Yelm Creek Estates Lot 11 Plan 2052-2 Final Stamped
GENERAL NOTES BUILDING CODE: 2018 INTERNATIONAL BLDG. CODE (IBC), AND BY REFERENCE WHERE APPLICABLE THE 2018 INTERNATIONAL RESIDENTIAL CODE (IRC) AS AMENDED BY LOCAL JURISDICTION. ROOF LIVE LOAD = 25 PSF (SNOW) ROOF DEAD LOAD = 15 PSF FLOOR LIVE LOAD = 40 PSF (REDUCIBLE) FLOOR DEAD LOAD = 15 F --'SF: WIND LOAD = 85 MPH WIND SPEED, EXPOSURE "B" WIND LOAD = 110 MPH WIND SPEED, EXPOSURE "B" PER IBC SOIL SITE CLASS "D" CONSTRUCTION T T f=E: VB OCCUPANCY GROUP: R-3 CONTRACTOR SHALL VERIFY ALL NOTES, DIMENSIONS 4 CONDITIONS PRIOR TO CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO IDENTIFY ALL OMISSIONS AND/OR DISCREPANCIES TO THE ARCHITECT PRIOR TO PROCEEDING WITH WORK, DIMENSIONS TAKE PRECEDENT OVER SCALED DRAWINGS, DEFERRED SUBMITTAL ITEMS THE FOLLOWING IS A LIST OF ITEMS THAT ARE NOT INCLUDED IN THIS PLAN AND SHOULD BE PROVIDED BY THE BUILDER AT TIME OF APPLICATION FOR PERMIT OR AS A DEFERRED SUBMITTAL ITEM: - ALTERNATIVE I-JOIST/BEAM MANUFACTURER PLANS. - MANUFACTURED TRUSS DESIGNS AND LAYOUTS - HVAC SYSTEMS DESIGN - ELECTRICAL PLANS 4 SPECIFICATIONS (IF REQUIRED) SITE WORK GENERAL UNLESS A SOILS INVESTIGATION Bl' A QUALIFIED SOILS ENGINEER IS PROVIDED, FOUNDATION DESIGN IS BASED ON AN ASSUMED AVERAGE SOIL BEARING OF 1500 PSF, EXTERIOR FOOTINGS SHALL BEAR 18" (MINIMUM) BELOW FINISHED GRADE. ALL FOOTINGS TO BEAR ON FIRM UNDISTURBED EARTH BELOW ORGANIC SURFACE SOILS. BACKFILL TO BE THOROUGHLY COMPACTED, BOLT HEADS AND NUTS BEARING AGAINST WOOD TO BE PROVIDED WITH 1/4"x3"x3" PLATE WASHERS. WOOD BEARING ON OR INSTALLED WITHIN V OF MASONRY OR CONCRETE TO BE PRESSURE TREATED WITH AN APPROVED PRESERVATIVE. FOUNDATION SILL BOLTS TO BE 5/S" DIAMETER AT GG' -O" O.C. U.N.O. WITH MIN. 1" EMBEDMENT METAL FRAMING CONNECTORS TO BE MANUFACTURED BY SIMPSON STRONG -TIE OR USP STRUCTURAL CONNECTORS INSULATION AND MOISTURE PROTECTION GENERAL MAINT,41N 1" CLEARANCE ABOVE INSULATION FOR FREE AIR FLOW. INSULATION BAFFLES TO EXTEND &" ABOVE BATT INSULATION INSULATION BAFFLES TO EXTEND 12" ABOVE LOOSE FILL INSULATION INSULATE BEHIND TUBS/SIHOUJERS, PARTITIONS AND CORNERS FACE -STAPLE FACED BATTS FRICTION -FIT UNF,4CED BATTS USE 4 MIL POL'T- VAPOR RETARDER AT EXTERIOR WALLS R-10 INSULATION UNDER ELECTRIC UJ,4TER HEATERS. INSULATION MATERIALS INSULATION MATERIAL, INCLUDING FACINGS, SUCH AS VAPOR RETARDERS OR VAPOR PERMEABLE MEMBRANES INSTALLED WITHIN FLOOR -CEILING ASSEMBLIES, ROOF -CEILING ASSEMBLIES, WALL ASSEMBLIES, CRAWL SPACES, AND ATTICS SHALL HAVE A FLAME -SPREAD INDEX NOT TO EXCEED 25 WITH AN ACCOMPANYING SMOKE -DEVELOPED INDEX NOT TO EXCEED 450 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 EXCEPT I ONS: I. WHEN SUCH MATERIAL ARE INSTALLED IN CONCEALED SPACES, THE FLAME -SPREAD AND SMOKE-DEVELOPEMENT LIMITATIONS DO NOT APPLY TO THE FACINGS, PROVIDED THAT THE FACING IS INSTALLED IN SUBSTANTIAL CONTACT WITH THE UNEXPOSED SURFACE OF THE CEILING, FLOOR, OR WALL FINISH. 2. CELLULOSE LOOSE -FILL INSULATION, WHICH IS NOT SPRAY APPLIED, COMPLYING WITH THE REQUIREMENTS OF IRC 8302.1.10.3, SHALL ONLY BE REQUIRED TO MEET THE SMOKE -DEVELOPED INDEX OF NOT MORE THAN 450. INFILTRATION CONTROL EXTERIOR JOINTS AROUND WINDOWS AND DOOR FRAMES, PENETRATIONS IN FLOORS, ROOFS AND WALLS AND ALL SIMILAR OPENINGS SHALL BE SEALED, CAULKED, GASKETED OR WEATHERSTRIPPED TO LIMIT AIR LEAKAGE. VAPOR 5ARRIER5 / GROUND COVERS AN APPROVED VAPOR BARRIER SHALL BE PROPERLY INSTALLED IN ROOF DECKS, IN ENCLOSED CEILING SPACES AND AT EXTERIOR WALLS. A GROUND COVER OF G MIL (0.00G") BLACK POLYETHYLENE OR EQUIVALENT SHALL BE LAID OVER THE GROUND IN ALL CRAWL SPACES. THE GROUND COVER SHALL BE OVERLAPPED ONE FOOT AT EACH JOINT AND SHALL EXTEND TO THE FOUNDATION WALL. W,4LL FL,45HINCx APPROVED CORROSION -RESISTANT FLASHING SHALL BE PROVIDED IN THE EXTERIOR WALL ENVELOPE IN SUCH A MANNER AS TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH AND SHALL BE INSTALLED TO PREVENT WATER FROM REENTERING THE EXTERIOR WALL ENVELOPE. APPROVED CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: I. AT TOP OF ALL EXTERIOR WINDOW AND DOOR OPENINGS IN SUCH A MANNER AS TO BE LEAKPROOF, EXCEPT THAT SELF -FLASHING WINDOWS HAVING A CONTINUOUS LAP OF NOT LESS THAN I -I/8" (28 mm) OVER THE SHEATHING MATERIAL AROUND THE PERIMETER OF THE OPENING, INCLUDING CORNERS, DOC NOT REQUIRE ADDITIONAL FLASHING± JAMB FLASHING MAY ALSO BE OMITTED WHEN SPECIFICALLY APPROVED BY THE BUILDING OFFICIAL. 2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH PROJECTING LIPS ON BOTH SIDES UNDER STUCCO OPENINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD, OR METAL COPINGS AND SILLS. 4. CONTINUOUSLY ABOVE ALLPROJECTING WOOD TRIM, 5. WHERE EXTERIOR PORCHES, DECKS, OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD CONSTRUCTION. 6, AT WALL AND ROOF INTERSECTIONS. 1. AT BUILT-IN GUTTERS, FOUNDATION WATERPROOFING $ DAMPROOFING DAMPROOF ING EXCEPT WHERE REQUIRED BY 2018 IRC 8406.2 TO BE WATERPROOFED, FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE DAMPROOFED FROM THE TOP OF THE FOOTING TO THE FINISHED GRADE. MASONRY WALLS SHALL HAVE NOT LASS THAN $' PORTLAND CEMENT PARGING APPLIED TO THE EXTERIOR OF THE WALL. PARGING SHALL BE DAMPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. 1. BITUMINOUS COATING 2.3 POUNDS PER SQ, YD, OF ACRYLIC MODIFIED CEMENT 3, 8" COAT OF SURFACE BONDING CEMENT COMPLYING WITH ASTN C SSl 4. ANY MATERIAL APPROVED FOR WATERPFOORING IN 2010 IRC R406.2 5. OTHER APPROVED METHODS OR MATERIALS. EXCEPTION: PARGING OF UNIT MASONRY WALLS IS NOT REQUIRED WHERE A MATERIAL IS APPROVED FOR DIRECT APPLICATION TO THE MASONRY. FOUNDATION WATERPROOFING 4 DAMPROOFING (CONTINUED) WATERPROOFING IN AREAS WHERE HIGH WATER TABLE OR OTHER SEVERE SOIL -WATER CONDITIONS ARE KNOWN TO EXIST, EXTERIOR FOUNDATION WALLS THAT RETAIN EARTH OR ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE WATERPROOFED FROM THE TOP OF FOOTING TO FINISHED GRADE. WALLS SHALL BE WATERPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING. I. 2 -PLY HOT MOPPED FELT 2, 55 POUND ROOF ROLLING 3, 6 -MIL POLYVINYL CHLORIDE 4. 6 -MIL POLYETHYLENE 5.40 -MIL POLYMER -MODIFIED ASPHALT 6. 60 -MIL FLEXIBLE POLYMER CEMENT 1. 8' GEMENT-BASED, FIBER -REINFORCED, WATERPROOF COATING 8. 60 -MIL SOLVANT-FREE, LIQUID -APPLIED SYNTHETIC RUBBER EXCEPTION: ORGANIC-SOLVANT-BASED PRODUCTS SUCH AS HYDROCARBONS, CHLORINATED HYDROCARBONS, KETONS AND ESTERS SHALL NOT BE USED FOR ICF WALLS WITH EXPANDED POLYSTYRENE FOAM MATERIAL. USE OF PLASTIC ROOFING CEMENTS, ACRYLIC COATINGS, LATEX COATINGS, MORTARS AND PARGINGS TO SEAL ICF WALLS IS PERMITTED, COLD -SETTING ASPHALT OR HOT ASPHALT SHALL CONFORM TO TYPE OF ASTM D 443. HOT ASPHALT SHALL BE APPLIED AT A TEMPERATURE OF LESS THAN 200 DEG. F. ALL JOINTS IN MEMBRANE WATERPROOFING SHALL BE LAPPED AND SEALED WITH AN ADHESIVE COMPATIBLE WITH THE MEMBRANE. DRAFTSTOPPING & FIRE BLOCKING DRAFT5TOPPING WHEN THERE IS USABLE SPACE BOTH ABOVE 4 BELOW THE CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLEY, DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DIRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE ABOVE d A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES: I. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2, FLOOR FRAMING IS CONSTRUCTED OF TRUSS -TYPE OPEN -WEB OR PERFORATED MEMBERS. DRAFTSTOPPING SHALL CONSIST OF MATERIALS LISTED IN 2018 IRC IR302J2 FIREBLOCKING FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO FORM AN EFFECTIVE BARRIER BETWEEN STORIES, AND BETWEEN A TOP STORY AND THE ROOF SPACE. FIREBLOCKING SHALL BE PROVIDED IN WOOD -FRAME CONSTRUCTION IN THE FOLLOWING LOCATIONS: 1. IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS AS FOLLOWS: I.I. VERTICALLY AT THE CEILING AND FLOOR LEVELS. 1.2. HORIZONTALLY AT INTERVALS NOT EXCEEDING 1OFt 2. AT ALL INTERCONNECTIONS BETWEEN CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR AT SOFFITS, DROP CEILINGS, AND COVE CEILINGS. 3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER STAIRS SHALL COMPLY WITH 2018 IRC 8302.1 4. AT OPENINGS AROUND VENTS, PIPES, AND DUCTS AT CEILING AND FLOOR LEVEL, WITH AN APPROVED MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND PRODUCTS OF COMBUSTION. 5. FOR THE FIIREBLOCKING OF CHIMNEYS AND FIREPLACES, SEE 2018 IRC R1003J,3. G. FIREBLOCKING OF CORNICES OF A TWO-FAMILY DWELLING IS REQUIRED AT THE LINE OF DWELLING UNIT SEPERATION, FIREBLOCKING SHALL CONSIST OF MATERIALS LISTED IN 2010 IRC SECTION R302.11.1.3 LOOSE -FILL INSULATION MATERIAL SHALL NOT BE USED AS A FIREBLOCK UNLESS SPECIFICALLY TESTED IN THE FORM AND MANNER INTENDED. THE INTEGRITY OF ALL FIREBLOCKS SHALL BE MAINTAINED. LIGHTING 2015 WSEC SECTION R404- LIGHTING EQUIPMENT R404.1 LIGHTING EQUIPMENT: NOT LESS THAN 90 PERCENT OF LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH EFFICACY LAMPS 8404.1.1 LIGHTING EQUIPMENT:FUEL GAS LIGHTING SYSTEMS SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. DRILLING AND NOTCHING STUDS. RG02.G DRILLING AND NOTCHING OF STUDS SHALL BE IN ACCORDANCE WITH THE FOLLOWING: I. NOTCHING. ANY STUD IN AN EXTERIOR WALL OR BEARING PARTITION SHALL BE PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH 2. DRILLING. ANY STUD SHALL BE PERMITTED TO BE BORED OR DRILL, PROVIDED THAT THE DIAMETER OF THE RESULTING HOLE IS NOT MORE THAN G0 PERCENT OF A SINGLE STUD WIDTH, THE EDGE OF THE HOLE IS NOT MORE THAN 5/0 INCH CIG mm) TO THE EDGE OF THE STUD, AND THE HOLE IS NOT LOCATED IN THE SAME SECTION AS A CUT OR NOTCH. STUDS LOCATED IN EXTERIOR WALLS OR BEARING PARTITIONS DRILLED OVER 40 PERCENT AND UP TO GO PERCENT SHALL BE DOUBLED WITH NOT MORE THAN TWO SUCCESSIVE DOUBLED STUDS BORED. SEE 2010 IRC FIGURES RG02.G(U AND RG02.G(2). -EXCEPTION: USE OF APPROVED STUD SHOES IS PERMITTED WHEN THEY ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. RG02.6.1 DRILLING AND NOTCHING OF TOP PLATE. WHERE PIPING OR DUCTWORK IS PLACED IN OR PARTLY IN AN EXTERIOR WALL OR INTERIOR LOAD-BEARING WALL, NECESSITATING CUTTING, DRILLING OR NOTCHING OF THE TOP PLATE BY MORE THAN 50 PERCENT OF ITS WIDTH, A GALVANIZED METAL TIE OF NOT LESS THAN 0.054 INCH THICK (1.31 mm) CIG ea) AND 111/2 INCHES (30 mm) WIDE SHALL BE FASTENED ACROSS AND TO THE PLATE AT EACH SIDE OF THE OPENING WITH NOT LESS THAN EIGHT 10d (0.148 INCH DIAMETER) NAILS HAVING A MINIMUM LENGTH OF 1 1/2 INCHES (38 MM) AT EACH SIDE OR EQUIVALENT. THE METAL TIE MUST EXTEND NOT LESS THAN 6 INCHES PAST THE OPENING. SEE 2010 IRC FIGURE RG02.G.1. -EXCEPTION: WHERE THE ENTIRE SIDE OF THE WALL WITH THE NOTCH OR CUT IS COVERED BY WOOD STRUCTURAL PANEL SHEATHING. DOORS, WINDOWS AND SKYLIGHTS GENERAL ALL SKYLIGHTS AND SKY WALLS TO BE LAMINATED GLASS UNLESS NOTED OTHERWISE. BEDROOM EMERGENCY EGRESS WINDOWS SHALL HAVE MINIMUM NET CLEAR OPENING OF 5.1 SQ. FT WITH MINIMUM NET CLEAR OPENING WIDTH OF 20" AND MINIMUM NET CLEAR OPENING HEIGHT OF 24" FINISHED SILL HEIGHT SHALL BE MAXIMUM 44' ABOVE FLOOR, MEASURED FROM THE FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING WINDOW FLASHING TO BE FASTENED PER 2016 IRC R103.4 WINDOW GUARDS ARE REQUIRED PER 2018 IRC R312.1 SAFETY GLAZING SHALL BE INSTALLED IN THE FOLLOWING LOCATIONS OR AS OTHERWISE REQUIRED PER 2018 IRC R300.4.3 SIDE HINGED DOORS EXCEPT JALOUSIES SLIDING GLASS DOORS AND PANELS IN SLIDING 4 BI -FOLD CLOSET DOOR ASSEMBLIES OF A DOOR IN THE CLOSED POSITION 4 BOTTOM EDGE IS LESS THAN /o0" ABOVE 1. SIHOUJER AND BATH TUB, HOT TUB, UJIHIRLPOOL, SAUNA, STEAM ENCLOSURES 2. GLAZING W/ THE EXPOSED EDGE WITHIN A 24" ARC OF EITHER VERTICAL EDGE 3, STORM DOORS 4 THE W,4LKING SURFACE 5, GLAZING GREATER THAN 9 S.F. AND LESS THAN 18" ABOVE FINISHED FLOOR 0 GLAZING IN GUARDRAILS �- GLAZING LESS THAN 18" ABOVE FINISHED FLOOR 8. STAIRS AND RAMPS ADJACENT WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 3G" ABOVE THE PLANE OF ADJACENT WALKWAY SURFACE OF STAIRWAYS LANDINGS BETWEEN FLIGHTS OF STAIRS AND RAMPS SHALL BE CONSIDER A HAZARDOUS LOCATION. PER 2010 IRC R300.4.G MECHANICA HEATING EQUIPMENT MECHANICAL HEATING EQUIPMENT ALL WARM -AIR FURNACES SHALL BE LISTED AND LABELED BY AN APPROVED AGENCY AND INSTALLED TO LISTED SPECIFICATIONS. NO WARM -AIR FURNACES SHALL BE INSTALLED IN A ROOM USED OR DESIGNED TO BE USED AS A BEDROOM, BATHROOM, CLOSET OR IN ANY ENCLOSED SPACE WITH ACCESS ONLY THROUGH SUCH ROOM OR SPACE, EXCEPT DIRECT VENT FURNACE, ENCLOSED FURNACES AND ELECTRIC HEATING FURNACES, LIQUIFIED PETROLEUM GAS -BURNING APPLIANCES SHALL NOT BE INSTALLED IN A PIT, BASEMENT OR SIMILAR LOCATION WHERE HEAVIER THAN AIR GAS MIGHT COLLECT. APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH AN APPROVED MEANS FOR REMOVAL OF UNBURNED GAS. HEATING AND COOLING EQUIPMENT LOCATED IN A GARAGE WHICH GENERATES A GLOW, SPARK OR FLAME CAPABLE OF IGNITING FLAMMABLE VAPORS SHALL BE INSTALLED WITH THE PILOTS AND BURNERS FOR HEATING ELEMENTS AND SWITCHES AT LEAST 10" ABOVE THE FLOOR LEVEL. TEMPERATUERE CONTROL THE PRIMARY SPACE CONDITIONING SYSTEM WITHIN EACH DWELLING UNIT SHALL BE PROVIDED WITH AT LEAST ONE PROGRAMMABLE THERMOSTAT FOR THE REGULATION OF TEMPERATURE WSEC 5EC.403.1.1 VENTILATION EVERY FACTORY BUILT CHIMNEY, TYPE L VENT, TYPE B GAS VENT OR TYPE BW GAS VENT SHALL BE INSTALLED IN ACCORDANCE WITH THE TERMS OF ITS LISTING, MFR'S INSTALLATION INSTRUCTIONS AND APPLICABLE CODE REQUIREMENTS. A TYPE L VENTING SYSTEM SHALL TERMINATE NOT LESS THAN 2 FEET ABOVE THE HIGHEST POINT WHERE THE VENT PASSES THROUGH THE ROOF OF THE BUILDING AND AT LEAST 2' HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10' OF THE VENT. INTEGRATED WHOLE HOUSE VENT SYSTEM INTEGRATED 24 HR WIHOLE HOUSE VENTILATION SYSTEM. * USING A SUPPLY FAN W/ MANUAL 4 MOTORIZED DAMPER. * FAN TIMER EXTERNALLY LOCATED ON THE SIDE OF FURNACE OR GARAGE WALL 220 CFM REQUIRED W/ A RUN TIME OF 0 NRS. MIN. FAN MUST OPERATE AT LEAST ONCE EVERY THREE HOURS SO VENTILATION EFFECTIVENESS CAN BE 1.0 * S" SMOOTH WALL PIPE (OPERATION DESCRIPTION TO BE PROVIDED PER M1505.4) SYSTEM TO BE TESTED AT FINAL INSPECTION 4 LABELED BUILDING AIR LEAKAGE TESTING 2018 W5EC 8402.4.1.2 TESTING SHALL OCCUR AT ANY TIME AFTER ROUGH IN AND AFTER INSTALLATION OF PENETRATIONS OF THE BUILDING ENVELOPE. WHEN REQUIRED BY THE BUILDING OFFICIAL, THE TEST SHALL BE CONDUCTED IN THE PRESENCE OF DEPARTMENT STAFF. THE BLOWER DOOR TEST RESULTS SHALL BE RECORDED ON THE CERTIFICATE REQUIRED PER WSEC 8401.3 201a WASHINGTON STATE ENERGY CODE - TABLE 402.1.1 INSULATION AND FENESTRATION REQUIRMENT BY COMPONET CLIMATE ZONE 5 4 MARINE 4 - HEATING BY OTHER FUELS FENESTRATION U -FACTOR CEILING WALL ABOVE GRADE WALL BELOW GRADE MASS WALL FLOOR SLAB ON GRADE VERTICAL OVERHEAD 0.25 0.50 R -4S R-21 R-10/15/21 R -21/21H R-38 R-10 105 3001-4500 60 15 TB 105 120 2' UTILITY ROOM NOTES/MAKE UP AIR: I. WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING CONSTRUCTION, THE EQUIVALENT LENGTH OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG, THE LABEL OR TAG SHALL BE LOCATED WITHIN G FEET OF THE EXHAUST DUCT CONNECTION. 2. INSTALLATIONS EXHAUSTING MORE THAN 200 CFM CHALL BE PROVIDED WITH MAKE UP AIR WHERE A CLOSET IS DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN OPENING HAVING AN AREA OF NOT LESS THAN 100 SQ. INCHES FOR MAKE UP AIR SHALL BE PROVIDED IN THE CLOSET ENCLOSURE, OR MAKE UP AIR SHALL BE PROVEDED BY OTHER APPR. MEANS. 100 SQ INCH TRANSFER GRILL PER IRC G243S.4 0014.(o) M1505.4.3 MECHANICAL VENTILATION RATE. THE WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM SHALL PROVIDE OUTDOOR AIR ATA CONTINUOUS RATE AS DETERMINED IN ACCORDANCE WITH TABLE M1506.4.3(1) OR EQUATION 15-1, EQUATION 15-1 VENTILATION RATE IN CUBIC FEET PER MINUTE = (0.01 X TOTAL SQUARE FOOT AREA OF HOUSE) + 3/47.5 X(NUMBER OF BEDROOMS + IAa BUT NOT LESS THAN 30 CFM FOR EACH DWELLING UNIT CONTINUOUS WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM AIRFLOW RATE REQUIREMENTS DWELLING UNIT FLOOR AREA (50, FT> 0-I 2-3 NUMBER OF BEDROOMS 4-5 AIRFLOW IN CFM 6-1 <1 < 1500 30 45 (00 15 w 1501-3000 45 60 15 90 105 3001-4500 60 15 90 105 120 4501 - 6000 15 90 105 120 135 6001 - 1500 90 1 105 1 120 135 150 > 1500 105 1 120 1 135 1 150 165 INTERMITTENT WHOLE -HOUSE MECHANICAL VENTILATION RATE FACTORS RUN-TIME q IN EACH 4 -HOUR SEGMENT 25% 33% 50% 66% 15% 100 e FACTOR 4 3 2 1.5 13 1.0 MINIMUM R;znlllRFf) F)eWAII5T RATFS AREA TO BE VENTED EXHAUST RATES KITCHENS 100 CFM INTERMITTENT OR 25 CFM CONTIMUOUSLY BATHROOM / LAUNDRY / SIMILAR 50 CFM INTERMITTENT OR AREAS 20 CFM CONTIMUOUSLY BALANCED WHOLE HOUSE VENTILATION. BALANCED WHOLE HOUSE VENTILATION IS DEFINED AS ANY COMBINATION OF CONCURRENTLY OPERATING RESIDENTIAL UNIT MECHANICAL EXHAUST AND MECHANICAL SUPPLY WHEREBY THE TOTAL MECHANICAL EXHAUST AIRFLOW RATE IS WITHIN 10 PERCENT OR 5 CFM, WHICHEVER IS GREATER, OF THE TOTAL MECHANICAL SUPPLY AIRFLOW RATE. INTERMITTENT DRYER EXHAUST, INTERMITTENT RANGE HOOD EXHAUST, AND INTERMITTENT TOILET ROOM EXHAUST AIRFLOW RATES ABOVE THE RESIDENTIAL DWELLING OR SLEEPING UNIT MINIMUM VENTILATION RATE ARE EXEMPT FROM THE BALANCED AIRFLOW CALCULATION. POSTING OF CERTIFICATE 2018 WSEC 8401.3 CERTIFICATE. A PERMANENT CERTIFICATE SHALL BE COMPLETED BY THE BUILDER OR OTHER APPROVED PARTY AND POSTED ON A WALL IN THE SPACE WHERE THE FURNACE IS LOCATED, A UTILITY ROOM, OR AN APPROVED LOCATION INSIDE THE BUILDING. WHEN LOCATED ON AN ELECTRICAL PANEL, THE CERTIFICATE SHALL NOT COVER OR OBSTRUCT THE VISIBILITY OF THE CIRCUIT DIRECTORY LABEL, SERVICE DISCONNECT LABEL, OR OTHER REQUIRED LABELS. THE CERTIFICATE SHALL LIST THE PREDOMINANT R -VALUES OF INSULATION INSTALLED IN OR ON CEILING/ROOF, WALLS, FOUNDATION (SLAB, BELOW -GRADE WALL, AND/OR FLOOR) AND DUCTS OUTSIDE CONDITIONED SPACES U -FACTORS FOR FENESTRATION AND THE SOLAR HEAT GAIN COEFFICIENT (SHGC) OF FENESTRATION: THE RESULTS FROM ANY REQUIRED DUCT SYSTEM AND BUILDING ENVELOPE AIR LEAKAGE TESTING DONE ON THE BUILDING: AND THE RESULTS FROM THE WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FLOW RATE TEST. WHERE THERE IS MORE THAN ONE VALUE FOR EACH COMPONENT, THE CERTIFICATE SHALL LIST THE VALUE COVERING THE LARGEST AREA. THE CERTIFICATE SHALL LIST THE TYPES AND EFFICIENCIES OF HEATING, COOLING, WHOLEHOUSE MECHANICAL VENTILATION, AN SERVICE WATER HEATING APPLIANCES. WHERE A GAS-FIRED UNV NTED ROOM HEATER, ELECTRIC FURNACE, OR BASEBOARD ELECTRIC HEATER IS INSTALLED IN THE RESIDENCE, THE CERTIFICATE SHALL LIST 'GAS-FIRED UNvENTED ROOM HEATER,' "ELECTRIC FURNACE' OR "BASEBOARD ELECTRIC HEATER,' AS APPROPRIATE. AN EFFICIENCY SHALL NOT BE LISTED FOR GAS-FIRED UNvENTED ROOM HEATERS, ELECTRIC FURNACES OR ELECTRIC BASEBOARD HEATERS THE CODE OFFICIAL MAY REQUIRE THAT DOCUMENTATION FOR ANY REQUIRED TEST RESULTS INCLUDE AN ELECTRONIC RECORD OF THE TIME, DATE AND LOCATION OF THE TEST. A DATE STAMPED SMART PHONE PHOTO OR AIR LEAKAGE TESTING SOFTWARE MAY BE USED TO SATISFIED THIS REQUIREMENT. 2018 WASHINGTON STATE ENERGY CREDIT -TABLE R40(o.3 ENERGY CREDITS CREDITI OPTION I DESCRIPTION PRESCRIPTIVE COMPLIANCE IS BASED ON TABLE R402.1.1 WITH THE FOLLOWING MODIFICATIONS: VERTICAL FENESTRATION U = 0.20 FLOOR R-38 0.5 1.3 SLAB ON GRADE R-10 PERIMETER AND UNDER ENTIRE SLAB BELOW GRAPE SLAB R-10 PERIMETER AND UNDER ENTIRE SLAB OR COMPLIANCE BASED ON SECTION R402.1.4: REDUCE THE TOTAL CONDUCTIVE UA BY 5%. COMPLIANCE BASED ON R402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 3.0 AIR CHANGES PER HOUR MAXIMUM AT 50 PASCALS OR FOR R-2 OCCUPANCIES, OPTIONAL COMPLIANCE BASED ON SECTION 8402.4.1.2: REDUCE THE TESTED AIR LEAKAGE TO 0.3 CFM/FT2 MAXIMUM AT 50 PASCALS AND ALL WHOLE HOUSE VENTILATION REQUIREMENTS AS DETERMINED BY SECTION 0.5 2.1 M1501.3 OF THE INTERNATIONAL RESIDENTIAL CODE OR SECTION 403.6 OF THE INTERNATIONAL MECHANICAL CODE SHALL BE MET WITH A HIGH EFFICIENCY FAN(S) (MAXIMUM 0.35 WATTS/CFM), NOT INTERLOCKED WITH THE FURNACE FAN (IF PRESENT). VENTILATION SYSTEMS USING A FURNACE INCLUDING AN ECM MOTOR ARE ALLOWED, PROVIDED THAT THEY ARE CONTROLLED TO OPERATE AT LOW SPEED IN VENTILATION ONLY MODE. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED, THE MAXIMUM TESTED BUILDING AIR LEAKAGE, AND SHALL SHOW THE QUALIFYING VENTILATION SYSTEM AND ITS CONTROL SEQUENCE OF OPERATION. AIR -SOURCE CENTRALLY DUCTED HEAT PUMP WITH MINIMUM HSPF OF S.5, 1.0 3.2 TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE HEATING EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL SUPPLY AND RETURN DUCTS LOCATED IN AN UNCONDITIONED ATTIC SHALL BE DEEPLY BURIED IN CEILING INSULATION IN ACCORDANCE WITH SECTION 8403.3.1. FOR MECHANICAL EQUIPMENT LOCATED OUTSIDE THE CONDITIONED SPACE, A MAXIMUM OF 10 LINEAR FEET OF RETURN DUCT AND 5 LINEAR FEET OF SUPPLY DUCT CONNECTIONS TO THE EQUIPMENT MAY BE OUTSIDE THE DEEPLY BURIED INSULATION. 0.5 4,1 ALL METALLIC DUCTS LOCATED OUTSIDE THE CONDITIONED SPACE MUST HAVE BOTH TRANSVERSE AND LONGITUDINAL JOINTS SEALED WITH MASTIC. IF FLEX DUCTS ARE USED, THEY CANNOT CONTAIN SPLICES. DUCT LEAKAGE SHALL BE LIMITED TO 3 CFM PER 100 SQUARE FEET OF CONDITIONED FLOOR AREA. AIR HANDLERS) SHALL BE LOCATED WITHIN THE CONDITIONED SPACE, WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWING: ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION OR FOR R-2 OCCUPANCY, ELECTRIC HEAT PUMP WATER HEATER(S), MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION, SHALL 2.0 5.5 SUPPLY DOMESTIC HOT WATER TO ALL UNITS. IF ONE WATER HEATER IS SERVING MORE THAN ONE DWELLING UNIT, ALL HOT WATER SUPPLY AND RECIRCULATION PIPING SHALL BE INSULATED WITH R-0 MINIMUM PIPE INSULATION. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SPECIFY THE WATER HEATER EQUIPMENT TYPE AND THE MINIMUM EQUIPMENT EFFICIENCY. ALL OF THE FOLLOWING APPLIANCES SHALL BE NEW AND INSTALLED IN THE DWELLING UNIT AND SHALL MEET THE FOLLOWING STANDARDS: DISHWASHER -ENERGY STAR RATED REFRIGERATOR (IF PROVIDED) -ENERGY STAR RATED WASHING MACHINE -ENERGY STAR RATED 0.5 1.1 DRYER -ENERGY STAR RATED, vENTLESS DRYER WITH A MINIMUM CEF RATING OF 5.2. TO QUALIFY TO CLAIM THIS CREDIT, THE BUILDING PERMIT DRAWINGS SHALL SPECIFY THE OPTION BEING SELECTED AND SHALL SHOW THE APPLIANCE TYPE AND PROVIDE DOCUMENTATION OF ENERGY STAR COMPLIANCE. AT THE TIME OF INSPECTION, ALL APPLIANCES SHALL BE INSTALLED AND CONNECTED TO UTILITIES. DRYER DUCTS AND EXTERIOR DRYER VENT CAPS ARE NOT PERMITTED TO BE INSTALLED IN THE DWELLING UNIT, SYSTEM TABLE 8406.2 TYPE FUEL NORMALIZATION CREDITS FOR AN INITIAL HEATING SYSTEM USING A HEAT PUMP THAT MEETS FEDERAL STANDARDS FOR THE EQUIPMENT 10 2 LISTED IN TABLE C403.3.2(I)C. OR C403.3.2(2) OR AIR TO WATER HEAT PUMP UNITS THAT ARE CONFIGURED TO PROVIDE BOTH HEATING AND COOLING AND ARE RATED IN ACCORDANCE WITH AHRI 550/550 6.0 1 TOTAL: 0 r rmJ J J J O Lu rm r 0 N 0 < UJ 0 N 0 N LO 0 co 0 41 N uj co J J >= C6 c: U (� J 0LNNQ o C C W L� Q- •9) n� `� -a M o�-0 (a > o� 0 J Q� ca ) U ("D�,�,.o cn 3 i a) Q - OL cr�ami0coCD a0 o 0 o cn cis CU J c Ecn c U O c ++J a_ CIS aa) J N C o l 0 Q (c$L X Cl ca a) W o W a)70 i o� aai�>.�no`n>. H co +�. .t-0(Da) (� Q J H +�. J U - Ln o 00 o. 0 .Qi 70 E - u z c a;M Q 000 N E M In :2 N cn O �D d REVISION DATE: INIT: PROJECT: DATE: 12-21-2021 INIT: 4 PROJECT . *NOTE* BUILDING AIR LEAKAGE TEST REQUIRED AS PER 2018 WSEC 8402.4.1.2 DUCTS -DUCTS SHALL BE LEAK TESTED IN ACCORDANCE WITH WSU R5-33 PER 2015 WSEC 8403.3.3 -DUCTS, AIR HANDLERS, FILTER BOXES SHALL BE SEALED AS PER M160L4.1-R403.3.2J 2015 WSEC 2015 IRC 8311.3 FLOOR AND LANDINGS AT EXTERIOR DOORS. THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT LESS THAN THE DOOR SERVED. LANDING SHALL HAVE A DIMENSION OF NOT LESS THAN 36" (914MM) MEASURED IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR LANDING SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS HORIZONTAL (2 PERCENT) *DRYER VENT* 2015 IRC M1502.4.6 LENGTH IDENTIFICATION. WHERE THE EXHAUST DUCT EQUIVALENT LENGTH EXCEEDS 35 FEET (10 (o65 MM), THE EQUIVALENT LENGTH OF THE EXHAUST DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG, THE LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEE (1829 MM) OF THE EXHAUST DUCT CONNECTION 2015 IRC R 303.7 INTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE TO ILLUMINATE THE LANDINGS AND TREADS. THE LIGHT SOURCE SHALL BE CAPABLE OF ILLUMINATING TREADS AND LANDINGS TO LEVEL OF NOT LESS THAN 1 FOOT-CANDLE (11 LUX) AS MEASURED AT THE CENTER OF TREADS AND LANDINGS. THERE SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL TO CONTROL THE LIGHT SOURCE WHERE THE STAIRWAY HAS SIX OR MORE RISERS, 2015 IRC R 311.1.9 ILLUMINATION STAIRWAY SHALL BE PROVIDED WITH IN ACCORDANCE WITH SECTION 8303.7 4 8303.5 LIl 8302.5 DWELLING -GARAGE OPENING AND PENETRATION PROTECTION, OPENINGS AND PENETRATIONS THROUGH THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE IN ACCORDANCE WITH SECTIONS 8302.5.1 THROUGH 8302.5.3. 8302.5.1 OPENING PROTECTION. OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 $ INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB -CORE STEEL DOORS NOT LESS THAN 1 a INCHES (35 MM) THICK, OR 20-MINU7E FIRE -RATED DOORS, EQUIPPED WITH A SELF-CLOSING DEVICE. 8302.5.2 DUCT PENETRATION. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO, 26 GAGE (0.45 MM) SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL NOT HAVE OPENINGS INTO THE GARAGE. 8302.5.3 OTHER PENETRATIONS. PENETRATIONS THROUGH THE SEPARATION REQUIRED IN SECTION 8302.6 SHALL BE PROTECTED AS REQUIRED BY SECTION 8302.11, ITEM 4 8302.6 DWELLING -GARAGE FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE 8302.6 OPENINGS IN GARAGE WALLS SHALL COMPLY WITH SECTION 8302.5 ATTACHMENT OF GYPSUM BOARD SHALL COMPLY WITH TABLE 8702.3.5. THE WALL SEPARATION PROVISIONS OF TABLE R302.6 SHALL NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR THE THE ADJACENT DWELLING UNIT WALL. 8302.7 UNDER -STAIR PROTECTION. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER -STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH z INCH (12.7 MM) GYPSUM BOARD, DROOM 3 E] 10'-6 "X11' - PLE,45E REFER TO 5HEET 1/4 FOR ENERGY CREDIT FROF05ED UNDER THE 2010 WA5HINGTON 5TATE ENERGY CREDIT-T,45LE 8406.3 EGRESS D401 XO 304015H co 110V \ OS® Nr DOWN 168 LE 15AE LOFT X � 2 2'-V I II I 5'-0" 2'-10" 2'-4" 4'-4" 15'-2" 41-41121-611 3 _On 36'-0" 1CI UPPER FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/411 =1'-0" PROVIDE FIRE5LOCKING AS REQUIRED (SEE NOTES ON SHEET 1) UJINDOLU HEADERS AT (0'-8" 45OVE SUIS FLOOR, U.N.O. EXTERIOR LUALL-S TO E�)E 2Xro AT lro" O.C., UN.O. INTERIOR PARTITIONS TO E3E 2X4 AT 1G'' O.C. (2XG � PLUM5ING-� UUALLS) U.N.O. PROVIDE SUPP 1=MI=NTA1 JOIST5/5LOCKINC 5ELCLU SHEAR UJALL5 AS INDICATED ON FRAMING FLAN PROVIDE SOLID FRAMING EQUAL TO THE UJIDTIH OF THE MENDER 5EING SUPPORTED SMOKE DETECTORS VENTILATION REQUIREMENTS OF IRC T,45LE M1505.4.4 NSTAL L SMIO E DETECTC)F=S WHERE IND ICATEE) oSD ALL SMOK1= DETECTOR RECEIVE THERE FCUJFR FROM THE PRIMARY APPLIED TO THE GARAGE SIDE AND INTEFTc°_ONNECTED PER 8314.4 4 FT��14.G CARBON MONOXIDE ALARMS 1 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 25 CFM CONTINUOUS FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND, 5ATHROOMS/TOILET ROOMS/ WHERE PRIMARY POWER IS INTERRUPED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL O C/M BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH, OTHER THAN THOSE REQUIRED FOR OF E�O CFM INTERMITTENT OR 20 OVERCURRENT PROTECTION. ENTRY PORCH: EXCEPTIONS: SF. L CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED WHERE 120 INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER. J SG �e V ^J+ (>D C NV J 2 E C 3c: N 0) p+. U O L O QQ 4040 XO f_A U�-0 ca- 5040 XO U a> Q= R/S ci c U a)N -Oi EGRESS cn (1) o 2 c6 �} � m _ca � J W w- 4c:X O O a 0 O � N U Q N "X 3 6 "X60" -� w O H c0 a- o ca > Q J H +. J U S a_ SOAK TUB — o 00 a. : IIIIII 2465 W.I. III* I t OUJNE01 5A I 70 " i 0 . ii M M co I a0rn0 N 12'-0"X9'-0" 00 E M 00 Ln Y f'V N M W Ln N cn O = .c a REVISION DATE: NIT: PROJECT #: OWN '5 SUITE C' - AV L 4V O 14'-O"X15'-0" DATE: 5' 6 NIT: 2 JACK 4 F= HE PROJECT: E O 2(VT)O) `v 'R� � 1/z "7 I I-rII Its fl�� LIl 8302.5 DWELLING -GARAGE OPENING AND PENETRATION PROTECTION, OPENINGS AND PENETRATIONS THROUGH THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE IN ACCORDANCE WITH SECTIONS 8302.5.1 THROUGH 8302.5.3. 8302.5.1 OPENING PROTECTION. OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 $ INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB -CORE STEEL DOORS NOT LESS THAN 1 a INCHES (35 MM) THICK, OR 20-MINU7E FIRE -RATED DOORS, EQUIPPED WITH A SELF-CLOSING DEVICE. 8302.5.2 DUCT PENETRATION. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO, 26 GAGE (0.45 MM) SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL NOT HAVE OPENINGS INTO THE GARAGE. 8302.5.3 OTHER PENETRATIONS. PENETRATIONS THROUGH THE SEPARATION REQUIRED IN SECTION 8302.6 SHALL BE PROTECTED AS REQUIRED BY SECTION 8302.11, ITEM 4 8302.6 DWELLING -GARAGE FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE 8302.6 OPENINGS IN GARAGE WALLS SHALL COMPLY WITH SECTION 8302.5 ATTACHMENT OF GYPSUM BOARD SHALL COMPLY WITH TABLE 8702.3.5. THE WALL SEPARATION PROVISIONS OF TABLE R302.6 SHALL NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR THE THE ADJACENT DWELLING UNIT WALL. 8302.7 UNDER -STAIR PROTECTION. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER -STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH z INCH (12.7 MM) GYPSUM BOARD, DROOM 3 E] 10'-6 "X11' - PLE,45E REFER TO 5HEET 1/4 FOR ENERGY CREDIT FROF05ED UNDER THE 2010 WA5HINGTON 5TATE ENERGY CREDIT-T,45LE 8406.3 EGRESS D401 XO 304015H co 110V \ OS® Nr DOWN 168 LE 15AE LOFT X � 2 2'-V I II I 5'-0" 2'-10" 2'-4" 4'-4" 15'-2" 41-41121-611 3 _On 36'-0" 1CI UPPER FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/411 =1'-0" PROVIDE FIRE5LOCKING AS REQUIRED (SEE NOTES ON SHEET 1) UJINDOLU HEADERS AT (0'-8" 45OVE SUIS FLOOR, U.N.O. EXTERIOR LUALL-S TO E�)E 2Xro AT lro" O.C., UN.O. INTERIOR PARTITIONS TO E3E 2X4 AT 1G'' O.C. (2XG � PLUM5ING-� UUALLS) U.N.O. PROVIDE SUPP 1=MI=NTA1 JOIST5/5LOCKINC 5ELCLU SHEAR UJALL5 AS INDICATED ON FRAMING FLAN PROVIDE SOLID FRAMING EQUAL TO THE UJIDTIH OF THE MENDER 5EING SUPPORTED SMOKE DETECTORS VENTILATION REQUIREMENTS OF IRC T,45LE M1505.4.4 NSTAL L SMIO E DETECTC)F=S WHERE IND ICATEE) oSD ALL SMOK1= DETECTOR RECEIVE THERE FCUJFR FROM THE PRIMARY APPLIED TO THE GARAGE SIDE AND INTEFTc°_ONNECTED PER 8314.4 4 FT��14.G CARBON MONOXIDE ALARMS 1 8315.5 POWER SOURCE, CARBON MONOXIDE ALARMS SHALL RECEIVE THEIR PRIMARY POWER 25 CFM CONTINUOUS FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND, 5ATHROOMS/TOILET ROOMS/ WHERE PRIMARY POWER IS INTERRUPED, SHALL RECEIVE POWER FROM A BATTERY. WIRING SHALL O C/M BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH, OTHER THAN THOSE REQUIRED FOR OF E�O CFM INTERMITTENT OR 20 OVERCURRENT PROTECTION. ENTRY PORCH: EXCEPTIONS: SF. L CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED WHERE 120 INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER. VENTILATION SCHEDULE VENTILATION REQUIREMENTS OF IRC T,45LE M1505.4.4 E Y 50L NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT EXHAUST RATES APPLIED TO THE GARAGE SIDE KITCHENS (V -T.0) 100 CFM INTERMITTENT OR 1 UPPER FLCOF, 25 CFM CONTINUOUS SF. 5ATHROOMS/TOILET ROOMS/ 1" FCHANICAL EXHAUST CAPACITY 2 LAUNDRY ROOM (V.T.0) OF E�O CFM INTERMITTENT OR 20 SF. ENTRY PORCH: CFM CONTINUOUS VENTILATION RATE FOR WHOLE HOUSE FAN TO 5E -15 CFM PER T,45LE M1E0E.4.3(1) INDOOR AIR QUALITY HVAC CONTRACTOR TO SPECIFY LOCATION, 1 12'-0° AREA SUMMARY MATERIAL NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM THE RESIDENCE AND ATTICS APPLIED TO THE GARAGE SIDE MAIN FI -00R: 8,49 S7. UPPER FLCOF, 1203 SF. TOTAL-: 2082 SF. GARAGE: 37C SF. ENTRY PORCH: F:; I F:; I SF. PATIO: 120 SF. MAIN FLOOR PLAN © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" - ALL DOOR/UJINDOLU HEADERS TO 5E_ 4x10 DF*12 AT 2x& 5EARING WALLS , U.N.O., (o' -O" MAX. SPAN - ALL DOOR/LUINDOUJ IHEADI=RS TO 5E 4X10 DF#2 AT 2x4 SEARING UJAL L5, U.N.O., ro'-0" MAX. SPAN UJINDOUJ HEADERS AT ABOVE 5UE3 FLOOR, U.N.O. PROVIDE FIFFE3L OCKING AS RFQL2 IRED (51=E NOTES ON SHEET 1) EXTERIOR WALLS TO 5E 2X& AT 16" (MAX.) O.C. U.N.O. NTERIOR PARTITIONS TO SE 2x4 AT lro" O.C. (2Xro �@ PL-UMI5ING UJAL-L-S, UN.O.) - DUCTS THROUGH UUALL OR CEILING COMMON TO HOUSE 1MIN, 2(o GAGE STEEL PROVIDE SOL15 FRAMING EQUAL- TO THE UJIDTH OF THE MEM5ER 5EING SUPPORTED (UN -C.) TABLE 302.6 [)WELL ING -GARAGR SEPARATION SEPARATION MATERIAL NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM THE RESIDENCE AND ATTICS APPLIED TO THE GARAGE SIDE FROM HABITABLE ROOM ABOVE THE GARAGE NOT LESS 5/5 INCH TYPE X GYPSUM BOARD OR EQUIVALENT STRUCTURES) SUPPORTING FLOOR/CEILIING ASSEMBLIES Lo USED FOR SEPARATION REQUIRED BY THIS SECTION NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT GARAGE LOCATION LESS 3 FEET NOT LESS 1/2 INCH GYPSUM OR EQUIVALENT FROM A DWELLING UNIT ON THE SAME LOT APPLIED TO THE INTERIOR SIDE OF EXTERIOR WALLS THAT ARE WITHIN THIS AREA FOR SI : 1 INCH = 25.4 MMJ FOOT =304.5 MM. N I N Lo O N J o �e V ^J+ (>D C NV J 2 E C 3c: N 0) p+. U O L O QQ N f_A U�-0 ca- Off- N N Q_ oa�ia���o��a�i�� U a> Q= .� J ci c U a)N -Oi N J cn (1) o 2 c6 �} � m _ca � J W w- 4c:X O O a 0 O ca �� N U Q N O cn N co o -� w ca E- c H c0 a- o ca > Q J H +. J U Lr, — o 00 a. 70 E 0 U �o M M co a0rn0 N 00 E M 00 Ln Y f'V N M W Ln N cn O 41 .c a REVISION DATE: NIT: PROJECT #: DATE: 12-21-2021 NIT: 2 JACK 4 PROJECT: 4" SPHERE SVALL - NOT PASS,/THROUGH HANDRAIL TO BE PRESENT ON ON AT LE=AST ONE SIDE OF STAIR. F4ANE)GRIP f=ORTION OF I4ANDRAIL5 SHALL HAVE CIRCULAR GROSS SECTION OF 11/4" MIN. 4 2" MAX. ALL REQUIRED GUARDRAILS TO BE 36" 4 / MIN. IN HEIGHT. OPENINGS FOR REQUIRED GUARDS ON T1HE SIDES OF STAIR TREADS SMALL NOT ALLOW A SPHIERE 43ia INCHES (107mm) TO PASS THIROUeHI 3/4" MIN. -11/4" MAX NOSING 7 SIMPSON LSG ORISIMULAR BRACKET SPHERE UNABLE TREAD ..TO PASS THROUGH OPENING SELOLU STAIR INSTALL GLOB 'L CEILING, AND JJALLS 2X4 THRUST IBLOCK (3) 2X12 STRINGERS FIRE BLOCKING '@ MID -SPAN AND IN STUD WALLS ALONG AND IN LINE WITH STRINGERS IF AREA UNDER STAIRS IS UNFINISHED INTERIOR/GUARDRAIL STAIR NOTE=S: - HANDRAILS MUST NOT PROJECT MORE THAN 41/211( 114 MM) INTO THE STAIRWAY. IRC SECTIONS R311.18.2 - THE SPACING BETWEEN INTERMEDIATE HANDRAIL MEMBERS MUST NOT ALLOW A 4" SPHERE TO PASS THROUGH ANY OPENING. IRC SECTION 8312.1.3 - MINIMUM STAIRWAY WIDTH ABOVE HANDRAIL SHALL BE NO LESS THAN 36 INCHES, IRC SECTION R317.1 - STAIR 4 STAIR LANDING MINIMUM WIDTH SHALL BE NO LESS THAN 36" (31/2" CLEAR IF ONE HANDRAIL, S 27" CLEAR IF 2 HANDRAILS. IRC SECTION R311.11 - THE TREADS LEADING EDGE CURVATURE CAN HAVE A MAX. RADIUS OF 9/16", THE MAX. BEVELING OF THE NOSING SHALL BE NO MORE THAN /z" IRC SECTION R311.7.5.3 - RISER OR TREAD MAXIMUM DIFFERENTIAL SHALL BE NO MORE THAN 3/a" RC SECTION 8311.7.5.1 - NOSING IS NOT REQUIRED FOR STAIRS WITH TREADS GREATER THAN II" IRC SECTION 8311.7.5.3 EXTERIOR STAIR NOTES: - EXTERIOR STAIR LIGHTING AT TOP LANDING WITH CONTROLS INSIDE THE DWELLING. IRC SECTION R303.8 - A MAXIMUM SLOPE OF 1:48 (2%) IS REQUIRED AT EXTERIOR LANDINGS AND TREADS FOR DRAINAGE. IRC SECTION 8311.3 INTERIOR WINDER STAIR NOTES: - WINDER TREADS ARE REQUIRED TO HAVE A MINIMUM OF 6" DEPTH AT INNER EDGE. RC SECTION 8311.1.5.2.1 - WINDER TREAD DEPTH OF 10" WITH IN 12" OF THE INSIDE. IRC SECTION 8311.1.5.2.1 LANDING NOTES: - LANDING WIDTH SHALL NOT BE LESS THAN THAT OF STAIR SERVED IRC 8311.7.6 - LANDING SHALL NOT BE LESS THAN 36 INCHES IN DIRECTION OF TRAVEL IRC 8311.7.6 STAIR DETAIL SCALE: N.T.S. R4024.1.2 TESTING. THE BUILDING OR DWELLING UNIT SHALL BE TESTED AND VERIFIED AS HAVING AN AIR LEAKAGE RATE OF NOT EXCEEDING 3 AIR CHANGES PER HOUR. TESTING SHALL BE CONDUCTED WITH A BLOWER DOOR ATA PRESSURE OF 0.2 INCHES W.G. (50 PASCALSW). WHERE REQUIRED BY THE CODE OFFICIAL, TESTING SHALL BE CONDUCTED BY AN APPROVED THIRD PARTY. A WRITTEN REPORT OF THE RESULTS OF THE TEST SHALL BE SIGNED BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE CODE= OFFICIAL. TESTING SHALL BE PE=RFORME=D AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF THE BUILDING THERMAL ENVELOPE. ONCE VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE R402.4.1.1), OPERABLE WINDOWS AND DOORS MANUFACTURED BY SMALL BUSINESS SHALL BE PERMITTED TO BE SEALED OFF AT THE FRAME PRIOR TO THE TEST. WEATHERSTRIPPED 2X4 BLOCKING TYP. 2/2" HIGH 5/S° GWB TYPE °X° TRUSS BOTTOM CHORD AT ALL SIDES L 5/5 " GWB TYPE "X' S/S GWB TYPE X — 22 x 30 ATTIC ACCESS OPENING ACCESS HATCH- CEILING INSULATE FULL DEPTH ATTIC ACCESS DETAIL SCALES: N.T.E. 11/2 " HARDUJOOD HANDRAIL SOLID BLOCKING AS REQUIRED PRE FINISH METAL BRACKET TYP. TAT f=. H,4N1:)iR,41L 2X 8402.4.1.2 TESTING. THE BUILDING OR D LEAKAGE RATE OF NOT EXCEEDING 3 BLOWER DOOR AT A PRESSURE OF 0.2 OFFICIAL, TESTING SHALL BE CONDUCTS RE=SULTS OF THE TEST SHALL BE SIGNEE CODE OFFICIAL. TESTING SHALL BE PEI THE BUILDING THERMAL ENVELOPE. ON R402.4.I.1), OPERABLE WINDOWS AND DC BE SEALED OFF AT THE FRAME PRIOR J FLLING UNIT SHALL BE TESTED AND VERIFIED AS HAVING AN AIR SIR CHANGES PER HOUR, TESTING SHALL BE CONDUCTED WITH A INCHES W.G. (50 PASCALSW). WHERE REQUIRED SY THE CODE .D BY AN APPROVED THIRD PARTY. A WRITTEN REPORT OF THE 3 BY THE PARTY CONDUCTING THE TEST AND PROVIDED TO THE :FORMED AT ANY TIME AFTER CREATION OF ALL PENETRATIONS OF ;E VISUAL INSPECTION HAS CONFIRMED SEALING (SEE TABLE ORS MANUFACTURED BY SMALL BUSINESS SHALL BE PERMITTED TO TO THE TE=ST, =AC:E ACCESS DETAIL. SCALE= N.T.S. SIDING PRODUCT 38 HD INSULATION OPTION WATER HEATING SYSTEM SHALL INCLUDE ONE OF THE FOLLOWING: 5.5 ELECTRIC HEAT PUMP WATER HEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATER HEATING SPECIFICATION. /2" DRYWALL 2x STUDS a 16" olc �— VENT FLUE JP %—/2" DRYWALL THRU ROOF / x 2x4 CLEAT 6" / MIN. =n V 7 1/2" DRYWALL CC) 0 • 0 WATER HEATER 2x STUDS X16"0/0 2x4 CLEAT m SEISMIC STRAPPING PER MANUFACTURERS SPECIFICATIO S (UPC SEC .507.2) 2X4 CLEAT SECURE SHAPED 2xIO SPACER TO 2x4 ' CLEATS WITH (5)-16d NAILS m SHAPED 2X10 SPACERS WILL BE CUT TO INSURE A TIGHT FIT TO WATER HEATER WATER HEATER STRAPS WILL RESIST LATERAL FORCES EQUAL TO 100% OF GRAVITY LOADING z PLATFORM MUST BE ANCHORED TO WALL FINISHED FLOOR TYI=ICTAL WATER HEATER DETAIL SCALE: N.T.S. WSEC 2018 8403.5.3 HOT WATER PIPE INSULATION (PRESCRIPTIVE) INSULATION FOR HOT WATER PIPE,BOTH WITHIN AND OUTSIDE THE CONDITIONED SPACE, SHALL HAVE A MINIMUM THERMAL RESISTANCE (R -VALUE) OF R-3 2018 UPC 312.6 FREEZING PROTECTION. NO WATER,SOIL,OR WASTE PIPE SHALL BE INSTALLED OR PERMITTED OUTSIDE OF A BUILDING, IN ATTICS OR CRAWL SPACE, OR IN AN EXTERIOR WALL UNLESS, WHERE NECESSARY, ADEQUATE PROVISION IS MADE TO PROTECT SUCH PIPE FROM FREEZING. ALL HOT AND COLD WATER PIPES INSTALLED OUTSIDE THE CONDITIONED SPACE SHALL BE INSULATED TO A MINIMUM R-3 CONT. METAL GI 5/4 X 8 FASCIA 2 x 6 STU: W/ R-21 SIDING PER EL ON TYVEK 7/16" PLY OR OSB S COMPOSITION ROOFING ON iie it f=I T I Inl�ml ArM�nlfi M=O TOI ICC�C ®C� SECTION "A" © 2021 Level Design, LLC. TYPICAL ROOF CONSTRUCTION COMPOSITION ROOF SHINGLES - 1E�*' ROOFING FELT -/1�" SHEATHING RATED 24/1ro - STRUCTURAL SYSTEM AS NOTED ON FRAM INS PLAN - R-4� INSULATION - E,/B" GW5, CEILING - 1/B" TO 1/4" 1ME61H SCREEN OVER OPENINGS - MINIMUM NET FREE VENTILATING AREA SHALL ESE 1/1E�O OF VENTE=D AREA SPACE OR 1/300 IF 0-50% VENTING IN UPPER ATTIC OR RAFTER SPACE. PER IRC R806 .2 - PROVIDE 1" MINIMUM CLEARANCE 5ETWEEN INSULATION AND &MEATI-IING; AT VENTS PER IRC SECTION RBOC .3 TYPICAL WALL CONSTRUCTION - SIDINCx AND/OR VENEER PER ELEVATION - 1/1ro'I PLY OR 055 SHTC:;.( U.N.O � - TYVEK 5UILDINr;r WRAP OR ECS. - 2Xro STUDS e fro" O.C. EXTERIOR WALLS U.N.O. EXTERIOR WALL NOTCH 2F5%, 50FRING 40% roO% 5ORINr-� IF DOU5LI-D 4 NOT MORE- THAN TWO SUCCESSIVE- STUDS. - 2x-- STUDS e 1G " O.C., INTERIOR PARTITIONS (2X0 � PLUMBING WALLS NON-5EARING WALL MAXIMUM NOTCH .40%, 5CFRING; r00% HOLES NO CLOSER THE 5/0 INCH TO FACE OF STUD - R-21 INSULATION WITH VAPOR 5ARRIER - 1/2" INTERIOR SW=ATHING TYPICAL FLOOR CONSTRUCTION - FINISHED FLOOR F:1FR PLANS - 3/411 T$G PLYWOOD SU5FLOOR (GLUE= AND NAIL) - FLOOR JOISTS PE -R PLAN - R -3a INSULATION OVER UNHEATED AREAS SEE NOTE ON SHEET 1 C;C)I M'C)SI I ION NC 15' FELT PAPER 7/16" SHEATHING ROOF FRAMING F INSULATION BAFF VENTED BLOCKII` 5/4 x 8 FASCIA CONTINUOUS MET; R-10 RIGID INSUL 2x6 STUDS 16" R-21 INSULATION 1/16" SHEATHING TYVEK WRAP - T' SIDING PER FLF� 3/411 T 4G PLYW002 FLOOR JOISTS PE WINDOW HDR. PEf 5/4 TRIM SURROU WINDOW W/ INS, GI 3/4" T&G PLYWOC: FLOOR JOISTS PE R-38 INSULATION 5/4 X 10 TRIM 54 2X P.T. WOOD SIL 4" 4 CO TO STOI 4" 4 PE SET IN I W/ FILTFr,- �YF�7, I LI\ I L1�1 V SCALE: 1/4" =1'-0" )RAIN AVEL DVER TYPICAL WA SECTION SUBFL PL SUB SCALE : N.T.S. NOTE: 1/16" SHEATHING NOT RFOJIRED ON EXT. WALLS UJHFRF T1-11 51DINC3 15 SRFGIFIFD (UNLESS NOfiEp 07PERUJ15E IN THE 5PEAR UJAI-l- 5PEOIFIOATIONS) N I N Lo O N J C6 c o 0 3N U_ J L E +� 3' �a) co O j 0 CO: 0 U O +, N N C) - Q — —0 >+ N cn 03 O� - Cl � 75N -E c1 N oawwp-ow- m:o U ( o Q= J Q cZ U u�i a� O U L c6 -0 a � N }, N 0) _cz c J cz z5 c 0 a O O c W O Ca �-0 C_ a) C U Q N O cn N D cOi) gas(DE�E�cn m U c O cis N J� 0) t— cod 0.oO ca > aJt—+.J U �n — o ON .5 N ca 70 o - U to o M Mco a 00rn N 00 E M 00 Ln Y f'V N M W N cn O �o a u - REVISION DATE: NIT: PROJECT #: DATE: 12-21-2021 INIT: 3 JACK 4 �: PROJECT CONT. METAL GUTTER 0 5/4 X 8 FASCIA BD, TYP TOP PLATE 6 X &CORBEL, TYP SUB FLOOR TCP PI AT;: WRAP P.T. (o x POST UJ/ 1 x CEDAR TYP. SUB FLOOR 3EVEL SIDING x 4 CORNER BD. TYP. -5/4 x 10 BAND BD. TYP. DN, TO GRADE RIGHT ELEVATION CONT. METAL GUTTER ON 5/4 X 8 FASCIA BD. TYP. (" BEVEL SII 5/4 x 4 CORNER BD. SCALE: 1/4" =1'-0" 5/4 x 10 BAND BD, TYP. N I WRAP P.T. 6 x (o 6 POST UJ/ I x CEDAR a, TYP. SUB FLOOR N Lo O N J C6 c o Tie V ^J+ 3J 'L }� c N J F C E N 0 0 j O O -0 Cc: U O +� N N LO QQ O0 co O N N Oi O U! CU co lA § aD � O ULui70}, � O N N �m _� J W � a O O X 0 cn O �-6 N U Q N O(n N a � O -2) Ca a) E E co N � U 3EVEL SIDING x 4 CORNER BD. TYP. -5/4 x 10 BAND BD. TYP. DN, TO GRADE RIGHT ELEVATION CONT. METAL GUTTER ON 5/4 X 8 FASCIA BD. TYP. (" BEVEL SII 5/4 x 4 CORNER BD. SCALE: 1/4" =1'-0" 5/4 x 10 BAND BD, TYP. v LEFT ELEVATION PROVIDE STEPS DN, TO GRADE ;, CORBEL, TYP. ME 5/4 x 4 COF 5/4x10B/ TYP. DN, TO GRADE REAR ELEVATION SCALE: 1/4" =1'-0" �L GUTTER ON SCIA BD, TYP, BD. TYP. DN. TO GRADE r-vo I wi I x L'=�'4N TYP. NOTE APPROVED NU-15ER5 OF: ADDRESSES SHALL 5E PROVIDED FOR ALL NEW 5UILDINC3e IN SJGH A POSITION AS TO 5E PLAINLY VISI5LE AND L1-0�I5LE FROM TL1E STREET OF, ROAD FRONT ELEVATION FR®eN CITIL APR2OP��1<1= ADDRI=55 NJ15I=RS ARE REQJIR1=» TC 5E SCALE: 1/4" =1'-0" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" - VERIF`i SHEAR WALL NAILING AND NOLDOWNS ARE PER PLAN AND SCHEDULE PRIOR TO INSTALLINGr SIDINGT MASONRY AND WOOD FRA�E CHIMNEYS ARE TO 5E CONSTRUCTED PER I.R.G. PROVIDE C3ALVAN17ED SILFE7 M1-7`AL FLASHING AND GOUNTI-RFLASHIN(S AT ALL ROOF / UJALL INTI-RSI-CTIONS, GI4IMNI-Y5, AND SKYLIGI[TS PROVIDE- WE-ATHERSTRIPPING; AND FLASNINr;r AT ALL DOORS AND WINDOWS AS REQUIRED GAJLK ALL E-XTE-RIOR JOINTS AND PE-NETRATIONS POST ADDRI=SS ON E3LD(-:x. PRIOR TO FINAL INSPI=GTION LOTS SMALL 51- GRADED AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALL. SLOPE- SHALL 5E (o" IN FIRST 10 FT, OFR DRAINS OR &WALES SHALL 5E PROVIDED TO E-NSJRE DRAINAC:;1- AWAY FROM STRUCTJRI- - FASTI=NI=RS TO 51= NOT-DIPPI=D C3ALV. STEEL, STAINLESS OR ALUM. (CORROSION R1=5ISTAN7) NOTE: PROVIDE CONTINUOS PRE -PAINTED G.I. "Z" FLASHING AT ALL EXT. DOOR d WINDOW HEADERS. DN rP. N I WRAP P.T. 6 x (o 6 POST UJ/ I x CEDAR a, TYP. SUB FLOOR N Lo O v LEFT ELEVATION PROVIDE STEPS DN, TO GRADE ;, CORBEL, TYP. ME 5/4 x 4 COF 5/4x10B/ TYP. DN, TO GRADE REAR ELEVATION SCALE: 1/4" =1'-0" �L GUTTER ON SCIA BD, TYP, BD. TYP. DN. TO GRADE r-vo I wi I x L'=�'4N TYP. NOTE APPROVED NU-15ER5 OF: ADDRESSES SHALL 5E PROVIDED FOR ALL NEW 5UILDINC3e IN SJGH A POSITION AS TO 5E PLAINLY VISI5LE AND L1-0�I5LE FROM TL1E STREET OF, ROAD FRONT ELEVATION FR®eN CITIL APR2OP��1<1= ADDRI=55 NJ15I=RS ARE REQJIR1=» TC 5E SCALE: 1/4" =1'-0" © 2021 Level Design, LLC. SCALE: 1/4" =1'-0" - VERIF`i SHEAR WALL NAILING AND NOLDOWNS ARE PER PLAN AND SCHEDULE PRIOR TO INSTALLINGr SIDINGT MASONRY AND WOOD FRA�E CHIMNEYS ARE TO 5E CONSTRUCTED PER I.R.G. PROVIDE C3ALVAN17ED SILFE7 M1-7`AL FLASHING AND GOUNTI-RFLASHIN(S AT ALL ROOF / UJALL INTI-RSI-CTIONS, GI4IMNI-Y5, AND SKYLIGI[TS PROVIDE- WE-ATHERSTRIPPING; AND FLASNINr;r AT ALL DOORS AND WINDOWS AS REQUIRED GAJLK ALL E-XTE-RIOR JOINTS AND PE-NETRATIONS POST ADDRI=SS ON E3LD(-:x. PRIOR TO FINAL INSPI=GTION LOTS SMALL 51- GRADED AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALL. SLOPE- SHALL 5E (o" IN FIRST 10 FT, OFR DRAINS OR &WALES SHALL 5E PROVIDED TO E-NSJRE DRAINAC:;1- AWAY FROM STRUCTJRI- - FASTI=NI=RS TO 51= NOT-DIPPI=D C3ALV. STEEL, STAINLESS OR ALUM. (CORROSION R1=5ISTAN7) NOTE: PROVIDE CONTINUOS PRE -PAINTED G.I. "Z" FLASHING AT ALL EXT. DOOR d WINDOW HEADERS. DN rP. N I N Lo O N J C6 c o Tie V ^J+ 3J 'L }� c N J F C E N 0 0 j O O -0 Cc: U O +� N N LO QQ O0 co O N N Oi O U! CU co lA § aD � O ULui70}, � O N N �m _� J W � a O O X 0 cn O �-6 N U Q N O(n N a � O -2) Ca a) E E co N � U 0 0 Q � (� N J L a) H (O a � +. (a > Q J H +. J U Ln — o 00 a. 70 o - U o M M co Q 00 N 00 E M 00 Ln Y f'V N � M >- W N N O 41 .c a REVISION DATE: NIT: PROJECT #: DATE: NIT: 412-21-2021 JACK 4 PROJECT: 12/9/2021 SHEAR WALLSMARK CALLOUTTYPICAL SHEARWALL NOTESTYPICAL HOLDDOWN NOTES*TYPEDESCRIPTIONTYPICAL SHEARWALL NOTES12/9/2021 12/9/2021 12/9/2021 12/9/2021