DESIGN FOR PERMIT
LONGMIRE ST SE15347LONGMIRE ST SE15425SITE PLANSCALE: 1" = 50'CIRCUIT FEET ADDED: 0'Sq. Footage: 2400Panel Size: 200AMPHeat Type: ELECTRICEst. Demand: 6.36kWLRC: 65% V. Drop: 0.5%% Flicker: 1.5%559422-14718415kVA 120/240v AØY1417 40TFeedPERM METERINST 1/0OH TPLXInstalled at site:Grid Number:kVA Rating:TRANSFORMER INSTALLATION (OH)Company ID#:Primary phase connected to:Tested Secondary VoltageMaterial ID#:Foreman to redline the following information25kVA 120/240v6211250P01559407-147171SITE SPECIFIC NOTESAT P01GRID #: 559407-147171HANG 25kVA, 120/240V OH XFMR3-11, 1-8AINST L/B C/O, FUSE @ 10TINST STIRRUP TAP CØINST POLE GND (IF REQ'D)AT M01PERM METERP01 TO P02:REMV ±210' OF #2 OH OPEN SEC TPLX2-20AP01 TO M01:INST ±80' 1/0 OH SEC TPLXMETER DEPT TO SET METERCUSTOMER NOTE:CUSTOMER RESPONSIBLE FOR INSTALLING CONDUIT & 3/8" NYLON PULL ROPE.SITE MUST BE READY 1-WEEK PRIOR TO CONSTRUCTION DATE25kVA 120/240vFault Current: 6,100R/X: 0.8 %Z: 1.7559407-14717125kVA 120/240v CØWIRE REMOVAL TABLEWorkLocationWire Size & Type QuantityLength(perconductor)RemarksFrom ToP01 P02 SEC #2 OH TPX1210'559419-147188FeedFeedP01P02JOB 105098554@P01 HANG NEW25KVA OH XFMR ANDINSTALL FUSE@P01-P02: REMOVEEXISTING OH LINE INADVANCE OFMOSSMAN ROADINSTALL@P1-M01: NEWOVERHEAD SERVICETO SHOP FOR GOLFCOURSE*CREW WILL HAVEFLAGGERS*NO UNDERGROUNDWORK EXPECTED*MOSSMAN RDFUTUREEXTENSION