Tahoma Terra-II - Building G - Electrical SetJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-001-003.dwg
8/11/2023 11:27:52 AME-001ELECTRICAL LEGEND & ABBREVIATIONS ABBREVIATIONS(SOME ABBREVIATIONS MAY NOT BE USED ON DRAWINGS)ABBREVIATIONDESCRIPTIONABBREVIATIONDESCRIPTIONA or AMPAMPERESMCM, KCMTHOUSAND CIRCULAR MILSACALTERNATING CURRENTMDFMAIN DISTRIBUTION FRAMEA/CAIR CONDITIONINGMECHMECHANICALAICAMPERE INTERRUPTING CAPACITYMINMINIMUMALALUMINUMMLOMAIN LUGS ONLYARCHARCHITECTURALMOP, MOCPMAXIMUM OVERCURRENT PROTECTIONATSAUTOMATIC TRANSFER SWITCHNICNOT IN CONTRACTAWGAMERICAN WIRE GAUGENTSNOT TO SCALEBKRBREAKEROCON CENTERBLDGBUILDINGPAPUBLIC ADDRESSCCONDUITPBPULLBOXC.O.CONDUIT ONLYØ or PHPHASECBCIRCUIT BREAKERPNLPANELCCTVCLOSED CIRCUIT TELEVISIONPRPAIRCFMCUBIC FEET PER MINUTEPRIPRIMARYCKTCIRCUITPVCPOLYVINYL CHLORIDECLGCEILINGRECPTRECEPTACLECONCCONCRETEREQREQUIREDCTCURRENT TRANSFORMERRMROOMCUCOPPERSHTSHEETCWCOLD WATERSPSINGLE POLEDCDIRECT CURRENTSPDSURGE PROTECTIVE DEVICEDIADIAMETERSPDTSINGLE POLE, DOUBLE THROWDIVDIVISIONSPSTSINGLE POLE, SINGLE THROWDPDTDOUBLE POLE, DOUBLE THROWSWSWITCHDPSTDOUBLE POLE, SINGLE THROWSWBDSWITCHBOARDDWGDRAWINGTELTELEPHONEEGCEQUIPMENT GROUND CONDUCTORTVTELEVISIONELECELECTRICTTBTELECOMMUNICATIONS TERMINAL BOARDEMTELECTRICAL METALLIC TUBINGTYPTYPICALEXST, (E)EXISTINGULUNDERWRITERS LABORATORYEVELECTRIC VEHICLEUFUNDERFLOORFAFIRE ALARMUGUNDERGROUNDFCFOOTCANDLEVVOLTSFLAFULL LOAD AMPSVAVOLT AMPERESGFCIGROUND FAULT CIRCUIT INTERRUPTERVACVOLTS ALTERNATING CURRENTGNDGROUNDVARREACTIVE VOLT AMPERESHPHORSEPOWERWWATTSIDFINTERMEDIATE DISTRIBUTION FRAMEWPWEATHERPROOFJ-BOXJUNCTION BOX/WWITHKVKILOVOLTSW/OWITHOUTKVAKILOVOLT AMPERESXFERTRANSFERKWKILOWATTSXFMRTRANSFORMERLTLIGHTLTGLIGHTINGMAXMAXIMUMMCAMINIMUM CIRCUIT AMPSMCBMAIN CIRCUIT BREAKERMCCMOTOR CONTROL CENTERCOUNTER HEIGHT (*) CASEWORK OUTLETS SWITCHES AND DIMMERS RECEPTACLES THERMOSTATS CLOCKSOCCUPANCY SENSORSDATA (COMPUTER) TV (TELEVISION) TV WALL MOUNTED SPEAKERS CLOCK/SPEAKER FIRE ALARM MANUAL STATIONS SIGNALING DEVICES REMOTE ANNUNCIATOR SECURITY KEY PAD CARD READER CCTV CCTV POLE MOUNTED +3 INCHES ABOVE SPLASH AS DIRECTED 90 INCHES 48 INCHES 18 INCHES48 INCHES 18 INCHES 18 INCHES 90 INCHES, GYM OR COMMONS - 120" 90 INCHES CENTER OF TV BRACKET 16 FEET 48 INCHES 48 INCHES TO TOP WITHIN 6 INCHES OF GRAPHIC PLAQUES REMOTE ALARM LIGHTS 80 INCHES TO BOTTOM 60 INCHES TO BOTTOM 60 INCHES TO BOTTOM 80 INCHES TO BOTTOM 48 INCHES TO TOPWALL PHONE 48 INCHES(MEASURE TO CENTER OF BOX, UNLESS OTHERWISE INDICATED)OUTLET MOUNTING HEIGHTS CAMERA MOUNT 12 FEET MAXIMUMPROJECTORABOVE WHITEBOARD, TO BE COORDINATEDDISTRIBUTIONPANELBOARD - SURFACEPANELBOARD - EXISTING (SURFACE PANEL SHOWN)SWITCHBOARD OR MCC (DRAWN TO SCALE)MAGNETIC MOTOR STARTER OR OTHER MOTORCONTROL DEVICE AS SCHEDULEDDRY TYPE TRANSFORMERWIRING CONCEALED IN CEILING OR WALLWIRING CONCEALED UNDERGROUND OR BELOW FLOORWIRING EXPOSEDWIRING HOMERUNCONDUIT UP, DOWNFLEXIBLE WIRING CONNECTIONDISCONNECT SWITCHFUSED DISCONNECT SWITCHGENERALSCHEDULED EQUIPMENT CONNECTION (INCLUDEALL WIRING, DISCONNECTING MEANS, CONTROLAND OTHER REQUIREMENTS SCHEDULED)#AA - SHEET WHERE DETAIL SHOWN# - IDENTIFYING NUMBERDETAIL SYMBOL:#REVISION CALLOUT#FLAG NOTE#SCHEDULED CONDUIT CALLOUTLIGHTING## - IDENTIFYING NUMBERBUBBLE NOTE TAG SYMBOL:LUMINAIRE (TO SCALE ON DRAWINGS)EMERGENCY FIXTURE - TWIN HEADNEMERGENCY LIGHTING UNITCOMBINATION EXIT SIGN AND TWIN HEADa,bINDICATES CONTROL ZONEPOLE MOUNTED LIGHTINDICATES LUMINAIRE TYPELIGHTING CONTROLDIGITAL SWITCH STATIONSINGLE POLE TOGGLE SWITCHSWITCH SUBSCRIPTS:MLVLVM4D32KEPDIMMERMANUAL MOTOR STARTERLOW VOLTAGE MASTERKEY OPERATEDEXPLOSION PROOFLOW VOLTAGEFOUR WAYTHREE WAYDOUBLE POLEMCMOMENTARY CONTACTPSWITCH W/PILOT LIGHTTTIMERWPWEATHERPROOFW/OVERLOADSa, b, cMULTIGANG SWITCH STATIONPHOTOCELL, EXTERIOROSOCCUPANCY SENSORDAYLIGHT SENSOR - DUAL ZONEPOWERCMWWPREFCOPDFIGDUPLEX RECEPTACLE (NEMA 5-20R)SUBSCRIPT: COPIERCEILINGWEATHERPROOFMICROWAVEREFRIGERATORCHILLED WATER FOUNTAINISOLATED GROUNDDWDISHWASHERPWALL MOUNT PROJECTOR TVVIDEO DISPLAY OUTLET. REFER TOARCHITECTURAL DETAILS FOR MOUNTING HEIGHTALL RECEPTACLES ARE TAMPER RESISTANTFOURPLEX RECEPTACLE (NEMA 5-20R)DUPLEX RECEPTACLE, 1/2 CONTROLLED BYOCCUPANCY SENSOR OR TIME SWITCHASTERISK INDICATES COUNTER HEIGHT OUTLET(DUPLEX RECEPTACLE SHOWN)RANGE RECEPTACLE (NEMA 14-50R)DRYER RECEPTACLE (NEMA 14-30R)SPECIAL PURPOSE OUTLET (AS NOTED)GFCI DUPLEX RECEPTACLE (NEMA 5-20R)DISCONNECT SWITCHFUSED DISCONNECT SWITCHJUNCTION BOXMOTOR CONNECTIONWCHDWHSUBSCRIPT: EQUIPMENT CONNECTIONWATER COOLERHAND DRYERWATER HEATERCOMMUNICATIONS# OUTLET W/ RJ45 DATA JACK W/ CAT 6 CABLE TO SERVER# INDICATES QUANTITY OF DATA JACKS IF MORE THAN ONE.#CAT 5 CABLE AND COAX TO MEDIA PANELOUTLET WITH RJ45 DATA JACK AND (1) F CONNECTOR WITH# INDICATES QUANTITY OF DATA JACKS IF MORE THAN ONEWIRELESS ACCESS POINT STATION WITH (1) CAT 6A CABLETERMINATED IN A BISCUIT STYLE ENCLOSURE WITH (1)CAT 6A OUTLET, INSTALL WAP FURNISHED BY OWNERAPINTERCOM / CLOCKCOMBINATION DIGITAL CLOCK & SPEAKERINTERCOM SPEAKERINTERCOM CALL SWITCHINTRUSION / ACCESS CONTROLKEY PADCARD READERELECTRIC STRIKEXXFIRE ALARMFAPFIRE ALARM CONTROL PANELFAAFIRE ALARM ANNUNCIATORFMANUAL STATIONFCHORN [SPEAKER] "C" INDICATES CEILING MOUNTFC"C" INDICATES CEILING MOUNTHORN [SPEAKER] WITH VISUAL SIGNAL (STROBE)HHEAT DETECTORSMOKE DETECTORLIGHT FIXTURE CALLOUTSF1aPNL-13EMPANELBOARD AND CIRCUIT NUMBERCONTROL ZONE IDFIXTURE TYPEEMERGENCY EGRESS FIXTURE(HATCH & CALLOUT SHOWN)FIXTURE SYMBOLUL924 EMERGENCY TRANSFER RELAYMPCRESKPLINE TYPESEXISTING WORKNEW WORKdz1DAYLIGHT ZONE IDdz1: PRIMARYdz2: SECONDARYERLIGHT FIXTURE ON NIGHT LIGHT CIRCUITPROVIDE UNSWITCHED HOT CONDUCTORN(N) = NIGHT LIGHT CIRCUIT(CONTINUOUSLY ON)SPLIT WIRED FOURPLEX (1) DUPLEX RECEPTACLEUNSWITCHED, (1) DUPLEX RECEPTACLE CONTROLLEDBY OCCUPANCY SENSOR OR TIME SWITCHRECESSED FLOOR BOX FOR POWER & SIGNAL(DUPLEX AND DATA DROP SHOWN)MEDIA PANEL WITH INTEGRATED POWER.(1) CAT 6 CABLE AND (1) COAX TO DEMARC AT EXTERIOR OFBUILDING.MAGNETIC CONTACTSSYMBOL FOR SECURITY ALARM CONTROL PANEL
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-001-003.dwg
8/11/2023 11:27:52 AME-002ELECTRICAL NOTESENERGY CODE NOTES:THE FOLLOWING NOTES REFERENCE APPLICABLE SECTIONS OF THEWASHINGTON STATE ENERGY CODE AS IT APPLIES TO THIS PROJECT.LIGHTINGLIGHTING SYSTEM CONTROLS (C405.2): MANDATORY.EXCEPTION: SECURITY AREAS REQUIRING CONTINUOUS LIGHTING;EMERGENCY AREAS REQUIRING CONTINUOUS LIGHTING (EXCLUDESBUILDING EGRESS ILLUMINATION GREATER THAN 0.02 WATTS/SF),OCCUPANCY SENSORS (C405.2.1): REQUIRED FOR MULTI-PURPOSE, LOUNGE,LUNCH, BREAK, PRIVATE OFFICE, STORAGE, RESTROOM, JANITOR, AND OTHERROOMS 300SF OR LESS.OCCUPANCY SENSOR MANUAL ON (C405.2.1.1): REQUIRED.EXCEPTION: PUBLIC CORRIDORS; STAIRS; RESTROOMS; MAIN ENTRIES;MAIN LOBBIES; WHERE MANUAL ON WOULD BE UNSAFE.TIME SWITCH (C405.2.2): REQUIRED WHERE OCCUPANCY SENSOR OR DIGITALWALL BOX TIMER (C405.2.6) IS NOT PROVIDED.TIME SWITCH LIGHT REDUCTION (C405.2.2.1 &C405.2.2.2): MANUAL CONTROLSARE REQUIRED TO PROVIDE UNIFORM 50% MINIMUM ILLUMINATION REDUCTIONFOR AREAS WITH TIME SWITCH CONTROL.EXCEPTION: SPACES WITH (1) LIGHT FIXTURE RATED LESS THAN 100WATTS; SPACES LESS THAN 0.6 WATTS/SF; CORRIDORS, EQUIPMENTROOMS, PUBLIC LOBBIES, ELECTRIC ROOMS, AND MECHANICAL ROOMS.EXCEPTION: IN DAYLIGHT ZONES WITH DAYLIGHT RESPONSIVE CONTROLS.DAYLIGHT RESPONSIVE (C405.2.4): AUTOMATIC DIMMING REQUIRED FORDAYLIGHT ZONES WITH MORE THAN (2) LIGHT FIXTURES.EXCEPTION: PATIENT CARE SPACES; DWELLING UNITS; SLEEPING UNITS;DAYLIGHT ZONES ON 1ST FLOOR ABOVE GRADE IN A-2.EXTERIOR LIGHTINGAUTOMATIC LIGHTING CONTROLS SHALL BE CONFIGURED TO TURN OFFLIGHTS AS A FUNCTION OF DAYLIGHT USING PHOTO SENSOR.AREA LIGHTING CONTROLS GENERAL REQUIREMENT (C405.2.8):MAXIMUM CIRCUIT RATING FOR SINGLE SWITCH OR AUTOMATIC CONTROL IS 20AMPERES. CIRCUIT BREAKERS MAY NOT BE USED AS SOLE MEANS OFCONTROL.ELECTRICAL POWER SYSTEMSAUTOMATIC CONTROL OF 120 VOLT 15 AND 20 AMPERE RECEPTACLE OUTLETS(C405.2.10): REQUIRED FOR AT LEAST 50% OF ALL RECEPTACLES IN PRIVATEOFFICES, OPEN OFFICES, CONFERENCE ROOMS, PRINTING AND/OR COPYROOMS, BREAK ROOMS, WORK STATIONS. WHERE CONTROLLEDRECEPTACLES ARE REQUIRED, THEY SHALL BE LOCATED WITHIN 6 FEET OF ANUNCONTROLLED RECEPTACLE IN ROOMS LARGER THAN 200 SF.APPROVED CONTROL DEVICES: OCCUPANCY SENSORSYSTEM COMMISSIONINGMANDATORY GENERAL REQUIREMENTS (C408.1): COMMISSIONING LED BY ACERTIFIED COMMISSIONING PROFESSIONAL IS REQUIRED FOR ELECTRICALPOWER AND LIGHTING SYSTEMS (C405) AND FOR ENERGY METERING (C409).UNDER DEFINITIONS, THE ENGINEER OF RECORD FOR THE PROJECT MAY BECONSIDERED THE CERTIFIED COMMISSIONING PROFESSIONAL IF QUALIFIED TOPERFORM COMMISSIONING SERVICES FOR THE ENTIRE COMMISSIONINGPROCESS.GENERAL ELECTRICAL NOTES:1. BRANCH CIRCUIT NOTES:A.ONLY BRANCH CIRCUIT HOMERUNS INDICATE CONDUCTOR COUNT IF MORE THAN TWO WIRE CIRCUIT PLUS GROUND. CONTINUE WIRE COUNT TO OUTLETS AS REQUIRED TO PROVIDE INDICATED PHASE, NEUTRAL, AND EQUIPMENT GROUND CONDUCTORS PER CODE BASED ON CIRCUIT DESIGNATIONS INDICATED.B.FOR SWITCHED OUTLETS, PROVIDE ADDITIONAL CONDUCTOR COUNT REQUIRED FOR SWITCH LEGS TO ACCOMMODATE SWITCHCONTROL INDICATED. MAINTAIN UNSWITCHED LEG IN LIGHTINGBRANCH CIRCUITS TO EXIT, EMERGENCY, AND NIGHT LIGHTINGSHOWN.C.PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR EACH CIRCUITSERVING COMPUTER PURPOSE OUTLETS. MINIMUM BRANCH CIRCUIT CONDUCTOR SIZE FOR OUTDOOR AND EXTERIOR BUILDINGD. LIGHTING WIRING SHALL BE #10 AWG.2.WHERE ROOM OCCUPANCY SENSORS ARE REQUIRED/INDICATED,PROVIDE QUANTITY AND LOCATION OF DEVICES PER MANUFACTURER'S RECOMMENDATION FOR COMPLETE ROOM COVERAGE AND TO MINIMIZE FALSE ACTIVATION THRU OPEN DOORS.3. REFER TO ARCHITECTURAL PLANS FOR LIGHT FIXTURE LOCATIONSAND FOR MOUNTING HEIGHT OF SUSPENDED AND WALL MOUNTEDLIGHT FIXTURES. REFER TO REFLECTED CEILING PLANS, INTERIORELEVATIONS, EXTERIOR ELEVATIONS, ROOM SECTIONS, AND DETAILS SHOWN ON ARCHITECTURAL CONTRACT DOCUMENTSPRIOR TO ROUGH-IN. REPORT CONFLICTS TO ARCHITECTURAL/ENGINEER FOR RESOLUTION.4.REFER TO ARCHITECTURAL ELEVATIONS FOR LOCATION AND MOUNTING HEIGHT OF WIRING DEVICES. REPORT CONFLICTS TOARCHITECT/ENGINEER FOR RESOLUTION.5. VERIFY EXACT LOCATION OF FLOOR BOXES WITH KNEE SPACESAND CASEWORK. OBTAIN ARCHITECT APPROVAL PRIOR TO ROUGH-IN.7. VERIFY BACK BOX REQUIREMENTS OF EQUIPMENT FURNISHEDUNDER OTHER THAN DIVISION 16 SECTIONS AND EQUIPMENTFURNISHED BY OWNER.8. REFER TO OTHER DIVISIONS OF THE PROJECT DOCUMENTS TOIDENTIFY ADDITIONAL SYSTEMS, EQUIPMENT AND PRODUCTS THAT REQUIRE FIELD WIRING AND ELECTRICAL CONNECTION WHICH ARE NOT INDICATED, BUT ARE TO BE INCLUDED AND SHOWN IN THE DESIGN BUILD ELECTRICAL PLANSUBMITTAL. INCLUDES (BUT IS NOT LIMITED TO):HVAC EQUIPMENT120 VAC OUTLETS FOR AIR TEMPERATURE CONTROLS PLUMBING EQUIPMENTAUTOMATIC AND MANUAL DOOR OPERATORSFIRE SMOKE DAMPERSOPERABLE PARTITIONSFOOD SERVICE EQUIPMENTELECTRIC HAND DRYERSMOUNTING HEIGHTS HEIGHT OF OUTLETS(MEASURED TO CENTER OF BOX, UNLESS OTHERWISE INDICATED)COUNTER HEIGHT (*) +3 INCHES ABOVE SPLASHCASEWORK AND OTHER OUTLETS AS DIRECTEDWIRING DEVICES:SWITCHES AND DIMMERS 48 INCHESRECEPTACLES 18 INCHESTHERMOSTATS 54 INCHESCLOCKS90 INCHESWATER COOLERSMANUFACTURERRECOMMENDATIONLOAD CENTERS +48 INCHES TO TOP CIRCUITBREAKER IN DESIGNATEDADA ACCESSIBLE UNITSOCCUPANCY SENSORS: WALL BOX SENSOR 48 INCHES ROOM AND AREA SENSORSMANUFACTURERRECOMMENDATION(NOT TO EXCEED 12 FT.)SIGNAL: VOICE (TELEPHONE) 18 INCHESDATA (COMPUTER)18 INCHESWALL PHONE 48 INCHESTV (TELEVISION) 18 INCHESTV WALL MOUNTED CENTER OF MOUNTINGBRACKETSPEAKERS 90 INCHESPUBLIC TELEPHONE 48 INCHESFIRE ALARM:MANUAL STATIONS48 INCHES TO TOPSIGNALING DEVICES80 INCHES TO BOTTOMREMOTE ALARM LIGHTS80 INCHES TO BOTTOMREMOTE ANNUNCIATOR 60 INCHES TO BOTTOMGRAPHIC PLAQUES60 INCHES TO BOTTOMSECURITY: KEY PAD 54 INCHES TO TOPMOTION SENSORS MANUFACTURERRECOMMENDATIONCARD READER 48 INCHES TO TOPNURSE CALL:PATIENT STATION 48 INCHESDUTY STATION48 INCHESTOILET STATION 38 INCHESBATH STATION 72 INCHESEMERGENCY STATION48 INCHESDOME LIGHT90 INCHESGENERAL POWER SHEET NOTES:1.TO ACCOMMODATE FOR VOLTAGE DROP FOR16A, 120V LOADS, ON 20A/1PH CIRCUIT, FOR WIRE LENGTHFROM 70' TO 115' PROVIDE 2#10 AWG AND #10 CU GND, ANDWIRE LENGTH BETWEEN 115' TO 175' PROVIDE 2#8 AWG AND#8 CU GND.2.PROVIDE 20A/1P 120V CIRCUIT TO POWER DUCT SMOKEDETECTORS, PROVIDE 20A/1P 120V FOR HVAC CONTROLS,AND PROVIDE 20A/1PH 120V CIRCUIT TO POWER MOTORIZEDDAMPERS. REFER TO MECHANICAL DRAWINGS FORLOCATION AND EXACT QUANTITY OF DUCT SMOKEDETECTORS, MOTORIZED DAMPERS AND CONTROLS.3.FOR MECHANICAL EQUIPMENT ELECTRICAL REQUIREMENTS AND CIRCUITS REFER TO ELECTRICALCONNECTION SCHEDULE ON SHEET E7.2. UNLESS SHOWNON THE PLANS. FOR EQUIPMENT LOCATION AND ADDITIONALREQUIREMENTS REFER TO MECHANICAL DRAWINGS.4.FOR ELECTRICAL LAYOUT AND CONNECTION IN RESIDENTIALUNITS REFER TO ASSOCIATED ENLARGED PLANS.5.FOR EACH LOW VOLTAGE SYSTEM DEVICE INCLUDING DATA/PHONE, FIRE ALARM, NURSE CALL, ACCESS CONTROLAND ANY OTHER TELECOMMUNICATION SYSTEMS SHOWNLOW VOLTAGE CONSULTANT DRAWINGS PROVIDE BACK BOXAND MUD RING IN ACCORDANCE WITH MANUFACTUREREQUIREMENTS. PROVIDE 3/4" CONDUIT WITH PULL STRINGTO ABOVE CEILING JUNCTION BOX. FOR EXACT LOCATIONAND QUANTITY OF DEVICES AND COMPLETE REQUIREMENTSCOORDINATE WITH OWNER.6.PROVIDE HORIZONTAL PATHWAY FOR LOW VOLTAGESYSTEMS INCLUDING FIRE ALARM UTILIZING CONDUIT ANDJUNCTION BOXES ROUTED BACK TO ELECTRICAL AND IDFROOMS. COORDINATE LOCATION OF J-BOXES WITH CEILINGACCESS POINTS.7.PROVIDE 20A, 120V CIRCUITS AND POWER CONNECTIONS ASREQUIRED FOR LOW VOLTAGE EQUIPMENT.8.ALL EXIT DOOR LOCKING DEVICES TO BE APPROVED BY THEBUILDING CODES AGENCY AND FIRE MARSHAL. DOOR LOCKMUST BE ELECTRONIC AND RELEASE UPON ACTIVATION OFTHE FIRE ALARM OR SPRINKLER SYSTEM, POWER FAILURETO THE FACILITY; OR BY ACTIVATING A KEY BUTTON ORKEY PAD LOCATED AT EXITS FOR USE BY STAFF FOR SERVICE. SEE DETAIL SHEET E8.2. FOR LOCATION AND QUANTITY REFER TO ARCHITECTURAL DRAWINGS.2.PROVIDE 1" CONDUITS STUBBED UP TO NURSE STATION ASREQUIRED FOR EMERGENCY CALL, DATA, ETC.3.PROVIDE TAMPER PROOF RECEPTACLES IN ALL AREAS THATARE ACCESSIBLE BY MEMORY CARE RESIDENTS.4.SEE ARCHITECTURAL PLANS FOR LOCATION OF FIRE RATEDCONSTRUCTION.5.VERIFY EXACT LOCATION OF FLOOR BOXES AND OUTLETSLOCATED IN KNEE SPACES AND CASEWORK. OBTAINARCHITECT APPROVAL PRIOR TO ROUGH-IN.6.VERIFY BACK BOX REQUIREMENTS OF EQUIPMENTFURNISHED UNDER OTHER THAN DIVISION 26 SECTIONS ANDEQUIPMENT FURNISHED BY OWNER.GENERAL LIGHTING SHEET NOTES:1.EXTERIOR LIGHT FIXTURES ARE DESIGNATED FORDUSK TO DAWN OPERATION AND SHALL BECONTROLLED BY PHOTO SENSOR.2.LIGHTING IN ALL INTERIOR SPACES SHALL BECONTROLLED WITH OCCUPANCY SENSORS EXCEPTRESIDENT (SLEEPING) ROOMS, PATIENT CAREROOMS, SHOWER ROOMS AND CORRIDORSCONTROLLED AT NURSE STATION, LIGHT FIXTURESIDENTIFIED FOR CONTINUOUS OPERATION(NIGHTLIGHTS), AND IN SPACES WHERE AUTOMATICSHUTOFF WOULD ENDANGER OCCUPANT SAFETY(ELECTRICAL AND MECHANICAL ROOMS).3.OCCUPANCY SENSORS SHALL BE INSTALLED FORMANUAL ON/AUTOMATIC OFF OPERATION EXCEPT INWINDOWLESS SPACES AND CORRIDORS WHEREOCCUPANCY SENSORS SHALL BE INSTALLED TOALLOW FULL AUTOMATIC OPERATION. PROVIDEREMOTE OVERRIDE SWITCH FOR CORRIDOR LIGHTS.4.PRIOR TO ROUGH-IN COORDINATE EXACT EXIT SIGNLOCATIONS WITH LOCAL AHJ .5.THE CONTRACTOR SHALL PROVIDE ALL CONTROLPANELS, CONTROLLERS, RELAYS, SWITCHING,CABLING, SPECIAL BALLASTS OR ANY OTHERCOMPONENT REQUIRED FOR A COMPLETE ANDOPERABLE SYSTEM. CONTROL SYSTEM SHALL BEMANUFACTURED BY NLITE, LC&D, LUTRON ORAPPROVED EQUAL.6.CONTRACTOR TO SUPPLY ALL SHOP DRAWINGS WITHWIRING DIAGRAMS, CUT SHEETS OF ALLCOMPONENTS AND DETAIL SEQUENCE OF OPERATIONFOR APPROVAL BEFORE ORDERING.7.LUMINARIES INSTALLED IN DAYLIGHT ZONE TO HAVECONTINUOUS DIMMING BALLASTS.8.MAXIMUM LOAD ON EACH 20A/1PH CIRCUIT SHOULDNOT EXCEED 16A.9.TO ACCOMMODATE FOR VOLTAGE DROP FOR 16A,120V LOADS, ON 20A/1 CIRCUIT, FOR WIRE LENGTHFROM 70' TO 115' PROVIDE 2#10 AWG AND #10 CUGND, AND WIRE LENGTH BETWEEN 115' TO 175'PROVIDE 2#8 AWG AND #8 CU GND.GENERAL ENLARGED UNITS SHEET NOTES:1.FOR EXACT LOCATION OF UNIT APPLIANCES, LIGHTING FIXTURESAND WIRING DEVICES HEIGHTS REFER TO ARCHITECTURAL CONTRACT DOCUMENTS PRIOR TO ROUGH-IN. REPORT CONFLICTSTO ARCHITECT/ENGINEER FOR RESOLUTION.2.VERIFY BACK BOX REQUIREMENTS OF EQUIPMENT FURNISHEDUNDER OTHER THAN DIVISION 26 SECTIONS AND EQUIPMENT FURNISHED BY OWNER.3.FOR EACH LOW VOLTAGE SYSTEMS DEVICE SHOWN PROVIDE BACKBOX AND MUD RING IN ACCORDANCE WITH MANUFACTURE REQUIREMENTS. PROVIDE 3/4" CONDUIT WITH PULL STRING TOABOVE CEILING JUNCTION BOX.4.RESIDENTIAL LOADS TO BE CIRCUITED TO RESIDENTIAL LOAD CENTERS. REFER TO PANEL SCHEDULES FOR CIRCUIT NUMBERS.5.FOR ACTUAL LOAD CALCULATIONS OF INDIVIDUAL UNITS, REFER TOELECTRICAL SCHEDULES.1.FOR RESIDENTIAL UNIT LIGHTING FIXTURE SCHEDULE REFER TOSHEET E7.12.PROVIDE TAMPER PROOF RECEPTACLES PER NEC 406.12.3.IN ALL ACCESSIBLE UNITS WIRE RANGE HOOD CONTROLS TO ACCESSIBLE SWITCH LOCATED ON THE WALL NEXT TO LIGHT SWITCH. COORDINATE WITH HOOD MANUFACTURE EXACT SWITCHTYPE AND WIRING REQUIREMENTS.
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-001-003.dwg
8/11/2023 11:27:53 AME-003ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS1.REGULATORY REQUIREMENTSA.NATIONAL ELECTRICAL CODE, STATE AND LOCAL ELECTRICAL AND BUILDING CODES,LOCAL UTILITY COMPANY REQUIREMENTS. OBTAIN REQUIRED PERMITS ANDINSPECTIONS.B.LISTING AND LABELING: FURNISH AND INSTALL ONLY PRODUCTS THAT ARE LISTEDAND LABELED BY ONE OR MORE OF THE FOLLOWING TESTING LABORATORIES ASAPPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ):UNDERWRITER'S LABORATORIES, INC (UL)ETL TESTING LABORATORIES, INC (ETL)FACTORY MUTUAL (FM)2.SUBMITTALSA.OBTAIN WRITTEN APPROVAL FROM OWNER PRIOR TO ORDERING MATERIALS ANDCOMMENCING WORK.B.LIGHTING SYSTEMS: PROVIDE PRODUCT SUBMITTALS ON LIGHT FIXTURES, LAMPS,AUTOMATIC CONTROLS, LOW VOLTAGE SWITCHING CONTROLS. INCLUDE SHOPDRAWINGS FOR LOW VOLTAGE SWITCHING CONTROL.C.POWER SYSTEMS: PROVIDE PRODUCT SUBMITTALS ON CONDUIT, WIRE, CABLE,WIRING DEVICES AND COVER PLATES. PROVIDE PRODUCT SUBMITTALS AND SHOPDRAWINGS ON DISTRIBUTION EQUIPMENT, TO INCLUDE SWITCHBOARDS ANDPANELBOARDS. PROVIDE PRODUCT SUBMITTALS AND SHOP DRAWINGS ONGENERATOR SYSTEMS AND TRANSFER SWITCHES.D.LOW VOLTAGE SYSTEMS: PROVIDE PRODUCT SUBMITTALS ON ALL WIRE AND CABLE,EQUIPMENT, COMPONENTS, AND DEVICES BEING FURNISHED FOR EACH SYSTEM.INCLUDE SHOP DRAWINGS FOR FIRE ALARM, EMERGENCY CALL, MEMORY CARECONTROLLED EGRESS, AND TELEPHONE.E.SUBMIT PRODUCT DATA AND SHOP DRAWINGS FOR SERVICE EQUIPMENT TO SERVINGUTILITY FOR REVIEW AND APPROVAL IN ADDITION TO OWNER SUBMITTALREQUIREMENTS.F.OPERATION AND MAINTENANCE MANUALS: SUBMIT OPERATION AND MAINTENANCEMANUALS IN APPROVED ELECTRONIC FORMAT FOR THE FOLLOWING: LIGHT FIXTURES,AUTOMATIC LIGHTING CONTROLS, LOW VOLTAGE SWITCHING CONTROLS, POWERDISTRIBUTION EQUIPMENT, ALL LOW VOLTAGE SYSTEMS, GENERATOR SYSTEMS ANDTRANSFER SWITCHES, AND OTHER ELECTRICAL SYSTEMS REQUESTED BY OWNER.G.RECORD DRAWINGS: MAINTAIN AT THE PROJECT SITE ONE SET OF CLEAN, DRY, ANDLEGIBLE RED-LINED RECORD DRAWINGS. INDICATE ELECTRICAL CHANGES,ELECTRICAL WORK ADDED, CIRCUITING, ONE LINE DIAGRAMS, SCHEDULES,CONSTRUCTION NOTES, AND DETAILS FOR A COMPLETE AS BUILT ELECTRICAL PLANDOCUMENT. CREATE AND SUBMIT FINAL AS BUILT ELECTRICAL PLAN DOCUMENT INAUTOCAD AND PDF FORMATS AT CONTRACT CLOSEOUT.3.DEFINITIONSA.FURNISH: OBTAIN AND/OR PREPARE AND DELIVER TO THE PROJECT.B.INDICATED: SHOWN, SCHEDULED, NOTED, OR OTHERWISE CALLED OUT ON THEDRAWINGS.C.INSTALL: ENTER PERMANENTLY INTO THE PROJECT COMPLETE AND READY FORSERVICE.D.PROVIDE: FURNISH AND INSTALL COMPLETE AND READY FOR SERVICE.E.EQUIPMENT CONNECTION: MAKE BRANCH CIRCUIT CONNECTION, MOUNT ANDCONNECT CONTROL DEVICES AS REQUIRED. PROVIDE DISCONNECT ANDOVERCURRENT PROTECTION WHEN REQUIRED BY NEC AND IMC, IF NOT OTHERWISEINDICATED OR FURNISHED WITH EQUIPMENT.F.WIRING: CONDUCTORS IN RACEWAY OR AN APPROVED CABLE ASSEMBLY.G.PANEL: DISTRIBUTION PANELBOARD, LIGHTING & APPLIANCE PANELBOARD,LOADCENTER.4.ELECTRICAL SERVICEA.OBTAIN, PREPARE, AND FILE APPLICATION FORMS REQUIRED BY THE SERVING UTILITYFOR OBTAINING TEMPORARY AND PERMANENT SERVICES.B.UTILITY COMPANY CHARGES FOR INSTALLING POWER SERVICE SHALL BE PAID BY THEOWNER AND ARE NOT INCLUDED IN THE CONTRACT.C.MAKE ARRANGEMENTS WITH UTILITY COMPANY TO OBTAIN PERMANENT ANDTEMPORARY ELECTRICAL SERVICE TO THE PROJECT. COORDINATE AND ARRANGEFOR SCHEDULING OF UTILITY WORK.D.PROVIDE PICK-UP AND DELIVERY OF UTILITY COMPANY FURNISHED PRODUCTS ANDMATERIALS TO PROJECT SITE.E.PROVIDE TEMPORARY LIGHTING AND POWER DISTRIBUTION REQUIRED FOR THEPROJECT.F.PROVIDE LABOR AND MATERIALS FOR ELECTRICAL SERVICE PER UTILITY COMPANYREQUIREMENTS. WORK INCLUDES PRIMARY AND SECONDARY CONDUITS,SECONDARY WIRE, VAULTS, AND TRANSFORMER PADS. OBTAIN PRODUCT ANDINSTALLATION SPECIFICATIONS FROM THE UTILITY.G.THE FOLLOWING SHALL BE FURNISHED AND INSTALLED BY THE UTILITY COMPANY:PRIMARY CABLE, PAD MOUNT TRANSFORMERS, CURRENT TRANSFORMERS FORMETERING, AND CONDUCTORS BETWEEN CURRENT TRANSFORMERS AND METERSOCKETS.H.THE FOLLOWING SHALL BE FURNISHED BY THE UTILITY COMPANY AND INSTALLED BYTHE CONTRACTOR: METER SOCKETS.5.RACEWAYSEMT FOR DRY AND DAMP LOCATIONS; RIGID GALVANIZED STEEL FOR WET LOCATIONSABOVE GRADE; SCHEDULE 40 PVC FOR WET LOCATIONS BELOW GRADE; FLEXIBLECONDUIT FOR FINAL CONNECTIONS TO RECESSED LIGHT FIXTURES AND EQUIPMENTSUBJECT TO VIBRATION OR MOVEMENT. FLEXIBLE CONDUIT MAY BE USED WHERECONCEALED IN WALLS. MINIMUM CONDUIT SIZE FOR HOMERUNS & FOR CONDUITINSTALLED BELOW GRADE AND UNDER CONCRETE SLAB SHALL BE 3/4".6.CONDUIT FOR OUTDOOR ELECTRICAL WORKINSTALL 24 INCHES MINIMUM BELOW GRADE FOR 600 VOLTS AND BELOW. PROVIDE 6"WIDE METALLIC CORE YELLOW WARNING TAPE 12 INCHES BELOW FINAL GRADE.MINIMUM CONDUIT SIZE FOR ELECTRICAL BELOW 600 VOLTS SHALL BE 3/4 INCH.PRODUCTS AND INSTALLATION FOR ELECTRICAL SERVICE CONDUITS SHALL COMPLYWITH UTILITY COMPANY REQUIREMENTS.7.CONDUCTORSA.600 VOLTS AND BELOW:COPPER BUILDING WIRE, TYPE THWN-2 OR XHHW-2 (90 DEGREE) UNLESS OTHERWISEINDICATED. MINIMUM CONDUCTOR SIZE #12 AWG EXCEPT MINIMUM CONDUCTOR SIZEFOR EXTERIOR BUILDING, AREA & SIGN LIGHTING & HOMERUNS GREATER THAN100-FEET SHALL BE #10 AWG.B.METAL CLAD (MC CABLE): UL 1569; COPPER CONDUCTORS, 600 VOLT 90 DEGREE CRATED CONDUCTOR INSULATION, PHASE IDENTIFIED, WITH GREEN INSULATEDCOPPER GROUNDING CONDUCTOR AND STEEL OUTER COVERING. INCLUDE NEUTRALCONDUCTOR FOR SWITCH LEGS PER NEC 404.2(C). PROVIDE PVC JACKETED MC CABLELISTED FOR THE PURPOSE WHERE USED IN DAMP OR WET LOCATIONS.C.NON METALLIC SHEATHED CABLE: TYPE NM AND SE, COPPER CONDUCTORS, 600VOLT INSULATION RATED 90 DEGREES C, WITH INTEGRAL EQUIPMENT GROUNDCONDUCTOR. INCLUDE NEUTRAL CONDUCTOR FOR SWITCH LEGS PER NEC 404.2(C).8.DISTRIBUTION EQUIPMENT 600 VOLTS AND BELOWCOMMERCIAL EQUIPMENT MANUFACTURED BY SQUARE D, SIEMENS, OR EATON. FULLSIZE (1"/POLE) AND MULTIPOLE COMMON TRIP CIRCUIT BREAKERS ONLY.DISCONNECT/SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE. WHERE INDICATED ONDRAWINGS, AIC RATING IS THE RMS SYMMETRICAL INTEGRATED EQUIPMENT SHORTCIRCUIT RATING OF THE COMPLETE ASSEMBLY.9.FUSINGUL CLASS J EXCEPT CLASS RK5 MAY BE USED FOR MOTOR LOADS.10. GROUNDINGA.GROUND NEW ELECTRICAL SERVICES AND SEPARATELY DERIVED SYSTEMS PERCODE.B.PROVIDE EQUIPMENT GROUNDING PER CODE EXCEPT INCLUDE A SEPARATEINSULATED GREEN EQUIPMENT GROUNDING CONDUCTOR IN FEEDERS AND INBRANCH CIRCUITS TO PLUG-IN OUTLETS.C.GROUNDING CONNECTIONS AND TERMINATIONS WHICH ARE BURIED OR OTHERWISEINACCESSIBLE SHALL BE MADE USING EXOTHERMIC WELDS.11. DEVICESA.GENERAL: PROVIDE COMMERCIAL SPECIFICATION GRADE WITH MATCHING COVERPLATE. RECEPTACLE OUTLETS SHALL BE DUPLEX NEMA 5-20R UNLESS OTHERWISEINDICATED, EXCEPT NEMA 5-15R MAY BE SUBSTITUTED FOR MULTI-OUTLET GENERALPURPOSE CIRCUITS IN OFFICE. DEVICE AND PLATE COLOR AS SELECTED BYARCHITECT/OWNER.B.DUPLEX RECEPTACLES, DWELLING UNITS, GUEST ROOMS & SUITES, AREASACCESSIBLE TO MEMORY CARE RESIDENTS: SAME MANUFACTURE, RATING, ANDCOLOR AS DUPLEX AND GFCI RECEPTACLES EXCEPT DEVICES SHALL BE UL LISTED ASTAMPER RESISTANT AND PERMANENT SPECIAL PURPOSE IDENTIFICATION SHALL BEVISIBLE ON THE DEVICE.C.GFCI: PROVIDE GFCI PROTECTION FOR OUTLETS LOCATED IN KITCHENS, WITHIN 6FEET OF SINKS, AT COUNTERS AND WORK SURFACES WHERE FOOD AND/ORBEVERAGES ARE PREPARED, AND AS OTHERWISE INDICATED.D.DUPLEX RECEPTACLES, CONTROLLED: SAME MANUFACTURER, RATING, AND STYLEAS SPECIFIED FOR DUPLEX RECEPTACLES EXCEPT DEVICES SHALL HAVE SPECIALPURPOSE IDENTIFICATION SYMBOL VISIBLE ON FACE OF EACH RECEPTACLECONTROLLED. COLOR: AS SELECTED. PROVIDE UL LISTED LOW VOLTAGE LOCALNETWORK STANDALONE 20 AMPERE PLUG LOAD RATED CONTROLLER.E.OUTDOOR CONVENIENCE OUTLETS: PROVIDE GFCI PROTECTED NEMA 5-20R DUPLEXRECEPTACLE WITH WEATHERPROOF METAL DEVICE PLATE WITH HINGED DEVICECOVER.F.OUTDOOR HVAC EQUIPMENT: PROVIDE OUTDOOR CONVENIENCE OUTLETS WITHIN 25FEET OF EQUIPMENT PER CODE.G.CONCEALED SERVICE FLOOR BOXES: HUBBELL HBLCFB SERIES FOR CONCRETEFLOORS, WITH STEEL FLUSH COVER/CARPET FLANGE ASSEMBLY AND REQUIREDDEVICE PLATES. PROVIDE 301 BASE FOR MAXIMUM 4-GANG DEVICE APPLICATIONS.H.ALL 120-VOLT, SINGLE-PHASE, 15- AND 20- AMPERE BRANCH CIRCUITS SUPPLYINGOUTLETS OR DEVICES INSTALLED IN DWELLING UNIT KITCHENS, FAMILY ROOMS,DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,RECREATION ROOMS, CLOSET, HALLWAYS, LAUNDRY AREAS, OR SIMILAR ROOMS ORAREAS SHALL BE PROTECTED BY AFCI. (NEC 210.12)12.LIGHTING FIXTURESPROVIDE FIXTURES COMPLETE WITH LAMPS AND MOUNTING HARDWARE. PROVIDEHANGARS, BRACKETS, PLATES, ANCHORS, AUXILIARY SUPPORTS AND OTHERMOUNTING ACCESSORIES REQUIRED BY BUILDING CONSTRUCTION AND CEILINGCONDITIONS. PROVIDE CONCRETE BASE FOR OUTDOOR POLE LIGHTS AND SIGNLIGHTS.13. OCCUPANCY SENSORS, DIGITAL CONTROLLERS, DAYLIGHT SENSORSEXCLUDING DWELLING AND RESIDENT SLEEPING UNITS, PROVIDE OCCUPANCYSENSORS, DIGITAL CONTROLLERS, AND DAYLIGHT SENSORS FOR AUTOMATICCONTROL OF LIGHTING AND DESIGNATED RECEPTACLES PER THE ENERGY CODE.OCCUPANCY SENSORS IN RESTROOMS AND OPEN OFFICE AREAS WITH PARTITIONSSHALL BE DUAL TECHNOLOGY (PIR/ULTRASONIC). PROVIDE ALL REQUIRED SYSTEMSSET UP, PROGRAMMING, AND COMMISSIONING. OCCUPANCY TIME DELAY SHALL BESET FOR 10 MINUTES UNLESS OTHERWISE DIRECTED. SET OCCUPANCY SENSITIVITYPER MANUFACTURER'S RECOMMENDATION AND ADJUSTMENT INSTRUCTIONS.APPROVED PRODUCT MANUFACTURERS: NOVITAS, WATT STOPPER, SENSOR SWITCH.14. LOW VOLTAGE LIGHTING CONTROLA.PROVIDE ALL COMPONENTS, WIRING, AND ACCESSORIES FOR AUTOMATIC ANDMANUAL REMOTE CONTROL SWITCHING OF LIGHTING BRANCH CIRCUITS USINGENERGY LIMITED CONTROL POWER. INCLUDE NECESSARY CLASS 2 TRANSFORMERS,20 AMPERES RELAYS RATED FOR THE CONNECTED LOADS, PHOTO/TIME SWITCHCONTROLLER, REMOTE ADJUSTABLE PHOTO SENSOR SUITABLE FOR OUTDOORWEATHERPROOF INSTALLATION, AND RELAY SCANNERS AS REQUIRED FOR INDICATEDCONTROL SEQUENCE OF SCHEDULED LIGHTING BRANCH CIRCUITS. MANUAL CONTROLSWITCHES SHALL BE HEAVY DUTY THREE POSITION MOMENTARY TOGGLE OR ROCKERTYPE SWITCH. LOW VOLTAGE CABLE SHALL BE UL TYPE CL2P, NEC CLASS 2P, WITHTEFLON JACKET OVERALL AND LISTED FOR USE IN DUCTS, PLENUMS, AND OTHER AIRHANDLING SPACES, MULTI-CONDUCTOR, STRANDED COPPER CABLE, #20 AWGMINIMUM, COLOR CODED. APPROVED MANUFACTURERS: GE, DOULAS LIGHTING,WATTSTOPPER OR APPROVED EQUAL.B. PROVIDE SHOP DRAWINGS INDICATING QUANTITY, LAYOUT, AND WIRING OF ALLSYSTEMCOMPONENTS AND SEQUENCE OF OPERATION. INSTALL SYSTEM IN ACCORDANCEWITH MANUFACTURER REQUIREMENTS AND APPROVED SHOP DRAWINGS. PROVIDEREQUIRED PROGRAMMING FOR INITIAL SET UP OF SYSTEM AS DIRECTED BY OWNER.15. EQUIPMENT CONNECTIONSA.PROVIDE POWER CONNECTIONS AND IN-SIGHT DISCONNECTING MEANS FOR ALLAPPLIANCES, HVAC, AND MECHANICAL EQUIPMENT BEING FURNISHED OR INSTALLEDUNDER THE CONTRACT. PROVIDE PIGTAIL AND PLUG WHERE REQUIRED FOR PLUG-INCONNECTIONS. FINAL EQUIPMENT SELECTIONS AND APPROVED PRODUCTS MAY BEDIFFERENT THAN INDICATED IN CONTRACT DOCUMENTS. OBTAIN CIRCUIT, CONDUITTERMINATION, AND VOLTAGE REQUIREMENTS FROM THE GENERAL, HVAC, ANDPLUMBING CONTRACTORS AND FROM THE OWNER FOR OWNER FURNISHEDEQUIPMENT. ENSURE APPLIANCE AND EQUIPMENT VOLTAGE, PHASE, AND CIRCUITSIZE MATCH ELECTRICAL CIRCUITS BEING PROVIDED PRIOR TO ROUGH-IN.16. FIRE ALARM SYSTEMPROVIDE BIDDER DESIGN FIRE ALARM SYSTEM AND CARBON MONOXIDE DETECTORSCONFORMING TO ALL REQUIREMENTS OF THE LOCAL AUTHORITY HAVINGJURISDICTION (AHJ). INCLUDE SHOP DRAWINGS, AHJ PLAN CHECK AND APPROVAL,PERMITTING, AND REQUIRED INSPECTORS. BUILDING IS FIRE SPRINKLERED.COORDINATE WITH SPRINKLER CONTRACTOR AND HVAC CONTRACTOR FOR FIREALARM INTERFACE REQUIREMENTS.17.TELEPHONE PREWIRE (RESIDENT UNITS)PROVIDE BIDDER DESIGN TELEPHONE PREWIRE TO EACH DWELLING AND/ORRESIDENT SLEEPING UNIT. ALLOW FOR DEDICATED CAT 5E UTP TELEPHONE CABLEFROM A BUILDING DEMARCATION TELEPHONE BOARD TO EACH BEDROOM AND EACHLIVING ROOM.18. SIGNAL PATHWAYA.SINGLE PURPOSE OUTLETS (VOICE, DATA, TV): 4-INCH SQUARE X 2-1/8-INCH DEEPOUTLET BOX WITH SINGLE GANG PLASTER RING. PROVIDE BLANK DEVICE PLATE ONUNUSED OUTLETS.B.TELECOMMUNICATIONS OUTLETS (COMBINATION VOICE/DATA): 4-INCH SQUARE X2-1/8-INCH DEEP OUTLET BOX WITH SINGLE GANG PLASTER RING. PROVIDE BLANKDEVICE PLATE ON UNUSED OUTLETS.C.OUTLET RACEWAY: UNLESS OTHERWISE INDICATED, PROVIDE 3/4 INCH DIAMETERCONDUIT CONCEALED INSIDE WALL OR CASEWORK FROM EACH OUTLET UP TONEAREST ACCESSIBLE ATTIC SPACE.19.EMERGENCY CALL SYSTEMPROVIDE BIDDER DESIGN WIRELESS EMERGENCY CALL SYSTEM CONFORMING TOREQUIREMENTS OF UL 2560, WAC 246-316 AND ALL OTHER REQUIREMENTS OF LOCALAHJ.20.CABLE TVCOORDINATE WITH THE CATV / INTERNET SERVICE PROVIDER TO BE SELECTED BYTHE OWNER AS REQUIRED TO SCHEDULE DESIGN AND INSTALLATION OF CABLESERVICE AND DISTRIBUTION TO EACH DWELLING AND/OR RESIDENT SLEEPING UNITAND OTHER LOCATIONS INDICATED ON PLANS.21. CONTROLLED ENTRANCE AND EGRESS SYSTEMPROVIDE BIDDER DESIGN CONTROLLED ENTRANCE AND EGRESS FOR MEMORY CAREAREAS CONFORMING TO REQUIREMENTS OF WAC 51-50-1008, WAC 388-78A-2380 ANDALL OTHER REQUIREMENTS OF LOCAL AHJ. SYSTEM SHALL INCLUDE MAGNETIC DOORAND GATE LOCKS, KEYPAD STATIONS, CENTRAL POWER SUPPLY(S) WITH BATTERYBACKUP, AND FIRE ALARM RELEASE. SYSTEM SHALL BE CAPABLE OF BEINGDE-ENERGIZED AT A DESIGNATED STAFF STATION.22.DIRECTORIES, NAMEPLATES AND LABELSA.CIRCUIT DIRECTORIES: TYPEWRITTEN INDEX OF CIRCUITS LOCATED ON INSIDE DOOROF EACH PANEL. IDENTIFY LOAD TYPE AND LOCATION USING FINAL ROOM NAMES ORNUMBERS VERIFIED BY OWNER.B.NAMEPLATES: ENGRAVED THREE-LAYER LAMINATED PLASTIC, WHITE LETTERS ONBLACK BACKGROUND, AFFIXED WITH STAINLESS STEEL SCREWS, ADHESIVEACCEPTABLE IN DRY LOCATIONS. USE BLACK LETTERS ON YELLOW BACKGROUNDFOR SERIES COMBINATION RATING IDENTIFICATION.C.LETTER HEIGHT: 1/2 INCH FOR SERIES COMBINATION RATING IDENTIFICATION. 1/4 INCH FOR SWITCHBOARDS, PANELBOARDS, CIRCUIT BREAKERS, AND DISCONNECTINGMEANS.D.FLASH PROTECTION LABELS: SELF ADHESIVE VINYL LABEL, MINIMUM 5 INCHES WIDE X3.5 INCHES HIGH, WITH ANSI HEADER TO READ WARNING OR DANGER ANDINFORMATION TEXT TO INCLUDE: ARC FLASH HAZARD APPROPRIATE PPE REQUIRED FAILURE TO COMPLY CAN RESULT IN DEATH OR INJURY REFER TO NFPA 70EE.SWITCHBOARDS, PANELBOARDS: PROVIDE NAMEPLATE TO IDENTIFY EQUIPMENTDESIGNATION, VOLTAGE, AND SOURCE OF SUPPLY FOR EACH, E.G. PANEL A, 208/120V,FED FROM PANEL M. PROVIDE ARC FLASH PROTECTION LABEL. PROVIDE SERIESCOMBINATION RATING NAMEPLATE WHERE SUCH RATING IS APPLICABLE.F.INDIVIDUAL CIRCUIT BREAKERS AND SWITCHES INSTALLED IN SWITCHBOARDS ANDPANELS WITHOUT CIRCUIT INDEX: PROVIDE NAMEPLATE TO IDENTIFY CIRCUITNUMBER AND LOAD SERVED.G.INDIVIDUAL ENCLOSED CIRCUIT BREAKERS, SAFETY SWITCHES, AND DISCONNECTINGMEANS: PROVIDE NAMEPLATE TO IDENTIFY LOAD SERVED AND CIRCUIT SOURCECIRCUIT NUMBER.H.NAMEPLATE AND LABEL LOCATION: SECURE TO EQUIPMENT FRONTS, EXCEPTRECESSED.23. SEISMIC RESTRAINT FOR LIGHT FIXTURESRECESSED AND SURFACE MOUNTED LIGHTING FIXTURES WEIGHTING LESS THAN 56LBS (25.4 KG) MAY BE SUPPORTED FROM METAL CEILING SUSPENSION SYSTEMS WITHAUXILIARY SUPPORT FROM STRUCTURAL MEMBERS USING TWO #12 AWG WIREHANGARS AT DIAGONAL CORNERS (HANGARS MAY BE SLACK). FIXTURES WEIGHING56LBS OR MORE MUST BE SUPPORTED DIRECTLY FROM THE STRUCTURE BYAPPROVED HANGARS. SECURELY FASTEN RECESSED AND SURFACE FIXTURES INPLACE; PROVIDE SEISMIC CLIPS (ONE EACH CORNER) FOR LAY-IN FIXTURES; ATTACHSURFACE FIXTURES TIGHT TO CEILINGS AND WALLS, AND SECURE FLUORESCENTFIXTURES WITHIN 12 INCHES OF EACH END.24. SEISMIC RESTRAINT FOR EQUIPMENTCOMPLY WITH REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE (IBC). OBTAINREQUIRED ANCHORING PLANS FROM EQUIPMENT MANUFACTURER INDICATING SIZEAND LOCATION OF ANCHORS SUITABLE FOR SEISMIC ZONE 3. PROVIDE SEISMICBRACING FOR TRAPEZE MOUNTED EQUIPMENT. SECURE FLOOR MOUNTEDEQUIPMENT TO CONCRETE FLOOR OR PAD WITH CORROSION PROOF ANCHORSHAVING A MINIMUM EMBEDDED LENGTH EQUAL TO 12 TIMES THE NOMINAL BOLTDIAMETER. SHALL BE REQUIRED FOR THE FOLLOWING:OUTDOOR SWITCHGEARSWITCHBOARDSGENERATORTRANSFER SWITCHOTHER EQUIPMENT REQUIRED BY CODE 25.GENERAL INSTALLATION REQUIREMENTSA.SUPPORT WIRING, CONDUIT, RACEWAYS, BOXES, EQUIPMENT, AND FIXTURES FROMBUILDING STRUCTURE. PROVIDE ADDITIONAL FRAMING, CHANNEL, OR LISTEDSUPPORT ATTACHMENTS AS REQUIRED TO SPAN OR SUPPORT BETWEENSTRUCTURAL MEMBERS AND TO AVOID INTERFERENCE FROM PIPES, DUCTS, ANDOTHER EQUIPMENT.B.DO NOT INSTALL SUPPORT ANCHORS TO PENETRATE THRU ROOF DECK.C.DO NOT VIOLATE THE INTEGRITY OR EXCEED THE CAPACITY OF THE BUILDINGSTRUCTURE USED FOR SUPPORT. PROVIDE OR FABRICATE ADDITIONAL SUPPORTELEMENTS TO TRANSMIT LOADS TO THE FLOOR OR OTHER PARTS OF THE BUILDINGSTRUCTURE THAN CAN CARRY THE LOAD AS APPROVED BY THE STRUCTURALENGINEER.D.INSTALL BOXES, ROUGH-IN CANS, AND CONDUIT PENETRATIONS TO MAINTAIN FIRERATING OF WALLS AND CEILINGS PER CODE. SEE ARCHITECTURAL AND STRUCTURALPLANS FOR LOCATION OF FIRE RATED CONSTRUCTION.26.EMERGENCY AND STAND-BY POWERA. GENERATOR: 125KW KOHLER NATURAL GAS OR APPROVED EQUAL.B. STAND-BY TRANSFER SWITCH: 200A/3PH 208VC. COORDINATE WITH GENERAL CONTRACTOR TO PROVIDE HOUSE KEEPING PAD FORTHE GENERATOR. PAD TO BE 6 INCHES HIGH AND EXTEND 12 INCHES MINIMUM ALLSIDES. COORDINATE WITH MECHANICAL CONTRACTOR FOR INSTALLATION OF REMOTEFUEL TANK, FUEL LINES, EXHAUST SYSTEM AND VENTILATION.27.DEMONSTRATION AND INSTRUCTIONSPROVIDE DEMONSTRATION AND INSTRUCTION OF OPERATION, MAINTENANCE ANDPROGRAMMING OF LIGHTING CONTROLS, GENERATOR SYSTEM, AND EACH LOWVOLTAGE SYSTEM TO OWNER'S PERSONNEL PRIOR TO CONTRACT CLOSEOUT.SCHEDULE SESSIONS AT CONVENIENCE OF OWNER. USE OPERATION ANDMAINTENANCE MANUALS AS BASIS OF INSTRUCTION. REVIEW CONTENTS OF MANUALWITH PERSONNEL IN DETAIL TO EXPLAIN ALL ASPECTS OF OPERATION ANDMAINTENANCE. DEMONSTRATE OPERATION, CONTROL, TROUBLE SHOOTING,MAINTENANCE, AND TESTING OF SYSTEM.
CBERRY VALLEY RD SETAHOMA BLVD SESPACELONGMIRE ST SEJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-100.dwg
8/11/2023 11:28:21 AME-100ELECTRICAL SITE PLANSCALE: SITE PLAN - ELECTRICAL1" = 40'-0"
g.1g.3g.4g.5g.2g.6g.7g.8g.Ag.Dg.Eg.CPATIOSTO.LIVING ROOMKITCHENBEDROOM #1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLFIRE RISERPATIOSTO.LIVING ROOMKITCHENBEDROOM #1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLg.BPATIOSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLPATIOSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALL1E-302TYP.g.1g.3g.4g.5g.2g.6g.7g.8g.Ag.Dg.Eg.CDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.g.B1E-302TYP.J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-213.dwg
8/11/2023 11:30:03 AME-213ELECTRICAL PLANS - BUILDING 'G'SCALE: ELECTRICAL PLAN - BUILDING 'G' - LEVEL 21/8" = 1'-0"SCALE: ELECTRICAL PLAN - BUILDING 'G' - LEVEL 11/8" = 1'-0"
g.1g.3g.4g.5g.2g.6g.7g.8g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.CDECKSTO.LIVING ROOMKITCHENBEDROOM #1ENTRYDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMLDRYHALLDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMLDRYHALLDECKSTO.LIVING ROOMKITCHENENTRYg.Bg.B4E-301TYP.g.1g.3g.4g.5g.2g.6g.7g.8g.Ag.Dg.Eg.Cg.BWPH-4WPH-4J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-214.dwg
8/11/2023 11:30:13 AME-214ELECTRICAL PLANS - BUILDING 'G'SCALE: ELECTRICAL PLAN - BUILDING 'G' - ROOF1/8" = 1'-0"SCALE: ELECTRICAL PLAN - BUILDING 'G' - LEVEL 31/8" = 1'-0"
DWR****
*REF**D10864242412121212121,3141816141416169,1113,1517,1923,25181818181818181818215,721202020202020202022222222221222LIVING ROOMSTO.PATIOBEDROOM #2BEDROOM #1CLO.CLO.LDRYBATH #1BATH#2W.I.C.KITCHENENTRYHALLF1F1F1F1F1F1F4F4F4F3F3F1W2W22-BEDRM LC2426DW*DR****
*REF1,3108215,714142218181818181813,159,1117,1964242412121212121616161616161616211616LIVING ROOMENTRYKITCHENBATH #1CLOSETLDRYHALLBEDROOM #1CLO.DECKSTO.F3F1F4F4F4F1F1W2F1W21-BEDRM LC2024DWR****
*REF**D10864242412121212121,3141816141416169,1113,1517,1923,25181818181818181818215,7202020202020202022222222221222STO.PATIOLIVING ROOMENTRYKITCHENBATH #1LDRYCLO.BEDROOM #2BEDROOM #1W.I.C.BATH#2HALLCLO.W2F1F4F4F4F1F1F1F1F1F3F1F3W22-BEDRM LC2426DWR*****REF**D*10864242412121212121,3141816141416169,1113,1517,1923,251818181818181818185,72120202020202222222222122216ENTRYKITCHENLIVING ROOMDECKSTO.BEDROOM #1W.I.C.HALLCLO.LDRYM.BEDROOMBATH#2BATH #1F1F1F1F1F1F4F4F4F1W2F3F3W218F12-BEDRM LC2426SCALE: UNIT 2.201/4" = 1'-0"E-301ENLARGED UNIT ELECTRICAL PLANSSCALE: UNIT 1.121/4" = 1'-0"J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-301-303.dwg
8/11/2023 11:30:46 AMSCALE: UNIT 2.211/4" = 1'-0"SCALE: UNIT 2.231/4" = 1'-0"
DWR****
*REF**D108642424121212121,3141816141416169,1113,1517,1927,29181818181818181818215,721202020202020222222221222242424242423,25ENTRYKITCHENBATH #1BATH#2M.BEDROOMHALLBEDROOM #2BEDROOM #1CLO.LDRYLIVING ROOMSTO.PATIOF1F1F1F4F4F4F1F1F1F3W2F3W218F13-BEDRM LCE-302ENLARGED UNIT ELECTRICAL PLANSSCALE: UNIT 3.201/4" = 1'-0"J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-301-303.dwg
8/11/2023 11:30:48 AM
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-501-508.dwg
8/11/2023 11:34:21 AME-507ONE-LINE DIAGRAM - BUILDING 'G'FEEDER SCHEDULE (COPPER)CALLOUTDESCRIPTIONREMARKS200-4-G2"C-4#3/0 +#6 GND CU125-2-G1 1/4"C-3#1 +#6 GND CUGENERAL ELECTRICAL NOTE:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT USE ONLY AND AS A "DESIGNASSIST" TO THE CONTRACTOR. FINAL DESIGN AND DETAILING IS BY THECONTRACTOR. FINAL DESIGN WORK INCLUDES (BUT IS NOT LIMITED TO): REVIEW OFALL CONTRACT DOCUMENTS, VERIFYING LIGHT FIXTURE LOCATIONS AND TYPES,UTILITY TRANSFORMER VAULT/PAD PLACEMENT, UTILITY COORDINATION, UTILITYPRIMARY CONDUIT SIZING AND VERIFICATION OF UNIT RANGE AND DRYERVOLTAGES (SERVICE AT THIS SITE IS 208V/3-PH)2.IN ADA ACCESSIBLE UNITS INSTALL LOAD CENTER +48 INCHES MEASURED TO HIGHESTCIRCUIT BREAKER.3.PROVIDE ADDRESS LABEL ON EACH UNIT CIRCUIT BREAKER PER UTILITYREQUIREMENTS.4.SERVICES HAVE BEEN SIZED TO ACCOMMODATE FUTURE EV CHARGERS PER WAC51-50-0427.MODULAR METER CENTER600A, 208Y/120V, 3Ø, 4WM200/3M125/2M125/2M125/2125-2-G125-2-G200-4-G600/3TO UNIT UTILITYTRANSFORMER VAULT200A SPACEONE-LINE DIAGRAM - BUILDING 'G' SERVICENOTE:1.ALL UNITS 120/208V, 1Ø, 3W.125-2-GM125/2125-2-GM125/2125-2-G
M125/2125-2-G
M125/2125-2-G
M125/2125-2-G HOUSEPANELHLCLCLCLCLCLCLCLC(2) 3"C-4#350 KCMM125/2125-2-GM125/2125-2-GM125/2125-2-GM125/2125-2-G LCLCLCLCMAINAPARTMENT UNIT(TYP OF 12)3 PHASE IN1 PHASE OUT3 PHASE IN3 PHASE OUTHOUSEPANELMETER CENTER LAYOUT
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-601 602.dwg
8/11/2023 11:34:32 AME-601ELECTRICAL DETAILS OSDIGITALON/OFF/DIMMINGROOMCONTROLLERDIGITAL LIGHTING CONTROL DIAGRAM - DAYLIGHT ZONES/OCCUPANCY SENSORONE CONTROL PAIR PERZONE AS REQUIRED0-10V DIMMINGCONTROLLINE VOLTAGE (POWER IN)SWITCH LEGS (a, b, ...) PERPLANLED DRIVERSECONDARYDAYLIGHT ZONEPRIMARY DAYLIGHTZONEGENERALAREA LIGHTSTO ADDITIONAL LIGHTS ANDSWITCH ZONES PER PLANDIMMINGCONTROL CIRCUITPER PLAN120/277VPOWER INDIGITALOCCUPANCYSENSORDIGITALMULTI-ZONEDAYLIGHTSENSORPROVIDE WHERE INDICATED(NOT REQUIRED ALL SPACES)CAT5e CABLE(TYPICAL)TO ADDITIONAL PLUGLOAD CONTROLLER(S)DPCDIGITAL PLUG LOADCONTROLLERSWITCHEDRECEPTACLE(S)120VPOWER INDIGITALON/OFF/DIMDIGITALON/OFFLED DRIVERLED DRIVERENERGY CODE COMMISSIONING NOTES FOR LIGHTING AND ELECTRICALRECEPTACLE CONTROLSA.FUNCTIONAL TESTING REQUIREMENTS SHALL BE COMPLETED FOR THE CONTROLLED RECEPTACLE AND LIGHTINGCONTROL SYSTEMS INSTALLED.a.DEVELOPING A COMMISSIONING PLAN PER WSEC C408.1.2b.CONDUCTING FUNCTIONAL PERFORMANCE TESTING PER WSEC C408.1.2.2c.COMPLETING AND CERTIFYING A COMMISSIONING REPORT PER WSEC C408.1.3d.FURNISHING COMMISSIONING COMPLETION DOCUMENTATION FOR APPROVAL BY INSPECTION AUTHORITIES PER WSECC408.14e.FURNISHING ALL COMMISSIONING REPORTS AND COMMISSIONING COMPLETION DOCUMENTATION TO THE OWNER FORINCLUSION INTO THE PROJECT CLOSEOUT DOCUMENTSf.PROVIDING ALL TOOLS, EQUUPMENT, MATERIALS, SERVICES, AND LABOR REQUIRED TO IMPLEMENT THECOMMISSIONING PLAN AND TO PERFORM FUNCTIONAL TESTING AND FOLLOW UP SPOT CHECK ACTIVITIES.
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-601 602.dwg
8/11/2023 11:34:37 AME-602ELECTRICAL DETAILS 12" 13 1/8"23 1
/8
"AASHTO-H2OTRAFFIC RATED LIDPROVIDE 48-INCHBONDING STRAPNOTE1.SET HANDHOLE ON 9" DEEPGRAVEL BASE EXTENDING 6"MIN BEYOND EACH SIDE. SETFLUSH WITH FINISHED GRADE.2.STRUCTURAL PLASTICHANDHOLE MAY BE USED INLANDSCAPE AREAS.BRASS 'L' BOLTS& NUTS IN DIAGONALCORNERSOPEN BOTTOMSCALE: HANDHOLE DETAILN.T.S.26 1
/2
"17 1/4"22"12"SELECTFILLCOMPACT BACKFILL12"6"MIN.3" MIN. (TYPICAL)TRENCH WIDTH 12" MINIMUM FORSHARED UTILITY TRENCH 30" MINIMUMMINIMUM COVER:24 IN SIGNAL24 IN POWER BELOW 600V36 IN POWER ABOVE 600V12" MIN.SEPARATIONBETWEENSIGNAL &POWERFINISH WORK AS SHOWNOR SPECIFIEDFINISHED GRADEWARNING TAPE WITHMETALLIC CORE3" MIN. (TYPICAL)DIRECT BURIED PVC POWERCONDUIT(S) PER PLANDIRECT BURIED SIGNALCONDUIT(S) OR CABLE ASREQUIREDELECTRIAL UTILITYSCALE: TRENCH SECTIONN.T.S.HANDHOLESPUN ALUMINUM COLLAR24" DIAMETER CAST IN PLACE CONCRETEBASE. EXPOSED PORTION TO HAVE RUBBEDFINISH.SONOTUBE FORM (MAY BE LEFT IN PLACEBELOW GRADE)FINAL GRADERACEWAY 24" BELOW FINAL GRADEAUGERED HOLE MAY BE USED ASCONCRETE FORM BELOW 30"#3 REBAR TIES AT 12"O.C.4#5 REBAR MINIMUM 3" FROM EDGEANCHOR BASE POLEGROUT UNDER3/4"x3/4" CHAMFERSMOOTH FINISHSCALE: POLE BASE DETAILN.T.S.ANCHOR BOLTSYSTEM &SECTIONGROUNDEQUIPHVLVFRONT10FT MIN (TYP)SCALE: PADMOUNTED TRANSFORMER DETAILN.T.S.NOTE: PROVIDE CABLE RACKS ANDNYLON TIES AS REQUIRED TO SECUREAND SEPARATE HV AND LV CABLES12"MIN.9"MIN.COMPACTED CRUSHEDGRAVEL BEDKNOCK OUT SUMPTRANSFORMER VAULTUTILITY VAULT CO. #504-LAOR EQUAL (56" X 56" X 42"D)#4/0 BARE COPPERGROUND LOOP6" MIN. THICK REINFORCED6' X 6' MIN CONCRETEPAD/VAULT COVER WITHCABLE ENTRANCEGROUND RODS EACH CORNERPAD MOUNTED DISTRIBUTIONTRANSFORMERGLAVANIZED C-CHANNELEACH SIDEEXTEND HV CONDUIT UP TOHV XFMR COMPARTMENT4 3/4" DIA KNOCKOUTSEACH SIDE3/4" DIA LIFTINSERTS EACHCORNERGNGNGNNPANEL4SERVICE PANEL42511491012SERVICE XFMR11234567891011BUBBLE NOTES:DRIVEN ELECTRODE SYSTEM.GROUNDING ELECTRODE CONDUCTOR.EQUIPMENT GROUNDING BUS.BONDING JUMPER. SIZE PER NEC TABLE 250.66.GROUNDING LOCKNUT.BUILDING GROUND ELECTRODE SYSTEM. (BUILDING STEEL& COLD WATER MAIN)NOT USED.INSULATED NEUTRAL BUS.RECEPTACLE, MOTOR, & EQUIPMENT CIRCUITS. (INCLUDEEQUIPMENT GROUND CONDUCTOR)LIGHTING CIRCUIT.EQUIPMENT GROUND CONDUCTOR. SIZE PER NEC TABLE250.122SECWINDINGMETAL CONDUIT8336GGSCALE: GROUNDING DIAGRAMN.T.S.
J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21202023/AD#DESC.DATEgeneral@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Elec\23-082 E-701.dwg
8/11/2023 11:34:43 AME-701ELECTRICAL SCHEDULESPROVIDE FIELD WIRING FORCONDENSATE PUMP WITH UNITAS REQUIREDINDOOR UNIT1/2"C-3#14 + GNDCIRCUIT SIZE AS SCHEDULEDWP208V 1ØOUTDOOR UNIT3-POLE TOGGLE DISCONNECT AT UNITSQ D TYPE K OR HUBBELL #HBL7810PROVIDE FLUSH OUTLET AND DEVICEPLATE IN FINISHED SPACES2P DISCONNECTMITSUBISHI SPLIT SYSTEM HVAC CONNECTION DIAGRAM