15 Apartments (Yelm) - MSMANUFACTURER'S DATA SHEETS (Material Submittal) Prepared For 15 Unit Apartments 315 Washington St SW Yelm, WA 98597 Authority Having Jurisdiction CITY OF YELM Prepared By: Najeeb Habib Columbia Fire Inc. 111 South Findlay St. Seattle WA 98108 Phone: (206) 232-8569 Fax (206) 340-6100 Columbia Fire Project #:2108192 TABLE OF CONTENTS 15 UNIT APARTMENTS 1.PIPING 2.FITTINGS / COUPLINGS 3.VALVES AND BACKFLOW PREVENTION 4.SPRINKLER HEADS AND ACCESSORIES 5.PIPE HANGERS 6.ELECTRICAL / FIRE ALARM COMPONENTS 7.MISCELLANEOUS EQUIPMENT 1.PIPING BLAZEMASTER CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet Page 1 of 2 APRIL 2016 TFP1915 Worldwide Contacts www.tyco-fire.com General Description TYCO CPVC Pipe and Fittings pro- duced by Tyco Fire Protection Prod- ucts (TFPP) are designed exclusively for use in wet pipe automatic fire sprinkler systems. The TYCO CPVC Pipe and Fittings are produced from BLAZEMASTER CPVC compound that is a specially developed thermo- plastic compound composed of post chlorinated polyvinyl chloride (CPVC) resin and state of the art additives. TYCO CPVC Pipe and Fittings are easier to install than traditional steel pipe systems, and at the same time, provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapt- ers are available to connect CPVC pipe to metallic piping. All female pipe thread adapters have brass inserts for durability. Grooved adapters connect directly to grooved end valves and metallic pipe, with flexible grooved end couplings. NOTICE The CPVC Pipe and Fittings produced with BLAZEMASTER CPVC compound described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Technical Data Sizes 3/4 Inch thru 3 Inch Maximum Working Pressure175 psi Approvals UL and C-UL Listed FM Approved LPCB Approved NSF Certified MEA Approved City of Los Angeles (Refer to Installation Handbook IH-1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.S.A. MaterialPipe: ASTM F442, SDR 13.5 Fittings: ASTM F438 (Sch. 40) ASTM F439 (Sch. 80) ASTM F1970 ColorOrange Installation TYCO CPVC Pipe and Fittings are to be to be installed in accordance with Installation Handbook IH-1900 dated April 2016. GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 TFP1915 Page 2 of 2 Copyright © 2016 Tyco Fire Products, LP. All rights reserved. BLAZEMASTER is a trademark of The Lubrizol Corporation. Care and Maintenance TYCO CPVC Pipe and Fittings are to be maintained and serviced in accordance with this section. Before closing a fire protection system control valve for inspection or main- tenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must first be obtained from the proper authorities and all person- nel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni- toring proprietary and/or central station alarms. The owner is responsible for the inspec- tion, testing, and maintenance of their fire protection system and de-vices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any authority having juris- diction. Contact the installing contrac- tor or product manufacturer with any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com 2.FITTINGS / COUPLINGS Sprinkler Head Adapters CPVC System Quick Reference Guide BRASTICTM Adapter Tee with metal thread insert This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking's technical documentation and always consult with the AHJ. Viking makes no representation or warranty as to whether following this guide will satisfy any rule or requirement. Please visit www.vikinggroupinc.com for the most current technical data and product specifications. All products must be installed in accordance with the manufacturer's current installation instructions. Viking reserves the right to change product specifications at any time without notice and without incurring obligation. Female Adapter with metal thread insert * Brass starter thread molded into plastic, virtually eliminating cross-threading. Straight 90º Elbow Tee 3/4 x 1/2 V5003SBT-101 100 1 x 1/2 V5003SBT-130 50 1 x 3/4 V5003SBT-131 50 3/4 x 1/2 V50073SBT-101 100 1 x 1/2 V50073SBT-130 50 1 x 3/4 V50073SBT-131 50 1 x 1 x 1 V5012SBT-101 50 1 x 1 x 1/2 V5012SBT-130 50 1 x 1 x 3/4 V5012SBT-010 50 Size (inches)Part Number Box Qty Spigot Female Adapter with metal thread insert 3/4 x 1/2 V5003SBI-101 100 1 x 1/2 V5003SBI-130 50 1 x 3/4 V5003SBI-131 10 3/4 x 1/2 V50032SBI-101 100 1 x 1/2 V50032SBI-130 50 3/4 x 1/2 V50073SBI-101 100 1 x 1/2 V50073SBI-130 50 1 x 3/4 V50073SBI-131 10 1-1/4 x 1/2 V50073SBI-166 5 Back to Back Cross with metal thread insert Back to Back Tee with metal thread insert 1 x 1 x 1 V5012SBI-010 50 3/4 x 3/4 x 1/2 V5012SBI-101 10 1 x 1 x 1/2 V5012SBI-130 50 1-1/4 x 1-1/4 x 1/2 V5012SBI-166 5 1-1/2 x 1-1/2 x 1/2 V5012SBI-209 5 2 x 2 x 1/2 V5012SBI-247 2 1 x 3/4 x 1/2 V5012RSBI-124 10 1-1/4 x 1 x 1/2 V5012RSBI-156 5 1-1/2 x 1-1/4 x 1/2 V5012RSBI-199 5 2 x 1-1/2 x 1/2 V5012RSBI-237 2 Size (inches)Part Number Box Qty 1 x 1 x 1/2 x 1/2 (1-1/8)V50353SBIS-130 20 1 x 1 x 1/2 x 1/2 (1-5/16)V50353SBIL-130 1 1/2 x 1/2 x 1 (1-1/8)V501133SBIS-075 30 1/2 x 1/2 x 1 (1-5/16)V501133SBIL-075 30 Sprinkler Head 90 with metal thread insert CPVC System Quick Reference Guide 2 CPVC System Quick Reference Guide 3 November 2014 November 2014 CPVC Standard Fittings Tee Bushing Reducing Tee 3/4 x 3/4 x 1 V5011R-102 10 1 x 3/4 x 3/4 V5011R-125 100 1 x 3/4 x 1 V5011R-126 10 1 x 1 x 3/4 V5011R-131 100 1-1/4 x 1 x 3/4 V5011R-157 5 1-1/4 x 1 x 1 V5011R-158 25 1-1/4 x 1 x 1-1/4 V5011R-159 5 1-1/4 x 1-1/4 x 3/4 V5011R-167 25 1-1/4 x 1-1/4 x 1 V5011R-168 25 1-1/4 x 1-1/4 x 1-1/2 V5011R-169 5 1-1/2 x 1-1/4 x 3/4 V5011R-201 5 1-1/2 x 1-1/4 x 1 V5011R-202 5 1-1/2 x 1-1/2 x 3/4 V5011R-210 25 1-1/2 x 1-1/2 x 1 V5011R-211 25 1-1/2 x 1-1/2 x 1-1/4 V5011R-212 5 1-1/2 x 1-1/2 x 2 V5011R-213 5 2 x 2 x 3/4 V5011R-248 2 2 x 2 x 1 V5011R-249 10 2 x 2 x 1-1/4 V5011R-250 2 2 x 2 x 1-1/2 V5011R-251 2 2-1/2 x 2-1/2 x 1 V5011R-289 1 2-1/2 x 2-1/2 x 1-1/4 V5011R-290 1 2-1/2 x 2-1/2 x 1-1/2 V5011R-291 1 2-1/2 x 2-1/2 x 2 V5011R-292 1 3 x 3 x 1-1/2 V5011R-337 1 3 x 2 V5011R-338 1 3 x 2-1/2 V5011R-339 1 Size (inches)Part Number Box Qty 1 x 3/4 V5018-131 100 1-1/4 x 3/4 V5018-167 25 1-1/4 x 1 V5018-168 25 1-1/2 x 3/4 V5018-210 5 1-1/2 x 1 V5018-211 25 1-1/2 x 1-1/4 V5018-212 25 2 x 3/4 V5018-248 2 2 x 1 V5018-249 2 2 x 1-1/4 V5018-250 2 2 x 1-1/2 V5018-251 2 2-1/2 x 1 V5018-289 15 2-1/2 x 1-1/4 V5018-290 1 2-1/2 x 1-1/2 V5018-291 1 2-1/2 x 2 V5018-292 1 3 x 1-1/2 V5018-337 15 3 x 2 V5018-338 1 3 x 2-1/2 V5018-339 1 90º Elbow 45º Elbow Cap Cross Coupling Reduced Coupling 3/4 V5011-007 250 1 V5011-010 100 1-1/4 V5011-012 25 1-1/2 V5011-015 25 2 V5011-020 2 2-1/2 V5011-025 1 3 V5011-030 1 3/4 V5007-007 250 1 V5007-010 100 1-1/4 V5007-012 25 1-1/2 V5007-015 25 2 V5007-020 2 2-1/2 V5007-025 1 3 V5007-030 1 1 x 3/4 V5007R-131 100 3/4 V5006-007 250 1 V5006-010 100 1-1/4 V5006-012 5 1-1/2 V5006-015 5 2 V5006-020 2 2-1/2 V5006-025 1 3 V5006-030 1 3/4 V5017-007 250 1 V5017-010 100 1-1/4 V5017-012 5 1-1/2 V5017-015 5 2 V5017-020 2 2-1/2 V5017-025 1 3 V5017-030 1 3/4 V5035-007 10 1 V5035-010 100 1-1/4 V5035-012 5 1-1/2 V5035-015 20 2 V5035-020 1 2-1/2 V5035-025 1 1 x 1 x 3/4 x 3/4 V5035R-131 10 3/4 V5001-007 250 1 V5001-010 100 1-1/4 V5001-012 25 1-1/2 V5001-015 25 2 V5001-020 10 2-1/2 V5001-025 1 3 V5001-030 1 1 x 3/4 V5001R-131 10 1-1/4 x 1 V5001R-168 5 1-1/2 x 3/4 V5001R-210 5 1-1/2 x 1 V5001R-211 5 1-1/2 x 1-1/4 V5001R-212 5 2 x 1 V5001R-249 2 2 x 1-1/2 V5001R-251 2 Size (inches)Part Number Box Qty CPVC Pipe Grooved Coupling Adapter 1-1/4 V5001G-012 30 1-1/2 V5001G-015 25 2 V5001G-020 15 2-1/2 V5001G-025 4 3 V5001G-030 2 3/4 34PIPE 240 1 1PIPE 180 1-1/4 114PIPE 105 1-1/2 112PIPE 75 2 2PIPE 60 2-1/2 212PIPE 30 3 3PIPE 15 3/4 V50032BI-007 250 1 V50032BI-010 100 1/2 V450-005 50 N/A V5097 24 N/A V5096 12 3/4 V5033E-007 1 1 V5033E-010 1 Quart V5097Q 12 Pint V5097P 12 Small V5093-S 100 Large V5093-L 100 3/4 V5003BI-007 10 1 V5003BI-010 50 1-1/4 V5003BI-012 5 1-1/2 V5003BI-015 5 2 V5003BI-020 2 3/4 V5004BI-007 10 1 V5004BI-010 10 1-1/4 V5004BI-012 5 1-1/2 V5004BI-015 5 2 V5004BI-020 2 Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty CPVC Transition Fittings Accessories Female Adapter with metal thread insert Male Adapter with metal thread insert Spigot Female Adapter with metal thread insert Test Plug Roller Brush Standard Union Solvent Cement Dauber CPVC System Quick Reference Guide 2 CPVC System Quick Reference Guide 3 November 2014 November 2014 CPVC Standard Fittings Tee Bushing Reducing Tee 3/4 x 3/4 x 1 V5011R-102 10 1 x 3/4 x 3/4 V5011R-125 100 1 x 3/4 x 1 V5011R-126 10 1 x 1 x 3/4 V5011R-131 100 1-1/4 x 1 x 3/4 V5011R-157 5 1-1/4 x 1 x 1 V5011R-158 25 1-1/4 x 1 x 1-1/4 V5011R-159 5 1-1/4 x 1-1/4 x 3/4 V5011R-167 25 1-1/4 x 1-1/4 x 1 V5011R-168 25 1-1/4 x 1-1/4 x 1-1/2 V5011R-169 5 1-1/2 x 1-1/4 x 3/4 V5011R-201 5 1-1/2 x 1-1/4 x 1 V5011R-202 5 1-1/2 x 1-1/2 x 3/4 V5011R-210 25 1-1/2 x 1-1/2 x 1 V5011R-211 25 1-1/2 x 1-1/2 x 1-1/4 V5011R-212 5 1-1/2 x 1-1/2 x 2 V5011R-213 5 2 x 2 x 3/4 V5011R-248 2 2 x 2 x 1 V5011R-249 10 2 x 2 x 1-1/4 V5011R-250 2 2 x 2 x 1-1/2 V5011R-251 2 2-1/2 x 2-1/2 x 1 V5011R-289 1 2-1/2 x 2-1/2 x 1-1/4 V5011R-290 1 2-1/2 x 2-1/2 x 1-1/2 V5011R-291 1 2-1/2 x 2-1/2 x 2 V5011R-292 1 3 x 3 x 1-1/2 V5011R-337 1 3 x 2 V5011R-338 1 3 x 2-1/2 V5011R-339 1 Size (inches)Part Number Box Qty 1 x 3/4 V5018-131 100 1-1/4 x 3/4 V5018-167 25 1-1/4 x 1 V5018-168 25 1-1/2 x 3/4 V5018-210 5 1-1/2 x 1 V5018-211 25 1-1/2 x 1-1/4 V5018-212 25 2 x 3/4 V5018-248 2 2 x 1 V5018-249 2 2 x 1-1/4 V5018-250 2 2 x 1-1/2 V5018-251 2 2-1/2 x 1 V5018-289 15 2-1/2 x 1-1/4 V5018-290 1 2-1/2 x 1-1/2 V5018-291 1 2-1/2 x 2 V5018-292 1 3 x 1-1/2 V5018-337 15 3 x 2 V5018-338 1 3 x 2-1/2 V5018-339 1 90º Elbow 45º Elbow Cap Cross Coupling Reduced Coupling 3/4 V5011-007 250 1 V5011-010 100 1-1/4 V5011-012 25 1-1/2 V5011-015 25 2 V5011-020 2 2-1/2 V5011-025 1 3 V5011-030 1 3/4 V5007-007 250 1 V5007-010 100 1-1/4 V5007-012 25 1-1/2 V5007-015 25 2 V5007-020 2 2-1/2 V5007-025 1 3 V5007-030 1 1 x 3/4 V5007R-131 100 3/4 V5006-007 250 1 V5006-010 100 1-1/4 V5006-012 5 1-1/2 V5006-015 5 2 V5006-020 2 2-1/2 V5006-025 1 3 V5006-030 1 3/4 V5017-007 250 1 V5017-010 100 1-1/4 V5017-012 5 1-1/2 V5017-015 5 2 V5017-020 2 2-1/2 V5017-025 1 3 V5017-030 1 3/4 V5035-007 10 1 V5035-010 100 1-1/4 V5035-012 5 1-1/2 V5035-015 20 2 V5035-020 1 2-1/2 V5035-025 1 1 x 1 x 3/4 x 3/4 V5035R-131 10 3/4 V5001-007 250 1 V5001-010 100 1-1/4 V5001-012 25 1-1/2 V5001-015 25 2 V5001-020 10 2-1/2 V5001-025 1 3 V5001-030 1 1 x 3/4 V5001R-131 10 1-1/4 x 1 V5001R-168 5 1-1/2 x 3/4 V5001R-210 5 1-1/2 x 1 V5001R-211 5 1-1/2 x 1-1/4 V5001R-212 5 2 x 1 V5001R-249 2 2 x 1-1/2 V5001R-251 2 Size (inches)Part Number Box Qty CPVC Pipe Grooved Coupling Adapter 1-1/4 V5001G-012 30 1-1/2 V5001G-015 25 2 V5001G-020 15 2-1/2 V5001G-025 4 3 V5001G-030 2 3/4 34PIPE 240 1 1PIPE 180 1-1/4 114PIPE 105 1-1/2 112PIPE 75 2 2PIPE 60 2-1/2 212PIPE 30 3 3PIPE 15 3/4 V50032BI-007 250 1 V50032BI-010 100 1/2 V450-005 50 N/A V5097 24 N/A V5096 12 3/4 V5033E-007 1 1 V5033E-010 1 Quart V5097Q 12 Pint V5097P 12 Small V5093-S 100 Large V5093-L 100 3/4 V5003BI-007 10 1 V5003BI-010 50 1-1/4 V5003BI-012 5 1-1/2 V5003BI-015 5 2 V5003BI-020 2 3/4 V5004BI-007 10 1 V5004BI-010 10 1-1/4 V5004BI-012 5 1-1/2 V5004BI-015 5 2 V5004BI-020 2 Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty Size (inches)Part Number Box Qty CPVC Transition Fittings Accessories Female Adapter with metal thread insert Male Adapter with metal thread insert Spigot Female Adapter with metal thread insert Test Plug Roller Brush Standard Union Solvent Cement Dauber CPVC System Quick Reference Guide 4 Viking | 210 N Industrial Park Drive, Hastings, MI 49058, Telephone: (269) 945-9501, Facsimile: (269) 945-9599 | www.vikinggroupinc.com MKT-1089 November 2014 Recommended Installation Practices and Precautions for Freedom® CPVC Systems • Install product according to the manufacturer’s instructions. • Follow recommended safe work practices. • Make certain that thread sealants, gasket lubricants, or fire stop materials are compatible with BlazeMaster® CPVC. • Use only latex-based paints if painting is desired. • Keep pipe and fittings in original packaging until needed. • Cover pipe and fittings with an opaque tarp if stored outdoors. • Follow proper handling procedures. • Use tools designed for use with plastic pipe and fittings. • Use proper solvent cement and follow application instructions. • Use a drop cloth to protect interior finishes. • Cut the pipe ends square. • Deburr and bevel the pipe end before solvent cementing. • When solvent cementing, rotate the pipe 1/4 turn when bottoming pipe in fitting socket. • Always apply solvent cement to the pipe first then fitting. • Avoid puddling of solvent cement in fittings and pipe. • Make certain that solvent cement does not run and plug the sprinkler head orifice. • Follow the manufacturer’s recommended cure times prior to pressure testing. • Fill lines slowly and bleed the air from the system prior to pressure testing. • Support sprinkler head properly to prevent lift up of the head through the ceiling when activated. • Keep threaded rod within 1⁄16” of the pipe. • Install BlazeMaster CPVC pipe and fittings in wet systems only or specially listed dry systems. • Follow manufacturer'hs recommendations for freeze protection. • Allow for movement due to expansion and contraction. • Renew your BlazeMaster CPVC pipe and fittings installation training every two years. • Follow manufacturer’s recommendations on pressure testing. • Follow current NFPA standards for use of antifreeze solutions. • Do not use petroleum or solvent-based paints, sealants, lubricants or fire stop materials. • Do not use any glycol-based solutions as an anti-freeze. • Do not use both Teflon® tape and thread sealants simultaneously. • Do not use solvent cement that exceeds its shelf life or has become discolored or gelled. • Do not allow solvent cement to plug the sprinkler head orifice. • Do not connect rigid metal couplers to BlazeMaster® CPVC grooved adapters. • Do not thread BlazeMaster CPVC pipe. • Do not use solvent cement near sources of heat, open flame, or when smoking. • Do not pressure test until recommended cure times are met. • Do not use dull or broken cutting tool blades when cutting pipe. • Do not use BlazeMaster CPVC pipe that has been stored outdoors unprotected and is faded in color. • Do not allow threaded rod to come in contact with the pipe. • Do not install BlazeMaster CPVC pipe in cold weather without allowing for expansion. • Do not install BlazeMaster CPVC pipe and fittings in dry systems, unless specifically Listed for such use. • Do not use ratchet cutters below 50˚F. • Do not use edible oils such as Crisco® as a gasket lubricant. • Do not install tape, insulated wire, or cable in direct contact with BlazeMaster CPVC pipe. Note: This list does not constitute as a complete installation guide. Dos Don'ts Blazemaster® is a registered trademark of Lubrizol Teflon® is a registered trademark of E. I. du Pont de Nemours and Company Crisco® is a registered trademark of the J.M. Smucker Company Regional Headquarters Viking SupplyNet - U.S. East 4B Cranberry Rd Parsippany, NJ 07054 Phone: 800-845-4645 Fax: 269-818-1639 Viking SupplyNet - U.S. South 100 Piedmont Court, Suite A Doraville, GA 30340 Phone: 800-234-2443 Fax: 770-446-3713 Viking SupplyNet - U.S. Midwest 2353 International St Columbus, OH 43228 Phone: 800-926-7757 Fax: 614-527-5818 Viking SupplyNet - U.S. West 9101 Sorensen Ave. Santa Fe Springs, CA 90670 Phone: 800-366-1727 Fax: 562-944-1058 Viking SupplyNet - Latin America 2840 SW 42nd St, Port 95 Ind Ctr Blg IV Hollywood, FL 33312 Phone: 954-791-1756 Fax: 954-791-1614 Viking SupplyNet - Canada 325 Vaughan Valley Blvd. Woodbridge, Ontario L4H 3B5 Phone: 905-856-3557 Fax: 905-856-3558 3.VALVES AND BACKFLOW PREVENTION Brass •Integral Seats with Brass Body and Disc •Swing Check •Threaded Ends Features Working Pressures Working Pressure Non-Shock (psi) Test Pressure (psi) Cold Water, Oil, Gas Body Cap Disc Bolt Pin Sealing Gasket Brass Brass Brass Brass Brass PTFE 1 2 3 4 5 6 No. Part Material Material Specifications 200 WOG 80 80 Shell (Air) Seat (Air) Part No. Size Dimensions are in inches A B Weight (Ibs) Description Brass Swing Check Valve, FNPT 10F322 10F323 10F324 10F325 10F326 10F327 1/2 3/4 1 1 1/4 1 1/2 2 2.067 1.299 0.512 0.401 2.382 1.417 0.709 0.546 2.835 1.614 0.906 0.826 3.228 1.969 1.181 1.359 3.740 2.244 1.417 1.861 4.213 2.638 1.772 2.754 6 4 ∅2 1 5 A B3 1 5 2 3 6 4 Swing Check Valve F • Max. Pressure: 200 PSI WOG • Max. Temp.: 180 1" Model 8000 1" Model 8011 1½" – 2" Model 8011 Grooved 1½" – 2" Model 8000 Thread x Groove 1¼" – 2" Model 8000 Threaded Reliability, Versatility, Code Compatibility SS-M8000M8011-V003 · 02/22 TESTa n DRAIN® and Re m o t e TEST® are registered trademarks of AGF Manufacturing Inc. Reliability, Versatility, Code Compatibility Model 8000/8011 r e s i d e n t i a lri s e r PaCK™ Pre-Assembled TESTa n DRAIN® Riser Sizes: 1"1¼"1½"2" The AGF Re s i d e n t i a l Ri s e R PACK™ Model 8000/8011 is a prepackaged economical riser assembly designed for NFPA 13D and 13R residential fire sprinkler systems. The one-piece casting provides required NFPA signage on both sides allowing for left or right installation and are available with grooved, threaded, or thread x groove ends. Threaded ends allow for easy connection to metal or plastic piping systems and grooved ends use approved rubber gasket couplings for secure connections. Complies with NFPA requiements regarding testing• through a properly sized test orifice 1" Models are available to meet nominal K-factor• requirements of 2.8 to 5.6 1" 8000 Models utilize a ¾" ball valve with patented• TESTa n DRAIN® orifice specific outlet designed to accept either a standard garden hose or hard piped drain line 1¼", 1½", and 2" Models are available with orifices to• meet K-factors of 2.8 to 11.2 1¼", 1½", and 2" 8000 Models utilize a UL Listed/FM• Approved Model 3011BV In s p e c t o R 'sTEST™ ball valve Cast and machined bronze made in the U.S.A.• Includes UL Listed/FM Approved AGF Model 7500• Pressure Gauge (300 PSI); 13R Models also include Model 7600 3-Way Globe Valve Available as the Model 8011 with UL Listed/FM• Approved Model 7000 Pressure Relief Valve (1¼"-2") or Model 7200 Pressure Relief Valve (1") designed to provide relief, test, and drain through a single valve 3• ⁄8", 7⁄16", ½", 17⁄32", and 5⁄8" (ELO) orifice sizes Larger size risers are available on special order• Note: UL and FM standards for sprinkler system pressure relief valves require relief valves to operate within a range of their ratings. FM requires a relief valve to oPeN at a pressure no less than 85% of their rating and UL requires oPeNING at a pressure no greater than 105% of their rating. Both standards require the relief valves to CLoSe within a percentage below oPeN. Choose the relief valve comparing static pressure to 90% of the relief valve's rating to determine the estimated minimum oPeNING and 80% of the relief valve's rating for approximate maximum CLoSING. the relief valve should be installed where it is easily accessible for maintenance. Care should be taken that the relief valve CANNot be isolated from the system when the system is operational. A relief valve should NeVeR have a shutoff valve or a plug downstream of its outlet. A B CD A B C D A B CD A B C D 14 5 5 5 5 4 4 4 2 6 6 7 3 3 8 9 9 10 11 10 12 13 14 15 16 16 17 1 1 1 Job Name:__________________________________ Architect: ___________________________________ Engineer: ___________________________________ Contractor: _________________________________ USA Patent and Other Patents Pending AGF Manufacturing Inc. 100 Quaker Lane, Malvern, PA 19355 Phone: 610-240-4900 Fax: 610-240-4906 www.agfmfg.com 1" Model 8000 1" Model 8011 1¼"-2" Model 8000 1¼"-2" Model 8011 Dimensions Model SIZE A B C D Model 80001"101⁄2" (267 mm) 121⁄4" (311 mm) 43⁄4" * (121 mm) 61⁄4" (159 mm) 11⁄4"11" (279 mm) 121⁄4" ** (311 mm) 4" (102 mm) 61⁄2" (165 mm) 1½"12" (305 mm) 121⁄2" ** (317 mm) 41⁄8" (105 mm) 65⁄8" (168 mm) 2"12" (305 mm) 13" (329 mm) 43⁄8" (111 mm) 67⁄8" (174 mm)Model 80111"101⁄2" (267 mm) 121⁄4" (317 mm) 27⁄8" *** (73 mm) 61⁄4" (159 mm) 11⁄4"143⁄4" (375 mm) 15" (381 mm) 4" (102 mm) 61⁄2" (165 mm) 1½"151⁄4" (387 mm) 151⁄4" (387 mm) 41⁄8" (105 mm) 65⁄8" (168 mm) 2"151⁄4" (387 mm) 153⁄4" (399 mm) 43⁄8" (111 mm) 67⁄8" (174 mm) *Additional space may be necessary to allow for hard drain fitting if required **Valve handle clearance required - add 2" ***LIft handle clearance required - add 31⁄8" Components Item No.Part Qty. 1 RiserPACK - Bronze Casting 1 2 ¾" Male x Female Ball Valve 1 3 1" M3011BV In s p e c t o r ’stest Valve 1 4 M7500 Pressure Gauge (¼" 3-Way Globe Valve Included for 13R Systems Only) 1 5 Water Flow Alarm Switch 1 6 ¾" MNPT x ½" FNPT Hose Adaptor Orifice 1 7 M7200 ¾" Pressure Relief Valve 1 8 M7000 ½" Pressure Relief Valve 1 9 1" Brass Nipple 1 10 1" Brass Street Elbow 1 11 ½" Brass System Access Port Plug 1 12 1" Relief Valve Bypass Nipple 1 13 1" Relief Valve Bypass Tee 1 14 ½" NPT x-Barb Straight Fitting 1 15 ½" NPT x-Barb Elbow Fitting 1 16 Clamps 2 17 Nylobraid Relief Valve Drain Tubing 1 Model 8000/8011 r e s i d e n t i a lri s e r PaCK™ Ames Fire & Waterworks product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measure- ments, please contact Ames Fire & Waterworks Technical Service. Ames Fire & Waterworks reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fire & Waterworks products previously or subsequently sold. Deringer TM 20 Double Check Valve Assembly Sizes: 2"**– 8" Job Name –––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location –––––––––––––––––––––––––––––––––––––––––– Approval –––––––––––––––––––––––––––––––––––––––––––––– Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––– Features • Intergral shutoff valves indoor/outdoor application • 100% stainless steel housing • Tamper-resistant test cocks • Patented Dual-actionTM check modules - Poppet action at low flow - Swing action at high flow • Silicone elastomer check discs • Prewired supervisory switches • Flange adapters available • IPS grooved ends Specifications The Deringer 20 Double Check Valve shall utilize two independent Dual-action check modules and two integral resiliently seated shut-off valves all of which shall be contained within a single rigid valve housing constructed entirely of 304 stainless steel. Both integral shutoff valves shall include pre-wired supervisory tamper switches contained within a weatherproof actuator hous- ing approved for both indoor and outdoor use. Dual-action check modules shall operate as a “poppet style” check under low flow conditions, operate as a “swing style” check under high flow conditions and utilize replaceable silicone elastomer sealing discs. Assembly test cocks shall be handle-less and operate via a tamper resistant actuator. Assembly shall have a single full access service port and cover with an “inline” replaceable elastomer seal. Assembly shall be serviceable without special tools and approved for both horizontal and vertical applications. LEAD FREE* *The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. NOTICE ES-A-Deringer 20 HORIZONTAL VERTICALApproved for Fire Protection, Waterworks, Plumbing, and Irrigation Applications. Materials Valve Housing: 304 Stainless Steel Valve Cover: 304 Stainless Steel SOV Disks: EPDM/304SS SOV Shafts: 304 Stainless Steel SOV Bearings: Teflon® fluoropolymer/Bronze Non-wetted Bolts: Grade 8 Zinc Plated Check Disks: Silicone (NSF) Wetted Fasteners: 18-8 Stainless Steel Check Springs: 17-7 Stainless Steel Check Pins: 17-7/18-8 Stainless Steel Check Seats: Noryl® Polymer (NSF) O-rings: Buna-N (NSF) Pressure — Temperature Temperature Range: 33°F – 140°F Working Pressure: 10 – 175psi The DeringerTM 20 Double Check Valve Assembly is designed to prevent non-health hazard pollutants from entering the potable water supply system caused by backpressure and/or backsiphonage conditions Teflon® is a registered trademark of The Chemours Company. Noryl® is a registered trademark of SABIC Global Technologies B.V. Size Model Ht Hb L D H W Weight ES-A-Deringer 20 1951 © 2020 Watts USA: Backflow T: (978) 689-6066 • F: (978) 975-8350 • AmesFireWater.com USA: Control Valves T: (713) 943-0688 • F: (713) 944-9445 • AmesFireWater.com Canada: T: (905) 332-4090 • F: (905) 332-7068 • AmesFireWater.ca Latin America: T: (52) 55-4122-0138 • AmesFireWater.com Dimensions — Weights Flow Performance in.in. mm in. mm in. mm in. mm in. mm in. mm lbs kg 2 (21⁄2)** 20 7.1 180 2.9 74 22.3 566 0.0 0 10.0 254 11.0 279 52 24 21⁄2 20 7.1 180 2.9 74 18.7 475 0.0 0 10.0 254 11.0 279 38 17 3 20 7.4 188 2.9 74 18.7 475 0.0 0 10.3 262 11.0 279 40 18 4 20 7.9 201 2.9 74 18.7 475 0.2 5 10.3 262 11.0 279 42 19 6 20 10.1 257 4.5 114 25 726 1.0 25 14.6 370 13.8 351 90 41 8 20 10.4 264 5.4 137 30.7 780 1.8 46 15.8 401 13.8 351 141 64 Ht Hb D L H WPressure Loss (psid)Pressure Loss (psid)* Specific orientation & agency flow characteristics available on website * Specific orientation & agency flow characteristics available on website Rate of Flow (gpm) Rate of Flow (gpm) Standards AWWA C510-07 Compliant NSF/ANSI 372, UL CERTIFIED LEAD FREE End Connections - IPS Groove for Steel Pipe: AWWA C606 - Flange Adapters: ANSI B16.1 Class 125 = Rated Flow = UL Tested = 15 fps **2" size utilizes a 2 ½" assembly with 2 ½" groove to 2" female NPT adapter and couplings. Adapter and couplings ship unassembled. 4.SPRINKLER HEADS AND ACCESSORIES freedom® residential concealed pendent sprinkler vk494 (k4.9) tecHnical data the viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com visit the viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 1 of 5 Form No. F_012116 18.04.12 Rev 18.1 1. description Viking Freedom® Residential Concealed Pendent Sprinkler VK494 is a small thermosensitive, glass-bulb residential sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The orifice design, with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler’s efficient use of available water supplies for the hydraulically designed fire-protection system. The fast response glass bulb operating element and special deflector characteristics meet the challenges of residential sprinkler standards. The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile small-diameter cover assembly installed flush to the ceiling. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied, while also providing up to 1/2” (13 mm) of vertical adjustment. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is C-UL-US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. 2.listinGs and approvals Ul listed (c-Ul-Us-eU): Category VKKW Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing requirements that must be followed. 3.tecHnical dataSpecifications:Minimum Operating Pressure: Refer to the Approval Chart.Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPTNominal K-Factor: 4.9 U.S. (70.6 metric*)Glass-bulb fluid temperature rated to -65 °F (-55 °C) * Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. material standards:Sprinkler Body: Brass UNS-C84400 or QM BrassDeflector: Phosphor Bronze UNS-C51000Deflector Pins: Stainless Steel UNS-S30200Button: Brass UNS-C36000Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400Compression Screw: 18-8 Stainless SteelYoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-C51000Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeCover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc PlatingShipping Cap: Polyethylene cover plate materials:Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 or Stainless Steel UNS-S30400Spring: Beryllium NickelSolder: Eutecticordering information: (Also refer to the current Viking price list.)Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for thetemperature rating to the sprinkler base part number.Finish Suffix: Brass = A and ENT = JNTemperature Suffix: 155 °F (68 °C) = B, 200 °F (93 °C) = EFor example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.standard cover plates: Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16” diameter),or Base Part No. 15394 (square cover plate, 3-5/16”) stainless steel cover plates (not availble with any finish or paint): Base Part No. 21876 (2-3/4” diameter) or Base Part No. 21875 (3-5/16” diameter). Replaces Form No. F_012116 Rev 17.2 (added stainless steel cover plates) freedom® residential concealed pendent sprinkler vk494 (k4.9) tecHnical data the viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com visit the viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 2 of 5 Form No. F_012116 18.04.12 Rev 18.1 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number:Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/BTemperature Suffix: 135 °F/57 °C = A For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA. available finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the Viking website.)sprinkler Wrenches**:A. Heavy Duty Part No. 14047W/B** (available since 2006), orB. Head Cabinet Wrench Part No. 14031*** (available since 2006)C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007) **Requires a ½” ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets. sprinkler cabinet: Part No. 01731A (available since 1971) 4.installation Refer to appropriate NFPA Installation Standards. 5.operation During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand,causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. . Water flowing through the sprinklerorifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-sure at the sprinkler to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availability Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUaranteeFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. table 1: available sprinkler temperatUre ratinGs and finisHes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 temperature rating of the cover assembly (required)3 cover plate base part number4 large cover plate base part number4 square cover plate base part number4 bulb color Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) 13504 or 218766 13642 or 218756 15394 Red Intermediate 200 °F (93 °C) 150 °F (65 °C) 135 °F (57 °C) 13504 or 218766 13642 or 218756 15394 Green sprinkler finishes: Brass and ENT cover plate finishes6: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black corrosion resistant coatings5: ENT footnotes 1.The sprinkler temperature rating is stamped on the deflector. 2.Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3.Maximum ambient temperature for cover assembly is 100 °F (38 °C). 4.Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 5.The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring is exposed. 6.Stainless Steel versions are not available with any finishes or paint. freedom® residential concealed pendent sprinkler vk494 (k4.9) tecHnical data the viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com visit the viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 3 of 5 Form No. F_012116 18.04.12 Rev 18.1 approval chartviking vk494, 4.9 k-factor residential concealed pendent sprinkler for systems designed to nfpa 13d or nfpa 13r. for systems designed to nfpa 13, refer to the design criteria. for ceiling types refer to current editions of nfpa 13, 13r or 13d sprinkler base part number 1 sin npt thread size nominal k-factor maximum Water Wor- king pressureinchesmmU.s. metric 2 20759 VK494 1/2 15 4.9 70.6 175 psi (12 bar) max. coverage area 6 W X l ft. X ft. (m X m) flow Gpm (lpm) pressure psi (bar)Deflector to ceiling installation type listings and approvals3,5 minimum spacing ft. (m)155 °F (68 °C), 200 °F (93 °C) Temperature Rated Sprinklers 4 12 X 12 (3.7 X 3.7) 13 (49.2) 7.0 (0.48) Refer to Figure 2 Concealed with Cover Plate Assembly. See Footnote 8. See Footnotes 7,9, 10, & 11 8 (2.4) 14 X 14 (4.3 X 4.3) 13 (49.2) 7.0 (0.48) 16 X 16 (4.9 X 4.9) 13 (49.2) 7.0 (0.48) 18 X 18 (5.5 X 5.5) 17 (64.4) 12.0 (0.83) 20 X 20 (6.1 X 6.1) 20 (75.7) 16.7 (1.15) footnotes 1.Part number shown is the base part number. For complete part number, refer to current Viking price schedule. 2.Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3.This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. Refer also to Design Criteria. 4.Listed by Underwriter’s Laboratories, Inc. for use in the U.S., Canada, and European Union. 5.Meets New York City requirements, effective July 1, 2008. 6.For areas of coverage smaller than shown, use the “Flow” and “Pressure” for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum “Flow” and “Pressure” used. 7.Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate). 8.Other paint colors are available on request with the same listings as the standard finish colors. Stainless Steel cover plates are not available with any finishes or paint. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3. 9.Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 8. 10. C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT) 11. Stainless Steel Cover plate temperature rating is 135 °F (57 °C). Stainless Steel Cover Part Numbers: 218761 and 218751 (large diameter). freedom® residential concealed pendent sprinkler vk494 (k4.9) tecHnical data the viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com visit the viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 4 of 5 Form No. F_012116 18.04.12 Rev 18.1 desiGn criteria (Also refer to the Approval Chart on page 3.) Ul listing requirements (c-Ul-Us-eU): When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-age and minimum water supply requirements shown in the Approval Chart. For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: •The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or • Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13. •Minimum distance between residential sprinklers: 8 ft. (2.4 m). note: concealed sprinklers must be installed in neutral or negative pressure plenums only. important: always refer to bulletin form no. f_080415 - best practices for residential sprinkler Handling and installation. also refer to form no. f_080614 for general care, installation, and maintenance information. viking sprinklers are to be in-stalled in accordance with the latest edition of viking technical data, the appropriate standards of nfpa and any other similar authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. final approval and acceptance of all residential sprinkler installations must be obtained from the authorities Having Jurisdiction. sprinkler and adapter assembly •protective cap removed •Use wrench 14047W/b** step 1: carefully slide the wrench sideways around the deflector and pins sprinkler Wrench part no. 14047W/b** ** a 1/2” ratchet is required (not available from viking) 2-1/4” (57 mm) diameter opening required in the ceiling. step 2: carefully press the wrench upward and turn slightly to ensure engagement with the sprinkler wrench flats. figure 1: sprinkler installation and proper Wrench Usage never install the sprinkler by applying the installation wrench across the frame arms. do not overtighten. Use only the designated sprinkler wrenches, viking part numbers 14047W/b** or 14031**. a leak tight seal should be achieved by turning the sprinkler clockwise 1 to 1-1/2 turns beyond finger tight. sprinkler wrench flat sprinkler frame arms freedom® residential concealed pendent sprinkler vk494 (k4.9) tecHnical data the viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com visit the viking website for the latest edition of this technical data page www.vikinggroupinc.com Page 5 of 5 Form No. F_012116 18.04.12 Rev 18.1 figure 2: sprinkler dimensions and cover installation 1/2” (15 mm) npt 2-1/4”(58 mm)2-9/16” (65 mm)maximum 2-1/16” (52 mm)minimum 2-3/4” (70 mm) or 3-5/16” (84 mm)note: Upon sprinkler activation, the deflector descends to approximately 13/16” (21 mm) below the sprinkler body. figure 3: identification of custom paint for concealed covers All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates the custom color and will have a representative sample (a paint dot) of the paint on the label.FACTORY APPLIE D C USTO M P AI NT COLORfigure 4: square cover assembly 15394 3-5/16” (84 mm) Replaces Form No. F_012116 Rev 17.2 (added stainless steel cover plates) QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 1 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. DESCRIPTION Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers are designed for dry systems and preaction systems where it is necessary to prevent water or condensation from entering the drop nipple before sprinkler operation. They may also be installed in spaces subject to freezing and supplied from a wet system in an adjacent heated area. Viking Quick Response Dry HSW Sprinklers are available in various finishes and temperature ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indi- cated in the Approval Charts. (Note: FM Global has no approval classification for Polyester coatings as corrosion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Classes 2013 and 2015 NYC Approved: MEA 89-92-E, Volume 15 Refer to Approval Charts and Design Criteria for Listing and Approval that must be followed. 3. TECHNICAL DATA Specifications: Available since 1993. Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1” NPT or 25 mm BSPT Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths. * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -65 °F (-55 °C) Covered by the following U.S. Patent numbers: 8,636,075 and 8,376,060 and 10,220,231 Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Phosphor Bronze UNS-C51000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Compression Screw: Brass UNS-C36000 Pip Cap: Brass UNS-C31400 or UNS-C31600 Pip Cap Adapter: Brass UNS-C36000 Orifice: Copper UNS-C22000 or UNS-C11000 Tube: ERW Hydraulic Steel Tube Support (Internal): Stainless Steel UNS-S30400 Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish Barrel End and Threads: QM Brass Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800 Escutcheon Materials: Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800 Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080 ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400 Ordering Information: (Also refer to the current Viking price list.) Order QR Dry HSW Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix for the temperature rating, and then the suffix for the length (“A” dimension) to sprinkler base part number. Order in a specific length noted as the “A” dimension. The “A” dimension is the distance from the face of the fitting (tee) to the desired finished surface of the wall in which it is to be installed. These sprinklers are listed and approved in lengths from 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm) for the adjustable standard style, 3” to 47” (76.2 mm to 1,194 mm) for the plain barrel style, and 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm) for the adjustable recessed style. Lengths exceeding the standard lengths are available, with no approvals, on a “made-to-order” basis: Recessed Dry HSW up to 65- 1/2” (1,664 mm). Adjustable Standard Dry HSW up to 63-1/2” (1,613 mm). Plain Barrel Dry HSW up to 65” (1,651 mm). Contact the manufacturer for more information. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and ENT = JN For Light Hazard Occupancies Only Replaces Form No. F_031993 Rev 19.2 (Removed cover 15610.) QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 2 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G Escutcheon Suffix = Y for the adj. recessed sprinkler with the Model G-1 Escutcheon (no suffix needed for the Model E-1 Escutcheon). For example, sprinkler VK182 with 1” NPT Threads, a Chrome finish, a 155 °F (68 °C) temperature rating, the Model G-1 Escutcheon, and “A” length of 10” = Part No. 08386UFBY10. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the “Sprinkler Accessories” section.) Sprinkler Wrenches: A. Standard Wrench: Part No. 07297W/B (available since 1991) B. Wrench for recessed sprinklers: Part No. 07565W/B** (available since 1991) **A ½” ratchet is required (not available from Viking). Replacement Escutcheons: A. Adjustable Standard Dry Escutcheon: Base Part No. 08086F B. Model E-1 Recessed Dry Escutcheon Cup: Base Part No. 05459A C. Model G-1 Recessed Dry Escutcheon Cup: Base Part No. 20133 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the internal parts to open the water- way. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Quick Response Dry Horizontal Sidewall Sprinkler is available through a network of domestic and international distribu- tors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 155 °F (68 °C)100 °F (38 °C)Red Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)Green High 286 °F (141 °C)225 °F (107 °C)Blue Sprinkler Finishes: Brass, Chrome, White Polyester, and ENT Corrosion-Resistant Coating3,4: White Polyester and ENT in all temperature ratings Footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant Polyester and ENT coatings have passed the standard corrosion test required by the approving agencies indi-cated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Note: These coatings are NOT corrosion proof. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. Polyester and ENT coatings are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. 4 When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or tested as described in NFPA 25 on a more frequent basis. Figure 1: Standard Sprinkler Wrench 07297W/B QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 3 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 3: Adjustable Standard Dry Horizontal Sidewall Sprinkler Figure 4: Adjustable Standard Escutcheon Installation Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Horizontal Sidewall Sprinklers QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 4 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 1 (UL) Quick Response Dry Horizontal Sidewall Sprinklers For Light Hazard Occupancies Only Maximum 175 PSI (12 bar) WWP Sprinkler Base Part No.1 SIN Style Thread Size Nominal K-Factor2 Order Length Increment Listings and Approvals4 (Refer also to Design Criteria on page 106e.) NPT BSPT U.S.metric3 Inches mm cULus5 NYC6 VdS LPCB 08384U VK178 Adjustable Standard 1”--5.6 80.6 1/2”12.7 A1, A5 A1 -------- 16458U --25 mm --80.6 1/2”12.7 A1, A5 ---------- 08386U VK182 Adjustable Recessed 1”--5.6 80.6 1/4”6.35 B2, B6 B2 -------- 16454U --25 mm --80.6 1/4”6.35 B2, B6 ---------- 08388U VK174 Plain Barrel 1”--5.6 80.6 1/2”12.7 A3 A4 -------- 16456U --25 mm --80.6 1/2”12.7 A3 ---------- Approved Temperature Ratings A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C), and 286 °F (141 °C) B - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finishes and “A” Dimensions 1* - Chrome, or White Polyester7 sprinkler with a Chrome, Brass, or White Polyester Sleeve and Escutcheon with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm) 2* - Chrome, or White Polyester7 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm) 3 - Chrome, Brass, White Polyester7, or ENT7 with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm) 4 - Chrome or Brass with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm) 5 - ENT7 sprinkler with an ENT7 Sleeve and Escutcheon with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm) 6 - ENT7 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm) *Brass Finish is listed and approved but not standard offering, lead times of 6-8 weeks required. (Matching Brass escutcheons are not available.) Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths (“A” Dimensions indicated above). 3 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada for Light Hazard occupancies only. 6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 15. 7 cULus Listed as corrosion resistant. DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: Quick Response Dry Horizontal Sidewall Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edi- tion of NFPA 13 for standard spray sprinklers. • Limited to Light Hazard occupancies only. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft. (1.8 m). • Deflector must be positioned between 4” and 6” (102 mm and 152 mm) below the ceiling. Keep the top of the deflector oriented parallel with the ceiling. • Locate no less than 4” (102 mm) from end walls. • Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 5 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 2 (FM) Quick Response Dry Horizontal Sidewall Sprinklers For Light Hazard Occupancies Only Maximum 175 PSI (12 bar) WWP Sprinkler Base Part No.1 SIN Style Thread Size Nominal K-Factor2 Order Length Increment FM Approvals4 (Refer also to Design Criteria below.)NPT BSP U.S.metric3 Inches mm 08384U VK178 Adjustable Standard 1”--5.6 80.6 1/2”12.7 A1 16458U --25 mm --80.6 1/2”12.7 A1 08386U VK182 Adjustable Recessed 1”--5.6 80.6 1/4”6.35 B2 16454U --25 mm --80.6 1/4”6.35 B2 08388U VK174 Plain Barrel 1”--5.6 80.6 1/2”12.7 A3 16456U --25 mm --80.6 1/2”12.7 A3 Approved Temperature Ratings A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) B - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finishes and “A” Dimensions 1* - Bright Brass, Chrome, White Polyester, or ENT5 with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm) 2* - Bright Brass, Chrome, White Polyester, or ENT5 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm) 3 - Brass, Bright Brass, Chrome, White Polyester, or ENT5 “A” dimensions 3” to 47” (76.2 mm to 1,194 mm) *Brass Finish is listed and approved but not standard offering, lead times of 6-8 weeks required. (Matching Brass escutcheons are not available.) Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 K-Factor applies for standard lengths (“A” Dimensions indicated above). 3 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 4 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 FM approved as corrosion resistant. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: The Dry HSW Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including 2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflec- tor distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accord- ance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 6 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 6: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model G-1 Escutcheon Figure 5: Adjustable Recessed Dry Horizontal Sidewall Sprinkler with the Model E-1 Escutcheon QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 7 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 7: Quick Response Plain Barrel Dry Horizontal Sidewall Sprinkler QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERSTECHNICAL DATA Form No. F_031993 20.04.16 Rev 20.1 Page 8 of 8 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Figure 9: Dry Sprinkler Seal (Adjustable Standard Dry HSW Sprinkler is Shown) Figure 8: Dry Horizontal Sidwall Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area (Adjustable Standard Dry HSW Sprinkler is Shown) Replaces Form No. F_031993 Rev 19.2 (Removed cover 15610.) MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 1 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. DESCRIPTION Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The sprinkler is pre-assembled with a threaded adapter for installation with a low- profile cover assembly that provides up to ½” (12.7 mm) of vertical adjustment. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assem- bly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive environments and is cULus Listed as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approval: Class 2015 NYC Approved: MEA 89-92-E, Volume 32 VdS Approved: Certificate G4080021 LPCB Approved: Certificate number 096e/12 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40249 CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF) MED Certified: Standard EN 12259-1, EC-certificate 0832-MED-1003 Refer to Approval Chart 1 Design Criteria for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2006. Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by locating “250” stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 5.6 U.S. (80.6 metric†) Glass-bulb fluid temperature rated to -65°F (-55°C)Patents Pending *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). †Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Material Standards: Sprinkler Body: Brass UNS-C84400 Deflector: Copper UNS-C19500 for Sprinkler VK462 Phosphor Bronze UNS-C51000 for Sprinkler VK463Deflector Pins: Stainless Steel Alloy Bulb: Glass, nominal 3 mm diameter Replaces Form No. F_103005 Rev 18.1 (Updated MED approval.) MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 2 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Button: Brass UNS-C36000 Screws: 18-8 Stainless Steel Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon TapeYoke: Phosphor Bronze UNS-C51000 Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Cover Assembly Materials: Cover: Copper UNS-C11000 or Stainless Steel UNS-S30400 Base: Brass UNS-C26000 or UNS-C26800 Springs: Nickel AlloySolder: Eutectic Ordering Information: (Also refer to the current Viking price list.) Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately: Sprinkler: Base Part No. VK462 - 13503A for Brass finish and 13503JN for ENT finish. VK463 - HP Base Part No. 13667A Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number: Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E For example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667AB. Standard Cover Plate Assembly: Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16“ diameter), or Base Part No. 15394 (square cover plate, 3-5/16”) Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B Temperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPCB) = A, 165 °F (74 °C) = C For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 °C) temperature rating = 13504FC. Stainless Steel Cover Plates (not availble with any finish or paint): Base Part No. 21876 (2-3/4” diameter) or Base Part No. 21875 (3-5/16” diameter). Temperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPCB) = A, 165 °F (74 °C) = C For example, cover 21876 with a 165 °F (74 °C) temperature rating = 21876C NOTE: The cULus Listings for the square cover plate 15394 are for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Viking website.)Sprinkler Wrenches**: A. Heavy Duty Wrench Part No. 14047W/B (available since 2006), or B. Head Cabinet Wrench Part No. 14031*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover (available since 2007) **Requires a ½” ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets. Sprinkler Cabinet: Part No. 01731A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 3 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Temperature Rating of Cover Assembly (Required) Cover Plate Base Part Number3 Large Cover Plate Base Part Number3 Square Cover Plate Base Part Number3 Bulb Color Ordinary 155 °F (68° C)100 °F (38 °C)135 °F (57 °C) cULus 13504 or 218765 13642 or 218755 15394 Red139 °F (59 °C) FM and LPCB Intermediate 175 °F (79° C)150 °F (65° C)165 °F (74 °C)13504 or 218765 13642 or 218755 15394 Yellow Intermediate 200 °F (93° C)150 °F (65° C)165 °F (74 °C)13504 or 218765 13642 or 218755 15394 Green Cover Plate Finishes5: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Sprinkler Finishes: Brass and ENT Corrosion Resistant Coatings4: ENT Footnotes 1 The sprinkler temperature rating is stamped on the sprinkler deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 4 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-ible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway, but the Belleville spring is exposed. 5 Stainless Steel versions are not available with any finishes or paint. Figure 1: Identification of Custom Paint for Concealed Covers All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates the custom color and will have a representative sample (a paint dot) of the paint on the label.FACTORY APPLIE D C USTO M P AI NT COLORFigure 2: Square Cover Assembly 15394 3-5/16” (84 mm) MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 4 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Approval Chart 1 (UL) Mirage® Concealed Pendent Sprinklers VK462 and VK463 Sprinkler Base Part No.1 SIN Thread Size Nominal K-Factor Maximum Water Working Pressure Listings and Approvals4 (Refer also to Design Criteria) Inch mm U.S.metric2 cULus5 NYC VdS7 LPCB 12 Standard Response Applications 13503A VK462 1/2”--5.6 80.6 175 psi (12 bar)----AY1, CZ1 AY1, BZ1 AY1, CZ18 AY3 -- 19785A VK462 1/2”--5.6 80.6 175 psi (12 bar)------------AY2, CZ2 21356A VK462 --15 5.6 80.6 175 psi (12 bar)------------AY2, CZ2 Quick Response Applications 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AV1, BX1, AS3, BT3 AV1, BX16 ------AY3 -- 13503JN11 VK462 1/2”15 5.6 80.6 175 psi (12 bar)AV1, BX1, AS3, BT3 AV1, BX16 ---------- 13667A VK463 1/2”15 5.6 80.6 250 psi (17.2 bar)3 AV1, BX1 AV1, BX16 ---------- Sprinkler Temperature Ratings A - 155 °F (68 °C) B - 175 °F (79 °C) and 200 °F (93 °C) C - 200 °F (93 °C) Cover Plate Assembly Temperature Ratings1, 9 S - 135 °F (57 °C) cover 21876 or 21875 (large diameter) T - 165 °F (74 °C) cover 21876 or 21875 (large diameter) V - 135 °F (57 °C) cULus Listed cover 13504, 13642 (large diameter), or 15394 (square cover plate) X - 165 °F (74 °C) cover 13504, or 13642 (large diameter) Y - 135 °F (57 °C) cover 13504 LPCB Approved as 139 °F (59 °C) Z - 165 °F (74 °C) cover 13504 Cover Plate Assembly Finishes10 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 2 - Brass 3 - Stainless Steel Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 The Water Working Pressure rating is stamped on the deflector. 4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada. 6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32. 7 VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021. 8 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40249. 9 The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label. 10 Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. 11 cULus Listed as corrosion resistant. 12 MED Certified, Standard 12259-1, EC-certificate 0832-MED-1003. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 5 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERIA - UL (Also refer to Approval Chart 1) cULus Listing Requirements: Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below. •For hazard occupancies up to and including Ordinary Hazard, Group II. •Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m). •Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13. •Minimum distance from walls is 4 in. (102 mm). •Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measuredperpendicular to the wall. •The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed. NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. VdS Approval Requirements: a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials. b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight. c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-cies, except in OH4. NOTES: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system. Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling. The criterion for the dropping of the cover relevant for this approval is heat. Steps of installation: 1.Prepare the sprinkler key. 2.Remove the plastic cover. 3.Hold the sprinkler with the wrench and fasten it. 4.Replace the plastic cover and do not remove until the cover is installed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 6 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza- tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Approval Chart 2 (FM) Mirage®Standard Response Concealed Pendent Sprinkler VK462 Sprinkler Base Part No.1 SIN NPT Thread Size Nominal K-Factor Maximum Water Working Pressure FM Approvals3 (Refer also to Design Criteria below.)Inch mm U.S.metric2 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AW1, BX1 Sprinkler Temperature Ratings A - 155 °F (68 °C) B - 175 °F (79 °C) and 200 °F (93 °C) Cover Plate Assembly Temperature Ratings4 W - 139 °F (59 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) X - 165 °F (74 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) Cover Plate Assembly Finishes5 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label. 5 Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. Approval Chart 2 (FM) Mirage® Standard Response Concealed Pendent Sprinkler VK462 Sprinkler Base Part No.1 SIN NPT Thread Size Nominal K-Factor Maximum Water Working Pressure FM Approvals3 (Refer also to Design Criteria below.)Inch mm U.S.metric2 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AW1, BX1, AY2, BZ2 Sprinkler Temperature Ratings A - 155 °F (68 °C) B - 175 °F (79 °C) and 200 °F (93 °C) Cover Plate Assembly Temperature Ratings1, 4 Y - 139 °F (59 °C) cover 21875 or 21876 Z - 165 °F (74 °C) cover 21875 or 21876 W - 139 °F (59 °C) cover 13504, 13642 (large diameter), or 15394 (square cover plate) X - 165 °F (74 °C) cover 13504, 13642 (large diameter), or 15394 (square cover plate) Cover Plate Assembly Finishes5 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black 2 - Stainless Steel Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label. 5 Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA Form No. F_103005 18.07.24 Rev 18.2 Page 7 of 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com Sprinkler and Adapter Assembly •Protective cap removed •Use wrench 14047WB** Step 1: Carefully slide the wrench sideways around the deflector and pins Sprinkler Wrench Part No. 14047WB** ** A 1/2” ratchet is required (Not available from Viking) 2-1/4” (57 mm) diameter opening required in the ceiling. Step 2: Carefully press the wrench upward and turn slightly to ensure engagement with the sprinkler wrench flats. Figure 3: Sprinkler Installation and Proper Wrench Usage NEVER install the sprinkler by applying the installation wrench across the frame arms. DO NOT overtighten. Use only the designated sprinkler wrenches, Viking Part Numbers 14047WB** or 14031**. A leak tight seal should be achieved by turning the sprinkler clockwise 1 to 1-1/2 turns beyond finger tight. Sprinkler wrench flat Sprinkler frame arms Figure 4: Sprinkler Dimensions and Cover Installation 1/2” (15 mm) NPT 2-3/16”(55 mm)2-9/16” (65 mm)Maximum 2-1/16” (52 mm)Minimum 2-3/4” (70 mm) or 3-5/16” (84 mm)NOTE: Upon sprinkler activation, the deflector descends to approximately 13/16” (21 mm) below the sprinkler body. Replaces Form No. F_103005 Rev 18.1 (Updated MED approval.) 5.PIPE HANGERS Office/Manufacturing facility • 1375 SampSon ave. • Corona, Ca 92879 • ph: 951.737.5599 • Fax: 951.737.0330 custOMer service • 800.786.5266 www.tolco.com 38 www.tolco.com Revision 12/11/2009 Size Range — 3/4" thru 3" CPVC pipe Material — Pre-Galvanized Steel Function — Intended to perform as a hanger/restrainer to support CPVC piping used in automatic fire sprinkler systems. Fig. 23 can be installed on the top, bottom or side of a beam. The Fig. 23 also functions as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada (cUL) sizes 3/4" thru 2" to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge steel using (2) 1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features — Fig. 23 incorporates features which protect the pipe and ease installation. The flared edge design protects the CPVC pipe from any rough surface. It also incorporates snap restrain- ers allowing easier and faster installation. Easily attaches to the building structure using the two UL Listed hex head self thread- ing screws* furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish — Pre-Galvanized Order By — Figure number and pipe size * Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. Fig. 23 - Hanger for cpvc plastic pipe double Fastener Strap type dimensions • Weights cpvc Max. Hanger Fastener Hex Approx. pipe Size A B c Spacing (Ft.)Head Size Wt./100 3/4 31⁄8 19⁄16 13⁄16 51⁄2 5/16 9 1 33⁄8 111⁄16 13⁄16 6 5/16 9 11⁄4 43⁄16 23⁄32 13⁄16 61⁄2 5/16 11 11⁄2 47⁄16 27⁄32 13⁄16 7 5/16 12 2 47⁄8 27⁄16 13⁄16 8 5/16 15 21/2 109/32 211/16 13/16 Consult Factory 5/16 22 3 117/8 3 13/16 Consult Factory 5/16 25 Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 909.737.5599 • Fax: 909.737.0330 Distribution Center • 8790 Fruitridge Road • Sacramento, CA 95826 • Ph: 916.388.7800 • Fax: 916.388.1401 Manufacturing Facility • 4851 Homestead Road, Bldg. 118 • Houston, TX 77028 • Ph: 713.672.0058 • Fax: 713.672.0074 www.tolco.com 18 Fig. 24 Hanger For CPVC Plastic Pipe Double Fastener Strap Type - Side Mount Size Range – 3/4 thru 2 inch CPVC pipe. Material – Carbon Steel, Pre-Galvanized. Function – Intended to perform as a hanger/restrainer to support only CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom of a beam. The Fig. 24 can also function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals – Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) to support fire sprinkler piping. Meets and exceeds the requirements of N.F.P.A. 13, 13R, and 13D. Features – Figure 24 incorporates features which protect the pipe and ease installation. The flared edge design* protects the CPVC pipe from any rough surface. Easily attaches to the building structure using the two hex head self threading screws** furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre drilling of a pilot hole in wood is required. Finish—Pre-Galvanized. Order By – Figure number and CPVC pipe size. *Patent Pending ** Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. CPVC Pipe Size A B C Max. Hanger Spacing (Ft.) Fastener Hex Head Size Approx. Wt./100 3/4 2-5/16 1-5/32 1-3/16 5-1/2 5/16 9 1 2-5/8 1-5/16 1-3/16 6 5/16 9 1-1/4 3 1-1/2 1-3/16 6-1/2 5/16 11 1-1/2 3-1/4 1-5/8 1-3/16 7 5/16 12 2 3-11/16 1-27/32 1-3/16 8 5/16 15 Revision 5/24/2001 Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Clamps Fire Protection Solutions40 Fig. 28 - “Stand-Off” Hanger & Restrainer for CPVC Plastic Pipe & IPS Steel Pipe ** Size Range:— 3/4"(20mm)through 2"(50mm) Material:— Steel, Pre-Galvanized Function:— Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off" design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces. • Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation. • The "Stand-Off" design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"(7.9mm)extension socket eliminating impact tool damage to pipe. • Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4" x 1" tek type self drilling tapping screws. • UL Listed as a hanger and a restrainer for fire sprinkler piping. Approvals:— Underwriters Laboratory Listed in the USA (UL)and Canada (cUL)to support automatic fire sprinkler systems. May be installed into wood using fasteners supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint when installed on 3/8"(9.5mm)composite wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only. Order by:— Figure number and pipe size. Pat. # 7,455,268, Pat. # 7,832,248 ** With reduced spacing, consult factory. C A B Pipe Size ABCMax Hanger Approx. Spacing Wt./100 Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) lbs. (kg) 28-3/4 3/4"(20)31/32"(77.0)2"(50.8)31/2"(88.9)51/2 (1.67)18 (8.1) 28-1 1"(25)35/16"(84.1)23/16"(55.6)31/2"(88.9)6 (1.83)21 (9.5) 28-11/4 11/4"(32)35/8"(92.1)23/8"(60.3)31/2"(88.9)61/2 (1.98)23 (10.4) 28-11/2 11/2"(40)4"(101.6)21/2"(63.5)31/2"(88.9)7 (2.13)31 (14.0) 28-2 2"(50)41/2"(114.3)211/16"(68.3)35/8"(92.1)8 (2.44)34 (15.4) Hanger Application Hanger and Restraint Application Fig. 27B (2) RequiredFig. 27B (1) Required High Side of Hanger Application Fig. 29 TOLCO double offset hanger & restrainer for CPVC plastic pipe Function: Intended to perform as a hanger and restrainer for CPVC plastic fire sprinkler pipe. Provides double offset 1½" (38.1mm) x 1½" (38.1mm) from mounting surface. This design will ease installation by eliminating the need for wood block extension and allow retrofit attachment of hanger to sprinkler pipe. To install: Install using a rechargeable electric drill fitted with a 5/16" (8mm) socket attachment with the special #10 x 1" hex head self- threading screws provided. Install screws until they bottom out. Pipe can be “snapped” into hanger before or after installation of the screws to the mounting surface. Can be used as a single offset hanger by aligning “dimples” with top of mounting surface and utilizing two fasteners in any two of the three holes provided. Note: “Thumb tab” may be bent up to provide additional protection to the pipe but is not required for performance of the hanger / restrainer function. Follow us on social media to get the latest product and support information. Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com 13201 Dahlia Street, Suite 200 Fontana, CA 92337 United States Phone: 800-851-7415 © 2021 Eaton All Rights Reserved Printed in USA Publication No. IL309021EN SEIS-3 March 2021 B-Line Division Eaton.com/tolco Eaton is a registered trademark. All other trademarks are property of their respective owners. Seismic Instruction sheet Maximum hanger spacing required per NFPA 13 for CPVC plastic pipe Pipe size Hanger spacing 3/4" 5' 6" 1" 6' 0" 11/4" 6' 6" 11/2" 7' 0" 2" 8' 0" Meets and exceeds requirements of NFPA 13, 13R and 13D. US Patent No. 9,726,304 Can. Pat. No. 2618941 THUMB TAB (38.1mm) 1.5" 1.5" (38.1mm) (38.1mm) 1.5" 1.5" (38.1mm) FLUSH DOUBLE OFFSET SINGLE OFFSET (38.1mm)1.5" (38.1mm)1.5" 7.ELECTRICAL / FIRE ALARM COMPONENTS PRINTED IN USA PAGE 1 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For CE Marked (EN12259-5) / VdS Approved model use VSR-EU Service Pressure: 450 PSI (31 BAR) - UL Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL • Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 •Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. •Shock hazard. Disconnect power source before servicing. Serious injury or death could result. •Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. Ordering Information Nominal Pipe Size Model Part Number 2"DN50 VSR-2 1144402 2 1/2"DN65 VSR-2 1/2 1144425 3"DN80 VSR-3 1144403 3 1/2"-VSR-3 1/2 1144435 4"DN100 VSR-4 1144404 5"-VSR-5 1144405 6"DN150 VSR-6 1144406 8"DN200 VSR-8 1144408 Specifications subject to change without notice. Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com General Information The Model VSR is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering Information chart. The VSR may also be used as a sectional waterflow detector on large systems. The VSR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 2 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. NOTE: Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way. ADAPTER USE (2) 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm ±2mm MAX. DWG# 1146-1F Fig. 1 NOTE: For copper or plastic pipe use Model VSR-CF. Retard Adjustment The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms (Flowing water activates device in one direction only.) DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOWDIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered. Refer to the Compatible Pipe/Installation Requirements chart for size. Correct Incorrect Compatible Pipe/ Installation Requirements Model Nominal Pipe Size Nominal Pipe O.D. Pipe Wall Thickness Hole Size U-Bolt Nuts TorqueLightwallSchedule 10 (UL)Schedule 40 (UL)BS-1387 (LPC)DN (VDS) inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 1.25 + .125/- .062 33.0 ± 2.0 20 27 VSR-2 1/2 2.5 -2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 ---- VSR-2 1/2 -DN65 3.000 76.1 ------0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 2.00 ± .125 50.8 ± 2.0 VSR-3 1/2 3.5 -4.000 101.6 --0.120 3.05 0.226 5.74 ---- VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 -5.563 141.3 --0.134 3.40 0.258 6.55 ---- VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 --0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified technician should disable the alarm system. PRINTED IN USA PAGE 3 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 To remove knockouts: Place screwdriver at inside edge of knockouts, not in the center. DWG 1146-4 Fig. 2 Do not drill into the base as this creates metal shavings which can create electrical hazards and damage the device. Drilling voids the warranty. Fig. 4 Switch Terminal Connections Clamping Plate Terminal Fig. 3 Break out thin section of cover when wiring both switches from one conduit entrance. Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR is not recommended or advisable. A minimum flow of 10 GPM (38 LPM) is required to activate this device. Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig. 6 Mounting Dimensions DWG. 1146-14 3.50 in (89.0 mm) 2.34 in (59.4 mm) PIPE DIA. + 5.25 in (+ 133.4 mm) 5.56 in (141.2 mm)2.00 in (50.8 mm) U-BOLT NUT U-BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U-BOLT NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in DWG 1146-15 GREEN GROUND SCREWS Fig. 7 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate. Notes: 1. The Model VSR has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 4). Fig. 5 Typical Electrical Connections LOAD TO BELLNEUTRAL FROM BELL CONNECTOR EOL (End Of Line Resistor) BELLNEUTRAL FROM BREAKER BREAKER LINE FROM BREAKER NOTE: When connecting to a UL Listed control panel, use the panel’s resistor value for circuit supervision. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 4 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Removal of Waterflow Switch • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Fig. 8 Retard/Switch Assembly Replacement (See Fig. 8) The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell (if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the (2) original mounting screws. 8. Reconnect all wires. Perform a flow test and place the system back in service. Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection. DWG# 1146-10 BREAK OUT THIN SECTION OF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. DO NOT REMOVE (2) RETARD HOUSING SCREWS REMOVE (2) ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE RETARD/SWITCH ASSEMBLY (2) ORIGINAL MOUNTING SCREWS (2) LOCATING PINS (2) LOCATING PIN BOSSES IN BASE BASE BELLS PBA-AC & PDC-DC 5400777 - REV A • 12/20 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description These vibrating type bells are designed for use as fire or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4” (101mm) square electrical box for indoor use or on a model BBK-1 or HC-BB weatherproof backbox for outdoor applications. Weatherproof backbox model BBK- 1 or HC-BB, Stock No. 1500001. Notes 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C) 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to PDC-DC bells. Technical Specifications Dimensions 6” (150mm), 8” (200mm) and 10” (250mm) Enclosure Cover: Steel Finish: Red Powder Coat Base: non-corrosive composite material All parts have corrosion resistant finishes Model BBK-1 or HC-BB weatherproof backbox (optional) Voltages Available 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Environmental Limitations Indoor or outdoor use (See Note 1) -40° to 150°F (-40° to 66°C) (Outdoor use requires weatherproof backbox.) Termination AC Bells - 4 No. 18 AWG stranded wires DC Bells - 18 AWG stranded wire Service Use NFPA 13, 72, local AHJ *Specifications subject to change without notice. Features • Listed for indoor and outdoor use • Outdoor use requires BBK-1 or HC-BB weatherproof back box • Indoor use mounts directly to standard 4” box • Low current draw • High dB output • AC and DC models • DC models are motor driven, polarized, and have built in transient protection for supervised alarm circuits • Available in 6”, 8” and 10” sizes In outdoor or wet installations, bell must be mounted with weatherproof backbox, BBK-1 or HC-BB. Standard electrical boxes will not provide a weatherproof enclosure. If the bell and/or assembly is exposed to moisture, it may fail or create an electrical hazard. • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. R * ULC on PDC-DC Only Size inches (mm) Voltage Model Number Stock Number Current (Max.) Typical dB at 10 ft. (3m) (2) Minimum dB at 10 ft. (3m) (1) 6 (150)12VDC PDC-6-12 1750500 200mA 96 76 8 (200)12VDC PDC-8-12 1750502 .200mA 96 77 10 (250)12VDC PDC-10-12 1750504 .200mA 96 78 6 (150)24VDC PDC-6-24 1750501 .20mA 95 77 8 (200)24VDC PDC-8-24 1750503 20mA 83 79 10 (250)24VDC PDC-10-24 1750505 20mA 85 80 6 (150)24VAC PBA246 1806024*.17A 91 78 8 (200)24VAC PBA248 1808024*.17A 94 77 10 (250)24VAC PBA2410 1810024*.17A 94 78 6 (150)120VAC PBA1206 1806120*.05A 92 83 8 (200)120VAC PBA1208 1808120*.05A 99 84 10 (250)120VAC PBA12010 1810120*.05A 99 86 All DC bells are polarized and have built-in transient protection. * Does not have ULC listing. *** ** FM on PBA-AC Only 5400777 - REV A • 12/20 PAGE 2 OF 2 Potter Electric Signal Company, LLC •St. Louis, MO •Phone: 800-325-3936 •www.pottersignal.com BELLS PBA-AC & PDC-DC Wiring Rear View Installation Bell Dimension Inches (mm) Fig 1 Fig 3 2 11/16” (68 mm)DWG# 776-1 10” (250 mm)8” (200 mm)6” (150 mm) 5 3/4” (146 mm) 1 5/8” (41 mm) DWG# 776-2 3 3/8” (86 mm) 4 1/4” (108 mm) 3 3/8” (86 mm) 5” (127 mm) Weatherproof Backbox Dimensions Inches (mm) Fig 2 The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90” AFF and not less than 6” below the ceiling. 1.Remove the gong. 2.Connect wiring (see Fig. 3). 3.Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 4.Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 5.Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction). MODEL BBK-1 OR HC-BBFailure to install striker down will prevent bell from ringing. NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS . NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS . 8.MISCELLANEOUS EQUIPMENT SPRINKLER WRENCHES AND CABINETSTECHNICAL DATA Page 1 of 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Form No. F_122598 18.10.11 Rev 18.1.P65 1. DESCRIPTION A. Sprinkler Cabinets Viking sprinkler cabinets are metal enclosures constructed to store an emergency supply of spare sprinklers and a sprinkler instal- lation wrench. NFPA 13 requires a representative number of each type and temperature rating of sprinkler head to be kept in a cabinet on the premises. NFPA 13 also requires a special sprinkler wrench to be provided in the cabinet. This allows for immediate removal and replacement of sprinklers that have operated or that have become damaged. Stock of spare sprinklers should include sprinklers of all the types and temperature ratings as are installed in the sprinkler system, in the following quantities: B. Sprinkler Wrenches Viking sprinkler wrenches are special installation tools specifically designed for use with the various Viking sprinklers and spray nozzles. The appropriate wrenches must be used with the indicated sprinklers and nozzles to provide the proper leverage when tightening sprinklers or nozzles and to minimize slippage during installation. Using wrenches other than the ones designated for installation may damage the sprinkler. Refer to Tables 2a and 2b and the ap- propriate sprinkler or spray nozzle data page for the correct installation wrenches that must be used. Wrenches 21475M/B, 10896W/B, 07297W/B, 05118CW/B, 13635W/B, and 16888M/B provide the amount of leverage needed to tighten sprinklers and spray nozzles into pipe fittings while preventing sprinkler damage. No additional tools are necessary with these wrenches. The following wrenches require a separate ½” ratchet (not available from Viking) to provide the correct amount of leverage: 08336W/B, 10366W/B, 07565W/B, 11663W/B, 13032W/B, 13577W/B, 13619, 15466, 13623W/B, 15467W/B, 15209W/R, 13655W/B, 14031, 14047W/B, 16208W/R, and 16267. The internal diameters of sprinkler wrenches 08336W/B, 10366W/B, 15209W/R, 16208W/R, and 16267 are designed for use with the sprinkler contained in the protective shell. (A protective shell should be retained in the spare sprinkler cabinet.) Wrench part number 10551W/B is required for threading institutional escutcheon plates onto institutional sprinklers. Wrench part number 10729 is a 2-1/2” (63.5 mm) C-C face spanner wrench used for removing institutional escutcheon plates from institutional sprinklers (refer to the DISASSEMBLY section of institutional sprinkler technical data pages). Wrench part number 15915 is optional for removing protective sprinkler caps and for installing E-1 and F-1 Escutcheons on frame style pendent sprinklers from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Refer to Technical Bulletin Form No. 051808. 2. LISTINGS AND APPROVALS Refer to the specific sprinkler or spray nozzle technical data pages for sprinkler listings and approvals. 3. TECHNICAL DATA Specifications: Sprinkler Cabinets: Designed with four 3/16” diameter holes in back. Spacing of mounting holes: 3-1/2” (88.9 mm) length, 3-1/2” (88.9 mm) height. The sprinkler cabinet should be located adjacent to the main system riser. Material Standards: Sprinkler Cabinets: Cold Rolled Steel. Finish: Painted high-gloss red enamel interior and exterior, chrome plated door knob. Wrenches: Ductile Iron, Steel, Acetal, or 50% glass filled nylon (for head cabinet wrenches) Ordering Information: (Also refer to the current Viking price list.) Number of Sprinklers in the System Minimum Number of Spare Sprinklers Required Under 300 6 300-1,000 12 Over 1,000 24 Replaces Form No. F_122598 Rev 18.1 (Added P65 Warning.) SPRINKLER WRENCHES AND CABINETSTECHNICAL DATA Page 2 of 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Form No. F_122598 18.10.11 Rev 18.1.P65 A. Sprinkler Cabinets 1. Determine appropriate cabinet from Table 1 on this page for use with the specific model/number of sprinklers to be contained in the cabinet. 2. Specify cabinet part number and quantity needed. B. Sprinkler Wrenches 1. Determine the appropriate wrench for use with the given sprinkler or spray nozzle model from Tables 2a and 2b. 2. Specify the wrench part number and quantity needed. NOTE: Sprinklers and sprinkler wrenches are not supplied with the cabinets; they must be ordered separately. 4. INSTALLATION Refer to the appropriate sprinkler or spray nozzle technical data page. 5. OPERATION Refer to the sprinkler or spray nozzle techical data page for the particular model used. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking sprinkler wrenches and cabinets are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Table 1: Sprinkler Cabinet Ordering Information and Dimensions For Sprinkler Models:Cabinet Capacity Cabinet Part No. Size Length Height Depth Viking frame style sprinklers 6 sprinklers 01724A Available since 1971. 10-3/16” (259 mm) 4-11/16” (103 mm) 2-9/16” (65 mm) Viking frame style sprinklers, ESFR K14 sprinklers, K16.8 pendent sprinklers, and K25.2 EC sprinklers 12 sprinklers (6 K25.2 EC sprinklers) 01725A Available since 1971. 10-3/16” (259 mm) 8-9/16” (217 mm) 2-9/16 (65 mm) Viking concealed and flush style sprinklers, ESFR K25.2 and K22.4 pendent sprinklers, and K19.6 CMSA sprinklers 5-6 sprinklers 01731A Available since 1971. 13-13/16” (351 mm) 5-11/16” (144 mm) 3” (76 mm) High Challenge® Sprinklers, upright ESFR sprinklers, and Intermediate Level Sprinklers 6 sprinklers 03985A Available since 1977 12-5/8” (321 mm) 9-1/8” (232 mm) 4-1/8” (105 mm) SPRINKLER WRENCHES AND CABINETSTECHNICAL DATA Page 3 of 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Form No. F_122598 18.10.11 Rev 18.1.P65 IMPORTANT NOTES The sprinkler cabinet should be easily accessible. The sprinkler cabinet must not be exposed to corrosive atmospheres or temperatures above 100 °F (38 °C). The stock of spare sprinklers should include an adequate number of sprinklers of each type and temperature rating. The stock of sprinklers must be in good condition. A sprinkler wrench of the appropriate type must be included in the cabinet. Orient sprinklers and sprinkler wrench as indicated in Figure 1 below. CAUTION: When replacing automatic sprinklers in an existing system, be sure to replace with sprinklers of the correct type, thread size, orifice size, temperature rating, and finish. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to the appropriate sprinkler data page. Viking sprinklers and spray nozzles are designed to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable. The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction prior to installation. Figure 2: Sprinkler Cabinet 01724A (Sprinklers and wrench not included) Figure 3: Sprinkler Cabinet 01725A (Sprinklers and wrench not included) Figure 1: Correct orientation of sprinklers and wrench inside cabinet. (12-head cabinet shown) SPRINKLER WRENCHES AND CABINETSTECHNICAL DATA Page 4 of 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Form No. F_122598 18.10.11 Rev 18.1.P65 Part No. 10896W/B Part No. 21475M/B Table 2a: Sprinkler Wrenches For Sprinkler Models:Use Wrench: Frame-style sprinklers and spray nozzles 21475M/B Available since 2017 Wax coated Frame-style sprinklers and spray nozzles 10896W/B Available since 2000 or 05000CW/B* Wax coated sprinklers and domed concealed pendent sprinklers 13577W/B Available since 2006 replaces 07398W* Recessed horizontal sidewall sprinklers with protective shields, domed concealed horizontal sidewall sprinklers, and recessed pendent sprinklers 13655W/B Available since 2006 Coated and recessed ECOH K14 sprinkler 13032W/B Available since 2004 Standard adjustable and plain barrel dry sprinklers, K16.8 and ECOH K14 sprinklers 07297W/B Available since 1991 Recessed and domed concealed dry sprinklers 07565W/B Available since 1991 High Challenge® sprinklers, upright ESFR sprinklers, and ELO sprinklers** 05118CW/B Available since 1981 Coated, recessed, and domed concealed ELO sprinklers 11663W/B Available since 2001 Pendent K14 and K16.8 ESFR sprinklers 13635W/B double ended (use Side A) Available since 2006, or 10285W/B* Pendent K25.2, K22.4 ESFR sprinklers and K19.6 CMSA Sprinkler VK592 13635W/B double ended (use Side B) Available since 2006, or 12143W/B* Upright EC K25.2 sprinklers 16888M/B Available since 2011 QR and EC Concealed Sprinklers VK461, VK462, VK463, VK464, VK465, VK632, and VK634 (also optional for cap removal) 14031† Available since 2006 QR and EC Concealed Sprinklers VK461, VK462, VK463, VK464, VK465, VK632, and VK634 14047W/B (heavy duty) Available since 2006 Residential Concealed Sprinklers VK456, VK457, VK474, and VK488 (also optional for removal of protective caps) 13619† (red) Available since 2006 * Wrench no longer available. May still be used until wrench replacement is necessary. * *ELO sprinklers manufactured before Dec. 2001 use wrench part number 07297W/B (07565W/B for coated and recessed). †Ideal for sprinkler cabinets. Part No. 07297W/B Part No. 13577W/B & 13032W/B Part Nos. 07565W/B & 11663W/B Part No. 05118CW/B Part No. 13635W/B Part No. 14031 Part No. 14047W/B Figure 4a: Sprinkler Wrenches Part No. 13655W/B Part No. 16888M/B SPRINKLER WRENCHES AND CABINETSTECHNICAL DATA Page 5 of 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Form No. F_122598 18.10.11 Rev 18.1.P65 Part No. 08336W/B Part No. 10366W/B Part No. 10551W/B Part No. 10729 Figure 4b: Sprinkler Wrenches Table 2b: Sprinkler Wrenches For Sprinkler Models:Use Wrench: Residential Concealed Sprinklers VK456, VK457, VK474, and VK488 13623W/B (heavy duty) Available since 2006 Residential Concealed HSW Sprinkler VK480 16267† or 16208W/R (heavy duty) Available since 2010 Mirage® QR ELO Concealed Sprinklers VK636 and VK469 (also optional for removal of protective caps) 15466† Available since 2009 Mirage® QR ELO Concealed Sprinklers VK636 and VK469 15467W/B (heavy duty) Available since 2009 Mirage® Concealed and flush style sprinklers 08336W/B (heavy duty) Available since 1993 Mirage® Concealed and flush style sprinklers 10366W/B† Available since 1998 Residential Flush Pendent Sprinklers VK476 and VK478 15209W/R (heavy duty) Available since 2009 Recessed Flush Dry Sprinklers VK482 18315 (heavy duty) Available since 2014 Mirage® and Freedom® Concealed Sprinklers VK461, VK462, VK463, VK464, VK465, VK469, VK474, VK632, VK634, VK636, and VK488 (optional concealed cover installer tool) 14412†, or 14867 for the large diameter cover, Available since 2007 Shipping Cap Remover/ Escutcheon Installer (optional***)15915† Available since 2010 Institutional style flush sprinklers (for installation of the escutcheon plate) 10551W/B Available since 1999 Institutional style flush sprinklers (spanner wrench for escutcheon plate removal)10729 Available since 1999 ***Allows removal of sprinkler caps and installation of E-1 and F-1 escutcheons on frame style pendent sprinklers from the floor. †Ideal for sprinkler cabinets. Part No. 15209W/R Part No. 16267 Part No. 15915 Part No. 16208W/R Part No. 14412 Part No. 14867 Part Nos. 13619 & 15466 Part Nos. 13623W/B & 15467W/B Part No. 18315 Replaces Form No. F_122598 Rev 18.1 (Added P65 Warning.)