSTS SHALL BE 0.148'0 COMMON. (1601 SINKERS MAY BE USED WITH PRIOR WRITTEN APPROVAL BY THE STRUCTURAL ENGINEER) NOTES; 1, 2x TOP PLATE 2. CONTINUE HEADER TO END STUD 3. 8d @ 3' ❑.C, EACH WAY ON HEADER 4. SIMPSON STHD14 - INSTALL PER MANUFACTURER'S RECOMMENDATIONS 5. (2) 1001 NAILS TO HEADER 6, CORNER END STUD AS OCCURS 7. (2) 2x STUDS OR 4x POST 8. 801 @ 3" ❑,C, ALL PLATES, HEADERS, AND STUDS 9. �' NOMINAL APA RATED SHEATHING 10. R"0 ANCHOR BOLTS - EMBED 7" MINIMUM WITH 3"x3"x4" PLATE WASHER 11. (2) 2x PLATES - NAIL SHEATHING TO EACH PLATE 12. 801 3" O,C, INTO EACH PLATE 13. TOP OF CONCRETE 14, LSTA24 ACROSS HEADER 15, HEADER NOTES: A. ALL STUDS TO BE DOUGLAS FIR #2 IN LATERAL RESTRAINT PANELS, NOTES; 1. EDGE NAILING 2. C❑NTINU❑US FASCIA WITH (2) 1001 NAILS INT❑ EACH OUTRIGGER @ 24' D.C. 3. 2x4 OUTRIGGER @ 24' ❑.0 4. (2) lOd NAILS PER TRUSS 5. SIMPSON A35 CLIP AT EACH OUTRIGGER 6. GABLE END TRUSS - SHEATHING AND NAILING PER SHEARWALL SCHEDULE 7, 1601 @ 6' ❑,C. BOTTOM TRUSS CHORD TO WALL BLOCK 8. 2x4 BRACE @ 48" D.C. WITH SIMPS❑N A35 CLIP EACH END 9. TRUSSES PER PLAN FLOOR -TO -FLOOR HOLD DOWN STRAP SCALE: N.T.S. TYPICAL HOLDOWN DETAILS STHD8 STHD14 HDQ8 HDU5 Q � 1. SHEARWALL PER PLAN SHEAR PANEL EDGE NAILING 4. BREAK SHEAR PANELS OVER RIM 5. 2. BASE PLATE NAILING 6. NA LED PORION 7. 0 3. SHEAR PANEL EDGE NAILING BOTTOM PLATE 9. ® 00 4. LTP5 @ 12' D.C. 0 B EAR sP 5, 16d TOENAILS @ 6'0/c (4) I; 17' 6. PLYWOOD SUBFLOOR (3) MAXIMUM 0 30' MI 2, INTERI❑R SHEARWALL PER PLAN REBAR 8. BOTTOM PLATE a' (1) LENGTH ONE a4 9. 1j' LSL RIM/BLOCKINGC1) 10. 1601 @ 4' D.C. '.di.. IN SHEAR CONE �• '• (2)1\ 1 MIN. •., °o . / REBAR LENGTH • a •• n n°,• p ' • ". Q C cmtNER �M1 STHD CONNECTIONS HDQ8 CONNECTION HDU CONNECTION Q z d Q Q O Q � 1. SHEARWALL PER PLAN SHEAR PANEL EDGE NAILING 4. BREAK SHEAR PANELS OVER RIM 5. 0 L z O NOTES: 1. SHEARWALL PER PLAN 2. BASE PLATE NAILING 1. SHEARWALL PER PLAN SHEAR PANEL EDGE NAILING 4. BREAK SHEAR PANELS OVER RIM 5. 2. BASE PLATE NAILING 6. PLYWOOD SUBFL❑OR 7. FLOOR JOIST PER PLAN 3. SHEAR PANEL EDGE NAILING BOTTOM PLATE 9. 1j' LSL RIM 4. LTP5 @ 12' D.C. cv B O 5, 16d TOENAILS @ 6'0/c (4) I; NOTES: 6. PLYWOOD SUBFLOOR (3) 1. TRUSS BOTTOM CHORD 7. FLOOR JOIST PER PLAN (5) 2, INTERI❑R SHEARWALL PER PLAN O 8. BOTTOM PLATE a' (1) 3. 2x6 FLAT BLOCKING @ 12' L L- 9. 1j' LSL RIM/BLOCKINGC1) 10. 1601 @ 4' D.C. (5) 4. (6)1601 NAILS SIMPSON A35 @ 12' (2)1\ (2)-\5. TYPICAL FLOOR TO FLOOR WALL CONNECTION SCALE: N.T.S NOTES: 1. SHEARWALL PER PLAN 2. BASE PLATE NAILING 3. SHEAR PANEL EDGE NAILING 4. BREAK SHEAR PANELS OVER RIM 5. 1601 TOENAILS @ 6'0/c 6. PLYWOOD SUBFL❑OR 7. FLOOR JOIST PER PLAN 8. BOTTOM PLATE 9. 1j' LSL RIM U TYPICAL FLOOR -TO -FLOOR CONNECTION SCALE: NJ.S. TRUSS TO INTERIOR SHEARWALL SCALE: N.T.S. 1) 2) 3) NOTES: 1. TOP PLATE SPLICE OVER STUD ONLY. 2. DOUBLE TOP PLATE 3. WOOD STUDS TYPICAL TOP PLATE SPLICE SCALE: N.T.S. m w H Q M V7 SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET SS M aA � U cv B O I; O � a' W � M a � I� W M V7 SCALE: AS SHOWN DATE: Sept. 2021 DRAWING NUMBER 11789 SHEET SS