PSE FINAL 105098738 MOUNTAIN MEADOWSN
Vicinity Map
46.9591, -122.6274
Owner / Developer Contact Info
officeATTN:
COPPER RIDGE, LLC
PO BOX 73790
PUYALLUP, WA 98373
EVAN MANN 253.820.7835
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
GAS
PHONE
CABLE TV
511877253 105098738
N/A 105099610
N/A N/A
N/A N/A
N/A N/A
N/A N/A
511877256 107061200
N/A 106381322
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
St. Lights
Relocation
Removal
Temporary
Job Order
Distribution
Service Stubs
HP Svc/MSA
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, PER THE TRENCH
PROFILE, AND ALL EXCAVATIONS AT THE TRANSFORMER/HANDHOLE VAULT SITES
SUCH THAT PSE FACILITIES WILL MATCH FINAL GRADE. VAULT HOLES WILL HAVE
STABLE LEVEL BOTTOMS. CUSTOMER WILL PROVIDE 6" OF CRUSHED ROCK FOR
VAULT BEDDING. ALL TRENCHES WILL HAVE 6" OF WASHED SAND COVER AND 4"
BEDDING FOR ALL CONDUITS. THE CUSTOMER WILL PROVIDE SELECT BACKFILL, IF
REQUIRED, AND COMPACTION AS NECESSARY. THE CUSTOMER IS RESPONSIBLE FOR
DISPOSAL OF ALL NATIVE SPOILS NOT SUITABLE FOR USE AS BACKFILL. ALL
TRENCHES MAY BE JOINT WITH GAS, TELEPHONE AND TV CABLE.
ALL CABLES/CONDUITS TO BE INSTALLED IN CUSTOMER'S TRENCH AT THE DEPTH
INDICATED IN TRENCH DETAIL (DEPENDENT UPON SIZE OF CONDUIT BEING INSTALLED
TO MEET MIN 36" OF COVER). INSTALL CABLE ID TAGS AT EACH END OF THE PRIMARY
CABLES PER THE CIRCUIT ONE-LINE DIAGRAM.
UNLESS OTHERWISE SPECIFIED BY MUNICIPALITIES, INSTALL PVC (DB-120) ROAD
CROSSINGS AS INDICATED ON THE CROSSINGS CONDUIT TABLE & AS SHOWN ON
WORK SKETCH. CROSSINGS SHALL BE INSTALLED BY CUSTOMER/DEVELOPER PER
PUGET SOUND ENERGY STANDARDS.
AT SYMBOL: INSTALL UNDERGROUND PRIMARY CABLES IN
CONDUIT. CABLE LENGTH AND CONDUIT SIZE AS INDICATED ON PRIMARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL 600 VOLT UG SECONDARY CABLES IN
CONDUIT. CABLE/CONDUIT SIZE AND LENGTH AS INDICATED ON SECONDARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL MINI-PAD HANDHOLE & PADMOUNT TRANSFORMER.
ADDITIONAL EQUIPMENT AS INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY PEDESTAL/HANDHOLE W/ (3)
MULTI-CONNECTORS. SIZE AS INDICATED ON SECONDARY HH/PEDESTAL TABLE.
(EXCAVATION: 3' SQ.)
AT SYMBOL: INSTALL JUNCTION BOX HANDHOLE. ADDITIONAL EQUIPMENT AS
INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY CABLE & CONDUIT STUB-OUT.
AT SYMBOL: INSTALL STREET LIGHTING STANDARD. SIZE AND TYPE OF
STANDARD/LUMINARIE AS INDICATED ON STREET LIGHTING TABLE. (CUSTOMER TO
EXCAVATE & INSTALL CORRUGATED STREET LIGHT TUBES FOR PLACEMENT OF THE
STREET LIGHT STANDARDS. )
INCLEMENT WEATHER CONDITIONS MAY CAUSE DELAYS IN CONSTRUCTION TIMES
AND DATES.
POWER GENERAL NOTES - PLAT PROJECT
105098738107061200Phone
INTOLIGHT Contact Information:
LARS LARSON
425.456.2701
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ .04.13.22
...
A. VASQUEZ .04.13.22
REDT # ( RW-124573 )YELM
MOUNTAIN MEADOWS
1Ø PRIMARY U/G LINE EXTENSION - 22 S/F LOTS
P# 21713310400, 8818 BURNETT RD SE, YELM, WA, 98597
PUGET SOUND ENERGY
N/A IP 344-60
107061200 105098738
N/A 1 OF 4
THURSTON 344 CIONC QSTHLE
13SW-T17N-R01E 281.042 280.038
1701E051 1702E068 1701E051 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
.
.
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
11.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:DON BETTENCOURT
206.445.5958
Don.Bettencourt@pse.com
x
xx
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit Field Face
Quadrant
Climbing
Space
Road Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
NOT TO SCALE
...
...
...
EVAN@SOUNDBUILTHOMES.COM
VAULT DETAIL @ V01-V03
NOT TO SCALE
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
FRONT
FRONTTYPICAL NOTCH-OUT FOR TRANSFORMER,
NOT TO SCALE
& SECONDARY PEDESTAL/HANDHOLE
BACK OF EASEMENT
STANDARD
EASEMENT
LINE
ROW
10'
PL
1'
4' - 5'
Min.
1'
7'7'
TRANSFORMER
(WHEN PRESENT)
42"
45°42"
1'
45°Property LineRoad Side
Top View of Mainline Trench for
Single Stubout Location
4'Property LineRoad Side
Top View of Mainline Trench for Pedestal
or Double Stubout Location
42"45°
4'
45°
STUBOUT EXCAVATION DIMENSIONS
NOT TO SCALE
JOINT TRENCH DETAIL
NOT TO SCALE JOINT TRENCH DETAIL
NOTES:
1. If the final backfill contains rocks greater than 8 inches in diameter , install 12 inches compacted sand shading across the full width of the trench. *
If the final backfill contains rocks 8 inches in diameter or smaller , install 6 inches compacted sand shading across the full width of the trench. *
2. Rocks greater than 10 inches diameter are not permitted in the final backfill.
3. Sand bedding is required under PSE gas pipe. Bedding is not required for the full width of the trench; it shall extend from the
side of the trench nearest to where the gas main/service is installed to a minimum of 6 inches on the opposite side of the gas line.
4. Utilities shall not be stacked over the gas line in the trench.
5. If wet utilities will be included in the trench, please contact PSE or local power company directly for clearance requirements.
6. Reduced clearance of 4 inches between power and communication, must have approval of the communications companies.
* Alternatives to full-width trench shading require PSE approval.
Primary & Secondary-Mainline Gas & Communications (NTS)
ROAD SIDE
NATIVE
SECONDARY POWER
PEDESTAL
MATERIAL
P/L
Power
Secondary
Power
Primary
Conduit
Tel. & TV
12" Min
12" Sand
Cover when
gas line is in
trench
Sand
6" or 12"
4" Sand Bedding
1'
36"
Cover
42"
Gas
12"
18"
Lower 2"
10"
Pedestal
PSE 10' FRONTAGE
EASEMENT
1'
Cover
ROAD SIDE
MINIPAD
MINIPAD
FIELD SIDE
VAULT
6" of crushed rock
(base for vault)
P/L
Power
Secondary
Power
Primary
Gas
12" Min Horizontal Separation
Communications
42" Min
21"1'
Feeder
38"
2"
4" Sand Bedding
12" Sand
Cover
36"
Cover
4" Sand Bedding
42"
6" Additional depth when
Feeder is required
PSE 10' FRONTAGE EASEMENT
1'
TRANSFORMER
Final
Backfill
Initial
Backfill
Trench Depth
42" - 48"
Primary
Dirt Pile
Final Grade
24" Min
36"
Min Cover
Over Power
48"
Max
Depth
Final Backfill
Gas
4" Sand Bedding
Property Line
intercept (depth varies).
SidewalkCurb
Location of roof drain
48" Typical
Width may vary per
Number of Utilities
and Conduits
6" or 12" Min Sand Shading
Over Gas after Compaction
12" Min
R/W or
Excavated
12" Typical
Power
Secondary
Power
TV & TEL
12" Min
12" Min
Separation
4,5
1,2
1
3
6
6" or 12" Min Sand Shading
Over Power after Compaction1
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED EQUIPMENT
TRANSFORMER
APPROVED
AREA
COMBUSTIBLE BUILDING WALLS & ROOF10'
10'
10'
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
3' MIN
@ H1A
SHALL BE STAGGERED
CONNECTOR BARS
IN THE FRONT
NEUTRALS SHALL BE 18"
16"
13"
12"10"
2"
10"
Pedestal will accept up to six 3" conduits
SEALED WITH FOAM
CONDUIT SHALL BE
120 PVC CONDUIT ELBOWS
TYPICAL 24" RADIUS DB
SIDE VIEW WITH CONDUIT
10"
18"
16"
13"
10"
2"
36"
FRONT VIEW WITH CONDUIT
SECONDARY PEDESTAL DETAIL
NOT TO SCALE
J-BOX CABLE ENTRY DETAIL
NOT TO SCALE 12kV CABLE ROUTING
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
SITE
1 2
3 4 5
14
13
12
11
109
TRACT A
OPEN SPACE
17 16
15
19
18
76 8
202122 56'
14740
14867 14872GAS ONLY89TH WAY SE89TH AVE SEBURNETT RD SE89TH WAY SE
#4ACSR14822 14834
8812
14770
8815FEED
EX 1-2"BURNETT RD SE50'
'A'
'B'
8815
C
FUSE @ 40T
SW#T87221
56'56'40'
YEL
25
A
C
A
C
A
FEED YEL
25
SW#T87222
#
4
C
U
#
4
C
U
ABCABCC #4ACSRA
Y
E
L
M
HW
Y
S
E BURNETT RD SE50'60'1" = 50'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ .04.13.22
...
A. VASQUEZ .04.13.22
REDT # ( RW-124573 )YELM
MOUNTAIN MEADOWS
1Ø PRIMARY U/G LINE EXTENSION - 22 S/F LOTS
P# 21713310400, 8818 BURNETT RD SE, YELM, WA, 98597
PUGET SOUND ENERGY
N/A IP 344-60
107061200 105098738
1" = 50'2 OF 4
THURSTON 344 CIONC QSTHLE
13SW-T17N-R01E 281.042 280.038
1701E051 1702E068 1701E051 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
.
.
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
SITE PLAN
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
YEL-25
12.02.21
287 340 326
19 N/A N/A
306 340 326
...
...
...
SCHED.SQ. FT.
MAX LRC =
CIRCUIT FEET ADDED: 1170'
17 3500
115 AMPS
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
DEDICATED FACILITIES (105098738) Dedicated Stub Locations
SITE SPAN ADDITIONAL REMARKS LABOR UNITS
#FROM TO FOOTAGE
-V02 LOT 6 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 7 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 9 20 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 10 20 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 12 40 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 13 45 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 17 65 DED. CONDUIT & WIRE 2-36, 2-54A
-H1A LOT 18 55 DED. CONDUIT & WIRE 2-36, 2-54A
-V01 LOT 20 45 DED. CONDUIT & WIRE 2-36, 2-54A
-V01 LOT 21 45 DED. CONDUIT & WIRE 2-36, 2-54A
TOTAL FT=400
SITE SPECIFIC NOTES
DEVELOPER TO COORDINATE WITH PSE
PROJECT MANGER & SERVICE PROVIDER
PRIOR TO EXCAVATING WITHIN 3' OF LOCATE
MARKS OF PSE ENERGIZED FACILITIES
CROSSING CONDUIT TABLE
X-ING
#
LOCATION GAS POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY LOCATION
SIZE
(IN)TYPE QTY
X01 'A'TR. A ELEC ONLY 2 DB120 1 105 ( )' SCL PRIMARY
X02 TR. A 'B'4 40 1 W GAS ONLY 65 ( )' ECL GAS MAIN
X03 LOT 21 LOT 1 2 40 1 E 3 DB120 2 65 ( )' ECL GAS SVC, SECONDARY
X04 LOT 18 LOT 4 2 40 1 W 3 DB120 2 65 ( )' WCL GAS SVC, SECONDARY
X05 LOT 18 LOT 5
4 40 1 E 2 DB120 1 65 ( )' WCL GAS MAIN, PRIMARY
----3 DB120 1 65 ( )' WCL SECONDARY
X06 LOT 14 LOT 15 2 40 1 N 3 DB120 2 65 ( )' SCL GAS SVC, SECONDARY
2" PVC PLUG /CAPS = 6 2" YELLOW SCH 40 PVC = 195 FT 2" DB120 GREY PVC = 170 FT 2" PVC PLUG /CAPS = 4
4" PVC PLUG /CAPS = 4 4" YELLOW SCH 40 PVC = 130 FT 3" DB120 GREY PVC = 455 FT 3" PVC PLUG /CAPS = 14
BREAKLINE~1540'
AT P01 (559804-146888) 40' CLASS 3, 1978
-TRANSFER EXISTING 'C' PHASE TAP TO 'A' PHASE
AT P02 (559810-146896) 40' CLASS 3, 1978
-INSTALL SWITCH # T87222
AT P03 (560022-146902) 40' CLASS 3, 1971
-INSTALL 1Ø TERM ON NEW BI-UNIT (8721000) FIBERGLASS ARM W/
LINK BREAK C/O & SURGE ARRESTOR (TSU1C1) 6043.1000
-STIRRUP (2254000)
-ALUM "H" CONNECTOR (2167000)
-FUSE @ 40T (3412500); TAP 'A' PHASE
-INSTALL SWITCH # T87221
-INSTALL 2" PRI RISER ON EXISTING STANDOFF BRACKETS(RIS2CSS) 6042.1000
NEW 1/O AL
EJG776-AØ
BØADK911#4ACSRBØADK910FEED'A'
FUSE @ 40T
SW#T87221
YEL
25
C
A
C
A
C
A
FEED YEL
25
NEW 1/O AL
EJG777-AØ
NEW 1/O AL
EJG779-AØ
BØADK966
BØADL027
BØADL112
NEW 1/O AL
EJG778-AØ
BØADL028
BØADL029
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ .04.13.22
...
A. VASQUEZ .04.13.22
REDT # ( RW-124573 )YELM
MOUNTAIN MEADOWS
1Ø PRIMARY U/G LINE EXTENSION - 22 S/F LOTS
P# 21713310400, 8818 BURNETT RD SE, YELM, WA, 98597
PUGET SOUND ENERGY
N/A IP 344-60
107061200 105098738
AS SHOWN 3 OF 4
THURSTON 344 CIONC QSTHLE
13SW-T17N-R01E 281.042 280.038
1701E051 1702E068 1701E051 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
.
.
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
EX OVERHEAD CIRCUIT MAP 1702E068
SCALE: 6" = 1 MILE
NEW PRIMARY UNDERGROUND CIRCUIT ONE-LINE DIAGRAM
NOT TO SCALE
EX UNDERGROUND CIRCUIT MAP 1701E051
NOT TO SCALE
SITE
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT CABLE ASBUILT INFORMATION - FOREMAN COMPLETE
FROM TO SIZE
(IN)QTY.
DESIGN
LENGTH
(FT)
BENDS PULL
(LBS)
PULL
REV
(LBS)
CABLE
SIZE
DESIGN
LENGTH
(FT)
PHASE - ID TAG RECORD RECORD PHASE TAPPED & ACTUAL FOOTAGE INSTALLED LUBRICANT (Gal.)
90°45°22°11°A B C MANUFACTURER COMPOUND YEAR NOTES CONDUIT CABLE EST.ACTUAL
P03 V01 2 1 275 1 ---99 204 1/0 AL JKT 420 EJG776 ---1.7
V01 V02 2 1 230 2 ---216 202 1/0 AL JKT 305 EJG777 ---1.2
V02 V03 2 1 165 --2 -109 108 1/0 AL JKT 175 EJG778 ---0.7
V03 E01 2 1 110 ----CONDUIT ONLY -----
V03 V04 CABLE ONLY 122 133 1/0 AL JKT 340 EJG779 ---1.4
2" PVC (FT) & BENDS =780 3 0 2 0 1/0 AL JKT TOTAL (FT) =1240 TTL(Gal.) = 5.0
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS TRANSFORMER ID NUMBERS
(COMPANY ID)
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
V01 560008
146935
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 AØ
V02 560023
146957
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 AØ
V03 560011
146968
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 AØ
Existing
V04
559977
146963
4'x6'x3'6"
Combo Vault
Matid: Existing
37.5KVA MP TRF
120/240
Matid: Existing
1 -
ELB10J 6041.1000 EX BØ
SITE
'A'
1 2
3
4
5
14
13
12
11
10
9
17
16
15
19
18
7
6
8
20
2122
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. BETTENCOURT 206.445.5958 .
A. VASQUEZ .04.13.22
...
A. VASQUEZ .04.13.22
REDT # ( RW-124573 )YELM
MOUNTAIN MEADOWS
1Ø PRIMARY U/G LINE EXTENSION - 22 S/F LOTS
P# 21713310400, 8818 BURNETT RD SE, YELM, WA, 98597
PUGET SOUND ENERGY
N/A IP 344-60
107061200 105098738
N/A 4 OF 4
THURSTON 344 CIONC QSTHLE
13SW-T17N-R01E 281.042 280.038
1701E051 1702E068 1701E051 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
.
.
RIGHT OF WAY
CAROLYN BANASKY
253.476.6416
.
.
.
...
...
...
NOT TO SCALE
NEW CONDUIT DIAGRAM
1.
2.
3.
4.
5.
ALL STREET LIGHTING POLES ARE TO BE INSTALLED PER STANDARD
6375.4800 (page #2) IN THE "LINE WORK PRACTICES MANUAL".
ALL POLES (WOOD, CONCRETE OR FIBERGLASS) ARE TO BE SET
PLUMB AND EMBEDDED TO THE GROUND LINE MARKED ON THE
POLE.
BACKFILL AROUND POLE WITH 5/8" MINUS GRAVEL AND COMPACT IN
6" LIFTS. (PEA GRAVEL AND NATIVE SOILS ARE NOT ACCEPTABLE.)
APPROXIMATELY 1 CU. YD. OF 5/8" MINUS CRUSHED ROCK WILL BE
REQUIRED.
THE DEVELOPER IS REQUIRED TO SUPPLY AND INSTALL PLASTIC
(NON PAPER) STREET LIGHT TUBES (MINIMUM 18" DIAMETER) TO
AID IN THE INSTALLATION OF THE STREET LIGHTING POLES. THE
DEVELOPER MUST ALSO SUPPLY THE REQUIRED 5/8" MINUS
GRAVEL AT EACH STREET LIGHT LOCATION.
IN ALL SHOEBOX AND COBRAHEAD INSTALLATIONS, THE LUMINAIRE
MUST BE LEVELED.
DEVELOPER MUST SUPPLY DURABLE LID/COVER AT EACH STREET
LIGHT TUBE.
6.
NOT TO SCALE
STREET LIGHT TUBE DETAIL
Plan View Detail
of Street Light Tube
Wire Entrance
Slot
Street Light
Tube
Field
Side
Road
Side
Wire
Entrance Slot
45°
45°
Position 3" x 6" wire entrance slot 45 degrees
left or right from a line perpendicular to road-
way through center of tube.
Field Side
3" x 6" Wire
Entrance Slot
45°
45°
Street light tube
set 2" below grade.
Road Side
18" - 24" Minimum
Depending on
Pole Type
5'-0"
20"
26"
SECONDARY HH/PEDESTAL TABLE
Site
Pedestal
or
Handhole
Number of
Positions
Required
Remarks
H1A PEDESTAL 4 - SEPS4 6050.1000
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER Foreman - Complete
FROM TO (1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in)Design (ft)90°45°22°11°(Percent)(Percent)Actual Amount Installed Cable Conduit
V01 H1A 350 115 3 115 2 3.3 2.0
V01 LOT 1 4/O 95 70 3 30 2 4.0 3.4
V01 LOT 2 4/O 95 70 3 30 3 4.0 3.4
V01 LOT 19 1/O 60 70 3 60 1 4.2 3.6
V01 LOT 20 1/O 55 70 3 55 1 4.1 3.5
V01 LOT 21 1/O 55 70 3 55 1 4.1 3.5
V01 LOT 22 1/O 60 70 3 60 1 4.2 3.6
H1A LOT 3 4/O 85 70 3 20 3 4.4 3.5 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H1A LOT 4 4/O 85 70 3 20 2 4.4 3.5 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H1A LOT 18 4/O 55 70 3 55 1 4.7 3.8
V02 LOT 5 1/O 50 70 3 50 1 3.5 3.4
V02 LOT 6 1/O 45 70 3 45 1 3.4 3.3
V02 LOT 7 1/O 40 70 3 40 1 3.4 3.2
V02 LOT 8 1/O 45 90 3 45 1 3.7 3.7
V02 LOT 9 4/O 85 120 3 85 1 3.3 3.2 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V02 LOT 17 4/O 165 70 3 100 3 3.5 3.5 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V03 LOT 10 4/O 95 160 3 95 1 3.8 3.7 LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V03 LOT 11 1/O 55 70 3 55 1 3.8 3.5
V03 LOT 12 1/O 50 70 3 50 1 3.7 3.4
V03 LOT 13 1/O 55 70 3 55 1 3.8 3.5
V03 LOT 14 1/O 60 70 3 60 1 3.8 3.6
V03 LOT 15 4/O 130 70 3 65 2 3.9 3.8
V03 LOT 16 4/O 130 70 3 65 3 3.9 3.8
1/O UG Triplex (ft) =630 3" PVC & BENDS (ft)=1310 35 0 0 0 3.9
4/O UG Triplex (ft) =1020
350 UG Triplex (ft) =115 TOTAL QTS OF GLUE 3.9
STREET LIGHT CIRCUITRY TABLE - 105099610
SITE
#FROM
CABLE INFO AS-BUILT
REMARKSTYPELFTYPELENGTH
FL1 -#6 CIC -- BY INTOLIGHT
FL2 -#6 CIC -- BY INTOLIGHT
FL3 -#6 CIC -- BY INTOLIGHT
FL4 -#6 CIC -- BY INTOLIGHT
SL1 -#6 CIC -
SL2 -#6 CIC -
SL3 -#6 CIC -
SL4 -#6 CIC -
SL5 -#6 CIC -
SL6 -#6 CIC -
TOTAL FT =###TOTAL FT =
STREET LIGHT TABLE (BY INTOLIGHT)
SITE
#
STATION
OFFSET
POLE LUMINAIRE TUBE
WO #
(INTOLIGHT)
BILLING
SCH.GRID #INTOLIGHT
TAG #TYPE ARM MTG HT.WATTS STYLE TUBE
LENGTH
TUBE
DIAMETER
SL1 -XXXXX
XXXXX ----------
SL2 -XXXXX
XXXXX ----------
SL3 -XXXXX
XXXXX ----------
SL4 -XXXXX
XXXXX ----------
SL5 -XXXXX
XXXXX ----------
SL6 -XXXXX
XXXXX ----------
SL7 -XXXXX
XXXXX ----------
SL8 -XXXXX
XXXXX ----------
SL9 -XXXXX
XXXXX ----------
SL10 -XXXXX
XXXXX ----------
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SECONDARY 3"
PRIMARY 2"
CONDUIT LEGEND
ST. LIGHTS