FA SUBMITTAL DOCUMENTATION- TAHOMA APTS- BLDG 1
11409 58Th Ave E- Puyallup, WA. 98373 GWF-7075 GWF-7075 Intelligent Fire Alarm Control Panel Analog and Networking Systems General The Gamewell-FCI®, GWF-7075 is an Addressable Fire Alarm Control Panel (FACP). The GWF-7075 has a signaling line circuit (SLC) loop that is used to connect the addressable detectors. The SLC loop is capable of supporting up to 75 detectors and 75 modules using the System Sensor® Velociti® Protocol, and it also offers the built-in support for the SWIFT™ wireless fire alarm devices. The GWF-7075 is equipped with two configurable Notification Appliance Circuits (NACs) that support a maximum output of 2.5A. This panel communicates with the built-in, dual-line digital and IP communicator including an optional cellular communication module. The GWF-7075 fire alarm control panel offers the following powerful features: The GWF-7075 panel supports a variety of devices, including the following accessories: FEATURES & BENEFITS • Built-in support for up to 75 detectors and 75 modules operating in Velociti® or CLIP mode • Offers a four line LCD display with 40 characters per line • Available in a red or a black cabinet • GWF-7075 can be surface or flush mounted • Contains a built-in USB interface used for programming •Includes the programmable date setting for Daylight Saving Time • Uses a JumpStart Auto Programming® feature for easy programming • System programmable from the front panel • Provides a built-in dual phone line, digital alarm communicator/ transmitter (DACT), IP or optional cellular technologies •Firmware can be upgraded in the field • Supports up to four SWIFT™ wireless gateways. Each gateway may include up to 49 wireless devices • Supports Class B (Style 4) and Class A (Style 6 or Style 7 configuration for SLC, and SBUS • Offers a built-in synchronization for appliances from AMSECO™, Gentex®, System Sensor®, and Wheelock™ • Reports events to the Central Station by point or by zone • detector sensitivity • pre-trouble maintenance alert • day/night thresholds • calibration trouble alert •drift compensation • RA-1000 Remote Annunciator • 5880 - LED I/O Module • GFPS-6S Intelligent Remote Power Supply • 5824 Serial/Parallel Printer Interface Module (for printing system reports) 2 Optional Accessories RA-1000: Remote Annunciator The RA-1000 is a remote annunciator used to operate the GWF-7075 Fire Alarm Control Panel (FACP). It connects to the control panel via the RS-485 system bus. The RA-1000 is equipped with five status LEDs which indicate: GFPS-6S: Intelligent Remote Power Supply The GFPS-6S intelligent power supply delivers 6A of notification appliance circuit (NAC) power and offers built-in synchronization from appliances developed by the following manufacturers: The GFPS-6S provides its own AC power connection, battery charging circuit, and backup battery for use with the GWF-7075 FACP. The output circuits can be programmed as NACs or as auxiliary power (configurable for constant, resettable, or door holder power). 5824: Serial / Parallel Module The 5824 is equipped with one parallel and one RS- 232 serial port that allows the GWF-7075 to connect to virtually any standard PC-compatible printer to generate reports on site. 5880: LED I/O Module The 5880 provides 40 programmable LED outputs and eight supervised dry contact inputs. These devices offer an effective way to customize remote annunciation. The GWF-7075 supports up to eight 5880 modules to offer maximum flexibility. 5220: Direct Connect Module The 5220 is a direct connect module used to connect a fire alarm control panel (FACP) to a city box or polarity reversal communicator. CELL-MOD: Cellular Fire Alarm Communicator (Plastic Enclosure) The CELL-MOD houses the GSM communicator inside a plastic enclosure that may or may not require an external antenna depending on the installation environment. COMPATIBLE DEVICES For a list of compatible devices, refer to the following documents: • Compatibility Addendum for Gamewell-FCI Manuals, P/N: 9000-0427-L8 • SWIFT™ Intelligent Wireless Detectors, P/N: 9021-60818 • SWIFT™ Intelligent Wireless Modules, P/N: 9021-60819 • SWIFT™ Wireless Gateway, P/N: 9021-60824 ORDERING INFORMATION GWF-7075: Intelligent Fire Alarm Control Panel. Red GWF-7075B: Intelligent Fire Alarm Control Panel, Black SBUS Accessories RA-1000: Remote Annunciator (Black) Dimensions: 7.4"H x 9.1"W x 1.5" (18.8 x 23.1 x 3.8) cm RA-1000R: Remote Annunciator (Red) GFPS-6S: Intelligent Remote Power Supply Dimensions: 16"H x 12.25"W 3"D (40.6 x 30.9 x 7.6) cm 5824: Serial / Parallel Module Dimensions: 6"H x 7.75"W x 1.44"D (15.0 x 19.4 x 3.6) cm 5880: LED I/O Module Dimensions: 7.75"H x 6"W x 1.94"D (19.4 x 15.0 x 4.8) cm 5220: Direct Connect Module Dimensions: 1.31"H x 6.5"W x 2.13"D (3.33 x 16.51 x 5.40)cm Miscellaneous Accessories HFSS: Software Suite. Provides programming, upload/ download and event reporting BB-17F: Remote Battery Box Cabinet. Holds up to two 18 Amp Hour batteries. Dimensions: 16" W x 10" H x 6" D (40.64 W x 25.40 H x 15.24 D) cm CELL-MOD: Cellular Communicator in Plastic Enclosure •Alarm •AC Power Loss • System Silenced • Trouble •Supervisory •System Sensor® •Faraday™ •Gentex® •AMSECO™ •Wheelock™ GWF-7075 Technical Specifications 9021-60966 | A | 12/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI®, System Sensor® and Velociti® are registered trademarks and SWIFT ™ is a trademark of Honeywell International, Inc. AMSECO™ is a registered trademark of Kobishi America Inc. Asco® is a registered trademark of Asco Power Technologies Inc. Farraday™ is a trademark of Faraday LLC. Gentex® is a registered trademark of Gentex Corporation Inc. Microsoft, Windows®, and the Windows Logo® are registered trademarks or trademarks of Microsoft Corporation. UL® is a registered trademark of Underwriter’s Laboratories Inc. Wheelock™ is a trademark of Cooper-Wheelock Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s GWF-7075 and other products available by visiting www.Gamewell-FCI.com SYSTEMS PHYSICAL: Overall Dimensions: 15.12” H x 12.71" W x 3.33” D 38.40 H x 32.28 W x 8.46 D cm Weight: 25 lbs. Color: Red or Black Environmental Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 0 to 93% relative humidity (non-condensing) ELECTRICAL: GWF-7075 Primary AC: 120 VAC @ 60 Hz, 900mA Total Accessory Load: 2.5A @ 27.4 VDC Class A Power-Limited NAC Power: 1A per NAC, 2.5A Total Aux Power: 27.4 VDC Form C Trouble & Alarm Relay: 2.5A @ 27.4 VDC, Resistive Standby Current: 165 mA Alarm Current: 310 mA Battery Charging Capacity: 7 to 35 AH Battery Size: 7 A/H maximum allowed in the control panel cabinet. Larger capacity batteries can be housed in the BB-17F accessory cabinet. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The GWF-7075 is designed to comply with the following standard: UL Standard: UL 864 9th Edition NFPA STANDARDS NFPA 13 Sprinkler NFPA 15 Water Spray NFPA 16 Foam Water NFPA 70 NFPA 72 Central Station Remote Signaling Local Protective Signaling Systems Auxiliary Protected Premises Unit & Water Deluge Releasing Service AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1869 CSFM: 7165-1703:0500 MEA COA: 6255 OSHPD (CA): Approved Releasing Solenoids: Asco® T8210A107 24 VDC 3 A max. 0 Hz Asco® 8210G207 24 VDC 3 A max. 0 Hz ISO 9001 Certification ASD-PL2F/ASD-PTL2F ASD-PL2FR Velociti® Series 3 Detectors Photoelectric Detectors Addressable Devices Photoelectric Detector Description The Gamewell-FCI, Velociti® Series 3 intelligent photoelectric detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 smoke detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The photoelectric detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The Gamewell-FCI, ASD-PL3 photoelectric detector's re-designed optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The sensitivity of Velociti series detectors can be programmed using the control panel software to suit the environment. The ASD-PL3R photoelectric detector is also remote test capable that may be used with a DNR (DNRW) duct smoke detector housing. The ASD-PTL3 multi- sensor detector offers either photoelectric detection or thermal detection through dual electronic thermistors at 135°F fixed temperature thermal sensing. For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number after the detector model. Note: Although the E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® Standard 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) • Includes dual LEDs for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ASD-PL3: Photoelectric smoke detector, bright white, Velociti ASD-PL3R: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, bright white, Velociti ASD-PTL3: Photoelectric smoke detector with thermal sensing, bright white, Velociti ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/ CLIP ASD-PL3R-IV: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, ivory, Velociti/CLIP ASD-PTL3-IV : Photoelectric smoke detector with thermal sensing, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. Note: “IV” suffix indicates Flashscan and CLIP devices. “WH” suffix indicates bright white B501-WHITE: 4” Flangeless mounting base, bright white B501-WHITE-BP: 4” Flangeless mounting base bulk pack, bright white B501-IV: 4” Flangeless mounting base, ivory B300-6: 6” Flanged mounting base, bright white B300-6-IV: 6” Flanged mounting base, ivory B300-6-BP: 6” Flanged mounting base bulk (Pack of 10) B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory DNR: Intelligent duct detector housing, non-relay DNRW: Intelligent duct detector housing, non-relay, watertight Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6” Base, bright white TR300-IV: Accessory Flange Ring for B300 6” Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCSCOF Series detectors. (Pack of 10) CK300-BL: Black detector kit. (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCSCOF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/ or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5-foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0617 | K | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Photoelectric Intelligent Detector: Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.49 cm) installed in B300-6 base 4 inches (10.16 cm) installed in B501 base Shipping Weight: 3.4 oz (96.4 g) Operating Temperature Range: Photo: 32° F to 122° F (0° C to 50° C) Photo in Duct Applications: -4° F to 158° F (-20° C to 70° C) Photo with Thermal: 32° F to 100° F (0° C to 38° C) Operating Humidity Range: 10% to 93% non-condensing Rate-of-Rise Detection: Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Air Velocity Range: 0 to 4,000 ft/min (0 to 1219.2 m/min) Electrical Specifications Voltage Range: 15 to 32 VDC Standby Current (@ 24 VDC): 200 UA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: 0.0063 STANDARDS The Velociti® Series 3 Photoelectric Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA FDNY: COA-219-02-E Vol. VI CSFM: 7272-1703:0501 ISO 9001 Certification MS-7 Series MS-7 Series Manual Fire Alarm Pull Stations Addressable Devices General The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated.* The station features screw terminals. The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi- flush mounting • Shock and vibration resistant • Both single and double action pull stations available • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode 2 MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual-action Agent Release Station The MS-7LR is designed for use with the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi-flush mounted on a standard double-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi-flush mounting. NYC-Plate The NYC-Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC-Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual-action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-I/O - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi-flush mount, plastic NY-PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. MS-7 Series Technical Specifications 9020-0616 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Velociti® and Gamewell-FCI are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s MS-7 Series and other products available by visiting www.Gamewell-FCI.com SYSTEMS Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D (14 x 10.1 x 3.2 cm) Operating Temperature: (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-35° to 66° C) Relative Humidity : (MS-7AF, MS-7ASF): 10 to 93% (non-condensing) (MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current: (MS-7AF, MS-7ASF): .00030 amps. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The MS-7 Series is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2465 FM: 3023594 MEA FDNY: 67-02-E Vol. VII CSFM: 7160-1703:0119 7160-1703:0170 7160-1703:0109 ISO 9001 Certification AMM-2IF Velociti® Series AMM-2IF Addressable Dual Monitor Module Addressable Devices General The Gamewell-FCI Velociti® Series, addressable dual monitor module, AMM-2IF, features two Style B, Class B initiating device circuits, each with an end-of-line resistor. This module provides addresses for any device or group of devices connected to each circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, 4-wire projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in these circuits. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The first circuit address is set via a rotary switch. The second circuit is automatically assigned the next higher address. The module has a single panel-controlled red LED. The AMM-2IF module is designed for installation in the signaling line circuit of any Gamewell-FCI addressable control panel. The AMM-2IF is designed to mount in a 4” square junction box, 2 1/8” deep. The initiating device circuit of the AMM-2IF can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices. Ordering Information AMM-2IF: Monitor module, two circuit, Style B, Class B FEATURES & BENEFITS • Supports Class B, Style B, initiating device circuits • Provides a visual rotary, decimal switch addressing (01-159) • Offers 40 ohm line resistance for each initiating circuit • Accommodates any normally open contact device • Displays bi-color LEDs flash green whenever the module is addressed, and light steady red on alarm* • Includes a compact size allows easy installation *Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Velociti® Series AMM-2IF Technical Specifications 9020-0629 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti®, E3 Series® and Gamewell-FCI are registered trademarks of Honeywell International Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series AMM-2IF and other products available by visiting www.Gamewell-FCI.com SYSTEMS Supervisory Current: 0.0075 amp. Alarm Current: .0057 amp. (LED lit) Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% (non-condensing) Dimensions: 4 1/2” H x 4” mW x 1 1/4” D (11 H x 10.2 W x 3 D cm) (Mounts in a 4” square by 2 1/8” deep box). End-of-line Resistor: 47 K ohms TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The Velociti® Series AMM-2IF is designed to comply with the following standards: UL Standards: UL 864 9th Edition UL 2572 for Mass Notification AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1949 2572 for Mass Notification FM: 3023594 MEA FDNY: 227-03-E Vol. IV CSFM: 7300-1703:0107 ISO 9001 Certification AMM-4F Velociti Series® AMM-4F Addressable Monitor Module Addressable Devices General The Gamewell-FCI Velociti® Series, addressable monitor module (AMM-4F) features a single Style D, Class A initiating device circuit. It may also be configured as a Style B, Class B initiating circuit with end-of-line resistor. This module provides an address for any device or group of devices connected to this circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, linear heat detection devices, 4-wire projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in this circuit. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The AMM-4F module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable control panel. The initiating circuit of the AMM-4F has a maximum line resistance of 40 ohms, allowing the module to accommodate a number of initiating devices at a distance from the module. The AMM-4F is designed to mount in a 4” square junction box 2 1/8” deep. The initiating device circuit of the AMM-4F can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices. Ordering Information AMM-4F: Addressable monitor module, single circuit Style D, Class A or Style BC/A and B FEATURES & BENEFITS •Compact size allows easy installation • Includes Class A, Style D, or Class B, Style B initiating circuit • Offers a visual rotary, decimal switch addressing (01-159) •Provides a 40 ohm line resistance for each initiating device circuit • Accommodates any N/O dry contact device •Bi-color LEDs flash green whenever the module is addressed, and light steady red on alarm* *Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Velociti Series® AMM-4F Technical Specifications 9020-0624 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti®, E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti Series® AMM-4F and other products available by visiting www.Gamewell-FCI.com SYSTEM Supervisory Current: .000375 amps. (LED flashing) Alarm Current: .005 amps. (LED lit) Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% (non-condensing) End-of-Line resistor: 47K ohms Dimensions: 4 1/2” H x 4” W x 1 1/4” D (11.4 x 10.2 x 3.2 cm) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The Velociti Series® AMM-4F is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1949 FM: 3023594 MEA FDNY: 277-03-E Vol. VI CSFM: 7300-1703:0102 ISO 9001 Certification Agency Listings AVDS115-02 • 12/3/2019 • Page 1 MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. AVDS115-02 • 12/3/2019 • Page 2 SpectrAlert Advance Outdoor Horn, Strobe, and Horn StrobeSpecifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MLD3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS115-02 • 12/3/2019 SpectrAlert Advance Diagrams Model Description Red White Wall Horn Strobes P2RK P2WK 2-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P2RK-P P2WK-P 2-Wire Horn Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) P2RK-R P2WK-R 2-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK P2WHK 2-Wire Horn Strobe, High cd, Outdoor (includes plastic weatherproof back box) P2RHK-P P2WHK-P 2-Wire Horn Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) P2RHK-R P2WHK-R 2-Wire Horn Strobe, High cd, Outdoor (does not include plastic weatherproof back box) P4RK P4WK 4-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P4RK-R —4-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK-120 —2-Wire Horn Strobe, High cd, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK SWK Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) SRK-P SWK-P Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) SRK-R SWK-R Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) SRHK SWHK Strobe, High cd, Outdoor (includes plastic weatherproof back box) SRHK-P SWHK-P Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) SRHK-R SWHK-R Strobe, High cd, Outdoor (does not include plastic weatherproof back box) Horns HRK —Horn, Red, Outdoor (includes plastic weatherproof back box) HRK-R —Horn, Red, Outdoor (does not include plastic weatherproof back box) Accessories SA-WBB SA-WBBW Metal Weatherproof Back Box WTP WTPW Metal Weatherproof Outdoor Flush-mounting Plate SpectrAlert Advance Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -R models require metal weatherproof outdoor flush mounting plate or a metal weatherproof outdoor back box (order separately). “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝Dia. 2.5˝ 2.5˝ 64mm119mm 142mm Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box Agency Listings SSM/SSV Series Alarm Bells System Sensor’s SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features • Approved for indoor and outdoor use • Low current draw • High dB output • Available in six-inch, eight-inch, and ten-inch sizes • AC and DC models • DC models polarized for use with supervision circuitry • Mount directly to standard four-inch square electrical box indoors • SSM and SSV series come pre-wired Reliable Performance. The SSM and SSV series provide loud resonant tones. The SSM series operates on 24VDC and are motor driven, while the SSV series operates on 120VAC utilizing a vibrating mechanism. Simplified Installation. For indoor use, the SSM and SSV series mount to a standard four-inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. The SSM and SSV series come pre-wired, to reduce installation time. The SSM series incorporates a polarized electrical design for use with supervision circuitry. S4011 331-01-E7135-1653:0217CS5493005255 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2011 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0260-010 • 08/11 • #2870 Ordering Information UL/FM Model No.ULC/Canadian Model No.Description SSM24-6 SSM24-6A Bell, 6˝, 24VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8˝, 24VDC, Polarized, 80dBA SSM24-10 SSM24-10A Bell, 10˝, 24VDC, Polarized, 81dBA SSV120-6 SSV120-6A Bell, 6˝, 120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8˝, 120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10˝, 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors SSM/SSV Specifications Architectural/Engineering Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 6˝/8˝/10˝ (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi-flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4˝ square electrical box having a maximum projection of 2½˝. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. Physical/Operating Specifications Operating Temperature Range –31°F to 140°F Operating Voltage SSM series: 24 VDC SSV series: 120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464 Absorbant Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. recognized under file number MH 20567. Sealed Lead-Acid Battery L: 5.94 in (151 mm) W: 2.56 in (65.0 mm) H: 3.70 in (94.0 mm) TH: 4.02 in (102 mm) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice. Nominal Voltage Nominal Capacity 20-hr. (0.35A) 10-hr. (0.65A) 5-hr. (1.20A) 1-hr. (4.20A) Approximate Weight Internal Resistance (approx.) Shelf Life (% of normal capacity at 68º F (20º C) 3 Months 6 Months 12 Months 12 volts 7.00 Ah 2.1 A or smaller 14.6 - 14.8 V 77º F (25º C) 6.51 Ah 5.95 Ah 4.20 Ah 4.52 lbs (2.05 kgs) 30m 91% 83% 64% Charge Method (Constant Voltage) Cycle Use Float Use Initial Current Control Voltage 13.6 - 13.8 VControl Voltage (Repeating Use) Specification Physical Dimensions: in (mm) Terminals UPG No. 40800 Maintenance-Free UB1270 5.94in (151mm)4.02 (102)3.70 (94)2.56 (65.0)Temperature Dependancy of Capacity 104 F (40 C) 77 F (25 C) (20 hour rate) 102% 100% 85% 32 F (0 C) 5 F (-15 C) 65% AGM Operational Temperature AGM Storage Temperature UPG Recommends (0 C to 40 C)32 F to 104 F 5 F to 113 F 5 F to 104 F (-15 C to 45 C) Charge Discharge (-15 C to 40 C) 32 F to 86 F (0 C to 30 C) 488 S. Royal Lane Coppell, Texas 75019 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com www.upgi.com All specifications subject to change without notice. L1713-1 Due to continuous improvements to our products, product may vary slightly from depiction. Copyright 2017 Universal Power Group, Inc. All rights reserved. Discharge Characteristics (Minute) (Hour) Discharge timeCell voltage (V/Cell)Discharge Time vs. Discharge Current Discharge Current = CA X Nominal Capacity(Minute)(Hour)Duration of Discharge Charge Voltage(V/Cell)Application Temperature Set Point Allowable Range Max.Charge Current Cycle Use 25 (77 )2.45 2.40~2.50 Standby 25 (77 )2.325 2.30~2.35 0.30C Final Discharge Voltage V/Cell 1.75 1.70 1.60 1.30 Discharge Current(A)0.2C>(A) 0.2C<(A)<0.5C 0.5C<(A)<1.0C (A)>1.0C Charge Current & Final Discharge Voltage Cycle Life vs Depth of DischargeShelf Life & Storage Effect of Temperature on CapacityOpen Circuit Voltage vs Residual Capacity UPG No. 40800 Maintenance-Free UB1270 488 S. Royal Lane Coppell, Texas 75019 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com www.upgi.com Let UPG Power Your Life. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2011 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0260-010 • 08/11 • #2870 Ordering Information UL/FM Model No.ULC/Canadian Model No.Description SSM24-6 SSM24-6A Bell, 6˝, 24VDC, Polarized, 82dBA SSM24-8 SSM24-8A Bell, 8˝, 24VDC, Polarized, 80dBA SSM24-10 SSM24-10A Bell, 10˝, 24VDC, Polarized, 81dBA SSV120-6 SSV120-6A Bell, 6˝, 120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8˝, 120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10˝, 120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors SSM/SSV Specifications Architectural/Engineering Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 6˝/8˝/10˝ (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi-flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4˝ square electrical box having a maximum projection of 2½˝. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA. Physical/Operating Specifications Operating Temperature Range –31°F to 140°F Operating Voltage SSM series: 24 VDC SSV series: 120 VAC Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years Electrical Specifications Model Gong Diameter (inches) Nominal Voltage Operating Voltage Limit Maximum Current Sound Output (dBA) SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 82 SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1mA/ FWR-53.5mA 81 SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 * Sound output measured at Underwriter Laboratories, as specified in UL464