FA Yelm Community Center 10-13-23FIRE ALARM SYSTEMDATE:YELM COMMUNITY CENTER
FIRE ALARM COMMUNICATOR
301 2ND STREET S.E.
YELM, WA 98597
REVISIONS:
_______________________________________________________
_______________________________________________________
_______________________________________________________
_______________________________________________________
_______________________________________________________10-13-23SCALE:DRAWN BY:NLHPROJECT NUMBER:SHEET:global4security.com 360.693.1900 VANCOUVER, WAYELMCOMMCNTRRev#0 - ORIGINAL SUBMITTAL
FA-11 OF 1AS SHOWNDESIGNED & REVIEWED BY:NICHOLAS E.H. (NICK HAGE)NICET 153213, LEVEL: IIIFIRE ALARM SYSTEMSPART NUMBERFIRE ALARM LEGENDQTY.FIRE ALARM CONTROL PANEL (EXISTING)GAMEWELLFACP7100-1D1.DO NOT START INSTALLATION BEFORE SYSTEM IS APPROVED BY THE AHJ.2.INSTALLATION TO BE DONE PER NFPA 72 (NATIONAL FIRE ALARM & SIGNALING CODE, 2019)AND ALL OTHER APPLICABLE CODES & STANDARDS.3.VERIFY EXACT LOCATIONS AND DIMENSIONS OF PANELS AND DEVICES BEFORE ROUGH IN.4.VERIFY ALL WIRING CONNECTIONS, BACKBOXES, CONDUITS, & CABLE TYPES BEFORE INSTALLATION.5.DO NOT RUN SLC AND VOICE CABLES IN SAME CONDUIT. MAINTAIN PROPER SEPARATION.IMPORTANT NOTES1.THIS IS AN ADDITION TO AN EXISTING FIRE ALARM SYSTEM. WE WILL BE ADDING A FIRE ALARMCOMMUNICATOR TO THE EXISTING FIRE ALARM PANEL. ALL EXISTING DEVICES TO REMAIN, NOOTHER NEW DEVICES.2.INSTALL NEW FIRE ALARM COMMUNICATOR (STARLINK) ABOVE EXISTING FACP. TIE TO AUXPOWER AND DACT/TELCO CONNECTIONS ON FACP. VERIFY SIGNAL STRENGTH PRIOR TO ROUGHIN (MOUNT WITHIN TEN FEET OF FACP IN SAME ROOM). PROVIDE TWO NEW 12V-10AHBATTERIES, MINIMUM.3.TEST ENTIRE SYSTEM PRIOR TO REQUESTING FINAL INSPECTION. FURNISH RECORD OFCOMPLETION AND RELATED DOCUMENTS IN FIRE DOCUMENTS CABINET NEXT TO FACP.SCOPE OF WORK - ADD NEW FIRE COMMUNICATORSYMBOLDESCRIPTIONMANUFACTURERHORN STROBESYSTEM SENSORFIRE CELLULAR MODULE COMMUNICATORSTARLINKCELLSLE-MAXVI-FIRE1 NEWTRANSMIT ALARM TO SUPERVISING STATIONDISPLAY AT FACP & REMOTE ANNUNCIATORTRANSMIT SUPERVISORY TO SUPERVISING STATIONTRANSMIT TROUBLE TO SUPERVISING STATIONSOUNDS EVACUATION SIGNALC. TROUBLETO RECEIVE SEPARATE & DISTINCTSIGNALS AS FOLLOWS:CENTRAL STATION ALARM SERVICENOTES:B. SUPERVISORYA. ALARMFIRE ALARMSEQUENCEOFOPERATIONSACTIVATION OF SPRINKLER VALVE TAMPERACTIVATION OF SMOKE DETECTORACTIVATION OF SPRINKLER WATER FLOWACTIVATION OF MANUAL PULL STATION(EXISTING)ACTIVATION OF HEAT DETECTORF(EXISTING)GAMEWELLPULL STATION (ADDRESSABLE)(EXISTING)GAMEWELLSMOKE DETECTOR (ADDRESSABLE)S(EXISTING)GAMEWELLHEAT DETECTOR (ADDRESSABLE)H[BATTERY](2x) 12V-10AHBACK UP BATTERIESZONE16 AWG, 2 CONDUCTOR, FPLP14 AWG, 2 CONDUCTOR, FPLP - REDABCABLE LEGEND*16 AWG, 4 CONDUCTOR, FPLPC*VERIFY ALL CABLE TYPES IN PRODUCT MANUALS / SPECS 14 AWG, 2 CONDUCTOR, FPLP - WHITEDNACANNUNAUXNKEY PLAN - 301 2ND STREET S.E.SCALE: NTSYELMCOMMUNITYCENTERBLDG2ND STREET SE
MCKENZIE AVEFACPCELLSE MOSMAN AVEFIRE ALARM SYSTEM - RISER DIAGRAM2x 12V-10AHBATTERIESGAMEWELLTO 120VACEXISTINGSERVER ROOMFIRE PANELSLCEXISTFIRECELLULARABOVE FACPDIALEREXISTINGTOTAL ALARMCURRENT, A10246.5440.2732.2538.3046.9200.375CURRENT, AALARMSUPERV.CURRENT, AQTYDESCRIPTIONMODULETOTAL SUPERVISORY CURRENTTOTAL ALARM AND SUPERVISORY CAPACITYTOTAL AMP-HOURS REQUIRED (AFTER 20% DERATING FACTOR)TOTAL SUPERVISORY CAPACITYTOTAL STANDBY HOURS TOTAL ALARM CAPACITYALARM PERIOD IN MINUTESTOTAL ALARM CURRENTTOTAL SUP.CURRENT, ANOTIFICATION APPLIANCES CIRCUITSPROVIDE TWO (2) 12V-10AH BATTERIES, MINIMUMBATTERY CALCULATIONS FOR FACPTOTAL CURRENT CIRCUIT #1 - EXISTING NOTIFICATION0.1700000.1700000.1250007100-1D1GAMEWELL FCI FIRE ALARM CONTROL PANEL0.1250000.0045000.000300ASD-PL211GAMEWELL FCI ADDRESSABLE SMOKE DETECTORTOTAL CURRENT CIRCUIT #2 - EXISTING NOTIFICATION0.0495000.003300EXISTNAC#10.0007500.000750AMM-4SF2GAMEWELL FCI ADDRESSABLE MONITOR MODULE0.0015000.0015000.660TO EXISTING HORN-STROBESEXISTNAC#2TO EXISTING HORN-STROBES0.0045000.000300ATD-L2F20GAMEWELL FCI ADDRESSABLE HEAT DETECTOR0.0900000.0060000.3250000.085000SLE-MAXVI-FIRE1STARLINK CELLULAR FIRE COMMUNICATOR MODULE0.3250000.0850000.880TO EXISTING SLC DEVICESFIREALARMNEXT TO FACPDOCUMENTS(NEW)0.0003750.000375FCI-MS-75GAMEWELL FCI ADDRESSABLE PULL STATION0.0018750.0018750.0750000.050000LCD-71001GAMEWELL FCI FIRE REMOTE ANNUNCIATOR0.0750000.050000C,CTROUBLE CONDITION AT PANELLOSS OF AC POWER