Loading...
1311L Submittal 1.23.23Yelm WRF 913 Northern Pacific Rd SE Yelm, WA 98597 Fire Alarm System Equipment Datasheets Battery Calculations Certifications E2 JOB # 1311C Prepared by: Emma Hyde Howe E-Squared Systems, LLC PO Box 731227 Puyallup, WA 98373 Ph: 253.284.3707 License: ESQUASL963BR FIRE ALARM Table of Contents Tab 1 …………………FIRE ALARM CONTROL PANEL Tab 2 …………………BOOSTER POWER SUPPLY Tab 3 …………………NOTIFICATION DEVICES Tab 4 …………………ADDRESSABLE INITIATING DEVICES Tab 5 …………………SYSTEM BATTERIES Tab 6 …………………BATTERY CALCULATIONS Tab 7 …………………CERTIFICATIONS TAB 1 FIRE ALARM CONTROL PANEL • Capable of providing up to 198 points to satisfy smaller installation needs • Connect up to 17 panels on one site with convenient single- point access using the SK-NIC Network Interface Card. Connected panels can have mixed compatible FACP models • Convenient field-upgradeable GJSNXBSF •#VJMUJOEVBMQBUI 1054BOE*1 DPNNVOJDBUJPOTXJUI PQUJPOBMDFMMVMBS NPEFMTBWBJMBCMFGPS SFMJBCMFCBDLVQ SFQPSUJOH • 6860 annunciator with a 4 x 40 large display •'PVSVTFS QSPHSBNNBCMFCVUUPOT NJOJNJ[FUJNFTQFOU FYFDVUJOHDPNQMFYPS SPVUJOFUBTLT • Built-in USB interface for convenient and quick programming • Programmable date setting for automatic and convenient Daylight Saving Time changes •+VNQ4UBSUkBVUP QSPHSBNNJOHSFEVDFT JOTUBMMBUJPOUJNF • 125 software zones and 125 output groups for fl exible design options 6808 "EESFTTBCMF'JSF"MBSN$POUSPM1BOFM 5IFJTBOBEESFTTBCMFGJSFBMBSNDPOUSPMQBOFM '"$1 UIBUJTB EJSFDUSFQMBDFNFOUGPSUIF'"$15IFDBOCFDPOGJHVSFEUP BDIJFWFBQPJOUDBQBDJUZPGQPJOUT*UIBTPOFCVJMUJOTJHOBMJOHMJOF DJSDVJU 4-$ XIJDIDBOTVQQPSU4ZTUFN4FOTPSk 4, TFOTPSTBOE 4,NPEVMFTPS)PDIJLJk 4% EFWJDFTQFSMPPQ "DPNNPODPNNVOJDBUJPOTBOEBOOVODJBUJPOMJOLBMMPXTVQUP QBOFMTUPCFDPOOFDUFEWJBDPQQFSPSfiCFSPQUJDDBCMF"EFTJHOBUFE QBOFMJTDPOfiHVSFEBTUIFDPNNVOJDBUPSGPSBMMQBOFMTJOUIFMJOLGPS DPOWFOJFOUTJOHMFQPJOUDPNNVOJDBUJPOT*UBMTPIBTBCVJMUJO EVBM MJOF1054BOE*1DPNNVOJDBUPSXJUIBEEJUJPOBMDFMMVMBSPQUJPOT BWBJMBCMF 5IFTZTUFNDBOCFFOIBODFECZBEEJOHNPEVMFTTVDIBTUIF SFNPUFBOOVODJBUPSXIJDIBMTPIBTGPVSQSPHSBNNBCMFGVODUJPO CVUUPOTUPIFMQBVUPNBUFUBTLTBOESFEVDFUJNFTQFOUBUUIFQBOFM 48*'5kXJSFMFTTDPNQBUJCJMJUZQSPWJEFTPQUJPOTGPSXJSFMFTTEFUFDUJPO UISPVHIB$MBTT"NFTIOFUXPSL*UJTJEFBMGPSIBSEUPXJSFMPDBUJPOT  CVJMEJOHTXIFSFOFXXJSJOHJTOPUBMMPXFE PSUPQSPWJEFBOFBTZJOTUBMM fi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• General Alarm (Red)'MBTIFTJGJO BMBSNTPMJEXIFOBMBSNJTTJMFODFE • Supervisory (Yellow):'MBTIFTJGB TVQFSWJTPSZDPOEJUJPOFYJTUTTPMJE XIFOTVQFSWJTPSZJTTJMFODFE •System Troubles (Yellow)'MBTIFT JGBUSPVCMFDPOEJUJPOFYJTUT TPMJEXIFOUSPVCMFJTTJMFODFE •System Silenced (Yellow) 0OXIFOBOBMBSN USPVCMFPS TVQFSWJTPSZDPOEJUJPOIBTCFFO TJMFODFECVUOPUZFUDMFBSFE • System Power (Green): 'MBTIFT GPS"$GBJMVSFTPMJEXIFO QPXFSTZTUFNTBSFOPSNBM USER INTERFACE 5IFCVJMUJOYBOOVODJBUPS XJUIDIBSBDUFS-$%EJTQMBZ BOEMBSHFFBTZUPVTFUBDUJMF UPVDIQBEDBOCFVTFEGPSTZTUFN PQFSBUJPO QSPHSBNNJOHBOE NBJOUFOBODF*UIBs fiWF-&%TGPS BMBSN TVQFSWJTPSZ TZTUFNUSPVCMF  TZTUFNTJMFODFEBOETZTUFNQPXFS 4ZTUFNPQFSBUJPOTJODMVEFTJMFODJOH BMBSNTBOEUSPVCMFT SFTFUUJOHBMBSNT BOEUIFEJTQMBZPGBMBSNUSPVCMFTBOE NFNPSZ5IFTZTUFNTOPOWPMBUJMF FWFOUIJTUPSZCVGGFSTUPSFT  FWFOUTGPSWJFXJOHGSPNUIFCVJMU JOPSSFNPUFBOOVODJBUPS4ZTUFN PQFSBUJPOTDBOCFJOJUJBUFEXJUIB NFDIBOJDBl fiSFfiHIUFSTLFZPSB WBMJEUPEJHJUPQFSBUPSTDPEF •UL-JTUFE4 • CSFM • FDNY$0" •FMBQQSPWFE SIGNAL LINE CIRCUIT (SLC) 5IF4-$MPPQTVQQPSUTNVMUJQMF EFWJDFUZQFT NBJOUFOBODFBMFSUT BOEB CVJMUJOTFOTPSUFTUUPDPNQMZXJUI/'1" DBMJCSBUJPOUFTUJOHSFRVJSFNFOUT INDICATOR LIGHTS PROGRAMMING 5IFTZTUFNPGGFSTTFWFSBMPQUJPOT UPTJNQMJGZBOETQFFEVQQSPHSBNNJOH +VNQ4UBSUkBVUPQSPHSBNNJOH NJOJNJ[FTQSPHSBNNJOHSFRVJSFEUPTUBSU BOFXTZTUFN5IFCVJMUJOLFZQBE PSUIF  PSSFNPUF BOOVODJBUPSTHJWFZPVPOTJUFBDDFTTUP DVSSFOUTZTUFNQSPHSBNNJOH 1SPHSBNNJOHDBOBMTPCFBDDPNQMJTIFE VTJOHUIF8JOEPXTkCBTFE)POFZXFMM 'JSF4PGUXBSF4VJUF )'44 QSPHSBN SOFTWARE TOOLS SKST:4JMFOU,OJHIU4FMFDUJPO5PPM QSPWJEFTUIFJOTUBMMFSPSEFTJHOBSDIJUFDU XJUIB8JOEPXTkTPGUXBSFTZTUFN DPOGJHVSBUJPOUPPMUPDSFBUFBEFUBJMFE#JMM PG.BUFSJBM #0. BOECBUUFSZ DBMDVMBUJPOT HFSS:)POFZXFMM'JSF4PGUXBSF4VJUF QSPWJEFTDPNNVOJDBUJPOBOEQBOFM QSPHSBNNJOH EFUFDUPSTUBUVT FWFOU IJTUPSZBOEBEEJUJPOBMEBUB3FRVJSFTB 1$SVOOJOH.JDSPTPGUk8JOEPXTk ADDITIONAL INFORMATION 5XJTUFEVOTIJFMEFEQBJS XJSFJTSFDPNNFOEFE 5IFBMTPIBTQSFTFUOPUJGJDBUJPO DBEFODFQBUUFSOT JODMVEJOH"/4*  "(&/$:-*45*/(4"/%"11307"-4 /1'" /'1" /'1" /'1"  /'1"$FOUSBMTUBUJPOSFNPUF 4JHOBMJOH-PDBM1SPUFDUJWF4JHOBMJOH 4ZTUFNT"VYJMJBSZ1SPUFDUFE1SFNJTFT 6OJU8BUFS%FMVHFSFMFBTJOHTFSWJDF 4VJUBCMFGPSBVUPNBUJD NBOVBM  XBUFSGMPX TQSJOLMFSTVQFSWJTPSZ %"$5 OPODPEFE TJHOBMJOHTFSWJDFT ORDERING INFORMATION "EESFTTBCMF'JSF"MBSN $POUSPM1BOFM 3FEDBCJOFU  COMPATIBLE ANNUNCIATORS 6860:Y-$%SFNPUe fiSF BOOVODJBUPS MJOFTBOEVQUP DIBSBDUFST QFSTZTUFNGPVS QSPHSBNNBCMFCVUUPOT 5860:Y-$%SFNPUe fiSF BOOVODJBUPSJTHSBZ3JTSFE 6855:Y-$%SFNPUe fiSF BOOVODJBUPS 5865-3 or 5865-4:-&%BOOVODJBUPST DBOEJTQMBZVQUP-&%T SFEBOE ZFMMPX 5IFIBTLFZTXJUDIFT GPSTJMFODFBOESFTFU BOEBTZTUFN USPVCMF-&% 5880:-&%*0NPEVMFIBT QSPHSBNNBCMF-&%PVUQVUTBOEFJHIU TVQFSWJTFEESZDPOUBDUJOQVUTXIJDIBSF VTFGVMGPSDVTUPNBQQMJDBUJPOT:PVDBO VTFVQUPFJHIUNPEVMFTPOPOF DPOUSPMQBOFMGPSNBYJNVm flFYJCJMJUZ *UTDPNQBDUTJ[FBMMPXTNPVOUJOHJOTJEF UIFBOOVODJBUPS PSJOBOBDDFTTPSZ DBCJOFU 6808 COMPATIBLE DEVICES AND ACCESSORIES 4FFUIFEBUBTIFFUTMJTUFECFMPXGPSB DPNQMFUFMJTUJOHPGUIF4, 4%PS48*'5 EFWJDFT 4,%FWJDFT%BUB4IFFU 4%%FWJDFT%BUB4IFFU  48*'5 XJSFMFTTEFWJDFT 'PSBDPNQMFUFBOEDVSSFOUMJTUJOHPG DPNQBUJCMFEFWJDFTBOEBDDFTTPSJFT WJTJU www.silentknight.com Important::PVDBOOPUNJY4,BOE4% EFWJDFTJOUIFTBNFGJSFBMBSNTZTUFN 1BHFPGŘ# 4,$0.1"5*#-&"%%3&44"#-& DEVICES SK-ACCLIMATE: Multi criteria photoelectric smoke detector with thermal 135°F fixed temperBture SK-BEAM: Reflected beam smoke detector without test feature SK-BEAM-T: Reflected beam smoke detector with test feature SK-CONTROL: Supervised control module SK-CONTROL-6: Six circuit supervised control module SK-DUCT: Photoelectric duct smoke detector with extended air speed range SK-FIRE-CO: Four criteria fire and carbon monoxide detector SK-HEAT: Fixed thermal detector (135°F) 4,)&"58'JYFEUIFSNBMEFUFDUPS m' XIJUF SK-HEAT-ROR: Fixed rate of rise detector (135°F) 4,)&"53038'JYFESBUFPGSJTF EFUFDUPS m' XIJUF SK-HEAT-HT: Fixed high temperature thermal detector (190°F) 4,)&"5)58'JYFEIJHIUFNQFSBUVSF UIFSNBMEFUFDUPS m' XIJUF SK-ISO: Fault isolator module SK-MINIMON: Mini monitor module SK-MONITOR: Monitor module SK-MONITOR-2: Dual input monitor module SK-MON-10: 10 input monitor module SK-PHOTO: Photoelectric smoke detector 4,1)05081IPUPFMFDUSJDTNPLF EFUFDUPS XIJUF SK-PHOTO-T: Photoelectric smoke detector with thermal (135°F fixed temperBture) 4,1)050581IPUPFMFDUSJDTNPLF EFUFDUPSXJUIUIFSNBM m'GJYFE UFNQFSBUVSF XIJUF SK-PHOTOR: Photoelectric detector with remote test capability 4,1)050381IPUPFMFDUSJDEFUFDUPS XJUISFNPUFUFTUDBQBCJMJUZ XIJUF SK-PULL-SA: Addressable single action pull station SK-PULL-DA: Addressable dual action pull station SK-RELAY: Addressable relay module SK-RELAY-6: Addressable Six relay control module SK-RELAYMON-2: Addressable Dual relay/monitor module SK-ZONE: Addressable zone interface module SK-ZONE-6: Six zone interface module # *7 CBTFGPS4,84FSJFT #-1NPVOUJOHCBTF # #- *7 8)*5& GMBOHFMFTTCBTF #'MBOHFMFTTNPVOUJOHCBTF #4 *7 8) *OUFMMJHFOUTPVOEFSCBTF #4*OUFMMJHFOUTPVOEFSCBTF #4-' *7 8) -PX'SFRVFODZ JOUFMMJHFOUTPVOEFSCBTF #4-'-PXGSFRVFODZJOUFMMJHFOU TPVOEFSCBTF #3# *7 8) 3FMBZCBTF #3#3FMBZCBTF ##* *7 8) *TPMBUPSCBTF B224BI: Isolator base SD COMPATIBLE ADDRESSABLE DEVICES SD505-6AB: Addressable 6" base SD505-6IB: Addressable 6" short circuit isolator base SD505-6RB: Addressable 6" relay base SD505-6SB: Addressable 6" sounder base SD500-AIM: Addressable input module (switch input) SD500-ANM: Addressable notification module SD500-ARM: Addressable relay module SD505-DTS-K: Remote test switch and LED indicator for the SD505-DUCTR SD505-DUCT: Addressable Duct Smoke Detector. SD505-DUCTR: Addressable Duct Detector housing with relay base. SD505-HEAT: Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C). SD500-LIM: Addressable Line isolator module SD500-MIM: Addressable Mini input monitor module (switch input) SD505-PHOTO: Photoelectric smoke detector SD500-PS/-PSDA: Addressable Single or dual action pull station SD500-SDM: Addressable smoke detector module AUDIBLE/VISIBLE DEVICES These AV devices are all 2-wire. Color: “R” indicates red; “W” denotes white. For a complete listing of Silent Knight AV devices go to XXXTJMFOULOJHIUDPN. CHSRL/CHSWL: Wall chime/strobe CHSCRL/CHSCWL: Ceiling chime/strobe CHRL/CHWL: Wall chime HRL/HWL: Wall horn P2RL/P2WL: Wall horn/strobe PC2RL/PC2WL: Ceiling horn/strobe SRL/SWL: Wall strobe SCRL/SCWL: Ceiling strobe SPSCRL/SPSCWL: Ceiling speaker/strobe SPSRL/SPSWL: Wall speaker/strobe SPRL/SPWL: Wall speaker SPCRL/SPCWL: Ceiling speaker SWIFT WIRELESS DEVICES SWIFT is only compatible with System Sensor (SK) devices. It is not compatible with Hochiki (SD) devices. 84,8(*8JSFMFTT(BUFXBZ 84,1)0508JSFMFTT1IPUPFMFDUSJDTNPLF EFUFDUPS WSK-PHOTO-T:8JSFMFTT.VMUJDSJUFSJB QIPUPFMFDUSJDTNPLFEFUFDUPSXJUIUIFSNBM EFUFDUJPO m'GJYFEUFNQFSBUVSF BOE #8CBTF WSK-HEAT:8JSFMFTT)FBU  m'GJYFE UFNQFSBUVSF BOE#8CBTF WSK-HEAT-ROR:8JSFMFTTIFBU 303 m'GJYFEUFNQFSBUVSF BOE#8 CBTF WSK-MONITOR:8JSFMFTTNPOJUPSNPEVMF WSK-RELAY:8JSFMFTTSFMBZNPEVMF W-USB:48*'55PPMT64#USBOTDFJWFSVTFE GPSDPNNVOJDBUJPOXJUI48*'5EFWJDFT SBUS ACCESSORIES 5496:"BNQOPUJGJDBUJPOQPXFSFYQBOEFS XJUIGPVSQPXFSMJNJUFEOPUJGJDBUJPO BQQMJBODFDJSDVJUPVUQVUT 5883:3FMBZ*OUFSGBDF1SPWJEFT'PSN$ SFMBZT 5824:4FSJBM1BSBMMFM1SJOUFS*OUFSGBDF .PEVMFGPSQSJOUFSDPOOFDUJPO 5895XL:1PXFS4VQQMZXJUITJY'MFYQVUƇ DJSDVJUT BOEUXP'PSN$SFMBZT.BYQFS TZTUFN 5815RMK:3FNPUFNPVOUJOHLJU %JNFOTJPOTŠ8YŠ)YŠ% COMMUNICATION OPTIONS CELL-CAB-SK:$FMMVMBSDPNNVOJDBUPS  NFUBMFODMPTVSFXJUIMPDLLFZ CELL-MOD:$FMMVMBSDPNNVOJDBUPS QMBTUJD FODMPTVSF  4PMFQBUI QPXFSFECZQBOFM IPGSM-4G:%VBMQBUIGJSFBMBSN DPNNVOJDBUPS DFMMVMBSBOEPS*1 QSJNBSZPS CBDLVQ TFMFDUBCMF SK-IP-2:3FNPUFSFQPSUJOHWJBUIF*OUFSOFU 3FRVJSFTB7JTPS"MBSNkSFDFJWFSBUUIFDFOUSBM TUBUJPO MISC. ACCESSORIES SK-NIC:/FUXPSL*OUFSGBDF$BSE1SPWJEFTB DPNNPODPNNVOJDBUJPOTMJOLGPSUIF SK-NIC-KIT:*OTUBMMBUJPO"DDFTTPSZ,JU SK-FML:'JCFS0QUJD.VMUJ.PEF  USBOTNJUUFSBOESFDFJWFS SK-FSL:'JCFS0QUJD4JOHMF.PEF RBB:3FNPUFCBUUFSZCPYBDDFTTPSZDBCJOFU GPSCBUUFSJFTUIBUBSFUPPMBSHFUo fiUJOUIF '"$1DBCJOFU%JNFOTJPOTŠ8YŠ)Y Š% NN8YNN)YNN%  SK-SCK:4FJTNJD$PNQMJBODF,JUVTFEUP TFDVSFMZGBTUFOCBUUFSJFTUPUIe fiSFQBOFM 1BHFPGŘ# 'MFYQVUk )POFZXFMMk  +VNQ4UBSUk 4JMFOU,OJHIUk  48*'5k BOE4ZTUFN 4FOTPSkBSFSFHJTUFSFE USBEFNBSLTPG)POFZXFMM *OUFSOBUJPOBM*OD )PDIJLJkJTBSFHJTUFSFE USBEFNBSLPG)PDIJLJ $PSQPSBUJPO.JDSPTPGUk BOE8JOEPXTkBSF SFHJTUFSFEUSBEFNBSLTPG .JDSPTPGU$PSQPSBUJPO 5IJTEPDVNFOUJTOPU JOUFOEFEUPCFVTFEGPS JOTUBMMBUJPOQVSQPTFT8F USZUPLFFQPVSQSPEVDU JOGPSNBUJPOVQUP EBUFBOEBDDVSBUF8F DBOOPUDPWFSBMMTQFDJGJD BQQMJDBUJPOTPSBOUJDJQBUF BMMSFRVJSFNFOUT"MM TQFDJGJDBUJPOTBSFTVCKFDU UPDIBOHFXJUIPVUOPUJDF 'PS5FDIOJDBM4VQQPSU DBMM  5FDIOJDBM4QFDJGJDBUJPOT PHYSICAL Overall Dimensions:Š8YŠ)YŠ% Shipping Weight:MCT Color:3FE ENVIRONMENTAL Operating Temperature:m'UPm' m$UP m$ Humidity:UPSFMBUJWFIVNJEJUZ OPO DPOEFOTJOH ELECTRICAL 6808 Primary AC:7"$!)[ "5PUBM "DDFTTPSZ-PBE"!7%$QPXFSMJNJUFE Standby Current:N" Alarm Current:N" Battery Charging Capacity:UP") Battery Size:")UP")NBYBMMPXFEJODPOUSPM QBOFMDBCJOFU-BSHFSDBQBDJUZCBUUFSJFTDBOCF IPVTFEJO3##BDDFTTPSZDBCJOFU Honeywell Silent Knight $MJOUPOWJMMF3PBE /PSUIGPSE $5 ]#] g)POFZXFMM*OUFSOBUJPOBM*OD NOTIFICATION APPLIANCE CIRCUITS (NACs) Four programmable circuits which can be programmed individually as: NACs:"!7%$QFSDJSDVJU QPXFSMJNJUFE XJUIBNBYJNVNDVSSFOUPG" Auxiliary Power Circuits:"!7%$QFSDJSDVJU  QPXFSMJNJUFE 4VQQPSUT$MBTT# 4UZMF BOE$MBTT" 4UZMFPS  DPOfiHVSBUJPOGPSUIF4-$ WIRING:4FFUIFQSPEVDUNBOVBMGPSXJSJOHEFUBJMT TAB 2 BOOSTER POWER SUPPLY SERIES 6 Amp and 10 Amp, 24 Volt Power Supplies The PS Series are independently configurable power supplies, allowing you to pair any input with any output, and feature LED diagnostics for troubleshooting. The PS Series is a remote power supply line from Gamewell-FCI. The HPF-PS6 is a 6 amp and the HPF-PS10 is a 10 amp, remote power supply with battery charger that maybe connected to any 12 or 24 volt fire alarm control panel (FACP) or used as a standalone power supply. The PS Series provides 24 VDC power for NACs (notification appliance circuits) configured as either Class B or Class A (requires the ZNAC-PS option card) with multiple sync protocol options. The PS Series also provides auxiliary power, constant or resettable, suited for detectors, annunciators, door holders, and other fire alarm system peripherals. The PS Series cabinet can hold two 7 AH or 18 AH batteries and can charge up to 33 AH batteries in a separate cabinet. FEATURES AND BENEFITS • Up to five (6 amp model) or seven (10 amp model) independently -configurable, power - limited output circuits for: —Class B and/or Class A NACs —Class B and/or Class A resettable or non- resettable 24V auxiliary power —door holder power • Converts from Class B to Class A wiring without losing any outputs using the ZNAC- PS converter card (sold separately) • Optimal for powering four -wire smoke detectors, annunciators, and other system peripherals requiring regulated power • Optional addressable control, monitor, and relay modules and power -supervision relay (EOLR-1) • Configurable for ANSI° Temporal 3 or Temporal coded output • UL -Listed NAC synchronization using System Sensor', Wheelock', Gentex°, or AMSECO° appliances • Synchronization can be triggered from FACP NAC/remote sync outputs, cascaded power supply, or a control module, single or multi, which may be housed within the power supply cabinet • Ability to cascade up to four power supplies • Two (6 amp model) or three (10 amp model) fully -isolated input/control circuits which can be programmed to any output • Two Form C normally -closed trouble relays for AC Trouble and General Trouble • 6 or 10 amp full load output, respectively, with 3 A maximum/circuit • Individual NAC power and trouble LEDs for diagnostic efficiency • Trouble history mode for diagnostic support • Wide range end -of -line supervision value (normal: 2-27K ohms) • Selectable earth fault detection (enable or disable) • AC trouble report delay timer • Completely configurable via onboard DIP switches, no extra software required • Self-contained in compact, locking cabinet constructed of heavy gauge steel with a corrosion -resistant powder coat chip and scratch -resistant finish • Cabinet designed with ten double knockouts and a removable door for ease of installation and wiring • Includes integral battery charger capable of charging up to 33 AH batteries • Cabinet can house two 7 AH or 18 AH batteries • Battery charger may be disabled via DI P switch for applications requiring larger batteries and external battery charger • Removable terminal blocks accommodate up to 12 AWG (3.1mm2) wire HPF-PS6/10 HPF-PS61106 Works with any UL 864 FACP which utilizes an industry -standard reverse -polarity notification circuit HPF-PS6/10 include the- Honeywell Power Products lock set (PN: 17059) and key (PN: 17051) Honeywell arrietiaell ,CM,4 �.,n ORDERING INFORMATION HPF-PS6: 6.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red --► HPF-PS6B: 6.0 A,120 VAC remote charger power supply in a lockable, metal enclosure, black HPF-PS10:10.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red HPF-PS1013: 10.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, black ZNAC-PS: Optional Class A converter card, sold separately AOM-2SF: Addressable Control Module for one Class B or Class A zone of supervised, polarized Notification Appliances. Notification Appliance Circuit option requires external 24 VDC to power notification appliances. AOM-2RF: Addressable relay module containing two isolated sets of Form -C contacts, which operate as a DPDT switch AMM -4F: Addressable Monitor Module for one zone of normally open dry -contact initiating devices. Includes plastic cover plate and end -of -line resistor. Module may be configured for either a Class B or Class A AMM -21F: Dual Monitor Module. Same as AMM -4F except it provides two inputs for Class B wiring only AMM-2RIF: Provides two monitored inputs and two Form -C relays. Functions in Class B wiring only MMO-6SF: Six -circuit supervised control module MMO-6RF: Six Form -C relay control module EOLR-1: 12/24 VDC end -of -line relay for monitoring four -wire smoke detector power BAT -1270 -BP: Battery, 12 volt, 7.0 AH, 5 -pack (two required) BAT -12180 -BP: Battery, 12 volt, 18AH, 2 -pack BAT -12330: Battery, 12 volt, 33AH SEISKIT-MULTI-1: Seismic kit for the PS Series. Includes bracket and hardware for two 7AH or two 18AH batteries. 17070: Alternate Honeywell Gamewell-FCI lock set, PK -625, 3/8" cam Page 2 of 3 — 9021-61096:B • 1/25/2021 HPS SERIES TECHNICAL SPECIFICATIONS PRIMARY (AC) POWEk H PF-PS6(B): 120 VAC, 50/60 Hz, 5.OA maximum HPF-PS10(B): 120VAC, 50/60 Hz, 6.2 A maximum Wire Size: #12-14 AWG with 600 V insulation COMMAND INPUT CIRCUIT Trigger Input Voltage: 9 to 32 VDC Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 -16 V) RELAY CIRCUITS Trouble Contact Rating: 4 A at 24 VDC OUTPUT CIRCUITS • 24 VDC filtered • HPF-PS6B: T138-TB9 — lA Regulated, 3A special applications; TB10-TB12 — 0.3A Regulated, 3A special applications • HPF-PS1013: T138-TI311-1.5A Regulated, 3A special applications; TB12-TB14 — 0.3A Regulated, 3A special applications • 6.0 A (HPF-PS6B) or 10.0 (HPF-PS10B) maximum total continuous current for all outputs Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.gamewell-fci.com SECONDARY POWER (BATTERY) CHARGING CIRCUIT • Supports lead -acid batteries only • Float -charge voltage: 27.6 VDC • Maximum current charge: 1.5 A • Maximum battery capacity: 18 AH (inside cabinet) • Maximum battery charging capacity: 33 AH (external cabinet) PHYSICAL Dimensions: 20.0"H x 14.5°W x 3.5"D (cm: 50.8H x 36.83W x 8.9D) Weight: with two 7Ah batteries is 24 pounds (10.9 kg), with two 18 AH batteries is 39 pounds (17.7 kg) STANDARDS AND CODES The HPF-PS complies with the following standards: NFPA 72: National Fire Alarm Code UL 864: Standard for Control Units for Fire Alarm Systems (NAC expander mode) UL 1481: Power Supplies for Fire Alarm Systems AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S24562 CSFM: 7315-1637:0505 FDNY Approved FM Approved 9021-61096 1 B 1 01/21 ©2021 Honeywell International Inc. Honeywell ao 11 1313-2 Series Cabinet (1313-2, 1313-21F, MBB -2) Product Installation Document PN 51880:A2 8/16/2013 13-726 The BB -2 Series Cabinet is hinged on the left and is shipped assembled with a chassis installed. It is designed to be mounted a minimum of 6 inches (15.24 cm) below the Fire Alarm Control Panel. Below are the cabinet dimensions for installation. 4 9.23 in. (23.44 cm.)�! Door 12.22 in. O (31.04 cm.) 000000000000000000000 000000000000000000000 000000000000000000000 -in. -(1.71 cm.) 9 in. (22.86 cm.) Cabinet 1.31 in. 2.75 in. (3.33 cm.) (6.99 cm.) 1.31 in. 4 6 in.(15.24 cm.) (3.33 cm.) O I0.87 in. in. -�+---------------------------------�- - - (2.21 cm.) � (3.6 (3.63 cm.) 10.25 in. 12 in. (26.04 cm.) (30.48 cm.) , O , O 0.25 in. (0.64 cm.) 1.50 in. x CO Diameter (3.81 cm.) ISO-6 Module ISO-6 Isolator Module Addressable Devices General ISO-6 Six Isolator Module The ISO-6 Six Isolator Module is an automatic switch that opens when the line voltage drops below four volts. Isolator modules should be spaced between groups of sensors or spaced with modules in a loop to protect the rest of the loop. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them. The remaining units on the loop continue to fully operate. Ordering Information ISO-6: Fault Isolator Module FEATURES & BENEFITS • Provides a removable 12 AWG to 18 AWG plug-in terminal blocks • Displays individual LED indicators • Unused addresses may be disabled • Contains rotary address switches • Complies with Class A or Class B operation • Includes mounting hardware • Mounts up to two modules in a BB-2 enclosure (optional) • Mounts up to six modules in a BB-6 enclosure with CH-6 chassis (optional) ISO-6 Technical Specifications 9021-60896 | B | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Velociti® E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters’ Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s ISO-6 and other products available by visiting www.Gamewell-FCI.com SYSTEM General Specifications: Operating Voltage: 15 to 32 VDC Maximum SLC Wiring Resistance: 40 Ohms Temperature Range: 32°F to 120°F (0° to 49°C) Relative Humidity: 10% to 85% non-condensing Wire Gauge: 12 to 18 AWG Dimensions: 6.8”H × 5.8”W × 1.25”D Specifications ISO-6: Standby Current: 2.7 mA Maximum Current Draw: 102 mA Specifications BB-2 Enclosure: Dimensions: 12½”H × 9½”W × 3.67½”D Specifications BB-6 Enclosure: Dimensions: 24½”H × 12.55½”W × 6.47½”D Accessories: . TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The ISO-6 is designed to comply with the following standard: UL Standard: UL 268 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S1949 ULC Listed: C5669 CSFM: 7300-1653:0160 FM: 3012062 MSFM: 2102 ISO 9001 Certification Figure 1 displays the BB-6 Enclosure with the CH-6. Figure 1 BB-6 Enclosure with CH-6 Chassis Honeywell SILENT KmGfff SK -ZONE -6 Six Zone Interface Module The inputs on the SK -ZONE -6 share acorn mon FACP signaling line circuit (SLC) input, and the initiating device circuits share a common external power supply. Otherwise, each input on the module operates independently from the others. If needed, you can disable a maximum of two unused inputs on the SK -ZONE -6 board. It transmits the status of a zone of two -wire detectors to the FACP. Status conditions are reported as normal, open, or alarm. The SK -ZONE -6 supervises the zone of detectors and the connection of the external power SUPPLY. All two -wire detectors being monitored must be UL compatible with the SK -ZONE -6. INSTALLATION The SK -ZONE -6 mounts in the Silent Knight IDP-ACB cabinet. The IDP- ACB has a built in chassis that will accommodate one or two SK -ZONE -6 modules. FEATURES & BENEFITS • Converts a Removable 12 to 18 Up to two unused conventional two -wire AWG plug-in terminal modules can be loop to an SLC loop blocks disabled • Six zone inputs • Individual LED for • Fully supervised each relay contact • Support for Class B • Two module mounting and Class Awiring in the IDP-ACB cabinet • Rotary address switches for fast installation • Mounting hardware included • UL Listed SK -ZONE -6 SK -ZONE -6 Technical Specifications PHYSICAL Height: 6.8"H x 5.8" W x 1.0"D Shipping Weight: 6.3 oz (196 g) ELECTRICAL Operating Voltage: 15 — 32VDC SLC Standby & Alarm Current: 2mA max SLC Loop Resistance: 4052 max. Initiating Device Circuit: Supervised, powerlimited Max. IDC Wiring Resistance: 2552 max External Power Supply Standby Current: 50mA Alarm Current: 70mA per module End -of -Line Resistance: 3.9k Q ENVIRONMENTAL Operating Temperature: 32°F — 120°F (0°C — 49°C) Humidity: 10%— 93% non -condensing For more information Learn more about Honeywell Silent Knight and other products by visiting www.sitentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 For a complete listing of all compliance approvals and COMPATIBILITY certifications, please visit ORDERING INFORMATION www.sitentknight.com. SK -ZONE -6: Six Zone Interface Module are registered Honeywell Silent Knight fire alarm control panels: Microsoft, Windows, and 6820: Addressable fire alarm control panel the Windows Logo are ACCESSORIES. registered trademarks IDP-ACB: SK Module Cabinet. Cabinet holds two or trademarks of SK -ZONE -6.15.25" H x 12.5" W x 3"D Microsoft Corporation. COMPATIBILITY Silent Knight°, System Sensor' and Honeywell' The SK-ZON E-6 is compatible with the following are registered Honeywell Silent Knight fire alarm control panels: trademarks of Honeywell 6820: Addressable fire alarm control panel International, Inc. 6820EVS: Addressable fire alarm control panel This document is not with an emergency voice system. intended to be used for 6808: Addressable fire alarm control panel installation purposes. We 6700: Addressable fire alarm control panel tryto keep our product information up -to 5700: Addressable fire alarm control panel date and accurate. We 5808: Addressable fire alarm control panel cannot cover all specific 5820XL: Addressable fire alarm control panel applications or anticipate all requirements. All 5820XL-EVS: Addressable fire alarm control panel specifications are subject with an emergency voice system to change without notice. For a list of detectors compatible with the SK- ZONE-6,see theSK-ZONE-6 Installation call 800-446-6444. ca It 80 -446 6444. Instruction (PN 156-3441-00). Doc 3501301 Rev E111/17 © 2017 Honeywell International Inc. Honeywell sELENT• Kl1iiGHT TAB 3 NOTIFICATION DEVICES FEATURES & BENEFITS • Sleek, low-profile design • Base included • Reliable analog communications for trouble-free operation • Age resistant polymer housing • Dual electronic thermistor design on the SK-Photo-T • Superior EMI resistance for reliability • Simple field cleaning for code compliance • Variety of mounting options to meet any application • Dual LED indicators for 360º visibility • Detector transmits signal to indicate maintenance is required • Optional remote LED annunciator (System Sensor® PN RA100Z) • Plug-in mounting provides ease of installation • Tamper-proof feature available on mounting bases • Listed for use in duct applications • Rotary address switches for fast installation • UL Listed • FM Approved SK-PHOTO, SK-PHOTO-T, and SK-PHOTOR Intelligent Photoelectric Smoke Detectors The SK-PHOTO is a photoelectric smoke detector, the SK PHOTO-T is a photoelectric smoke detector with thermal and SK-PHOTOR is a photoelectric detector with remote test capability. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with the Honeywell Silent Knight series fire alarm control panels (FACPs). SK-PHOTO and SK-PHOTO-T are plug-in type smoke sensors that combine a photoelectric sensing chamber with addressable analog communications. Point ID capability allows each detector’s address to be set with rotary address switches, providing exact detector locations for selective maintenance when chamber contamination reaches unacceptable levels. SK-PHOTO and SK-PHOTO-T have a unique optical sensing chamber that is engineered to sense smoke produced by a wide range of combustion sources. In the SK-PHOTO-T, dual electronic thermistors add 135ºF (57ºC) thermal technology to maximize detection. The SK-PHOTOR is a remote test capable detector for use with the DNR/ DNRW duct smoke detector (not included). COMPATIBILITY SK-Photo, and SK-Photo-T are compatible with the following detector bases: B210LP: 6” base (included) B501: 2 wire base B224RB: Relay base B224BI: Isolator base SK-PHOTO (BASE INCLUDED) For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-PHOTO, SK-PHOTO-T and SK-PHOTOR Technical Specifications PHYSICAL Height: 2.0” (5.0 cm) Diameter: 4.1” (10.4 cm) installed in B501 base ELECTRICAL Operating Voltage: 15–32VDC Standby Current: 300 μ A @ 24VDC Maximum Alarm Current: 6.5mA @ 24VDC max (with LED on) ENVIRONMENTAL Operating Temperature SK-Photo: 32º – 120ºF (0ºC – 49ºC) SK-Photo-T: 32º – 100ºF (0ºC – 38ºC) Humidity: 10% – 93% non-condensing OTHER RATINGS SK-Photo-T Thermal: Fixed temperature set point 135ºF (57ºC) Velocity: 0 – 4000 fpm (0 – 20 m/sec) INSTALLATION The SK-PHOTO and SK-PHOTO-T plug into a compatible Silent Knight series detector bases. The SK-PHOTOR is a remote test capable detector head included within the DNR (W) duct smoke detector. ORDERING INFORMATION SK-PHOTO: Photoelectric smoke detector SK-PHOTO-T: Photoelectric smoke detector with thermal (135°F fixed temperture) SK-PHOTOR: Photoelectric detector with remote test capability ACCESSORIES RA100Z: Remote LED annunciator XR2B: Detector removal tool. A removal and replacement tool for SK series plug-in detectors. Includes the T55-127-000 M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle XP-4: Extension Pole for XR2B. Extends from 5 – 15 ft. T55-127-000: Detector Removal Head BCK-200B: Black Detector Kit. For SK series detectors COMPATIBILITY The SK-PHOTO, SK-PHOTO-T and SK-PHOTOR are compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency mass notification system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency mass notification system. Doc 350118 | Rev G | 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 'NTE Standard, Relay, Isolator, Sounder, and Low Frequency Sounder Bases To meet local code and application requirements, Gamewell-FCI° offers standard 4" and 6" bases, as well ass pecialty base designs including relay, isolator, sounder and low frequency sounder bases that are UL listed for low frequency operation and complywith NFPA 72&F 2_� requirements for sleeping spaces for the new Gamewell-FCI Series of addressable detectors as well as previous generations. The standard 4" and 6" bases offer a plug-in detector base intended for use in intelligent systems, with screw terminals provided for power (+ and —), and remote annunciator 8300-6 Standard 6" B20OS-WH Sounder connections. Communication takes place over the power (+ and —) lines. The 4" base offers a Base (White) Base (White) compact design while the 6" base provides compatibility with a wider range of junction boxes. The specialty bases support application driven requirements. These bases employ a separate mounting plate that installs on various junction box sizes to eliminate unsightly surface - mount boxes. The mounting plate enables pre -wiring of all connections to speed and simplify installation. Relay bases (B224RB-WH/B224RB-IV) provide one form -C contact relayfor control of auxiliary functions, such as door closure and elevator recall. The relay can operate in two different modes (short and long delay). The activation time forthe short delay is 60-100 milliseconds, while the activation time for the long delay is 6-10 seconds. A shunt with pin headers, located on the base PC board, is used to setthe delaytiming. Isolator bases (B224B1-WH/B224B1-IV) allowthe Signaling Line Circuit (SLC) loop to operate under fault conditions created from a short circuit preventing an entire communication loop from being disabled. The base isolates the section of the loop containing the short circuit from the remainder of the circuit and automatically restores when the fault is corrected. Sounder and low frequency (-LF) sounder bases are designed for new and existing dwelling unit applications. They offer maximum flexibility in installation, configuration, and operation to meet or exceed UL 268 and UL 464 requirements. The low frequency sounder bases are designed to meet the NFPA 72 sleeping space requirementto produce a fundamental frequency of 520 Hz +/-10%with a square wave or its equivalent. Studies show that a lower frequency, centered around 520 Hz, is the most idealto wake sleeping occupants, even those with mild to severe hearing loss. FEATURES AND BENEFITS • Bases enable quick and secure detector • Standard white color with ivory and black plug-in • SEMS Screws provide easy wiring connection • UL 268 compliant • Support for 12-24 AWG provides installation flexibility • Multiple base formats meet application requirements options • Mechanical locking feature restricts removal of attached sensor head • Specialty Base Features: • Pre -wired mounting plate simplifies installation • Application driven feature sets B501 -WHITE Fla ngeless B501 -BL Flangeless 4" Base (White) 4" Base (Black) • Sounder bases both UL268 and UL464 compliant Honeywell �® l The B200S sounder and LF sounder bases (B200S-WH/B200S-IV/ B224RB-IV: Ivory, relay base B200S-LF-WH/B200S-LF-IV) adopt the same address as the B224BI-WH: White, isolator detector base detector, but use a unique device type on the loop. The Fire Alarm Control Panel (FACP) can use that address to command an individual sounder — or a group of sounders — to activate. The command set from the FACP can be tailored to multiple event - driven tone outputs allowing selection of volume (75 or 85 dBA), tone (ANSI Temporal 3, ANSI Temporal4, or March Time) and group. In addition, some FACPs will enable custom tone patterns. The B200S series sounder bases recognize the System Sensor synchronization protocol. This enables them to be used as a component of the general evacuation signal — along with other System Sensor AV appliances — when connected to a power supply or FACP output capable of generating the System Sensor synchronization pulses. The B200SR sounder and LF sounder bases (B200SR-WH/ B200SR-IV/B200SR-LF-WH/B200SR-LF-IV) are fully compatible with existing B501BH Series sounder base installations. The device enables users to select one of two B501 -supported tones (ANSI Temporal 3 or Continuous) through a jumper. PRODUCT LINE INFORMATION INTELLIGENT BASES "-IV" suffix indicates Ivory color model. "-BL" suffix indicates Black color model. "-WH" and "-WHITE" suffix indicates White color model. B21OLP: Flanged mounted base. B21OLPA: Same as B210LP; ULC listed. B21OLPBP: Bulk pack of B210LP, contains 10. B300-6: White, 6" base, standard flanged low -profile mounting base B224BI-IV: Ivory isolator detector base B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone; Uses Velociti° protocol B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone; Uses Velociti° protocol B20OS-LF-WH: White, Low Frequency Intelligent, programmable sounder base, produces a fundamental frequency of 520 Hz +/- 1011/6 with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement B20OS-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base, produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone; Intended for retrofit applications B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone; Intended for retrofit applications B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base, produces a fundamental frequency of 520 Hz+/ -10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement; intended for retrofit applications B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base, produces a fundamental frequency of 520 Hz+/ -10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applications. MOUNTING KITS AND ACCESSORIES 8300 -6 -BP: Bulk pack of B300-6, package contains 10 TR300: White, replacement flange for B210LP, B300-6 base B300 -6 -IV: Ivory,6" base, standard flanged low -profile mounting base. TR300-IV: Ivory, replacement flange for B210LP, B300 -6 -IV base 8501 -WHITE: White, 4" standard European flangeless mounting RA10OZ: Remote LED annunciator, 3 - 32 VDC, mounts to a U.S. base. UL/ULC listed single -gang electrical box; For use with B501 and B300-6 B501 -WHITE -BP: Bulk pack of B501 -WHITE, contains 10 8501 -BL: Black, 4" standard European flangeless mounting base B501 -IV: Ivory color, 4" standard European flangeless mounting base B224RB-WH: White, relay base JUNCTION BOX SELECTION GUIDE M02-04-00: Test magnet M02-09-00: Test magnet with telescoping handle CK300: White, detector color kit, pack of 10 CK300-IV: Ivory, detector color kit, pack of 10 CK300-BL: Black, detector color kit, pack of 10 Base Models Single Gang Double Gang 3.5" Oct. 4.0" Oct. 4.0" Square 4.0" Square with 3.0" mud ring 50 mm 60 mm 70 mm 75 mm B200S,B200SR Yes Yes Yes Yes Yes Yes No No No No B501 No No Yes No No Yes Yes Yes Yes No B300-6 Yes No Yes Yes Yes Yes No No No No B224B1, B224RB Yes Yes Yes Yes Yes Yes No No No No Box depth contingent on base and wire size. Refer to National Electric Code or applicable local codes for appropriate recommendations. Applies to all model variants "BL", "-LF", "-IV", "-WH", and "-WHITE". See Product Line Information for detailed model description. Page 2 of 3 — 9021-60540:K • 7/8/2019 INTELLIGENT BASES TECHNICAL SPECIFICATIONS ELECTRICAL For B300-6 Series bases: • Operating voltage: 15 to 32 VDC • Standby current: 170 pA maximum For B501 Series bases: • Operating voltage: 15 to 32 VDC • Standby current: 150 pA maximum For B200 Series bases: • External supply voltage: 16 to 33 VDC (FWR) • Standby current: 500 pA maximum • Alarm current for B200S(-IV)(-WH): 35 mA maximum at high-volume setting 15 mA maximum at low-volume setting • Alarm currentfor B200S-LF(-IV)(-WH) High- volume setting: 70 mA maximum @ 33.0 VDC 90 mA maximum @ 24.0 VDC 140 mA maximum @16.0 VDC • Alarm current for B20OS-LF(-IV)(-WH) Low- volume setting: 15 mA maximum C 33.0 VDC 20 mA maximum C 24.0 VDC 25 mA maximum C 16.0 VDC • Alarm current for B200SR(-IV)(-WH): 35 mA maximum • Alarm current for B200SR-LF(-IV)(-WH): 65 mA maximum C 33.0 VDC 90 mA maximum C 24.0 VDC 125 mA maximum @16.0 VDC SLC operating voltage: 15 to 32 VDC SLC standby current: See applicable sensor specification Sound output: Greaterthan 85 dBA minimum; measured in a UL reverberant room at 10 feet, 24 Volts (continuous tone) For 6224131, B224RB (-IV) (-WH) bases: • Operating voltage: 15 to 32 VDC (powered by SLC) • Standby ratings: <450 pA maximum @ 24VDC • Set time: (B224RB(-IV)(-WH) only): short delay 60-100 msec; long delay 6-10 seconds • Reset time: (B224RB/-IV/-WH only): 20 milliseconds maximum • Relay characteristics: (13224RB/-IV/-WH only): two -coil latching relay; one Form -C contact; ratings (UL/CSA): 0.9 A C 125 VAC, 0.9AC110VDC, and 3.0AC30VDC PHYSICAL Note: Specifications applies to all model variants "-BL", "-LF", "-IV", -WH, -WHITE. See Product Line Information for detailed model description. Diameter: • B501 -WH ITE: 4" (10.16 cm) • 6300-6, 13210LP: 6.1" (15.49 cm) • 13224131, B224RB: 6.2" (15.748 cm) • B200S, B200SR: 6.875' (17.46 cm) Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.gamewell-fci.com Wire gauge: • B224B1,B224RB:14to24AWG • B300-6,B210LP,B501,B200S,B200SR12to 24 AWG Temperature range: • B224B1, B224RB, B200S, B200SR: 32°Fto 120°F (0°C to 49°C) • B300-6, B21OLP, 8501:-4°Fto 150°F( -20°C to 66°C) Humidity range: 10% to 93% RH, non - condensing System temperature and humidity ranges: This system meets NFPA requirements for oper- ation at 0°C to 49°C (32°F to 1201F); and at a relative humidity (non -condensing) of 85% at 30°C (86°F) per N FPA, and 93%± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the use- ful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended thatthis system and all peripherals be installed in an environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F). AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to intelligent bases as noted. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S911 FM Approved CSFM: 7300-1653:0109,7300-1653:0126, 7300-1653:0213,7300-1653:0238 9021-60540 1 K 1 07/19 ©2019 Honeywell International Inc. FEATURES & BENEFITS • Installer can open station without causing an alarm condition • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets ADA requirement for 5 lbs maximum pull force to active • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) • Shell, door, and handle molded from durable LEXAN® • Reliable analog communications for trouble-free operation • Braille text on station handle • Rotary address switches for fast installation • Handle latches in down position and the word Activated appears, clearly indicating the station has been pulled • UL Listed, including UL 38, Standard of Manually Actuated Signaling System • CSFM Listed • MEA Listed SK-PULL-SA / SK-PULL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to activate the station. The SK-PULL-DA is a dual action pull station requiring two motions to active the station. The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel (FACP). Extremely easy to operate, the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal. The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. INSTALLATION The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square electrical box. You can also use the optional (System Sensor® PN BG-TR) trim ring if the station is being semi-flush mounted. SK-PULL-SA SK-PULL-DA For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-PULL-SA / SK-PULL-DA Technical Specifications PHYSICAL Dimensions: 5.5” H x 4" W x 1.45" D (14 x 10.2 x 3.7cm) Housing Material: LEXAN polycarbonate resin Bi-Colored LED: Blinking Green: Normal Steady Red: Alarm Switch: Single pole, single throw (SPST) normally open (N/O) switch which closes upon activation of the pull station ELECTRICAL Operating Voltage: 15 – 32VDC SLC Standby and Alarm Current: 350μ A Wire Gauge: Up to 12AWG (3.1 mm2) ENVIRONMENTAL Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing ORDERING INFORMATION SK-Pull-SA: Single Action Pull Station SK-Pull-DA: Dual Action Pull Station ACCESSORIES BG-TR: Optional trim ring. SB-I/O: Surface backbox, indoor/outdoor. * Unless otherwise noted, specifications apply to SK-Pull-SA and SK-Pull-DA COMPATIBILITY The SK-PULL-SA AND SK-PULL-DA are compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency voice system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency voice system Doc 350135 | Rev E | 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 FEATURES & BENEFITS • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green in normal state and is solid red in alarm • SEMS screws for easy wiring • UL Listed • Rotary address switches for fast installation SK-MONITOR Intelligent Monitor Module The SK-MONITOR is an addressable monitor module for use with Honeywell Silent Knight Series fire alarm control panels (FACPs). The SK-MONITOR is intended for use in intelligent, two-wire systems, where individual address of each module is selected using the built-in rotary switches. The SK-MONITOR supports Class A supervised or Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. INSTALLATION The SK-MONITOR mounts directly into a 4” square electrical box. The box must have a minimum depth of 2-1/8”. A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight.SK-MONITOR For a complete listing of all compliance approvals and certifications, please visit www.silentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight®, System Sensor® and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444. SK-MONITOR Technical Specifications PHYSICAL Height: 4.5”H x 4” W x 1.25”D (11.4 X 10.2 X 3cm) Shipping Weight: 6.3 oz (196 g) ELECTRICAL Operating Voltage: 15 – 32VDC Current Draw (LED on): 5.0mA max Operating Current (LED flashing): 375 μ A Standby Current: 400 μ A max @ 24 VDC (one communication every 5 sec with 47K EOL); 550 μ A max @ 24 VDC (one communication every 5 sec with EOL <1K) 5.5 mA (with LED latched on) LED Current: 5.5 mA (with LED latched on) End-of-Line Resistance: 47K W Initiating Device Circuit Wiring Resistance: 1,500 W max SLC Loop Resistance: 40 W max. ENVIRONMENTAL Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC) Humidity: 10% – 93% non-condensing ORDERING INFORMATION SK-MONITOR: Monitor Module ACCESSORIES. SMB500: 4” Square surface mount electrical box COMPATIBILITY The SK-MONITOR is compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency mass notification system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency mass notification system Doc 350131 | Rev G | 11/17 © 2017 Honeywell International Inc. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 S YSTEM SENSOR 500 Series Intelligent Modules The System Sensor intelligent module products are designed to meet a wide range of applications. Features • SEMS screws for easing wiring • Panel controlled status LED (except M501 M) • Analog communications • Rotary address switches (except M500X) • Low standby current • Mounts in standard 4 -junction box Agency Listings LISTED APPROVED Monitor and control modules can be used to supervise and activate sounders, strobes, door closers, pull stations, waterflow switches, conventional smoke detectors, and more. Each module is rigorously designed and tested for electromagnetic compatibility and environmental reliability, in many cases exceeding industry standards. Modules are addressed with easy-to-use rotary code switches. Full size modules mount in standard 4 in x 4 in x 2'/8 in junction box. Wiring terminals are easily accessible for troubleshooting. M500M Monitor Module, M501 M Mini Monitor Module, and M500DM Dual Input Monitor Module System Sensor monitor modules provide an interface to contact devices, such as security contacts, waterflow switches, or pull stations. M501 M and M50ODM are capable of Class B supervised wiring to the monitored device. M500M is capable of Class A supervision. Conventional 4 -wire smoke detectors can be monitored through their alarm and trouble contacts, wired as an initiating loop to the module. In addition to transmitting the supervised state of the monitored device (normal, open, or short), the full analog supervision measurement is sent back to the panel. This allows detection of impedance changes in the supervised loop to the monitored device. The M500DM module is capable of monitoring two separate Class B circuits simultaneously, making it ideal for waterflow tamper switch and flow switch monitoring. The compact size of the M501 M module allows it to fit inside devices or junction boxes behind devices. The M500X Isolator Module is an automatic switch that opens when the line voltage drops below four volts. Isolator modules should be spaced between groups of sensors or modules in a loop to protect the rest of the loop. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them. The remaining units on the loop continue to fully operate. The number of devices that can be installed between isolator modules varies depending on the device type. Please see your module's manual for more information. continued M502M Zone Interface Module The M502M Zone Interface Module allows intelligent panels to interface and monitor 2 -wire conventional smoke detectors. All 2 -wire detectors being monitored must be UL or ULC compatible with the module. The M502M module is addressed through the communication line of an intelligent system. It transmits the status of one zone of 2 -wire detectors to the fire alarm control panel. Status conditions are reported as normal, open, or alarm. The interface module supervises the zone of detectors and the connection of the external power supply. M500S Control Module The M500S Control Module provides supervised monitoring of wiring to load devices that require an external power supply to operate, such as horns, strobes, or bells. It is capable of Class A and Class B supervision. Upon command from the control panel, the M500S module will disconnect the supervision and connect the external power supply across the load device. The disconnection of the supervision provides a verification to the panel that the control relay actually turned on. The external power supply is always relay 500 Series Intelligent Module Specifications Operating Voltage 15 to 32 VDC Communication Line 40 fl max. Loop Impedance Temperature Range 32oF to 120°F (00 to 49°C) Relative Humidity 10% to 93% noncondensing Shipping Weight M501 M: 1.2 oz (37 g) Fault Detection Threshold Others: 6.3 oz (196 g) Dimensions M501 M: 2.7 in W x 1.7 in H x 0.5 in D 0OD Others: 4.275 in W x 4.675 in H x 1.4 in D Standby Current 300 pA max @ 24 VDC (one communication every 5 sec. with LED enabled) External Power Supply 18 to 28 VDC (100 mV ripple max.) End -of -Line Resistance 3.9 kQ (included) External Supply 11.5 mA @ 24 VDC (nominal) Standby Current External Supply 80 mA @ 24 VDC (nominal) Alarm Current Standby Current 300 pA max @ 24 VDC (one communication every 5 sec. with LED enabled) LED Current 5.5 mA (with LED latched on) Relay Contact Ratings 2.0 A @ 25 VAC (PF=.35), non -coded 3.0 A @ 30 VDC resistive, non -coded 2.0 A @ 30 VDC resistive, coded 0.46 A @ 30 VDC (UR=20ms), non -coded 0.7 A @ 70.7 VAC (PF=.35), non -coded 0.9 A @ 125 VDC resistive, non -coded 0.5 A @ 125 VAC (PF=.75), non -coded 0.3 A @ 125 VAC (PF=.35), non -coded isolated from the communication loop, so that a trouble condition on the power supply will never interfere with the rest of the system. Full analog measurement of the supervised wiring is transmitted back to the panel and can be used to detect impedance changes or other special test functions. M500R Relay Module The M50OR Relay Module contains two isolated sets of Form C contacts, which operate as a DPDT switch. The module allows the control panel to switch these contacts on command. No supervision is provided for the notification appliance circuit. M500FP Firefighter Phone Module The M500FP module is intended to monitor and control a loop of firefighter phones. It has the ability to differentiate between normal, off -hook, and trouble conditions. When taken off -hook, a phone will immediately receive a ringing tone, and the panel will receive an off - hook indication. The panel can then connect that off -hook phone to the main riser for the system. Standby Current 450 pA max. Isolation Impedance 2.25 kf) to 2.9 kQ Fault Detection Delay 250 ms min. Fault Detection Threshold 4 Volts Line Restoration Threshold 7 Volts 0OD Standby Current 750 pA max. @ 24 VDC (one communication every 5 sec. with 47k EOL) Alarm Current 970 pA max. (one communication every 5 sec.); 6 mA (with LED latched on) End -of -Line Resistance 47 kQ (two included) Standby Current 400 pA max @ 24 VDC (one communication every 5 sec. with 47k EOL); 600 IjA max @ 24 VDC (one communication every 5 sec. with EOL<1 k); 5.5 mA (with LED latched on) End -of -Line Resistance 47 kf) (included) Standby Current 2.4 mA max. (one communication every 5 sec. with LED enabled) Comm. Line Current 4.0 mA max. (no communication, LED off, 1200 0 phone) Acceptable Phone 1200 () (nominal) Resistance End -of -Line Resistance 3.9 kfl (included) SYSTEM ©t to c System Sensor. 3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensoccom SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 or current product information,inclu301the ates,.02/15tversion ofthis data sheet. MDDS74301 • 02/15 Protectowire Linear Heat Detector Introduction Protectowire Linear Heat Detector is a proprietary cable that detects heat anywhere along its length. The sensor cable is comprised of two steel conductors individually insulated with a heat sensitive polymer. The insulated conductors are twisted together to impose a spring pressure between them, then wrapped with a protective tape and finished with an outer jacket suitable for the environment in which the detector will be installed. Protectowire is a fixed temperature digital sensor and is therefore capable of initiating an alarm once its rated activation temperature is reached. At the rated temperature, the heat sensitive polymer insulation yields to the pressure upon it, permitting the inner conductors to move into contact with each other thereby initiating an alarm signal. This action takes place at the first heated point anywhere along the detector's length. It does not require a specific length to be heated in order to initiate an alarm, nor system calibration to compensate for changes in the installed ambient temperature. Protectowire Linear Heat Detector provides the advantages of line coverage with point sensitivity. DATA SHEET Features • Line coverage... continuous sensitivity. • Eight alarm temperature ratings. • The ability to withstand severe environmental conditions. • Approval for use hazardous locations when used with required equipment. • Ease of installation, testing, and splicing. • Compatibility with other initiation devices on same circuit. • Listed for spacing up to 50 ft. (15.2m). Applications Ideally suited to industrial high risk hazards as well as many types of commercial applications, Protectowire Linear Heat Detector has unique advantages over other types of detectors, especially when difficult installation factors or severe environmental conditions are present. When used with the appropriate Protectowire control equipment, the detector will activate a display, showing the location of an over heat or fire condition anywhere along its length. The detector also meets intrinsically safe standards and is Factory Mutual (FM) Approved for Class I, II, or III, Div. 1, Applicable Groups A, B, C, D, E, F & G hazardous areas, when used with suitably approved Protectowire control equipment. • Cable trays • Conveyors • Power distribution apparatus: switchgear, transformers, motor control centers • Dust collectors/ baghouses • Cooling towers • Warehouses/rack storage • Mines • Pipelines • Bridges, piers, marine vessels • Refrigerated storage • Tank farms • Aircraft hangars The Protectowire Company, Inc., 60 Washington Street, Pembroke, MA 02359 1 781-826-3878 I protectowire.com SIGNALING © Copyright 2022, The Protectowire Company, Inc. All rights reserved. i'M cL us Page 1 APPROVED LISTED PRQTECTE T Outer Jacket Polyester zinc Tape Coating PHSC y`` tpring Steel Heat Sensitive Conductor Polymer PRQTECTQWIRE PLR Protectowire Features & Benefits Polyester Copper Tape Coating W tPring Steel Heat Sensitive Conductor Polymer Approximately 5/32" (4mm) diameter • Alarm location identified and displayed, at the control panel, anywhere along its length when used with the exclusive Protectowire Alarm Point Location Meter. • Sensitivity unaffected by changes in ambient temperature or length of cable used on the detection circuit. Compensating adjustments are not required. • Installation and splicing is simple with common tools. Junctions can be made without effecting the integrity of the system. • Compatibility with other types of alarm initiating devices on the same circuit such as manual pull stations, thermal heat detectors and smoke detectors. • Installation possible in hazardous areas when used with suitably approved Protectowire control equipment. • Full range of temperatures and models available to accommodate the most demanding applications. • Different temperature detectors may be utilized in the same initiating circuit. • Detectors available on integrated stainless steel messenger wire for installations where mounting is difficult such as large open areas. DATA SHEET Description The detector is made in multiple temperature ratings to allow for differences in normal ambient temperature. Guidelines for selecting the proper detector temperature rating are the same as for automatic sprinklers and other heat actuated devices. Refer to the Temperature Rating Chart for proper model selection based upon installation temperature limits. Detector Types The detector's product range consists of two distinct types of cable. PHSC (Protectowire Heat Sensitive Cable) models are manufactured with steel conductors (top image on left). PLR (Protectowire Low Resistance) models are manufactured with special low-resistance conductors (bottom image on left). Please refer to the chart on page three for model number designation. All specifications are subject to change without notice. Jacketing Materials EPC (Extruded Polyvinyl Chloride) - is a durable flame retardant vinyl outer jacket designed for interior commercial and industrial applications. Features of this jacket include low moisture absorption, resistance to many common chemicals, and excellent flexibility at low temperatures. XCR (Extreme Corrosion Resistance) - is a high-performance fluoropolymer jacket designed for both interior and exterior environments. Features of this jacket include excellent chemical resistance, abrasion resistance, weather resistance, and high- temperature performance. XCR is the only heat detector that is FM -approved for corrosive environments. LSZH (Low Smoke Zero Halogen) - is a durable outer jacket designed for interior commercial and industrial applications requiring low smoke zero halogen performance. Features of this jacket include low moisture absorption, resistance to many common chemicals, and excellent flexibility at low temperatures. XLT (Extreme Low Temperature) - is an outer jacket specifically selected for cold storage and freezers. Features of this jacket include low moisture absorption and excellent performance in extremely low temperatures. This detector has been UL and FM tested to -60°F (-51°C) EPR (Extruded Polypropylene Rubber) - is an outer jacket designed for both interior and exterior environments. Features of this jacket include good abrasion resistance, chemical resistance, and weather resistance over a wide temperature range. • Test equipment is portable and available for easy Specifications field service. Maximum Voltage Rating: 30 VAC, 42 VDC • Detectors are ideal for activation of extinguishing equipment, Resistance PHSC Models: 0.185 ohms/ft. (0.607 ohms/m) such as deluge or pre -action sprinkler systems. Resistance PLR Models: 0.058 ohms/ft. (0.191 ohms/m) Min. Bend Radius: 2.5 inches (6.4cm) Nominal Diameter: 5/32 inch (4mm) Nominal Weight: 8lbs./500 ft. (3.6 kg/152m) The Protectowire Company, Inc., 60 Washington Street, Pembroke, MA 02359 1 781-826-3878 1 protectowire.com © Copyright 2022, The Protectowire Company, Inc. All rights reserved. Page 2 Accessories DATA SHEET The Protectowire Company offers an assortment of fasteners and splicing devices to facilitate installation for both standard and special applications. Full details are available upon request. Model Numbers, Temperature Ratings, and Approved Spacing Product Type Model Number Alarm Temperature Max. Ambient UL/cUL Approval/ FM Approval/ Temperature Max. Listed Spacing Max. Listed Spacing PHSC-EPC PHSC-155-EPC 155°F (68°C) 115-F (46°C)' 50 ft. / 15.2m 30 ft. / 9.1 m Multi -Purpose/ Commercial & Industrial PHSC-172-EPC 172-F (78°C) 130°F (54°C) 50 ft. / 15.2m 30 ft. / 9.1 m Applications PHSC-190-EPC 190°F (88°C) 150°F (66°C) 50 ft. / 15.2m 30 ft. / 9.1 m PHSC-220-EPC 220-F (105°C) 175-F (79°C)' 50 ft. / 15.2m 25 ft. / 7.6m PHSC-280-EPC 280'F (138°C) 200°F (93°C) 50 ft. / 15.2m 25 ft. / 7.6m PHSC-356-EPC 356'F (180°C) 221 °F (105°C) 50 ft. / 15.2m See Note 1 PHSC-XCR PHSC-155-XCR 155-F (68°C) 115-F (46°C)' 50 ft. / 15.2m 30 ft. / 9.1 m High Performance/ Industrial Applications PHSC-172-XCR 172°F (78°C) 130°F (54°C) 50 ft. / 15.2m 30 ft. / 9.1 m Excellent Abrasion & PHSC-190-XCR 190-F (88°C) 150°F (66°C) 50 ft. / 15.2m 30 ft. / 9.1 m Chemical Resistance PHSC-220-XCR 220'F (105°C) 175-F (79°C)' 50 ft. / 15.2m 25 ft. / 7.6m PHSC-280-XCR 280'F (138°C) 200°F (93°C) 50 ft. / 15.2m 25 ft. / 7.6m PHSC-356-XCR 356-F (180°C) 250°F (121 °C) 50 ft. / 15.2m See Note 1 PHSC- LSZH PHSC-135-LSZH 135°F (57°C) 100°F (38°C) 50 ft. / 15.2m 30 ft. / 9.1 m Multi-Purpose/Low Smoke Zero Halogen PHSC-155-LSZH 155°F (68°C) 115-F (46°C)' 50 ft. / 15.2m 30 ft. / 9.1 m PHSC-172-LSZH 172-F (78°C) 130°F (54°C) 50 ft. / 15.2m 30 ft. / 9.1 m PHSC-190-LSZH 190°F (88°C) 150°F (66°C) 50 ft. / 15.2m 30 ft. / 9.1 m PHSC-220-LSZH 220-F (105°C) 175°F (79°C)' 50 ft. / 15.2m 25 ft. / 7.6m PHSC-280-LSZH 280'F (138°C) 200°F (93°C) 50 ft. / 15.2m 25 ft. / 7.6m PHSC-356-LSZH 356-F (180°C) 250°F (121 °C) 50 ft. / 15.2m See Note 1 PHSC- XLT PHSC-135-XLT 135°F (57°C) 100-F (38°C) 50 ft. / 15.2m 30 ft. / 9.1 m Multi-Purpose/Excellent Low Temp. Properties PLR -EPR PLR -155 -EPR 155°F (68°C) 115-F (46°C)' 50 ft. / 15.2m 30 ft. / 9.1 m Good Weathering Properties & Flexibility PLR -172 -EPR 172°F (78°C) 130°F (54°C) 50 ft. / 15.2m 30 ft. / 9.1 m Over a Wide Temperature PLR -190 -EPR 190°F (88°C) 150°F (66°C) 50 ft. / 15.2m 30 ft. / 9.1 m Range PLR-XCR PLR-500-XCR 500'F (260°C) 392°F (200°C) 50 ft. / 15.2m See Note 1 High Performance/ Industrial Applications Excellent Abrasion & Chemical Resistance 'For open area applications the recommended UL 521 maximum ambient temperature for all 155 models is 100°F (38°C), and 220 models is 150°F (66°C). Temperatures shown in table are acceptable for UL Special Application use. "PHSC-135°F XLT has been UL Listed and FM Approved for -60°F (-51°C). Note 1: FM Approved for special application use only.All Protectowire models can be supplied on Messenger Wire. Add suffix "-M" to above model numbers. The Protectowire Company, Inc., 60 Washington Street, Pembroke, MA 02359 1 781-826-3878 1 protectowire.com © Copyright 2022, The Protectowire Company, Inc. All rights reserved. Page 31 DS6592AB-1222 TAB 4 ADDRESSABLE INITIATING DEVICES Agency Listings Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) AVDS01201 SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. AVDS01201 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2012 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS01201 • 3/12 SpectrAlert Advance Diagrams Model Description Wall Horn Strobes P2RK*†2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P2RHK*†2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) P2WK*†2-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2WHK*†2-Wire Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) P4RK†4-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) P4WK 4-Wire Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) P2RHK-120 2-Wire Horn Strobe, High cd, Red, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK*†Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box) SRHK*†Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box) SWK*†Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box) SWHK*†Strobe, High cd, White, Outdoor (includes plastic weatherproof back box) Horns HRK†Horn, Red, Outdoor (includes plastic weatherproof back box) Accessories SA-WBB Red, Metal Weatherproof Back Box SA-WBBW White, Metal Weatherproof Back Box SpectrAlert Advance Ordering Information Notes: * Add “-P” to model number for plain housing (no “FIRE” marking on cover), e.g., P2RK-P. † Add “-R” to model number for weatherproof replacement device (no back box included), only for use with weatherproof outdoor flush mounting plate, WTP and WTPW. “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝ Dia. 2.5˝ 2.5˝ Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Listed for ceiling mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L-Series can meet virtually any application requirement. The entire L-Series product line of ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L-Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383 AVDS868-02 • 12/01/2017 • Page 3 AVDS868-02 • 12/01/2017 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11 ⁄16 × 4 11 ⁄16 × 2 1 ⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3)8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens)6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions (SBBCRL, SBBCWL) 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS868-02 • 12/01/2017 • Page 3 Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 UL Current Draw Data Horn Strobe Tones and Sound Output Data UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 UL Max. Current Draw (mA RMS), Ceiling Horn Strobe, Candela Range (15–177 cd) DC Input 8–17.5 Volts 16–33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 FWR Input 16–33 Volts 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2017 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS868-02 • 12/01/2017 L-Series Dimensions Model Description Ceiling Horn Strobes PC2RL 2-Wire, Horn Strobe, Red PC2WL 2-Wire, Horn Strobe, White PC4RL 4-Wire, Horn Strobe, Red PC4WL 4-Wire, Horn Strobe, White L-Series Ordering Information Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box Model Description Ceiling Strobes SCRL Strobe, Red SCWL Strobe, White SCWL-CLR-ALERT Strobe, White, ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White 6.83" diam. (173 mm) 2.47" (62.7 mm) 1.37" (34.8 mm)6.92" diam. (175.77 mm) 2.5" (64 mm) 2-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box 4-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box A0531-01 A0545-00 A0546-00 A0494-01 For a ceiling-listed horn-only device, see AVDS865 “Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications”. Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383, 3057072 AVDS865-05 • 2/22/2018 • Page 1 Features • Updated Modern Aesthetics • Small profile devices for Horns and Horn Strobes • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Mounting plate for all standard and all compact wall units • Mounting plate shorting spring checks wiring continuity before device installation • Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Strobes and Horn Strobes listed for wall mounting only • Horns listed for wall or ceiling use The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. AVDS865-05 • 2/22/2018 • Page 2 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17⁄8 -inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D) Compact Wall-Mount Dimensions (including lens)5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D) Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D) 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. AVDS865-05 • 2/22/2018 • Page 3 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9*Coded High 85 90 90 10*3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on 2-wire horn strobes. Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains constantly on. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd) DC Input 8–17.5 Volts 16–33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.1K Temporal High 93 156 53 73 119 140 164 190 242 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 FWR Input 16–33 Volts 15cd 30cd 75cd 95cd 110cd 135cd 185cd Temporal High 83 107 156 177 198 234 287 Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Current Draw Data Horn Tones and Sound Output Data 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2018 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS865-05 • 2/22/2018 L-Series Dimensions Model Description Wall Horn Strobes P2RL 2-Wire, Horn Strobe, Red P2WL 2-Wire, Horn Strobe, White P2GRL 2-Wire, Compact Horn Strobe, Red P2GWL 2-Wire, Comp 2 fils act Horn Strobe, White P2RL-P 2-Wire, Horn Strobe, Red, Plain P2WL-P 2-Wire, Horn Strobe, White, Plain P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP 2-Wire, Horn Strobe, White, FUEGO P4RL 4-Wire, Horn Strobe, Red P4WL 4-Wire, Horn Strobe, White Wall Strobes SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT L-Series Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -SP models have “FUEGO” marking on cover. All -ALERT models have “ALERT” marking on cover. *Horn-only models are listed for wall or ceiling use. Model Description Horns* HRL*Horn, Red HWL*Horn, White HGRL*Compact Horn, Red HGWL*Compact Horn, White Accessories TR-2 Universal Wall Trim Ring Red TR-2W Universal Wall Trim Ring White SBBRL Wall Surface Mount Back Box, Red SBBWL Wall Surface Mount Back Box, White SBBGRL Compact Wall Surface Mount Back Box, Red SBBGWL Compact Wall Surface Mount Back Box, White 4.70" (11.94 cm)1.91" (4.85 cm) 1.25" (3.18 mm) 5.67" (14.4 cm) A0549-00A0550-00 Compact Strobe, Horn Strobe Compact Horn Strobe, Horn Strobe Horn A0548-00 A0547-00 4.7" 119 mm 5.67" 144 mm 1.25" 32 mm 3.46" 88 mm 1.91" 48.5 mm 1.25" 32 mm 5.27" 133.9 mm 3.46" 88 mm 1.25" 32 mm 5.27" 133.9 mm Wall Surface Mount Back Box SBBRL/SBBWL A0554-01 4.82" (12.24 cm)1.85" (4.69 cm) 5.78" (14.68 cm) A0557-00 1.55" (3.9 cm) 3.57" (9.1 cm) 5.38" (13.7 cm) Compact Wall Surface Mount Back Box SBBGRL, SBBGWL TAB 5 SYSTEM BATTERIES General Purpose DURA12-8F R T 1 2 8 0 S p e c i f i c a t i o n Ce l ls Pe r U n i t Vol t a g e P e r Un i t No r m al Op er at ing Te m p er at ur e R an g e C a pa c ity We ig ht Max . D isc h ar g e Cu r re n t In t e rn a l R e si s t an c e O pe r a t i ng Te m per a t ur e R a n g e 6 1 2 o8.0 A h @ 2 0h r -r a te to 1 .7 5 V p e r cel l @2 5 C A p p r o x . 2 .2 6 K g (±4%)Tol e r a nc e 8 0 A (5 s e c ) A p p r o x . 2 5 mΩ D i scha r g e : -2 0 ~60 o oCharge: 0 C ~5 0 C o oStorage: -20 C ~60 C o oCC o o25C±5 C Flo a t cha rg i n g Vo l t age Re co mm e n d e d Ma x i mu m C h ar g i ng Cu r r e nt L i m i t E q u a l i z at ion a n d C yc l e S e r v i ce Se lf D isc h ar g e Ter mi n al Co n st a i n e r M at e ria l Fa s t on Ta b 1 8 7 (F 1 )/Fa s t on t ab 25 0(F2 ) D i m e n s i o n s (1 2 V 8 .0 A h ) o13.7 t o 13 .9 VDC/uni t Av e r a g e a t 2 5 C 2.4 A o14.6 t o 14 .8 VDC/uni t Av e r a g e a t 2 5 C U n i t : m m F 1 oConstant C u r r e n t D i s c h a r g e C h a r a c t e r i s t i c s : A (2 5 C ) oConstant P o w e r D i s c h a r g e C h a r a c t e r i s t i c s : W (2 5 C ) F.V /Ti m e 5 M I N 1 0 M I N 1 5 M I N 3 0 M I N 2 H R 3 H R 4 H R 5 H R 8 H R 1 0 H R 2 0 H R1HR F.V/Time 10MIN 15MIN 30MIN 2HR 3HR 4HR 5HR 8HR 10HR 20HR1HR 5 M I N Di m e n s i o n : 1 5 1 (L )6 5 (W )1 00 (H)× × RITAR Valve R egu l at ed Le ad A c i d (V RL A ) b a tt er i es c an be st or ed ofor m ore th an 6 mo nth s a t 25 C . S elf -d i s c harg e ra tio less th an 3% oper m on th at 2 5 C. Ple ase cha r ge ba tte r i es b ef or e using . R T s e r i e s i s a g e n er a l p ur p o se b a t te r y w i t h 5 ye a rs d e s i g n l i f e i n fl o a t s e r v i c e . I t m e e ts w i th I E C a n d J I S s t an d a rd s .W i t h u p -d at e d A G M v a l v e r e g u la t e d te c h n o l o g y a nd h i g h p ur i t y r a w m a t e r i al s , t h e R T s e r i e s b at t e r y h a s re l i a b l e s ta n d b y se r v i c e l if e . I t is s u i t a bl e f o r U P S /E P S , m e d i c al e q u i p m e n t , e m e r g e n c y l ig h t a n d s e c u r i t y s y s te m s a p p l i c a t i on s . A .B .S . U L 9 4-H B , U L 9 4 -V0 O p t i o na l. A l l m en t io ne d va lu es a re a v e ra g e v al ue s .(±2%)To le r an c e 9 .6 0 V 3 1 .5 5 2 0 .6 9 1 5 .4 1 8 .2 0 2 5 .1 9 9 3 .1 7 9 2 .0 9 5 1 .7 0 6 1 .4 0 2 0 .9 2 4 0 .8 0 0 0 .4 2 8 1 0 .0 V 3 0 .4 1 2 0 .1 7 1 4 .9 1 8 .0 9 7 5 .1 3 0 3 .1 1 5 2 .0 5 6 1 .6 8 2 1 .3 9 0 0 .9 2 0 0 .7 9 2 0 .4 2 4 1 0 .2 V 2 8 .6 3 1 9 .1 7 1 4 .5 0 7 .9 7 3 5 .0 8 1 3 .0 8 2 2 .0 3 8 1 .6 6 5 1 .3 8 1 0 .9 1 2 0 .7 7 9 0 .4 1 3 1 0 .5 V 2 5 .7 3 1 7 .9 3 1 3 .6 8 7 .7 5 3 5 .0 1 9 3 .0 4 2 2 .0 2 0 1 .6 4 1 1 .3 6 9 0 .9 0 4 0 .7 7 6 0 .4 0 4 1 0 .8 V 2 3 .0 6 1 6 .7 2 1 2 .9 0 7 .4 9 7 4 .9 4 9 3 .0 1 7 1 .9 9 6 1 .5 8 5 1 .3 6 2 0 .9 0 0 0 .7 6 3 0 .3 8 8 1 1 .1 V 2 0 .1 7 1 5 .3 3 1 1 .9 0 7 .2 1 2 4 .8 3 2 2 .8 9 6 1 .9 5 7 1 .5 6 2 1 .3 5 7 0 .8 9 3 0 .7 5 1 0 .3 8 1 9 .6 0 V 3 4 2 .2 2 2 6 .8 1 7 0 .0 9 3 .9 6 2 .1 6 3 7 .4 7 2 5 .0 5 2 0 .4 3 1 6 .8 0 1 1 .0 6 9 .5 8 0 5 .1 3 6 1 0 .0 V 3 3 3 .3 2 2 2 .1 1 6 7 .6 9 2 .9 6 1 .2 4 3 6 .9 7 2 4 .6 4 2 0 .1 4 1 6 .6 5 1 1 .0 2 9 .4 9 0 5 .0 9 5 1 0 .2 V 3 1 7 .0 2 1 3 .3 1 6 5 .4 9 2 .1 6 0 .7 9 3 6 .6 5 2 4 .4 3 1 9 .9 5 1 6 .5 5 1 0 .9 4 9 .3 6 8 4 .9 6 4 1 0 .5 V 2 8 9 .4 2 0 4 .5 1 5 6 .8 9 0 .2 5 9 .9 7 3 6 .2 5 2 4 .2 5 1 9 .6 8 1 6 .4 2 1 0 .8 4 9 .3 0 2 4 .8 8 0 1 0 .8 V 2 6 1 .1 1 9 1 .3 1 4 8 .1 8 8 .1 5 9 .1 9 3 6 .0 0 2 3 .9 7 1 9 .0 2 1 6 .3 4 1 0 .8 0 9 .1 6 1 4 .6 8 4 1 1 .1 V 2 3 0 .2 1 7 8 .1 1 3 9 .5 8 5 .6 7 5 7 .8 9 3 4 .7 4 2 3 .5 0 1 8 .7 4 1 6 .2 8 1 0 .7 2 9 .0 2 5 4 .6 1 0 Duracell® Ultra Valve Regulated Lead Acid (VRLA) batteries can be stored for more than 6 months at 25°C. Self-discharge ratio less than 3% per month at 25°C. Please charge batteries before using. General Purpose © 2014 DURACELL, a division of the Gillette Company, Bethel, CT 06801. DURACELL is a registered trademark of the Gillette Company, used under license. All rights reserved. The information contained on this specification is generally descriptive only and is not intended to make or imply any representation guarantee or warranty with respect to any cells and batteries. Cell and battery design/ specification are subject to modification without notice. www.batteriesplus.com 1 2 V 8 .0 A h S tora g e cha r ac t e ri st ic C ha r ge c ha r a cter is t ic C ur v e f o r sta n db y u s e D i s c h a r g e c h a r a cte r i s t i c C ur v e Discharge Time 0.6 min 1.2 3 6 12 30 512 Hr 10 20 24 1C 13 12 11 10 9 6.5 6.0 5.5 5.0 4.5 4.3 4.0 3.7 3.3 3.0TerminalVoltage(V)3C 0.16C 0.62C 0.35C 0.093C 0.05C 15 14 13 12 11 10 9 7.5 7.0 6.5 6.0 5.5 5.0 4.5 5.0 4.7 4.3 4.0 3.7 3.3 3.0 0.24 0.20 0.16 0.12 0.08 0.04 0 120 100 80 60 40 20 0 0 42 86 28 Charge Time(h) 1210 1614 2018 24ChargeVoltage(V)Chcrge Voltage ①Discharge 100%(0.05CA×20h) 50%(0.05CA×10h) ② Charge Chcrge Voltage2.275V/C Charge Current0.1CA ③ Temperature 25℃ Charge Current Chcrge Volume ChargeCurrent(CA)ChargeVolume(%)Supplementary charge required (Carry out supplementary charge before use if 100% capacity is requires) Supplementary charge required before use. This supplementary charge will help to recover the capacity and should be made as early as possible. Supplementary charge may often fail to recover the capacity. The battery should never be left standing till this state is reached R T 1 2 8 0 Supplementary charge and storage guidelines S H EN ZHE N R ITA R PO W E R C O.,LT D . U RL :ww w.ritar power.co m 10 LifeExpectancy(years)0 10 Battery Temperature (℃) 402030 50 8 6 4 2 30℃ Storage Time (months) 20 0Capacity(%)40 60 100 80 40℃ 10℃ 0℃ 2 4 6 8 10 12 14 16 18 20 22 24 20℃ Floa t S e rvice : ※  E very month, rec om m end ins pec tion every batt ery voltage. ※  E very three m onths , rec om m end equaliz at ion c harge for one tim e. E qualiz ation c harge m ethod: Dis c harge: 100% rate c apac ity dis c harge. Charge: M ax . c urrent 0.3CA, c ons t ant voltage 2.4-2.45V/Cell c harge 24h. ※  E ffec t of tem perature on float c harge volt age: -3m V/℃/Cell. ※  Length of s ervic e life will be direc tly affec t ed by t he num ber of dis c harge . c y c les , dept h of dis c harge, am bient t em perature and c harging voltage. M a i n t e n a n c e & C a u t i o n s A d dr es s: R m4 0 5 ,To w e r C , Huaha n Bui l d i n g ,Lang shan R d 1 6 , Nanshan Dis t r i ct , Sh e n Zh e n , 51 8 0 5 7, Ch ina Tel:+86-755 -3398 1668 Fax:86-755 -8347 -51 80 2012 - Version 1 -20℃-10℃0℃5℃10℃20℃25℃30℃40℃45℃ 6V&12V 50%70%83%85%90%98%100%102%104%105% 2V 60%75%85%88%92%99%100%103%105%106% 6V&12V 46%66%76%83%90%98%100%103%107%109% 2V 55%70%80%85%92%99%100%104%108%110% A G M B a t t e r y Capacity Factors With Different Temperature Batte ry Type G E L B a t t e r y 0.2 C<(A)<1 .0C Final Di s charge Vol tage V/cel l D i sc h ar ge Cu r re n t (A)(A)≤0 .2C 1 .60V (A)≥1 .0C 1.75 V 1 .70V D i s c h a r g e C u r r e n t V S . D i s c h a r g e Vo l t a g e -0.2 Cx2h+0 .1Cx 1 2 h C o ns tant Vo lt a ge Fa st C h a r g e t h e b a t t e r i e s a t l e a s t o n c e e v e r y s i x m o n t h s , o i f t h e y a r e s t o r e d a t 2 5 C . C h a r g i n g M e t h o d : Consta n t Current -0 .2C x2 h +2.4 -2 .45V/ce llx 2 4 h,Max. Cu rren t 0.3 C -0.2 C x2h +0.3 Cx 4h Bol t Te r m inal To rque M 5 M6 M8 F3 F4 F13 F18 T25 T26 F8 F11 F12-1 F15 F5 F9 F10 F12 F14 F16 6~7N-m 8~1 0N-m 1 0~12N-m DURA12-8F BATTERY TYPE -20°C -10°C 0°C 5°C 10°C 20°C 25°C 30°C 40°C 45°C AGM Battery 12V 46%66%76%83%90%98%100%103%107%109% TAB 6 BATTERY CALCULATIONS Device Type Qty Total Qty Total 6808 Control Panel 1 x 0.190000 = 0.190000 1 x 0.250000 = 0.250000 SK-PHOTO (-T) x 0.000300 = x 0.000300 = SK-PHOTO-W (-T) 1 x 0.000200 = 0.000200 1 x 0.000450 = 0.000450 SK-HEAT(-HT) (-ROR) x 0.000300 = x 0.000300 = SK-HEAT-W(HT) (ROR) x 0.000200 = x 0.000450 = SK-BEAM x 0.002000 = x 0.002000 = SK-BEAM-T x 0.002000 = x 0.002000 = SK-DUCT x 0.000300 = x 0.000300 = SK-ACCLIMATE x 0.000300 = x 0.000300 = SK-CONTROL x 0.000375 = x 0.000375 = SK-MONITOR 6 x 0.000375 = 0.002250 6 x 0.000375 = 0.002250 SK-MINIMON x 0.000375 = x 0.000375 = SK-PULL-SA x 0.000375 = x 0.000375 = SK-PULL-DA 8 x 0.000375 = 0.003000 8 x 0.000375 = 0.003000 SK-MONITOR-2 x 0.000750 = x 0.000750 = SK-MON-10 x 0.003500 = x 0.003500 = SK-RELAY-6 x 0.001450 = x 0.001450 = SK-CONTROL-6 x 0.002250 = x 0.002250 = SK-RELAY x 0.000255 = x 0.000255 = SK-RELAYMON-2 x 0.001300 = x 0.024000 = SK-ZONE x 0.000270 = x 0.000270 = SK-ZONE-6 1 x 0.002000 = 0.002000 1 x 0.002000 = 0.002000 SK-FIRE-CO x 0.000300 = x 0.007200 = B200S x 0.000300 = x 0.000300 = B200S-LF x 0.000300 = x 0.000300 = B200SR x 0.000300 = x 0.000300 = B200SR-LF x 0.000300 = x 0.000300 = B224RB x 0.000500 = x 0.000500 = RTS151 x 0.000000 = x 0.007500 = RTS151KEY x 0.000000 = x 0.007500 = RA100Z x 0.000000 = x 0.010000 = SK-ISO x 0.000450 = x 0.000450 = ISO-6 1 x 0.002700 = 0.002700 1 x 0.102000 = 0.102000 B224BI x 0.000500 = x 0.000500 = SK-CONTROL (Aux. Power) x 0.001700 = x 0.007000 = SK-CONTROL-6 (Aux. Power) x 0.008000 = x 0.020000 = SK-ZONE (Aux. Power) x 0.012000 = x 0.090000 = SK-ZONE-6 (Aux. Power) x 0.050000 = x 0.270000 = B200S (Aux. Power) x 0.000500 = x 0.035000 = B200S-LF (Aux. Power) x 0.000550 = x 0.140000 = B200SR (Aux. Power) x 0.000500 = x 0.035000 = B200SR-LF (Aux. Power) x 0.001000 = x 0.125000 = IntelliKnight 6808 Battery Calculation Secondary Power Source Requirements Standby Current (amps) Secondary Alarm Current (amps) Current Draw Current Draw 1. Control Panel 2. Addressable SLC Devices 3. SLC Accessory Bases 4. SLC Isolator Devices 5. Auxiliary Power Draw - SLC Devices Page 1 1/23/2023Honeywell Internal 5860 x 0.020000 = x 0.025000 = 5824 x 0.045000 = x 0.045000 = 5496 x 0.010000 = x 0.010000 = 5895XL x 0.010000 = x 0.010000 = 6855 x 0.020000 = x 0.025000 = 6860 x 0.025000 = x 0.050000 = 5865-4 x 0.035000 = x 0.145000 = 5865-3 x 0.035000 = x 0.145000 = 5880 x 0.035000 = x 0.200000 = 5883 x 0.000000 = x 0.220000 = SK-IP-2 x 0.093000 = x 0.136000 = SK-IP-2UD x 0.098000 = x 0.155000 = CELL-MOD x 0.055000 = x 0.100000 = CELL-CAB-SK x 0.055000 = x 0.100000 = WSK-WGI Aux. Power x 0.040000 = x 0.040000 = SLC Power x 0.024000 = x 0.024000 = SK-NIC x 0.021000 = x 0.021000 = SK-NIC-KIT x 0.021000 = x 0.021000 = SK-FSL x 0.079000 = x 0.079000 = SK-FML x 0.053000 = x 0.053000 = SK-FFT x 0.120000 = x 0.230000 = Miscellaneous Device 3 x 0.000000 = x 0.000000 = Miscellaneous Device 4 x 0.000000 = x 0.000000 = Miscellaneous Device 5 x 0.000000 = x 0.000000 = NAC 1 1 0.002000 = 0.002000 0.002000 = 0.002000 NAC 2 0.000000 = 0.000000 = NAC 3 0.000000 = 0.000000 = NAC 4 0.000000 = 0.000000 = 0.202150 0.361700 8. Notification Appliance Circuits Total Standby Load Total Alarm Load 6. Accessory Modules Page 2 1/23/2023Honeywell Internal Note 2: Use the dropdowns in the yellow cells to enter values. x =4.852 AH x =0.030 AH 4.882 AH =x 1.20 5.86 AH IntelliKnight 6808 Battery Calculation Note 1: You are fully responsible for verifying these calculations. Required Alarm Time in Minutes 5 Minutes Alarm Load Current (Amps) 0.36170 Amps 0.084 Calculation in Total Sheet Required Standby Time in Hours 24 Hours Standby Load Current 0.20215 Amps 24 Battery Check The batteries can be charged by the 6808 Charger. The batteries can be housed in the 6808 Cabinet. Current Draw Check Total Current Load Multiply by the Derating Factor 1.2 Total Ampere Hours Required Recommended Batteries: BAT-1270 - 7AH Batteries Circuit#1 current is within the limitations of the circuit. Circuit#2 current is within the limitations of the circuit. Circuit#3 current is within the limitations of the circuit. Circuit#4 current is within the limitations of the circuit. 6808 Control Panel: The output current is within the panel's limitations. Page 3 1/23/2023Honeywell Internal Device Qty Total Qty Total HPF-PS6B 1 x 0.002000 = 0.002000 1 x 0.002000 = 0.002000 x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = 0.002000 0.002000 Device Qty Total Qty Total x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = 0.000000 0.000000 Device Qty Total Qty Total x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = 0.000000 0.000000 Device Qty Total Qty Total x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = x 0.000000 = 0.000000 0.000000 IntelliKnight 6808 Circuit Detail NAC 1 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load NAC 4 Non-Alarm Draw Alarm Draw NAC 2 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load NAC 3 Total Standby Load Total Alarm Load Page 4 1/23/2023Honeywell Internal Starting Voltage Minimum Voltage @ EOL Voltage Drop Warning % Wire Type Actual Resistance Percent Drop Circuit Name AWG Ohms Percent NAC 1 #12 Solid 0.12 0.00% NAC 2 #12 Solid 0.00 0.00% NAC 3 #12 Solid 0.00 0.00% NAC 4 #12 Solid 0.00 0.00% Current Draw Resistance Length Voltage @ EOL Amps Ohms/1000 ft. Feet (One Way)Volts IntelliKnight 6808 EOL Voltage Drop 20.4 Volts 16 Volts 10.00% 0.000 1.93 0 20.40 0.000 1.93 0 20.40 0.002 1.93 30 20.40 0.000 1.93 0 20.40 #10 Stranded 1.24 #12 Solid 1.93 #12 Stranded 1.98 Resistance Table Wire Type Resitance AWG Ohms/1000 ft. #10 Solid 1.21 Note: All Resistance values are taken from Table 8 Conductor Properties of the NFPA 70 National Electrical Code. All values are for Direct Current Resistance at 75°C (167°F). #16 Stranded 4.99 #18 Solid 7.77 #18 Stranded 7.95 #14 Solid 3.07 #14 Stranded 3.14 #16 Solid 4.89 Page 5 1/23/2023Honeywell Internal 12/20/2022 1311C YELM WRF Panel FACP Circuit Device Current # of Devices Current EOL T1 HPF-PS6B 6AMP BOOSTER SUPPLY 0.157 X 1 =0.157 Ohms Per Foot X Total Wire Length Current VDC Voltage TRIGGER 0 X 0 =0 1.588 30 X 0.157 =0.007 23.993 0 X 0 =0 0 X 0 =0 Total Current 0.157 Panel FACP Circuit Device Current # of Devices Current EOL T2 HPF-PS6B 6AMP BOOSTER SUPPLY 0.157 X 1 =0.157 Ohms Per Foot X Total Wire Length Current VDC Voltage TRIGGER 0 X 0 =0 1.588 550 X 0.157 =0.137 23.863 0 X 0 =0 0 X 0 =0 Total Current 0.157 Panel BPS 1 AT FACP Circuit Device Current # of Devices Current EOL N1 P2*L 75CD 0.111 X 1 =0.111 Ohms Per Foot X Total Wire Length Current VDC Voltage NOTIFICATION P2*K 75CD 0.154 X 1 =0.154 2.52 201 X 0.265 =0.134 23.866 0 X 0 =0 0 X 0 =0 0 X 0 =0 Total Current 0.265 Panel BPS 1 AT FACP Circuit Device Current # of Devices Current EOL N2 P2*L 15CD 0.044 X 1 =0.044 Ohms Per Foot X Total Wire Length Current VDC Voltage NOTIFICATION P2*L 30CD 0.065 X 2 =0.13 2.52 272 X 1.078 =0.739 23.261 PC2*L 75CD 0.137 X 2 =0.274 PC2*L 95CD 0.161 X 2 =0.322 P2*K 75CD 0.154 X 2 0.308 Total Current 1.078 Panel BPS 1 AT FACP Circuit Device Current # of Devices Current EOL N3 P2*L 30CD 0.065 X 1 =0.065 Ohms Per Foot X Total Wire Length Current VDC Voltage NOTIFICATION P2*K 75CD 0.154 X 1 =0.154 2.52 390 X 0.219 =0.215 23.785 0 X 0 =0 0 X 0 =0 Total Current 0.219 12/20/2022 1311C YELM WRF Panel BPS 1 AT FACP Circuit Device Current # of Devices Current EOL N4 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 2.52 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Panel BPS 1 AT FACP Circuit Device Current # of Devices Current EOL N5 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 2.52 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Panel BPS 2 SOLIDS ELECTRICAL ROOM Circuit Device Current # of Devices Current EOL N6 P2*L 75CD 0.111 X 2 =0.222 Ohms Per Foot X Total Wire Length Current VDC Voltage NOTIFICATION P2*K 75CD 0.154 X 1 =0.154 2.52 60 X 0.376 =0.057 23.943 0 X 0 =0 0 X 0 =0 0 X 0 =0 0 X 0 =0 0 X 0 =0 Total Current 0.376 Panel BPS 2 SOLIDS ELECTRICAL ROOM Circuit Device Current # of Devices Current EOL N7 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 1.588 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Panel BPS 2 SOLIDS ELECTRICAL ROOM Circuit Device Current # of Devices Current EOL N8 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 1.588 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Panel BPS 2 SOLIDS ELECTRICAL ROOM Circuit Device Current # of Devices Current EOL N9 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 1.588 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Panel BPS 2 SOLIDS ELECTRICAL ROOM Circuit Device Current # of Devices Current EOL N10 0 X 0 =0 Ohms Per Foot X Total Wire Length Current VDC Voltage SPARE 0 X 0 =0 1.588 0 X 0 =0.000 24.000 0 X 0 =0 0 X 0 =0 Total Current 0 Device Type Qty Total Qty Main Circuit Board Choose EOLR used ↓ 4.7k 1 X 0.1390 = 0.1390 1 X 0.1570 = Main Circuit Board with ZNAC-PS Class A card 0 X 0.1350 = 0.0000 0 X 0.1420 = NAC / Output # 1 1 X 0.0000 = 0.0000 1 X 0.2650 = NAC / Output # 2 1 X 0.0000 = 0.0000 1 X 1.0780 = NAC / Output # 3 1 X 0.0000 = 0.0000 1 X 0.2190 = NAC / Output # 4 1 X 0.0000 = 0.0000 1 X 0.0000 = NAC / Output # 5 1 X 0.0000 = 0.0000 1 X 0.0000 = 0.1390 X = X = = * Derating Factor required to compensate for the non-linear discharge characteristic of a battery. Calculation in Total Sheet HPF-PS6 Battery Calculation Secondary Power Source Requirements Standby Current (amps)Secondary Alarm Current (amps) Current Draw Current Draw Total Standby Load Total Alarm Load HPF-PS6 Battery Calculation Note 1: You are fully responsible for verifying these calculations . Note 2: You only need to make entries in the yellow cells Required Standby Time in Hours 24 Hours Standby Load Current (Amps) 0.1390 Amps 24 Recommended Batteries: BAT-1270 - 7AH Batteries Required Alarm Time in Hours 5 Minutes Alarm Load Current (Amps) 1.7190 Amps 0.084 Total Current Load *Multiply by the Derating Factor 1.2 Total Ampere Hours Required Page 1 12/20/2022 Total 0.1570 0.0000 0.2650 1.0780 0.2190 0.0000 0.0000 1.7190 3.336 AH 0.144 AH 3.48 AH x 1.20 ry Alarm Current (amps) Standby Time in Hours 1270 - 7AH Batteries d Alarm Time in Hours 4.18 AH Page 2 12/20/2022 Device Qty Total Qty P2*L 75CD 1 x 0.000000 = 0.000000 1 x 0.111000 = P2*K 75CD 1 x 0.000000 = 0.000000 1 x 0.154000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0.000000 Device Qty Total Qty P2*L 15CD 1 x 0.000000 = 0.000000 1 x 0.044000 = P2*L 30CD 2 x 0.000000 = 0.000000 2 x 0.065000 = PC2*L 75CD 2 x 0.000000 = 0.000000 2 x 0.137000 = PC2*L 95CD 2 x 0.000000 = 0.000000 2 x 0.161000 = P2*K 75CD 2 x 0.000000 = 0.000000 2 x 0.154000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0.000000 Device Qty Total Qty P2*L 30CD 1 x 0.000000 = 0.000000 1 x 0.065000 = P2*K 1 x 0.000000 = 0.000000 1 x 0.154000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0.000000 NAC / Output # 3 HPF-PS6 Circuit Detail NAC / Output # 1 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load NAC / Output # 2 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load Page 3 12/20/2022 Total 0.111000 0.154000 0.265000 Total 0.044000 0.130000 0.274000 0.322000 0.308000 1.078000 Total 0.065000 0.154000 0.219000 Page 4 12/20/2022 Device Qty Total Qty 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0.000000 Device Qty Total Qty 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0.000000Total Standby Load Total Alarm Load NAC / Output # 4 Non-Alarm Draw Alarm Draw Total Standby Load Total Alarm Load NAC / Output # 5 Non-Alarm Draw Alarm Draw Page 5 12/20/2022 Total 0.000000 Total 0.000000 Page 6 12/20/2022 TAB 7 CERTIFICATIONS Washinglan State Deparhnent of Labor & Industries_(https://Ini.wa.gov). Contractors DEER, SANDIFER M Owner or tradesperson DEER, SANDIFER M TENINO, WA 98589 Doing business as THURSTON County DEER, SANDIFER M WA UBI No. License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Electrician Active Meets current requirements. License specialties LIMITED ENERGY HVAC/RFRG License no. DEER*SM021 PC Effective — expiration 10/03/1998— 03/2712025 License Violations Mo........................................... o license violations during the previous 6 year period. Continuing education Course title First Aid CPR Completed 05/18/2022 Course Hours 4.00 FirstAid Course code WA2021-310 Course title 2020 Grounding and Bonding Completed Course code 03/22/2022 WA2021-254 Course Hours 4.00 Affidavit hours ........................... No affidavit hours reported. Workplace Safety & Health Check for any past safety and health violations found on jobsites this business was responsible for. No inspections during the previous 6 year period. Sandifer M Deer Fire Alarm Systems Level IV 129796 2025-08-01 � wa.nngm�zcxe oepammem or Labor & Industries_(https://Ini.wa.gov) Firkins, Charles Larrick Owner or tradesperson Firkins, Charles Larrick TACOMA, WA 98443 ...................................................................... PIERCE County WA UBI No. License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Electrician ................................ License specialties LIMITED ENERGY License no. FIRKICL850BB Effective expiration 02/18/2015— 02/01/2024 Active Meets current requirements. License Violations ....................................................... No license violations during the previous 6 year period. Continuing education ............................................... No continuing education credits have been reported for the next/current renewal. Workplace Safety & Health Check for any past safety and health violations found on jobsites this business was responsible for. No inspections during the previous 6 year period. Charles Larrick Firkins Fire Alarm Systems Level II 146805 2024-03-01 WangState rhn Laborshiron & IndustriesDepeentof (https://Ini.wa.gov). Register as a Contractor ANGELO, DAVID G Owner or tradesperson ANGELO, DAVID G PUYALLUP, WA 98375 Doing business as PIERCE County ANGELO, DAVID G WA UBI No. License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Electrician Active Meets current requirements. License specialties LIMITED ENERGY License no. ANGELDG942LB Effective — expiration 02/02/2007— 01/08/2025 License Violations No license violations during the previous 6 year period Continuing education No continuing education credits have been reported for the next/current renewal. Affidavit hours No affidavit hours reported. Workplace Safety & Health Check for any past safety and health violations found on jobsites this business was responsible for. No inspections during the previous 6 year period. NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES® NICET a Providing Certification Programs Since 7967 BE IT KNOWN THAT David G. Angelo IS HEREBY AWARDED THE FOLLOWING CERTIFICATION Fire Alarm Systems Leel II Certification Number 104949 :18,11 ZKONIN 1! Valid Through 2023-04-01 nicet.org/verify BASED UPON SUCCESSFUL DEMONSTRATION OF REQUISITE KNOWLEDGE, EXPERIENCE AND WORK PERFORMANCE AS SET FORTH BY THIS INSTITUTE. W-41, # + rte ' CHAIR OF THE NICET BOARD OF GOVERNORS A DIVISION OF THE NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS Washington State rhnof Labor & IndustriesDepeent (https://Ini.wa.gov). Contractors Ruddell, Justin M Owner or tradesperson Ruddell, Justin M SPANAWAY, WA 98387 .................................................................... Doing business as PIERCE County Ruddell, Justin M WA UBI No. License Verify the contractor's active registration / license / certification (depending on trade) and any past violations. Electrician License specialties LIMITED ENERGY License no. RUDDEJM864DP Effective — expiration 05/24/2014— 10/27/2025 Active Meets current requirements. License Violations No license violations during the previous 6 year period. Continuing education ............................................. No continuing education credits have been reported for the next/current renewal. Affidavit hours No affidavit hours reported. Workplace Safety & Health Check for any past safety and health violations found on jobsites this business was responsible for. No inspections during the previous 6 year period.