UPDATED WORK SKETCH 105098151 BERRY VALLEYT
BLDG 1
8 UNITS
~1000 SQ.FT.
BLDG 2
24 UNITS
~1000 SQ.FT.
BLDG 3
24 UNITS
~1000 SQ.FT.
BLDG 4
24 UNITS
~1000 SQ.FT.
TAHOMA BOULEVARD SE
BE
R
R
Y
V
A
L
L
E
Y
A
V
E
N
U
E
EX: 3-6"
EX: 4-4"
EX: 1-4"
(4) 350
(4) 350
(4) 350
(4) 350
DEVELOPER RESPONSIBLE FOR
CONDUIT/WIRE FROM VAULT TO
METER LOCATION (TYPICAL)
#4ACSR
CC#4ACSR
FUT: 1-4"ROAD AROAD CROAD BROAD BROAD B
ROAD B
WYNDSTONE CONDOS
105099121
56'
26'26'26'26'26'26'
26'91''A'
'B'
'C'
'D'
'E'
T FEEDYEL
25
1" = 50'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
E. ORTIZ .02.01.22
N/A .N/A
E. ORTIZ .02.01.22
REDT # ( RW-123753 )YELM
BERRY VALLEY
2Ø PRIMARY U/G LINE EXTENSION - 4 M/F BLDGS, 80 UNITS
15035 BERRY VALLEY ROAD, YELM, WA 98597
PUGET SOUND ENERGY
N/A N/A
N/A 105098151
1" = 50'2 OF 4
THURSTON N/A N/A QSTHLE
24SE-T17N-R01E N/A N/A
1701E096 1702E116 1701E096 YEL-25
COMCAST
TED AXTELL
253.878.2794
TELEPHONE
COMM TBD
COMM TEL TBD
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
SITE PLAN
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
YEL-25
06.11.21
301 310 317
25 17 0
326 327 317
...
...
...
SCHED.SQ. FT.
MAX LRC =
CIRCUIT FEET ADDED: 1,720
17 1,000
65 AMPS
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)BREAKLINE ~505 FTDEVELOPER TO COORDINATE WITH PSE
PROJECT MANGER & SERVICE PROVIDER
PRIOR TO EXCAVATING WITHIN 3' OF LOCATE
MARKS OF PSE ENERGIZED FACILITIES
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #1
8 + HP
1,000
200A
ELEC
43KW
65
2.2 @ V04
1.0 @ V04
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #2
24 + HP
1,000
200A
ELEC
99KW
65
1.6 @ V03
0.3 @ V03
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #3
24 + HP
1,000
200A
ELEC
99KW
65
1.6 @ V02
0.3 @ V02
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
Units:
BUILDING #4
24 + HP
1,000
200A
ELEC
99KW
65
1.6 @ V01
0.3 @ V01 Developer Note:
The following Fault Current information MUST BE conveyed
to the builder of the units:
All units may require upgraded house electrical equipment as the
fault current at the meter base may exceed 10,000 amps.
FAULT CURRENT TABLE
1Ø PM TRANSFORMERS (240/120V)
120V WINDINGS 240V WINDINGS
LOCATION SIZE R/X MIN.
%Z
FAULT
CURRENT
MIN.
%Z
FAULT
CURRENT
V01-V03 100kVA 0.5 2.43 57,300 AMPS 1.90 36,600 AMPS
V04 37.5kVA 0.6 2.23 18,700 AMPS 1.7 12,300 AMPS
CUSTOMER OWNED AND INSTALLED SECONDARY WIRE TABLE
BLDG.# OF
METERS SOURCE # OF RUNS WIRE SIZE REMARKS
1 9 V04 4 350 -
2 25 V03 4 350 -
3 25 V02 4 350 -
4 25 V01 4 350 -
ALL CUSTOMER-OWNED WIRE MUST BE INSTALLED ACCORDING TO THIS TABLE
M
A
T
C
H
L
I
N
E
A
-
A
(
S
E
E
B
E
L
O
W
R
I
G
H
T
)
M
A
T
C
H
L
I
N
E
A
-
A
(
S
E
E
A
B
O
V
E
L
E
F
T
)
CROSSING CONDUIT TABLE
X-ING
#
LOCATION POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY
X01 'A''B'4 DB120 1 65 ( )'SCL PRIMARY
X02 'B''C'2 DB120 2 135 ( )'ECL PRIMARY
X03 'D''E'2 DB120 1 75 ( )'ECL PRIMARY
2" DB120 GREY PVC = 345 FT 2" PVC PLUG /CAPS = 6
4" DB120 GREY PVC = 65 FT 4" PVC PLUG /CAPS = 2