Loading...
Energy Code Worksheet2018 Washington State Energy Code — Residential Energv Code Compliance for All Climate Zones in These requirements apply to all IRC building types, including detached one- and two-family dwellings and multiple single-family dwellings (townhouses). I� Project Information Contact Information 1437 ---- - Instructions: This single-family project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. Authorized Representative I Date ', _ All Climate Zones (Table R402.1.1)_ R•Value a 1.1—Factor' Fenestration U Factor " - - _ n/a 0.30 Skylight U -Factor b _ n/a 0.50 jGlazed Fenestration SHGC bje n/a n/a Ceiling a --- 49 i - --- 0.026 Wood Frame Wall gih _-- 21 int _-- _ 0.056 Floor _ 30 0.029 _ _ Below Grade Wall c•h 10/15/21 int +TB 0.042 Slab ','R -Value & Depth 10, 2 ft n/a R -values are minimums. U -factors and SHGC are maximums. When insulation is installed in a cavity that is less the label or design thickness of the insulation, the compressed R -value of the insulation from Appendix kathan Table A101.4 shall not be less than the R -value specified in the table, b The fenestration U -factor column exdudes skylights r__ 10/15/21 +STB" means R-10 continuous insulation on the exterior of the wall, or R 15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "STVmeans R-5 thermal break between floor slab and basement wall. d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. Ffor single rafter- orjoist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends over the top plate of the exterior wall R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the regwred perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of ICC 400. Int. (intermediate framing) denotes framing and insulation as described in Section 4103.2.2 including standard h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 _ Insulation. Prescriptive Pafh —Single Family 2018 Washington Stale Energy Code -R 2018 Washington State Energy Code - Residential Each dwelling unit In a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) to achieve the following minimum number of credits. To claim this credit, the building permit drawings shall specify the option selected and the maximum tested building air leakage, and show the qualifying ventilation system and its control sequence of operation. 1. Small Dwelling Unit: 3 credits Dwelling units less than 1,500 sf in conditioned floor area with less than 300 sf of fenestration area. Additions to existing building that are greater than 500 sf of heated floor area but less than 1,500 sf. 2. Medium Dwelling Unit: 6 credits All dwelling units that are not included in #1 or #3 3. Large Dwelling Unit; 7 credits Dwelling units exceeding 5,000 sf of conditioned floor area 4. Additions less than 500 square feet; 1.5 credits All other additions shall meet 1-3 above Before selecting your credits on this Summary table, review the details in Table 406.3 (Single Family), on page 4. Summary of Table R406.2 Heating Options 1 Fuel Normalization Descriptions Combustion heating minimum NAECAI Credits - select ONE heating option 0.0 ❑ User Notes 2 Heat pump` Electric resistance heat only - furnace or zonal 1.0 ---. 1.0 ❑ ❑ 4 DHP with zonal electric resistance per option 3A 0.5 ❑ _ 5 All other heating systems -1.0 ❑ Energy Options _ Energy Credit Option Descriptions Credits -select ONE energy option from each Cate orya j 1.1 Efficient Building Envelope 0.5 ❑ 1.2 Efficient Building_ Envelope 1.0 ❑ 1.3 1.4 Efficient Building Envelope Efficient Building Envelope 0.5 1.0 ❑ ❑ 1.5 Efficient Building Envelope 2.0 ❑ 1.6 Efficient Building Envelope 3.0 ❑ 1.7 Efficient Building Envelope 0.5 Ll 2.1 Air Leakage Control and Efficient Ventilation 0.5 ❑ 2.2 Air Leakage Control and Efficient Ventilation 1.0 El2.3 Air Leakage Control and Efficient Ventilation 1.5 ❑ 2.4 Air Leakage Control and Efficient Ventilation 2.0 ❑ High Efficiency HVAC 1.0 _ 3.2 High Efficiency HVAC 1.0 ❑ 3.3a _ High Efficiency HVAC 1.5 ❑ _4_, 3.4 High Efficiency HVAC 1.5 ❑ 3.5 High Efficiency HVAC 1.5 __ El 3.6' High Efficiency HVAC 2.0 ❑ 4.1 High Efficiency HVAC Distribution System 0.5 ❑ 4.2 High Efficiency HVAC Distribution System 1.0 ❑ Prescriptive Path -Single Family 2018 Washington State Energy Code -R 2018 Washington State Energy Code — Residential Summary of Table R406.2 (cont.) Energy Options Energy Credit Option Descriptions (cont.) Credits - select ONE energy option from each categor d User Notes 5.11 Efficient Water Heating 0.5 ❑ 5.2 Water Heating 0.5 ❑ _ 53 _Efficient Efficient Water Heating 1.0 ❑ 5.4 Efficient Water Heating 1.5 ❑ 5.5 Efficient Water Heating 2.0 ❑ 5.6 Water Heating 2.5 ❑ 6. le ,Efficient Renewable Electric Energy credits max) 1.0 j 7.1 1(3 Appliance Package 0.5 ❑ _ Total Credits 3.O _ CLEAR FORM a. An alternative heating source sized at a maximum of 0.5 W/sf (equivalent) of heated floor area or 500 W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category 5. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See the complete Table R406.2 for all requirements and option descriptions. Pleese print only pages 1. through3 of this worksheet forsUbmission.to your building official. Presaiplive Palh —Single Fatuity 2018 Washington State Energy Code -R healing system sizing calculator Is based on the Prescriptive Requirentenls of the 2018 Washington State Energy Code (WSEC) and ACCA gals J and S. This tool will calculate heating loads only. ACCA procedures For sizing cooling syslents should be used to determine cooling loads. complete the green drop -downs and boxes that are applicable to your project. As you make selections in the drop -downs for each section, some vrill be calculated for you. If you do not see the selection you need In the drop-dovrn options, please contact the WSU Energy Program at code@energy.vrsu.edu or (360) 956-2042 for assistance. (1T) 50 spanaway To see detailed instructions Tor each section, place your cursor on the word "Instructions" Design Temperature Envelope Heat Load 8,885 8(u /Hour FI ore t. Sumo/UAx eT msunafons -- Design Temperature Difference (1T) 50 spanaway Blu /Hour °""""'� Airleakage +envelope heat loss ,� ��� �- „�.N.. BuIlding and Duct Heaf Load 15,093 Btu/Hour Ducts In unconditioned space: sum o/building heat loss x JT = rrMoor(r0 degrees) -Outdoor Desyn Temp Area of Building Maximum Heat Equipment Output 18,866 Btu /Hour Building and duct heat loss x 1.401or torted air furnace Conditlortod Floor Area msuocr°"s Conditioned Floor Area (sq ft) 1.-03T: Average Ceiling Height Conditioned Volume mso-�cu°ns Average Ceiling Height ((t) ..... 8.0 11,496 Glazing and Door'sy U -Factor — X Area — UA msuucuons ( - `� u-aaa 0.280 182 � 50.96 Skylights U -Factor X Area — UA mstrucu°ns 0.50 0 --- Insulation Attic U -Factor X Area = UA ipso, coons '���Ra9 �v�. B.U26 792 20.59 Single Raker or Joist Vaulted Callings U -Factor X Area UA inso-ocuons � SIttt R -varve � No selection � --- Above Grade Walis fees Fie r/ WFactor X Area UA msuummns 0.056 � 1.542 86.35 R -n mrermmwre Floors U -Factor X Area UA R-38 0.025 19.80 .79z Below Grade Walls � ee Fra .e r) _ U -Factor X Area UA msuncuons Select R-vawe �. ' No selection � __ Slab Below Grade rsea Flsp a r! _ F -Factor X Le� UA mso-,mu°ns selxt conemml� �..._ �.. No selection --- Slab on Grade f Fmere. �) _ F -Factor X Len th UA msuuouons '��smx�R-varve y No selection --- Location of Ducts Iretrnalons -- — -= `y' _- Duct Leakage Coefficient trnamo d s�ce 1.00 Sum of UA 177.70 Envelope Heat Load 8,885 8(u /Hour FI ore t. Sumo/UAx eT AIr Leakage Heat Load 6,208 Btu /Hour Volumex O.6x eTx O.o18 anosec.aae Building Design Heaf Load 15,093 Blu /Hour °""""'� Airleakage +envelope heat loss ,� ��� �- „�.N.. BuIlding and Duct Heaf Load 15,093 Btu/Hour Ducts In unconditioned space: sum o/building heat loss x 1.10 Ducts in conditioned space: sum olbuilding heat lossx 1 Maximum Heat Equipment Output 18,866 Btu /Hour Building and duct heat loss x 1.401or torted air furnace Buildino and duct heat loss x 1.25 for heat Dump (oJ/of/I3) Window, Skylight and Door Schedule Project Information 1437 Ref. U -factor Exempt Swinging Door (24 sq. ft. max.) Exempt Glazed Fenestration (15 sq, it, max.) Vertical Fenestration (Windows and doors) Component Contact Infomation Width Height Area UA 20.0 4.00 0.0 0.00 Area UA 5.0 1.40 24.0 6.72 24.0 6.72 9.0 2.52 8.0 2.24 16.0 4.48 20.0 5.60 4.0 1.12 16.0 4.48 16.0 4.48 20.0 4.00 0.0 0.00 0.0 0.00 0.0 0.00 Ref. U -factor Exempt Swinging Door (24 sq. ft. max.) Exempt Glazed Fenestration (15 sq, it, max.) Vertical Fenestration (Windows and doors) Component Contact Infomation Width Height Area UA 20.0 4.00 0.0 0.00 Area UA 5.0 1.40 24.0 6.72 24.0 6.72 9.0 2.52 8.0 2.24 16.0 4.48 20.0 5.60 4.0 1.12 16.0 4.48 16.0 4.48 20.0 4.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 Sum of Vertical Fenestration Area and UA Vertical Fenestration Area Weighted U = UA/Area Overhead Glazing (Skylights) Component Width Height Qt. Feet Inch Feet Inch Sum o/Overhead Glazing Area and UA Overhead Glazing Area Weighted U = UA/Area Total Sum Of Fenestration AYea and UA (far heating system sizing calculations) 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.01 0.00 162.0 43.76 0.27 Area UA 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.0 0.00 0.00 182.0 47.76