STRUCTURAL CALCULATIONS
FOR THE
SOUNDBUILT HOMES RESIDENTIAL PROJECT
Plan L2-2482
December 1, 2021
Job No. : 09-059
Location: Lots 201 - 398, Tahoma Terra
Yelm, Washington
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010
1 1 1 12222////01010101////21212121
Copyright 2018, SEGA Engineers
STATEMENT OF WORK
SEGA Engineers was asked to provide a lateral loads analysis, shear wall
design, review of major framing members and foundation, and drawing red-lines
for a two-story wood framed single family residence. The roof framing is
manufactured trusses, the floor framing is 2x dimensional or open-web trusses,
and the foundation is typical concrete strip footings with a crawl space.
The application and use of these calculations is limited to a single site
referenced on the cover sheet. The cover sheet should have an original
signature in blue ink over the seal. The attached calculations may or may not
apply to other sites and the contractor assumes all responsibility and liability for
sites not expressly reviewed and approved. Please contact SEGA Engineers for
use at other sites.
SEGA Engineers will use that degree of care and skill ordinarily exercised under
similar circumstances by members of the engineering profession in this local. No
other warranty, either expressed or implied is made in connection with our
rending of professional services. For any dispute, claim, or action arising out of
this design, SEGA Engineers shall have liability limited to the amount of the total
fee received by SEGA Engineers.
Questions regarding the attached should be addressed to SEGA Engineers.
Greg Thesenvitz, PE/SE
SEGA Engineers
SEGA Engineers Project Plan L2-2482
Structural & Civil Consulting Engineers
Job No.09-059 By:GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date:05/18/21 Sht 1
Design Criteria
International Building Code (IBC), 2018
LOADS
Roof
DL 15 psf
LL 25 psf
Floor
DL 12 psf
LL 40 psf
Wind
Risk Category II
Design Wind Speed 110 mph (Vult)
Copyright 2021, SEGA Engineers
Design Wind Speed 110 mph (Vult)
Kzt 1.00
Exposure B
Seismic
Design Category D
SDS 1.00
Response Factor 6.5
CS =0.154
Importance Factor 1.00
Soil
Allowable Bearing 1,500 psf
Copyright 2021, SEGA Engineers
SEGA Engineers
/ Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010
LOADS
ROOF
DL
FLOOR
Roofing (Comp)
'12" OSB
2 x @ 24"
Insulation
51g" GWB
Misc.
LL Snow, Pf
Reduction, Cs
5112 pitch = 23 deg
Total Roof Load
DL Flooring
314" Plywood
2x12@16"oc
518" GWB
Misc.
LL Residential
Total Floor Load
DECKS
DL 2 x Decking
2x10@16"oc
Misc
LL Residential
Total Deck Load
WALLS
DL Siding
112" Plywood
2x6@16"oc
Insul
'12" GWB
Copyright 2017, SEGA Engineers
Project 1-2-2482
Job No. 09-059 By: GAT
Checked Date: 04/13/17 Sht 2
3.5 psf
1.8
3.5
1.1
2.8
1.5
14.2 psf
25 psf (115% Load Duration)
0.00 (C, = 1.1, other surfaces)
39.2 psf
0.5 psf
2.3
3.3
2.8
1.5
10.4 psf
40 psf
50.4 psf
4.3 psf
2.8
1.5
8.6
60 psf
68.6 psf
3.5
1.5 psf
1.7
0.6
2.2
1.5 psf
SEGA Engineers
PROJECT LZ - 1� ,bZ
Structural & Civil Consulting Engineers
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
S4
JOB NO. 0:5? —z9 j + FIGURED BY C—f
If 7 -
CHECKED BY DATE 24 SHEET OF
le 60V1f49--) r—;�T cl (,& r-c,�O )
-St1-cx1Z Lt3
MEE
`'�
of
7;t4-
RJB L«�
fd
Copyright 2017, SEGA Engineers
SEGA Engineers -Y,
PROJECT
Structural & Civil Consulting Engineers
JOB NO. au p �C� FIGURED BY
22939 SE 292nd Place -
Black Diamond, Washington 98010 CHECKED BY DATE �e/u SHEET OF
(360) 886-1017
S"r
(/ r4
r -r ov
r (L 1)
7 r LLS f-
0
I eq Ifo k-- ,, 7 ter.
fll4v
Copyright 2017, SEGA Engineers
SEGA Engineers PROJECT /-'Z
Structural & Civil Consulting Engineers
JOB NO. { rp FIGURED BY
22939 SE 292nd Place
Black Diamond, Washington 98010 !�
CHECKED BY DATE SHEET OF
(360) 886-1017 j�i�
j-- 1,664
0,1����
Fz*
17,
Copyright 2017, SEGA Engineers
w
,d/- -cI o,, l (w4,
�--
0�-
flztlS•r �
m�
SEGA Engineers,
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Framing _-17 ft Studs
@ Side Bearing Wall
Design Criteria
GAT
Stud Height =
17 feet
Stud Spacing =
16 inches
Truss Spacing =
2 feet
Roof DL =
15 psf
Roof LL =
25 psf (snow)
Tributary Span =
15 feet
Wind Load =
10.6 psf
Member Size and Proberties
For DL + Wind
Project 1-2-2482 '
Job No.
09-059
By:
GAT
Fbr = 1492 psi
F, = 1300 psi
CF = 1.10
Checked
Date
04/13/17
Sht
P�
w m = 10.60 psf
h=17.0ft
DL Force = 450 lbs
Snow Load = 750 lbs io
Try 2 x 6 using
HF -#2 @ 16 in oc
Fb = 850 psi
CF = 1.30
Fbr = 1492 psi
F, = 1300 psi
CF = 1.10
FSE = 283.5 psi
le = 204 in
E = 1.30E+06
CP = 0.21
Fc' = 296.3 psi
(Eq 16-12)
P = 450 lbs
fc: = 55 psi
w = 14.1 lbs/ft
M=511ft-lbs
fb = 810 psi
For DL + 3/4Wind + 3/4Snow
P = 1013 lbs
fe = 123 psi
w = 10.6 lbs/ft
M = 383 ft -lbs
fb = 608 psi
COPYRIGHT 2016, SEGA ENGINEERS
Cr = 1.35 (Table 2306.2.1)
d = 5.50 in
KCE=0.30 c'=0.80
Combined
Axial Bending Total
0.03 + 0.67 = 0.71 OK
(Eq 16-13)
Combined
Axial Bending Total
0.17 + 0.72 = 0.89 OK
SEGA Engineers
Structural & Civil Consulting Engineers
I
Project Typical Ftg
Job No. By: GAT
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010 Checked Date: 12/03/15 Sht.
Square Footing Design Ftg 36 x 36
_Design Parameters
f', = 2,500 psi Fy = 40,000 psi All. q = 1,500 psf
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Loads:
Col DL =
2.4
Col LL =
9.6
Floor LL =
0
Overburden =
0.0 in
Slab Thick. =
0.0 in
kip (Service Load)
kip (Service Load)
psf
(120 pcf assumed)
(150 pcf assumed)
Size and Footing Pressure
--- - - h = 8.0 in
qn = 1.40 ksf
; ;q'd A,'ea = 8.5' ft^2
Try 2.95 ft x
Fa-;torod Net S^A r"'r?s,w ' = 113 ksf
:tr::cic 'Or T wd-Wav Shear
?.vg d = 4.00 in
Vu = 16.75 kips
--- Fta. Thickness
(1.2D y 1.:L)
bo = 40.00 in (Critical Shear Parii-,�tvr)
B, = 1 (Long Side/Short Side of Column)
phi V, = 27.20 kips
Phi V, > V„ OK
Check for One -Way Shear
Vu = 5.598 kips
Phi Vc = 12.04 kips
Phi V, > Vu OK
Design Reinforcement
Ftg. &ze
M„ = 4.71 kip -ft
AS = 0.51 in^2 Use (3) - # 4 bars EW Reinforcement
a = 0.27 in 0.59 in"2
Phi M„ = 5.58 kip -ft
Phi Mn > Mu OK
AS min = 0.51 in^2 OK
Copyright 2015, SEGA Enginem
SEGA Engineers Project L2-2482
Structural & Civil Consulting Engineers
Job No. 09-059 By: GAT
22939 SE 292nd FL (360) 886-1017 ---
Black Diamond, WA 98010 Checked Date: 04/13/17 Sht.
LATERAL LOADS - (Alternate ASD)
CCIC6 A I h
Maximum Base Shear, V = F Sos W
R
Eq. 12.14-11
where,
F = 1.1 Two -Story Building
Sas =1.00 Ss = 1.5 Fa = 1.00 (Table 11.4-1, SS > 1.25)
R = 6.5 Table 12.14-1
W = Seismic Weight
For W:
Wr,&= (30ft) (52ft) (16 psf)+ ( 2 ) (30ft+ 52 ft) (4.0 ft) (9.5psf) = 31 kips
Wfloor= (30ft) (52ft) (14 psf)+ ( 2 ) (30ft+ 52 ft) (8.5ft) (9.5 psf) = 35 kips
Design Base Shear, V = ( .169) (66 kip) - 11.2 kip
E = 11.2 kip = 8.0 kip
1.4
WIND
Design Wind Pressure, ps = X Kn p,30
where,
a = 1.00 0 - 15 ft Exposure B
= 1.00 20 ft
= 1.00 25 ft
= 1.00 30 ft
Kri = 1.00
10.62 psf)
( x 0.6 =
10.62 psf)
p3o = 17.7 psf
10.62 psf)
( x 0.6 =
110 mph
PO -15 = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
P20 = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
Pts = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
Pao = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
W►otal = 66 kips
Eq. 28.6-1, Sect. 28.6.3
Figure 28.6-1
Section 26.8
Figure 28.6-1 (ASD)
( x 0.6 =
10.62 psf)
( x 0.6 =
10.62 psf)
( x 0.6 =
10.62 psf)
( x 0.6 =
10.62 psf)
Design Base Shear: (Wind)
Vtlb= (30ft) (10ft) (17.7psf) + (30ft) (5ft) (17.7psf)
+ (25ft) (5ft) (17.7psf) + (10ft) (5ft) (17.7psf) =11.1 x0.6 6.6 kips
VAS= (57ft) (10ft) (17.7psf) + (55ft) (5ft) (17.7psf)
+ (51 ft) (5ft) (17.7psf) + (45ft) (5ft) (17.7psf) =23.5x0.6 =14.1 kips
Therefore, Seismic Loads Govern for Lateral Design - Front/Back
Wind Loads Govern for Lateral Design - Side/Side
Copyright 2017, SEGA Engineers
SEGA Engineers Project L2-2482
Structural & Civil Consulting Engineers
Job No. 09-059 By: GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date: 04/13/17 Sht.
LATERAL LOADS - (cont'd)
Distribute Seismic Loads Over Height
Maximum Base Shear, V = 8.0 k
F. = wx V (Eq. 12.14-12)
W
Front = ( 31.2 ) ( 8.0 k) = 3.8 kip
(66.3)
Ffloor = ( 35.1 ) ( 8.0 k) = 4.2 kip
(66.3)
Fx = 8.0 kip
Copyright 2617, SEGA Engineers
SEGA Engineers
PROJECT
Structural & Civil Consulting Engineers
JOB NO. 09 -�S� FIGURED BY
?2439 5E 292nd Place ))
Black Diamond, Washington 98010 CHECKED BY DATE �l SHEET19 OF
(360) 886-1017 7
�t-S I b nj
WAIL
7_ 00 /Ik
ZF
D
'Jj��
Olt
Copyright 2017, SEGA Engineers
SEGA Engineers
PROJECT
Structural & Civil Consulting Engineers ----
JOB NO. (� -mss c� FIGURED BY �1
22939 SE 292nd Place
Black Diamond, Washington 98010
ck
(360) 886-1017 CHECKED BY DATE 1�/-7 SHEET/POP
5z �o !o
V'g t 45..l�S' %'4a 11 l��)1�����` �s► L l 4��� �'�` �t
�'}(S+ - rye
ft ?—[Ip LIL
z -
Al
'
D
_6v,)Atc. "
�iooa � Cqf-7 I
r
7 7- ?,/ c' 31 :- Sto� e'�" V
Zj f L ! C
/l 3
Copyright 2017, SEGA Engineers
t 5'sw'T'4) 5 -f -' ;A-V 14<
- s tq )?54
SEGA Engineers/
PROJECT -4
Structural & Civil Consulting Engineers
JOB NO. FIGURED BY
22939 SE 292nd Place - - - - 0q0 - -� - -
Black Diamond, Washington 98010
CHECKED BY DATE SHEET
(360) 886-1017( 17_ OF
-SM wA�.rS1 6 rJ car
,= /,-S�[f1-S` :-'3t�
3
Copyright 2017, SEGA Engineers
��?06r /SP�r
SEGA Engineers PROJECT PIAN L2=24K
Structural & Civil Consulting Engineers
22939 SE 292nd Place • Black Diamond, Washington 98010 JOB NO. 01�-05� FIGURED BY GAT
(360) 866-1017 • FAX 886-1016
CHECKED BY DATE 12/00/15 SHEET 10OF 10
LSTA30 - HDR a SILL LSTA30 - HDR a SILL
SNEAK WALL KEY PLAN YP 2FLACESJ
(
0—
SUrBIS x e 6TRI
SEE SIMPSON PRODUCT a
FOR PORTAL IN51ALLAI
11YP r
A = I,A4 SQ FT
:2 - GIRDER
TOP PLATE
/ (1YP. 2 PLACES)
� 1
A = 1194 SQ FT
GIRDER
PLATE
A = 381 5Q FT
(D—�1
S.. x e STRONGAWALL
SEE SIMPSON PRODUCT GL
FOR PORTAL INSTALLAT
(T— r.
I.
�j �LSTA30 - HDR 1 SILL
TO 3x BLOQCING.
(TYP.2 PLACES)
2
L5TA30 - HDR i SILL
s
ry
TO 3x BLOCKING.
(TYP. 2 PLACES) LBTA24 - BEAM
'^3
3
10 TOP PLATE
LSTA30 - HDR / SILL
TO 3x BLOCKING.
(TYR2 PLACES)
-7L 115 - BEAM
TO TOP PLATE
MAIN FLOOR
A = 1,055 SQ FT
L4
A = 381 5Q FT
(D—�1
S.. x e STRONGAWALL
SEE SIMPSON PRODUCT GL
FOR PORTAL INSTALLAT
(T— r.
I.
SHEAR WALL SCHEDULESHEAR WALL SCHEDULESHEAR WALL SCHEDULEMarkMinimumSheathing AnchorRemarks (4)MarkMinimumSheathing AnchorRemarks (4)MarkMinimumSheathing AnchorRemarks (4)Sheathing (1)Nailing (1)Bolts (2)Sheathing (1)Nailing (1)Bolts (2)Sheathing (1)Nailing (1)Bolts (2)A1/" OSB8d @ 6" o.c.5/" @ 60" o.c.Q = 230 plfA1/2" OSB8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA/2" OSB8d @ 6" o.c./8" @ 60" o.c.Qall = 230 plfor CDXor CDXor CDXor CDX15B1/2" OSB8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB1/2" OSB8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB/2" OSB8d @ 4" o.c./8" @ 32" o.c.Qall = 350 plfor CDXor CDXor CDX1/" OSB5/" @ 16" o.c.Q = 450 plfC1/2" OSB8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC1/2" OSB8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC/2" OSB8d @ 3" o.c./8" @ 16" o.c.Qall = 450 plfor CDXUse minimum 3x studsor CDXUse minimum 3x studsor CDXUse minimum 3x studsat abutting panel edgesat abutting panel edgesat abutting panel edgesand stagger edge nailing.and stagger edge nailing.and stagger edge nailing.D1/" OSB8d @ 2" o.c.5/" @ 16" o.c.Q = 600 plfD1/2" OSB8d @ 2" o.c.5/8" @ 16" o.c.Qall = 600 plfD/2" OSB8d @ 2" o.c./8" @ 16" o.c.Qall = 600 plf28allor CDXUse minimum 3x studsor CDXUse minimum 3x studsor CDXUse minimum 3x studsat all panel edgesat all panel edgesat all panel edgesand stagger edge nailing.and stagger edge nailing.and stagger edge nailing.Notes:Notes:Notes:1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing(24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance withAF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.