Tahoma Terra Apts Bld C Yelm13R Layout 1 (1)2ND FLOOR
SCALE 1/8"- 1'-0'
ALL PIPE TO BE 1 "CPVC UNLESS OTHERWISE NOTED.
SPRINKLER COVERAGE TO BE 18' X 18'
8' MAX OFF WALLS WITH 2 SPRINKLERS OR MORE WITHIN
THE COMPARTMENT
9' MAX OFF WALLS WERE A SINGLE SPRINKLER COVERS
THE COMPARTMENT
INSULATION TENTING DETAIL
General Notes
1. OWNER TO PROVIDE ADEQUATE HEAT (40°F. MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING.
2. CPVC PIPE SHALL HAVE HANGERS 6'-0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD.
3. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING. GARAGE LEVEL PIPING TO BE REVERSE TENTED TO PREVENT
FREEZING.
4. ALL PIPING TO BE 1" C.P.V.C. U.N.O.
3RD FLOOR/
N D FLOOR
1 . L %J
TO 3RD FLOOR/
FROM 2ND FLOOR
N
WATER FLOW
INDICATOR
N
N
PRESSURE /
GAUGE
11
FDC PIPING TO STREET SIDE OF
DOGHOUSE
\CHECK VALVE
DRAIN VALVE
W — DRAIN PIPED TO EXTERIOR
1.5" AMES 20008—FP BACKFLOW
PREVENTER
12
13
2"
\ 60'
N
SPRINKLER RISER
Sprinkler Symbol Legend both sheets total
SYM SPRINKLER ORIFICE SIZE, TYPE & FINISH
RELIABLE F1 RES 49 18'x18'
RELIABLE F1 RES 49 18'x18'
8" WATER MAIN
2.5" FDC FACING STREET
2" SUPPLY PIPING 60'
8" WATER MAIN 13
QUAN TEMP K FA(
155° 4.9
175° 1 4.9
V I Reliable F 3 QR DRY Sidewall 1 1 155' 1 5.6
TOTAL
DATE: 5/20/2022
3RD FLOOR
SCALE 1/8"— 1"-0"
1.25" FKUM 2ND
FLOOR
1.25"
TO 2ND FLOOR/
FROM UNDERGROUND
ACROSS BREEZWAY
EVERGREEN RE PROTECTION INC.
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone: (253) 252-7942
REV: I DRAWN: MH I SHEET: 1 OF 2
Sheet Title
0 2ND FLOOR
1 it TO 2ND FLOOR
Stamp
•------------------------
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
FIRE PROTECTION SPRINKLER SYSTEMS
Michael D. Hutchinson
i 1166 -40599 -BG Level
i
Evergreen Fire Protection. Inc
i EE GF 7LZ
a i
i
�
� �
Exp+res
i Signature*
DEC 31,22
NFPA 1,3R rPLAN
Tchomc Terra Apts. Bld C
e 14 3 01 TA HOMA BLVD S-Iff
Ye Im Wa..