Loading...
Energy Code Worksheet2018 Washington State Energy Code — Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Single Family— New & Additions (effective February 1, 2021) These requirements apply to all IRC building types, including detached one- and two-family dwellings and multiple single-family dwellings (townhouses). Project Information—Cont_ac_t Information 1361 Instructions: This single-family project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. Representative _ All Glmate Zones (Table R402.1.1) R-Value _ __ U-Factor'___ Fenestration U -Factor b n/a 0.30 Skylight U -Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling ` 49' 0.026 Wood Frame Wall g•h 21 int _ 0.056 Floor _ _ 30 _ _ 0.029 Below Grade Wall `-h 10/15/21 int + TB _ 0.042 ' Slab d•'R-Value & Depth 10, 2 ft n/a _ R -values are minimums. U -factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R -value of the insulation from Appendix Table A101.4 shall not be less than the R -value specifiedin the table. b The fenestration U -factor column excludes skylights. -- -- "10/15/21 +STB" means R-10 continuous Insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R-5 thermal break between floor slab and basement wall. d —-- R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. For single rafter- orjoist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth e extends over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for 9 climate zone 5 of ICC 400. Int. (Intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 insulation. Prescriptive Path -Single Family 2018 Washinglon State Energy Code -R 2018 Washington State Energy Code - Residential Energv Code Compliance for All Climate Zones in Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) to achieve the following minimum number of credits. To claim this credit, the building permit drawings shall specify the option selected and the maximum tested building air leakage, and show the qualifying ventilation system and its control sequence of operation. 1. Small Dwelling Unit: 3 credits Dwelling units less than 1,500 sf in conditioned floor area with less than 300 sf of fenestration area. Additions to existing building that are greater than 500 sf of heated floor area but less than 1,500 sf. 2. Medium Dwelling Unit: 6 credits All dwelling units that are not included in #1 or #3 3. Large Dwelling Unit: 7 credits Dwelling units exceeding 5,000 sf of conditioned floor area 4. Additions less than 500 square feet: 1.5 credits All other additions shall meet 1-3 above Before selecting your credits on this Summary table, review the details in Table 406.3 (Single Family), bn page 4. Summary of Table R406.2 Heating Options Fuel Normalization Descriptions Credits - select ONE heating option User Notes 1 ...._.Heat Combustion heating minimum NAECAb ._ 0.0 Q 2 pump° 1.0 ❑ -._. 3 Electric resistance heat only - furnace or zonal -1.0 ❑ 4 DHP with zonal electric resistance per option 3.4 0.5 ❑ 5 All other heating systems -1.0 ❑ Energy Options _ Energy Credit Option Descriptions Credits -select ONE energy option from each category 1.1 Efficient Building Envelope O.5 l ^ u 1.2 Efficient Building Envelope 1.0 ❑ 1.3 Efficient Building Envelope 0.5 1.4 Efficient Building Envelope _ 1.0 ❑ 1.5 _ Efficient Building Envelope _ 2.0 ❑ 1.6 Efficient Building Envelope 3.0 ❑ 1.7 Efficient Building Envelope _ _ _ 0.5 ❑ 2.1 Air Leakage Control and Efficient Ventilation 0.5 2.2 Air Leakage Control and Efficient Ventilation 1.0 ❑ 23 _ Air Leakage Control and Efficient Ventilation 1.5 _ ❑ 2.4 Air Leakage Control and Efficient Ventilation 2.0 ❑ 3.1a High Efficiency HVAC 3.2 High Efficiency HVAC 1.0 ❑ 3.3a High Efficiency HVAC 1.5 ❑ 3.4 High Efficiency HVAC 1.5 ❑ 3.5 High Efficiency HVAC 1.5 ❑ 3.6a High Efficiency HVAC 2.0 ❑ _ 4.1 _ High Efficiency HVAC Distribution System _ 0.5 ❑ 4.2 High Efficiency HVAC Distribution System 1.0 ❑ Prescriptive Path -Single Family 2018 Washington State Energy Code -R 2018 Washington State Energy Code — Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Single Family— New & Additions (effective February 1, 2021) Summary of Table R406.2 (cont.) Energy Options 5.1d Energy Credit Option Descriptions (cont.) Efficient Water Heating Credits - select ONE energy option from each category °_ 0.5 ❑ User Notes 5.2 Efficient Water Heating 0.5 ❑ 5.3 Efficient Water Heating 1.0 0 5.4 Efficient Water Heating 1.5 2.0 ❑ ❑ 5.5 Efficient Water Heating 5.6 Efficient Water Heating 2.5 ❑ 6.1e Renewable Electric Energy (3 credits max) 1.0 7.1 Appliance Package 0.5 ❑ Total Credits E10 'CLEAR FORM a. An alternative heating source sized at a maximum of 0.5 W/sf (equivalent) of heated floor area or 500 W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category S. Option 5.1 may be combined with options 5,2 through 5.6. See Table 406.3, e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See the complete Table R406.2 for all requirements and option descriptions. Please print onlypages<1,through 3:of#his u,!orksheet for submission to yourbuild)ng officiEil. Prescriptive Path —Single Family 2018 Washington State Energy Code -R Size: Wash ling system sizing calculator Is based on the Prescdpfive Requirements o(the 2018 Washington Stale Energy Code (WSEC) and ACCA J and S. This tool will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to delermine cooling loads. complete the green drop -downs and boxes that are applicable to your project. As you make selections In the drop -downs for each section, some will be calculated (or you. If you do not see the selecllon you need in the drop-down options, please contact the WSU Energy Program at code@energy.tvsu.edu or (360) 956-2042 for asslslance. Heating System Type: Oul ower synams OO neatwmp To see detailed instructions /or each section, place yourcursor on the word "Instructions" Design Temperature Insuucrons -� -� Design Temperature Difference (\T) 50 spacawav v i = IMoo r (/0 deg rces) - Ou fdoor Desgn Temp Area of Building Condltloned Ffoor Area Instrocuons Conditioned Floor Area (sq fQ ; -;1,36'1 Average Celling Height Conditioned Volume Instruamns Average Ceiling Height (N) '. ;. ',$;p 10,888 Glazing and Doors U -Factor X Area - UA Instructions -„ �- -— ^� u -o za� 0.280 '= :-768 � 47.04 Skylights U -Factor X Area = UA mstrocuons 0.50 "' --- Insulation Attic - — �: U -Factor X Area = UA mstrucuons R"49 ""'"" '�"" 0.026 ��9411�;;; 24.44 Single Rather or Joist Vaplted Cellings, _ U -Factor X Area UA Instrocuons sal�ect a -varve � No selecllon 0 --- Above Grade Walls U -Factor X Area UA (,ea Figura rJ Instructions a-zr tnte�ned,ate � � 0.056 "1,904=- % 196,62 Floors U•Factor X Area UA mstruouoos � ___,_, _ _ ... aae _. . 0.025 �� �967�"'- 24.03 Below Grade Walls (:ea viyvre r/ U -Factor X Area UA mstmcuons refect a-vawe � No selecllon 0 Slab Below Orade ( rag ,o r) _ _ F -Factor X Le� UA mstrocnons , �se�ece candtimmy No selecllon --- Slab on Grade ( Fig a 1/_ F -Factor X Len th UA mstrocnons --�.- -, - .z -_ . select R-va,ve ,_ No selecllon --- Location of Ducts Insuucuons -. � • Duct Leakage CoeHlclent cord.uam spare 1.00 Sum of UA 202.13 Envelope Heat Load 10,106 Btu/Hour Flyure 1- Sum of UAx eT Air Leakage Heat Load 5,880 Btu /Hour Valumex 0.6x �Tx 0.018 Ano.ec,:ee BUllding Design Heat load 15,986 Btu /Hour Air leakage + envePope heat loss �,,,,„-.�v^• Bullding and Duct Heal Load 15,986 Btu/Hour Ducts Jn unconditioned space: sum o! building heat loss x 1.10 Ducts in condirloned space: sum o/building heat loss x 1 Maximum Heat Equipment Output 19,982 Btu/Hour Buildino and duct heat loss x 1.40lor /orced a!r/umace euilding and duct heat /ors X 1.25 /or heat pump (Ol/gf/l3J Window, Skylight and Door Schedule Project Information Ref. U -factor Exempt Swinging Door (24 sq. ft. max.) Exempt Glazed Fenestration (15 sq. ft. max.) Vertical Fenestration (Windows and doors) Contact INorration 5.60 4.,.I', 16.0 ..,6, 1.3.61 20.0 5.60 9.8 2.74 .,.-�....... .... ...... :.�: „-.,..." rriasferd"ro4 8.96 Q 28 12.0 ... 3.36 ......'llI,IVIV P 0.0 0.00 Pro V% �aen -. VI ' IV VVI I dtftlh 0.0 r 9 2�Ole 0.00 I 1 0.00 bedro9ffit,? 0.0 0$ N � 0.0 ell lst4ta 0.00 %e t'arJ WE %2$.Vle 14M ne�e �gIV MZVV 0 Sise%arq e M 777 Z0, 0.0 77 0.0 0.00 0.0 , Yid:.. .- 3 .x 0.0 0.00 0.0 I- IeVV 0.00 _ 0.0 s` . 0.0 Ref. U -factor Exempt Swinging Door (24 sq. ft. max.) Exempt Glazed Fenestration (15 sq. ft. max.) Vertical Fenestration (Windows and doors) Contact INorration Width Height Qt. Feet Inch Feet Inch Component Width Height Description Ref, U -factor Qt. Feet Inch Inch Feet 5.60 4.,.I', 16.0 ..,6, 20.0 5.60 9.8 2.74 20.0 W 32.0 rriasferd"ro4 8.96 Q 28 12.0 3.36 3.56 P 0.0 0.00 Pro V% �aen -. VI ' IV VVI I dtftlh 0.0 r 9 2�Ole 0.00 I 1 0.00 bedro9ffit,? 0.0 0$ N � 0.0 ell lst4ta 0.00 %e t'arJ WE %2$.Vle 14M ne�e �gIV MZVV 0 Sise%arq e M 777 Z0, 0.0 77 0.0 0.00 0.0 , Yid:.. .- 3 .x 0.0 0.00 0.0 I- IeVV 0.00 _ 0.0 s` . 0.0 0.00 6w a 0.00 IV -I ell Width Height Qt. Feet Inch Feet Inch Component Width Height Description Ref, U -factor Qt. Feet Inch Inch Feet 2,..,2 5.60 4.,.I', 16.0 ..,6, 20.0 5.60 9.8 2.74 20.0 W 32.0 rriasferd"ro4 8.96 Q 28 12.0 3.36 3.56 P 0.0 0.00 Pro V% �aen -. re . IV VVI I dtftlh 0.0 r 9 2�Ole 0.00 0.0 ' 0.00 bedro9ffit,? 0.0 0$ N � 0.0 ell lst4ta 0.00 %e t'arJ WE %2$.Vle 14M ne�e �gIV MZVV 0 Sise%arq e M 777 Z0, 0.0 77 0.0 0.00 0.0 , Yid:.. .- 3 .x 0.0 0.00 0.0 I- IeVV 0.00 _ 0.0 0.00 0.0 0.00 6w a 0.00 IV -I ell 0.00 , le 0.0 0.00 t r 0.00 0.0 0.00 0.0 ell I VVl 0.00 0.01 0.00 3�_ 0.01 III ;;s IV 1 .Y:.�',.;'a N rr VIM U ell pp ell ,. .:?�,. ��,.....�Y- �.,,-.awe_-.� IN r 14 1 44 -==.; _rte;-=, ,-;-1,Yr;Y" �.""`,-.Y'�-%,YYYwMM .,..,�,Y.,✓ a Y c � Ile,_ "�_,...,� ... `."�' �Y, r..Y, Y Yx .f ..,.x Yrr''"-✓,.,„r.;'.Y-,Y ��Y .�Y�. ,�Y r a,`Y-["' � Y u NYNY .n^ rT . ,,.r4 �✓."� sY'"j„ �,--''''.�Y"�ca �r'-.�' ell �'�t� ?YIM `-�„r✓x err n -Y','.. kx...,',�,.�Y3 Y.:x-.r.' Ile vvvvvvv ' u -Y -;Yr^`> e v-�r' r GVe -1 vvvv NOR ll I ell IV Yom%.,.. �-Yell 'a'.. v,x-.s.`zu.✓"_"✓e,.. T Y Y.r,-`r. �. ,._.4Y 2,..,2 5.60 4.,.I', 16.0 ..,6, 20.0 5.60 9.8 2.74 20.0 W 32.0 el 8.96 12.0 3.36 3.56 0.0 0.00 ,. 0.0 . 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 WE Ogg 14M ne�e 0.00 0.0 777 0.0 77 0.0 0.00 0.0 0.00 0.0 3 2.4:1....:..,,,. 0.0 0.00 0.0 0.00 _ 0.0 0.00 0.0 0.00 6w a 0.00 0.0 0.00 , 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.01 0.00 0.01 0.00 rr r r Yx �Ys' r �-Yell MF IV AMA MENEM NO l 44 r � � ow Vell MM Y°r Area UA 20.0 4.00 0.0 0.00 Area UA 20.0 5.60 16.0 4.48 20.0 5.60 9.8 2.74 20.0 5.60 32.0 8.96 12.0 3.36 17.8 3.56 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.01 0.00 0.01 0.00 Sum of Vertical Fenestration Area and UA Vertical Fenestration Area Weighted U = UA/Area Overhead Glazing (Skylights) Component Width Height Sum of Overhead Glazing Area and UA Overhead Glazing Area Weighted U = UA/Area Total Sum Of Fenestration Area and UA (for heating system sizing calculations) 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.01 0.00 147.61 39.90 0.27 Area UA 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.00 167.6 43.90