Tahoma Terra-II - Building G - Mechanical SetLIST OF MECHANICAL DRAWINGSM-001MECHANICAL LEGEND & NOTESM-002MECHANICAL SCHEDULESM-003MECHANICAL SHEDULESM-004MECHANICAL SPECIFICATIONSM-005MECHANICAL SPECIFICATIONSM-101AFOUNDATION PLAN - BUILDING 'A'M-102BFOUNDATION PLAN - BUILDING 'B'M-103CFOUNDATION PLAN - BUILDING 'C'M-104DFOUNDATION PLAN - BUILDING 'D'M-105EFOUNDATION PLAN - BUILDING 'E'M-106FFOUNDATION PLAN - BUILDING 'F'M-107GFOUNDATION PLAN - BUILDING 'G'M-108HFOUNDATION PLAN - BUILDING 'H'M-201AMECHANICAL PLANS - BUILDING 'A'M-202AMECHANICAL PLANS - BUILDING 'A'M-203BMECHANICAL PLANS - BUILDING 'B'M-204BMECHANICAL PLANS - BUILDING 'B'M-205CMECHANICAL PLANS - BUILDING 'C'M-206CMECHANICAL PLANS - BUILDING 'C'M-207DMECHANICAL PLANS - BUILDING 'D'M-208DMECHANICAL PLANS - BUILDING 'D'M-209EMECHANICAL PLANS - BUILDING 'E'M-210EMECHANICAL PLANS - BUILDING 'E'M-211FMECHANICAL PLANS - BUILDING 'F'M-212FMECHANICAL PLANS - BUILDING 'F'M-213GMECHANICAL PLANS - BUILDING 'G'M-214GMECHANICAL PLANS - BUILDING 'G'M-215HMECHANICAL PLANS - BUILDING 'H'M-216HMECHANICAL PLANS - BUILDING 'H'M-301ENLARGED UNIT PLUMBING PLANSM-302ENLARGED UNIT PLUMBING PLANSM-303BLDG 'H' ENLARGED PLUMBING PLANSM-304PLUMBING DETAILSM-305RISER DIAGRAMSM-401ENLARGED UNIT HVAC PLANSM-402ENLARGED UNIT HVAC PLANSM-403BLDG 'H' ENLARGED HVAC PLANSVENT (V)HOT WATER (HW)COLD WATER (CW)VALVEUNIONHOSE BIBBCONCENTRIC REDUCERRELIEF VALVE OR SAFETY VALVEAUTHORITY HAVING JURISDICTIONAPPROXIMATELYARCHITECTURALAUTOMATICBRITISH THERMAL UNITBRITISH THERMAL UNIT/HOURBUILDINGCAPACITYCUBIC FEET PER MINUTECEILINGCLEANOUTCONNECTIONCONTINUE, CONTINUATIONCOLD WATERDEGREE FAHRENHEITDIAMETERDOWNDISHWASHERDRAWINGDRY BULBEACHENTERING AIR TEMPERATUREEFFICIENCYELECTRICAL, ELECTRICEXTERNAL STATIC PRESSUREEXHAUSTFLOOR DRAINFLEXIBLEFLOORFLOOR CLEAN OUTFULL LOAD AMPSGALLONGALVANIZEDHOT WATERINCHMAXIMUMMECHANICALMANUFACTURERMIDDLEMINIMUMNUMBERNOT TO SCALEOUTSIDE AIRPRESSURE DROPPHASEREFERENCEREQUIREDROOMSURFACE CLEANOUTSANITARY SEWERTEMPERATURETYPICALUNLESS NOTED OTHERWISEUNIFORM PLUMBING CODEVENT THROUGH ROOFVENTWASTEWITHWATTWET BULBWALL CLEAN OUTWASHINGTON STATE ENERGY CODEAHJAPPROXARCHAUTOBTUBTUHBLDGCAPCFMCLGCOCONNCONTCWDEG F, °FDIA, ØDNDWDWGDBEAEATEFFELECESPEXHFDFLEXFLFCOFLAGALGALVHWINMAXMECHMFRMIDMINNONTSOAPDPHREFREQ'DRMSCOSSTEMPTYPUNOUPCVTRVWW/WAWBWCOWSECFLOOR CLEANOUT (FCO)WASTE OR SOIL (W)PIPE DOWNPIPE UPPIPE TEE IN LINE, BRANCH PIPE DOWNP300ADETAIL IDENTIFICATION NUMBERSHEET ON WHICH DETAIL IS SHOWNNOTE:FOR DESCRIPTION OF OTHER ABBREVIATIONSSEE SCHEDULES AND ABBREVIATIONS LISTED IN UPC.PLUMBING GENERAL NOTES1.PIPING MATERIAL SCHEDULE:PIPINGLOCATIONMATERIAL JOINTCOLD WATER MAINSTYPE L COPPER SOLDER OR "PRESS-FIT"COLD WATERALLPEX MECHANICALHOT WATERALLPEXMECHANICALCW & HW - HEAT TRACEDALLTYPE L COPPERSOLDER OR "PRESS-FIT"WASTEALLABS OR PVCSOLVENT CEMENTVENTALLABS OR PVCSOLVENT CEMENTCONDENSATE DRAINALLPVCSOLVENT CEMENT2.PIPING INSULATION SCHEDULE:PIPING PIPEINSULATIONINSULATIONCONDUCTIVITY TYPESIZETYPE THICKNESSBTU-IN/HR-SF-°FCOLD WATER (ABOVEGROUND) >1"RUBATEX 1/2" 0.265HOT WATER ALLRUBATEX 1/2" 0.265ALL PIPING INSULATION AND COVERINGS SHALL HAVE AN ASTM FLAME SPREAD RATING OF 25 OR LESS AND AN ASTMSMOKE DEVELOPED RATING OF 50 OR LESS. REFRIGERANT PIPING AND INSULATION EXPOSED TO OUTDOORS SHALLBE PROTECTED BY METAL JACKETING.3.PRIOR TO ROUGH-IN FOR ALL PLUMBING FIXTURES, VERIFY FIXTURE LOCATIONS, FIXTURE MOUNTING HEIGHT ANDROUGH-IN LOCATIONS WITH ARCHITECTURAL FLOOR PLANS AND ARCHITECTURAL INTERIOR ELEVATIONS.4.PLUMBING PLANS ARE SCHEMATIC AND DO NOT SHOW EVERY OFFSET REQUIRED, PRIOR TO COMMENCING ROUGH-IN,COORDINATE WITH ALL TRADES FOR CLEARANCE REQUIREMENTS. OFFSETS ARE REQUIRED TO ACCOMMODATEBUILDING FRAMING & OTHER ELEMENTS OF CONSTRUCTION.5.MATERIALS, METHODS AND INSTALLATION SHALL COMPLY WITH CODE.6.PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTEDMATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL.7.PROVIDE DIELECTRIC CONNECTIONS BETWEEN DISSIMILAR METALS.8.INSTALL CLEANOUTS PER CODE AND SO THEY ARE EASILY ACCESSIBLE.9.PROVIDE MEANS TO ACCOMMODATE PIPING SYSTEM EXPANSION AND CONTRACTION.10.VERIFY SPACE AVAILABLE FOR ALL PLUMBING & ALL ROUTING. THIS DESIGN IS PRELIMINARY ONLY & REQUIRES FINALREVIEW SIZING CHECK; COORDINATION BY THE INSTALLING PLUMBER. SOME WASTE PIPES MAY REQUIRE 1% SLOPE &CORRESPONDING PIPE SIZE ADJUSTMENTS.11.PIPE ALL WATER HEATER RELIEF VALVES TO SAFE POINT OF DISCHARGE PER CODE.12.PROVIDE VALVE BOX AT REFRIGERATORS FOR ICE MAKER, MAY BE FED FROM ADJACENT FIXTURE.13.DISHWASHER MAY BE SERVED OFF HW TO ADJACENT SINK, PROVIDE AIRGAP FITTING IN DRAIN DISCHARGE PER CODE.14.THESE DRAWINGS ARE PROVIDED FOR PERMIT PURPOSES ONLY. FINAL INSTALLATION DESIGN IS BY THECONTRACTOR.15.INSTALL ALL PIPING CONCEALED UNLESS NOTED OTHERWISE.16.LOCATE ITEMS FOR ADA ACCESS AT ADA UNITS.17.PROVIDE SUBMITTALS ON ALL PRODUCTS TO OWNER FOR REVIEW PRIOR TO ORDERING MATERIALS.18.COORDINATE W/ ELECTRICAL CONTRACTOR, LOCATIONS & POWER WIRING FOR ALL ITEMS REQUIRING POWER.MECHANICAL LEGENDROUND DUCTELBOW W/ TURNING VANESDUCT UP (RECTANGULAR)DUCT UP (RECTANGULAR)DUCT DOWN (RECTANGULAR)DUCT UP (ROUND)DUCT DOWN (ROUND)DUCT DOWN (RECTANGULAR)SSWITCH FOR DOA UNIT1.CONTRACTOR SHALL CAREFULLY COORDINATE WORK W/ ALL OTHER TRADES, ESPECIALLY IN CEILING SPACES WHERE SPACE ISTIGHT. SHEET METAL CONTRACTOR SHALL HAVE PRIORITY OVER OTHER TRADES IN CEILING SPACE WHERE CONFLICTS OCCUR.2.ALL DUCTWORK SHOWN IS SCHEMATIC, CONTRACTOR SHALL PROVIDE ALL OFFSETS/ELBOWS AS REQ'D TO ALLOW ROUTINGAROUND STRUCTURE, ELECTRICAL, & OTHER INTERFERENCES.3.DUCTS SHALL BE CONSTRUCTED TO 1" PRESSURE CLASS & SEAL CLASS C (UNO).4.DUCT WORK SHALL BE GALVANIZED STEEL, PER CODE & SMACNA DUCT CONSTRUCTION STANDARDS.5.WALL CAPS SHALL BE GALVANIZED STEEL OR ALUMINUM, W/ FINISH PER ARCHITECT/ OWNER.6.THESE DRAWINGS ARE PROVIDED FOR PERMIT PURPOSE ONLY. FINAL INSTALLATION DESIGN IS BY THE CONTRACTOR.7.EXHAUST OUTLETS SHALL BE LOCATED MINIMUM 3' AWAY FROM OPERABLE OPENINGS & 10' FROM MECHANICAL INTAKES.8.LOCATE ITEMS FOR ADA ACCESS AT ADA UNITS.9.PRIOR TO ORDERING EQUIPMENT & MATERIALS, VERIFY SPACE AVAILABLE.10.PROVIDE SUBMITTALS ON ALL PRODUCTS TO OWNER FOR REVIEW PRIOR TO ORDERING MATERIALS.MECHANICAL GENERAL NOTESDESCRIPTIONSYMBOLDESCRIPTIONSYMBOLTTHERMOSTATCHECK VALVETHERMOMETERSTRAINER WITH BLOW-OFF VALVEMENERGY CODE NOTES1.MECHANICAL SYSTEMS SHALL COMPLY WITH THE WASHINGTON STATE ENERGY CODE - RESIDENTIAL PROVISIONS, PRESCRIPTIVEAPPROACH; SECTION 51-11R OF THE WASHINGTON ADMINISTRATIVE CODE (WAC).2.TEMPERATURE CONTROL SYSTEM SHALL HAVE A MINIMUM DEAD BAND OF 5 DEGREES.3.HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF PROVIDING NIGHT SETBACK & SEVEN DIFFERENTDAILY SCHEDULES.WATER METERADDITIONAL ENERGY EFFICIENCY POINTSOPTION #3.45.5DESCRIPTIONDUCTLESS MINI-SPLIT HEAT PUMP SYSTEM, ZONAL CONTROL: IN HOMES WHERETHE PRIMARY SPACE HEATING SYSTEM IS ZONAL ELECTRIC HEATING, ADUCTLESS MINI-SPLIT HEAT PUMP SYSTEM WITH A MINIMUM HSPF OF 10.0 SHALLBE INSTALLED AND PROVIDE HEATING TO THE LARGEST ZONE OF THE HOUSINGUNIT.WATER HEATING SYSTEM SHALL INCLUDE: ELECTRIC HEAT PUMP WATERHEATER MEETING THE STANDARDS FOR TIER III OF NEEA'S ADVANCED WATERHEATING SPECIFICATION.CREDITS2.02.5VENTILATION CODE NOTESA.VENTILATION IS BEING PROVIDED BY THE USE OF “WHOLE HOUSE MECHANICAL VENTILATION SYSTEM” PER IMC 403.4 & LOCALEXHAUST FANS PER IMC 403.4.7.1.AN ERV IS USED AS THE WHOLE HOUSE VENTILATION FAN (WITH CONTINUOUS OPERATION) WITH ENERGY RECOVERY PERTHE IMC AND WSEC.2.SYSTEM IS BALANCED TYPE PER IMC.3.WHERE USED TO SERVE BATHROOMS AIRFLOW IS INCREASED TO MEET IMC 403.4.7.B.MINIMUM VENTILATION PERFORMANCE (PER 2018 IMC, WASHINGTON STATE AMENDMENTS, TABLE 403.4.2):BEDRMS SFOA CFM ADJUSTMENT FACTOR ADJUSTED CFM CFM USED 1 500-1000 30 NOT DISTRIBUTED 1.25 37.5 50 2500-1000 35 NOT DISTRIBUTED 1.25 43.75 50C.CONTROL & OPERATION (IMC 403.4.5):1.LOCATION OF CONTROLS: CONTROLS FOR ALL VENTILATION SYSTEMS SHALL BE READILY ACCESSIBLE BY THE OCCUPANT.2.INSTRUCTIONS: OPERATING INSTRUCTIONS FOR WHOLE HOUSE VENTILATION SYSTEMS SHALL BE PROVIDED TO THEOCCUPANT BY THE INSTALLER OF THE SYSTEM.3.LOCAL VENTILATION SYSTEMS: LOCAL VENTILATION SYSTEMS SHALL BE CONTROLLED BY MANUAL SWITCHES.4.CONTINUOUS WHOLE HOUSE SYSTEMS: FANS SHALL OPERATE CONTINUOUSLY AND BE EQUIPPED WITH AN OVERRIDECONTROL. A CLEARLY VISIBLE LABEL SHALL BE AFFIXED TO THE CONTROLS READING “WHOLE HOUSE VENTILATION”.LEAVE ON UNLESS OUTDOOR AIR QUALITY IS POOR.D.LOCAL EXHAUST SYSTEMS (IMC 403.4.7): SHALL BE DESIGNED AND INSTALLED TO MEET ALL OF THE CRITERIA BELOW:1.LOCAL EXHAUST SHALL DISCHARGE OUTDOORS.2.EXHAUST OUTLETS SHALL COMPLY WITH IMC 501.3, WA STATE AMENDMENTS.3.PRESSURE EQUALIZATION SHALL COMPLY WITH IMC 501.4.4.EXHAUST DUCTS IN SYSTEMS WHICH ARE DESIGNED TO OPERATE INTERMITTENTLY SHALL BE EQUIPPED WITHBACK-DRAFT DAMPERS PER IMC 403.4.6.1 AND IMC 501.3.2.5.ALL EXHAUST DUCTS IN UNCONDITIONED SPACES SHALL BE INSULATED TO A MINIMUM OF R-8.6.TERMINAL OUTLETS SHALL HAVE AT LEAST THE EQUIVALENT NET FREE AREA OF THE DUCTWORK.7.TERMINAL OUTLETS SHALL BE SCREENED OR OTHERWISE PROTECTED AS REQUIRED BY IMC 501.3.2.G.EXHAUST FANS (IMC 403.4.6.1 & IMC 403.4.7.2): EXHAUST FAN CONSTRUCTION AND SIZING SHALL MEET IMC PERFORMANCE &ACOUSTIC CRITERIA. INSTALLATION OF THE SYSTEM OR EQUIPMENT SHALL BE CARRIED OUT IN ACCORDANCE WITHMANUFACTURER'S INSTALLATION INSTRUCTIONS.M-001MECHANICAL LEGEND & NOTESJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082C:\Users\NickH.HBHU\appdata\local\temp\AcPublish_17104\23-082_M-001-004.dwg
8/07/2023 4:00:01 PM
ELECTRIC MOTOR EFFICIENCYMOTOR HPTYPENOMINAL RPMMINIMUM EFFICIENCY0.25 OR LESSSINGLE PHASE180068.5%0.33SINGLE PHASE180072.4%0.5SINGLE PHASE180076.2%0.75SINGLE PHASE180081.8%1SINGLE PHASE180082.6%1THREE PHASE180083.5%1.5THREE PHASE180086.5%2THREE PHASE180086.5%3THREE PHASE180086.9%NOTES: ALL FAN AND PUMP MOTORS SHALL MEET OR EXCEED THE SCHEDULED EFFICIENCIES IN ORDER TO COMPLY WITH THE WASHINGTON STATE ENERGY CODE (WSEC)FAN SCHEDULESYMBOLBASIS OF DESIGNMANUFACTURERAND SERIES NO.TYPEAREA SERVEDCFMESPRPMWHEELDIAELECTRICALDRIVECONTROLMAXWEIGHTLBSREMARKSPOWERVOLTS / PHEF-50PANASONICFV-0511VKL2CEILING FANW/ LIGHTAPARTMENT:BATHROOM FAN500.375"895-19.4WATTS115/1DIRECT20=SPEED CONTROL=DISCONNECTACCESSORIES:12NOTE:ALL ITEMS ARE USED MULTIPLE TIMES ON PLANS; SEE PLANS FOR QUANTITIES AND LOCATIONS12ELECTRIC HEATER SCHEDULESYMBOLITEMDESCRIPTIONBASIS OF DESIGNMANUFACTURER ANDSERIES NO.AREA SERVEDEQUIPMENTCAPACITYELECTRICALREMARKSPOWERVOLTS / PHEH-1500* WALL HEATERKING"PAW" SERIESAPARTMENTS1.5 KW1500W208/1W/ CONTACTOR & TRANSFORMER FORREMOTE LOW-VOLTAGE THERMOSTATDH-1*DUCT HEATERRENEWAIRERH SERIESDOA-13,412 BTUH1000W,8.3A120/1SIZE A, SCR CONTROLDH-2DUCT HEATERRENEWAIREDOA-213,648 BTUH4 KW208/1SCR CONTROL* USED IN MULTIPLE LOCATIONS, SEE PLANS FOR QUANTITIES & LOCATIONS.PLUMBING FIXTURE SCHEDULESYMBOLDESCRIPTIONWVCWHWREMARKSP-1AWATER CLOSET4"2"1/2"-FLOOR MOUNT -TANK TYPE -ADA ACCESSIBLE, 1.0 GPF MAXP-3ALAVATORY2"2"1/2"1/2"DROP-IN,ADA ACCESSIBLE, 0.5 GPM MAXP-5AKITCHEN SINK2"2"1/2"1/2"DOUBLE BOWL, ADA ACCESSIBLE,W/ DISPOSER, 1.5 GPM MAXP-5BKITCHEN SINK2"2"1/2"1/2"SINGLE BOWL, W/ DISPOSER,1.5 GPM MAXP-9ATUB/SHOWER2"2"1/2"1/2"ADA ACCESSIBLE,1.75 GPM MAXP-9BTUB/SHOWER2"2"1/2"1/2"1.75 GPM MAXP-9CSHOWER2"2"1/2"1/2"1.75 GPM MAXP-10AWALL HYDRANT--3/4"-WALL MOUNTNON-FREEZEP-11BFUNNEL FLOOR DRAIN2"2"--W/ TRAP PRIMER CONNECTIONP-12AWASHER BOX2"2"1/2"1/2"PROVIDE DRAIN PAN FOR WASHERP-12BREFRIGERATOR BOX--1/2"-3= PROVIDE 2 POWER CONNECTIONS AND 2SWITCHES, 1 FOR FAN, 1 FOR LIGHT.S3NOTES:1.CONFIRM ALL FIXTURE TYPE & SELECTIONS WITH OWNER & ARCHITECT FOR UNIFORMITY W/OTHER FACILITIES SUITABILITY. VERIFY SPACE AVAILABLE FOR ALL FIXTURES PRIOR TOORDERING. VERIFY ALL FIXTURE ROUGH-IN REQUIREMENTS.2.CONFIRM LEFT HAND/RIGHT HAND CONFIGURATION FOR ALL FIXTURES.3.ADA ACCESSIBLE SHOWERS SHALL HAVE: 1/2" OR LESS THRESHOLD, W/ SINGLE LEVER SHOWERCONTROLS WITHIN 36" OF THE SHOWER SEAT. HANDHELD SHOWER ASSEMBLY SHALL COMPLYW/ ASME A112.18.1.4.PROVIDE ADA ACCESSIBLE FIXTURES AT ALL ADA TYPE UNITS.HEAT PUMP SCHEDULE - SPLIT SYSTEM TYPESYMBOLBASIS OF DESIGNMANUFACTURER ANDSERIES NO.AREA SERVEDCOOLING CAP. *HEATING CAP. **A - INDOOR UNIT ***B - OUTDOOR UNIT ***FILTERSMIN.OACFMMAX.OUTDOORUNITWEIGHTLBSMAX.INDOORUNITWEIGHTLBSREMARKSTOTALMBHSENS.MBHEFFICIENCYMBHEFFICIENCYFANCOMPRESSORFANELECTRICALTYPEMIN. SFCFMESPPWRQTYRLA (EA)QTYPWRMCAMOPVOLTS/PHHP-1MITSUBISHIMSZ-HM12 / MUZ-HM121 BEDDWELLING UNIT129.318 SEER12.210.0 HSPF400-30 W16.2155 W915208/1MFR.STD--10030INDOOR UNIT POWERED FROMOUTDOOR UNITHP-2MITSUBISHIMSZ-HM18 / MUZ-HM182 OR 3 BEDDWELLING UNIT1815.518 SEER1810.0 HSPF625-30 W17.4155 W1015208/1MFR.STD--10040INDOOR UNIT POWERED FROMOUTDOOR UNIT* COOLING CAPACITY IS AHRI RATING: AT 85° F DB; 66° F WB INDOOR COIL EAT AND 95° F OUTDOOR COIL EAT.** HEATING CAPACITY IS AHRI HI-TEMP RATING: AT 70° F DB INDOOR EAT AND 47° F DB; 43° F WB OUTDOOR COIL EAT.*** ON PLANS "A" DESIGNATES INDOOR UNIT, "B" DESIGNATES OUTDOOR UNIT. (E.G. HP-1B IS HP-1 OUTDOOR UNIT).MISCELLANEOUS SCHEDULESYMBOLBASIS OF DESIGNMANUFACTURER ANDSERIES NO.TYPEAREA / UNIT SERVEDCFMNOMINALSIZEELECTRICALREMARKSWATTSVOLTS/PHHT-1RAYCHEM HWATDOMESTIC HWPIPE HEAT TRACEDOMESTIC HW LINES--1500240/1DOMESTIC HW TYPE W/ POWER CONNECTION KIT;PROVIDE W/ GROUND FAULT PROTECTION SET TO 105°FHT-2RAYCHEM XLFREEZE PROTECTPIPE HEAT TRACEEXTERIOR CW LINES-5W/ LF1500240/1DOMESTIC HW TYPE W/ POWER CONNECTION KIT;PROVIDE W/ GROUND FAULT PROTECTION SET TO 40°FNOTES: 1.PROVIDE ALL INDOOR UNITS WITH CONDENSATE PUMPS.2.PROVIDE ALL INDOOR UNITS WITH WIRED PROGRAMMABLE THERMOSTATS.3. HP-1 & -2 USED MULTIPLE TIMES ON PLANS; SEE PLANS FOR QUANTITIES AND LOCATIONS.DEDICATED OUTSIDE AIR UNITSYMBOLITEM DESCRIPTIONBASIS OF DESIGNMANUFACTURER ANDSERIES NO.AREA SERVEDSUPPLY FANEXHAUST FANUNITELECTRICALENERGYRECOVERYSENSIBLEEFFICIENCYFILTERSMAX UNITWEIGHT(LBS)REMARKSTYPECFMESPDRIVETYPECFMESPDRIVEMCAVOLTS/PHDOA-1ENERGY RECOVERYVENTILATOR - INDOORRENEWAIRESL 75 HWHOLE HOUSEVENTILATION -APARTMENTSPLENUM500.6"DIRECTPLENUM500.6"DIRECT10115/182%2" MERV 835EC MOTORSDOA-2ENERGY RECOVERYVENTILATOR - INDOORRENEWAIRE HE1XINVBLDG H - COMMONAREASPLENUM4900.6"DIRECTPLENUM4900.6"DIRECT18.2115/160%2" MERV 8350EC MOTORSITEMS ARE USED MULTIPLE TIMES - SEE PLANS FORQUANTITIES AND LOCATIONS.FOR CONTINUOUS OPERATION. PROVIDE WALL CONTROLSWITH LABEL READING "WHOLE HOUSE VENTILATION (LEAVEON UNLESS OUTDOOR AIR QUALITY IS VERY POOR)".12NOTE:PROVIDE DOA'S WITH ELECTRIC DUCT HEATERS, SEEELECTRICAL DUCT HEATER SCHEDULE, M-002.12WATER HEATER SCHEDULESYMBOLBASIS OF DESIGNMANUFACTURER ANDSERIES NO.TYPEAREA SERVEDTOTALWATTAGEHEAT PUMPEFF. (COP)STORAGE(GAL)DOMESTIC HWELECTRICALREMARKSGPHEWTLWTVOLTS/PHWH-1BRADFORD WHITEAEROTHERMTANK, HEAT PUMP /ELECTRIC HYBRIDRESIDENCEDOMESTIC HW4.5 KW3.39502140130208/122" DIA. TANK W/ EXHAUST DUCTING KITWH-2CHRONOMITE CM SERIESELECTRICINSTANTANEOUSPUBLICRESTROOM3.12 KW---40110208/1W/ FIELD ADJUSTABLE TEMP DIALUSED MULTIPLE TIMES ON PLANS; SEE PLANS FOR QUANTITIES AND LOCATIONS11M-002MECHANICAL SCHEDULESJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082C:\Users\NickH.HBHU\appdata\local\temp\AcPublish_17104\23-082_M-001-004.dwg
8/07/2023 4:00:02 PM
VRF INDOOR HEAT PUMP SCHEDULESYMBOLBASIS OF DESIGNMANUFACTURER ANDSERIES NO.TYPEAREA SERVEDSERVED BYCAPACITY (MBH)CFMFILTERSUNIT ELECTRICALMAXWEIGHTLBSREMARKSCOOLINGHEATINGTYPEMCAVOLT/PHHP-101MITSUBISHIPLFY-P05CEILING CASSETTE 24" x 24"BLDG H - LEASE 1CU-1/BC-15.05.6280WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERHP-102MITSUBISHIPLFY-P05CEILING CASSETTE 24" x 24"BLDG H - LEASE 2CU-1/BC-15.05.6280WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERHP-103MITSUBISHIPKFY-P08WALL MOUNTEDBLDG H -MULTI-PURPOSECU-1/BC-18.09.0200WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERHP-104MITSUBISHIPKFY-P18WALL MOUNTEDBLDG H - LOUNGECU-1/BC-118.020.0300WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERHP-105MITSUBISHIPKFY-P15WALL MOUNTEDBLDG H - FITNESSCU-1/BC-115.017.0300WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERHP-106MITSUBISHIPKFY-P15WALL MOUNTEDBLDG H - YOGACU-1/BC-115.017.0300WASHABLE0.24208/150W/ CONDENSATE PUMP, ME CONTROLLERVRF OUTDOOR HEAT PUMP SCHEDULESYMBOLBASIS OF DESIGNMANUFACTURERAND SERIES NO.AREA SERVEDCOOLING CAPHEATING CAPACITYMAX.WEIGHTLBSUNIT ELECTRICALREMARKSTOTALMBHEFFMBHEFFMCAMFSVOLTS/PHCU-1MISUBISHIMXZ SERIESBLDG H - COMMON AREAS6013.3 EER664.10 COP3504650208/1 * COOLING CAPACITY IS AHRI RATING: AT 80°F DB; 67°F WB INDOOR COIL EAT AND 95°F OUTDOOR COIL EAT. ** HEATING CAPACITY IS AHRI HI-TEMP RATING: AT 70°F DB INDOOR COIL EAT AND 47°F DB; 43°F WB OUTDOOR COIL EAT.M-003MECHANICAL SCHEDULESJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-001-004.dwg
8/08/2023 10:52:38 AM
MECHANICAL SPECIFICATIONS:22 05 00 - MECHANICAL COMMON WORK RESULTS1.CODE COMPLIANCE: ALL WORK SHALL COMPLY WITH ALL LOCAL CODES AND ORDINANCES.WORKERS ASSIGNED TO THIS PROJECT SHALL BE FAMILIAR AND KNOWLEDGEABLE OF ALLAPPLICABLE CODES; BY VIRTUE OF BIDDING THE PROJECT THE CONTRACTOR REPRESENTSTHAT WORKERS HAVE SUCH KNOWLEDGE. THROUGHOUT THE PROJECT DOCUMENTS, ITEMSARE SHOWN OR SPECIFIED IN EXCESS OF CODE REQUIREMENTS; IN ALL SUCH CASES, THEWORK SHALL BE DONE SO THAT CODE REQUIREMENTS ARE EXCEEDED AS INDICATED.2.DRAWINGS: DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL ARRANGEMENT OFTHE CONSTRUCTION, AND THEREFORE DO NOT SHOW ALL NECESSARY OFFSETS, FITTINGS,AND ACCESSORIES WHICH ARE REQUIRED TO FORM COMPLETE AND OPERABLE SYSTEMS.3.FIELD VERIFICATION: CHECK FIELD CONDITIONS AND VERIFY ALL MEASUREMENTS ANDRELATIONSHIPS INDICATED ON THE DRAWINGS BEFORE SUBMITTING BIDS AND AGAINBEFORE PROCEEDING WITH THE WORK.4.PERMITS, FEES AND INSPECTIONS: OBTAIN AND PAY FOR ALL PERMITS, LICENSES, FEES ANDINSPECTIONS AS REQUIRED BY THE AHJ AND UTILITIES. COORDINATE WITH AHJ ANDARRANGE SYSTEM INSPECTIONS. MAINTAIN RECORDS OF ALL SYSTEM TESTS AND AHJINSPECTIONS.6.QUALITY ASSURANCE CHECKS: PRIOR TO PROVIDING SUBMITTALS VERIFY THAT PROPOSEDPRODUCT MEETS PROJECT REQUIREMENTS; INCLUDING: LEAD/DELIVERY TIMES COMPATIBLEWITH SCHEDULE, PROPER VOLT/PHASE, WEIGHT DOES NOT EXCEED THAT ALLOWED, SPACEVERIFICATION HAS BEEN DONE, PRODUCT IS SUITABLE FOR CONDITIONS, MANUFACTURER ISACCEPTABLE, SPECIFIED FEATURES ARE PROVIDED, EQUIPMENT EFFICIENCIES COMPLY WITHCODE.7.SUBMITTALS - PRODUCT DATA: SHALL SUBMIT MANUFACTURERS PRODUCT DATA FOR ALLPRODUCTS PROPOSED TO BE USED FOR REVIEW. PRODUCTS SHALL NOT BE USED UNTILAPPROVED BY THE OWNER OR HIS REPRESENTATIVE. SUBMITTALS MAY BE ELECTRONICTYPE IN “PDF” FORMAT; SUBMIT WITH TABLE OF CONTENTS.8.SUBMITTALS - SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR INDICATED SYSTEMS FORREVIEW. PRODUCTS SHALL NOT BE ORDERED OR INSTALLED UNTIL SHOP DRAWINGS HAVEBEEN APPROVED. SEE INDIVIDUAL SPECIFICATION SECTIONS AND DRAWING NOTES FORSYSTEMS AND AREAS REQUIRING SHOP DRAWINGS. SHOP DRAWINGS SHALL BECONTRACTOR PREPARED DRAWINGS SHOWING THE DETAILS OF THE INSTALLATION. SUBMITPDF OR ACAD FILES WITH A TRANSMITTAL.9.RECORD DRAWINGS: MAINTAIN A SET OF CONTRACT PLANS AT THE PROJECT SITE UPONWHICH ALL CHANGES FROM THE AS-BID PLANS ARE NOTED. AT THE COMPLETION OF THEPROJECT DELIVER TO THE OWNER ONE COMPLETE SET OF THESE RECORD DRAWINGS.10.PROTECTION AND DAMAGE: PROTECT ALL ITEMS FROM DAMAGE OF ANY KIND (INCLUDESWATER, CORROSION, FREEZING, DIRT/DUST, CONDENSATION, PHYSICAL DAMAGE, ETC.) BOTHIN STORAGE AND WHEN INSTALLED, UNTIL FINAL PROJECT ACCEPTANCE. PROTECTBUILDING AND SITE AREAS FROM DAMAGE. RESTORE ALL EXISTING ITEMS THAT AREDAMAGED TO PRE-CONSTRUCTION CONDITIONS (OR BETTER). REPLACE ALL NEW ITEMSTHAT ARE DAMAGED WITH NEW, EXCEPT WHERE CLEANING OR REPAIR CAN RESTORE THEITEM TO A NEW CONDITION, SATISFACTORY TO THE OWNER.11.COORDINATION: COORDINATE ALL CONSTRUCTION ACTIVITIES WITH OTHER TRADES,INCLUDING THE RELATIVE LOCATION OF ITEMS, SCHEDULING THE WORK, ANDINTERCONNECTIONS OF SYSTEMS. COORDINATE WITH THE OWNER AND COOPERATE FULLYSO AS TO MINIMIZE CONFLICTS AND TO ALLOW FULL OWNER USAGE (UNO) OF INDICATEDAREAS DURING CONSTRUCTION.12.FINAL INSPECTION: PRIOR TO ACCEPTANCE OF THE WORK, PUT ALL SYSTEMS INTOOPERATION FOR A PERIOD OF NOT LESS THAN 5 WORKING DAYS SO THAT THEY MAY BEINSPECTED BY THE OWNER.13.INSTRUCTION: PROVIDE INSTRUCTIONS AND DEMONSTRATIONS FOR THE OWNER'SREPRESENTATIVES ON THE OPERATION AND MAINTENANCE OF ALL EQUIPMENT.14.O&M MANUALS: PROVIDE O&M MANUALS FOR ALL EQUIPMENT, INDICATING REQUIREDMAINTENANCE. INCLUDE: SIZE OF ALL FILTERS, BELTS, AND SIMILAR ITEMS REQUIRINGROUTINE REPLACEMENT; LIST OF CONTACTS FOR SERVICE AND PARTS FOR EQUIPMENT.15.WARRANTY: ALL WORK AND EQUIPMENT SHALL BE WARRANTED TO BE FREE FROM DEFECTSAND CAPABLE OF PROVIDING SATISFACTORY OPERATION FOR A PERIOD OF ONE YEAR AFTERPROJECT FINAL ACCEPTANCE.16.COMPLETE SYSTEMS: NOT ALL NECESSARY MATERIALS TO PERFORM THE WORK REQUIREDARE SPECIFIED OR SHOWN. CONTRACTOR SHALL PROVIDE ALL ITEMS NEEDED TO HAVECOMPLETED PROPERLY OPERATING SYSTEMS; ITEMS PROVIDED SHALL BE OFCOMMERCIAL/INSTITUTIONAL QUALITY, CONSISTENT WITH THE QUALITY OF RELATED ITEMSPROVIDED ON THE PROJECT.17.IDENTIFICATION:A.PIPING: LABEL ON 20 FOOT CENTERS WITH SELF-STICKING COLORED MARKERS,LETTERED TO IDENTIFY THE PIPE CONTENTS, AND BANDED AT EACH END WITH ARROWTAPE INDICATING THE DIRECTION OF GLOW. MARKERS SHALL BE SIMILAR AND EQUAL TOBRADY "SYSTEM 1." LETTERING AND COLORS SHALL COMPLY WITH ANSI A13.1. INADDITION, PIPING SHALL BE PAINTED, COLORS AS SELECTED BY OWNER.B.VALVES: LABEL WITH IDENTIFICATION TAGS MADE OF ENGRAVED PHENOLIC MATERIAL,WITH 1/8” HIGH WHITE LETTERING ON A BLACK BACKGROUND, ENGRAVED WITHABBREVIATION OF SYSTEM SERVED, AND INDICATION OF THE FUNCTION OF THE VALVE.CHAIN TAG TO VALVE.C.EQUIPMENT: LABEL WITH IDENTIFICATION TAGS MADE OF ENGRAVED PHENOLICMATERIAL, WITH 1/4” HIGH WHITE LETTERING ON A BLACK BACKGROUND, ENGRAVEDWITH EQUIPMENT I.D. (SAME AS USED ON PLANS) AND AREA SERVED. PRE-DRILL ANDANCHOR TO EQUIPMENT WITH TWO SCREWS.D.CONTROLS: LABEL CONTROL COMPONENTS WITH IDENTIFICATION TAGS MADE OFENGRAVED PHENOLIC MATERIAL, WITH 1/8” HIGH WHITE LETTERING ON A BLACKBACKGROUND, ENGRAVED WITH ITEM IDENTIFIER MATCHING THAT USED ON CONTROLSHOP DRAWINGS. EXCEPT THAT ROOM THERMOSTATS AND CO2 SENSORS DO NOTREQUIRE LABELS; ROOM EXHAUST FAN SWITCHES SHALL BE LABELED IN A GENERICFASHION TO BE UNDERSTOOD BY ROOM USER.18.TESTING: ALL PIPING AND DUCT SYSTEMS SHALL BE TESTED PER CODE REQUIREMENTS.PRESSURIZED PIPING SYSTEMS SHALL BE PRESSURE TESTED TO AT LEAST 1.5 TIMES THESYSTEMS OPERATING PRESSURE.19.CONTRACTOR LAY-OUT: THE CONTRACTOR IS REQUIRED TO DO FURTHER DESIGN ANDLAYOUT TO FINALIZE THE DESIGN SHOWN ON THE PROJECT DRAWINGS. SUCH WORKINCLUDES LAYOUT SKETCHES TO VERIFY RISES AND DROPS IN PIPING AND DUCTWORK,COORDINATION OF ELEVATIONS WITH OTHER TRADES, SELECTING FINAL EQUIPMENTLOCATIONS, AND NOTIFYING OTHER TRADES OF ITEMS TO BE RELOCATED, ETC. THEENGINEER HAS NOT BEEN HIRED TO DO A FULL DESIGN; THIS IS A "DESIGN ASSIST" SET OFDOCUMENTS.20.SEISMIC: ALL PIPING, DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AND BRACED FORTHE SEISMIC CATEGORY FOR THIS PROJECT PER CODE.21.BUILDING ACCESS DOORS: HINGED LOCKABLE STEEL ACCESS DOORS, FOR WALL OR CEILINGINSTALLATION. MINIMUM 16 GAUGE FRAME AND 14 GAUGE DOOR, CONCEALED HINGE, CAMAND CYLINDER LOCK, ANCHORING PROVISIONS, AND 1: WIDE FRAME TO CONCEAL ROUGHBUILDING OPENING. PROVIDE OF 18-8 STAINLESS STEEL CONSTRUCTION WITH NO. 4 FINISHWHERE USED IN RESTROOMS, LOCKER ROOMS, KITCHENS, AND SIMILAR "WET" AREAS.PROVIDE OF STEEL CONSTRUCTION WITH PRIME COATED FINISH IN OTHER AREAS. SIZESHALL BE 12" X 12" (UNLESS INDICATED OTHERWISE) BUT SHALL BE LARGE ENOUGH TOALLOW NECESSARY ACCESS TO ITEM BEING SERVED AND SIZED TO ALLOW REMOVAL OF THEITEM (WHERE ACCESS DOOR IS THE ONLY MEANS OF REMOVAL WITHOUT DISTURBING FIXEDCONSTRUCTION). DOOR SHALL MAINTAIN FIRE RATING OF ELEMENT INSTALLED IN;REFERENCE DRAWINGS FOR REQUIRED RATING. ACCESS DOORS SHALL ALL BE KEYEDALIKE. PROVIDE TWO (2) KEYS FOR EACH DOOR. PROVIDE ACCESS DOORS TO ALLCONCEALED ITEMS REQUIRING SERVICE OR FUTURE REPLACEMENT. (I.E. TRAP PRIMERS,VALVES, DAMPER ACTUATORS, ETC.).22.OFFSETS/FITTINGS: INCLUDE ALL NECESSARY FITTINGS AND OFFSET TO COMPLETELYCONNECT UP ALL SYSTEMS, MAINTAIN CLEAR ACCESS PATHS TO EQUIPMENT, AND COMPLYWITH ALL PROJECT REQUIREMENTS. OFFSETS ARE REQUIRED TO ROUTE PIPING AND DUCTSAROUND BUILDING STRUCTURAL ELEMENTS, ROOF SLOPES, MECHANICAL SYSTEMS,ELECTRICAL SYSTEMS, AND NUMEROUS OTHER ITEMS. DUE TO THE SCHEMATIC NATURE OFTHE PLANS SUCH OFFSETS ARE NOT SHOWN. DETERMINE THE QUANTITY OF OFFSETS ANDFITTINGS REQUIRED, AND THE LABOR INVOLVED. EQUIPMENT AND FIXTURE CONNECTIONSMAY REQUIRE MORE THAN 10 PIPING ELBOWS PER PLUMBING FIXTURE; DUCT RUNSTYPICALLY WILL REQUIRE 2 ADDED ELBOWS (OR TRANSITIONS/OFFSETS) EVERY 20 FEET OFDUCT RUN AND COIL PER PIPE LINE.20 07 00 - MECHANICAL SYSTEMS INSULATION1.PIPING INSULATION: RIGID MOLDED FIBERGLASS INSULATION, SIZED TO MATCH PIPE APPLIEDTO, THERMAL CONDUCTIVITY SHALL NOT EXCEED 0.24 BTU-INCH/HR-SF-DEGREES F AT 75DEGREES F, WITH JACKET CONSISTING OF HIGH DENSITY WHITE KRAFT BONDED TOALUMINUM FOIL AND HAVING A PRESSURE SENSITIVE ADHESIVE CLOSURE SYSTEM,INTEGRAL VAPOR BARRIER WITH MAXIMUM 0.02 PERM RATING. FITTINGS SHALL USEFIBERGLASS INSULATION PACKED INSIDE MINIMUM 20 MIL WHITE PVC FITTING COVERS,SIZED/SHAPED TO MATCH FITTING AND ADJACENT PIPE.2.HANGER INSERTS: EXPANDED PERLITE OR CALCIUM SILICATE INSULATION; WITH NO MORETHAN 5% DEFORMATION AT 100 PSI; AND MAXIMUM CONDUCTIVITY OF 0.32BTU-IN/HR-SF-DEGREES F; WITH MINIMUM 18 GAUGE GALVANIZED STEEL SHIELDS. PROVIDE360 DEGREE TYPE INSERT WHERE PIPE IS CLAMPED FOR SUPPORT.3.REFRIGERANT PIPING INSULATION: FLEXIBLE CELLULAR ELASTOMERIC INSULATION, SIZEDTO MATCH PIPE APPLIED TO, THERMAL CONDUCTIVITY SHALL NOT EXCEED 0.27BTU-INCH/HR-SF-DEGREES F AT 75 DEGREES F WITH LONGITUDINAL ADHESIVE SEALED JOINT,AND MAXIMUM 0.08 PERM RATING. FITTINGS SHALL USE MITERED/FORMED INSULATIONSEALED/ATTACHED WITH ADHESIVE GLUED IN PLACE.4.METAL JACKET: ALUMINUM ROLL JACKETING, FABRICATED OF TYPE 3003 OR 5005 ALUMINUM,MINIMUM 0.020 INCH THICK, WITH INTEGRAL 1 MIL HEAT BONDED POLYETHYLENE MOISTUREBARRIER.5.DUCTWORK: BLANKET FIBERGLASS INSULATION, 0.75 LB PER CUBIC FOOT MINIMUM DENSITY,THERMAL CONDUCTIVITY NO GREATER THAN 0.25 BTU-IN/HR-SQ.FT-DEGREES F. AT 75DEGREES F WITH FACTORY APPLIED VAPOR PROOF JACKET CONSISTING OF ALUMINUM FOILCOVER WITH OPEN MESH FIBERGLASS REINFORCEMENT, LAMINATED TO UL RATED KRAFT,VAPOR TRANSMISSION RATE SHALL NOT EXCEED 0.05 PERMS.6.PIPING AND EQUIPMENT INSULATION INSTALLATION:A.PROVIDE INSULATION ON THE SURFACES OF ALL ENERGY CONVEYING, ENERGYCONSUMING, OR ENERGY STORAGE DEVICES (I.E. PIPES, EQUIPMENT, VALVES, FITTINGS,ACCESSORIES, ETC.) INSTALLED AS PART OF THIS PROJECT EXCEPT WHERESPECIFICALLY EXCLUDED.B.PROVIDE INSULATION CONTINUOUS THROUGH ALL SUPPORTS ON PIPING 1-1/2 INCH ANDLARGER USING INSERTS.C.INSULATE ALL PIPING WITH INSULATION THICKNESSES AS REQUIRED BY CODE, AND NOLESS THAN AS FOLLOWS THICKNESS:PIPE SIZE (INCHES)FLUID TEMPCOND*MRT**<11 TO < 1.51.5 TO <44 TO <=8----------------------------------------------------------------------------------------------------------------> 3500.32 - 0.342504.55.05.05.0251 - 3500.29 - 0.322003.04.04.54.5201 - 2500.27 - 0.301502.52.52.53.0141 - 2000.25 - 0.291251.51.52.02.0105 - 1400.21 - 0.281001.01.01.51.540 - 600.21 - 0.27750.50.51.01.0<400.20 - 0.26750.51.0 1.01.0----------------------------------------------------------------------------------------------------------------*CONDUCTIVITY (BTU-IN/(HR-SF-DEG F)**MEAN RATING TEMPERATURE (DEG F)D.COLD WATER IS ASSUMED TO BE 50°F.7.DUCT INSULATION INSTALLATION:A.ALL DUCTS SHALL BE INSULATED EXCEPT AS NOTED BELOW.B.INSULATION THICKNESSES SHALL PROVIDE THE R-VALUES AS REQUIRED BY CODE, ANDEXCEED CODE AS INDICATED. MINIMUM INSULATION:1)EXHAUST/RELIEF AIR DUCTS:A)WITHIN CONDITIONED AREA, FROM AUTOMATIC DAMPER TO EXTERIOR: 4.0 INCHTHICK.B) WITHIN CONDITIONED AREA, FROM AUTOMATIC DAMPER TO INTERIOR: NOINSULATION REQUIRED.C)OUTSIDE CONDITIONED AREA: NO INSULATION REQUIRED WHERECONDENSATION CANNOT OCCUR; OTHERWISE 2.0 INCH.20 05 19 - PIPING SPECIALTIES8.THERMOMETERS: ADJUSTABLE ANGLE TYPE, BRASS CONSTRUCTION, 7-INCH SCALE,ALUMINUM CASE, RED READING MERCURY, WHITE FACE WITH BLACK NUMERALS, ANDMARKINGS IN DEGREES F. PROVIDE SOCKETS WITH EXTENSION NECKS WHERE INSTALLED ONINSULATED PIPING. THERMOMETER TEMPERATURE RANGES SHALL BE APPROXIMATELY 30DEG F HIGHER AND LOWER THAN NORMAL SYSTEM SETPOINT (OR OPERATING RANGE).9.UNIONS: RATED AT MINIMUM 125 PSIG AT 200 DEGREES F; PROVIDE UNIONS AT THREADEDCONNECTIONS TO ALL EQUIPMENT AND ITEMS WHICH MAY REQUIRE REPLACEMENT.PROVIDE DIELECTRIC CONNECTORS WHERE DISSIMILAR METALS JOIN; DIELECTRIC UNIONSSHALL NOT BE USED.20 05 29 - HANGERS, SUPPORTS, SLEEVES AND SEALS1.PIPE HANGERS AND SUPPORTS:A.GENERAL: SHALL CONFORM TO MSS SP-58 AND MSS SP-69 AND SHALL BE COPPERPLATED WHERE IN CONTACT WITH COPPER PIPE OR BE PROVIDED WITH FACTORY MADEISOLATORS TO PREVENT CONTACT OF DISSIMILAR MATERIALS.B.REFRIGERANT PIPE: PROVIDE VIBRATION DAMPENING CUSHION CLAMPS CONSTRUCTEDOF THERMOPLASTIC ELASTOMER WITH NYLON INSERT LOCK-NUTS ON REFRIGERANTPIPE AND PIPE SUBJECT TO VIBRATION.C.HANGERS: SHALL PERMIT ADEQUATE ADJUSTMENT AFTER ERECTION WHILE STILLSUPPORTING THE LOAD. PIPE GUIDES AND ANCHORS SHALL BE INSTALLED TO KEEPPIPES IN ACCURATE ALIGNMENT, TO DIRECT EXPANSION MOVEMENT, AND TO PREVENTBUCKLING, SWAYING, AND UNDUE STRAIN.D.SPACING: SHALL BE SPACED AS REQUIRED BY THE MORE STRINGENT OF MSS SP-69,CODE, PIPING MANUFACTURER, OR NOTES ON PLANS (LIMITING LOADS). CAST IRONDRAINAGE PIPE SHALL HAVE SUPPORTS INSTALLED NOT OVER 1' FROM EACH PIPEFITTING JOINT AND AT EACH CHANGE IN DIRECTION OF THE PIPING (FOR PIPING 2" ANDLARGER).E.INSULATION: SHALL BE CONTINUOUS THROUGH ALL SUPPORTS FOR PIPING 1-1/2 INCHAND LARGER. PROVIDE WITH RIGID INSULATION INSERT AND METAL SHEILD AT SUPPORTPOINT.2.PIPING SEISMIC RESTRAINTS: PROVIDE SEISMIC BRACING FOR ALL NATURAL GAS PIPING.PROVIDE SEISMIC SUPPORTS FOR ALL OTHER PIPING 2-INCH AND LARGER LOCATED MORETHAN 12-INCHES OR MORE BELOW THE BUILDING SUPPORTING MEMBER (UNO). PROVIDETRANSVERSE BRACING ON 20' INTERVALS, LONGITUDINAL BRACING ON 40' INTERVALS.3.PIPE SLEEVES AND SEALS: SLEEVES SHALL BE FABRICATED OF 20 GAUGE SHEETMETAL ANDSHALL ALLOW 1/2" SPACE AROUND INNER PIPE AND SHALL EXTEND AT LEAST 1" BEYONDPENETRATED ELEMENT SURFACES. PROVIDE SLEEVES AT ALL WALL, FLOOR, AND CEILINGPENETRATIONS (EXCEPT WHERE COMPLETELY SOLID INTERIOR ELEMENTS SUCH ASCONCRETE SLABS ARE PENETRATED). SEAL BETWEEN SLEEVE AND PIPE WITH UL APPROVEDFIRE SEALANT SYSTEM (EXCEPT WHERE INDICATED OTHERWISE). SEAL BETWEEN SLEEVEAND ELEMENT PENETRATED WITH SAME MATERIAL ELEMENT IS CONSTRUCTED OF (I.E.,CONCRETE, PLASTER, ETC.). ALL SEALING SHALL BE PROVIDED SO AS TO MAINTAIN THE FIRERATING OF THE ELEMENT BEING PENETRATED. SEALS IN EXTERIOR OR BELOW GRADEWALLS OR SLABS SHALL BE INTERLOCKING SYNTHETIC RUBBER LINK TYPE; THUNDERLINE"LINK-SEAL". SUBMIT SHOP DRAWING OR PROPOSED UL FIRE SEAL SYSTEM.4.DUCT SUPPORTS: SHALL BE SPACED ON MAXIMUM 8 FOOT CENTERS EXCEPT WHERE THEDUCT SIZE IS LARGER THAN 24" DIAMETER (OR RECTANGULAR EQUIVALENT, E.G. 24X20)HANGERS SHALL BE ON MAXIMUM 6 FOOT CENTERS. COMPLY WITH SMACNA STANDARDSAND CODE.5.DUCT SLEEVES AND SEALS: PROVIDE DUCT CLOSURE COLLARS FABRICATED OF GALVANIZEDSTEEL ANGLE, MINIMUM 1-1/2'X1-1/2” 24 GAUGE, SIZED TO SEAL OFF OPENINGS BETWEEN THEDUCT AND ELEMENT PENETRATED. PROVIDE CLOSURE COLLARS AT ALL WALL, FLOOR, ANDCEILING PENETRATIONS AT MECHANICAL ROOMS. SEAL BETWEEN DUCT AND ELEMENTPENETRATED WITH UL APPROVED FIRE SEALANT (EXCEPT WHERE INDICATED OTHERWISE);PROVIDE GALVANIZE STEEL SLEEVE THROUGH ELEMENT WHERE REQUIRED AS PART OFSEAL SYSTEM. SEAL BETWEEN SLEEVE AND ELEMENT PENETRATED WITH SAME MATERIALELEMENT IS CONSTRUCTED OF (I.E., CONCRETE, PLASTER, ETC.). ALL SEALING SHALL BEPROVIDED SO AS TO MAINTAIN THE FIRE RATING OF THE ELEMENT BEING PENETRATED.SUBMIT SHOP DRAWING OR PROPOSED UL FIRE SEAL SYSTEM.20 05 93 - BALANCING1.GENERAL: SHALL BE BY A COMPANY SPECIALIZING IN THIS WORK.2.COORDINATION: COORDINATE AND ASSIST WITH BALANCER TO ALLOW FOR ACCESS TO ALLITEMS. PROVIDE ADDED BALANCING DEVICES AS THE BALANCER MAY REQUIRE.3.BALANCE: BALANCE SYSTEM TO VALUES SHOWN ON DRAWINGS, PROVIDE WRITTEN REPORTDOCUMENTING UNIT DATA AND ALL BALANCING WORK. MARK FINAL DAMPER POSITIONS WITHPERMANENT MARKER. PROVIDE SHEAVES CHANGES AS DIRECTED BY THE BALANCER ORENGINEER.22 05 10 - PIPE AND PIPE FITTINGS1.STEEL PIPE AND FITTINGS: BLACK STEEL PIPE PER ASTM A53, TYPE E OR S, GRADE A OR B,SCHEDULE 40 UNLESS INDICATED OTHERWISE.A.THREADED FITTINGS: MALLEABLE IRON PER ASME B16.3, CAST IRON PER ASME B16.1 ORB16.4.B.WELDED FITTINGS: WELD FITTINGS PER ASTM A234; SEAMLESS BUTT-WELDING TYPE PERASME B16.9; SOCKET WELD TYPE PER ASME B16.11. FLANGES AND FLANGED FITTINGS:WELD-NECK OR SLIP-ON TYPE, FORGED STEEL, PER ASTM B16.5.2.COPPER PIPE AND FITTINGS: TYPE L OR K COPPER, HARD TEMPER, PER ASTM B88.WROUGHT COPPER AND BRONZE FITTINGS PER ANSI B16.22, CAST ALLOY FITTINGS PERB16.18, AND CAST BRONZE THREADED FITTINGS PER ASME B16.15. CAST FITTINGS SHALL NOTBE USED FOR BRAZED JOINTS.3.CAST IRON PIPE AND FITTINGS: SERVICE WEIGHT NO-HUB CAST IRON PIPE PER CISPI-301 ANDASTM A888 FOR USE WITH MECHANICAL NO-HUB COUPLINGS AND CAST IRON DRAINAGEPATTERN FITTINGS. STAINLESS STEEL MECHANICAL COUPLINGS AND NEOPRENE GASKETSPER CISPI-310, ASTM C1277, AND ASTM C564.4.COPPER DWV PIPE AND FITTINGS: COPPER DRAINAGE TUBE PER ASTM B306. WROUGHTCOPPER FITTINGS PER ASME B16.29, CAST COPPER ALLOY FITTINGS PER ASME B16.23.5.GALVANIZED STEEL DWV PIPE AND FITTINGS: GALVANIZ3ED STEEL PIPE PER ASTM A53 GRADEB, TYPE 5, SCHEDULE 40. CAST-IRON THREADED DRAINAGE FITTINGS PER ASTM B16.12 ANDCAST IRON SCREWED FITTINGS PER ASME B16.4.6.PVC DWV PIPE AND FITTINGS: PVC DRAIN PIPE PER ASTM D1785, ASTM D2665, WITH SOLVENTCEMENT JOINTS. FOAM CORE PIPE NOT ALLOWED. PVC DRAINAGE FITTINGS PER ASTMD2665, ASTM F1866. SOLVENT CEMENT PER ASTM D2564.7.ABS DWV PIPE AND FITTINGS: ABS DRAIN PIPE PER ASTM D2661, WITH SOLVENT CEMENTJOINTS. FOAM CORE PIPE NOT ALLOWED. ABS DRAINAGE FITTINGS PER ASTM D2661 ORASTM D3311. SOLVENT CEMENT PER ASTM D2235.8.PVC PIPE AND FITTINGS: PVC PRESSURE PIPE PER ASTM D1785, SCHEDULE 40, WITHSOLVENT CEMENT JOINTS. FOAM CORE PIPE NOT ALLOWED. PVC SOCKET TYPE FITTINGSPER ASTM D2466. SOLVENT CEMENT PER ASTM D2564.9.PEX PIPE AND FITTINGS:A.GENERAL: CROSS-LINKED POLYETHYLENE (PEX), MANUFACTURED PER ASTM F876 AND F877. COLOR SHALL BE BLUE FOR COLD WATER SYSTEMS, AND RED FOR HOT WATER AND HOT WATER RECIRCULATION SYSTEMS. MINIMUM PRESSURE RATING OF100 PSI AT 180 DEG F, AND 80 PSI AT 200 DEG F IN ACCORDANCE WITH THE PLASTIC PIPE INSTITUTE STANDARDS.B.FIRESTOP PENETRATIONS: PIPING SYSTEM MANUFACTURER (OR FIRE SEAL MANUFACTURERS) SHALL HAVE LISTED METHODS (ACCEPTABLE TO THE AHJ) FOR PIPING PENETRATIONS THROUGH RATED BUILDING ELEMENTS (FOR THE TYPE OF ELEMENTS PENETRATED ON THIS PROJECT).C.INSULATION: INSULATION MAY BE INTEGRAL WITH PIPING, MATERIAL SHALL COMPLYWITH SPECIFIED INSULATION FOR THE PIPING SYSTEM, AND BE CREDITED TOWARD THEINSULATION LEVEL REQUIRED.D.FLAME/SMOKE: PIPING SYSTEM SHALL HAVE A FLAME SPREAD/SMOKE DEVELOPMENT RATING OF 25/50 IN ACCORDANCE WITH ASTM E84 (RATING MAY BE ACHIEVED WITH A SUITABLE INSULATION WRAP OR OTHER PROTECTIVE METHODS TESTED AND CERTIFIED BY THE PIPING MANUFACTURER).E.INSTALLATION:1)MINIMUM BEND RADIUS (COLD BENDING): NO LESS THAN SIX TIMES THE OUTSIDE DIAMETER. USE A BEND SUPPORT AS SUPPLIED BY THE PEX TUBING MANUFACTURER FOR TUBING WITH A BEND RADIUS LESS THAN STATED.2)DO NOT INSTALL PEX TUBING WITHIN 6 INCHES OF GAS APPLIANCE VENTS OR WITHIN 12 INCHES OF ANY RECESSED LIGHT FIXTURES.3)DO NOT EXPOSE PEX TUBING TO DIRECT SUNLIGHT FOR MORE THAN 30 DAYS.4)USE STRIKE PROTECTORS WHERE PEX TUBING PENETRATES A STUD OR JOIST ANDHAS THE POTENTIAL FOR BEING STRUCK WITH A SCREW OR NAIL.5)USE TUBING MANUFACTURER SUPPLIED BEND SUPPORTS WHERE BENDS ARE LESS THAN SIX TIMES THE OUTSIDE TUBING DIAMETER.10.PIPE, PIPE FITTING, AND JOINT APPLICATION:SYSTEMPIPE SIZE PIPINGFITTING/JOINTCOLD AND HOT2"TYPE L COPPERSOLDER JOINTSWATERABOVEGROUND 2" & LESS PEX PEX FITTINGS--------------------------------------------------------------------------------------------------------------------------------COLD AND HOTALLTYPE K COPPERSOLDER JOINTSWATERUNDERGROUND --------------------------------------------------------------------------------------------------------------------------------WASTE & VENTALLGALV STEELDWV, THREADEDABOVEGROUND ORCAST IRONDWV CAST IRON, NO-HUB ORCOPPER DWVDWV COPPER, SOLDEREDORPVC DWVDWV PVC, SOLVENTORABS DWVDWV ABS, SOLVENT--------------------------------------------------------------------------------------------------------------------------------WASTE & VENTALLCAST IRON NO HUBUNDERGROUND ORPVC DWVDWV PVC, SOLVENTORABS DWVDWV ABS, SOLVENT---------------------------------------------------------------------------------------------------------------------------------TRAP PRIMERPIPINGALL PEX PEX FITTING---------------------------------------------------------------------------------------------------------------------------------CONDENSATEALL PVC SOLVENT-------------------------------------------------------------------------------------------------------------------------------- 11.INSTALLATION:A.INSTALL PIPING CONCEALED UNLESS SPECIFICALLY NOTED OTHERWISE. COORDINATEWITH OTHER TRADES AND ALL EXISTING CONDITIONS. INSTALL TO ALLOW MAXIMUMACCESS TO COMPONENTS INSTALLED IN PIPING SYSTEM.B.FOLLOW ESTABLISHED PROFESSIONAL PRACTICES FOR JOINING OF PIPING AND SO ASTO SUIT THE SYSTEM PRESSURES AND TEMPERATURES INVOLVED.21 11 00 - FACILITY WATER DISTRIBUTION1.BALL VALVES:A.2 INCHES AND SMALLER: 600 PSI NON-SHOCK COLD WORKING PRESSURE, 100 PSI AT 300DEG F, BRONZE BODY, FULL PORT, 2 PIECE CONSTRUCTION, ANTI-BLOWOUT STEM, REINFORCED PTFE SEATS, STAINLESS STEEL OR CHROME PLATED BRASS OR SILICON BRONZE BALL, LEVER HANDLE, SOLDER OR THREADED CONNECTIONS. PROVIDEWITH EXTENDED LEVER HANDLE WHERE VALVE IS INSTALLED IN SYSTEMS WITH INSULATIONTHICKNESS GREATER THAN 0.5 INCH. NIBCO S-585-80-LF, T-585-80-LF (ORAPPROVED).2.DRAIN VALVES: BRONZE BALL VALVE, MINIMUM 125 PSI-SWP, ANTI-BLOWOUT STEM, STAINLESS STEEL OR CHROME PLATED BRASS BALL, REINFORCED TFE SEAT, SOLDER ORTHREADED INLET CONNECTION, MALE 3/4 INCH HOSE THREAD OUTLET CONNECTION, WITH BRASS CAP AND CHAIN. NIBCO S-585-70-HC, T-585-70-HC (OR APPROVED).3.ACCESSORIESA.WATER HAMMER ARRESTORS: ALL METAL, FACTORY PRE-CHARGED WITH INERT GAS,SEALED INTERNAL BELLOWS; 125 PSI WORKING PRESSURE. ALL WETTED PARTS SHALLBE TYPE 300 STAINLESS STEEL, BRASS OR COPPER. PDI (PLUMBING AND DRAINAGEINSTITUTE) SIZES AS INDICATED. WHERE NOT SIZED, PROVIDE SIZES IN ACCORDANCEWITH PDI STANDARDS. ZURN "SHOKTROL", WADE "SHOKSTOP", OR J. R. SMITH"HYDROTROL".4.DOMESTIC WATER EXPANSION TANKA.TYPE: DIAPHRAGM THERMAL EXPANSION ABSORBER. AMTROL “ST” SERIES (ORAPPROVED).B.CONSTRUCTION: WELDED STEEL CONSTRUCTION, WITH POLYPROPYLENE LINER,BUTYL/EPDM DIAPHRAGM, STAINLESS STEEL AIR CHARGING VALVE, 175 PSIG WORKINGPRESSURE, CONFIGURATION/CONNECTIONS TO SUIT INSTALLATION, NSF 61 APPROVED,AND ASME CERTIFIED.C.CAPACITY: AS INDICATED ON PLANS; WHERE NOT INDICATED PROVIDE 2.0 GALLON TANKVOLUME (MINIMUM).5.INSTALLATION: PROVIDE ALL PIPING AS INDICATED AND AS REQUIRED TO ALLOW SUPPLYCONNECTIONS TO EACH FIXTURE AND EQUIPMENT ITEM REQUIRING WATER SUPPLY.PROVIDE OFFSETS AS REQUIRED TO ACCOMMODATE BUILDING CONSTRUCTION AND ACCESSREQUIREMENTS PER SECTION 20 05 00. FOR MULTISTORY BUILDINGS INCLUDE COSTS TOOFFSET VERTICAL PIPING AT EACH FLOOR LEVEL SINCE STRUCTURAL MEMBER LOCATIONSWILL NOT BE THE SAME ON EACH FLOOR. COORDINATE INSTALLATION OF ITEMS WITH ALLTRADES THAT ARE AFFECTED BY THE WORK TO AVOID CONFLICTS.6.FLUSHING AND DISINFECTION: FLUSH AND DISINFECT THE SYSTEM PER CODE. PROVIDEWATER QUALITY TESTS TO CONFIRM CLEANLINESS.M-004MECHANICAL SPECIFICATIONSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-001-004.dwg
8/07/2023 4:35:23 PM
MECHANICAL SPECIFICATIONS (CONTINUATION)22 13 00 - SANITARY SEWER SYSTEM1.CLEANOUTS-GENERAL: ALL CLEANOUTS SHALL HAVE CAST IRON BODIES WITH BRONZECOUNTERSUNK RECTANGULAR SLOTTED PLUGS, LUBRICATED WITH A NON-HARDENINGTEFLON BASE THREAD LUBRICANT AND HAVING A GASKET SEAL. CLEANOUTS LOCATEDIN WATERPROOF MEMBRANE FLOORS SHALL BE PROVIDED WITH AN INTEGRAL CASTFLANGE AND FLASHING DEVICE. ALL CLEANOUTS SHALL BE THE SAME SIZE AS THE PIPEWHICH THEY ARE INTENDED TO SERVE (BUT NOT LARGER THAN 4-INCH).2.FLOOR CLEANOUTS: AREAS WITH BARE CONCRETE FLOORS: J. R. SMITH NO. 4100SERIES ADJUSTABLE FLOOR CLEANOUT WITH ROUND HEAVY DUTY NICKEL BRONZE TOP.AREAS WITH TERRAZZO (AND SIMILAR POURED FLOORS): J. R. SMITH NO. 4180 SERIESADJUSTABLE FLOOR LEVEL CLEANOUT WITH ROUND HEAVY DUTY NICKEL BRONZE TOPWITH TERRAZZO RECESS. AREAS WITH CARPET: J. R. SMITH 4020-X SERIES ADJUSTABLEFLOOR LEVEL CLEANOUT WITH ROUND HEAVY DUTY NICKEL BRONZE TOP AND CARPETCLAMP.3.WALL CLEANOUTS: CAST IRON FERRULE WITH CAST BRONZE TAPER THREADED PLUG,WITH PLUG TAPPED 1/4-INCH, 20 THREAD, TO ACCEPT ACCESS COVER SCREW; WITHSTAINLESS STEEL ACCESS COVER AND VANDAL PROOF SCREW.4.OUTSIDE CLEANOUTS: HEAVY DUTY, ROUND, CAST IRON, DOUBLE-FLANGED HOUSING,HAVING SCORIATED CAST IRON COVER WITH LIFTING DEVICE, FERRULE AND BRONZECLOSURE PLUG. HOUSING AND LID SHALL BE GALVANIZED AND HAVE VANDALRESISTANT SCREWS. J. R. SMITH NO. 4251 OR 4256 SERIES.5.VENT FLASHING:A.GENERAL: STYLE AND TYPE TO SUIT ROOFING SYSTEM, MATCH VENT PIPE SIZE,AND PROVIDE WATERPROOF BUILDING PENETRATION. PROVIDE WITH ADEQUATEBASE SIZE FOR PROPER FLASHING INTO ROOF SYSTEM.B.EPDM OR COMPRESSION MOLDED RUBBER; SUITABLE FOR TEMPERATURES FROM-60 DEG F TO 270 DEG F; RESISTANT TO OZONE AND UV LIGHT. FLASHING SHALLHAVE ALUMINUM OR GALVANIZED STEEL BASE FOR FLASHING OR ATTACHMENT TOROOF (STYLE TO SUIT ROOF TYPE). PROVIDE STAINLESS STEEL CLAMP.C.2.5 LB SHEET LEAD, EXTENDING AS A SLEEVE ALL AROUND VENT PIPE WITH BASEEXTENDED OUT MINIMUM 10 INCHES ALL AROUND; TOP COUNTER-FLASHINGOVERLAP 2" AND TURNED DOWN INSIDE VENT PIPE.6.INSTALLATION: PROVIDE ALL PIPING AS INDICATED AND AS REQUIRED TO ALLOWCOMPLETE AND PROPER WASTE, DRAIN, AND VENT CONNECTIONS TO EACH FIXTUREAND EQUIPMENT ITEM REQUIRING CONNECTION. PROVIDE OFFSETS AS REQUIRED TOACCOMMODATE BUILDING CONSTRUCTION AND ACCESS REQUIREMENTS PER SECTION20 05 00. FOR MULTISTORY BUILDINGS INCLUDE COSTS TO OFFSET VERTICAL PIPINGTHROUGH EACH FLOOR LEVEL SINCE STRUCTURAL MEMBER LOCATIONS WILL NOT BETHE SAME ON EACH FLOOR. VERIFY POINTS OF CONNECTION, INVERT ELEVATIONS, ANDGRADE REQUIREMENTS BEFORE BEGINNING INSTALLATION OR ORDERING MATERIALS.VENTS EXTENDING THROUGH ROOF SHALL TERMINATE AT LEAST 10 INCHES ABOVEROOFING; AND NOT LESS THAN 10 FEET FROM AND 3 FEET ABOVE ANY BUILDINGOPENING. PROVIDE VENT FLASHING AT EACH VENT THROUGH ROOF; UTILIZEWATER-PROOF METHOD AS REQUIRED TO BEST SUIT ROOFING MATERIAL AND ROOFINGSYSTEM MANUFACTURER.7.MISCELLANEOUS DRAINS: PROVIDE DRAIN PIPING FOR ALL DRIP PANS, UNITCONDENSATE DRAINS, UNIT P-TRAPS, ETC. RUN PIPING TO NEAREST POINT OFDRAINAGE, OR AS SHOWN ON DRAWINGS. WHERE ROUTING IS NOT SHOWN, ROUTE TONEAREST POINT OF PROPER DRAINAGE.8.SLOPE: INSTALL ALL HORIZONTAL SOIL OR WASTE LINES WITH A SLOPE OF 1/4-INCH PERFOOT UNLESS NOTED OTHERWISE. COORDINATE WITH AHJ IF WRITTEN APPROVAL ISREQUIRED FOR EXCEPTIONS TO 1/4-INCH PER FOOT SLOPE.22 40 00 - PLUMBING FIXTURES1.GENERAL:A.PROVIDE NEW FIXTURES AND FITTINGS, APPROVED, FREE FROM FLAWS ANDBLEMISHES WITH FINISHED SURFACES CLEAR, SMOOTH AND BRIGHT. VISIBLEPARTS OF FIXTURE BRASS AND ACCESSORIES, AND ALL ITEMS LOCATED INACCESSIBLE CABINET SPACES, SHALL BE HEAVILY CHROME PLATED. ALL STOPS,P-TRAPS AND ITEMS EXPOSED TO VIEW SHALL BE CHROME PLATED (EXCEPTWHERE SPECIFICALLY NOTED OTHERWISE). ALL PRODUCTS AND CONNECTIONSSHALL BE IN COMPLIANCE WITH CODE, LOCAL UTILITIES DEPARTMENT STANDARDS,AND HEALTH DEPARTMENT REQUIREMENTS.B.TYPES: VERIFY SPECIFIED FIXTURE TYPES WITH THE ARCHITECTURAL ANDPLUMBING DRAWINGS TO CONFIRM THE REQUIREMENTS ARE CONSISTENT (E.G.FIXTURES ARE WALL MOUNTED VERSUS FLOOR MOUNTED TYPE, LOCATIONS OFADA FIXTURES MATCH, ETC.). WHERE CONFLICTS OCCUR CLEARLY IDENTIFY THEISSUE ON THE FIXTURE SUBMITTAL ALONG WITH A PROPOSED RESOLUTION; ORRESOLVE PRIOR TO MAKING THE SUBMITTAL BY THE PROJECT RFI PROCESS.C.SPACE VERIFICATION: PRIOR TO ORDERING ANY FIXTURES OR MAKINGSUBMITTALS, CONTRACTOR SHALL CHECK THE DRAWINGS AND VERIFY THAT ALLFIXTURES WILL FIT THE SPACE AVAILABLE (I.E. FIXTURES FIT ANY CABINETSFIXTURES ARE TO BE INSTALLED IN; FIXTURES HAVE ADEQUATE ACCESSCLEARANCES FOR PROPER USE; ETC.).D.LEAD-FREE REQUIREMENT: ALL ITEMS IN CONTACT WITH POTABLE WATER SHALLBE LEAD FREE. FIXTURES USED TO DISPENSE POTABLE WATER FOR DRINKINGSHALL MEET THE REQUIREMENTS OF NSF/ANSI 61.1)ALL VITREOUS CHINA AND ENAMELED CAST IRON FIXTURES SHALL BE FINISHEDWHITE UNLESS SPECIFICALLY NOTED OTHERWISE.2)ALL STAINLESS STEEL SINKS SHALL BE SOUND DEADENED, AND SHALL HAVEFAUCET LEDGE (EXCEPT WHERE NOTED SPECIFICALLY WITHOUT LEDGE).3)IN INTERESTS OF OWNER'S STANDARDIZATION, FIXTURES OF SIMILAR TYPESHALL BE PRODUCT OF ONE MANUFACTURER; TRIM OF SIMILAR TYPE SHALL BEPRODUCT OF ONE MANUFACTURER.2.CARRIERS: TYPE TO SUIT FIXTURE AND BUILDING CONSTRUCTION, WITH ADDEDANCHORS, BRACING, WALL BACKING AND ACCESSORIES TO COMPLY WITH MAXIMUMSPECIFIED FIXTURE MOVEMENT. CONCEALED IN WALL. PROVIDE WITH ALL HARDWAREAND ACCESSORIES FOR PROPER FIXTURE SUPPORT TO SUIT THE APPLICATION.3.SPECIALTIESA.GENERAL: UNLESS INDICATED OTHERWISE, THE FOLLOWING FITTINGS ANDMATERIALS (I.E. SPECIALTIES) SHALL BE USED.B.FIXTURE TRAPS: 17 GAGE SEAMLESS CHROME PLATED CAST BRASS TUBING, WITH2 INCH MINIMUM SEAL, AND CLEANOUT, SIZE AS REQUIRED BY UNIFORM PLUMBINGCODE (UNLESS A LARGER SIZE IS INDICATED), AND CONFIGURED TO SUIT THEAPPLICATION.C.EXPOSED PIPING AND FITTINGS: IN FINISHED AREAS AND IN ACCESSIBLE CABINETS,PROVIDE PIPING WITH CHROME PLATING OR SLEEVED WITH CHROMED SLEEVES OROF STAINLESS STEEL CONSTRUCTION/FINISH; ALL CHROME TO HAVE A BRIGHTPOLISHED FINISH. NO EXPOSED COPPER ALLOWED (INCLUDES ACCESSIBLECABINET AREAS).D.STOPS: QUARTER TURN BALL VALVE WITH LOOSE KEY, SIZE AS REQUIRED.E.RISERS: FLEXIBLE BRAIDED STEEL TYPE; RATED FOR 125 PSIG.F.ESCUTCHEONS: CHROME PLATED, LOW PROFILE.G.REFRIGERATOR WALL BOX: 20 GAUGE HOT DIPPED GALVANIZED STEEL BOX WITH 18GAUGE FACE PLATE, ½" INLET X 1/4" OUTLET COMPRESSION ANGLE VALVE. GUYGRAY MODEL BIM875.H.HOT WATER TEMPERATURE LIMITING VALVE: THERMOSTATIC WATERTEMPERATURE MIXING VALVE WITH INTEGRAL CHECKS, COMPLYING WITH ASSE1070 AND UPC CHAPTER 4. BRASS BODY WITH BRASS AND STAINLESS STEELINTERNAL COMPONENTS. LEONARD “ECO-MIX” 270 / SYMMONS “MAXLINE” MODEL5-210.4.INSTALLATION OF FIXTURESA.GENERAL: ALL FIXTURES SHALL BE COMPLETELY CONNECTED TO PIPING ASNEEDED TO MAKE A COMPLETE AND OPERABLE INSTALLATION.B.FIXTURE LOCATIONS: MOUNTING HEIGHTS AND LOCATIONS OF FIXTURES SHALL BEAS SHOWN ON THE ARCHITECTURAL DRAWINGS AND IN ACCORDANCE WITHCONTRACT DOCUMENT REQUIREMENTS. LOCATIONS SHALL BE VERIFIED ANDCOORDINATED WITH THE VARIOUS TRADES AFFECTED BY THE INSTALLATION OFTHESE FIXTURES. WHEN NO INDICATED OR SHOWN, OBTAIN MOUNTING LOCATIONAND HEIGHTS FROM THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.C.ROUGH-IN: DETERMINE ROUGH-IN LOCATION OF FIXTURE UTILITIES TO SUITFIXTURE LOCATION, FIXTURE DIMENSIONS, ELEMENTS OF CONSTRUCTION (I.E.BEAMS, STUDS, ELECTRICAL, DUCTS, ETC.), ACCESS REQUIREMENTS, CASEWORKDIMENSIONS, ITEMS WHICH MAY DRAIN/CONNECT TO FIXTURE, USE OF FIXTURE,AND RELATED CONSIDERATIONS. THE FIXTURE ROUGH-IN LOCATIONS INDICATEDON THE PLANS IS SCHEMATIC, AND IS NOT TO BE USED FOR FINAL ROUGH-INPURPOSES.D.OFFSETS: PROVIDE OFFSETS IN PIPING TO FIXTURES TO ACCOMMODATE BUILDINGSYSTEMS. SUCH OFFSETS SHALL INCLUDE OFF-SETTING WASTE PIPING INTOCABINET BASES (IN KICK SPACE WHERE POSSIBLE) TO ACCOMMODATE BEAMSLOCATED DIRECTLY BELOW WALLS BEHIND FIXTURES.E.CARRIERS: ALL OFF-THE-FLOOR (I.E. WALL) MOUNTED FIXTURES SHALL BEINSTALLED WITH SUPPORTING CARRIERS AND ADDITIONAL ANCHORS, BRACING ANDSUPPORTS TO TRANSMIT FIXTURE LOADS TO THE FLOOR AND BUILDINGSTRUCTURE WITHOUT EXCEEDING THE MAXIMUM SPECIFIED FIXTURE MOVEMENT.PRIOR TO CONCEALING CARRIER AND ASSOCIATED SUPPORTS REVIEW ADEQUACYOF SUPPORT SYSTEM WITH ARCHITECT/ENGINEER.F.FIXTURE SEALANT: WHERE FIXTURES ABUT TO WALLS, FLOORS, AND CABINETSSEAL ALL JOINTS WITH A UNIFORM FILLET BEAD OF SEALANT. PROVIDE AT OTHERLOCATIONS AS RECOMMENDED BY FIXTURE MANUFACTURER.G.ESCUTCHEONS: PROVIDE ESCUTCHEONS AT EACH POINT WHERE AN EXPOSEDPIPE OR OTHER FITTING PASSES THROUGH WALLS, FLOORS, BACKS OF CABINETS,OR CEILINGS.H.HOT WATER TEMPERATURE LIMITING VALVE: INSTALL ON ALL LAVATORIES,BATHTUBS, SHOWERS, WHIRLPOOLS, BIDETS AND AS FIXTURES REQUIRED BYCODE.I.CLEANING: AFTER COMPLETION OF INSTALLATION REMOVE ALL LABELS ANDTHOROUGHLY CLEAN ALL FIXTURES, TRIM AND FITTINGS.23 31 00 - DUCTWORK SYSTEMS1.GENERAL: FABRICATE AND INSTALL DUCTWORK IN ACCORDANCE WITH SMACNA DUCTCONSTRUCTION STANDARDS, ASHRAE HANDBOOKS, AND CODE.2.DUCT SIZES: ALL DUCT SIZES ARE INSIDE CLEAR DIMENSIONS. WHERE INSIDE DUCTLINING IS SHOWN, DUCT DIMENSIONS ARE TO THE INSIDE FACE OF LINING.3.DUCT PRESSURE CLASS: CONSTRUCT TO 1" PRESSURE CLASS.4.DUCTS: CONSTRUCT OF GALVANIZED SHEET STEEL, SUITABLE FOR LOCK FORMINGWITHOUT FLAKING OR CRACKING, CONFORMING TO ASTM A653 AND A924, HAVING A ZINCCOATING OF 0.90 OUNCES TOTAL PER SQUARE FOOT FOR BOTH SIDES OF A SHEET,CORRESPONDING TO COATING DESIGNATION G90. DUCT GAUGE, REINFORCEMENT,JOINTS, SEAMS AND CONNECTIONS SHALL BE AS SHOWN IN SMACNA HVAC DUCTCONSTRUCTION STANDARDS ACCORDING TO THE PRESSURE CLASS OF THE SYSTEMAND THE DUCT DIMENSIONS. SELECT HEAVIER GAUGE DUCT WITHOUT (OR WITHSMALLER) REINFORCEMENT TO SUIT SPACE AVAILABLE.5.DUCT INSTALLATION: INSTALL ALL DUCTWORK IN SIZES AND LOCATIONS AS SHOWN ONTHE DRAWINGS AND AS BUILDING CONSTRUCTION ALLOWS. PROVIDE ALL ACCESSORIESAND CONNECTIONS TO PROVIDE COMPLETE AND OPERABLE HEATING, VENTILATING, AIRCONDITIONING, AND EXHAUST SYSTEMS. DUCT SHALL BE INSTALLED LEVEL AND IN NEATLINES WITH THE BUILDING CONSTRUCTION. ALL DUCTS ARE TO BE INSTALLEDCONCEALED UNLESS INDICATED OTHERWISE.6.DUCT SEALING: SEAL ALL JOINTS IN ACCORDANCE WITH SEAL CLASSIFICATION ASSHOWN IN SMACNA HVAC DUCT CONSTRUCTION STANDARDS AND PER CODE.7.FLEXIBLE DUCT: FACTORY INSULATED FULLY LINED FLEXIBLE DUCT. DUCT SHALL HAVEFULL INTERNAL LINER, REINFORCED WITH ZINC COATED STEEL HELIX, LINER BONDED TO1-INCH THICK FIBERGLASS INSULATION, WITH MAXIMUM CONDUCTIVITY OF 0.26BTU-INCH/HR-SQ.FT.-DEGREE F AT 75 DEGREES AND HAVING A POLYETHYLENE OUTERVAPOR BARRIER. PROVIDE ENDS WITH COMPRESSION CLAMPS FOR POSITIVECONNECTION TO OVAL OR ROUND FITTINGS. SHALL COMPLY WITH NFPA 90A AND 90BAND SHALL BE UL LISTED AND LABELED AS A CLASS 1 CONNECTOR PER UL STANDARD181. FLEXIBLE DUCT SHALL ONLY BE USED AT DIFFUSER CONNECTION, AND SHALL NOTEXCEED 2 FEET IN LENGTH, IN STRAIGHT RUNS ONLY (UNLESS SPECIFICALLY SHOWNOTHERWISE ON PLANS). DUCT PRESSURE RATING SHALL MATCH PRESSURE CLASS OFDUCT SYSTEM INSTALLED ON.8.DRAIN PANS: GALVANIZED STEEL DRAIN PAN, FULLY WELDED TO BE WATERTIGHT WITH3/4-INCH DRAIN CONNECTION. SIZE TO FULLY CAPTURE LEAKAGE OF ITEM SERVED.23 34 00 - FANS1.GENERAL:A.TYPE/RATING: TYPE AS INDICATED AND EQUAL TO MFR LISTED. FANS SHALL BEARAMCA CERTIFIED SEAL UNLESS INDICATED OTHERWISE.B.GUARDS: FANS SHALL BE EQUIPPED WITH BELT GUARDS. GUARDS SHALL BEFACTORY FABRICATED AND COMPLY WITH OSHA REGULATIONS. ALL EXPOSEDOPENINGS INTO FAN HOUSINGS SHALL BE PROTECTED WITH SUBSTANTIAL METALSCREENS OR GRATINGS.C.DRIVES: SHALL BE SIZED FOR NOT LESS THAN 150% OF THE RATED MOTORHORSEPOWER.D.MOTORS: SHALL BE U.L LISTED TEFC TYPE, METING WSEC EFFICIENCYREQUIREMENTS; PROVIDE ECM WHERE NOTED OR REQ'D TO MEET EFFICIENCIES.E.CAPACITY: FAN CAPACITY SHALL NOT BE LESS THAN THE VALUES LISTED ON THEDRAWINGS. FAN PERFORMANCE RATINGS SHALL BE BASED ON LABORATORYTESTS CONDUCTED IN ACCORDANCE WITH AMCA TEST CODE.F.BACKDRAFT DAMPERS (BDD): PROVIDE ALL FANS W/ BDD'S; MFR'S STANDARD,RATED FOR VELOCITY & PRESSURE EXPOSED TO.2.INSTALLATION: PROVIDE FLEXIBLE CONNECTIONS IN DUCTWORK CONNECTIONS TO ALLFANS WHERE SHOWN ON DRAWINGS. INSTALL ALL FANS WITH VIBRATION ISOLATORS SOTHAT NO EXCESSIVE VIBRATION IS TRANSMITTED TO THE STRUCTURE. PRIOR TO AIRBALANCING, CHECK FOR CORRECT ROTATION, TIGHTEN BELTS TO PROPER TENSIONAND LUBRICATE BEARINGS PER MANUFACTURER'S RECOMMENDATIONS.23 81 26 - SPLIT SYSTEM AIR CONDITIONING UNITS/ HEAT PUMPS - DUCTLESS1.AIR CONDITIONING UNIT:A.SPLIT SYSTEM DUCTLESS AIR CONDITIONER (OR HEAT PUMP, AS INDICATED.INDOOR UNIT: WALL (OR CEILING) SUSPENDED UNIT (CONFIGURATION ASINDICATED ON PLANS), WITH FAN, ADJUSTABLE DISCHARGE OUTLET.B.ACCEPTABLE MANUFACTURERS: MITSUBISHI, TRANE, LG.2.CONDENSATE PUMP: PROVIDE UNITS WITH CONDENSATE PUMPS AS NEEDED FORCONDENSATE DRAINAGE. WHERE NOT AVAILABLE INTERNAL TO UNIT, PROVIDEEXTERNAL TYPE, WITH HOLDING TANK, CONTROLS, AND GPM CAPACITY AT LEAST 4TIMES UNIT CONDENSATE RATE, AT 20 FEET OF HEAD. PROVIDE MOUNTING ASSEMBLYAND ACCESSORIES FOR COMPLETELY CONNECTED AND FUNCTIONING UNIT.3.REFRIGERANT PIPING: HARD DRAWN ACR COPPER TUBING PER ASTM B280, TYPE L,WITH SILVER BRAZED JOINTS AND WROUGHT COPPER FITTINGS PER ASME B16.22. USEONLY LONG RADIUS ELBOWS. FLARED FITTINGS (AT EQUIPMENT CONNECTIONS ONLY)SHALL COMPLY WITH ASME B16.26. SOFT COPPER TUBING MAY ONLY BE USED ON RUNSLESS THAN 50-FEET OR WHERE NECESSARY (I.E. WHEN ROUTING THROUGH SLEEVES,OR SIMILAR POOR ACCESS AREAS).4. INSTALLATION:A.GENERAL: INSTALL ALL EQUIPMENT AT LOCATIONS AND AS SHOWN ON THEDRAWINGS AND SO AS TO ALLOW MAXIMUM ACCESS TO UNITS. PRIOR TOSELECTING UNIT FINAL LOCATION, CONFIRM THAT: PROPER UNIT CLEARANCES ANDACCESS WILL BE PROVIDED; NO ADVERSE AIRFLOW CONDITIONS ARE PRESENT;CONFIRM LOCATION AND INSTALLATION DETAILS WITH OTHER TRADES. UNITSSHALL BE LEVEL AND ALIGNED WITH BUILDING WALLS. SET OUTDOOR UNIT ONCONCRETE PAD.B.REFRIGERANT PIPING: SHALL BE SILVER BRAZED. BLEED DRY NITROGEN THROUGHPIPING DURING BRAZING TO MINIMIZE OXIDATION. KEEP ALL OPEN ENDS OF PIPINGCAPPED WHEN NOT BEING WORKED. PIPING SHALL BE ROUTED CONCEALED,EXCEPT WHERE ROUTED OUTDOORS AND WHERE NOTED. PIPING SHALL BE RANPLUMB AND SQUARE TO BUILDING WALLS, AND IN A NEAT PROFESSIONAL MANNER.PROVIDE SIGHT GLASS IN REFRIGERANT LIQUID PIPING AT OUTDOOR UNIT.C.REFRIGERANT CHARGE: UNITS SHALL BE CHECKED FOR PROPER REFRIGERANTCHARGE AND OIL LEVEL AND CHARGED TO PROPER LEVELS AFTER ALL LEAKTESTING AND EVACUATION WORK HAS BEEN COMPLETED.5.LEAK TESTING AND EVACUATION: DISCONNECT AND ISOLATE FROM THE SYSTEM ANYCONTROLS, RELIEF VALVES, OR OTHER COMPONENTS THAT MAY BE DAMAGED BY THETEST PRESSURE. PROVIDE 1 PRESSURE TEST, AND SYSTEM EVACUATION PERSTANDARD PROFFESSIONAL REFRIGERATION PRACTICE. LET VACUUM STAND FOR AMINIMUM OF 24 HOURS BEFORE CHARGING SYSTEM.6.START-UP: PROVIDE START-UP IN ACCORDANCE WITH MANUFACTURERSRECOMMENDATIONS. CHECK UNIT FOR PROPER OPERATION IN RESPONSE TOTHERMOSTAT SETTINGS INCLUDING: PROPER FAN ROTATION, NO EXCESSIVEVIBRATION, NO UNUSUAL NOISES, PROPER UNIT CYCLING IN RESPONSE TO ROOMTEMPERATURE, NO EXCESSIVE ROOM TEMPERATURE SWINGS, NO SAFETIES ORELECTRICAL DEVICES TRIPPING OUT. SUBMIT WRITTEN REPORT DETAILING ALLSTART-UP PROCEDURES AND FINDINGS.SECTION 23 82 47 - ELECTRIC HEATERS1.TYPE: WALL OR CEILING MOUNTED ELECTRIC FORCED AIR HEATER.2.CONSTRUCTION: HEATER HOUSING SHALL BE CONSTRUCTED OF HEAVY GAUGE STEEL,WITH A SLOTTED FRONT GRILLE; FOR RECESSED INSTALLATION AS SHOWN ON THEDRAWINGS (OR TO SUIT CONSTRUCTION). UNIT SHALL HAVE BAKED-ON ENAMEL ORPOWDER COAT FINISH, WHITE. HEATING ELEMENTS SHALL BE THE SEALED TYPE WITHPARALLEL STEEL FINS, WITH CAPACITY AS SCHEDULED.3.MOTOR AND FAN: MOTOR SHALL BE MULTI-POLE, TOTAL ENCLOSED, PERMANENTLYLUBRICATED TYPE. FAN OPERATING RPM SHALL NOT EXCEED 600.4.ELECTRICAL AND CONTROLS: UNIT SHALL HAVE AUTOMATIC RESET THERMAL LIMIT,POWER DISCONNECT SWITCH, AND WITHOUT THERMOSTAT (UNLESS INDICATEDOTHERWISE). TO BE CONTROLLED BY A LOW VOLTAGE REMOTE WALL THERMOSTAT.5.ACCESSORIES: RECESS MOUNTING ADAPTER TO SUIT INSTALLATION ARRANGEMENTREQUIRED; WALL MOUNTING BOX; 24 VOLT CONTACTOR FOR REMOTE CONTROL OFHEATER VIA REMOTE LOW VOLTAGE THERMOSTAT OR BY BUILDING CONTROLS.COORDINATE REQUIREMENTS WITH PROJECT CONTROL SYSTEM.SECTION 23 09 33 - ELECTRONIC CONTROLS FOR HVAC1.DESIGN AND INSTALLATION: THE ENTIRE CONTROL SYSTEM SHALL BE DESIGNED ANDINSTALLED BY SKILLED CONTROL SYSTEM DESIGNERS, ELECTRICIANS AND MECHANICS,ALL OF WHOM ARE PROPERLY TRAINED AND QUALIFIED FOR CONTROL SYSTEM DESIGNAND INSTALLATION.2.PROGRAMMABLE THERMOSTAT: SHALL BE 7-DAY PROGRAMMABLE SOLID STATE TYPE,SPECIFICALLY DESIGNED FOR COMMERCIAL USE. UNIT (AND RELATED RELAY MODULE,AND CONTROLS) SHALL ALLOW FOR 1ST-STAGE ECONOMIZER COOLING, 2ND STAGE UNITCOOLING, 1ST STAGE HEATING, 2ND STAGE HEATING AND PROVIDE OTHER FEATURESAS REQUIRED BY THE SEQUENCE OF OPERATION. THERMOSTAT SHALL HAVE MEANS TOBYPASS TIME CLOCK, HAVE AUTO-COOL-OFF-HEAT SWITCHING, SETPOINTADJUSTMENTS, AND TIME/DAY ADJUSTMENTS. SHALL HAVE, ECONOMIZER FAULTDETECTION AS REQUIRED BY CODE.3.GENERAL TIME CLOCK: 365 DAY PROGRAMMABLE TIMECLOCK, FOR CONTROL OF UP TOINDEPENDENT LOADS EACH WITH A DIFFERENT SCHEDULE, WITH MULTIPLE SETPOINTSOF PROGRAMMING. EACH OUTPUT ABLE TO BE PROGRAMMED AS A MAINTAINED ORMOMENTARY CONTACT CLOSURE WITH DURATION OF 1 TO 59 SECONDS. FEATURESSHALL INCLUDE: TIME OF DAY SCHEDULING, HOLIDAY PROGRAMMING, DAYLIGHTSAVINGS TIME ADJUSTMENT, LEAP YEAR CORRECTION, MANUAL OVERRIDE, ANDBATTERY BACK-UP (FOR ONE MONTH OPERATION WITHOUT POWER).4.CONTROL DAMPERS: PARALLEL BLADE OR OPPOSED BLADE TYPE, AS SELECTED BYCONTRACTOR TO BEST SUIT APPLICATION (UNLESS A SPECIFIC TYPE IS INDICATED).CLASS 1A LEAKAGE RATED.5.ACTUATORS: BRUSHLESS DC MOTOR TYPE CONTROLLED BY A MICROPROCESSOR WITHMANUAL POSITIONING MECHANISM AND CONTROL DIRECTION OF ROTATION SWITCHACCESSIBLE ON ITS COVER, COMPATIBLE WITH CONTROL DEVICES USED WITH.ACTUATOR SHALL BE PROPORTIONAL OR TWO POSITION TYPE, AS REQUIRED FORAPPLICATION. ALL ACTUATORS SHALL SPRING RETURN UPON POWER INTERRUPTION.6.ELECTRICAL:A.GENERAL: PROVIDE ALL ELECTRICAL WIRING AND DEVICES IN ACCORDANCE WITHAPPLICABLE CODES AND DIVISION 26 REQUIREMENTS. IT SHALL BE THERESPONSIBILITY OF THE CONTROL CONTRACTOR TO PROVIDE POWER FOR ALLCONTROL DEVICES REQUIRING POWER. COORDINATE WITH THE DIVISION 26CONTRACTOR TO ARRANGE FOR NECESSARY POWER CIRCUITS. ALL CONTROLDEVICES SHALL OBTAIN POWER FROM CIRCUITS DEDICATED TO CONTROL POWER.B.WIRING AND CONDUIT: ALL WIRING SHALL BE INSTALLED IN CONDUIT AND INACCORDANCE WITH DIVISION 26 SPECIFICATIONS, EXCEPT THAT LOW VOLTAGEWIRING WITHIN CEILING PLENUM SPACES, MECHANICAL MEZZANINES, AND ATTICSMAY BE INSTALLED WITHOUT CONDUIT. WIRING IN WALLS SHALL BE IN CONDUIT.WIRING SHALL BE IN ACCORDANCE WITH MANUFACTURERS DIRECTIONS FORCONTROL DEVICES, AND BE COLOR CODED.C.MOTOR STARTERS/RELAYS: SHALL BE BY DIVISION 26; EXCEPT FOR LOADS 1/2 HPAND LESS WHICH SHALL BE RELAYS, PROVIDED BY THIS SECTION.7.MISCELLANEOUS WIRING: PROVIDE ALL NECESSARY CONTROL WIRING AND INTERLOCKSBETWEEN UNITS AND ACCESSORIES TO ALLOW FOR PROPER OPERATION.SECTION 23 09 93 - HVAC SEQUENCE OF OPERATION1.GENERAL: PROVIDE COMPLETE SYSTEM WITH SEQUENCES OF OPERATION ASSPECIFIED HEREIN. PROVIDE COMPLETE CONTROL SYSTEM SHOP DRAWINGSINDICATING ALL CONTROL DEVICES AND WIRING CONNECTIONS; SEE SECTION 23 09 33.ALL TEMPERATURE SETPOINTS AND TIME CONTROL SETTINGS SHALL BE ADJUSTABLE.VARIOUS THERMOSTATS ARE NOT SHOWN ON THE DRAWINGS BUT ARE REQUIRED PERTHE SEQUENCE OF OPERATION SPECIFIED. COORDINATE WITH ENGINEER FORLOCATION OF ALL SUCH THERMOSTATS PRIOR TO INSTALLING. SEE PLANS FOR UNITSWITH MOTORIZED DAMPERS IN THE DUCTS AND MISCELLANEOUS OTHER ITEMSREQUIRING CONTROL.2.TIME CONTROL: CONTROL SYSTEM SHALL PROVIDE TIME SCHEDULE CONTROL (I.E.OCCUPIED/UNOCCUPIED/ WARM-UP MODES SWITCHING) FOR ALL HVAC AND EXHAUSTEQUIPMENT. PROVIDE INDEPENDENT OCCUPIED/UNOCCUPIED SCHEDULES ANDOPTIMUM START (I.E. WARM-UP) CYCLE FOR EACH HVAC UNIT (UNLESS NOTEDOTHERWISE).3.FANS: SEE PLANS FOR WHICH OF THE FOLLOWING CONTROL METHOD IS REQUIRED.A.WALL SWITCH: FAN SHALL BE CONTROLLED BY ON/OFF WALL SWITCH. FAN SHALLBE ON WHEN SWITCH IS IN THE ON POSITION, AND BE OFF OTHERWISE.4.ELECTRIC HEATERS - WALL TYPE - OCCUPIED MODE: HEATER SHALL BE ON ONCE SPACETEMPERATURE HAS FALLEN 2 DEG F OR MORE BELOW SETPOINT, AND SHALL BE OFFONCE TEMPERATURE HAS RISEN 1 DEG F OR MORE ABOVE SETPOINT.5.DUCTLESS SPLIT HEAT PUMPS: SHALL BE CONTROLLED BY INTEGRAL CONTROLS AND ALOCAL WALL THERMOSTAT FURNISHED WITH THE UNIT6.MISCELLANEOUS: DAMPERS/DEVICES: SEE PLANS FOR OTHER DAMPERS AND DEVICESREQUIRING CONTROL. PROVIDE CONTROL INDICATED. WHERE CONTROL IS NOT INDICATEDPROVIDE STANDARD SEQUENCE TYPICAL FOR SUCH DEVICES IN SIMILARPROJECTS/APPLICATIONS.M-004MECHANICAL SPECIFICATIONSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082C:\Users\NickH.HBHU\appdata\local\temp\AcPublish_17104\23-082_M-001-004.dwg
8/07/2023 4:00:03 PM
g.1g.1g.3g.3g.4g.4g.5g.5g.2g.2g.6g.6g.7g.7g.8g.8g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.Cg.Bg.B4"W UPTO SCO4"W, 10213"W, 124"W UPTO WCO4"W UPTO WCO4"W UPTO SCO4"W, 10213"W4"W UPTO WCO4"W UPTO WCO2-1/2"CW,21612-1/2"CW2"CW2"CW2"CW UP,54 (TYP)2"W (TYP)3"W, 12M-107GFOUNDATION PLAN - BUILDING 'G' 1/8" = 1'-0"FOUNDATION PLAN - BUILDING 'G'2'8'4'16'SCALE: 1/8" = 1'-0"0'J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-107G.dwg
8/07/2023 4:00:34 PMGENERAL NOTES:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUTIS NOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGFIXTURE LOCATIONS, VERIFYING SPACE AVAILABLE FOR ALL PIPING,COORDINATING WORK WITH OTHER TRADES, DESIGN OF FINAL PLUMBINGSYSTEM AND PREPARATION OF CONSTRUCTION SHOP DRAWINGS (BASEDON THESE REVIEWS AND DESIGN/COORDINATION WORK).2.SEE STRUCTURAL DWGS FOR LOCATIONS OF FOUNDATION COMPONENTS.ITEMS SHOWN ON THIS DRAWING ARE APPROXIMATE ONLY. OFFSET ITEMSAS NEEDED TO CLEAR FOOTINGS & OTHER UNDER GROUND ITEMS.3.FOR PIPE SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE "PLUMBINGFIXTURE SCHEDULE", SHEET M-002.4.PRIOR TO BEGINNING ANY WORK, CONTRACTOR SHALL VERIFY DEPTH OFSITE PIPING AT PROPOSED CONNECTION LOCATIONS AND CONFIRM PIPINGSLOPES IN ORDER TO PROVIDE PROPER WORKING SEWER SYSTEM.5.REVIEW ALL DRAWINGS & SUBMITTALS AND VERIFY FIXTURE LOCATIONSPRIOR TO BEGINNING WORK.6.NUMBER AFTER WASTE (W) PIPE SIZE IS DFU FOR THAT SECTION OF PIPE.7.NUMBER AFTER CW & HW PIPE SIZE IS WSFU FOR THAT SECTION OF PIPE.8.PROVIDE TRAP PRIMER VALVE & TRAP PRIMER LINES TO SERVE ALL FLOORDRAINS & FLOOR SINKS.9.ROUTE WASTE PIPING FROM SUDS GENERATING FIXTURES TO COMPLY W/CODE (ROUTING DISTANCES SHOWN ARE APPROXIMATE).10.SEE RISER DIAGRAMS SHEET M-304 FOR VERTICAL WASTE/VENT PIPING.11.SEE DETAIL 2, SHEET M-304 FOR CLEAN OUT DETAIL.12.INVERT ELEVATION BASED ON FINISHED FLOOR ELEVATION OF 0.00'.13.HOSE BIBB SUPPLY LINES MAY BE RUN ABOVE GRADE IN APARTMENTCEILING SPACE.1KEYED NOTES:CONNECT TO SITE PIPING. VERIFY LOCATIONS AND COORDINATE WITHSITE CONTRACTOR.3/4" CW UP TO P-10A; PROVIDE W/ ACCESSIBLE ISOLATION VALVE.2
g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.CPATIOSTO.LIVING ROOMKITCHENBEDROOM #1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLFIRE RISERPATIOSTO.LIVING ROOMKITCHENBEDROOM #1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLg.Bg.BPATIOSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLPATIOSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALL1M-4021M-3023.201M-4021M-3023.201M-4021M-3023.201M-4021M-3023.202"CW UP/DN12"CW UP/DN12"CW UP/DN12"CW UP/DN1g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.CDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.DECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM #2LDRYHALLCLO.g.Bg.B1M-4021M-3023.201M-4021M-3023.201M-4021M-3023.201M-4021M-3023.201-1/2"CW UP/DN11-1/2"CW UP/DN11-1/2"CW UP/DN11-1/2"CW UP/DN1g.1g.3g.4g.5g.2g.6g.7g.8g.1g.3g.4g.5g.2g.6g.7g.8M-213GMECHANICAL PLANS - BUILDING 'G'J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-213G-214G.dwg
8/07/2023 4:01:37 PMGENERAL NOTES:1.SEE ENLARGED PLUMBING & HVAC PLANS ON SHEETS M-301, M-302, M-303,M-401, M-402 & M-403 FOR ADDITIONAL WORK.2.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUTIS NOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGFIXTURE LOCATIONS, VERIFYING SPACE AVAILABLE FOR ALL PIPING,COORDINATING WORK WITH OTHER TRADES, DESIGN OF FINAL PLUMBINGSYSTEM AND PREPARATION OF CONSTRUCTION SHOP DRAWINGS (BASEDON THESE REVIEWS AND DESIGN/COORDINATION WORK).3.FOR PIPING SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE “PLUMBINGFIXTURE SCHEDULE” SHEET M-002.4.ALL ISOLATION VALVES SHALL BE ACCESSIBLE. COORDINATE WORK WITHOTHER TRADES TO ENSURE ACCESSIBILITY. PROVIDE BUILDING ACCESSDOORS AS NECESSARY.5.OFFSET PLUMBING PIPING AND VTR'S TO AVOID DUCTWORK AND OTHEROBSTRUCTIONS. TERMINATE VTR'S A MINIMUM OF 15 FEET FROM ANYOUTSIDE AIR INTAKES.6.PROVIDE TRAP PRIMER VALVES AND TRAP PRIMER PIPING TO SERVE ALLFLOOR DRAINS AND FLOOR RECEPTORS. COORDINATE LOCATIONS WITHARCHITECT AND OTHER TRADES. PROVIDE ISOLATION VALVE IN CW PIPINGTO TRAP PRIMER VALVE; PROVIDE BUILDING ACCESS DOOR TO ALLOWACCESS TO VALVE AND TRAP PRIMER. SEE DETAIL 1, SHEET M-304.7.SEE RISER DIAGRAMS ON SHEET M-305 FOR UNIT WASTE & VENT PIPING.8.ALL VENTS ARE 2" UNO.9.ALL KEYED NOTES MAY NOT BE USED EVERY SHEET.10.DUCTLESS SPLIT SYSTEM HEAT PUMP REFRIGERANT LINE LENGTH ISLIMITED TO A MAX OF 65'. CONTRACTOR TO ROUTE REFRIGERANT LINESWITH SHORTEST/MOST EFFICIENT LINE LENGTH POSSIBLE.11.ORIENT OUTDOOR HEAT PUMPS FOR PROPER AIRFLOW THRU COILS W/MINOR IMPACT TO ADJACENT UNITS.1KEYED NOTES:SEE SHEET M-304 FOR APARTMENT WATER DISTRIBUTION DETAILS.OUTDOOR UNIT SERVES 3RD LEVEL INDOOR UNIT.2 1/8" = 1'-0"MECHANICAL PLAN - BUILDING 'G' - LEVEL 12'8'4'16'SCALE: 1/8" = 1'-0"0' 1/8" = 1'-0"MECHANICAL PLAN - BUILDING 'G' - LEVEL 22'8'4'16'SCALE: 1/8" = 1'-0"0'
g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.Cg.Bg.B2" VTRRG/RL LINESETS (TYP)RG/RL PIPING DN,ROUTE TO INDOORUNITS (TYP)HP-2B (TYP)2" VTR2" VTR2" VTR2" VTR2" VTR2" VTR2" VTR4" VTR (TYP)4" VTR (TYP)g.Ag.Ag.Dg.Dg.Eg.Eg.Cg.Cg.Bg.B4M-4014M-3012.234M-4014M-3012.234M-4014M-3012.234M-4014M-3012.232" VTR (TYP)4" VTR (TYP)2" VTR (TYP)DECKSTO.LIVING ROOMKITCHENBEDROOM #1ENTRYDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH #1ENTRYCLO.M.BEDROOMLDRYHALLDECKSTO.LIVING ROOMKITCHENBEDROOM #1W.I.C.BATH#2BATH #1ENTRYCLO.M.BEDROOMLDRYHALLDECKSTO.LIVING ROOMKITCHENENTRYg.1g.3g.4g.5g.2g.6g.7g.8g.1g.3g.4g.5g.2g.6g.7g.8M-214GMECHANICAL PLANS - BUILDING 'G'J O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-213G-214G.dwg
8/07/2023 4:01:39 PMGENERAL NOTES:1.SEE ENLARGED PLUMBING & HVAC PLANS ON SHEETS M-301, M-302, M-303,M-401, M-402 & M-403 FOR ADDITIONAL WORK.2.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUTIS NOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGFIXTURE LOCATIONS, VERIFYING SPACE AVAILABLE FOR ALL PIPING,COORDINATING WORK WITH OTHER TRADES, DESIGN OF FINAL PLUMBINGSYSTEM AND PREPARATION OF CONSTRUCTION SHOP DRAWINGS (BASEDON THESE REVIEWS AND DESIGN/COORDINATION WORK).3.FOR PIPING SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE “PLUMBINGFIXTURE SCHEDULE” SHEET M-002.4.ALL ISOLATION VALVES SHALL BE ACCESSIBLE. COORDINATE WORK WITHOTHER TRADES TO ENSURE ACCESSIBILITY. PROVIDE BUILDING ACCESSDOORS AS NECESSARY.5.OFFSET PLUMBING PIPING AND VTR'S TO AVOID DUCTWORK AND OTHEROBSTRUCTIONS. TERMINATE VTR'S A MINIMUM OF 15 FEET FROM ANYOUTSIDE AIR INTAKES.6.PROVIDE TRAP PRIMER VALVES AND TRAP PRIMER PIPING TO SERVE ALLFLOOR DRAINS AND FLOOR RECEPTORS. COORDINATE LOCATIONS WITHARCHITECT AND OTHER TRADES. PROVIDE ISOLATION VALVE IN CW PIPINGTO TRAP PRIMER VALVE; PROVIDE BUILDING ACCESS DOOR TO ALLOWACCESS TO VALVE AND TRAP PRIMER. SEE DETAIL 1, SHEET M-304.7.SEE RISER DIAGRAMS ON SHEET M-305 FOR UNIT WASTE & VENT PIPING.8.ALL VENTS ARE 2" UNO.9.ALL KEYED NOTES MAY NOT BE USED EVERY SHEET.10.DUCTLESS SPLIT SYSTEM HEAT PUMP REFRIGERANT LINE LENGTH ISLIMITED TO A MAX OF 65'. CONTRACTOR TO ROUTE REFRIGERANT LINESWITH SHORTEST/MOST EFFICIENT LINE LENGTH POSSIBLE.11.ORIENT OUTDOOR HEAT PUMPS FOR PROPER AIRFLOW THRU COILS W/MINOR IMPACT TO ADJACENT UNITS.1KEYED NOTES:SEE SHEET M-304 FOR APARTMENT WATER DISTRIBUTION DETAILS.OUTDOOR UNIT SERVES 3RD LEVEL INDOOR UNIT.2 1/8" = 1'-0"MECHANICAL PLAN - BUILDING 'G' - LEVEL 32'8'4'16'SCALE: 1/8" = 1'-0"0' 1/8" = 1'-0"MECHANICAL PLAN - BUILDING 'G' - ROOF2'8'4'16'SCALE: 1/8" = 1'-0"0'
P-12BP-1AP-12ACWHW7M-304WH-1HP-2AC4M-303ROUTE 3/4" CONDENSATE TO FLOORDRAIN IN OUTDOOR STORAGE;COORDINATE WITH STRUCTURALFOR PENETRATIONS THRUSTRUCTURAL & FRAMING MEMBERSMAINTAIN MINIMUMCLEARANCES PER MFR.RECOMMENDATIONS1"HW W/ HT-1FROM WH-1 TOPEX MANIFOLD1"CWDUCTLESSSPLIT SYSTEMHEAT PUMPHT-2 ON CW LINES INUNCONDITIONED SPACEP-5A1"CW14P-3AP-3AHW/CW PEXMANIFOLDSP-1A1013.63610.13STO.KITCHENENTRYBATH#1W.I.C.HALLLDRYCLO.BATH#2LIVING ROOMBEDROOM#1BEDROOM#2PATIOP-11BCLO.3P-9A(TYP)P-9BHW/CW PEXMANIFOLDS7M-3041013.36610.13CWHWP-12AP-12B3(TYP)WH-1HP-2AP-11B2C
4M-305ROUTE 3/4" CONDENSATE TO FLOORDRAIN IN OUTDOOR STORAGE;COORDINATE WITH STRUCTURALFOR PENETRATIONS THRUSTRUCTURAL & FRAMING MEMBERSMAINTAIN MINIMUMCLEARANCES PER MFRRECOMMENDATIONS1"HW W/ HT-1FROM WH-2 TOPEX MANIFOLD1"CWDUCTLESSSPLIT SYSTEMHEAT PUMPHT-2 ON CW LINES INUNCONDITIONED SPACESTO.KITCHENENTRYBATH#1W.I.C.HALLLDRYCLO.BATH#2LIVING ROOMBEDROOM#1BEDROOM#2PATIOCLO.P-5A41P-1AP-3AP-1AP-3AP-9BP-9AP-12BP-3AP-3AP-1AP-1AP-12A1114.38710.88CWHWHW/CW PEXMANIFOLDS7M-304WH-1HP-2AP-11BC 4M-303ROUTE 3/4" CONDENSATE TO FLOORDRAIN IN OUTDOOR STORAGE;COORDINATE WITH STRUCTURALFOR PENETRATIONS THRUSTRUCTURAL & FRAMING MEMBERSMAINTAIN MINIMUMCLEARANCES PER MFR.RECOMMENDATIONS1"HW W/ HT-1FROM WH-1 TOPEX MANIFOLD1"CWDUCTLESSSPLIT SYSTEMHEAT PUMPHT-2 ON CW LINES INUNCONDITIONED SPACEP-5A1"CW134P-3ADECKSTO.LIVING ROOMKITCHENBEDROOM#1W.I.C.BATH#2BATH#1ENTRYCLO.M.BEDROOMLDRYHALLREF.RP-9AP-9B3(TYP)(TYP)P-12BP-1AP-12ACWHW7M-304WH-1HP-1AP-11BC 4M-303ROUTE 3/4" CONDENSATE TO FLOORDRAIN IN OUTDOOR STORAGE;COORDINATE WITH STRUCTURALFOR PENETRATIONS THRUSTRUCTURAL & FRAMING MEMBERSMAINTAIN MINIMUMCLEARANCES PER MFR.RECOMMENDATIONS1"HW W/ HT-1FROM WH-1 TOPEX MANIFOLD1"CWDUCTLESSSPLIT SYSTEMHEAT PUMPHT-2 ON CW LINES INUNCONDITIONED SPACEP-5A1"CW14P-3AHW/CW PEXMANIFOLDS78.8847.88STO.KITCHENENTRYBATH#1HALLCLO.LDRYCLOSETLIVING ROOMBEDROOM #1DECK3P-9A(TYP)M-301ENLARGED UNIT PLUMBING PLANSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-301-302.dwg
8/07/2023 4:01:53 PMGENERAL NOTES:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUT ISNOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGFIXTURE LOCATIONS, VERIFYING SPACE AVAILABLE FOR ALL PIPING,COORDINATING WORK WITH OTHER TRADES, DESIGN OF FINAL PLUMBINGSYSTEM AND PREPARATION OF CONSTRUCTION SHOP DRAWINGS (BASED ONTHESE REVIEWS AND DESIGN/COORDINATION WORK).2.SEE GENERAL NOTES SHEET M-001.3.WATER SUPPLY TO EACH APARTMENT UNIT IS VIA PEX VALVE MANIFOLDS. SEEDETAIL ON SHEET M-304 FOR SIZING; SEE DETAIL ON SHEET M-304 FORTYPICAL APARTMENT HW/CW PIPING.PEX MANIFOLD4.MANIFOLD SIZING:MANIFOLD SUPPLY PIPING, SEE DETAIL ON M-304 FOR SIZING # = NUMBER OF FIXTURES (INCLUDES TRAP PRIMER)## = WSFU5.GC TO SELECT FINAL LOCATION OF PEX DISTRIBUTION MANIFOLDS & PROVIDEACCESS IN EACH UNIT.6.FOR PIPING SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE “PLUMBINGFIXTURE SCHEDULE” SHEET M-002.7.PROVIDE WALL CLEANOUT IN WASTE PIPING BENEATH ALL SINKS.8.CONFIRM CLEANOUT LOCATIONS IN "TYPE A+B" UNITS WITH FOUNDATIONPLANS; NOT ALL CLEANOUTS MAY BE REQUIRED DEPENDING ON UNITORIENTATION AND UNDERGROUND PIPING LAYOUT.9.CONFIRM WASTE/VENT RISER LOCATIONS IN UNITS WITH FOUNDATION PLANS;SOME RISERS MAY VARY DEPENDING ON UNIT ORIENTATION ANDUNDERGROUND PIPING LAYOUT.10.ALL ISOLATION VALVES SHALL BE ACCESSIBLE. COORDINATE WORK WITHOTHER TRADES RI ENSURE ACCESSIBILITY. PROVIDE BUILDING ACCESSDOORS AS NECESSARY.11.CONFIRM BATHTUB ORIENTATION. ARCHITECT'S DEPICTION OF BATHTUB DOESNOT NECESSARILY MATCH PLUMBING REQUIRED (OR MATCH THE BEST WAY OFROUTING PLUMBING).12.OFFSET PLUMBING PIPING AND VTR'S TO AVOID DUCTWORK AND OTHEROBSTRUCTIONS.13.ALL VENTS ARE 2" UNO.14.ROUTE PIPING SO AS NOT TO OBSTRUCT ACCESS TO EQUIPMENT.15.PROVIDE TRAP PRIMER VALVES AND TRAP PRIMER PIPING TO SERVE ALLFLOOR DRAINS AND FLOOR RECEPTORS. COORDINATE LOCATIONS WITHARCHITECT AND OTHER TRADES. PROVIDE ISOLATION VALVE IN CW PIPING TOTRAP PRIMER VALVE; PROVIDE BUILDING ACCESS DOOR TO ALLOW ACCESS TOVALVE AND TRAP PRIMER.16.SEE RISER DIAGRAMS ON SHEET M-305 FOR UNIT WASTE & VENT PIPING.17.SEE M-2XX SERIES DRAWING SHEETS FOR HOSE BIBB LOCATIONS & VENTINGPLANS.KEYED NOTES:CW PIPING UP/DN; SEE M-304, DETAIL 7.PROVIDE 1/2" TRAP PRIMER LINE TO FLOOR DRAIN. SEE DETAIL 1, M-304.WASTE/VENT PIPING UP & DN, SEE WASTE & VENT RISERS ON SHEET M-305.PROVIDE HW CONNECTION & WASTE CONNECTION, WITH AIR GAP, TODISHWASHER FROM FIXTURE.1/2"CW LINE TO TRAP PRIMER. PROVIDE W/ ACCESS DOOR.ROUTE CONDENSATE TO SAFE POINT OF DISCHARGE. VERIFY LOCATION W/OWNER & ARCHITECT PRIOR TO BEGINNING WORK.1324######56M-3012M-3011UNIT 2.21M-3013 1/4" = 1'-0"UNIT 2.23M-3014 1/4" = 1'-0"2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0' 1/4" = 1'-0"UNIT 2.20UNIT 1.12 1/4" = 1'-0"
P-12BP-1AP-12A1013.63610.13CWHWHW/CW PEXMANIFOLDS7M-304WH-1HP-2AC4M-303ROUTE 3/4" CONDENSATE TO FLOORDRAIN IN OUTDOOR STORAGE;COORDINATE WITH STRUCTURALFOR PENETRATIONS THRUSTRUCTURAL & FRAMING MEMBERSMAINTAIN MINIMUMCLEARANCES PER MFR.RECOMMENDATIONS1"HW W/ HT-1FROM WH-1 TOPEX MANIFOLD1"CWDUCTLESSSPLIT SYSTEMHEAT PUMPHT-2 ON CW LINES INUNCONDITIONED SPACEP-5B1"CW13(TYP)4PATIOSTO.LIVING ROOMKITCHENBEDROOM#1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM#2LDRYHALLP-11B3(TYP)P-9AP-9BP-1AP-3AP-3AM-302ENLARGED UNIT PLUMBING PLANSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-301-302.dwg
8/07/2023 4:01:53 PMGENERAL NOTES:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUT ISNOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGFIXTURE LOCATIONS, VERIFYING SPACE AVAILABLE FOR ALL PIPING,COORDINATING WORK WITH OTHER TRADES, DESIGN OF FINAL PLUMBINGSYSTEM AND PREPARATION OF CONSTRUCTION SHOP DRAWINGS (BASED ONTHESE REVIEWS AND DESIGN/COORDINATION WORK).2.SEE GENERAL NOTES SHEET M-001.3.WATER SUPPLY TO EACH APARTMENT UNIT IS VIA PEX VALVE MANIFOLDS. SEEDETAIL ON SHEET M-304 FOR SIZING; SEE DETAIL ON SHEET M-304 FORTYPICAL APARTMENT HW/CW PIPING.PEX MANIFOLD4.MANIFOLD SIZING:MANIFOLD SUPPLY PIPING, SEE DETAIL ON M-304 FOR SIZING # = NUMBER OF FIXTURES (INCLUDES TRAP PRIMER)## = WSFU5.GC TO SELECT FINAL LOCATION OF PEX DISTRIBUTION MANIFOLDS & PROVIDEACCESS IN EACH UNIT.6.FOR PIPING SIZES TO INDIVIDUAL PLUMBING FIXTURES SEE “PLUMBINGFIXTURE SCHEDULE” SHEET M-002.7.PROVIDE WALL CLEANOUT IN WASTE PIPING BENEATH ALL SINKS.8.CONFIRM CLEANOUT LOCATIONS IN "TYPE A+B" UNITS WITH FOUNDATIONPLANS; NOT ALL CLEANOUTS MAY BE REQUIRED DEPENDING ON UNITORIENTATION AND UNDERGROUND PIPING LAYOUT.9.CONFIRM WASTE/VENT RISER LOCATIONS IN UNITS WITH FOUNDATION PLANS;SOME RISERS MAY VARY DEPENDING ON UNIT ORIENTATION ANDUNDERGROUND PIPING LAYOUT.10.ALL ISOLATION VALVES SHALL BE ACCESSIBLE. COORDINATE WORK WITHOTHER TRADES RI ENSURE ACCESSIBILITY. PROVIDE BUILDING ACCESSDOORS AS NECESSARY.11.CONFIRM BATHTUB ORIENTATION. ARCHITECT'S DEPICTION OF BATHTUB DOESNOT NECESSARILY MATCH PLUMBING REQUIRED (OR MATCH THE BEST WAY OFROUTING PLUMBING).12.OFFSET PLUMBING PIPING AND VTR'S TO AVOID DUCTWORK AND OTHEROBSTRUCTIONS.13.ALL VENTS ARE 2" UNO.14.ROUTE PIPING SO AS NOT TO OBSTRUCT ACCESS TO EQUIPMENT.15.PROVIDE TRAP PRIMER VALVES AND TRAP PRIMER PIPING TO SERVE ALLFLOOR DRAINS AND FLOOR RECEPTORS. COORDINATE LOCATIONS WITHARCHITECT AND OTHER TRADES. PROVIDE ISOLATION VALVE IN CW PIPING TOTRAP PRIMER VALVE; PROVIDE BUILDING ACCESS DOOR TO ALLOW ACCESS TOVALVE AND TRAP PRIMER.16.SEE RISER DIAGRAMS ON SHEET M-305 FOR UNIT WASTE & VENT PIPING.17.SEE M-2XX SERIES DRAWING SHEETS FOR HOSE BIBB LOCATIONS & VENTINGPLANS.KEYED NOTES:CW PIPING UP/DN; SEE M-304, DETAIL 7.PROVIDE 1/2" TRAP PRIMER LINE TO FLOOR DRAIN. SEE DETAIL 1, M-304.WASTE/VENT PIPING UP & DN, SEE WASTE & VENT RISERS ON SHEET M-305.PROVIDE HW CONNECTION & WASTE CONNECTION, WITH AIR GAP, TODISHWASHER FROM FIXTURE.1/2"CW LINE TO TRAP PRIMER. PROVIDE W/ ACCESS DOOR.ROUTE CONDENSATE TO SAFE POINT OF DISCHARGE. VERIFY LOCATION W/OWNER & ARCHITECT PRIOR TO BEGINNING WORK.1324######56M-30212'8'SCALE 1/4" = 1'-0"1'4'0'UNIT 3.20 1/4" = 1'-0"
SURFACE CLEANOUT DETAIL NTSSEE PLAN FORPIPE ROUTINGPIPE INDEPENDENT OFCLEANOUT BOXFINISHGRADE24"X24"X6"CONCRETEPADCLEANOUTBOX2M-304TRAP PRIMER DETAIL NTS1/2" (TYP)ACCESS DOORTRAP PRIMER VALVEFINISHED FLOORTO FLOOR DRAINTRAP (TYP)PRIMER MANIFOLD(S) (WHERESERVING MORE THAN ONEFLOOR DRAIN)CW LINE1M-304WASTE PIPE TOP-TRAP, SEEPLAN FOR SIZETRAP PRIMERLINEFLOORS WITH EMBEDWATERPROOF MEMBRANESMEMBRANE BELOWFLASHING COLLAR3M-304HEAT PUMP WATER HEATER DETAIL NTSSEISMIC STRAP (TYP)R-10 RIGID INSULATION1" HWRELIEF VALVE, PIPEDISCHARGE FULL SIZETO FLOOR DRAIN4M-3041" CW1.EXPANSION TANK PIPING, RELIEF VALVE PIPING, HEAT TRACED PIPING, AND ALLOTHER PIPING WITHIN 18" OF WATER HEATER CONNECTION SHALL BE COPPER.2.PROVIDE MINIMUM INSTALLATION CLEARANCES PER MFR. RECOMMENDATIONS.PROVIDE MINIMUM 30" CLEARANCE IN FRONT OF UNIT FOR MAINTENANCE ACCESS.NOTES:GALVANIZED SHEETMETAL PAN3/4" DRAIN; PIPETO FLOOR DRAINWATERHEATEREXHAUST DUCT TOWALL CAP W/ BDD6M-304APARTMENT UNIT WATER DISTRIBUTION RISERM-3047NTSNOTE:FOR SIZES TO INDIVIDUAL PLUMBING FIXTURES, SEE PLUMBING FIXTURE SCHEDULE ON SHEET M-002.FINISH FLOOR(CONSTRUCTION VARIES)FIXTURECOUNTMANIFOLD CONFIGURATION2 2 PORT MANIFOLD3 4 PORT MANIFOLD, (1) CAPPED4 4 PORT MANIFOLD5 6 PORT MANIFOLD, (1) CAPPED6 6 PORT MANIFOLD7 8 PORT MANIFOLD, (1) CAPPED8 8 PORT MANIFOLD9 10 PORT MANIFOLD, (1) CAPPED10 10 PORT MANIFOLDMINIMUM LINE SIZEPEX PIPE TABLELINESIZEMAXIMUM WATERSUPPLY WSFU(BASED ON 8FPS)1/2"33/4"7.51"191-1/4"331-1/2"502"135WATER SUPPLY DISTRIBUTION GENERAL NOTES:1.WATER SUPPLY MAINS SHALL BE OF MATERIAL AS SPECIFIED ON SHEETM-001. MANIFOLD WATER SUPPLY LINES SERVING INDIVIDUAL DWELLINGUNITS SHALL BE PEX. MANIFOLDS SHALL BE PROVIDED WITH 1/2" FITTINGSFOR PEX TUBE CONNECTION. 1/2" PEX TUBING SHALL SUPPLY INDIVIDUALFIXTURES FROM MANIFOLDS. SIZES PER THE TABLES ON THIS SHEET OR ASSHOWN ON THE PLANS.2.WATER SUPPLY TUBING SHALL BE RUN CONTINUOUSLY FROM MANIFOLD TOFIXTURE WITHOUT FITTINGS, SUPPLYING ONLY ONE FIXTURE.3.INSTALLATION SHALL COMPLY WITH TUBING MANUFACTURER'SINSTALLATION INSTRUCTIONS.4.ISOLATION VALVES SHALL BE IN ACCESSIBLE LOCATION ABOVE CEILINGS ORACCESSIBLE THROUGH ACCESS PANEL DOORS. COORDINATE INSTALLATIONLOCATIONS WITH GENERAL CONTRACTOR.5.SYMBOL NOMENCLATURE:MANIFOLD SYMBOLS###MANIFOLD SUPPLYLINE SIZETOTAL NUMBER OF WATERSUPPLY FIXTURE UNITSSERVED BY THIS MANIFOLDFIXTURE COUNT, TOTALNUMBER OF FIXTURESSERVED BY THIS MANIFOLDNTSAPARTMENT MANIFOLD/PIPE SIZINGACCESSIBLE APARTMENTUNIT VALVE (TYP)CW MAIN CONCEALED INWALL OR CEILING, SEEPLANS FOR ROUTINGLEVEL 2LEVEL 1CW MAIN, SEEFOUNDATION PLANSFOR SIZELEVEL 34M-304ATTIC1-1/2"CWPIPING RUN BELOWATTIC INSULATION1"CW1"CWWATER HEATER,(TYP)PEX CW VALVEMANIFOLD (TYP)PEX HW VALVEMANIFOLD (TYP)PEX PIPING ROUTED TOFIXTURE, SEE SCHEDULETHIS SHEET FOR SIZING (TYP)CONTRACTOR TO SELECTACCESSIBLE LOCATIONS FORPEX MANIFOLDSPROVIDE ISOLATION VALVESON ALL HW/CW RUNS FROMPEX MAINIFOLDS TO FIXTURESERVED; VALVES MAY BESTOP VALVES @ FIXTURES1"HW1"CW2"CWFUNNEL FLOORDRAINFUNNEL FLOOR DRAIN DETAIL NTSM4M-3041"CWWATER HEATER,(TYP)PEX CW VALVEMANIFOLD (TYP)PEX HW VALVEMANIFOLD (TYP)PEX PIPING ROUTED TOFIXTURE, SEE SCHEDULETHIS SHEET FOR SIZING (TYP)CONTRACTOR TO SELECTACCESSIBLE LOCATIONS FORPEX MANIFOLDSPROVIDE ISOLATION VALVESON ALL HW/CW RUNS FROMPEX MAINIFOLDS TO FIXTURESERVED; VALVES MAY BESTOP VALVES @ FIXTURESM4M-3041"CWWATER HEATER,(TYP)PEX CW VALVEMANIFOLD (TYP)PEX HW VALVEMANIFOLD (TYP)PEX PIPING ROUTED TOFIXTURE, SEE SCHEDULETHIS SHEET FOR SIZING (TYP)CONTRACTOR TO SELECTACCESSIBLE LOCATIONS FORPEX MANIFOLDSPROVIDE ISOLATION VALVESON ALL HW/CW RUNS FROMPEX MAINIFOLDS TO FIXTURESERVED; VALVES MAY BESTOP VALVES @ FIXTURESMWATER METER W/ REMOTEREADING CAPABILITIES; SELECTPER CODE & TYPE AS SELECTED BYOWNER; COORDINATE W/ E.C. FORREQUIRED CONNECTIONS (TYP)8"Ø1"HW1"CW1"HW1"CW3/4" CONDENSATE;PIPE TO FLOOR DRAINEXPANSION TANK,PRE-CHARGE TO BLDGPRESSURE, MIN 2 GALCW TO EACH APARTMENT UNIT,CONCEALED IN CEILING OR WALL(TYP)INSTANTANEOUS WATER HEATER NTS8M-304FINISHED FLOORHW TO FIXTUREINSTANTANEOUS ELECTRICWATER HEATER, MOUNT ASHIGH BELOW FIXTURE ASPOSSIBLECW TO WH, W/ INLINE STOPVALVECW ANGLE STOP VALVEFIXTURE AS NOTED ONDRAWINGS. TYPE VARIES.M-304PLUMBING DETAILSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-304-305.dwg
8/07/2023 4:02:03 PM
Scale: NTSScale: NTSWASHERWASTE & VENT RISERTUB/SHOWERWASTE & VENT RISERAM-305BM-305Scale: NTSKITCHEN SINKWASTE & VENT RISERCM-305Scale: NTSWATER CLOSETWASTE & VENT RISERDM-305Scale: NTSLAVATORYWASTE & VENT RISEREM-3052
"W
3
"W1-1/2"V2
"
VKITCHENSINKKITCHENSINK2"W2
"W
2
"W
3
"W1-1/2"V2
"
VTUB/SHOWER2"WTUB/SHOWERROUTE TO VTR'S2
"W
3
"W
3
"W1-1/2"V2
"
V2"WWASHERWASHERROUTE TO VTR'SROUTE TO VTR'SWC
O WC
O
2"W2"W1-1/2"V2"V2"WLAVLAVROUTE TO VTR'SWCWC 3"W3"W3"W2"V2"V4"WROUTE TO VTR'SWASHERTUB/SHOWERKITCHENSINKWC
O LAVWC
9 DFU6 DFU6 DFU3 DFU1-1/2"V1-1/2"V1-1/2"V9 DFU2"V6 DFU4 DFU2 DFU2"W1-1/2"V2"V6 DFUM-305RISER DIAGRAMSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-304-305.dwg
8/07/2023 4:02:03 PM
WH-18"ØLOUVERED DOOR, SEEARCHITECTURAL PLANS1TRG/RLPIPING UPHP-2ATEH-1500STO.KITCHENENTRYBATH#1W.I.C.HALLCLOSETLDRYCLOSETBATH#2LIVING ROOMBEDROOM#1BEDROOM#2PATIO2145TEH-1500EF-50EF-50SSSDOA-1DH-16x6CEG506x6CD-450RANGE HOOD64"Ø(TYP)3(TYP)LOUVERED DOOR,SEE ARCH PLANSRANGE HOODHP-2ARG/RLPIPING UP8"ØEH-15006x6CD-4504"ØSSEF-506x6CEG50EH-1500EF-50S4"Ø TYPWH-14TTTKITCHENENTRYBATH#1W.I.C.HALLCLO.LDRYCLO.BATH#2LIVING ROOMBEDROOM#1BEDROOM#2PATIODOA-1DH-115264"Ø(TYP)3(TYP)2WH-18"ØLOUVERED DOOR, SEEARCHITECTURAL PLANSTRG/RLPIPING UPHP-2A3(TYP)1DECKSTO.LIVING ROOMKITCHENBEDROOM#1BATH#2BATH#1ENTRYCLO.M.BEDROOMLDRYHALLTEH-1500TEH-1500DOA-1DH-1EF-50EF-50SS6x6CD-4506x6CEG50S45RANGE HOOD64"Ø(TYP)WH-18"ØLOUVERED DOOR, SEEARCHITECTURAL PLANS1EF-50TRG/RLPIPING UPHP-1ATEH-1500STO.KITCHENENTRYHALLCLO.LDRYCLOSETLIVING ROOMBEDROOM #1DECK2BATH#15RANGE HOOD6x6WSG506x6CEG50S464"Ø(TYP)3(TYP)DOA-1DH-1M-401ENLARGED UNIT HVACPLANSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-401-402.dwg
8/07/2023 4:02:10 PMM-4012M-4011UNIT 2.21M-4013 1/4" = 1'-0"UNIT 2.23M-4014 1/4" = 1'-0"2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0'2'8'SCALE 1/4" = 1'-0"1'4'0' 1/4" = 1'-0"UNIT 2.20UNIT 1.12 1/4" = 1'-0"GENERAL NOTES:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUTIS NOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGAIR INLET/OUTLET LOCATIONS, VERIFYING CONTROL DEVICE LOCATIONS,VERIFYING PROPER DUCT SIZES, VERIFYING SPACE AVAILABLE FOR ALLEQUIPMENT, VERIFYING SPACE AVAILABLE FOR ALL DUCTWORK,VERIFYING RELIEF AIR PATH, COORDINATING WORK WITH OTHER TRADES,FINAL DESIGN OF HVAC SYSTEMS AND PREPARATION OF FINALCONSTRUCTION SHOP DRAWINGS (BASED ON THESE REVIEW EFFORTSAND DESIGN/COORDINATION WORK).2.SEE MECHANICAL NOTES ON SHEET M-001.3.LOCATE ALL EQUIPMENT, DAMPERS, AND ITEMS REQUIRING ADJUSTMENTOR MAINTENANCE TO BE ACCESSIBLE. PROVIDE BUILDING ACCESS DOORSAS REQUIRED. PROVIDE DUCT ACCESS DOORS AT ALL BDD'S ANDMOTORIZED DAMPERS.4.DUCTWORK SHALL BE CONSTRUCTED TO THE PRESSURE CLASSCORRESPONDING TO THE FAN STATIC PRESSURE THAT SERVES THE DUCT,BUT NO LESS THAN 1-INCH WG (PLUS/MINUS AS APPROPRIATE). SEALDUCTWORK FOR SEAL CLASS C PER CODE REQUIREMENTS.5.ALL DUCTS ARE PRELIMINARY AND ARE TO INDICATE FREE AREAREQUIRED AND HAVE NOT BEEN VERIFIED TO FIT. CONTRACTOR ISRESPONSIBLE TO REVIEW DRAWING AND SELECT FINAL DUCT SIZES ANDROUTING TO SERVE CONSTRUCTION.6.DUCTWORK TO BE ROUTED IN JOIST SPACE; SEE ARCHITECTURAL PLANSFOR JOIST BAY FIRE PROOFING WHERE DRYER & RANGE EXHAUST DUCTSARE ROUTED WITHIN JOIST BAYS. SEE STRUCTURAL PLANS FOR JOISTPENETRATION REQUIREMENTS.7.EXHAUST OUTLETS TO MAINTAIN 3' SEPARATION FROM ALL OPERABLEOPENINGS.8.SEE M-2XX SERIES DRAWING SHEETS FOR REFRIGERANT PIPE ROUTING &OUTDOOR HEAT PUMP LOCATION.9.SEE WATER HEATER DETAIL 4/M-304.10.SEE ELECTRICAL FOR POWER & FAN SWITCHES.11.COORDINATION ALL DUCT ROUTING W/ GC FOR ROUTING & SOFFITREQUIREMENTS.12.VERIFY PREFERRED LOCATION OF EF'S W/ OWNER & ARCHITECT PRIOR TOROUGH-IN.1KEYED NOTES:4"Ø EXHAUST DUCT.6"Ø RANGE EXHAUST DUCT.TERMINATE DUCT WITH WALL CAP MINIMUM 3' FROM OPERABLE OPENINGS.PROVIDE SIGN AT SWITCH TO READ: "WHOLE HOUSE VENTILATION (LEAVE ONUNLESS OUTDOOR AIR QUALITY IS VERY POOR)."ROUTE TO OUTDOOR UNIT, LOCATED ON ROOF.FACTORY-BUILT COMBINATION INTAKE/ EXHAUST TERMINATION.12x12 TG, W/ 1212 TD. PROVIDE W/ ELBOWS AS SHOWN.12"Ø UP TO RVI.12"Ø UP TO RVR.23456789
2WH-18"ØLOUVERED DOOR, SEEARCHITECTURAL PLANSTRG/RLPIPING UPHP-2A3(TYP)1PATIOSTO.LIVING ROOMKITCHENBEDROOM#1BATH#2BATH#1ENTRYCLO.M.BEDROOMBEDROOM#2LDRYHALLTEH-1500TEH-1500DOA-1DH-16x6CEG506x6CD-450EF-50EF-50TEH-15005RANGE HOODS44"Ø (TYP)SS6M-402ENLARGED UNIT HVACPLANSJ O B N O. :I S S U E D A T E :D R A W N B Y :R E V I S E D :S H E E TP R O J E C T FAX:PHONE:207 FOURTH AVENUE SOUTHEAST,PUYALLUP, WASHINGTON 98372ROSS DECKMAN & ASSOCIATES INC.R D A253 . 840 . 9405253 . 840 . 9503+APPROVAL STAMPSTAHOMA TERRA APARTMENTS PHASE II
-- TAHOMA BLVD SE
YELM, WA 98597
21208/7/2023MBPERMIT SET8/7/2023#DESC.DATE
SIGNED8/7/2023general@hultzbhu.comPhone: (253) 383-32571111 Fawcett Ave Suite 100e n g i n e e r s i n c HULTZFax: (253) 383-3283Job Number:Tacoma, WA 98402BHU23-082I:\2023 Jobs\23-082\Drawings\Mech\23-082_M-401-402.dwg
8/07/2023 4:02:11 PMM-40212'8'SCALE 1/4" = 1'-0"1'4'0'UNIT 3.20 1/4" = 1'-0"GENERAL NOTES:1.THESE DRAWINGS HAVE BEEN PREPARED FOR PERMIT. FINAL DESIGN ANDDETAILING IS BY THE CONTRACTOR. FINAL DESIGN WORK INCLUDES (BUTIS NOT LIMITED TO): REVIEW OF ALL CONTRACT DOCUMENTS, VERIFYINGAIR INLET/OUTLET LOCATIONS, VERIFYING CONTROL DEVICE LOCATIONS,VERIFYING PROPER DUCT SIZES, VERIFYING SPACE AVAILABLE FOR ALLEQUIPMENT, VERIFYING SPACE AVAILABLE FOR ALL DUCTWORK,VERIFYING RELIEF AIR PATH, COORDINATING WORK WITH OTHER TRADES,FINAL DESIGN OF HVAC SYSTEMS AND PREPARATION OF FINALCONSTRUCTION SHOP DRAWINGS (BASED ON THESE REVIEW EFFORTSAND DESIGN/COORDINATION WORK).2.SEE MECHANICAL NOTES ON SHEET M-001.3.LOCATE ALL EQUIPMENT, DAMPERS, AND ITEMS REQUIRING ADJUSTMENTOR MAINTENANCE TO BE ACCESSIBLE. PROVIDE BUILDING ACCESS DOORSAS REQUIRED. PROVIDE DUCT ACCESS DOORS AT ALL BDD'S ANDMOTORIZED DAMPERS.4.DUCTWORK SHALL BE CONSTRUCTED TO THE PRESSURE CLASSCORRESPONDING TO THE FAN STATIC PRESSURE THAT SERVES THE DUCT,BUT NO LESS THAN 1-INCH WG (PLUS/MINUS AS APPROPRIATE). SEALDUCTWORK FOR SEAL CLASS C PER CODE REQUIREMENTS.5.ALL DUCTS ARE PRELIMINARY AND ARE TO INDICATE FREE AREAREQUIRED AND HAVE NOT BEEN VERIFIED TO FIT. CONTRACTOR ISRESPONSIBLE TO REVIEW DRAWING AND SELECT FINAL DUCT SIZES ANDROUTING TO SERVE CONSTRUCTION.6.DUCTWORK TO BE ROUTED IN JOIST SPACE; SEE ARCHITECTURAL PLANSFOR JOIST BAY FIRE PROOFING WHERE DRYER & RANGE EXHAUST DUCTSARE ROUTED WITHIN JOIST BAYS. SEE STRUCTURAL PLANS FOR JOISTPENETRATION REQUIREMENTS.7.EXHAUST OUTLETS TO MAINTAIN 3' SEPARATION FROM ALL OPERABLEOPENINGS.8.SEE M-2XX SERIES DRAWING SHEETS FOR REFRIGERANT PIPE ROUTING &OUTDOOR HEAT PUMP LOCATION.9.SEE WATER HEATER DETAIL 4/M-304.10.SEE ELECTRICAL FOR POWER & FAN SWITCHES.11.COORDINATION ALL DUCT ROUTING W/ GC FOR ROUTING & SOFFITREQUIREMENTS.12.VERIFY PREFERRED LOCATION OF EF'S W/ OWNER & ARCHITECT PRIOR TOROUGH-IN.1KEYED NOTES:4"Ø EXHAUST DUCT.6"Ø RANGE EXHAUST DUCT.TERMINATE DUCT WITH WALL CAP MINIMUM 3' FROM OPERABLE OPENINGS.PROVIDE SIGN AT SWITCH TO READ: "WHOLE HOUSE VENTILATION (LEAVE ONUNLESS OUTDOOR AIR QUALITY IS VERY POOR)."ROUTE TO OUTDOOR UNIT, LOCATED ON ROOF.FACTORY-BUILT COMBINATION INTAKE/ EXHAUST TERMINATION.12x12 TG, W/ 1212 TD. PROVIDE W/ ELBOWS AS SHOWN.12"Ø UP TO RVI.12"Ø UP TO RVR.23456789