Engineering CalcsCopyright 2021, SEGA Engineers
STRUCTURAL CALCULATIONS
FOR THE
SOUNDBUILT HOMES RESIDENTIAL PROJECT
Plan L2-2853
October 12, 2021
Job No. : 12-021
Location: Lots 201-398, Tahoma Terra
Yelm, Washington
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010
10 10 10 10////11112222////21212121
STATEMENT OF WORK
SEGA Engineers was asked to provide a lateral loads analysis, shear wall
design, review of major framing members and foundation, and drawing red-lines
for a two story wood framed single family residence. The roof framing is
manufactured trusses, the floor framing is 2x dimensional or wood I-joists, and
the foundation is typical concrete strip footings with a crawl space.
The application and use of these calculations is limited to a single site referenced
on the cover sheet. The cover sheet should have an original signature in blue ink
over the seal. The attached calculations may or may not apply to other sites and
the contractor assumes all responsibility and liability for sites not expressly
reviewed and approved. Please contact SEGA Engineers for use at other sites.
SEGA Engineers will use that degree of care and skill ordinarily exercised under
similar circumstances by members of the engineering profession in this local. No
other warranty, either expressed or implied is made in connection with our
rending of professional services. For any dispute, claim, or action arising out of
this design, SEGA Engineers shall have liability limited to the amount of the total
fee received by SEGA Engineers.
Questions regarding the attached should be addressed to SEGA Engineers.
Greg Thesenvitz, PE/SE
SEGA Engineers
SEGA Engineers Project Plan L2-2853
Structural & Civil Consulting Engineers
Job No.12-021 By:GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date:05/17/21 Sht 1
Design Criteria
International Building Code (IBC), 2018
LOADS
Roof
DL 15 psf
LL 25 psf
Floor
DL 12 psf
LL 40 psf
Wind
Risk Category II
Design Wind Speed 110 mph (Vult)
Copyright 2021, SEGA Engineers
Design Wind Speed 110 mph (Vult)
Kzt 1.00
Exposure B
Seismic
Design Category D
SDS 1.00
Response Factor 6.5
CS =0.154
Importance Factor 1.00
Soil
Allowable Bearing 1,500 psf
Copyright 2021, SEGA Engineers
SEGA Engineers
/ Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010
LOADS
ROOF
DL
FLOOR
Roofing (Comp)
'12" OSB
2x @24"
Insulation
518" GWB
Misc,
LL Snow, Pf
Reduction, Cs
7112 pitch = 30 deg
Total Roof Load
DL Flooring
3!4" Plywood
2x12@16"oc
518" GWB
Misc.
LL Residential
Total Floor Load
DECKS
DL 2 x Decking
2x10@16"oc
Misc
WALLS
LL Residential
Total Deck Load
DL Siding
112" Plywood
2x6@16"oc
Insul
'1211 GWB
Copyright 2017, SEGA Engineers
Project 1-2-2853
Job No. 12-021 By: GAT
Checked Date: 11/16/17 Sht 2
3.5 psf
1.8
3.5
1.1
2.8
1.5
14.2 psf
25 psf
0.00
0.5 psf
2.3
3.3
2.8
1.5
10.4 psf
(115% Load Duration)
(Ct = 1.1, other surfaces)
39.2 psf
40 psf
50.4 psf
4.3 psf
2.8
1.5
8.6
60 psf
3.5
1.5 psf
1.7
0.6
2.2
68.6 psf
9.5 psf
SEGA En ineers PROJECT
Structural & Civil Consulting Engineers
JOB NO. I L 074 FIGURED BY C-
CHECKED BY DATE SHEET ; OF
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
L2 — Z'6'53
AC
'7-/Z Y til
9/ z: P0
'Bi; t e- T'+ri o
-7
20
S%L 1-1 r &L& X�----
f3
V=
(o► 73 } Se
l
Copyright 2012, SEGA Engineers
m
SEGA En ineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
PROJECT" L Z. - zl �& S3
JOB NO. Z Z GFIIG'%;URED BY G; .4^
CHECKED BY DATE +t j,(,SHEET - OF
3
...wry.
t / r low_
JZ 3 LyL
-G! Z.1 d Z r
V = J. 43
7z( 3.z�) (q•s'�L = zd� ,�,���, Nz a�
rte,
3,'3 �z,r j
P` �+4), ZilL jrr�t
C0"n;"
V= zr` l- oc
U,
Copyright 2012, SEGA Engineers
SEGA En ineers - PROJECT
Structural & Civil Consulting Engineers LZ — Z��3
JOB NO. Z _� FIGURED BY L -i A 7-
22939 5E 292nd Place Com, ----✓ -
Black Diamond, Washington 98010 CHECKED BY DATE 1 j*'Z4 SHEET -5 OF
{360} 886-1017
?sr) t) 4 o Pz r z � S�ja� 700 3t-,:
to 4-5 Olt
J740
� ✓ \������ ��j��' ~ � � ,f �?" ���/ 1� ��� r +fir J I f"y'l��
i! 7. tw�
Copyright 2012, SEGA Engineers
SEGA Engineers PROTECT
Structural & Civil Consulting Engineers
JOB NO. FIGURED BY
22939 SE 292nd Place • Black Diamond, Washington 98010
(360) 886-1017 • Fax (360) 886-1016 CHECKED BY DATE�Ii�tj SHEE74C OF
0t7S�- L a,�� r}`��,�'�3 ~— �4 �® '/fit re
15" e nluo
-F-7/,s
�
4k-
�j- 9,-z-kc-
lZ�
Copyright 2010, SEGA Engineers
�� -7'
--- -v4
59t-, )la - f
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Square Footing Design Ftg 36 x 36
Design Parameters
f',: = 2,500 psi Fy = 40,000 psi
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Col DL = 2.4 kip (Service Load)
Col LL = 9.6 kip (Service Load)
Floor LL =
0
psf
Overburden=
0.0 in
(120 pcf assumed)
Slab Thick. =
0.0 in
(150 pcf assumed)
Size_ and Footing Pressure
h =
8.0 in
kip -ft
qn =
1.40
ksf
Req'd Area =
8.57
ft^2
Try 2.95 ft x 2.95 ft
Factored Net Soil Pressure = 2.13 ksf
Project Typical Ftg
Job No. By: GAT
Checked Date: 12/03/15 Sht. 7
All. q = 1,500 psf
< Ftg. Thickness
< Min. Ftg. Size
(1.21D + 1.6L)
Check for Two -Way Shear
Avg d = 4.00 in
Vu = 16.76 kips
bo = 40.00 in (Critical Shear Perimeter)
Bc = 1 (Long Side/Short Side of Column)
phi Vc = 27.20 kips
Phi V, > V„ OK
Check for One-Wav Shear
Vu =
5.598
kips
Phi V, =
12.04
kips
Phi Ve
>
V„ OK
Design Reinforcement
Mu =
4.71
kip -ft
As =
0.51
in^2
a =
0.27
in
Phi Mn =
5.58
kip -ft
Phi Mn
>
Mu OK
AS min =
0.51
in^2 OK
Use (3) - # 4 bars EW _Reinforcement
0.59 in"2
Copyright 2015, SEGA Engineers
SEGA Engineers /
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Square Footin Desi n Ftg 42 x 42
Design Parameters
f', = 2,500 psi Fy = 40,000 psi
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Loads:
Col DL = 3.2 kip (Service Load)
Col LL = 12.8 kip (Service Load)
Floor LL = 0 psf
Overburden = 0.0 in (120 pcf assumed)
Slab Thick. = 0.0 in (150 pcf assumed)
Size and Footing Pressure
h = 8.0 in
q„ = 1.40 ksf
Req'd Area = 11.43 ft"2
Try 3.40 ft x 3.40 ft
Project Typical Ftg
Job No. By: ____GAT
Checked Date: 12/03/15 Sht.
All. q = 1,500 psf
< Ftg. Thickness
< Min. Ftg. Size
Factored Net Soil Pressure = 2.13 ksf (1.21D + 1.6L)
Check for Two -Way Shear
Avg d = 4.00 in
V„ = 22.84 kips
bo = 40.00 in (Critical Shear Perimeter)
BC = 1 (Long Side/Short Side of Column)
phi VG = 27.20 kips
Phi VC > V" OK
Check for One -Way Shear
V, = 8.079 kips
Phi Vc = 13.87 kips
Phi VC > VU OK
Desian Reinforcement
Mu =
7.61
kip -ft
As =
0.70
in A 2
a =
0.32
in
Phi Mn =
7.62
kip -ft
Phi Mn
>
Mu OK
As min =
0.59
in^2 OK
Use (4) - # 4 bars EW �AReinforcement
0.79 in^2
Copyright 2015, SEGA Engineers
SEGA Engineers Project L2-2853
Structural & Civil Consulting Engineers
Job No. 12-021 By: GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date: 06/08/13 Sht.
LATERAL LOADS - (Alternate ASD)
SEISMIC
Maximum Base Shear, V = F SDs W
R
Eq. 12.14-11
where,
F = 1.1 Two -Story Building
SDS =1.00 SS = 1.5 Fa = 1.00 (Table 11.4-1, SS > 1.25)
R = 6.5 Table 12.14-1
W = Seismic Weight
For W:
W..f= (28 ft) (44 ft) (16 psf)+ (2) (28ft+ 44 ft) (4.0ft) (9.5psf) = 25 kips
Weoor= (28 ft) (50ft) (14 psf)+ (2) (28ft+ 50 ft) (8.5 ft) (9.5psf) = 32 kips
W total = 57 kips
Design Base Shear, V =
( .169)
(57 kip)
= 9.7 kip
(x0.6=
E =
9.7 kip
- 6.9 kip
{ x
0.6 =
10.62
psf}
WIND
0.6 =
10.62
psf)
Design Wind Pressure, ps =
A Kz1 Ps30
11.15psf)
where,
+
(45ft)
(5ft)
= 1.00
(17.7psf)
0 - 15 ft
Exposure B
= 1.00
{18.6 psf)
20 ft
Therefore,
1.00
25 ft
Wind Loads Govern for Lateral Design - Side/Side
= 1.00
30 ft
= 1.05
35 ft
KZt = 1.00
P30 = 17.7 psf
110 mph
PO.,5 = ( 1.00
( 1.00 )
(17.7 psf) =
17.70 psf
P20 = ( 1.00 }
( 1.00 )
(17.7 psf) =
17.70 psf
P25 = ( 1.00)
( 1.00 )
(17.7 psf) =
17.70 psf
Pao = ( 1.00)
( 1.00 )
(17.7 psf) =
17.70 psf
P35 = ( 1.05 }
( 1.00 )
(17.7 psf) =
18.59 psf
Design Base Shear: (Wind)
Eq. 28.6-1, Sect. 28.6.3
Figure 28.6-1
Section 26.8
Figure 28.6-1 (ASD)
{x0.6=
(30ft)
10.62
psf}
(x0.6=
+
10.62
psf)
{ x
0.6 =
10.62
psf}
( x
0.6 =
10.62
psf)
(x0.6=
(10ft)
11.15psf)
(17.7 psf)
Vfrn=
(30ft)
(10ft)
(17.7 psf) + (30ft) (5ft)
(17.7psf)
+
30 ft)
(5ft)
(17.7 psf) + (30ft) (5ft)
(17.7 psf)
+
30 ft)
(1ft)
{18.6 psf)
=13.8x0.6 8.3 kips
V515=
(57ft}
(10ft)
(17.7 psf) + (52ft) (5ft)
(17.7 psf)
+
(45ft)
(5ft)
{17.7 psf) + (17ft} (5ft)
(17.7psf)
+
(5ft)
(1 ft)
{18.6 psf)
=20.3 x 0.6 = 12.2 kips
Therefore,
Wind Loads Govern for Lateral Design - Front/Back
Wind Loads Govern for Lateral Design - Side/Side
Copyright 2013, SEGA Engineers
SEGA Engineers-/
Structural & Civil Consulting Engineers
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
PROJECT L,'L— ZSC3
JOB NO. Z 0Z4 FIGURED BY
CHECKED BY DAT?r*Zti L SHEET-7�OF
T f.�ta90a t r
�; 3 Z S_rf-
q*
-O.-4
Copyright 2012, SEGA Engineers
SEGA Engineers PROJECT
Structural & Civil Consulting Engineers GZ_ �'
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
JOB NO. rZ� FIGURED BY 6,4r
CHECKED BY DATE -'y/=, SHEET+q OF
7' 3,573* h, -C - "�-dcP14`. �>
tl'a'n7't 3 �P 1, q7
VK kjk��s")(V,
T- r (
Copyright 2012, SEGA Engineers
/GL 3 r 1--0n10fAS
N�
Xdw
Jt -)14S&
LS?A3D
w
+1t',,'-
ov'^] .1 4 ezq
Wm
E:
SEGA Engineers-
PROJECT
Structural & Civil Consulting Engineers
JOB NO. Z r FIGURED BY 6AA-r
CHECKED BY DATE / LSHEEf I OF
22939 SE 292nd Place
Black Diamond, Washington 98010
(360) 886-1017
L z. — -L? S3
-!;VOW- 1 L
F_ vimar
=
Copyright 2012, SEGA Engineers
SEGA ]Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place • Black Diamond, Washington 98010
(360) 886-1017 • FAX 886-1016
PROJECT L2-2,553
JOB NO. 12-021 FIGURED BY G,47
CHECKED BY DATE 02/21/12 SHEET � OF
SHEAR WALL KEY PLAN
17
3---------------------------A
UFFER FLOOR
A = 1,322 5Q FT
-
Q �
5
L51A30 - HDR 4 SILL: •
U
TO 3x BLOCKING.
A�`Tr
(TYP. 2 PLACES) LSTA30 - HDR 4 SILL
TO 3x BLOCKING
i
________
(1YP. 2 PL4CE5)
1 LSTA30 - HDR 4 SILL
TO 3x BLOCKING.
(TI .2 PLACES)
2 \yR�ryl 2 a�
2
3
3
LSTA30 - HDR 4 SILL
3x BLOCKING.
1171.2 PLACES)
'
U
sr
<ar
B B
A A
A
MAIN FLOOR
A = 1,063 5Q FT
A
QSr�
G
6 6
6
ti G
y� tF
A =391 50 FT
A
❑ ❑
7 7
(TYP. OF I
SHEAR WALL SCHEDULESHEAR WALL SCHEDULESHEAR WALL SCHEDULEMarkMinimumSheathing AnchorRemarks (4)MarkMinimumSheathing AnchorRemarks (4)MarkMinimumSheathing AnchorRemarks (4)Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3)1/" OSB or5/" @ 60" o.c.A1/2" OSB or8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA1/2" OSB or8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA/2" OSB or8d @ 6" o.c./8" @ 60" o.c.Qall = 230 plfCDXCDXCDXB1/" OSB or8d @ 4" o.c.5/" @ 32" o.c.Qall = 350 plfB1/2" OSB or8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB/2" OSB or8d @ 4" o.c./8" @ 32" o.c.Qall = 350 plfCDXCDXCDX15C1/2" OSB or8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC1/2" OSB or8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC/2" OSB or8d @ 3" o.c./8" @ 16" o.c.Qall = 450 plfCDXUse minimum 3x studsCDXUse minimum 3x studsCDXUse minimum 3x studsat abutting panel edgesat abutting panel edgesat abutting panel edgesand stagger nails.and stagger nails.and stagger nails.RSee Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for ConstructionNotes:Notes:Notes:1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathingNotes:1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing(24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance withAF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.