Tahoma Terra Apts Bld D Yelm13R Layout 1 (1)SCALE 1 /8"— 1"-0" ALL PIPE TO BE 1 "CPVC UNLESS OTHERWISE NOTED. SPRINKLER COVERAGE TO BE 18' X 18' 8' MAX OFF WALLS WITH 2 SPRINKLERS OR MORE WITHIN THE COMPARTMENT 9' MAX OFF WALLS WERE A SINGLE SPRINKLER COVERS THE COMPARTMENT INSULATION TENTING DETAIL General Notes 1. OWNER TO PROVIDE ADEQUATE HEAT (40°F. MIN) TO PREVENT SPRINKLER PIPES FROM FREEZING. 2. CPVC PIPE SHALL HAVE HANGERS 6'-0" c\c AND NOT MORE THAN 6" FROM ANY SPRINKLER HEAD. 3. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT FREEZING. GARAGE LEVEL PIPING TO BE REVERSE TENTED TO PREVENT FREEZING. 4. ALL PIPING TO BE 1" C.P.V.C. U.N.O. '0 3RD FLOOR/ vA 2ND FLOOR I .LJ TO 3RD FLOOR/ FROM 2ND FLOOR FDC PIPING TO STREET SIDE OF DOGHOUSE \CHECK VALVE N WATER FLOW INDICATOR N DRAIN VALVE N PRESSURE / GAUGE 11 v — DRAIN PIPED TO EXTERIOR 1.5" AMES 2000B—FP BACKFLOW PREVENTER 12 31= 13 / g" WATER MAIN 2" 60' N SPRINKLER RISER Sprinkler Symbol Legend both sheets total SYM SPRINKLER ORIFICE SIZE, TYPE & FINISH RELIABLE F1 RES 49 18'x18' RELIABLE F1 RES 49 18'x18' 2.5" FDC FACING STREET 2" SUPPLY PIPING 60' 8" WATER MAIN 13 QUAN TEMP K FA( 96 155° 4.9 175° 1 4.9 V I Reliable F 3 QR DRY Sidewall 1 24 1 155' 1 5.6 TOTAL DATE: 5/20/2022 SCALE 1/8"= 1"-0" 1 1.25" FROM 2ND FLOOR FLOOR 1" TO 2ND FLOOR I1 3.02 IR 1.25" 1 - - , . ..I I TO 2ND FLOOR/ L- �I FROM UNDERGROUND Stamp ACROSS BREEZWAY 1 ST FLOOR SCALE 1/8"— 1"-0" EVERGREEN RE PROTECTION INC. PO BOX 998 Puyallup, WA 98371 EVERGFP967LZ Phone: (253) 252-7942 REV: I DRAWN: MH I SHEET: 1 OF 2 ------------------------�--, WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Michael D. Hutchinson i 1166 -40599 -BG Level i Evergreen Fire Protection. Inc i EE GF 7LZ a i i � � � +res i Signature* �E-P DEC 31.22 Sheet Title NFPA 13R =IRE PLAN Tchomc Terra ,Apt. Bld D e 14 3 01 TA HOMA BLVD S-Iff Ye Im Wa..