Loading...
1311C YELM WRF FAD Submittal 1-23-23SCOPE OF WORK INSTALL NEW SILENT KNIGHT SK -6808 ADDRESSABLE FIRE ALARM PANEL IN GROUP H-4 OCCUPANCY FOR ADDITIONAL FIRE DETECTION COVERAGE IN 4 BUILDINGS. PANEL TO TIE INTO EXISTING FIRE PANEL. PROVIDE FIRE ALARM VISUAL AND AUDIBLE NOTIFICATION THROUGHOUT BUILDINGS. PROVIDE PROTECTO WIRE AND PULL STATIONS THROUGHOUT BUILDINGS. BUILDINGS ARE NOT SPRINKLED. DESIGNED IN ACCORDANCE WITH: NFPA 72 2019 NEC 2020 IBC 2018 INSTALLATION NOTES: 1) PRIOR TO CALLING FOR INSPECTION, THE INSTALLER SHALL PROVIDE DOCUMENTATION TO THE LOCAL AHJ STATING THAT THE SYSTEM HAS BEEN INSTALLED, TESTED, EVALUATED AND CONFIRMED TO BE IN ACCORDANCE WITH ALL GOVERNING CODES AND THE APPROVED PLANS. THE FIRE ALARM INSTALLER SYSTEM INSTALLER SHALL COMPLETE AN NFPA 72 RECORD OF COMPLETION (NFPA 72 10.18.2.1). THE RECORD OF COMPLETION SHALL BE PROVIDED TO THE AHJ INSPECTOR AT THE TIME OF THE INSPECTION (NFPA 72 10.18.2.1.2.4). 2) INSTRUCTIONS FOR OPERATING, TESTING, AND MAINTENANCE OF THE SYSTEM ALONG WITH RECORD DRAWINGS OTHERWISE REFERRED TO "AS-BUILTS" AND EQUIPMENT SPECIFICATIONS SHALL BE PROVIDED AT AN APPROVED LOCATION. 3) ALL SYSTEMS AND DEVICES SHALL BE INSTALLED AND TESTED PER THE MANUFACTURE'S LISTING AND THE AUTHORITY HAVE JURISDICTION (NFPA 72 10.14.2.1). LABEL ALL DEVICE LOCATIONS. 4) FACP AND ALL REMOTE POWER SUPPLIES REQUIRE A DEDICATED 120VAV - 20AMP CIRCUIT. A NOTICE PLACED IN THE FACP SHALL DIRECT PERSONNEL TO THE LOCATION OF THE ELECTRICAL PANEL THAT IS SUPPLYING DEDICATED POWER TO THE SYSTEM (NFPA 72 10.5.5.1). THE DEDICATED CIRCUIT BREAKER THAT SERVES THE FIRE ALARM SYSTEM SHALL BE LABELED AND SECURED AGAINST TAMPERING WITH A RED BREAKER LOCKOUT. 5) WALL MOUNTED STROBES SHALL BE PLACED 80" MINIMUM TO 96" MAXIMUM ABOVE FLOOR LEVEL (NFPA 72 18.5.4.1 & 2). WALL MOUNTED STROBES SHALL BE SIZED IN ACCORDANCE WITH (NFPA 72 TABLE 18.5.4.3.1(A). CEILING MOUNTED STROBES SHALL BE PLACED AND SIZED IN ACCORDANCE WITH (NFPA 72 TABLE 18.5.4.3.1(B). 6) WHEN MORE THAN TWO NOTIFICATION APPLIANCES ARE VISIBLE AT THE SAME TIME IN THE SAME ROOM OR ADJACENT SPACE OR THE FIELD OF VIEW THE FLASH OF THE STROBES SHALL BE SYNCHRONIZED (NFPA 72 18.5.4.3. (3) AND (4). 7) PULL STATIONS SHALL BE PLACED BETWEEN 42 AND 48 INCHES ABOVE FLOOR LEVEL. DEVICES SHALL BE RED IN COLOR (ICC A117.1 309 AND NFPA 72 17.14.5). 8) CENTER SMOKE DETECTORS IN CORRIDORS WITH CEILING LIGHTING AND THE FA STROBES. SMOKE DETECTORS IN CORRIDORS ARE TO BE SPACED PER NFPA 72 17.6.3.1 (H) AND 17.7.3.2.4.2 (4). 9) AUDIBILITY REQUIREMENTS: A SOUND LEVEL OF 75dbA or 15dbA OVER AMBIENT SHALL BE REACHED IN ALL AREAS PROVIDED WITH FIRE ALARM DEVICES PER SPECIFICATION AND NFPA-72. 10) SET STROBE CANDELA OUTPUT AS SHOWN ON PLANS. SET HORN TO MED SETTING 11) FIRE ALARM CIRCUITS TO BE INSTALLED, SECURED, AND TERMINATED IN ACCORDANCE WITH NEC, NFPA 72, AND LOCAL AHJ REQUIREMENTS AND STANDARDS. 12) NOTIFY E -SQUARED SYSTEMS OF ANY DESIGN QUESTIONS OR CHANGES PRIOR TO INSTALLATION OR FABRICATION. COMPARE DRAWINGS WITH CURRENT CONTRACT DRAWINGS PRIOR TO INSTALLATION. 13) ANY ALTERATIONS OR VARIATIONS FROM THE DRAWINGS SHOULD BE APPROVED PRIOR TO PROCEEDING AND DOCUMENTED ON THE AS -BUILT DRAWINGS. VERIFY DEVICE LOCATIONS PRIOR TO INSTALLATION. 14) REFERENCE FACTORY INSTRUCTION MANUALS CURING INSTALLATION OF FIRE CONTROL EQUIPMENT. 15) DETECTORS SHALL NOT BE MOUNTED IN A DIRECT AIR STREAM. DO NOT INSTALL DETECTORS WITH IN 3'-0" OF AIR DIFFUSERS. 16) US ONLY U.L. LISTED DEVICES. 17) DO NOT INSTALL DETECTOR HEADS UNTIL FINAL CLEANING HAS BEEN PERFORMED. 18) FIELD DETERMINE INTERFACE REQUIREMENTS AND LOCATIONS OF EQUIPMENT SUPPLIED BY OTHER TRADES. (I.E. SPRINKLER DEVICES, HVAC UNITS, FIRE DAMPERS, ELEVATOR CONTROLS, & FAN CONTROLS.) 19) NOTIFY E -SQUARED A MIN. OF 1 WEEK PRIOR TO THE INSTALLATION OF ALL WIRING, DEVICES, AND POWER, FOR SCHEDULING OF SYSTEM CHECK OUT AND PROGRAMMING. E -SQUARED REQUIRES A MIN. OF 2 DAYS ON SITE FOR CHECKS PRIOR TO SCHEDULING A FIRE ALARM FINAL. LARGER SYSTEMS WILL REQUIRE MORE TIME. FAILURE TO HAVE WORK COMPLETED WILL REQUIRE RESCHEDULING AND ADDITIONAL COSTS. 9 r :I w d I LTA &TiTj :19 913 NORTHERN PACIFIC RD SE YELM, WA 98597 FIRE ALARM SYSTEM ELECTRICAL NOTES: 1) INSTALLATION SHALL COMPLY WITH NFPA 70, PARTICULARLY ARTICLE 760, AND SHALL ALSO COMPLY WITH NFPA 72, AND ALL LOCAL ELECTRICAL CODES AND LOCAL JURISDICTION REQUIREMENTS. 2) CONDUIT INDICATED ON PRINTS IS DIAGRAMMATIC AND MAY BE REROUTED PER FIELD REQUIREMENTS. 3) AC POWER SHALL NOT OCCUPY THE SAME CONDUIT AS FIRE PROTECTION CIRCUITS (MOST FIRE DETECTION CKT'S ARE NEC CLASS 3) 4) ALL SLC LOOP WIRING SHALL BE MINIMUM 2 CONDUCTOR #16, UNSHIELDED, LOW/MID CAPACITANCE FIRE ALARM CABLE OF THE PROPER RISER AND/OR PLENUM TYPE. SEE WIRE LEGEND FOR PROJECT SPECIFIC TYPE/GAUGE. 5) CONVENTIONAL FIRE DETECTION INITIATING DEVICE CIRCUITS OR NOTIFICATION APPLIANCE CIRCUITS SHALL NOT BE PARALLEL BRANCHED (TEE TAPPED) TO ENSURE SUPERVISION OF WIRING. ADDRESSABLE CLASS "A" FIRE DETECTION SIGNALING LINE CIRCUITS (SLC) SHALL NOT BE PARALLEL BRANCHED (TEE TAPPED) TO ENSURE SUPERVISION OF WIRING. 6) OBSERVE POLARITY OF ALL FIRE DETECTION WIRING. POLARITY SHALL BE MAINTAINED THROUGHOUT ENTIRE SYSTEM; WIRE SHALL BE MARKED AND IDENTIFIED WHERE SPLICED, AND AT ANY JUNCTION BOXES. 7) THE FIRE ALARM PANEL GROUND SHALL BE A SEPARATE CONTINUOUS GROUND WIRE BACK TO THE SOURCE GROUND; CONDUIT GROUND IS NOT ACCEPTABLE PER MANUFACTURER'S SPECIFICATIONS. 8) ALL FIELD WIRING SHALL BE CHECKED FOR SHORTS, GROUNDS, & PROPER END OF LINE RESISTOR (ELR) VALUES BEFORE SCHEDULING E -SQUARED FOR SYSTEM CHECK OUT. DOCUMENT CIRCUIT READINGS AND PRESENT TO E -SQUARED TECHNICIAN UPON INITIAL ARRIVAL ON SITE. PROVIDE E -SQUARED A MIN. OF 1 WEEK NOTICE PRIOR TO CHECK OUT. 9) FIRE ALARM PANEL, AND ANY OTHER FIRE DETECTION EQUIPMENT REQUIRING 120VAC, SHALL BE SUPPLIED BY A DEDICATED CIRCUIT BREAKER OTHER (NON -FIRE DETECTION) EQUIPMENT SHALL NOT SHARE THE FIRE ALARM CIRCUIT(S). THIS BREAKER SHALL BE PROVIDED WITH A BREAKER LOCK -OUT FOR ALL FIRE ALARM EQUIPMENT AND MARKED "FIRE ALARM CIRCUIT CONTROL". 120VAC POWER BY OTHERS. 10) POWER SHALL NOT BE APPLIED TO THE FIRE ALARM PANEL UNLESS A REPRESENTATIVE FROM E -SQUARED IS PRESENT. 11) WIRE NUTS ARE NOT ALLOWED. ALL SPLICES ARE TO BE TERMINATED ON TERMINAL STRIPS. (APPLICABLE TO MILITARY INSTALLATIONS ONLY) 12) ALL SLC, NOTIFICATION, AND SPEAKER WIRING SHALL BE STYLE 6 (CLASS A). NO OUTPUT CIRCUITS, FROM FCP, OR RETURN CIRCUITS SHALL BE RUN IN THE SAME CONDUIT. VERTICAL SEPARATION OF CONDUITS SHALL BE AT LEAST 1 FOOT AND HORIZONTAL SEPARATION SHALL BE AT LEAST 4 FEET. 13) ELECTRICAL FINAL SHALL BE COMPLETED PRIOR TO SCHEDULING E—SQUARED FOR CHECK—OUT, UNLESS REQUIRED OTHERWISE BY AHJ. SYSTEM INPUT SYM QTY MODEL NUMBER DESCRIPTION MANUFACTURER 1� MOUNTING CIRCUIT TYPE Q GAUGE COLOR 1 ADDRESSABLE CIRCUIT FPLP A(1,7—,3,.) 16/2 RED JACKET 1 FACP 1 6808 ADDRESSABLE FIRE ALARM PANEL SILENT KNIGHT SURFACE MOUNT OfOf w 6'-0" 2 BPS 1 HPF-PS6B 6AMP 5 CIRCUT POWER SUPPLY FCI SURFACE MOUNT 14/2 3 :D [if ``' DURA12-8 :3 a a = � & BPS JACKET 4 FM—BBl 2 M13132 2 BOARD CABINET FCI SURFACE MOUNT 7 ADDRESSABLE CIRCUIT UG RATED 5 ~ m w o� o� Qzo 0 wv o w 12 2 6 " 1 SK -ZONE -6 6 ZONE CONVENTIONAL TO SLC MODULE SILENT KNIGHT IN MBB2 JACKET C) 7 d J p O w ~O w 8 INITIATING DEVICES O z �v~i �o a� PHOTOELECTRIC SMOKE DET. ADDRESSABLE SILENT KNIGHT ON BASE 10 1 B300-6 6" SENSOR BASE v 4" ¢� c�ac� MUDRING 11 0 8 SK -PULL -DA MANUAL PULL STATION DUAL ACT.- ADDRESSABLE SILENT KNIGHT 4" SQ 1.5" DEEP W/S.G. MUDRING 12 ❑M ALARM @ FCP SK -MONITOR SINGLE POINT MONITOR MODULE, ADDRESSABLE SILENT KNIGHT 4" X X X 13 0 4 M50OX ISOLATOR MODULE RIXSON 4" SQ 1.5" DEEP W/S.G. MUDRING TROUBLE @ FCP X X X X PROTECTO WIRE MONITOR MODULE CONTACTS 15 SUPV. © FCP NOTIFICATION DEVICES 17 WP 4 P2RK RED WALL MOUNTED HORN/STROBE WP SYSTEM SENSOR WP BACK BOX 18 C 4 PC2RL RED CEILING MOUNTED HORN/STROBE SYSTEM SENSOR 4" SQ 1.5" DEEP W/S.G. MUDRING 19 5 P2RL RED WALL MOUNTED HORN/STROBE :�D ACTIVATE FIRE SQ 1.5" DEEP W/S.G. MUDRING 20 X X X 21 a- HORN/STROBES 22 23 24 ACTIVATE FIRE lj::�:_ FOR SEE ADDITIONAL MOUNTING OPTIONS DATA SHEETS, PROVIDED. 0 WATERFLOW BELL ::5 TRANSMIT GEN ALM X X X LLJ TO MONITORING C") TRANSMIT WF ALM Cr) TO MONITORING TRANSMIT TROUBLE X X X X TO MONITORING TRANSMIT SUPERVISORY TO MONITORING ACTIVATE UNIT X X X HORN/STROBES DESIGNER OF RECORD: SAND�FER DEER MCET ( #129796 BILL OF MATERIALS (BOM) ITEM SYM QTY MODEL NUMBER DESCRIPTION MANUFACTURER 1� MOUNTING CIRCUIT TYPE CABLE TYPE NO. GAUGE COLOR 1 ADDRESSABLE CIRCUIT FPLP A(1,7—,3,.) 16/2 RED JACKET 1 FACP 1 6808 ADDRESSABLE FIRE ALARM PANEL SILENT KNIGHT SURFACE MOUNT TOP AT 6'-0" 2 BPS 1 HPF-PS6B 6AMP 5 CIRCUT POWER SUPPLY FCI SURFACE MOUNT 14/2 3 JACKET 4 DURA12-8 12V-8AH BATTERY DURACELL MOUNTS IN FACP & BPS JACKET 4 FM—BBl 2 M13132 2 BOARD CABINET FCI SURFACE MOUNT 7 ADDRESSABLE CIRCUIT UG RATED 5 FIS 1 ISO -6 6 INPUT ISOLATOR MODULE FCI IN MBB2 12 2 6 " 1 SK -ZONE -6 6 ZONE CONVENTIONAL TO SLC MODULE SILENT KNIGHT IN MBB2 JACKET 7 8 INITIATING DEVICES 9 Z 1 SK -PHOTO PHOTOELECTRIC SMOKE DET. ADDRESSABLE SILENT KNIGHT ON BASE 10 1 B300-6 6" SENSOR BASE SILENT KNIGHT 4" SQ 1.5" DEEP W/S.G. MUDRING 11 0 8 SK -PULL -DA MANUAL PULL STATION DUAL ACT.- ADDRESSABLE SILENT KNIGHT 4" SQ 1.5" DEEP W/S.G. MUDRING 12 ❑M 6 SK -MONITOR SINGLE POINT MONITOR MODULE, ADDRESSABLE SILENT KNIGHT 4" SQ 1.5" DEEP W/S.G. MUDRING 13 0 4 M50OX ISOLATOR MODULE RIXSON 4" SQ 1.5" DEEP W/S.G. MUDRING 14 500' PHSC-155-XCR SINGLE CONTACT 155° HEAT DET. WIRE PROTECTO WIRE MONITOR MODULE CONTACTS 15 16 NOTIFICATION DEVICES 17 WP 4 P2RK RED WALL MOUNTED HORN/STROBE WP SYSTEM SENSOR WP BACK BOX 18 C 4 PC2RL RED CEILING MOUNTED HORN/STROBE SYSTEM SENSOR 4" SQ 1.5" DEEP W/S.G. MUDRING 19 5 P2RL RED WALL MOUNTED HORN/STROBE SYSTEM SENSOR 4" SQ 1.5" DEEP W/S.G. MUDRING 20 21 22 23 24 MOUNT MANUAL PULL STATIONS SO ACTUATION LEVER IS AT +48" ABOVE FINISHED FLOOR. MOUNT HORN/STROBES AND STROBES WITH BOTTOM OF STROBE AT +80" ABOVE FINISHED FLOOR. ENTIRE LENS MUST BE BETWEEN 80" & 96" AND NO LESS THAN 6" BELOW CLG. MOUNT ALL PANELS WITH TOP AT 6'-0" AFF. SET STROBE CANDELA OUTPUT AS SHOWN ON PLANS. SET INTERIOR HORNS TO LOW SETTING, EXTERIOR HORNS TO HIGH SETTING. lj::�:_ FOR SEE ADDITIONAL MOUNTING OPTIONS DATA SHEETS, PROVIDED. ALL CABLES SHOULD BE 16-12AWG SOLID, MID CAPACITANCE, PLENUM AS SHOWN(EXCEPT U.G.), NON—SHIELDED. ALL CONDUITS SHOULD BE 3/4" MINIMUM/OR AS REQUIRED BY NEC 70 UNLESS OTHERWISE NOTED ON PLANS. INDOOR CABLE REPRESENTS WINDI CITY WIRE PART NUMBERS. UNDERGROUND (U.G.) CABLE REPRESENTS WEST PENN PART NUMBER. cn z Li 0 U w cn N w N Q C) N Ld w p LLI 0 I W JOB # 1311 C FA -01 CABLE/CONDUCTOR ST CIRCUIT TYPE CABLE TYPE NO. GAUGE COLOR 1 ADDRESSABLE CIRCUIT FPLP A(1,7—,3,.) 16/2 RED JACKET 2 NOTIFICATION APPLIANCE CIRCUIT FPLP N(1,2,3 .... 14 2 RED JACKET 3 CONVENTIONAL CIRCUIT FPLP B 12/2 RED JACKET 4 24VDC POWER FPLP C 14/2 RED JACKET 5 PROTECTO WIRE PHSC—XCR FPLP P(1,2,3....) 16 2 RED JACKET 6 BOOSTER POWER SUPPLY TRIGGER CIRCUIT FPLP T 1 ,2,3,... 12 2 RED JACKET 7 ADDRESSABLE CIRCUIT UG RATED AQUASEAL A 1 ,2,3,... 12 2 BLACK — JACKET 8 NOTIFICATION APPLIANCE CIRCUIT UG RATED AQUASEAL N 1 ,2,3,... 12 2 BLACK JACKET 9 CONVENTIONAL CIRCUIT UG RATED) ASEAL Bg 12/2 BLACK JACKET ALL CABLES SHOULD BE 16-12AWG SOLID, MID CAPACITANCE, PLENUM AS SHOWN(EXCEPT U.G.), NON—SHIELDED. ALL CONDUITS SHOULD BE 3/4" MINIMUM/OR AS REQUIRED BY NEC 70 UNLESS OTHERWISE NOTED ON PLANS. INDOOR CABLE REPRESENTS WINDI CITY WIRE PART NUMBERS. UNDERGROUND (U.G.) CABLE REPRESENTS WEST PENN PART NUMBER. cn z Li 0 U w cn N w N Q C) N Ld w p LLI 0 I W JOB # 1311 C FA -01 6' HIGH CWUNIJNK FENCE W/BARB WIRE CEN TR L PUMP STATIO CHEMICAL BLDG &TE MAP SCALE: NTS 6' HIGH CHAINLINK FENCE N Z W '75 O U W (/) N W N � I Q o C) N Ld W CD JOB # 1311 C FA - 02 1 20F8 W N LL N U Li-- � Ln Qm cl- Q -j a LLJ =W LLJ o � z L.L. JOB # 1311 C FA - 02 1 20F8 00 I- U � 00 J N 12 D_ N 12 W J ~ J X FEED FORWARD o �a-r- cn c� a-0 AREA 300 '� N2-9 N 00 WP 75CD L7 r� F/I<-6-2N2LLJ ,o Ln N L97M127o'Nz-10EOL CENTRIFUGE o 30CD PUMP STATION FL97M11 o_ N2-8 NZ Ag,B g, N g 3 A 15CD A Ag,Ngz M X P5 L97M10 A > Lu / U) O MBR GALLERY z co Q 402 w 0 U Q MRB 2 TANK MRB 1 TANK cn cn ( ON OCCUPIED - (NON OCCUPIED' <N2-7 0 U 75CD o� Q ANOXIC WP o 2N2 TANKSLd z= o- CZ Ld � N cv I o Q C N W � MECH/ELEC BLDG ® AREA 401 A,Nz 2N J J Ag,Bg Ngz3 A b L97MoM IN 1" CONDUIT P ji W N2 -<:'a L97M08 F >< u% N2 -6N2 ' NZ -5 ` 9 5 C D/0'\<C � C 95CD C O W O 13,N3 L� Q:� Q w AERATION P 4 N2- Nz-3 0 LSI U TAN TAN KS N2 30CD 2N2 75CD 1 - LL LL- — U ;o, o WP 0 w LJ P3 J U �MM A L97M07 Q W P2 v A F A L97 6 F97M03 AL97M05 CABINETS F 2A M CLEAN IN PLACE (CIP) MBB2 B,N3 #1&2 J , , Nz , , BLDG AREA 403 HOUSE S01 2 Nz Nz 1 ZONE -6 L971 ELEC ROOM 70 Nz 2 & ISO -6 N- A 75CD400 75CD MODULES IS06 02 X AB,T FACP BPS1PZ >< w B,Nz,N3 o M L97M04 A,N1 N LL N U � LL- TO CHEM BUILDING Ag,Ng1 Ln Q 0-) 0- Q J w � a =W LLJ o � z LL. MBR BU LD NG PLAN SCALE: 1 /8"=1'-0" NORTH JOB # 1311C FA -03 3OF8 M r7 00 I- cy) N') U� J Q 00 U) 0- N W J ~ J X >- LL- L7 2 0 � O N W Q N 04 00 O N 1 J) to N W Lo W O N M O 0_ 0_ 07 z W O U CHEMICAL BUILDING W 600 J 0 Q 0 CENTRIFUGE FEED PUMP w S TAT I O N z= cl�m oZ W N N o Q � N M L97M02 i? CD FROM MBR BUILDING A P, Ag,Ng1 X#' F A L97M01 N'N1-2 I TO CONTROL 75CD N3-2 BUILDING WP ;o� ;o� o ww 30CD N3 Ag,Bg N,-1 2N, o�o� Ag,Ng3 75CD F Mp2 L97M14 FROM FWRD O �_ FEED N3-1 '\o' W 0 75CD BUILDING LL - WP Ag,Bg,Ng3 Q Q V) U CD LSI z Q 00LdU w Q W m En LL- -':5 w N U u— N00 i Qm CHEMICAL BUILDING FLOOR PLAN CENTRIFUGE PUMP STATION PLAN c w = Q SCALE: 1/8"=1'-0" _ SCALE: 1/8"=1'-0" _ j Q p NORTH NORTH W � � Q W W O � z LL— O-) JOB # 1311C FA -04 4OF8 IV ME PRO W CEN TRI . CENTRI. NORTH PROTECTO EXIT WIRE T MBR ELECTRICAL ROOM SLC & NAC RISERSCALE: NTS Nv, cn z W 0 U W cn N W N Q o p N Ld W o W' JOB # 1311 C FA - 05 1 5 OF 8 W ry ry N LL N U � Ln Q(Y) 0- Q �J Q w � � w W o � z CD JOB # 1311 C FA - 05 1 5 OF 8 00 r DESISNER OF R ECORDo CONNECT TO EARTH GROUND PER ARTICLE 760 OF NEC. FAILURE TO U � 00 JAN (n Ln N SAND�FER DEER CONNECT TO A METALLIC GROUND WATER PIPE OR GROUND ROD WILL RESULT IN LOSS OF LIGHTNING PROTECTION. PANEL NEUTRAL OR 12 � J j< >- CONDUIT GROUND IN NOT ACCEPTABLE. USE #14 AWG MINIMUM. > MCET \/ V (FAS) CONNECT TO 12 A/H TO 18 A/H BATTERIES, MAX. USE #14 AWG WIRE MIN. 0 ��O (fin I - v #129796 (NON -POWER LIMITED) Q W N 00 ;n� WXLn O N m• O 0_ 0_ 0 ® �❑❑ (� 7off O (n w ❑ 0 j o ® 0 LLJ ❑ (crn ALARM SUpEWSORY TROUBLE VLENCEDD POWER O o 0 0 0�❑ O C3 O�Q O ° ❑ ® O Eu CD C ® Q Of Q o OO O❑ OO O O oo LLJ O❑ O❑ 0 cc O CD❑ ° ,o °rl 0 ®��� ®� 0 1 ° LJ ® 0 O e tE O ® {B C7 G C7 o ® l} ® {i �� ® X z S Z C�O�Q Q0� FRE ALARM c�oHMM o 3 e o o ° FE3❑ g g ®®� ®� 0 ® o g ® 0 o COO nf�nlG�MG�IDC�LA40O G3 o......_.. o ° ® o ® O ® ®d ®� ® + v o g >} ® Q ❑ g I z w Q N o ® ® O ��� ® O ® g ®� o ®® + rl) C3® ®a g ®®❑�® II Q o N ® �® O>a ® ® + v w o ❑0 OIleo oEl ®® Q C3 g m ®o��® rl + ®0 V CN g z Ll ° L3 ° L ❑ El ❑ v o ®o / L� U Q U W ° �. o 0 HH HH � ® 0 0 rAGs G ®® ° �� Z ®® ®Doo®®®®®® �® o — © z o ®o®a� iI 0 000 El L) 0 ® m � iz 0f O ° ° o o® ® H o o o �° �%5 o w -- Z J rz %1 v i (J o a EJ EJ / El 00 + ® m ® , (n �,� ® EE 0 ® � L� o di 6d ® A ® ❑ g g ® m � o O ®opo ° �� ®0 ® � + CD V / V) Q ®moo ®o ? ❑®®�m W �® i coo K3 M t;j = El . E❑ Ell]® . � O ®®®o Q ®0 ® J W _j z =� fy�^ye, ° o° o° ( ) CO W (n Vl (1) (n N (n 7b ;b 70 -� ;b D D n+ o+ n n Z z z Z U N N + ;ou N N 0+ ❑❑uu m_m_ 0z0z 0 LLJ �cf) N U � L.LN 0 0 LL_ Ln Q0-)cl- Q jJW a �W LLJ o � z L.L. SILENT KNIGHT 6820 CONTROL PANEL WIRING TERMINALS 6820 WIRE DIAGRAM 2 SCALE: NTS SCALE: NTS JOB # 1311C FA—06 6 OF 8 M I'7 00 r - CB � U � SET STROBE CANDELA OUTPUT AS SHOWN ON PLANS. J ro SIGNAL LINE CKT LOOP 1 (-) Uj SET HORNS TO LOW UNLESS NOTED OTHERWISE.2(+) 1(-) SPRINKLER DEVICE, OR N.O. DRY CONTACT DEVICE. SPRINKLER DEVICE, OR N.O. DRY CONTACT DEVICE. w N J SIGNAL LINE CKT LOOP 1 (+) ^ O (n Q Q U ;�I� BETWEEN J -BOXES �1A FROM FACP 3 47K EOL Z D rO 47K EOL 3» RESISTOR RESISTOR N Lv SPECIFICATIONS: TO ELEVATOR Q N � N 00 MOUNTING: 6.1 INCH DIAMETER (15.5 CM) 4 INCH SQUARE BOX WITH OR WITHOUT PLASTER RING B300-6 BASE RECALL CIRCUIT(S). O' to r- MIN. DEPTH 1.5 INCHES VERIFY CONNECTIONS I ro ENTIRE STROBE LENS TO BE LOCATED BETWEEN 80" AND 96" AFF AND NO 4 INCH OCTAGONAL BOX, MIN. DEPTH 1.5 INCHES (TYPICAL, WHEN REQUIRED) 3.5 INCH OCTAGONAL BOX, MIN. DEPTH 1.5 INCHES SINGLE GANG BOX, MIN. DEPTH 1.5 INCHES WITH ELEVATOR CONTRACTOR. TO WON FIRE DOOR CONTROLLER LL1 X N p m .. CLOSER THAN 6" BELOW CLG. VERIFY CONNECTIONS p a_ MANUAL ALARM STATION, SPRINKLER DEVICE, OR Q Q a, a, 7 z 7 z Q Q WITH CONTRACTOR. a_ N.O. DRY CONTACT DEVICE. 6 3 6 3 0 0 0 0 D O O O 7 2(6 7 2 8 8 O IA (0 Il co 0 O x t`S Z`5 4 4 01 O ,A (0 Il 00 O ti ci b I I = v v `3 43 = 0 0 b 3 3 1 2 3 4 b 9 g SPEAKER/STROBE STROBE 80" TO BOTTOM YEL(-) 47K EOL O1 -M N O O O M N O O OF J -BOX RESISTOR (+)\110 O O O MOUNTING DETAIL RED(+) (-)BLK FINISHED FLOOR (-)TO NEXT DEVICE T� (+)TO NEXT DEVICE Z W 4" x 2-1/8" SK—MIM SK MONITOR -2 SK PULL—DA SK RELAY 0 0 J -BOX, TYP. 4" x 2-1/8" 1A, TYP. ADDRESSABLE MONITOR MODULE DUAL MONITOR MODULE ADDRESSABLE PULL STATION ADDRESSABLE RELAY MODULE UTYPICAL, J -BOX, TYP. (TYPICAL, WHEN REQUIRED) ( WHEN REQUIRED) (TYPICAL, WHEN REQUIRED) (TYPICAL, WHEN REQUIRED) LiII � - - - - o II D_ Q 0 0 N SPEAKER/STROBE OR STROBE MOUNTING PLATE (-)BLK 1C (-)BLK TO DOOR HOLDERS Z = FRONT VIEW SIDE VIEW (+)RED (+)RED p z (PROVIDED WITH ENCLOSURE) TO FAN R -20E N/CI\yl PR -1 RELAY w N -24VDC 1 1C SHUTDOWN CIRCUIT. r,0 C Ily VERIFY CONNECTIONS. I y1 UPON AC POWER LOSS THE ON BLUEQ p FROM SNAC-81N +24VDC �_ N/Oily \y I I (TYPICAL, WHEN REQUIRED) y 18/35VDC N/C l�yl RELAY WILL DE -ENERGIZE WHICH WILL DE -ENERGIZE THE DOOR HOLDERS KEEPING N.C. YELLOW WIRE NUT !� N LJ THE LOAD OFF OF THE BATTERIES. TYPICAL WALL MOUNT DETAIL C N/O LyJ ' ORANGE � O SCALE: NTS — TEST COIL (+) 8 0 TEST COIL (-) 7 0 O OcoM RELAY SHOWN (+) s ADDRESSABLE RELAY REQUIRED FOR O ,� o ,� o �, O o ENERGIZED (-)BLK RED(t) SLC Looe OUT 5 0 HVAC SHUTDOWN INTERFACE. ADD N N N TTWIRE NUT COM (-) 4R 0. -20E RELAY WHEN SWITCHING AC VOLTAGE. VERIFY IN FIELD, TYP. us Z = sK_'qj''oorwTPAI/yt RA/RTS (-) 3 � RA (+) 2 0 IF SWITCHING LOW VOLTAGE THROUGHELA AOM-2RF, R -20E RELAYS ARE NOT NEEDED. . 120VAC O v IO 24VDC FROM SNAG -4 8 /Rrs (+) 1 VERIFY WITH MECHANICAL CONTRACTOR. W C/7 DNR DUCT DETECTOR HOUSING (-)TO NEXT DEVICE (REQUIRES ADDRESSABLE SMOKE DETECTOR) (+)TO NEXT DEVICE (TYPICAL, WHEN REQUIRED) SK— RELAY IDP RELAY IF RELAYS ARE NOT WIRED IN A ADDRESSABLE RELAY MODULE 1A, TYP. IF RELAYS ARE NOT WIRED IN A ADDRESSABLE RELAY MODULE N.E. OR FAIL-SAFE CONFIGURATION, (TYPICAL, WHEN REQUIRED) N.E. OR FAIL-SAFE CONFIGURATION, (TYPICAL, WHEN REQUIRED) W O THEY MUST BE LOCATED WITHIN 3 FT. THEY MUST BE LOCATED WITHIN 3 FT. OF THE CONTROLLED DEVICE. OF THE CONTROLLED DEVICE. Q Cf) (PROVIDED WITH ENCLOSURE) o J Q Lv Ms C R -20E ^ II �_ LiJ USE UNSHIELDED WIRE UNLESS OTHERWISE NOTED. SK—MONITOR2 N/C 120VAC 47K EOL & N/O NA R RESISTOR & C 0 00 \ ALL SHIELDS MUST BE TIED THROUGH, ISOLATED, AND TERMINATED, IF USED. O O % % 1D O W z FCI SLC LOOPS ARE LIMITED TO 1,000' MAX., PER LOOP, IF SHIELDED WIRE IS USED. NCO J 45 Q � e QQ T-1 (TYPICAL, WHEN REQUIRED) (n L 3 g (RELAY SHOWN ENERGIZED) - S-32 2 CKT, 7 1 Ip T-2 8 ELEVATOR SHUNT POWER SUPERVISION «T 21 9O /TAMPER SUPERVISION DEVICE ADDRESS O O O 99 DETECTORS. MAX./SLC 98 MODULES MAX./SLC (PROVIDED WITH ENCLOSURE) c R -20E 47K EOL & N/C 120VAC RESISTOR TYPICAL CEILING MOUNT DETAIL Z DEVICE TYPE DESIGNATION. N/O NA SCALE: NTS — S =SMOKE DETECTOR M = MODULE & C o J & N/C W 1D O N/O S TYPICAL ADDRESS DESCRIPTION (TYPICAL, WHEN REQUIRED) (RELAY SHOWN DE -ENERGIZED) ' ^ VNI B, TYP. C, TYP. W �1 �1 LL_ Ln + + + + + ` 4.7K OHM (a) �` 0` X + 24VDC 1 ST FLOOR ELEVATOR SHUNT ACTIVATION Q � 0- i 1 /2 WATT — DOOR HOLDER POWER c z < —� ` OUT -1 OUT -3 J � SNAC 4Q LJ W O � z TO ELEV. SHUNT NEUTRAL �1 B, TYP. 120VAC POWER BRKR., POWER AVAILABLE LIGHT + + + + + BY SITE ELECT. HOT CONTR. HOT c7)SWITCHED /O �O \ \0/ 4.7K OHM (a) a DETAILS SHOWN ARE TYPICAL AND ALL SWITCHED HOT TO ELEV. SHUNT 1/2 WATT DETAILS MAY NOT APPLY TO ALL JOBS. TRIP BRKR., BY SITE ELECT. CONTR. OUT -2 OUT -4 REF. LAYOUT DRAWINGS& B.O.M. 135' FIXED TEMP. HEAT DETECTOR SNAC 4 W/ N.O. CONTACT TYPICAL NAC WIRING DETAIL TYPICAL ADDRESSABLE DEVICE WIRING 4 HOT SCALE: NTS _ (j) SCALE: NTS _ JOB # 1311C ELEVATOR SHUNT TRIP DETECTOR FA -07 7 OF 8 M M CD r - U � Q o0 DESIGNER OE RECORD: J ��� ENTIRE STROBE LENS TO BE LOCATED w J N SANDIFER D BETWEEN 80" AND 96" AFF AND NO CLOSER THAN 6" BELOW CLG. U) w >< >_ >- � NICET IV(FAS)4"X2.1/8" CEILING 2 N 0 o QNB #129796 J—BOX, TYP. .� �► W �, N � O 00 O SNAC ® I�Lo II EXIT DOORWAY ;�� w c14 O FACP W W OPENING m O a_ ANNUN II zo^ o I� 80" BATT _ I .. .. I o 0 72" a 60" 48" _ _ 0 5' MAX. I~ HORN/STROBE OR STROBEMANUAL MOUNTING PLATE 80" TO BOTTOM STATION OF J—BOX FIRE 0 U) /7777777777777777777777777z w FINISHED FLOOR EQUIPMENT MOUNTING DETAIL TYPICAL HORN 8c STROBE WALL MOUNT DETAIL 0 SCALE: NTS _ SCALE: NTS _ (a 42" MIN. 48" MAX. Lij cn N NOTES: 1. DETAIL NOT INTENDED TO SHOW SPATIAL RELATIONSHIP OF DEVICES. Ja REFERENCE FLOOR PLANS FOR ACTUAL LOCATIONS. > 0 Of FINISHED FLOOR Q 0 0 w INSTALLATION NOTES: N 1, THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX U' SHALL BE NOT LESS THEN 42" AND NOT GREATER THAN 48" A. F. F. z = 2. MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN o Z 5' OF THE EXIT DOORWAY OPENING ON EACH FLOOR. W CV C Q o CV CFIUNG MANUAL STATION MOUNTING DETAILS 3 TOP OF DEVICE SPEAKER/STROBE SCALE: NTS _ LQL:j o HORN/STROBE 6" MIN. DETAILS SHOWN ARE TYPICAL AND ALL STROBE DETAILS MAY NOT APPLY TO ALL JOBS. o o REF. LAYOUT DRAWINGS& B.O.M. SPEAKER HORN VISUAL DEVICE STROBE HORN/STROBE AUDIBLE DEVICE SPEAKER/STROBE HORN OR SPEAKER 96" MAX. TOP OF LENS 90" MIN. 80" MIN. Li__j TOP OF DEVICE BOTT. OF LENS Li— J (/) CD LLQ I L1J � O 3 00 Z DETECTORS WITHIN THIS AREA SHALL HOT BE LOCATED DIRECTLY IN THE AIR STREAM SDIFFUSERR OF SUPPLY AIR REGISTERS. 36' a' TUBE SUPPORT HOLE REQUIRED FOR BEND OR OTHER DUCTS MORE THAN 3 FT. WIDE. OBSTRUCTION J \ z TO PREVENT THE CLEAN AIR am- FROM BLOCKING THE SMOKE MOUNT SMOKE DETECTOR A TO THE DETECTOR WHEN THE MINIMUM OF 3' AWAY FROM BATH/ BACK BOX T U cn L O :2 FINISHED FLOOR SA & RA ARE WITHIN 15 FT. SHOWER/KITCHENL ROOM OPENINGS. NO' MOUNT DETECTOR 1.5 FT FROM CEILING LEVEL BETWEEN BACK BOX CEILING THE SA AND RA REGISTERS. 000 SMOKE DET. DUCT WIDTH AIRFLOW IR IFFUS SUADER PPLY r7, OR HEAT Dom, DIRECTION i w :�7 w INSTALLATION NOTES: 3 - O SMOKE DETECTOR MIN. DISTANCE — — INSERT RUBBER PLUG IN THIS END OF INLET TUBE 1. MOUNT VISUAL AND COMBINATION AUD0LE/VISUAL HORN BASE MODELS: + + + 4•SO. BOX 6-10 DUCT 6-10 DUCT APPLIANCES SUCH THAT THE ENTIRE LENS IS NOT LESS THAN HACK BOX LIGHT FIXTURE 1' - Q" NON -HORN BASE MODELS BOX 4•SO'BOX RETURN TUBE SLANT CUT FACE ORIENTED DOWNSTREAM OF AIRFLOW EQUIVALENT WIDTHS EQUIVALENT WIDTHS �(DO 80" AND NOT GREATER THAN 96" A.F.F. + + + MIN. DISTANCE 3.OR SHED/SLOPE CEILING (>1:8 PITCH) 10011, NOT INSERT RUBBER PLUG IN OUTLET TUBE) moo roo /8 2. MOUNT AUDIBLE APPLIANCES SUCH THAT THE TOP OF MIN. DISTANCE THE APPLIANCE IS AT A MINIMUM HEIGHT OF 90" A. F. F AND BACK BOX RETURN AIR SYSTEMS: INLET TUBE HOLES FACE UPSTREAM OF AIRFLOW SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2000 CFM 0.09 m s IN ( / ) BELOW THE FINISHED CEILING AT A MINIMUM HEIGHT 6 . APPLIAN ESNOTIFICATION 4' THE RETURN AIR DUCT OR PLENUM UPSTREAM OF ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR CONNECTIONS OR INDOOR a• so. eox BACK BOX DECONTAMINATION EQUIPMENT AND APPLIANCES. 3. IN AREAS WHERE MORE THEN TWO VISIBLE NOTIFICATION INNER LLJ APPLIANCES ARE IN ANY FIELD OF VIEW, THEY SHALL FLASH AUDIBLE OR VISIBLE ONLY AUDIBLE/VISIBLE DEVICES DEVICES WALL N0. COMMON SUPPLY AND RETURN AIR SYSTEMS: WHERE MULTIPLE AIR HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN c IN SYNCHRONIZATION. SHALL BE MOUNTED SUCH SHALL BE MOUNTED SUCH THAT THE MOUNTING HEIGHT THAT THE MOUNTING HEIGHT MEASURED TO THE BOTTOM SMOKE DET OR HEAT DET. 4• CAPACITY GREATER THAN 2000 CFM (0.9m3/s), THE RETURN AIR SYSTEM SHALL BE PROVIDED WITH SMOKE DETECTORS. 4. IN CORRIDOR APPLICATIONS: MEASURED TO THE BOTTOM OF THE STROBE LENS OF THE NAC APPLIANCE SHALL BE 80" ABOVE THE PULL STATION 0 RETURN AIR RISERS: N A. VISIBLE NOTIFICATION APPLIANCES SHALL BE LOCATED SHALL BE 80" ABOVE THE FINISHED FLOOR. FINISHED FLOOR. O 12• WHERE RETURN AIR RISERS SERVE TWO OR MORE STORES AND SERVE ANY PORTION OF A RETURN AIR SYSTEM HAVING A DESIGN CAPACITY GREATER THAN 15000 CFM (7.1m3/s), SMOKE DETECTORS SHALL BE INSTALLED AT EACH STOREY. SUCH SMOKE DETECTORS U O� WITHIN 15' FROM THE END OF A CORRIDOR WITH SEPARATION O SMOKE DET. (ONLY) if �/� Li Ln NOT GREATER THAN 100' BETWEEN APPLIANCES. B. WALL—MOUNTED VISIBLE NOTIFICATION APPLIANCES SHALL a8• BOX FLAT CEILING SHALL BE LOCATED UPSTREAM OF THE CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR DUCTS OR PLENUMS SUPPLY AIR SMOKE DETECTORS: V / si 00 Q BE PERMITTED IN EITHER THE END WALL OR THE SIDE WALL I IF INSTALLED, SUPPLY AIR SMOKE DETECTORS SHALL BE MOUNTED IN THE DUCT DOWNSTREAM OF BOTH THE FAN AND THE FILTERS. Q OF THE CORRIDOR. NOT ADDITIONAL SMOKE DETECTORS IN THE SUPPLY AIR SYSTEM ARE NOT REQUIRED WHERE THE AIR PASSES THROUGH OTHER SMOKE C. IF THERE IS AN INTERRUPTION OF THE CONCENTRATED COMPARTMENTS. VIEWING PATH, SUCH AS A FIRE DOOR, AN ELEVATION CHANGE, SMOKE DAMPERS THAT ARE PART OF A SMOKE BARRIER SHALL BE INSTALLED IN THE PLANE OF THE FIRE PARTITION AND NOT AFTER JW OR ANY OTHER OBSTRUCTION, THE AREA SHALL BE TREATED SMOKE & HEAT DETECTOR PLACEMENT THE FIRST AIR DUCT INLET OR OUTLET, WHICHEVER IS CLOSER TO THE SMOKE BARRIER. IF THE SMOKE DAMPER IS CONTROLLED BY Q = AS A SEPARATE CORRIDOR. GENERAL NOTES: AIR SYSTEM SMOKE DETECTOR IT SHALL BE LOCATED UPSTREAM OF THE SMOKE DAMPER BUT AFTER ANY INLET OR OUTLET IN W A. DO NOT APPLY POWER TO ANY DEVICE UNTIL AUTHORIZED BY A HONEYWELL REPRESENTATIVE. THAT DUCT. 0__1 5. SLEEPING AREAS: B. SEE FLOOR PLANS FOR ALL DEVICE LOCATIONS, DEVICE COUNTS, AND DEVICE ADDRESSES. W O A. FOR ROOMS WITH A LINEAR DIMENSION GREATER THAN 16', C. FOLLOW DEVICE INSTALLATION INSTRUCTIONS INCLUDED WITH DEVICES. WHERE IN -DUCT SMOKE DETECTORS ARE INSTALLED IN CONCEALED LOCATIONS MORE THAN 10ft ABOVE THE FINISHED FLOOR, OR IN ARRANGEMENTS WHERE THE DETECTOR'S ALARM LIGHT IS NOT READILY VISIBLE TO RESPONDING PERSONNEL, THE DETECTOR SHALL z THE VISIBLE NOTIFICATION APPLIANCES SHALL BE LOCATED D. DETECTOR GUIDELINES: NO SMOKE DETECTORS ALLOWED IN GARAGES. BE PROVIDED WITH REMORE ALARM INDICATORS TO BE INSTALLED IN A READILY ACCESSIBLE LOCATION AND SHALL BE CLEARLY WITHIN 16' OF THE PILLOW. NO SMOKE DETECTORS ALLOWED IN UNFINISHED ATTICS. LABELED TO INDICATE BOTH THEIR FUNCTION AND THE AIR HANDLING UNIT(S) ASSOCIATED WITH EACH DETECTOR. (EXCEPTION: B. IF THE DISTANCE FORM THE TOP OF THE STROBE LENS IS NO SMOKE DETECTORS ALLOWED IN AREAS WITH >100'F OR <40'F. WHERE THE SPECIFIC DETECTOR IN ALARM IS INDICATED AT THE CONTROL UNIT) EQUAL TO OR GREATER THEN 24" FROM THE CEILING THEN ION SMOKE DETECTORS MUST BE > 20' FROM COOKING APPLIANCES. DETECTORSO SMOKE ALLOWED RCOOKINGOM (PHOTHE STROBE SHALL BE 110cd. IF THE DISTANCE FROM THE NO SMT DOOR TOKI CHEN ORS OWER/TUB ROOM O EDETECTORS WIT IN3'FROM TOP OF THE STROBE LENS IS LESS THEN 24" TO THE CEILING NO SMOKE DETECTORS WITHIN 3' HORIZONTAL FROM CEILING FAN BLADE TIP. THE STROBE SHALL BE 177cd. SMOKE DETECTORS ARE REQUIRED IN BASEMENTS ON CEILING ADJACENT TO STAIRWELLS. MOUNTING HEIGHTS FOR WALL MOUNTED NOTIF APPLIANCES 4 ADDITIONAL DEVICE MOUNTING DETAILS 5 DUCT DETECTOR MOUNTING DETAILS 6 SCALE: NTS SCALE: NTS SCALE: NTS JOB # 1311C FA -08 8 OF 8