Nisqually Landing Building AWATER MAIN
C-&
FIRE HYDRANT
POST INDICATOR VALVE
cffI y.!pm +0q#_1
- ram sr�rslr
�� �SI�rIr.Rz� Si
r
EIVIi H Y 507 = -
r■
x+
I .
I//-6" D.I. FIRE SUPPLY
- DOUBLE DEFECTOR CHECK
VALVE AND VAULT
FIRE DEPARTMENT CONNECTION ASSEMBLY
1 1
".1-0031w
PROJECT LOCATION
w
1�
VICINITY MAP
L
NO SCALE
U.G. NOTES
1. THIS SITE PLAN IS FOR REFERENCE ONLY. SEE ARCHITECTURAL AND CIVIL
DRAWINGS FOR ADDITIONAL SITE INFORMATION.
2. ALL UNDERGROUND PIPING IS BY OTHERS.
3. UNDERGROUND INSTALLER MUST HOLD STATE OF WASHINGTON LEVEL "U"
LICENSE.
4. ALL UNDERGROUND PIPING TO BE INSTALLED, RESTRAINED, FLUSHED, AND
TESTED PER NFPA 13 & 24.
5. MINIMUM BURY IS 4'-0".
6. PATRIOT START POINT AT FLANGE INSIDE BUILDING.
FLOW TEST
STATIC
53
RESIDUAL
47
FLOW
1160
SOURCE
CITY OF YELM
LOCATION
170TH ST.
DATE
12/7/2021
6" D.I. FIRE SUPPLY
LISTER NOTE:
SEND 1- CAP WITH EACH
SHA TEE
1"0 STEEL NIPPLE
X CONFIRM LENGTH IN FIELD
STEEL ADJUSTABLE DROP------ FIRESTOP PENETRATION THROUGH RATED LID
Nk NIPPLE TO SPRINKLER IN SOFFIT USING HILTI FS -ONE
ADN DROP DETAIL
SCALE: NTS
SITE PLAN
SCALE: 3/32"=1'-Y'
I
JILDING A
PATRIOT START POINT IN
SPRINKLER RISER ROOM
5'-0" OUT DONE BY OTHERS
FLG
6" ELECTRIC BELL
WIRED BY OTHERS
ANVIL 187
SCALE: NTS
CPVC PIPE NOTES:
1. ROOMS WITH MULTIPLE RESI SPRINKLERS TO BE SPACED A
MAXIMUM OF 16' APART, A MINIMUM OF 8' APART
AND A MAXIMUM OF 8' FROM WALLS.
2. ROOMS WITH A SINGLE RESI SPRINKLER TO BE SPACED A
A MAXIMUM OF 10' FROM ALL WALLS.
3. ALL CPVC PIPE TO BE INSTALLED PER ITS LISTING.
4. ALL CPVC PIPE TO BE 1"0 UNLESS NOTED OTHERWISE.
5. HANGER SUPPORTS TO BE WITHIN 9" OF A SPRINKLER DROP.
6. MAXIMUM HANGER SPACING:
3/4"OPIPE:51/2'
1"0 PIPE:6'
11/4"0 PIPE: 61/2'
11/2"0 PIPE: 7'
2"0 PIPE: 8'
7. ALL AREAS OF SPRINKLER PIPING TO BE AT LEAST 40°F.
8. ALL SPRINKLER PIPING AT THE ROOF TO BE COVERED BY
INSULATION. THIS WORK IS BY OTHERS.
9. SPRINKLERS HAVE BEEN OMITTED FROM BATHROOMS
AND CLOSETS AS ALLOWED PER NEPA 13R.
INIFRED
9%'
TR
- CPVC
TRIC BELL, 120 V
-_D AND
3Y OTHERS)
SPRINKLER HEAD N
IOX W/ WRENCH
2" SxG ADAPTER
2" FLEX CPi
RELIABLE GRVD
SIDENTIAL RISER-
' FLOW SWITCH
ESSURE RELIEF
>-K TEST AND DRAIN
2" FLEX CPLG
6"x2" GRVD�
CONC REDUCER
START POINT
FLANGE
RISER DETAIL
SCALE: 4z"=1'-0°
Al A2 A3 A4 A5 A6 A7 (A8( 9) A
�� -y / c 29'-b 19'-6 Z9' -b# 29'-b 29'-6 29'-6
01
LILL(
F4 Ul&IUNIT Ddu
U-1
11136 SF
I 1
>U1
m
I I
F�
'iiia
>000111'PLOOR - WOOD JOISTS
I I I I
0
I 1� n
Fj�Fle tJ'1` D �1 F4
r-
i, iv u u
I I
* NFPA 13R - 6.6.5 Except as provided for in 6.6.5.1,
sprinklers shall not be required in any porches, balconies,
corridors, carports, porte cocheres, and stairs that FIRST FLOOR
are open and attached.
7 SCALE: 1/8"=17
Filli i Pi PLAN PROVIi
ACOUSTIC -i UNDE RL AYM ENT AT HARD
FIN15i Fli 5URi
f
CEILING ASSEMBLY
SCALE: NTS
11 j
-j - -I - - - - - - - -
I I
* NFPA 13R - 6.6.5 Except as provided for in 6.6.5.1,
sprinklers shall not be required in any porches, balconies,
corridors, carports, porte cocheres, and stairs that
are open and attached.
* NFPA 13R - 6.6.5 Except as provided for in 6.6.5.1,
sprinklers shall not be required in any porches, balconies,
corridors, carports, porte cocheres, and stairs that
are open and attached.
I
HANGER LEGEND
SPRINKLER LEGEND
QUALITY CONTROL BY
UNIT D1 HC
DATE
DESIGN CRITERIA
CONTRACT WITH
Iii_jA108
U1
-
OGS
Pk
1132 SIF
1
9
�-11/2 1 i� IJU 1�Vt-
B
COACH SCREW ROD
ij
101 SIF
--
i
a
Lou
a12.11810
w w
F
T
T
---
FABRICATION
BY
DATE
1. DESIGNED PER NFPA 13R WITH HYDRAULIC CALCULATION OF
UP TO 4 -HEADS IN A SINGLE COMPARTMENT.
2. SEE ADDITIONAL CPUC NOTES ON PLAN.
-----I
1
F 0.0
�1--
---- --
--_--- -
11
-,
1
SPRINKLER HEAD LEGEND
- - -
-
-- ----
o ^
- --�--
--�--
1
1
2
5
16
3 7 1
8 16 2 SPRAY
0
�f�Jfi
1/2
SYM
MANUF
MODEL SIN RESPONSE TYPE
THREAD K TEMP
SIZE FACTOR
HEAD
FINISH
ESCUTCH
TYPE
ESCUTCH
FINISH
QTY
CITY OF YELM
SHOWN THUSLY (1-6) WHICH ARE END TO END.
3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION
B E LL EV U E, WA 98005
BRENDAN PALMER - 206.475.3670
F FLUSH SHELL
O • 1„
•
1/s'
G
CEILING FLANGE
3
4
17
32
SPRAY
❑
3/4"
RELIABLE
KRES49 R3596 FAST REC. PEND.
4.9K 165
WHITE
WHITE
WHITE
I
4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
H SIDE BEAM BRACKET
❑D 1
f
REUABLE KRES49 R3596 FAST REC. PEND. 1/2' 4.9K 217 WHIRE WHITE WHILE 16
ti 2 - WAY EARTHQUAKE BRACE
PROJECT NAME:
F4
<D° RELIABLE F3RES44 RA5231 QR DRY 1 1' 4.4K 155 WHITE WHITE WHIiE 8
K
1
2
U5
7 1
16 2 SIDEWALL
U0
Q
1/2°
Oo
� 4 -WAY EARTHQUAKE BRACE
1
PIPE NOTES
1. CPVC PIPE THROUGHOUT UNITS.
5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, APPLICABLE EDITION
6. JOINING OF PIPE AND FITTINGS, THREADED & WELDED, SHALL BE IN ACCORDANCE
WITH NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
7. OWNER TO PROVIDE ADEQUATE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER
SYSTEM TO PREVENT WATER IN PIPES FROM FREEZING.
8. ALL WIRING OF ELECTRICAL DEVICES (IF REQUIRED) TO BE PROVIDED
BY OTHERS
N i s q u a l l y Landing Building A
17021 103rd AVENUE SE
YELM, WA 98597
SITE PLAN AND LEVEL 1
D❑
--- `------
1"
P POWDER DRIVEN STUD
HANGER LEGEND
SPRINKLER LEGEND
QUALITY CONTROL BY
DATE
DESIGN CRITERIA
CONTRACT WITH
xx
HYDRAULIC
CALCULATION POINT
GENERAL NOTES
B
COACH SCREW ROD
ij
SPRINKLER
ORIFICE SIZES
AND TYPE
i
a
Lou
a12.11810
w w
F
APPROVED FOR
FABRICATION
BY
DATE
1. DESIGNED PER NFPA 13R WITH HYDRAULIC CALCULATION OF
UP TO 4 -HEADS IN A SINGLE COMPARTMENT.
2. SEE ADDITIONAL CPUC NOTES ON PLAN.
1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED.
PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISERS AND DIMENSIONS
EXXE L PACIFIC
NORTHUP WAY SUITE #300
D BM. CLAMP W "STRAP
SPRINKLER HEAD LEGEND
APPROVAL REQUIRED
E EYELET
1
2
5
16
3 7 1
8 16 2 SPRAY
0
O
1/2
SYM
MANUF
MODEL SIN RESPONSE TYPE
THREAD K TEMP
SIZE FACTOR
HEAD
FINISH
ESCUTCH
TYPE
ESCUTCH
FINISH
QTY
CITY OF YELM
SHOWN THUSLY (1-6) WHICH ARE END TO END.
3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION
B E LL EV U E, WA 98005
BRENDAN PALMER - 206.475.3670
F FLUSH SHELL
O • 1„
•
1/s'
G
CEILING FLANGE
3
4
17
32
SPRAY
❑
3/4"
RELIABLE
KRES49 R3596 FAST REC. PEND.
4.9K 165
WHITE
WHITE
WHITE
56
4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
H SIDE BEAM BRACKET
❑D 1
f
REUABLE KRES49 R3596 FAST REC. PEND. 1/2' 4.9K 217 WHIRE WHITE WHILE 16
ti 2 - WAY EARTHQUAKE BRACE
PROJECT NAME:
SHORT CLIP
<D° RELIABLE F3RES44 RA5231 QR DRY 1 1' 4.4K 155 WHITE WHITE WHIiE 8
K
1
2
3
8
7 1
16 2 SIDEWALL
Q
Q
1/2°
� 4 -WAY EARTHQUAKE BRACE
1
PIPE NOTES
1. CPVC PIPE THROUGHOUT UNITS.
5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO. 13, APPLICABLE EDITION
6. JOINING OF PIPE AND FITTINGS, THREADED & WELDED, SHALL BE IN ACCORDANCE
WITH NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
7. OWNER TO PROVIDE ADEQUATE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER
SYSTEM TO PREVENT WATER IN PIPES FROM FREEZING.
8. ALL WIRING OF ELECTRICAL DEVICES (IF REQUIRED) TO BE PROVIDED
BY OTHERS
N i s q u a l l y Landing Building A
17021 103rd AVENUE SE
YELM, WA 98597
SITE PLAN AND LEVEL 1
M ALL THREAD ROD
1"
P POWDER DRIVEN STUD
1" 2 DRY TYPE
TEMP RATING
� STRUCTURE TO CENTER
LINE OF PIPE IN INCHES
FITTING LEGEND
R EXPANSION BOLT
O • 1
za O� z3
0 >- o
S PIPE SPIKE
T
O ORDINARY
$ INTERMEDIATE
HIGH
it 3
zo
a ¢
') n
P PIPE -O -LET
U
/2" 1"
F PLAIN END FIT FITTING
9. PBIYTINOTHERS &EQUIPMENT (IFREQUIRED)TOBEPROVIDED
DESIGNER
Joseph Johnson
CAD FILE
FP -01
V
1., ® 1/2"
SN GROOVED SHAPED NIPPLE
10. FURRING OF PIPE & EQUIPMENT (IF REQUIRED)TO BE PROVIDED
DATE
6/30/22
W
E@E
9W
EXTRA HIGH
VERY EXTRA HIGH
1
1„
1„
TSN THREADED SHAPED NIPPLE
BY OTHERS
X
112" 1/2"
TOTAL 80
1
1 JOB NO.
17-0575
__'ME
M
Q":
F4
CPVC PIPE NOTES:
1. ROOMS WITH MULTIPLE RESI SPRINKLERS TO BE SPACED A
MAXIMUM OF 16' APART, A MINIMUM OF 8' APART
AND A MAXIMUM OF 8' FROM WALLS.
2. ROOMS WITH A SINGLE RESI SPRINKLER TO BE SPACED A
A MAXIMUM OF 10' FROM ALL WALLS.
3. ALL CPVC PIPE TO BE INSTALLED PER ITS LISTING.
4. ALL CPVC PIPE TO BE 1"0 UNLESS NOTED OTHERWISE.
5. HANGER SUPPORTS TO BE WITHIN 9" OF A SPRINKLER DROP.
6. MAXIMUM HANGER SPACING:
3/4"OPIPE:51/2'
1"0 PIPE: 6'
11/4"0 PIPE: 61/2'
11/2"0 PIPE: 7'
2"0 PIPE: 8'
7. ALL AREAS OF SPRINKLER PIPING TO BE AT LEAST 40°F.
8. ALL SPRINKLER PIPING AT THE ROOF TO BE COVERED BY
INSULATION. THIS WORK IS BY OTHERS.
9. SPRINKLERS HAVE BEEN OMITTED FROM BATHROOMS
AND CLOSETS AS ALLOWED PER NFPA 13R.
WOAD FLOOR -WOOD ,JOIST
FrHISH Fk00R PER PLAN. PROVIDE
FUSTIC MAT UNDERLA.YMENTAT HARD
FINISHED FLOOR SURFACES
X211" GYPCRETE
1 9W T&G FLOOR SHEATHING PER STRUCT
1'J -D. JOIST, SIZE & SPACING PER STRUCT--
3-1' MIN. UN FAC EDAOOLISTIO BATT
111:5ULATION
IRC- 1 RESILIENT CFtANNELAT 1•b'-0.0.
t LAYER SN' PROPRIETAIRY T1P1E 7C
O'VP$UM WAL-LBO-ARD
CEILING ASSEMBLY
IMTA
36'-9 1/27
wi.wvia, wiPviw, F"w wv..V.ca, uiiu awns a UL
are open and attached.
A3
29'-6"
U1
UNIT C2 u
I A302 I U,
--U1_L 11/2�_I�Iz -�
--T
I
* NFPA 13R - 6.6.5 Except "'provided for in 6.6.5.1,
sprinklers shall not be required in any porches, balconies,
corridors, carports, porte cocheres, and stairs that
are open and attached.
29'-6"
1 A
vVMUVia, wiPviw, Pviw vVWIcIca, unu awns uwt GVIIIUVIJ, GUIIJVIW, )1VILV l:VI:IICICJ, UIIU bLUlIJ 111U1
are open and attached. are open and attached.
SECOND FLOOR
SCALE: 1/8"=1'-0"
I I
A5
29'-6"
29'-6"
* NFPA 13R - 6.6.5 Except as provi ed for in 6.6.5.11 /
sprinklers shall not be required in a porches, balconies,
corridors, carports, porte cocheres, a d stairs that
are open and attached. HIRD FLOOR
SCALE: 1/8"=1'-0",,
ANVIL 187
TYP !CAL WOOD TR US S Root is s6m BLy
A3F I IAA T ,SHIN OLE 5. CLASS'C' M IN.
R60. AG. UNDERLAYMENT
RQQF SHEATHiNQ PER *TRU CTURAL
PROVIDE INS ULAT ION BAFFLES WHERE
ATTIC CLEARANCE I5 LESS THAN}
INDICATED INSULATION THFCKNF=85
MANLIfA4:;T1JREQ'rYQQD
ROOF TRkJS$ES AT 24' 0-C.
R-49 MIN. F19ERGLA99 PATT OR BLOWN -IN
IN BULATIQN (2 LArER,S R3K = 24.5" 13AT-F
TryICKN ESS)
RC -1 RE.SIL IE NT CHANNEL AT 16' O.C.
iii' OW13 OEILINIv
AR BARRIER PRi"r=RR SPjZANT YYrTH PERM
RATINGa OF 1.0 OR LEBS
ROOF ASSEMBLY
SCALE: NTS SCALE: NTS
SCALE: NTS
Horizontal
Stabilize and Restraint
29'-6"
I
A7
29'-6"
* NFPA 13R - 6.6.5 Except as provided for in 6.6.5.1,
sprinklers shall not be required in any porches, balconies,
corridors, carports, porte cocheres, and stairs that
are open and attached.
REMOTE AREA
(4) SPRINKLERS HYDRAULICALLY CALCULATED
TO PROVIDE 13 GPM MINIMUM FLOW
PER NFPA #13R & SPRINKLER HEAD LISTING
DEMAND AT (FLG): 53.3 GPM ® 36.5 PSI
FILE: NISQUALLY A SINGLE HEAD.SDF
REMOTE AREA
(1) SPRINKLER HYDRAULICALLY CALCULATED
TO PROVIDE 20 GPM MINIMUM FLOW
PER NFPA #13R & SPRINKLER HEAD LISTING
DEMAND AT (FLG): 20.0 GPM ® 33.8 PSI
SCALE: NTS
F4
HANGER LEGEND
SPRINKLER LEGEND
QUALITY CONTROL BY
DATE
DESIGN CRITERIA
CONTRACT WITH:
xx HYDRAULIC
CALCULATION POINT
GENERAL NOTES
B ICOACH
SCREW ROD
o
=
SPRINKLER�
ORIFICE SIZES
AND TYPE
of
w
z
W
a
w w
(n
APPROVED FOR
FABRICATION
BY
DATE
1. DESIGNED PER NFPA 13R WITH HYDRAULIC CALCULATION OF
UP TO 4 -HEADS IN A SINGLE COMPARTMENT.
Z. SEE ADDITIONAL CPVC NOTES ON PLAN.
1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED.
12. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISERS AND DIMENSIONS
EXXE L PACIFIC
11820 NORTHUP WAY SUITE #300
»
D BM. CLAMP W STRAP
SPRINKLER HEAD LEGEND
APPROVAL REQUIRED
E EYELET
1
2
5
16
3 7 1
8 16 2 SPRAY
0
1/2
SYM MANUF
MODEL SIN RESPONSE TYPE
THREAD K
TEMP
SIZE FACTOR
HEAD
FINISH
ESCUTCH
TYPE
ESCUTCH
FINISH
QTl
CITY OF YELM
SHOWN THUSLY (1-6) WHICH ARE END TO END.
3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION
BELLEVUE WA 98005
�
BRENDAN PALMER - 106.475.3670
F FLUSH SHELL
OO • 1"
• 1/2"
G
CEILING FLANGE
3
4
17
32
SPRAY
❑
3/4"
RELIABLE
KRES49 R3596 FAST REC. PEND.
4.91K 165
WHITE
WHITE
WHITE
109
4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH
NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
H SIDE BEAM BRACKET
■ 1„
RELIABLE KRES49 R3596 FAST REC. PEND. 1/2' 4.91K 217 WHITE WHITE WHITE 32
~ 2 - WAY EARTHQUAKE BRACE
PROJECT NAME .
SHORT CLIP
DRY RELIABLE F3RES44 RA5231 QR DRY HSW 1" 4.4K 159 WHITE WHITE WHITE 16
K
1
2
3,
8
1
16 2 SIDEWALL
Q
Q
4 - WAY EARTHQUAKE BRACE
5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET NO.13, APPLICABLE EDITION6. JOINING OF PIPE AND FITTINGS, THREADED & WELDED, SHALL BE IN ACCORDANCENisqually
WITH NFPA PAMPHLET NO. 13, APPLICABLE EDITION.
7. OWNER TO PROVIDE ADEQUATE HEAT IN AREAS PROTECTED BY A WET PIPE SPRINKLER
SYSTEM TO PREVENT WATER IN PIPES FROM FREEZING.
8. ALL WIRING OF ELECTRICAL DEVICES (IF REQUIRED) TO BE PROVIDED
BY OTHERS
Landing BuiIding A
17021 103rd AVENUE SE
YELM, WA 98597
LEVEL 2 AND LEVEL 3
M THREAD ROD
11/2"ALL
a ,
P POWDER DRIVEN STUD
1"
2DRY TYPE
n STRUCTURE TO CENTER
0 LINE OF PIPE IN INCHES
R EXPANSION BOLT
♦ 1
S PIPE SPIKE
TEMP
Q
$
RATING
ORDINARY
INTERMEDIATE
m Z
of 3:O
LU
Y o
z a
a =
m
>
z
a 0
FITTING LEGEND
PIPE NOTES
1. CPVC PIPE THROUGHOUT UNITS.
T
P PIPE -O -LET
U
O
/2" 1"
F PLAIN END FIT FITTING
9. PAINTING OF PIPE &EQUIPMENT (IF REQUIRED) TO BE PROVIDED
DESIGNER
Joseph Johnson
CAD FILE
Z Z
BY OTHERS
1/1
SN GROOVED SHAPED NIPPLE
10. FURRINGOTOHERS F PIPE & EQUIPMENT (IF REQUIRED) TO BE PROVIDED
DATE
6/30/22
FP -02
W
ggE
EXTRA HIGH
VERY EXTRA HIGH
1„
TSN THREADED SHAPED NIPPLE
X
/y' 1/2"
TOTAL 157