Yelm Creek Estates Lot 10 Plan 2052-2 Final StampedGENERAL NOTES BUILDING CODE: 2018 INTERNATIONAL BLDG. CODE (IBC), AND BY REFERENCE WHERE APPLICABLE THE 2016 INTERNATIONAL RESIDENTIAL CODE (IRC) AS AMENDED BY LOCAL JURISDICTION. ROOF LIVE LOAD = 25 PSF (SNOW) ROOF DEAD LOAD = 15 PSF FLOOR LIVE LOAD = 40 PSF (REDUCIBLE) FLOOR DEAD LOAD = 15 PSF WIND LOAD = 85 MPH WIND SPEED, EXPOSURE "B" WIND LOAD = 110 MPH WIND SPEED, EXPOSURE "B" PER IBC SOIL SITE CLASS "D" CONSTRUCTION TYPE: VB OCCUPANCY GROUP: R-3 CONTRACTOR SHALL VERIFY ALL NOTES, DIMENSIONS d CONDITIONS PRIOR TO CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO IDENTIFY ALL OMISSIONS AND/OR DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING WITH WORK. DIMENSIONS TAKE PRECEDENT OVER SCALED DRAWINGS. DEFERRED 5U5MITTAL ITEM5 THE FOLLOWING IS A LIST OF ITEMS THAT ARE NOT INCLUDED IN THIS PLAN AND SHOULD BE PROVIDED BY THE BUILDER AT TIME OF APPLICATION FOR PERMIT OR AS A DEFERRED SUBMITTAL ITEM: - ALTERNATIVE I-JOIST/BEAM MANUFACTURER PLANS. - MANUFACTURED TRUSS DESIGNS AND LAYOUTS - HVAC SYSTEMS DESIGN - ELECTRICAL PLANS 8 SPECIFICATIONS (IF REQUIRED) SITE UJORK GENERAL UNLESS A SOILS INVESTIGATION BY A QUALIFIED SOILS ENGINEER IS PROVIDED, FOUNDATION DESIGN IS BASED ON AN ASSUMED AVERAGE SOIL BEARING OF 1500 PSF. EXTERIOR FOOTINGS SHALL BEAR IS" (MINIMUM) BELOW FINISHED GRADE. ALL FOOTINGS TO BEAR ON FIRM UNDISTURBED EARTH BELOW ORGANIC SURFACE SOILS. BACKFILL TO BE THOROUGHLY COMPACTED. BOLT HEADS AND NUTS BEARING AGAINST WOOD TO BE PROVIDED WITH 1/4"x3"x3" PLATE WASHERS. WOOD BEARING ON OR INSTALLED WITHIN I" OF MASONRY OR CONCRETE TO BE PRESSURE TREATED WITH AN APPROVED PRESERVATIVE. FOUNDATION SILL BOLTS TO BE 5/0" DIAMETER AT 6'-O" O.G. U.N.O. WITH MIN. 7" EMBEDMENT METAL FRAMING CONNECTORS TO BE MANUFACTURED BY SIMPSON STRONG -TIE OR USP STRUCTURAL CONNECTORS INSULATION AND MOISTURE PROTECTION GENERAL (MAINTAIN I" CLEARANCE ABOVE INSULATION FOR FREE AIR FLOW. INSULATION BAFFLES TO EXTEND /o" ABOVE BATT INSULATION INSULATION BAFFLES TO EXTEND 12" ABOVE LOOSE FILL INSULATION INSULATE BEHIND TUBS/SHOWERS, PARTITIONS AND CORNERS FACE -STAPLE FACED BATT& FRICTION -FIT UNFACED BATT& USE 4 1" IIL POLY VAPOR RETARDER AT EXTERIOR WALLS R-10 INSULATION UNDER ELECTRIC WATER HEATERS. INSULATION MATERIALS INSULATION MATERIAL, INCLUDING FACINGS, SUCH AS VAPOR RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN FLOOR -CEILING ASSEMBLIES, ROOF -CEILING ASSEMBLIES, WALL ASSEMBLIES, CRAWL SPACES, AND ATTICS SHALL HAVE A FLAME -SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING SMOKE -DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN ACCORDANCE WITH ASTM E 54 EXCEPTIONS- I. WHEN SUCH MATERIAL ARE INSTALLED IN CONCEALED SPACES, THE FLAME -SPREAD AND SMOKE-DEVELOPEMENT LIMITATIONS DO NOT APPLY TO THE FACINGS, PROVIDED THAT THE FACING IS INSTALLED IN SUBSTANTIAL CONTACT WITH THE UNEXPOSED SURFACE OF THE CEILING, FLOOR, OR WALL FINISH. 2. CELLULOSE LOOSE -FILL INSULATION, WHICH IS NOT SPRAY APPLIED, COMPLYING WITH THE REQUIREMENTS OF IRC 8302.1.10.3, SHALL ONLY BE REQUIRED TO MEET THE SMOKE -DEVELOPED INDEX OF NOT MORE THAN 450, INFILTRATION CONTROL EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, PENETRATIONS IN FLOORS, ROOFS AND WALLS AND ALL SIMILAR OPENINGS SHALL BE SEALED, CAULKED, GA5KETED OR WEATHERSTRIPPED TO LIMIT AIR LEAKAGE. VAPOR BARRIER3 / GROUND COVER5 AN APPROVED VAPOR BARRIER SHALL BE PROPERLY INSTALLED IN ROOF DECKS, IN ENCLOSED CEILING SPACES AND AT EXTERIOR WALLS. A GROUND COVER OF 6 MIL (0.006") BLACK POLYETHYLENE OR EQUIVALENT SHALL BE LAID OVER THE GROUND IN ALL CRAWL SPACES. THE GROUND COVER SHALL BE OVERLAPPED ONE FOOT AT EACH JOINT AND SHALL EXTEND TO THE FOUNDATION WALL. WALL FLA&PING APPROVED CORROSION -RESISTANT FLASHING SHALL BE PROVIDED IN THE EXTERIOR WALL ENVELOPE IN SUCH A MANNER AS TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH AND SHALL BE INSTALLED TO PREVENT WATER FROM REENTERING THE EXTERIOR WALL ENVELOPE. APPROVED CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: I. AT TO OF EXTERIOR WINDOW AN 00 OPENINGS IN SUCH A MANN AS TO LEAKPROOF, P ALL ER R D D DOOR PE ER BE LE PR , EXCEPT THAT SELF -FLASHING WINDOWS HAVING A CONTINUOUS LAP OF NOT LESS THAN 1-1/8" (20 mm) OVER THE SHEATHING MATERIAL AROUND THE PERIMETER OF THE OPENING, INCLUDING CORNERS, DOO NOT REQUIRE ADDITIONAL FLASHING± JAMB FLASHING MAY ALSO BE OMITTED WHEN SPECIFICALLY APPROVED BY THE BUILDING OFFICIAL. 2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH PROJECTING LIPS ON BOTH SIDES UNDER STUCCO OPENINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD, OR METAL COPINGS AND SILLS, 4. CONTINUOUSLY ABOVE ALLPROJECTING WOOD TRIM, 5. WHERE EXTERIOR PORCHES, DECKS, OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD CONSTRUCTION. 6. AT WALL AND ROOF INTERSECTIONS. 1. AT BUILT-IN GUTTERS. FOUNDATION WATERPROOFING 4 DAMPROOFING DAMPROOFING EXCEPT WHERE REQUIRED BY 2018 IRC R406.2 TO BE WATERPROOFED, FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE DAMPROOFED FROM THE TOP OF THE FOOTING TO THE FINISHED GRADE. MASONRY WALLS SHALL HAVE NOT LASS THAN 8" PORTLAND CEMENT PARGING APPLIED TO THE EXTERIOR OF THE WALL. PARGING SHALL BE DAMPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. I. BITUMINOUS COATING 2.3 POUNDS PER SQ. YD. OF ACRYLIC MODIFIED CEMENT 3. s' COAT OF SURFACE BONDING CEMENT COMPLYING WITH A5TN C S8i 4. ANY MATERIAL APPROVED FOR WATERPFOORING IN 2018 IRC 8406.2 5, OTHER APPROVED METHODS OR MATERIALS. EXCEPTION: PARGING OF UNIT MASONRY WALLS IS NOT REQUIRED WHERE A MATERIAL IS APPROVED FOR DIRECT APPLICATION TO THE MASONRY, FOUNDATION WATERPROOFING 4 DAMPROOFING (CONTINUED) WATERPROOFING IN AREAS WHERE HIGH WATER TABLE OR OTHER SEVERE SOIL -WATER CONDITIONS ARE KNOWN TO EXIST, EXTERIOR FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE WATERPROOFED FROM THE TOP OF FOOTING TO FINISHED GRADE. WALLS SHALL BE WATERPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. 1. 2 -PLY HOT MOPPED FELT 2.55 POUND ROOF ROLLING 3. 6 -MIL POLYVINYL CHLORIDE 4. 6 -MIL POLYETHYLENE 5. 40 -MIL POLYMER -MODIFIED ASPHALT 6. 60 -MIL FLEXIBLE POLYMER CEMENT I. 8" CEMENT -BASED, FIBER -REINFORCED, WATERPROOF COATING 8. 60 -MIL SOLVANT-FREE, LIQUID -APPLIED SYNTHETIC RUBBER EXCEPTION: ORGANIC-SOLVANT-BASED PRODUCTS SUCH AS HYDROCARBONS, CHLORINATED HYDROCARBONS, KETONS AND ESTERS SHALL NOT BE USED FOR ICF WALLS WITH EXPANDED POLYSTYRENE FOAM MATERIAL. USE OF PLASTIC ROOFING CEMENTS, ACRYLIC COATINGS, LATEX COATINGS, MORTARS AND PARGINGS TO SEAL5EAL ICF WALLS IS PERMITTED. COLD-S TTIN ASPHALT OR HOT ASPHALT SHALL CONFORM TO TYPE r- OF ASTM D 449. HOT ASPHALT SHALL BE APPLIED AT A TEMPERATURE OF LESS THAN 200 DEG. F. ALL JOINTS IN MEMBRANE WATERPROOFING SHALL BE LAPPED AND SEALED WITH AN ADHESIVE COMPATIBLE WITH THE MEMBRANE. DRAETSTOPPING 4 EIRE BLOCKING 1DRAFT5TOPPING WHEN THERE IS USABLE SPACE BOTH ABOVE 4 BELOW THE CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLEY, DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. WHERE THE A55EMBLY IS ENCLOSED BY A FLOOR MEMBRANE ABOVE 8 A CEILING MEMBRANE BELOW, DRAFT5TOPPING SHALL BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES: I. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2, FLOOR FRAMING IS CONSTRUCTED OF TRUSS -TYPE OPEN -WEB OR PERFORATED MEMBERS. DRAFTSTOPPING SHALL CONSIST OF MATERIALS LISTED IN 2016 IRC R302.12 FIREBLOCKING FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO FORM AN EFFECTIVE BARRIER BETWEEN STORIES, AND BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING SHALL BE PROVIDED IN WOOD -FRAME CONSTRUCTION IN THE FOLLOWING LOCATIONS: I. IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS AS FOLLOWS: I.I. VERTICALLY AT THE CEILING AND FLOOR LEVELS. 1.2. HORIZONTALLY AT INTERVALS NOT EXCEEDING 10ft 2. AT ALL INTERCONNECTIONS BETWEEN CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR AT SOFFITS, DROP CEILINGS, AND COVE CEILINGS. 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER STAIRS SHALL COMPLY WITH 2018 IRC R302.1 4. AT OPENINGS AROUND VENTS, PIPES, AND DUCTS AT CEILING AND FLOOR LEVEL, WITH AN APPROVED MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND PRODUCTS OF COMBUSTION. 5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES, SEE 2010 IRC 81003.19. 6. FIREBLOCKING OF CORNICES OF A TWO-FAMILY DWELLING IS REQUIRED AT THE LINE OF DWELLING UNIT SEPERATION. FIREBLOCKING SHALL CONSIST OF MATERIALS LISTED IN 2018 IRC SECTION 8302.11.1.3 LOOSE -FILL INSULATION MATERIAL SHALL NOT BE USED AS A FIREBLOCK UNLESS SPECIFICALLY TESTED IN THE FORM AND MANNER INTENDED. THE INTEGRITY OF ALL FIREBLOCKS SHALL BE MAINTAINED. LIGHTING 2018 WSEC SECTION 8404- LIGHTING EQUIPMENT 8404.1 LIGHTING EQUIPMENT: NOT LESS THAN 90 PERCENT OF LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH EFFICACY LAMPS 8404.1.1 LIGHTING EQUIPMENT:FUEL GAS LIGHTING SYSTEMS SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. DRILLING AND NOTCHING STUDS. 8602.6 DRILLING AND NOTCHING OF STUDS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: I. NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING PARTITION SHALL BE PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH 2. DRILLING. ANY STUD SHALL BE PERMITTED TO BE BORED OR DRILL, PROVIDED THAT THE DIAMETER OF THE RESULTING HOLE IS NOT MORE THAN 6O PERCENT OF A SINGLE STUD WIDTH, THE EDGE OF THE HOLE IS NOT MORE THAN 5/0 INCH (1(o mm) TO THE EDGE OF THE STUD, AND THE HOLE IS NOT LOCATED IN THE SAME SECTION AS A CUT OR NOTCH. STUDS LOCATED IN EXTERIOR WALLS OR BEARING PARTITIONS DRILLED OVER 40 PERCENT AND UP TO (o0 PERCENT SHALL BE DOUBLED WITH NOT MORE THAN TWO SUCCESSIVE DOUBLED STUDS BORED. SEE 2018 IRC FIGURES 8602.60) AND 8602.6(2). -EXCEPTION: USE OF APPROVED STUD SHOES IS PERMITTED WHEN THEY ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. IR&O2.6.1 DRILLING AND NOTCHING OF TOP PLATE. WHERE PIPING OR DUCTWORK IS PLACED IN OR PARTLY IN AN EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL, NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A GALVANIZED METAL TIE OF NOT LESS THAN 0.054 INCH THICK (1.37 mm) (1(o ea) AND 111/2 INCHES (38 mm) WIDE SHALL BE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE OPENING WITH NOT LESS THAN EIGHT 10d (0.148 INCH DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 1 1/2 INCHES (38 MM) AT EACH SIDE OR EQUIVALENT. THE METAL TIE MUST EXTEND NOT LESS THAN 6 INCHES PAST THE OPENING. SEE 2010 IRC FIGURE 8602.6.1. -EXCEPTION. WHERE THE ENTIRE SIDE OF THE WALL WITH THE NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL SHEATHING. DOORS, WINDOWS AND SKYLIGHTS GENERAL ALL SKYLIGHTS AND SKY WALLS TO BE LAMINATED GLASS UNLESS NOTED OTHERWISE. BEDROOM EMERGENCY EGRESS WINDOWS SHALL HAVE MINIMUM NET CLEAR OPENING OF 5.7 SQ. FT WITH MINIMUM NET CLEAR OPENING WIDTH OF 20" AND MINIMUM NET CLEAR OPENING HEIGHT OF 24" FIN15HED SILL HEIGHT SHALL BE MAXIMUM 44' ABOVE FLOOR, MEASURED FROM THE FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING WINDOW FLASHING TO BE FASTENED PER 2018 IRC 8703.4 WINDOW GUARDS ARE REQUIRED PER 2010 IRC 8312.1 SAFETY GLAZING SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS OR AS OTHERWISE REQUIRED PER 2018 IRC R308.4.3 SIDE HINGED DOORS EXCEPT JALOUSIES SLIDING GLASS DOORS AND PANELS IN SLIDING 4 BI -FOLD CLOSET DOOR ASSEMBLIES OF A DOOR IN THE CLOSED POSITION & BOTTOM EDGE IS LESS THAN 60" ABOVE 1. SHOWER AND BATH TUB, HOT TUB, WHIRLPOOL, SAUNA, STEAM ENCLOSURES 2. GLAZING W/ THE EXPOSED EDGE WITHIN A 24" ARC OF EITHER VERTICAL EDGE 3, STORM DOORS 4 THE WALKING SURFACE S C -;LAZING GREATER THAN 9 S.F. AND LESS THAN 18" ABOVE FINISHED FLOOR GLAZING IN GUARDRAILS �. GLAZING LF -66 THAN 18" ABOVE FINISHED FLOOR 8. STAIRS AND RAMPS ADJACENT WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 36" ABOVE THE PLANE OF ADJACENT WALKWAY SURFACE OF STAIRWAYS LANDINGS BETWEEN FLIGHTS OF STAIRS AND RAMPS SHALL BE CONSIDER A HAZARDOUS LOCATION. PER 2018 IRC 8308.4.6 MECHANICAL HEATING EQUIPMENT MECHANICAL HEATING EQUIPMENT ALL WARM -AIR FURNACES SHALL BE LISTED AND LABELED BY AN APPROVED AGENCY AND INSTALLED TO LISTED SPECIFICATIONS. NO WARM -AIR FURNACES SHALL BE INSTALLED IN A ROOM USED OR DESIGNED TO BE USED AS A BEDROOM, BATHROOM, CLOSET OR IN ANY ENCLOSED SPACE WITH ACCESS ONLY THROUGH SUCH ROOM OR SPACE, EXCEPT DIRECT VENT FURNACE, ENCLOSED FURNACES AND ELECTRIC HEATING FURNACES. LIQUIFIED PETROLEUM GAS -BURNING APPLIANCES SHALL NOT BE INSTALLED IN A PIT, BASEMENT OR SIMILAR LOCATION WHERE HEAVIER THAN AIR GAS MIGHT COLLECT, APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH AN APPROVED MEANS FOR REMOVAL OF UNBURNED GAS. HEATING AND COOLING EQUIPMENT LOCATED IN A GARAGE WHICH GENERATES A GLOW, SPARK OR FLAME CAPABLE OF IGNITING FLAMMABLE VAPORS SHALL BE INSTALLED WITH THE PILOTS AND BURNERS FOR HEATING ELEMENTS AND SWITCHES AT LEAST IS" ABOVE THE FLOOR LEVEL. TEMPERATUERE CONTROL THE PRIMARY SPACE CONDITIONING SYSTEM WITHIN EACH DWELLING UNIT SHALL BE PROVIDED WITH AT LEAST ONE PROGRAMMABLE THERMOSTAT FOR THE REGULATION OF TEMPERATURE WSEC 5EC.403.1.1 VENTILATION EVERY FACTORY BUILT CHIMNEY, TYPE L VENT, TYPE B GAS VENT OR TYPE BW GAS VENT SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF ITS LISTING, MFR'S INSTALLATION INSTRUCTIONS AND APPLICABLE CODE REQUIREMENTS. A TYPE L VENTING SYSTEM SHALL TERMINATE NOT LESS THAN 2 FEET ABOVE THE HIGHEST POINT WHERE THE VENT PASSES THROUGH THE ROOF OF THE BUILDING AND AT LEAST 2' HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10' OF THE VENT. INTEGRATED WHOLE HOU3E VENT 3i'3TEM INTEGRATED 24 HR WHOLE HOUSE VENTILATION SYSTEM. * USING A SUPPLY FAN W/ MANUAL 8 MOTORIZED DAMPER. * FAN TIMER EXTERNALLY LOCATED ON THE SIDE OF FURNACE OR GARAGE WALL. 220 CFM REQUIRED W/ A RUN TIME OF S NRS. MIN. FAN MUST OPERATE AT LEAST ONCE EVERY THREE HOURS SO VENTILATION EFFECTIVENESS CAN BE 1.0 * 8" SMOOTH WALL PIPE (OPERATION DESCRIPTION TO BE PROVIDED PER M1505.4) SYSTEM TO BE TESTED AT FINAL INSPECTION 4 LABELED BUILDING AIR LEAKAGE TESTING 201E W3EC 8402.4.1.2 TESTING SHALL OCCUR AT ANY TIME AFTER ROUGH IN AND AFTER INSTALLATION OF PENETRATIONS OF THE BUILDING ENVELOPE. WHEN REQUIRED BY THE BUILDING OFFICIAL, THE TEST SHALL BE CONDUCTED IN THE PRESENCE OF DEPARTMENT STAFF. THE BLOWER DOOR TEST RESULTS SHALL BE RECORDED ON THE CERTIFICATE REQUIRED PER WSEC R401.3 2010 WASHINGTON STATE ENERGI CODE = TABLE 402.1.1 INSULATION AND FENESTRATION REQUIRMENT BY COMPONET CLIMATE ZONE 5 s MARINE 4 - HEATING BY OTHER FUELS FENESTRATION U -FACTOR CEILING WALL ABOVE GRADE WALL BELOW GRADE MASS WALL FLOOR SLAB ON GRADE VERTICAL OVERHEAD 0.28 0.50 R-49 R-21 R-10/15/21 R -21/21H R-38 R-10 45 60 15 90 TB 3001-4500 60 2' UTILITY ROOM NOTES/MAKE UP AIR: I. WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING CONSTRUCTION, THE EQUIVALENT LENGTH OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR TAG SHALL BE LOCATED WITHIN (o FEET OF THE EXHAUST DUCT CONNECTION. 2. INSTALLATIONS EXHAUSTING MORE THAN 200 CFM CHALL BE PROVIDED WITH MAKE UP AIR WHERE A CLOSET IS DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN OPENING HAVING AN AREA OF NOT LESS THAN 100 SQ. INCHES FOR MAKE UP AIR SHALL BE PROVIDED IN THE CLOSET ENCLOSURE, OR MAKE UP AIR SHALL BE PROVEDED BY OTHER APPR. MEANS. 100 SQ INCH TRANSFER GRILL PER IRC G2439.4 (614.(o) M1505.4.3 MECHANICAL VENTILATION RATE. THE WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM SHALL RROVIDE OUTDOOR AIR ATA CONTINUOUS RATE AS DETERMINED IN ACCORDANCE WITH TABLE 1-11505.4.30) OR EQUATION 15-1. EQUATION 15-1 VENTILATION RATE IN CUBIC FEET PER MINUTE - (0.01 x TOTAL SQUARE FOOT AREA OF HOUSE) = 3/41.5 x (NUMBER OF BEDROOMS = 01/g BUT NOT LESS THAN 30 CFM FOR EACH DWELLING UNIT CONTINUOUS WHOLE -HOUSE M;=e-UANlr"_dl vFNTII ATIr AJ AYATFM Al;=l Pall;PATE;PFr7l IIVFMFNT0, DWELLING UNIT FLOOR AREA (50. FT.) 25% 339. NUMBER OF BEDROOMS (069. T5% 0-1 2-3 4-5 6 -1 <l AIRFLOW IN CFM 3 < 1500 30 45 60 15 90 1501-3000 45 60 15 90 105 3001-4500 60 15 90 105 120 4501 - 6000 15 90 105 120 135 (0001-1500 90 105 120 135 150 > 1500 105 120 135 150 165 INTF;PMITTFNT MF( UANlr Al vFNTII dTInN ;PATE Fdr'TnFP..i RUN-TIME % IN EACH 4 -HOUR SEGMENT 25% 339. 509. (069. T5% 100% FACTOR 4 3 2 1.5 1.3 1.0 MINIMUM FPF:MIIIPF:n;:YWMll;T IPdTFB AREA TO BE VENTED EXHAUST RATES KITCHENS 100 CFM INTERMITTENT OR J 25 CFM CONTIMUOUSLY BATHROOM / LAUNDRY / SIMILAR 50 CFM INTERMITTENT OR AREAS 20 CFM CONTIMUOUSLY BALANCED UJHOLE HOUSE VENTILATION. BALANCED W14CLE HOUSE VENTILATION IS DEFINED AS ANY COMBINATION OF CONCURRENTLY ORERATING RESIDENTIAL UNIT MECHANICAL EXHAUST AND MECHANICAL SURRLY WHEREBY THE TOTAL MECHANICAL EXHAUST AIRFLOW RATE IS WITHIN 10 PERCENT OR 5 CFM, WHICHEVER IS GREATER, OF THE TOTAL MECHANICAL SUPPLY AIRFLOW RATE. INTERMITTENT DRYER EXHAUST, INTERMITTENT RANGE HOOD EXHAUST, AND INTERMITTENT TOILET ROOM EXHAUST AIRFLOW RATES ABOVE THE RESIDENTIAL DWELLING OR SLEEPING UNIT MINIMUM VENTILATION RATE ARE EXEMPT FROM THE BALANCED AIRFLOW CALCULATION. POSTING OF CERTIFICATE 2018 WSEC 8401.3 CERTIFICATE. A PERMANENT CERTIFICATE SHALL BE COMPLETED BY THE BUILDER OR OTHER APPROVED PARTY AND POSTED ON A WALL IN THE SPACE WHERE THE FURNACE IS LOCATED, A UTILITY ROOM, OR AN APPROVED LOCATION INSIDE THE BUILDING, WHEN LOCATED ON AN ELECTRICAL PANEL, THE CERTIFICATE SHALL NOT COVER OR OBSTRUCT THE VISIBILITY OF THE CIRCUIT DIRECTORY LABEL, SERVICE DISCONNECT LABEL, OR OTHER REQUIRED LABELS, THE CERTIFICATE SHALL LIST THE PREDOMINANT R -VALUES OF INSULATION INSTALLED IN OR ON CEILING/ROOF, WALLS, FOUNDATION (SLAB, BELOW -GRADE WALL, AND/OR FLOOR) AND DUCTS OUTSIDE CONDITIONED SPACES U -FACTORS FOR FENESTRATION AND THE SOLAR HEAT GAIN COEFFICIENT (5HGC) OF FENESTRATION: THE RESULTS FROM ANY REQUIRED DUCT SYSTEM AND BUILDING ENVELOPE AIR LEAKAGE TESTING DONE ON THE BUILDING: AND THE RESULTS FROM THE WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FLOW RATE TEST. WHERE THERE IS MORE THAN ONE VALUE FOR EACH COMPONENT, THE CERTIFICATE SHALL LIST THE VALUE COVERING THE LARGEST AREA. THE CERTIFICATE SHALL LIST THE TYPES AND EFFICIENCIES OF HEATING, COOLING, WHOLEHOUSE MECHANICAL VENT IATION AN D SERVICEWATER HEATING APPLIANCES, WHERE A GAS-FIREDUNVENTED ROOM HEATER, ELECTRIC FURNACE, OR BASEBOARD ELECTRIC HEATER IS INSTALLED IN THE RESIDENCE, THE CERTIFICATE SHALL LIST "GAS-FIRED UNVENTED ROOM HEATER,' 'ELECTRIC FURNACE" OR 'BASEBOARD ELECTRIC HEATER,' AS APPROPRIATE. AN EFFICIENCY SHALL NOT BE LISTED FOR GAS-FIRED UNVENTED ROOM HEATERS, ELECTRIC FURNACES OR ELECTRIC BASEBOARD HEATERS THE CODE OFFICIAL MAY REQUIRE THAT DOCUMENTATION FOR ANY REQUIRED TEST RESULTS INCLUDE AN ELECTRONIC RECORD OF THE TIME, DATE AND LOCATION OF THE TEST, A DATE STAMPED SMART PHONE PHOTO OR AIR LEAKAGE TESTING SOFTWARE MAY BE USED TO SATISFIED THIS REQUIREMENT. 2010 WASHINGTON STATE ENERGI' CREDIT-TA5LE R40(o.3 ENERGI' CREDITS CREDITI OPTION I DESCRIPTION PRESCRIPTIVE COMPLIANCE IS BASED ON TABLE 8402.1.1 WITH THE FOLLOWING MODIFICATIONS: VERTICAL FENESTRATION U = 0.28 FLOOR R-38 0.5 1.3 SLAB ON GRADE R-10 PERIMETER AND UNDER ENTIRE SLAB BELOW GRADE SLAB R-10 PERIMETER AND UNDER ENTIRE SLAB OR COMPLIANCE BASED ON SECTION 8402.1.4: REDUCE THE TOTAL CONDUCTIVE UA BY 5%, COMPLIANCE BASED ON 8402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 3.0 AIR CHANGES PER HOUR MAXIMUM AT 50 PASCALS OR FOR R-2 OCCUPANCIES, OPTIONAL COMPLIANCE BASED ON SECTION R402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 0.3 CFM/FT2 MAXIMUM AT 50 PASCALS AND ALL WHOLE HOUSE VENTILATION REQUIREMENTS AS DETERMINED BY SECTION 0.5 2.1 M1501.3 OF THE INTERNATIONAL RESIDENTIAL CODE OR SECTION 403.8 OF THE INTERNATIONAL MECHANICAL CODE SHALL BE MET WITH A HIGH EFFICIENCY FAN(S) (MAXIMUM 0.35 WATTS/CFM), NOT INTERLOCKED WITH THE FURNACE FAN (IF PRESENT). VENTILATION SYSTEMS USING A FURNACE INCLUDING AN ECM MOTOR ARE ALLOWED, PROVIDED THAT THEY ARE CONTROLLED TO OPERATE AT LOW SPEED IN VENTILATION ONLY MODE, TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED, THE MAXIMUM TESTED BUILDING AIR LEAKAGE, AND SHALL SHOW THE QUALIFYING VENTILATION SYSTEM AND ITS CONTROL SEQUENCE OF OPERATION. AIR -SOURCE CENTRALLY DUCTED HEAT PUMP WITH MINIMUM HSPF OF 9.5, 1.0 3.2 TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE HEATING EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL SUPPLY AND RETURN DUCTS LOCATED IN AN UNCONDITIONED ATTIC SHALL BE DEEPLY BURIED IN CEILING INSULATION IN ACCORDANCE WITH SECTION R403.31. FOR MECHANICAL EQUIPMENT LOCATED OUTSIDE THE CONDITIONED SPACE, A MAXIMUM OF 10 LINEAR FEET OF RETURN DUCT AND 5 LINEAR FEET OF SUPPLY DUCT CONNECTIONS TO THE EQUIPMENT MAY BE OUTSIDE THE DEEPLY BURIED INSULATION. 0.5 4.1 ALL METALLIC DUCTS LOCATED OUTSIDE THE CONDITIONED SPACE MUST HAVE BOTH TRANSVERSE AND LONGITUDINAL JOINTS SEALED WITH MASTIC. IF FLEX DUCTS ARE USED, THEY CANNOT CONTAIN SPLICES. DUCT LEAKAGE SHALL BE LIMITED TO 3 CFM PER 100 SQUARE FEET OF CONDITIONED FLOOR AREA. AIR HANDLER(S) SHALL BE LOCATED WITHIN THE CONDITIONED SPACE. WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWING: ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION OR FOR R-2 OCCUPANCY, ELECTRIC HEAT PUMP WATER HEATER(S), MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION, SHALL 2.0 5.5 SUPPLY DOMESTIC HOT WATER TO ALL UNITS, IF ONE WATER HEATER IS SERVING MORE THAN ONE DWELLING UNIT, ALL HOT WATER SUPPLY AND RECIRCULATION PIPING SHALL BE INSULATED WITH R-8 MINIMUM PIPE INSULATION. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE WATER HEATER EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL OF THE FOLLOWING APPLIANCES SHALL BE NEW AND INSTALLED IN THE DWELLING UNIT AND SHALL MEET THE FOLLOWING STANDARDS: DISHWASHER -ENERGY STAR RATED REFRIGERATOR (IF PROVIDED) -ENERGY STAR RATED WASHING MACHINE -ENERGY STAR RATED 0.5 1.1 DRYER -ENERGY STAR RATED, VENTLE55 DRYER WITH A MINIMUM CEF RATING OF 5.2. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SHOW THE APPLIANCE TYPE AND PROVIDE DOCUMENTATION OF ENERGY STAR COMPLIANCE, AT THE TIME OF INSPECTION, ALL APPLIANCES SHALL BE INSTALLED AND CONNECTED TO UTILITIES. DRYER DUCTS AND EXTERIOR DRYER VENT CAPS ARE NOT PERMITTED TO BE INSTALLED IN THE DWELLING UNIT. SYSTEM TABLE R406.2 TYPE FUEL NORMALIZATION CREDITS FOR AN INITIAL HEATING SYSTEM USING A HEAT PUMP THAT MEETS FEDERAL STANDARDS FOR THE EQUIPMENT 1.0 2 LISTED IN TABLE C403.3.2(1r- OR C403.3.2(2) OR AIR TO WATER HEAT PUMP UNITS THAT ARE CONFIGURED TO PROVIDE BOTH HEATING AND COOLING AND ARE RATED IN ACCORDANCE WITH AHRI 550/590 6.0 I TOTAL: O J rm J 0 UJ J 0It J O LU O r - o N UJ O < UJ O N 0 N LO 00 O N uj - 100 - J ui z J >N rn c > o a 10D -J LE +' +� 0 0` o � c N +� N N •Q O >. N Co as 03 co � N Co N o� o �3 a>i U- ,N N ate+ O CIS 3: L N Q- ,� J CL c U g E J a� oa�2cncEc N co aD.�U c +,J Q cz c O N u�c �vi- 0 a , W �m � N O N i2 to +' cn aXi o N N m S2 CO O ca E' ��a� a) oco F-� d +�+ CO > Q J H +�. J U �r, 00 011 '0 N � E U C:> a; M :0 Q 00 E (V E Ln 40 CV w N O a � REVISION DATE: INIT: RROJECT: DATE: 12/20/2021 NIT: 4 PROJECT . �NOTE� BUILDING AIR LEAKAGE- TEST REQUIRED AS PER 2018 WSE=C R402.4.1.2 DUCTS -DUCTS SMALL BE LEAK TESTED IN ACCORDANCE WITH WSU RS -33 PER 2018 WSEC 8403.3.3 -DUCTS, AIR HANDLERS, FILTER BOXES SHALL BE SEALED AS PER M1601.4.1 -R403.3.2.1 2018 WSEC 2018 IRC 8311.3 FLOOR AND LANDINGS AT EXTERIOR DOORS. THERE= SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT LESS THAN THE DOOR SERVED. LANDING SMALL HAVE A DIMENSION OF NOT LESS THAN 36" (914MM) MEASURED IN THE DIRECTION OF TRAVEL THE SLOPE AT EXTERIOR LANDING SMALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2 PERCENT) *DRYER VENT* 2018 IRC M1502.4.6 LENGTH IDENTIFICATION. WHERE THE EXHAUST DUCT EQUIVALENT LENGTH EXCEEDS 35 FEET (10 668 MM), THE EQUIVALENT LENGTH OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR TAG SHALL BE LOCATED WITHIN (o FEE (1829 MM) OF THE EXHAUST DUCT CONNECTION 2018 IRC R 303.E INTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE TO ILLUMINATE THE LANDINGS AND TREADS. THE LIGHT SOURCE SHALL BE CAPABLE OF ILLUMINATING TREADS AND LANDINGS TO LEVEL OF NOT LESS THAN I FOOT-CANDLE (11 LUX) AS MEASURED AT THE CENTER OF TREADS AND LANDINGS. THERE SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL TO CONTROL THE LIGHT SOURCE WHERE THE STAIRWAY HAS SIX OR MORE RISERS. 2018 IRC R 311.7.9 ILLUMINATION STAIRWAY SHALL BE PROVIDED WITH IN ACCORDANCE WITH SECTION 8303.7 $ R303.8 1 i 14'-6" g719OW OWNER' SUITE 14'-0°X15'-0" ® N 110V SSD r p1m DOWN 16 41 ° LE15URE LOFT x 12'-O"X6'-6" CC) 1, R302.5 DWELLING -GARAGE OPENING AND PENETRATION PROTECTION, OPENINGS AND PENETRATIONS THROUGH THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE IN ACCORDANCE WITH SECTIONS 8302.5.1 THROUGH 8302.5.3, 8302.5.1 OPENING PROTECTION, OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 a INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB -CORE STEEL DOORS NOT LESS THAN 1 a INCHES (35 MM) THICK, O8 20 -MINUTE FIRE -RATED DOORS, EQUIPPED WITH A SELF-CLOSING DEVICE. 8302.5.2 DUCT PENETRATION. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE (0.48 MM) SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL NOT HAVE OPENINGS INTO THE GARAGE. 8302.5.3 OTHER PENETRATIONS. PENETRATIONS THROUGH THE SEPARATION REQUIRED IN SECTION 8302.6 SHALL BE PROTECTED AS REQUIRED BY SECTION 8302.11, ITEM 4 8302.6 DWELLING -GARAGE FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE 8302.6 OPENINGS IN GARAGE WALLS SHALL COMPLY WITH SECTION R302.5 ATTACHMENT OF GYPSUM BOARD SHALL COMPLY WITH TABLE R702.3.5, THE WALL SEPARATION PROVISIONS OF TABLE 8302.6 SHALL NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR THE THE ADJACENT DWELLING UNIT WALL. 8302.7 UNDER -STAIR PROTECTION. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE: WALLS, UNDER -STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH z INCH (12A MM) GYPSUM BOARD, PLE,45E REFER TO 5NEET 1/4 FOR ENERG'' CREDIT FROP05ED UNIDER THE 2018 WA514INGTON 5TATE ENERGY CREIDIT-TA5LE 8406.3 31�tii EA 8'-10" DL —1 (VTO) 2 N UTILITY 9'-6"X5'-6" AT IC 11 ow 60"x32" N T/S UPPER FLOOR PLAN 4'-4° 4'-4" 36' -0" �10V L D VENTILATION REQUIREMENTS OF 1=--C TABLE 1-11505,4-4 ° E p ROOM 2 L x 10'-6"XI cofV LH 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 25 CFM CONTINUOUS LH r E3ATHROOMS/TOILET ROOMS/ WHE=RE PRIMARY POWER IS INTERRUPED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL O C/M BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH, OTHER THAN THOSE REQUIRED FOR OF 50 CFM INTERMITTENT OR 20 OVERCURRENT PROTECTION, ENTRY PORCH: EXCEPTIONS: SF-. 1. CARBON MONOXIDE- ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED WHERE �r INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER. cf) c P pROC +� > U >+ 70J 0 -0i 2 c))() a)}. E cn a) O O i 10' "X13140" 0 O❑_ QczQ >,a) _c_n U :3 -0 C13 a) EGRESS 0 o a) - _j Q ct c U I ao)E�c�J E L � O 0 N 0�� c 5- _ C O J c O O Q W C - a 0 72 a) 0� a)� o �, ) 4❑ 5040 XO > J H ca a-❑ (� 5'-6° Q H Ln U 3'-0" 214o" 11'-0" DL —1 (VTO) 2 N UTILITY 9'-6"X5'-6" AT IC 11 ow 60"x32" N T/S UPPER FLOOR PLAN 4'-4° 4'-4" 36' -0" �10V L D 110V � SSD V Lu 3030�FX ° 2'-4" 1 2'-1011 5'-11" R/S 4068 BI -PASS 5'-0" 15'-2" m 5'-0" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" PROVIDE 1-1RE5LOC<NG AS REQUIRED (SEE NOTES ON SKEET 1) WINDOW LEADERS AT 0'-8" ABOVE SUB F:LOOK, U.N.O. EXTERIOR WALLS TO ESE 2Xro AT leo" O -C., UN_O. INTERIOR PARTITIONS TO E3E 2X-4,47 fro" O.C. (2Xro �@ PLUME 31NG WALLS) U -N -0 - PROVIDE SUPPLEMENTAL JOISTS/E 3LOCKING 5E -LOW SI -IE ­AR WALL.. AS INDICATE -D ON F:RAMINe PIAN PROVIDE SOLIF-) HRAMING E -QUAL TO THE WIDTH OF- TLE MEME5ER EYEING SUPPORTED (UN.O.) SMOKE DETECTORS VENTILATION REQUIREMENTS OF 1=--C TABLE 1-11505,4-4 ° E p ROOM 2 L x 10'-6"XI ' LH 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 25 CFM CONTINUOUS LH r 110V � SSD V Lu 3030�FX ° 2'-4" 1 2'-1011 5'-11" R/S 4068 BI -PASS 5'-0" 15'-2" m 5'-0" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" PROVIDE 1-1RE5LOC<NG AS REQUIRED (SEE NOTES ON SKEET 1) WINDOW LEADERS AT 0'-8" ABOVE SUB F:LOOK, U.N.O. EXTERIOR WALLS TO ESE 2Xro AT leo" O -C., UN_O. INTERIOR PARTITIONS TO E3E 2X-4,47 fro" O.C. (2Xro �@ PLUME 31NG WALLS) U -N -0 - PROVIDE SUPPLEMENTAL JOISTS/E 3LOCKING 5E -LOW SI -IE ­AR WALL.. AS INDICATE -D ON F:RAMINe PIAN PROVIDE SOLIF-) HRAMING E -QUAL TO THE WIDTH OF- TLE MEME5ER EYEING SUPPORTED (UN.O.) SMOKE DETECTORS VENTILATION REQUIREMENTS OF 1=--C TABLE 1-11505,4-4 NSTALL SMOKE DETECTORS WHERE INDICATED OSD ALL SMOKE DETECTOR RECEIVE THERE POWER HROIl TLE PE�IMARY APPLIED TO THE GARAGE SIDE AND INTERCONNECTED PER 831,4.4 4 8314.0 CARBON MONOXIDE ALARMS 1 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 25 CFM CONTINUOUS FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND, E3ATHROOMS/TOILET ROOMS/ WHE=RE PRIMARY POWER IS INTERRUPED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL O C/M BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH, OTHER THAN THOSE REQUIRED FOR OF 50 CFM INTERMITTENT OR 20 OVERCURRENT PROTECTION, ENTRY PORCH: EXCEPTIONS: SF-. 1. CARBON MONOXIDE- ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED WHERE 120 INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER. VENTILATION SCHEDULE VENTILATION REQUIREMENTS OF 1=--C TABLE 1-11505,4-4 SYMBOL NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT EXHAUST RATES APPLIED TO THE GARAGE SIDE KITCHENS (V.T.0) 100 C7M INTERMITTENT OR 1 UPPER FLOOR: 25 CFM CONTINUOUS 51-. E3ATHROOMS/TOILET ROOMS/ MECHANICAL EXHAUST CAPACITY 2 LAUNDRY ROOM (V.T.0) OF 50 CFM INTERMITTENT OR 20 SP. ENTRY PORCH: CFM CONTINUOUS VENTILATION RATE 7OR WHOLE HOUSE 7,4N TO BE 15 CFM PER TABLE M1505.4.30) INDOOR AIR QUALITY HVAC CONTRACTOR TO SPE�CIF­Y LOCATION. i 12'-0" AREA SUMMARY MATERIAL N I NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT un APPLIED TO THE GARAGE SIDE MAIN FLOOR: a4e SF-. UPPER FLOOR: 1203 51-. TOTAL: 2052 SF. GARAGE: 3-1-1 SP. ENTRY PORCH: 55 SF-. PATIO: 120 SF-. cf) c c 0 +� > U >+ 70J 0 -0i 2 c))() a)}. E cn a) O O i +. -0 p+. U O 0 O❑_ QczQ >,a) _c_n U :3 -0 C13 a) _ 0 o a) - _j Q ct c U I ao)E�c�J E i 12'-0" AREA SUMMARY MATERIAL N I NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM THE RESIDENCE AND ATTICS APPLIED TO THE GARAGE SIDE MAIN FLOOR: a4e SF-. UPPER FLOOR: 1203 51-. TOTAL: 2052 SF. GARAGE: 3-1-1 SP. ENTRY PORCH: 55 SF-. PATIO: 120 SF-. MAIN FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" - ALL DOOR/WINDOW HEADERS TO BE 4X10 D71*2 AT 2xr BEARING WALLS , U.N.O., G -0" MAX. SPAN - ALL DOOR/UJINDOUJ HEADERS TO BE 4X10 DP#2 AT 2x4 BEARING WALLS, U.N.O., (o' -O" MAX. SPAN - WINDOW LEADERS AT ro'-8" ABOVE SUB 7LOOR, U.N.O. - PROVIDE EIREBLOCKING AS REQUIRED (SEE NOTES ON SHEET 1) EXTERIOR WALLS TO 5E� 2Xro AT fro" (MAX.) O -C. U.N.O. INTERIOR PARTITIONS TO BE 2x4 AT 1(o" O.C. (2X(o 'S PLUMBING WALLS, U.N.O.) DUCTS THROUGH WALL OR CEILING COMMON TO HOUSE MIN. 2G GAGE STEEL PROVIDE SOLID HRAMIING EQUAL TO THE UJIDTH OF THE MIE1 IE 3ER BEING SUPPORTED (U-N.O.) T,45LE 302.6 DWELL ING-G,4RAGR 5E1=,4R,4TI0N SEPARATION MATERIAL N I NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM THE RESIDENCE AND ATTICS APPLIED TO THE GARAGE SIDE FROM HABITABLE ROOM ABOVE THE GARAGE NOT LESS 5/8 INCH TYPE X GYPSUM BOARD OF EQUIVALENT STRUCTURE(S) SUPPORTING FLOOR/CEILIING ASSEMBLIES O USED FOR SEPARATION REQUIRED BY THIS SECTION NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT GARAGE= LOCATION LESS 3 FEET NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM A DWELLING UNIT ON THE SAME LOT APPLIED TO THE INTERIOR SIDE OF EXTERIOR WALLS THAT ARE WITHIN THIS AREA FOR SI : 1 INCH = 25.4 MMI FOOT =304.8 MM. N I N O N J cf) c c 0 +� > U >+ 70J 0 -0i 2 c))() a)}. E cn a) O O i +. -0 p+. U O 0 O❑_ QczQ >,a) _c_n U :3 -0 C13 a) _ 0 o a) - _j Q ct c U (D a) 0�� ao)E�c�J E L � O 0 N 0�� c 5- _ C O J c O O Q W C - a 0 72 a) 0� a)� o �, ) 4❑ a) m o cnOELcza) O E cp�a) > J H ca a-❑ (� J Q H Ln U o 00 0% c� 70 o M M 00 Q 00 N 00 NN M W Ln N cn Z C:) x %0 a LL. REVISION DATE: INIT: PROJECT: DATE: 12/20/2021 INIT: 2 JACK 4 PROJECT: HANDRAIL TO BE PRESENT ON ON AT LEAST ONE SIDE OF STAIR, HANDGRIP PORTION OF HANDRAILS COMPOSITION ROOFING ON 4" SPHERE 5 ALL SHALL HAVE CIRCULAR GROSS SECTION MGL -r=l IGCiG LCL iG b CSI T I IA IY'1=LI AY1vICA IT NOT PASS HROUCzH OF I /4 " M IN. 2 " MAX. ALL REQUIRED GUARDRAILS TO BE aro" / MIN. IN HEIGHT, OPENINGS AOR REQUIRED GUARDS ON THE SIDES OF STAIR TREADS SHALL NOT ALLOW A SPHERE 43/8 INCHES (107mm) TO PASS TIHROUeIH 3/4" MIN. -11/4" MAX NOSING; 2X4 THRUST BLOCK SIMPSON LSC ORISIMULAR BRAGKI=T ro" SPHER€ UNABLE TO PASS THROUGH OPENING BELOW STAIR INSTALL 1/2" GWB a CEILING, AND WALLS (3) 2X12 STRINGERS FIRE BLOCKING @ MID -SPAN AND IN STUD WALLS ALONG AND IN LINE WITH STRINGERS IF AREA UNDER STAIRS 15 UNFINISHED INTERIOR/GUARDRAIL STAIR NOTES: - HANDRAILS MUST NOT PROJECT MORE THAN 41/2" ( 114 MM) INTO THE STAIRWAY. IRC SECTIONS R311.18.2 - THE SPACING BETWEEN INTERMEDIATE HANDRAIL MEMBERS MUST NOT ALLOW A 4" SPHERE TO PASS THROUGH ANY OPENING. IRC SECTION 8312.1.3 - MINIMUM STAIRWAY WIDTH ABOVE HANDRAIL SHALL BE NO LESS THAN 36 INCHES, IRC SECTION 8311.1.1 - STAIR & STAIR LANDING MINIMUM WIDTH SHALL BE NO LESS THAN 36" (311/2" CLEAR IF ONE HANDRAIL, S 21" CLEAR IF 2 HANDRAILS. IRC SECTION R311.11 - THE TREADS LEADING EDGE CURVATURE CAN HAVE A MAX. RADIUS OF 9/1611. THE MAX. BEVELING OF THE NOSING SHALL BE NO MORE THAN 1/2" IRC 5FG710N 8311.1.5.3 - RISER OR TREAD MAXIMUM DIFFERENTIAL SHALL BE NO MORE THAN 3/S" IRC SECTION 8311.1.5.1 - NOSING IS NOT REQUIRED FOR STAIRS WITH TREADS GREATER THAN 11". IRC SECTION 8311.1.5.3 FXTFRIOR STAIR NOTES: - EXTERIOR STAIR LIGHTING AT TOP LANDING WITH CONTROLS INSIDE THE DWELLING. IRC SECTION 8303.8 - A MAXIMUM SLOPE OF 1:48 (2%) IS REQUIRED AT EXTERIOR LANDINGS AND TREADS FOR DRAINAGE, IRC SECTION 8311.3 INTERIOR WINDER STAIR NOTES: - WINDER TREADS ARE REQUIRED TO HAVE A MINIMUM OF 6" DEPTH AT INNER EDGE, IRC SECTION R311.15.2.1 - WINDER TREAD DEPTH OF 10" WITH IN 12" OF THE INSIDE, IRC SECTION 8311.7.5.2.1 LAND ING NOTES: - LANDING WIDTH SHALL NOT BE LE55 THAN THAT OF STAIR SERVED IRC R311.7.6 - LANDING SHALL NOT BE LF55 THAN 36 INCHES IN DIRECTION OF TRAVEL SG R311,1.6 STAIR DETAIL SCALE: N.T.S. 8402.4.1.2 TESTING. THE BUILDING OR DWELLING UNIT SHALL BE TFSTFD AND VERIFIED AS HAVING AN AIR LEAKAGE RATE OF NOT EXCEEDING 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A BLOWER DOOR AT A PRESSURE OF 0.2 INCHES W.G. (50 PA5CAL5W). WHERE REQUIRED BY THE CODE OFFICIAL, TESTING SHALL BE CONDUCTED BY AN APPROVED THIRD PARTY. A WRITTEN REPORT OF THE RESULTS OF THE TEST SHALL BE SIGNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE CODE OFFICIAL. TESTING SHALL BE PERFORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF THE BUILDING THERMAL ENVELOPE. ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE R402.411), OPERABLE WINDOWS AND DOORS MANUFACTURED BY SMALL 5U51NF55 SHALL BE PERMITTED TO BE SEALED OFF AT THE FRAME PRIOR TO THE TEST. 2X4 BLOG<NG TYP. O2/2" HIGH 5/g" GWB TYPE "X" AT ALL SIDES WFATHFRSTRIPPFD TRU55 BOTTOM CHORD GWB TYPE "X" Sia G.W.B. TYPE "X" 22 x 30 ATTIC ACCESS OPENING ACCESS HATCH- CEILING INSULATE FULL DEPTH ATTIC ACCESS DETAIL SCALE: N.T.S. �7 z 0 Z LL > 0 m d CC) 1 /2 " HARDLUOOD HAND RA I L SOLID 5LOGKING AS REQUIRED PRE FINISH METAL BRAG<E7 TTP. T` f=. H,4NFD�R,4 f L 2015 WESG / R402.2.4 - ACCESS HATCHES AND DOORS, ACCESS DOORS FROM CONDITIONED SPACES TO UNCONDITIONED SPACES (E.G., ATTICS AND CRAWL SPACES) SHALL BE WEATHER5TRIPPED AND INSULATED TO A LEVEL EQUIVALENT TO THE INSULATION ON THE SURROUNDING SURFACES. ACCESS SHALL BE PROVIDED TO ALL EQUIPMENT THAT PRFVENT5 DAMAGING OR COMPRESSING THE INSULATION. A WOOD FRAMED OR EQUIVALENT BAFFLE OR RFTAINFR 15 REQUIRED TO BE PROVIDED WHEN L005F FILL INSULATION IS INSTALLED, THE PURPOSE OF WHICH IS TO PREVENT THE LOOSE FILL INSULATION FROM SPILLING INTO THE LIVING SPACE WHEN THE ATTIC ACCESS IS OPENED, AND TO PROVIDE A PERMANENT MEANS OF MAINTAINING THE INSTALLED R -VALUE OF THE LOOSE FILL INSULATION. PLEASE SHOW THE REQUIRED BAFFLE FRAMING AND INSULATION ATTACHED TO THE ACCESS LID, 3/4" T & G PLYWD WEATHER5TRIPPED SIDING PRODUCT 2X BLOCKING TYP. R-38 HD INSULATION IS" X 24" MIN CRAWL SPACE ACCESS FLOOR JOISTS AS PER PLAN C UJL SFACE ACCESS 1I E TA I L SGAL1=: N.T.S. OPTION WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWINr 5.5 ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION. /2" DRYWALL 2x STUDS 16" c/c —1/2 ° DRYWALL 2x4 CLEAT 6" O MIN. „z 0O 0 WATER O HEATER Cc) SEISMIC STRAPPING PER \ MANUFACTURERS 5PECIFICATIC (UPC, SEG .501.2) - SECURE SHAPED 2xIO SPACER TO 2x4 CLEATS WITH (5)-16d NAILS m SHAPED 2xIO SPACERS WILL BE CUT TO O INSURE A TIGHT FIT TO WATER HEATER WATER HEATER STRAPS WILL RESIST LATERAL FORCES EQUAL TO 100% OF GRAVITY LOADING PLATFORM MUST BE ANCHORED TO WALL FINISHED FLOOR TYi=IC:AL WATER HEATER DETAIL SCALE: N.T.S. W5EC 2018 8403.5.3 HOT WATER PIPE INSULATION (PRESCRIPTIVE) INSULATION FOR HOT WATER PIPE,BOTH WITHIN AND OUTSIDE THE CONDITIONED SPACE, SHALL HAVE A MINIMUM THERMAL RESISTANCE (R -VALUE) OF R-3 2018 UPC 312.6 FREEZING PROTECTION. NO WATER,501L,OR WASTE PIPE SHALL BE INSTALLED OR PERMITTED OUTSIDE OF A BUILDING, IN ATTICS OR CRAWL SPACE, OR IN AN EXTERIOR WALL UNLESS, WHERE NECESSARY, ADEQUATE PROVISION 15 MADE TO PROTECT SUCH PIPE FROM FREEZING. ALL HOT AND COLD WATER PIPES INSTALLED OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED TO A MINIMUM R-3 VENT FLUE UP THRU ROOF 1/2 ° DRYWALL 2x STUDS 16" c/c 2x4 CLEAT 2x4 CLEAT 4"4F SFT IT W/ FIL SECTION "A" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" TYPICAL ROOF CONSTRUCTION - CO1'1P05ITION ROOF SHINGLES - 1E�# ROOFINGx FELT COMPOSITION RC--"'" - H/fro" SIHEATIHING RATED 24/1(o 15" FELT PAPER - STRUCTURAL SYSTEM AS NOTED ON FRAMING PLAN 1/16" SHEATHING R-49 INSULATION ROOF FRAMING F GLU5 CEILING INSULATION BAFF 1/a" TO 1/4" MESH SCREEN OVER OPENINGS VENTED BLOCKY - MINIMUM NET F:FEE VENTILATINCx ARI=A SHALL 5E 1/150 5/4 x 8 FASCIA OF VENTED AREA SPACE OR 1/300 IF 40=�Oio CONTINUOUS MET; VENTING IN UPPER ATTIC OR RAFTER SPACE. PER IRC RaOro_2 - PROVIDI= 1" MINIMUM CLEARANCE 5E7 J€EN INSULATION R-10 RIGID INSUL AND SHIT-ATIHING AT VENTS PER IRC SECTION R000.3 TYPICAL WALL CONSTRUCTION - SIDING AND/OR VENEER PER ELEVATION - -1/10" PLY OR OS5 SIHTG.( U.N.O ) - TYVEK 5UILDING WRAP OR EQ. - 2Xro STUDS e fro" O.C. EXTERIOR WALLS U.N.O. EXTERIOR WALL NOTCH 2E i%, 5ORING 40% (oO% 50RING IF DOU5LED $ NOT MORE THAN TWO SUCCESSIVE STUDS. SEE NOTE ON SKEET 1 - 2x4 STUDS 'a) 10" O.C., INTEFIOR PARTITIONS (2X(o e PLU1"I5I1HCa WALLS) NON=FEARING WALL MAXIMUM NOTCH 40%, 5CRI1NG (oO% HOLES NO CLOSET, THE E�/8 INCH TO TACE OF STUD = R=21 INSULATION WITH VAPOR 5ARRIER 1/2" GW5. INTERIOR SHEATHING TYPICAL FLOOR CONSTRUCTION - 711NIS�1F=D FLOOR PEE, PLANS - 3/4" 74G PLYWOOD SU51FLOOR (GLUE AND NAIL) - F-LOOR JOISTS PER PLAN - R-30 INSULATION OVEF, UNH4EAT1-D AFEAS 2x6 STUDS 16" R-21 INSULATION 1/16" SHEATHING TYVFK WRAP - T' SIDING PER ELE� 3/4" TeG PLYWOOC FLOOR JOISTS P€ WINDOW HDR. PEf 5/4 TRIM 5URROU WINDOW W/ INS, GI 3/4" T8G PLYWOOC FLOOR JOISTS PE R-38 INSULATION 5/4 X 10 TRIM B/ 2X P.T. WOOD 51L 4" 4 GO TO STOI 4" 4 PF SFT IN I W/ FILTL. I �-,Y". TAL GUTTER ON 45CIA BD. TYP, 5 6 16 "o.c. 1LATION RR ELEVATIONS WRAP ON OR OSB SHEATHING, TYPICAL WALL 5ECTION w SUBFL i SUB FL SCALE : N.T.S. 7/1(o11 5HEATHING NOT REQUIRED ON EXT. WALLS WHERE T1=11 SIDING IS SPECIFIED (UNLESS NOTED OTHERW15E IN THE SMEAR WALL SPECIFICATIONS) N I 0 Z D m Lo O � z> N m 10" MIN. TRI=AD omJ c c 0 X i � � J 2 N +. i fA N� 0 0 N +• N N L Q ��-0 p+. U O Q ul oaco mi a� 0 C, 0 -cam y: ul Na N ) cn Q N E ccoJ E cu co 0 o o w` c Q C O 1-1 J � c� N O o m 4— Q cz c � (D0u) OPENINGS AOR REQUIRED GUARDS ON THE SIDES OF STAIR TREADS SHALL NOT ALLOW A SPHERE 43/8 INCHES (107mm) TO PASS TIHROUeIH 3/4" MIN. -11/4" MAX NOSING; 2X4 THRUST BLOCK SIMPSON LSC ORISIMULAR BRAGKI=T ro" SPHER€ UNABLE TO PASS THROUGH OPENING BELOW STAIR INSTALL 1/2" GWB a CEILING, AND WALLS (3) 2X12 STRINGERS FIRE BLOCKING @ MID -SPAN AND IN STUD WALLS ALONG AND IN LINE WITH STRINGERS IF AREA UNDER STAIRS 15 UNFINISHED INTERIOR/GUARDRAIL STAIR NOTES: - HANDRAILS MUST NOT PROJECT MORE THAN 41/2" ( 114 MM) INTO THE STAIRWAY. IRC SECTIONS R311.18.2 - THE SPACING BETWEEN INTERMEDIATE HANDRAIL MEMBERS MUST NOT ALLOW A 4" SPHERE TO PASS THROUGH ANY OPENING. IRC SECTION 8312.1.3 - MINIMUM STAIRWAY WIDTH ABOVE HANDRAIL SHALL BE NO LESS THAN 36 INCHES, IRC SECTION 8311.1.1 - STAIR & STAIR LANDING MINIMUM WIDTH SHALL BE NO LESS THAN 36" (311/2" CLEAR IF ONE HANDRAIL, S 21" CLEAR IF 2 HANDRAILS. IRC SECTION R311.11 - THE TREADS LEADING EDGE CURVATURE CAN HAVE A MAX. RADIUS OF 9/1611. THE MAX. BEVELING OF THE NOSING SHALL BE NO MORE THAN 1/2" IRC 5FG710N 8311.1.5.3 - RISER OR TREAD MAXIMUM DIFFERENTIAL SHALL BE NO MORE THAN 3/S" IRC SECTION 8311.1.5.1 - NOSING IS NOT REQUIRED FOR STAIRS WITH TREADS GREATER THAN 11". IRC SECTION 8311.1.5.3 FXTFRIOR STAIR NOTES: - EXTERIOR STAIR LIGHTING AT TOP LANDING WITH CONTROLS INSIDE THE DWELLING. IRC SECTION 8303.8 - A MAXIMUM SLOPE OF 1:48 (2%) IS REQUIRED AT EXTERIOR LANDINGS AND TREADS FOR DRAINAGE, IRC SECTION 8311.3 INTERIOR WINDER STAIR NOTES: - WINDER TREADS ARE REQUIRED TO HAVE A MINIMUM OF 6" DEPTH AT INNER EDGE, IRC SECTION R311.15.2.1 - WINDER TREAD DEPTH OF 10" WITH IN 12" OF THE INSIDE, IRC SECTION 8311.7.5.2.1 LAND ING NOTES: - LANDING WIDTH SHALL NOT BE LE55 THAN THAT OF STAIR SERVED IRC R311.7.6 - LANDING SHALL NOT BE LF55 THAN 36 INCHES IN DIRECTION OF TRAVEL SG R311,1.6 STAIR DETAIL SCALE: N.T.S. 8402.4.1.2 TESTING. THE BUILDING OR DWELLING UNIT SHALL BE TFSTFD AND VERIFIED AS HAVING AN AIR LEAKAGE RATE OF NOT EXCEEDING 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A BLOWER DOOR AT A PRESSURE OF 0.2 INCHES W.G. (50 PA5CAL5W). WHERE REQUIRED BY THE CODE OFFICIAL, TESTING SHALL BE CONDUCTED BY AN APPROVED THIRD PARTY. A WRITTEN REPORT OF THE RESULTS OF THE TEST SHALL BE SIGNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE CODE OFFICIAL. TESTING SHALL BE PERFORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF THE BUILDING THERMAL ENVELOPE. ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE R402.411), OPERABLE WINDOWS AND DOORS MANUFACTURED BY SMALL 5U51NF55 SHALL BE PERMITTED TO BE SEALED OFF AT THE FRAME PRIOR TO THE TEST. 2X4 BLOG<NG TYP. O2/2" HIGH 5/g" GWB TYPE "X" AT ALL SIDES WFATHFRSTRIPPFD TRU55 BOTTOM CHORD GWB TYPE "X" Sia G.W.B. TYPE "X" 22 x 30 ATTIC ACCESS OPENING ACCESS HATCH- CEILING INSULATE FULL DEPTH ATTIC ACCESS DETAIL SCALE: N.T.S. �7 z 0 Z LL > 0 m d CC) 1 /2 " HARDLUOOD HAND RA I L SOLID 5LOGKING AS REQUIRED PRE FINISH METAL BRAG<E7 TTP. T` f=. H,4NFD�R,4 f L 2015 WESG / R402.2.4 - ACCESS HATCHES AND DOORS, ACCESS DOORS FROM CONDITIONED SPACES TO UNCONDITIONED SPACES (E.G., ATTICS AND CRAWL SPACES) SHALL BE WEATHER5TRIPPED AND INSULATED TO A LEVEL EQUIVALENT TO THE INSULATION ON THE SURROUNDING SURFACES. ACCESS SHALL BE PROVIDED TO ALL EQUIPMENT THAT PRFVENT5 DAMAGING OR COMPRESSING THE INSULATION. A WOOD FRAMED OR EQUIVALENT BAFFLE OR RFTAINFR 15 REQUIRED TO BE PROVIDED WHEN L005F FILL INSULATION IS INSTALLED, THE PURPOSE OF WHICH IS TO PREVENT THE LOOSE FILL INSULATION FROM SPILLING INTO THE LIVING SPACE WHEN THE ATTIC ACCESS IS OPENED, AND TO PROVIDE A PERMANENT MEANS OF MAINTAINING THE INSTALLED R -VALUE OF THE LOOSE FILL INSULATION. PLEASE SHOW THE REQUIRED BAFFLE FRAMING AND INSULATION ATTACHED TO THE ACCESS LID, 3/4" T & G PLYWD WEATHER5TRIPPED SIDING PRODUCT 2X BLOCKING TYP. R-38 HD INSULATION IS" X 24" MIN CRAWL SPACE ACCESS FLOOR JOISTS AS PER PLAN C UJL SFACE ACCESS 1I E TA I L SGAL1=: N.T.S. OPTION WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWINr 5.5 ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION. /2" DRYWALL 2x STUDS 16" c/c —1/2 ° DRYWALL 2x4 CLEAT 6" O MIN. „z 0O 0 WATER O HEATER Cc) SEISMIC STRAPPING PER \ MANUFACTURERS 5PECIFICATIC (UPC, SEG .501.2) - SECURE SHAPED 2xIO SPACER TO 2x4 CLEATS WITH (5)-16d NAILS m SHAPED 2xIO SPACERS WILL BE CUT TO O INSURE A TIGHT FIT TO WATER HEATER WATER HEATER STRAPS WILL RESIST LATERAL FORCES EQUAL TO 100% OF GRAVITY LOADING PLATFORM MUST BE ANCHORED TO WALL FINISHED FLOOR TYi=IC:AL WATER HEATER DETAIL SCALE: N.T.S. W5EC 2018 8403.5.3 HOT WATER PIPE INSULATION (PRESCRIPTIVE) INSULATION FOR HOT WATER PIPE,BOTH WITHIN AND OUTSIDE THE CONDITIONED SPACE, SHALL HAVE A MINIMUM THERMAL RESISTANCE (R -VALUE) OF R-3 2018 UPC 312.6 FREEZING PROTECTION. NO WATER,501L,OR WASTE PIPE SHALL BE INSTALLED OR PERMITTED OUTSIDE OF A BUILDING, IN ATTICS OR CRAWL SPACE, OR IN AN EXTERIOR WALL UNLESS, WHERE NECESSARY, ADEQUATE PROVISION 15 MADE TO PROTECT SUCH PIPE FROM FREEZING. ALL HOT AND COLD WATER PIPES INSTALLED OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED TO A MINIMUM R-3 VENT FLUE UP THRU ROOF 1/2 ° DRYWALL 2x STUDS 16" c/c 2x4 CLEAT 2x4 CLEAT 4"4F SFT IT W/ FIL SECTION "A" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" TYPICAL ROOF CONSTRUCTION - CO1'1P05ITION ROOF SHINGLES - 1E�# ROOFINGx FELT COMPOSITION RC--"'" - H/fro" SIHEATIHING RATED 24/1(o 15" FELT PAPER - STRUCTURAL SYSTEM AS NOTED ON FRAMING PLAN 1/16" SHEATHING R-49 INSULATION ROOF FRAMING F GLU5 CEILING INSULATION BAFF 1/a" TO 1/4" MESH SCREEN OVER OPENINGS VENTED BLOCKY - MINIMUM NET F:FEE VENTILATINCx ARI=A SHALL 5E 1/150 5/4 x 8 FASCIA OF VENTED AREA SPACE OR 1/300 IF 40=�Oio CONTINUOUS MET; VENTING IN UPPER ATTIC OR RAFTER SPACE. PER IRC RaOro_2 - PROVIDI= 1" MINIMUM CLEARANCE 5E7 J€EN INSULATION R-10 RIGID INSUL AND SHIT-ATIHING AT VENTS PER IRC SECTION R000.3 TYPICAL WALL CONSTRUCTION - SIDING AND/OR VENEER PER ELEVATION - -1/10" PLY OR OS5 SIHTG.( U.N.O ) - TYVEK 5UILDING WRAP OR EQ. - 2Xro STUDS e fro" O.C. EXTERIOR WALLS U.N.O. EXTERIOR WALL NOTCH 2E i%, 5ORING 40% (oO% 50RING IF DOU5LED $ NOT MORE THAN TWO SUCCESSIVE STUDS. SEE NOTE ON SKEET 1 - 2x4 STUDS 'a) 10" O.C., INTEFIOR PARTITIONS (2X(o e PLU1"I5I1HCa WALLS) NON=FEARING WALL MAXIMUM NOTCH 40%, 5CRI1NG (oO% HOLES NO CLOSET, THE E�/8 INCH TO TACE OF STUD = R=21 INSULATION WITH VAPOR 5ARRIER 1/2" GW5. INTERIOR SHEATHING TYPICAL FLOOR CONSTRUCTION - 711NIS�1F=D FLOOR PEE, PLANS - 3/4" 74G PLYWOOD SU51FLOOR (GLUE AND NAIL) - F-LOOR JOISTS PER PLAN - R-30 INSULATION OVEF, UNH4EAT1-D AFEAS 2x6 STUDS 16" R-21 INSULATION 1/16" SHEATHING TYVFK WRAP - T' SIDING PER ELE� 3/4" TeG PLYWOOC FLOOR JOISTS P€ WINDOW HDR. PEf 5/4 TRIM 5URROU WINDOW W/ INS, GI 3/4" T8G PLYWOOC FLOOR JOISTS PE R-38 INSULATION 5/4 X 10 TRIM B/ 2X P.T. WOOD 51L 4" 4 GO TO STOI 4" 4 PF SFT IN I W/ FILTL. I �-,Y". TAL GUTTER ON 45CIA BD. TYP, 5 6 16 "o.c. 1LATION RR ELEVATIONS WRAP ON OR OSB SHEATHING, TYPICAL WALL 5ECTION w SUBFL i SUB FL SCALE : N.T.S. 7/1(o11 5HEATHING NOT REQUIRED ON EXT. WALLS WHERE T1=11 SIDING IS SPECIFIED (UNLESS NOTED OTHERW15E IN THE SMEAR WALL SPECIFICATIONS) N I N Lo O N omJ c c 0 70 a)U >+ i � � J 2 N +. i fA N� 0 0 N +• N N L Q ��-0 p+. U O O❑_ -0 �Q 70 oaco mi a� 0 C, 0 -cam V� ) o Q—,.—J Qct �U Na N ) cn Q N E ccoJ E cu co 0 o o w` c Q C O 1-1 J � c� N O o m 4— Q cz c � (D0u) c Fn aXi -a ❑ o-2oc0 En0E-�,mu, co E o zE cn H (Z d❑ a (z > Q J H Z J o 00 0% 0 N c� 70 o � � o M M 00 'V Q00 c1n N 00 N C0 N C0 ri - N LnC) of Z x � a REVISION DATE: INIT: PROJECT: DATE: 12/20/2021 INIT: 3 JAG< 4 �: PROJECT I DN. TO eRADE RIGHT ELEVATION SCALE: 1/4" =1'-0" LEFT ELEVATION I 11I yIVL � 1-1 � DN. TO GRADE SCALE: 1/4" =1'-0" TTER ON SD. TYF. 0R INA )NT. METAL # X S FASCI C S/4 x 4 Ci p v pNYTO GRADE REAR ELEVATION SCALE: 1/411 =1'-0" POST U1/ I x CEDAR TYP. DN. TO GRADE NOTE APPROVED NUM5ER5 OR ADDRESSES SHALL ISE PROVIDED AOR ALL NFW E3UILDING5 IN SUCI 4 A POSITION AS TO I f— P MINI 1 VISI�I AND �1�1 SROM TNS STP��T OP PO,4D FRONT ELEVATION ��° �N �I�I� � ��°�� K�.ADDRESS NJMI�ERS ARE REQJIRED TO 5E © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" - VER11-Y SHEAR WALL NAILING AND HOLDOWNS ARE PER PLAN AND SCb1=DJLE PRIOR TO INSTALLING SIDING MASONRY AND WOOD 7RA1 IE CkIMN)=YS AR€ TO 5E CONSTRUCTED PSR I.R.C. - PROVIDE GALVANIZED SKEET ME7,4L 7LASLIING AND COJNTERI-LASHING AT ALL F,OOF / WALL INTEFRSECTIONS, CbIMN]=YS, AND SKYLIGHTS - PROVIDE WZATLIZRSTRIPPING AND FLASHING AT ALL DOORS AND WINDOWS AS R1=QJIRI=D CAULK ALL EXTERIOR JOINTS AND PENETRATIONS - POST ADDRESS ON 5LDG, PRIOR TO FINAL INSPECTION - LCTS SLIALL E5F GRADED AS TO DRAIN SJRFACE UJATER AWAY FROM 7OUNDATION WALL. SLOPE SMALL 5E G " IN 1-1RS7 10 1-7, OR DRAINS OR SWALES SMALL BZ PROVIDED TO ENSURE DRAINAGE AWAY FROM STRUCTURE - PASTFNERS TO ISE NOT -DIPPED GALV. STEE-L, 5TAINLF,55 OR ALUM. (CORROSION RE-SISTANT) NOTE: PROVIDE CONTINUOS PRE -FAINTED G.I. IIEII FLASHING AT ALL EXT. DOOR S WINDOUJ LEADERS, R 5D, TYF. SAND 13D, TYP. N N Lo O N J c � � m o c m 0 i J C N +. i C O i fA N Otf ' N +. �c" - p+. U O O❑_ QQ O N N N 2 0 o , 0 Q=�J Qct cU N N 0 c �c� N E S J o�'2w2Ec _ J c O O Q c� c +� N� c� -0 ❑ ) O O(n O cn O cD N O c� N -i > J H (a ❑ ca Q H U L, o co 0% N c� 70 o � u � o MM M Q cc N 00 00 Ln N NLn ca M W N cn Z O x 40 a REVISION DATE: NIT: PROJECT: DATE: 12/20/2021 INIT: 4 JACK 4 PROJECT: 12/9/2021 SHEAR WALLSMARK CALLOUTTYPICAL SHEARWALL NOTESTYPICAL HOLDDOWN NOTES*TYPEDESCRIPTIONTYPICAL SHEARWALL NOTES12/9/2021 12/9/2021 12/9/2021 12/9/2021