13R submittal NO DOMESTIC SHUT OFF (3)Date Revised:AUG 2007
TYCO MATERIAL SAFETY DATA SHEET Supersedes:APR 2007
Information on this form is furnished solely for the purpose of compliance with the U.S.Occupational Safety and Health Act ,the Canadian Hazardous Products Act and Controlled
Products Regulations and shall not be used for any other purpose. IPS Corporation urges the customers receiving this Safety Data Sheet to study it carefully to become aware of the
hazards,if any,of the product involved. In the interest of safety,you should notify your employees,agents and contractors of the information on this sheet.
SECTION I - PRODUCT INFORMATION
:seicnegremEnoitatropsnarTEMANS'REILPPUSEMANS'RERUTCAFUNAM
0039-424)008(:CERTMEHCstcudorPgnidliuBdnaeriFocyTocyTrofnoitaroproCSPI
:seicnegremElacideMSSERDDASSERDDA
ChtroN154,973xoB.O.P,.tSniaM.S90171 42(YNAPMOCE3eunevAnonna Hour No.) (800)451-8346
Gardena,CA.90248 U.S.A. (310)898-3300 Lansdale,PA 19446,USA Business:Tyco (215)362-0700
:EMANEDARTYLIMAFdnaEMANLACIMEHC
epiPcitsalPCVPCroftnemeCCOVwoL005PFT®RETSAMEZALBstnevloScinagrOdnaniseRCVPCfoerutxiM
SECTION II - HAZARDOUS INGREDIENTS, EXPOSURE LIMITS, TRANSPORT & WHMIS DATA
None of the ingredients below are listed as APPROX %ACGIH ACGIH TNOPUDAHSOAHSO
carcinogens by IARC, NTP, OSHA or ACGIH.LETS)B(LEA)A(05CL05DLLETSLEPLETSVLTTHGIEWYB#SAC
.PA.N.PA.N.PA.N.PA.N02-018-28-84686)CVPC(niseRedirolhClynivyloPdetanirolhC
Tetrahydrofuran (THF), Stabilized 109-99-9 30 - 60 50 PPM Skin 100 PPM Skin 200 PPM 250 PPM Oral: 2880 mg/kg (rat) Inhalation 3 hrs.50 PPM 75 PPM
21,000 PPM (rat)
Methyl Ethyl Ketone (MEK)78-93-3 3 - 7 200 PPM 300 PPM 200 PPM 300 PPM Oral: 3.98 g/kg (rat) Inhalation 4 hrs.
Dermal: 8-10 mg/kg (rabbit) 4,000 PPM (rat)
,OLCLnoitalahnI,)tar(gk/gm0091:larOMPP05nikSMPP025-11-49-801enonaxeholcyC
Dermal: 1.0 g/kg (rabbit)4 hrs: 2000 PPM rat)
OLCLnoitalahnI)tar(gk/g57.9:larOMPP0001MPP057MPP057MPP00531-71-46-76enotecA
Dermal: 20 g/kg (rabbit)4 hrs: 16,000 PPM (rat)
All of the constituents of IPS adhesive products are listed on the TSCA inventory of chemical substances maintained by the US EPA and/or the Canadian Domestic
Substance List (DSL),or are exempt from such listings.
(A) Dupont and BASF mfg's Acceptable Exposure Limit (AEL)guidelines for 8 hour and 12 hour TWA, (B) Dupont/BASF recommended STEL for 15 minute TWA.
DOT,IATA,IMO/IMDG SHIPPING IN SNOITANGISEDDRAZAHLAICEPSNOITAMROF
Proper Shipping Name:Adhesives EXCEPTION: Case quantities of cement in
Hazard Class:3 containers of less than one liter may be HMIS NFPA HAZARD RATING
Identification Number:UN 1133 shipped as LIMITED QUANTITY or HEALTH:2 2 0 -MINIMAL
Packing Group:II CONSUMER COMMODITY, ORM-D FLAMMABILITY:3 3 1 -SLIGHT
ETAREDOM-210:YTIVITCAERdiuqiLelbammalF:deriuqeRlebaL
TDG INFORMATION SUOIRES-3EVITCETORP
TDG CLASS:FLAMMABLE LIQUID EREVES-4H-B:TNEMPIUQE3
SHIPPING NAME:ADHESIVES (TETRAHYDROFURAN)
)seitivitcagnidlew-tnevloslamronrof(nikS/dnaH,eyE=BIIGP,3311:REBMUNNU
WHMIS CLASSIFICATION:CONTROLLED PRODUCT H =Eye,Hand/Skin,Respiratory Protection and Impermeable Apron (splash/
CLASS B,DIVISION 2 immersion risks)
CLASS D,DIVISION 2B
SECTION III - PHYSICAL DATA
TNIOPGNIZEERF)C°/F°(TNIOPGNILIOBRODOECNARAEPPA
serhT(laerehtEdiuqilypurysmuidem,deR )C°59-(F°931-)C°75(F°331)MPP05-2=dloh
Based on Acetone
SPECIFIC GRAVITY @ 73°F ±3.6°(23°C ±2°) VAPOR PR )%(EMULOVYBELITALOVTNECREP).gHmm(ERUSSE
%08-07:xorppAgniliobtsrifnodesab.gHmm091040.0±0.1lacipyT
component,Acetone @ 68°F (20°C)
RETAWNIYTILIBULOS)1=CAUB(ETARNOITAROPAVE)1=riA(YTISNEDROPAV
.retawnielbulosyletelpmocnoitroptnevloS0.1>94.2
Resin portion separates out.
NOITAMROFNIHPNOITUBIRTSIDLIO/RETAWFOTNEICIFFEOC
.PA.N.VA.N
VOC STATEMENT Maximum VOC emissions as applied and tested per SCAQMD Rule 1168,Test Method 316A:490 grams/liter. After drying and curing there are negligible or no emissions.
BlazeMaster®
TFP-500 One Step Solvent Cement
MSDS (Material Safety Data Sheet)
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page of 4 JUNE, 2008 TFP990
514
OFFSET
C.P.V.C. - STEEL- COPPER
HANGER
SIZE
MATERIAL
FINISH
PATENT No. 6,648,278.
FUNCTION
INSTALLATION
WOOD
#905
STEEL
FEATURES
#905
ORDERING
906
- 3/4" thru 2"pipe.
- Carbon Steel.
- Mil. Galvanized..
-
- To support horizontal piping - C.P.V.C.,Copper or Steel.
Hanger and restrainer in listed mounting positions - Top,Bottom or Side.
Provides stability on vertical piping.
- Per N.F.P.A13,13R and 13D on
top,bottom or side of building element. Space by pipe type.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
in :
CPVC pipe - screw- no pre-drill.
Copper pipe -
Steel pipe - 1/4 x11/2 lag screw - no pre-drill.
in :
* 1 1/2 Offset.
* 3/4 and 1” pipe size a e common center-line.
* Leg design produces superior strength.
* Offset edge eliminates abrasion.
* Required screw has 5/16" hex head - included
- Part # and pipe size.
# sold separately.
AFCON
AFCON
LISTINGS -
EX 4231, EX 2551
906
FASTENERS
#905
On 3/8" wood web use # backing nuts. - see drawing.
- UL Listed per NFPA13
screw- no pre-drill.
""
CPVC pipe - 1/4" or #14 Tek Screw.
Copper pipe - 1/4" or #14 Tek Screw.
Steel pipe - 1/4" or #14 Tek Screw.
"
" m d with
4/04
1 1/2”
CAD
FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET
No. 19–1.5
TD915
4–1.1.20
9/2001
TYCO FIRE PRODUCTS
451 North Cannon Avenue
Lansdale, Pennsylvania 19446
www.tyco-fire.com
TECHNICAL SERVICES
TEL: (800) 381-9312 • FAX: (800) 791-5500
E-MAIL: techserv@tycofp.com
Part No. Size Sch. T/O Wt.
80000 3/4"405/8"0.11 lb.
80001 1" 40
3/4"0.19 lb.
80002 1
1/4"40 7/8"0.26 lb.
80003 1
1/2"801"0.51 lb.
80004 2" 80 1
3/8"0.90 lb.
80005 2
1/2"8019/16"1.59 lb.
80006 3" 80 1
11 /16"2.41 lb.
Tee
Part No. Size Sch. T/O Wt.
80025 3/4"409/16"0.09 lb.
80026 1" 40
3/4"0.14 lb.
80027 1
1/4"40 7/8"0.21 lb.
80028 1
1/2"8011/16"0.40 lb.
80029 2" 80 1
1/4"0.79 lb.
80030 2
1/2"8011/2"1.14 lb.
80031 3" 80 1
13/16"1.82 lb.
90° ElbowReducing
90° Elbow
CrossReducing
Cross
Part
Size Sch.
T/O Wt.
No. 1 2 lb.
80015 1" x
3/4"40 11/16"11/16"0.28
Part No. Size Sch. T/O Wt.
80009 3/4"409/16"0.13 lb.
80010 1" 40
15/16"0.23 lb.
80011 1
1/4"4015/16"0.34 lb.
80012 1
1/2"8011/16"0.67 lb.
80013 2" 80 1
3/8"1.00 lb.
80014 2
1/2"8019/16"1.91 lb.
80008 3" 80 1
13/16"2.89 lb.
Part No. Size Sch. T/O Wt.
80050 3/4"403/8"0.08 lb.
80051 1" 40
3/8"0.11 lb.
80052 1
1/4"40 3/4"0.20 lb.
80053 1
1/2"80 7/16"0.31 lb.
80054 2" 80
3/4"0.56 lb.
80055 2
1/2"80 3/4"0.89 lb.
80056 3" 80 1" 1.19 lb.
45° Elbow
Fittings
Nom.Pipe Size Avg. O.D. Inches Avg. I.D. Inches Wt. Lbs./Ft.Wt. H2O filled Pipe Lbs./Ft.Ft. of Pipe per Lift Wt. per Lift Lbs.
3/4"1.050 0.874 0.17 0.43 7875 1413
1" 1.315 1.101 0.26 0.67 5040 1320
11/4"1.660 1.394 0.42 1.07 2835 1191
11/2"1.900 1.598 0.55 1.40 2205 1136
2" 2.375 2.003 0.86 2.20 1260 1063
2 1/2"2.875 2.423 1.26 3.22 1215 1531
3" 3.500 2.952 1.87 4.79 720 1344
Introduction
2
2
11
T/O
T/O
T/O T/O
Part
Size Sch.
T/O Wt.
No. 1 2 lb.
80032 1" x
3/4"40 11/16"13/16"0.16
Pipe
Technical Data
Tyco Fire Products (TFP) BlazeMaster®CPVC pipe and
fittings are designed exclusively for use in wet pipe
automatic fire sprinkler systems. They are made from a
specially developed thermoplastic compound composed of
post chlorinated polyvinyl chloride (CPVC) resin and state of
the art additives. TFP BlazeMaster
®CPVC products are
easier to install than traditional steel pipe systems, and at
the same time, they provide superior heat resistance and
strength as compared to traditional CPVC and PVC piping
materials used in the plumbing trade. Various adapters are
available to connect CPVC pipe to metallic piping. All female
pipe thread adapters have brass inserts for durability.
Grooved adapters connect directly to grooved end valves
and metallic pipe, with flexible grooved end couplings.
Sizes:3/4"– 3"
Maximum Working Pressure:175 psi
Approvals:UL, FM, CUL, NSF, Dade County, LPCB,
MEA, and the City of Los Angeles
Note:See current TFP BlazeMaster Installation Instructions and
Technical Manual, for exact listing/approval information
Manufacture Source:U.S.A.
Material:
Pipe:ASTM F442, SDR 13.5
Fittings:ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80)
Color:Orange
PRINTED IN USA PAGE 1 OF 4MFG. #5401205 - REV G
9/09
VSR-SG
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
AND GLUE-IN UNION
FOR CPVC PIPE
General Information
The Model VSR-SG is a vane type waterfl ow switch for use on wet
sprinkler systems using CPVC plastic fi ttings (manufactured by Tyco,
Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1”,
1 ¼”, 1 ½”, or 2” pipe sizes. It is equipped with a union to accommodate
installation in confi ned spaces.
The VSR-SG contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a fl ow of 10 GPM (38 LPM) or more
occurs downstream of the device. The fl ow condition must exist for a
period of time necessary to overcome the selected retard period.
UL, CUL and CSFM Listed
Service Pressure: Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Conduit Entrances: Two openings provided for 1/2" conduit.
Individual switch compartments suitable
for dissimilar voltages.
Environmental Specifi cations:
• NEMA 4/IP54 Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fi tting.
• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
• Installation must be performed by qualifi ed personnel and in
accordance with all national and local codes and ordinances.
• Shock hazard. Disconnect power source before servicing. Serious
injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
injury or death could result.
Specifi cations subject to change without notice.
Stock Number: 1144460
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
Enclosure
The VSR-SG switches and retard device are enclosed in a general
purpose, die-cast housing. The cover is held in place with two tamper
resistant screws which require a special key for removal. A fi eld
installable cover tamper switch is available as an option which may
be used to indicate unauthorized removal of the cover. See bulletin
number 5401103 for installation instructions of this switch.
Waterfl ow switches that are monitoring wet pipe sprinkler systems shall
not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterfl ow switches used for this
application may result in unintended discharges caused by surges,
trapped air, or short retard times.
Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833 • www.pottersignal.com
Thread
Size
Sprinkler
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)F C F C
1 2 NPT
(R1 2)
155
175
68
79 175 (12)
100
150
38
66 4.9 2.25 (57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R351616 x 16 (4.9x4.9) 13 (49) 7.0 (0.48)
18 x 18 (5.5x5.5) 17 (64 3) 12.0 (0.83)
20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)
Deflector - to - ceiling
Maximum 1 (25mm) to 4 (100mm)
3.
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fitting to
ceiling
Inch (mm)
F1 3 4 (19.0)Min.=3 4 (19.1)
Max.=11 2 (38.1)
3 16 -15 16 (4.7 - 24.0)
F2 1 2 (12.7)Min.=15 16 (23.8)
Max.=11 2 (38.1)
3 16 -1116 (4.7 - 17.4)
Escutcheon*, F1 or F2, Data:
*Note:Escutcheons F1 or F2 may be used with
Model F1 Res 49 & 58 Recessed Pendent Sprinkler
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)
R3516
14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73)
16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83)
18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0)
20 x 20 (6.1x6.1) 22 (83.2) 20.2 (1.4)
*Deflector - to - ceiling
Maximum 4 (100mm) to 8 (203mm)
*Note:The F1 Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1. Maximum beam depth = 7 (178mm)
2.Beamspacingatorgreaterthan7.5ft.(2.3m)oncenter.
Technical Data: F1 Res 49 Pendent and Recessed Pendent
Thread
Size
Sprinkler
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)F C F C
½NPT
(R½)
155
175
68
79 175 (12)
100
150
38
66 5.8 2.25 (57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Ceiling -to-
Deflector
Inch (mm)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53)
1-4
(25-100)R3513
14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53)
16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)
20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0)
Technical Data: F1 Res 58 Pendent and Recessed Pendent
•Model F1 Res 49 Recessed
Pendent / FP
•Model F1 Res 49 CCP
Pendent
4.
Fig. 4
Fig. 3
Thread
Size
Sprinkler
Temp.
Rating
CCP
Assembly
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)
F C F°C F C
½NPT
(R½)155 68 135 57 175 (12)
100
150
38
66 4.9 2.25 (57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R3516
14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)
16 x 16 (4.9x4.9) 14 (53) 8.2 (0.56)
18 x 18 (5.5x5.5) 18 (68.1) 13.5 (0.93)
20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)
“A”
Cover Adjustment
Inch (mm)
“B”
CCP Height
Inch (mm)
1 2 (12.7)15 16 (24)
3 16 (4.7)3 4 (19)
CCP Options Data:
FP Position
“A”
Inch (mm)
Max. Recessed
7 16 (11)
Min. Recessed
15 16 (24)
FP Data “A”:
FP push-on/thread-off
escutcheon
Technical Data: F1 Res 49 CCP and FP
Note:Sprinklers shown in Fig. 3 and Fig. 4 are not
suitable for installation in ceilings which have
positive pressure in the space above.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F3QR
Quick Response
Dry Sprinklers Bulletin 157 Rev. HBulletin 157 Rev. H
Features
The Model F3QR sprinkler utilizes Belleville Spring
Closure Technology. Reliable is the first in the industry
to produce a Quick Response Dry Concealed sprin-
kler utilizing this technology.
Styles available
Pendent
Recessed FP Pendent
Recessed F1 Pendent
Concealed
Horizontal Sidewall
Recessed FP Horizontal Sidewall
Recessed F1 Horizontal Sidewall
1½” (38mm) escutcheon adjustment on pendent sprinkler.
½” (13mm) escutcheon adjustment on recessed sprin-
kler with push-on/ thread-off FP Model Escutcheon ring.
3/8” (9.5mm) cover plate adjustment on concealed
sprinkler with push-on/ thread-off CCP Cover Plate.
3/4” (19mm) escutcheon adjustment on recessed
sprinkler with F1 Escutcheon.
Attractive appearance. Employs 3mm frangible glass
bulb and galvanized nipple.
Lengths available to accommodate installation di-
mensions from 2” - to - 48” (51mm - to - 1219mm), in
¼” (6mm) increments.
Available in a variety of plated and painted finishes.
Polyester Coated Corrosion Resistant Sprinklers.
US Patent Numbers 5,775,431 and 5,967,240.
Approvals
Listed by Underwriters Laboratories Inc. and UL Cer-
tified for Canada (cULus)
Style Response
Sprinkler
System Type Hazard
Pendent
Recessed Pendent
Recessed F1 Pendent
CCP Concealed
(R5714)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
Ordinary
Horizontal Sidewall
Recessed Horizontal Sidewall
(R5734)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
Certified by FM Approvals
Style Response
Sprinkler
System Type Hazard
Pendent
Recessed F1 Pendent
(R5714)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
Ordinary,
Groups
1&2
Horizontal Sidewall
Recessed F1 Horizontal Sidewall
(R5734)
Quick
Wet Pipe
Dry Pipe
All Preaction
Light
NYC MEA 258-93-E
1.
2.
•
•
•
•
•
•
•
3.
4.
5.
6.
7.
8.
9.
10.
1.
2.
3.
Concealed
(See Fig. 4)
Recessed FP Pendent
(See Fig. 3)
Recessed F1
Horizontal Sidewall
(See Fig. 9)
Horizontal Sidewall
(See Fig. 6)
Pendent
(See Fig. 1)
Recessed F1 Pendent
(See Fig. 5)
Recessed FP
Horizontal Sidewall
(See Fig. 8)
Pendent / HB
(See Fig. 2)
Horizontal Sidewall / HB
(See Fig. 7)
Technical Specifications
Style: Sidewall and Recessed Sidewall
Threads: 1/2" NPT or IS07-1 R1/2
Nominal K -Factor: 4.4 (63 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F(68°C)
175°F(79°C)
Recessed Escutcheons
F2 Recessed
FV Recessed
Sprinkler Wrenches
Model W2
Model GFR2 (Recessed)
Model F1 Res44 Horizontal Sidewall Sprinkler Installation Dimensions
Face of fitting
to finished wall 211 (51 mm)
1/2" (13mm) +/- 1/4" (6mm)
+/- 1/4" (6mm)
2-1/2"
2-1/4" 1-15/16"
Top of Deflector Down from
(57mm) (49mm) -- - --- Ceiling to Either 4" to 6"
DIA. DIA. (100 to 1500 mm) or 6" to 12"
(150 to 300 mm) Based on
5/16" Hydraulic Calculations
1/2" (13mm) (8mm)
Dimensions F2 & FV Recessed Escutcheon Installation
Model F1 Res44 Horizontal Sidewall Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe SystemsM
Maximum Coverage Areae
ft. x ft. (m x m)
Flow Pressure
gpm (1/min) psi (bar)
Deflector to
Ceiling Distance
12 x 12 (3.7 x 3.7)
12 (45) 7.5 (0.52)
4 to 6 inches
(100 to 150 mm)
14 x 14 (4.3 x 4.3)
14 (53) 10.2 (0.70)
15 x 15 (4.6 x 4.6)
15 (57) 11.6 (0.80)
16 x 16 (4.9 x 4.9)
16 (61) 13.3 (0.92)
16 x 18 (4.9 x 5.5)
18(68) 16.8(1.16)
16 x 20 (4.9 x 6.1)
23 (87) 27.4(l.89)
18 x 18 (5.5 x 5.5)
19 (72) 18.7(l.29)
12 x 12 (3.7 x 3.7)
14 (53) 10.2 (0.7)
6 to 12 inches
(150 to 300 mm)
14 x 14 (4.3 x 4.3)
16(61) 13.2(0.91)
15 x 15 (4.6 x 4.6)
16 (61) 13.2 (0.91)
16 x 16 (4.9 x 4.9)
17 (64) 15.0 (1.03)
16 x 18 (4.9 x 5.5)
20 (76) 20.7(l.43)
16 x 20 (4.9 x 6. 1)
23(87) 27.4(1.89)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Reliable Page 10 of 15