Loading...
Structural BUILDING A - 2018 IBC - PLANS ~ 10-23-23GENERAL NOTES: The Structure has been designed to resist code -required vertical and lateral forces after the construction of all structural elements have been completed. Stability of the structural elements prior to completion is the sole responsibility of the General Contractor. Builder is to verify all dimensions prior to starting work. All changes to structure must be reviewed and approved by Phillips Structural Engineering. All materials, methods, and workmanship shall be in accordance with the International Building Code (IBC) 2018 Edition. The Builder is responsible for using safe work practices and conforming to all safety ordinances. Any construction observation performed by the Structural Engineer is for general conformance with design aspects per IBC 1704.6 and is not intended in any way to review the General Contractor's construction procedures. Structural observation does not waive the responsibility for special inspections per Section 1705. STANDARDS: All methods, materials and workmanship shall conform to the 2018 International Building Code (IBC) as amended and adopted by the local Building Official or applicable jurisdiction. STRUCTURAL DESIGN CRITERIA AND LOADING: ROOF LOADING: • DEAD LOAD = 20PSF (NO TILE WEIGHT INCLUDED) • ROOF LIVE LOAD (Lr) = 20PSF • TYPICAL FLAT ROOF SNOW LOAD (Pf) = 25PSF • SNOW EXPOSURE FACTOR (Ce) = 1.0 • SNOW LOAD IMPORTANCE FACTOR (Is) = 1.0 **TYPICAL ROOF SNOW LOAD SHALL NOT BE LESS THAN 25PSF WIND DESIGN DATA: • BASIC DESIGN WIND SPEED (V) = 110 MPH • ALLOWABLE STRESS DESIGN WIND SPEED (Vasd) = 85 MPH • RISK CATEGORY = II • WIND IMPORTANCE FACTOR (Iw) = 1.0 • WIND EXPOSURE = " B" • TOPOGRAPHICAL EFFECT (Kzt) = 1.00 EARTHQUAKE DEIGN DATA: • RISK CATEGORY = II • SEISMIC IMPORTANCE FACTOR (le) = 1.0 • MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS - Ss = 1.29 - S1 = 0.47 • SEISMIC DESIGN CATEGORY (SDC) _ " D" • BASIC SEISMIC FORCE -RESISTING SYSTEM = LIGHT -FRAMED (WOOD) WALLS SHEATHED WITH WOOD STRUCTURAL PANEL RATED FOR SHEAR RESISTANCE • RESPONSE MODIFICATION FACTOR (R) = 6.5 • ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE SOIL INFORMATION: Per the soils report prepared by Insight Geologic, Inc. an Allowable Soil Bearing Pressure (ASBP) of 3000psf has been used for design. It is the contractor's responsibility to verify that all footings bear on firm/unyielding, undisturbed earth or compacted "Structural Fill" that meets or exceeds the allowable soil bearing pressure. Soils under footings and slabs to be a minimum of 95% compacted per the Modified Proctor Density Test (ASTM D1557). All construction on fill shall be reviewed by a licensed Geotechnical Engineer. FOUNDATIONS: Bottom of exterior footings shall be a minimum of 18" below finished grade for frost protection U.N.O. bearing on undisturbed native soils. Backfill with dry, free draining soils. Backfill next to any retaining walls with a minimum of 12" gravel or free draining soil per typical detailing. Appropriate drainage shall be provided adjacent to the base of exterior foundations draining to daylight per Soils Engineer requirements. CONCRETE: All concrete materials and placement shall conform to the current ACI 318 code. Concrete shall be made with Portland Cement ASTM C-150 Type II or Type I and shall be Ready -Mixed per ASTM C-94. Minimum compressive strength shall be 3000 PSI* at 28 days with a minimum water/cement ratio of 0.45. All concrete shall be air entrained 5 ±1 %. Max aggregate size = 7/8". *Special Inspection not required for concrete compressive strength. 3000 PSI compressive strength has been specified for weathering protection. Structural design of concrete has been based on 2500 PSI compressive strength. PLAN VERACITY: Every attempt has been made to insure the accuracy of these engineered documents, site conditions, product availability, etc. All information listed above must be verified prior to construction and fabrication. Any changes or deficiencies on or to the plan must be transmitted to Phillips Structural Engineering, PLLC for written approval. LICENSE OF ENGINEERING DOCUMENTS: 1. Grant of License. Phillips Structural Engineering, PLLC grants the Licensee a nonexclusive Right of Use for the purpose of constructing a single structure (use) from this engineering package. Future uses of this drawing set are permitted when accompanied by an originally stamped "Site Specific Re -Use Letter" for each additional site and payment has been made to Phillips Structural Engineering, PLLC. 2. Ownership of Engineering Calculations and Drawings. Phillips Structural Engineering, PLLC shall retain "Title 17 USC Rights and Ownership" of the Copyright Law of The United States of America of these Engineering Documents and all subsequent copies of the engineering. The Licensee is not permitted unlimited reuse of these documents without prior consent. 3. Copy and Transfer Restrictions: Unauthorized copying of the Engineering documents is strictly forbidden. The Engineering is permitted to be used by the Licensee only, and may not be transferred to a 3rd party without prior written consent of Phillips Structural Engineering, PLLC. PHLUPS 37RUC7URAL EHOHEERHO REINFORCING STEEL: All reinforcing steel to be GRADE 60 PER ASTM A-615. Reinforcement lap splices shall be the greater of 32 bar diameters or 18". Lap horizontal steel at all corners and intersections in footings and walls with continuous corner bars. Footing reinforcement shall run continuous thru pad/expanded footings. Minimum concrete cover over reinforcing steel shall be provided as follows: • INTERIOR FACES OF SLAB AND WALL BARS = 1%2 " • EXPOSED TO WEATHER OR EARTH = 1%2" AT #5 AND SMALLER AND 2" AT #6 AND LARGER. • CONCRETE CAST AGAINST SOIL = 3" WOOD FRAMING AND CARPENTRY: General Requirements: Provide minimum nailing per 2018 IBC table 2304.10.1 or as indicated on the drawings. Do not notch or drill structural members, except as permitted by the Engineer. Framing Connectors: Only ICC / IAPMO approved connectors shall be used in framing applications as manufactured by Simpson Strong -Tie or equivalent. Provide maximum size and quantity of fasteners shown in the manufacturer's catalog U.N.O. Fasteners: Bolts shall be per ASTM A-307 with standard cut washers or malleable iron washers. Post -installed anchors require Engineer's approval prior to installation. Contact Phillips Structural Engineering for possible alternatives. Nails shall be common wire nails or equivalent pneumatically drive nails (P -nails), American or Canadian manufacturer only as indicated below. P -nails shall be installed per the manufacturer's guidelines. COMMON WIRE NAIL DIAMETER (INCHES) MINIMUM LENGTH NAIL (INCHES) APPLICATION 8d COMMON 0.131 2%" SHEATHING 1 O COMMON 0.148 2y" SHEATHING N/A 0.131 3" FRAMING 12d COMMON 0.148 3X" FRAMING 16d COMMON 0.162 3%2" FRAMING Wood Sheathing (Structural): Roof sheathing shall be %2" CDX or 7/6" OSB nailed w/ 8d @ 6" o.c. along panel edges, and 12" o.c. in field. Span index shall be 24/0. Plywood Sub Flooring shall be 3/4" T&G CDX or OSB (glued & nailed). Nailing shall be 1 Od @ 6"o.c. along panel edges, and 12"o.c. in field (U.N.O.) Span index shall be 48/24. Stagger all end laps per typical detailing. All sheathing shall bear the grade trademark of the American Plywood Association (APA). Studs: All studs shall be kiln dried (KD) or surface dried (SD). Each stud shall bear the stamp of the West Coast Lumber Inspection Bureau (WCLIB) or Western Wood Products Association (WWPA) showing grade mark or approved equal. All studs and framing material shall be 2x nominal minimum material and species shall be a minimum of Doug -Fir #2 meeting the following minimum strength properties: Fb= 900psi, Fv=180psi, E=1,600,000psi. Headers: All headers (HDR) not specified or otherwise noted on the plan with spans <_5-0" are to be 4x8 DF#2 or (2)2x10 HF#2 with at least one cripple and one king stud at each end. Spans between 5-0" and 8'-0" shall have headers as noted on plan and have at least two cripples and one king stud U.N.O. Spans greater that 8'-0" shall have framing and support per plan. Heavy Timbers: All timbers above sizes listed above including posts and beams shall be Doug -Fir #2 or better (Typically 6x beams and posts). Glu -Laminated Beams (GLB): All GLB shall be in conformance with ANSI Al 90. 1, American National Standards for Structural Glue -Laminated Timber. Grade 24F -V4 shall meet or exceed the following minimum structural properties: Fb=2400psi, Fv=240psi, E=1,800,000psi and shall be used at simple spans. Grade 24F -V8 shall be used at continuous and cantilevered spans. As an alternative at continuous/cantilevered spans an equivalent size (width x depth) PSL beam may be substituted (see below). Parallel Strand Lumber (PSL): All PSL shall be in conformance with ASTM D2559 and NER-292. PSL strength requirements shall meet or exceed the following minimum structural properties: Fb=2,900psi, Fv=290psi, E=2,000,000psi. Laminated Veneer Lumber (LVL): All LVL shall be in conformance with ASTM D2559. LVL shall be made of Doug -Fir (DF)and meet or exceed the following minimum structural properties: Fb= 2,600psi, Fv=285psi, E=1,900,000psi. Preservative Treatment (P.T.): All exposed framing including lumber, plywood and deck materials shall be pressure treated with 0.25#/cf pentachlorophenol per AWPA specification P-5 or other approved treatment. All cutting and boring after pressure treatment shall be cared for in accordance with AWPA specification M-4. Exposed framing includes, but is not limited to: 1. Joists, girders and subfloor that is closer than 18" to exposed ground in crawl spaces. 2. Wood framing (including sheathing) that rest on exterior foundation stem walls and is 8" or less from exposed earth. 3. Any other wood product in direct contact with concrete or masonry. Wood Connectors at P.T. Conditions: Metal connectors which are in contact with pressure treated wood shall be protected with one of the following: Simpson "ZMAX" G185 Galvanization, Triple Zinc Coated, hot Dipped Galvanized or other approved method. Pre -Engineered Roof Trusses: All prefabricated wood roof trusses shall be designed by or under the direct supervision of a licensed Professional Engineer registered in the state where the structure is located. The truss shop drawings shall bear the stamp of that Engineer and shall be fabricated and installed per the latest Truss Plate Institute standards. Where trusses are not provided to complete the roof system, overframing members with positive connections shall be provided as directed by the Truss Engineer. Details on overframing shall be provided in the truss shop drawing package which shall be consistent with the modeling of the trusses. All necessary temporary and permanent bridging, blocking, pre -notched plates, hangers, etc. for the stability of the truss elements under gravity and lateral loads shall be designed, detailed/specified and furnished by the manufacturer. The Truss Manufacturer shall verify all setbacks, dimensions and bearing points prior to fabrication. Deviations from the layout shown on approved engineering plans shall be submitted to PSE for further evaluation. Maximum allowable deflections shall be as follows: Roof Total Load = L/360 or 1" (whichever is less) Roof Snow/Live Load = L/480 or 3/4" (whichever is less) Trusses shall be designed for the spans and conditions shown and be constructed from a minimum of Hem -Fir timber and be furnished and installed in conformance with the manufacturer's published specifications. Additional concentrated loads from mechanical units and misc. equipment shall be accounted for/coordinated with sub -contractors, the Designer of Record and Truss Engineer. Framing has been designed assuming Hem -Fir plates w/ 405psi crushing capacity, truss engineer to confirm compatibility and add bearing enhancers or additional support as required. Where trusses align with shear walls, truss engineer to design and provide a truss that has been designed to transfer lateral wind and seismic forces as shown on the plans. Loading indicated (100plf minimum) shall be designed by the truss engineer to transfer from roof or floor sheathing to shearwall below. Shop drawings including truss engineering shall be submitted to the Engineer of Record for approval prior to submittal to the jurisdiction and fabrication. Should the truss engineering not be submitted to the Engineer of Record for review the builder is assuming responsibility and proceeding at their own risk. Alteration of the truss layout indicated on the plans may require supporting structural and foundation changes, therefore prior approval by the designer and Structural Engineer is required. Trusses shall not be field altered in any way without written approval from the Licensed Truss Engineer of Record. STRUCTURALSTEEL A. ALL DETAILING, FABRICATION, AND ERECTION SHALL CONFORM TO THE AISC "MANUAL OF STEEL CONSTRUCTION. "STEEL SHALL CONFORM TO THE FOLLOWING, UNO: ALL STEEL, UNO ANGLES CHANNELS, EMBEDMENTS IN CONCRETE AND MISC. METALS, UNO SQUARE AND RECTANGULAR ASTM A992, GRADE 50 ASTM A36, Fy = 36 ksi ASTM A36, Fy = 36 ksi OR STEEL TYPES LISTED UNDER "ALL STEEL" ASTM A500, GRADE B, Fy = 46 ksi C. ALL WORK SHALL BE IN ACCORDANCE WITH THE AISC SPECIFICATION. B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ERECTION AIDS THAT INCLUDE, BUT ARE NOT LIMITED TO: ERECTION ANGLES; LIFT HOLES, AND OTHER AIDS. D. GROUT FOR BEARING PLATES (IF REQUIRED) SHALL BE NON -SHRINK EMBECO BY MASTER BUILDERS, INC. OR APPROVED EQUAL. SYMBOL & ABBREVIATIONS LEGEND: X BEAM # CALLOUT (REF. CALCULATIONS) ® C XI HOLD DOWN CALLOUT (REF. HOLDOWN TABLE) S W # SHEARWALL CALLOUT (REF. SHEARWALL TABLE) X SECTION REFERENCE A. B. ANCHOR BOLT AFF ABOVE FINISHED FLOOR C.I.P. CAST IN PLACE CONC. CONCRETE E. N. SHEARWALL EDGE NAIL E.O.R. ENGINEER OF RECORD E. W. EACH WAY FDN. FOUNDATION F. F. FINISHED FLOOR GWB GYPSUM WALL BOARD HDR HEADER (SEE STRUCTURAL NOTES FOR SIZE) L.B.W. LOAD BEARING WALL MFR MANUFACTURER (N) NEW O.C. ON CENTER P. E. PRE-ENGINEERED P.T. PRESSURE TREATED S. W. SHEARWALL T.O.F. TOP OF FRAMING T.O.W. TOP OF WALL U.N.O. UNLESS NOTED OTHERWISE V.I.F. VERIFY IN FIELD SHEAR WALL (SW) AND ANCHORAGE SCHEDULE (DOUG -FIR) (o) Label ASD S.W. Capacity (PLF) Seismic/Wind Minimum RequiredStud APA Rated Sheathing (panel) (A) (B) (C) (D) (N) Panel Edge Nailing ®Sheathing Edges (D) (E) (K) & Blocking Size ®Adjoining Panel Edges (C) (F) (L) Rim Joist Or Block Connection To Top Plate (n (ap (Does not apply to crawlspace) 2x Bottom Plate Attachment Sill Plate Attachment (0)Anchor Bolt & Concrete Below (J) (K) (M) Sill Plate Size ®Fdn. Nailin To Wood Below (I) SW6 260/365 / 316'"OSB 1 Side () 0.131x2Yz' ®6" O.C. 2x_ LTP4 ®30"OC 16d ®6" O.C. OR 12d � 4" O.C. 5/8 @ 48" O.C. 2x SW4 380/532 z/6"OSB (1) Side 0.131x2Y2' ® 4" O.C. 2x_ LTP4 0 16"OC 16d ® 4" O.C. OR 12d @ 3" O.C. W @ 32" O.C. 2x SW3 490/685 �16'OSB (1) Side 0.131x2Y2" ® 3" O.C. 3x_ LTP4 0 10"OC 16d ® 3Y2" O.C. 9/8" ® 24" O.C. 2x 1.) PROVIDE APA APPROVED GLUE, I I I (2) 2X KINGM N NAIL ALL PLYWOOD TO JOISTS II I°I II II TYP. U) Z PER GENERAL NOTESII II I.I II I STUD ALI.I°I°I TYPICAL WALL FRAMING MANDATORY NOTES A. ALL SHEATHING PANELS SHALL BE INSTALLED HORIZONTALLY TO ALL WALL FRAMING (4'x8' SHEETS TYPICALLY). BLOCK ALL PANEL EDGES. B. N/A C. BLOCK ALL SHEATHING PANEL EDGES D. SHEARWALL SHEATHING/NAILING SHALL BE PROVIDED THE ENTIRE LENGTH OF THE WALLS INDICATED ON THE PLANS. ENDS OF FULL HEIGHT SHEARWALLS ARE DESIGNATED BY EXTERIOR BUILDING CORNERS, CORRIDORS, WALL PENETRATIONS OR AS DESIGNATED ON THE PLANS. SEE PLANS & TABLE FOR REQUIRED HOLDOWNS (ALL SHEARWALLS REQUIRE SHEATHING ABOVE & BELOW OPENINGS WITH SAME NAIL PATTERN). E EDGE NAIL SHEATHING AT ALL HOLDOWN POST/STUDS. EDGE NAILING IS REQUIRED TO EACH STUD USED IN A BUILT-UP HOLDOWN POST (MULTIPLE 2X STUDS). SEE TYPICAL DETAILS FOR FURTHER INFORMATION. F INTERMEDIATE STUDS SHALL BE 2X_ MINIMUM AND NAILED WITH 0.131"0 X 2Y2" FIELD NAILING AT 12" O.C. (WHERE STUD SPACING EXCEEDS 16" O.C. PROVIDE FIELD NAILING @ 6" O.C.) G. USE 0.131"Ox2Y2" NAILS TYPICALLY FOR LTP CLIPS WHEN INSTALLING OVER SHEATHING. IF LTP CLIPS ARE INSTALLED DIRECTLY TO FRAMING, 0.131"OX1Y2" NAILS MAY BE USED. LTP CLIPS MUST BE INSTALLED WITH LONG DIMENSION HORIZONTALLY. A35 OR RBC CLIPS MAY BE USED WHEN ATTACHING ROOF BLOCKING TO TOP PLATE. H. LTP4'S NOT REQ'D WHERE RIM SHEATHING OVERLAPS THE SECOND FLOOR BOTTOM PLATE. I' SHEATHING SHALL BE CONTINUOUS OVER BOTTOM PLATE AND RIM OR SILL PLATE PER TYPICAL DETAILING WITH EDGE NAILING AT EACH. WHEN TWO ROWS OF NAILING ARE REQ'D AT DOUBLE SIDED SHEARWALLS SEE TYPICAL DETAILING FOR FASTENERS AND BLKG. J. ALL ANCHOR BOLTS SHALL HAVE STEEL PLATE WASHERS 0.229"x3"X3". ANCHOR BOLTS W/ STANDARD 90' BEND SHALL BE EMBEDDED 7" INTO CONCRETE. PLATE WASHERS SHALL EXTEND TO WITHIN Y2" OF SHEATHING EDGE. K. PROVIDE "HOT -DIPPED" GALVANIZED NAILS/BOLTS AND METAL CONNECTORS WHEN ATTACHING TO PRESSURE TREATED MATERIALS. L WHERE 3x STUDS ARE REQ'D AT ADJOINING PANEL EDGES (2) 2x STUDS MAY BE NAILED TOGETHER IN PLACE OF USING A SINGLE 3x. FACE NAIL STUDS TOGETHER W/ 16d AT SAME SPACING SHOWN IN 2X BOTTOM PLATE ATTACHMENT COLUMN. PANEL EDGE NAILING IS REQUIRED TO EACH OF THE DOUBLE STUDS AND SHALL BE STAGGERED M. POST INSTALLED ANCHORS MAY NOT BE A VIABLE ALTERNATIVE. CONTACT PHILLIPS STRUCTURAL ENGINEERING FOR CONSULTATION. N. APA RATED PLYWOOD MAY BE USED IN PLACE OF OSB 0. ALL NAILING SHALL BE PER IBC TABLE 2304.10.1 U.N.O. HOLDOWN AND STRAP TABLE Holdown Label (G) Simpson Strong -Tie Product Label (SKU) (A) (B) (C) (F) G H Strap/Holdown Attachment and Required Fasteners Anchorage to Required NAILING and Required SCREWS Foundation Boundary Studs and Boundary Studs ( D) [1] STHD14/STHD14RJ (2) 2X STUDS W/ (30) 0.148"Ox3Y4" NAILS N/A EMBEDDED STRAP [1]Alt HDU5-SDS2.5 N/A (2) 2X STUDS W/ (14) Y4%2Y2" SDS SCREWS SIMPSON SB%x24 [2] HDQ8-SDS3 N/A (3) 2X STUDS W/ (20) V'0" SDS SCREWS SIMPSON SB7i8X24 (SEE NOTE E) 0 MANDATORY NOTES A. INSTALLATION OF ALL HOLDOWN ANCHORS AND STRAPS SHALL BE PER THE MANUFACTURE'S RECOMMENDATIONS B ALL METAL CONNECTORS IN CONTACT WITH PRESSURE TREATED (P.T.) MATERIAL SHALL BE COATED WITH SIMPSON "Z -MAX" (G-185) GALVANIZATION, TRIPLE ZINC COATED FOR CORROSION PROTECTION. ® SUPPLEMENTAL NOTES C. ALTERNATE HOLDOWN TYPES MAY BE ACCEPTABLE WITH WRITTEN APPROVAL OF PHILLIPS STRUCTURAL ENGINEERING. D. ALTERNATE ADHESIVE ANCHORS MAY BE AVAILABLE, CONTACT PHILLIPS STRUCTURAL ENGINEERING E. IF 6" STEMWALLS ARE USED, THREADED ROD WITH DOUBLE NUT AND PLATE EXTENDED INTO THE FOOTING IS REQ'D. SEE ALTERNATE DETAILING. SB%"X24 & SB1X30 MAY ONLY BE USED IN 8" STEMWALLS. F. STHD14RJ HOLDOWNS ARE TYPICALLY TO BE INSTALLED WHERE A RIM JOIST OCCURS. G. SIMPSON HDU5-SDS2.5 MAY BE USED AS AN ALTERNATE TO STHD14(RJ). H.1 STRAPS MAY BE INSTALLED OVER SHEATHING PANEL EDGE NAILING Z 0 PANEL EDGE BOUNDARY (STAGGER NAILING 0 PANEL EDGES) NAILING (6" O.C. MAX. SPACING) TRUSS/RAFTER PER PLAN TYPICALLY - FACE NAIL DOUBLE TOP PLATES W/ 0.131"0 X 3" ®12" O.C. STAGGERED BEAM PER SIMPSON ST6236 W/ (40) RIM JOIST/BLOCKING • PLAN 0.1620 x 2Y2" NAILS (CENTER ON SPLICE) 4'-0" MIN Z •I I•I I -I II II I•I I`I LI LI I. 1-1/2" 1-1/2" MIN MIN(12) DOUBLE 2X TOP PLATE II II II 0.131"0 x 3" LONG P -NAIL 0 EACH. . o INTERMEDIATE FRAMING II II SPLICE U.N.O. (FIELD) MEMBER NAILING°I I"I II II I'I I'I I°I (12" O.C. MAX. SPACING) I I,I II II II II LI (2) ROWS OF (4) 16d NAILS II SPLICE SPLICE NOTES: II II II II II II II CRIPPLE & 1.) PROVIDE APA APPROVED GLUE, I I I (2) 2X KINGM N NAIL ALL PLYWOOD TO JOISTS II I°I II II TYP. U) Z PER GENERAL NOTESII II I.I II I STUD ALI.I°I°I TYPICAL WALL FRAMING 2.) STAGGER PANELS TO OFFSET°I I. -Ile -Ile JOINTS AS SHOWN.II II II II STUD ® BOT SPLICE NOTE: LOCATION (TYP) w 7/16" SHEATHING AT ROOF (APA RATED) WHERE PLATE DISCONTINUITIES ARE CREATED BY BEAMS & PIPES, ETC. STRAP W/ (1)-SIMPSON ST6224 UNLESS w NOTED OTHERWISE. STRAP MAY BE PLACED ON TOP OR SIDE OF PLATES @ CONTRACTOR'S OPTION. TYPICAL HORIZONTAL PLYWOOD DIAPHRAGM LAYOUT 2 TYPICAL TOP CHORD SPLICE 3 BEAM FLUSH TO DBL TOP PLATE P10��Op� ���� S���Q� ����0�����0VIG IMPORTANT FRAMING NOTE: GENERAL CONTRACTOR/FRAMER SHALL VERIFY ALL CONCENTRATED LOADS FROM ABOVE TO HAVE SOLID BEARING CONTINUOUS TO THE FOUNDATION (INCLUDING SQUASH BLOCKING IN CRAWLSPACE/FLOOR FRAMING). ANY CHANGES TO FOUNDATION AND STRUCTURE FROM ARCHITECTURAL PLANS SHALL BE NOTED AND ALL AFFECTED PARTIES SHALL BE NOTIFIED. TYPICAL FRAMING NOTES: 1. Roof diaphragm nailing per Wood Sheathing Notes. 2. Solid blocking shall be provided between the bearings of every rafter or truss. Attach every rafter & truss to framing with Simpson H2.5T or clip indicated in typical detailing. 3. Provide solid built-up studs or posts under all girder trusses, roof beams and floor beams. Solid blocking (squash blocking) is required in all floor cavities under built-up studs/posts. Built -ups or posts shall run continuous to the foundation. 4. Exterior walls shall be nailed & detailed per SW6 U.N.O. All panel edges shall be blocked per shearwall table. 5. Where (2) shearwalls meet at a corner/intersection, the sheathing of each wall shall be edge nailed to the studs/post which the holdown is attached to. 6. Provide a solid rim joist where floor joist bear on exterior walls per typical details. 7. Roof joists/trusses are shown schematically on the plan and are not intended to show every location of every joist/truss. 8. Top plates are assumed to be continuous and may be spliced per typical detailing on this sheet. 9. All columns not specified or shown on the plans are to be a minimum of (2) 2x studs spike laminated together with 16d nails @ 6" o.c. (stagger). 10. All post -beam intersections shall contain positive connections to resist against uplift and/or lateral displacement. 11. Anchorage of walls to the foundation shall be provided in accordance with the shearwall schedule. 12. Typical Walls shall be framed with Doug -Fir U.N.O. 13. Walls shall be anchored to the foundation per the minimum requirements of SW6 (%"0 A.B. @ 48" o.c. embedded 7" and no more than 12" from ends of each sill and 2 bolts minimum) with 3"x3"x%4" square washers firmly attached between plate and nut. 14. All walls over 10' tall shall have bracing/blocking at 48" o.c. (flat or on edge). t T 1 Z 0 a U U w 0 U) Z z O LD cn w w U-1 Q 0 Lu 0 Lu PHILLIPS STRUCTURAL ENGINEERING PO Box 108, Milton, WA 98354 Phone: (253) 344-1666 www.PhillipsSE.com i ASNr i G' � P k 11:65� w 3 394 Lw S O LyCs 10/23/2023 ALL VARIATIONS FROM DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWINGS SHALL BE REPORTED TO THE DESIGNER FOR RESOLUTION WITH THE ENGINEER PRIOR TO PROCEEDING WITH WORK; FAILURE TO COMPLY BY THE CONTRACTOR SHALL BE THEIR SOLE RESPONSIBILITY FOR ANY COSTS NECESSARY FOR REMEDIAL WORK. REUSE OF DOCUMENTS UNAUTHORIZED ALTERATION OF ANY OF THE INFORMATION ON THIS DOCUMENT WILL INVALIDATE THE DOCUMENT, ENGINEER'S SEAL AND SIGNATURE. THE DESIGNS AND IDEAS INCORPORATED HEREIN, AS A TOOL OF PROFESSIONAL SERVICE, IS THE PROPERTY OF PHILLIPS STRUCTURAL ENGINEERING, PLLC AND IS NOT TO BE USED IN PART OR IN WHOLE BY ANY PARTY FOR ANY OTHER PROJECT WITHOUT WRITTEN AUTHORIZATION FROM PHILLIPS STRUCTURAL ENGINEERING, PLLC. Q W Z 0 C) > W J J< Q a � O� 2 W p (D < Z Q L0 J a') O WIND SPEED: 110 MPH WIND EXPOSURE: B ROOF SNOW LOAD: 25 PSF GENERAL NOTES DRAWN BY: AMS ORIGINAL DRAWING DATE: OCT. 23, 2023 SCALE: N.T.S. (U. N. 0.) PSE NUMBER: PSE 23.074 DESIGNER: KEIMIG SHEET NO: S-0 t T 1 AMSOCT. 23, 2023PSE 23.0749955 TAHOMA BLVD SE YELM, WAPSF25WIND SPEED:WIND EXPOSURE:ROOF SNOW LOAD:DRAWN BY:ALL VARIATIONS FROM DIMENSIONSAND CONDITIONS SHOWN ON THEDRAWINGS SHALL BE REPORTED TOTHE DESIGNER FOR RESOLUTIONWITH THE ENGINEER PRIOR TOPROCEEDING WITH WORK; FAILURETO COMPLY BY THE CONTRACTORSHALL BE THEIR SOLERESPONSIBILITY FOR ANY COSTSNECESSARY FOR REMEDIAL WORK.REUSE OF DOCUMENTSUNAUTHORIZED ALTERATION OF ANYOF THE INFORMATION ON THISDOCUMENT WILL INVALIDATE THEDOCUMENT, ENGINEER'S SEAL ANDSIGNATURE. THE DESIGNS AND IDEASINCORPORATED HEREIN, AS A TOOLOF PROFESSIONAL SERVICE, IS THEPROPERTY OF PHILLIPS STRUCTURALENGINEERING, PLLC AND IS NOT TOBE USED IN PART OR IN WHOLE BYANY PARTY FOR ANY OTHERPROJECT WITHOUT WRITTENAUTHORIZATION FROM PHILLIPSSTRUCTURAL ENGINEERING, PLLC.SHEET NO:ORIGINALDRAWING DATE:PSE NUMBER:SCALE:REVISIONS PO Box 108, Milton, WA 98354Phone: (253) 344-1666www.PhillipsSE.comPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGDESIGNER:2018 IBC / ASCE 7-16B110 MPHN.T.S. (U.N.O.)REV. DELTA DATE REVISION DESCRIPTION KEIMIG10/23/2023FOUNDATION PLAN "BUILDING A"SCALE : 14" = 1'-0"FOUNDATION PLAN1SD-11SD-110SD-12SD-12SD-11SD-17SD-1FOOTING SCHEDULE1SD-11SD-1 MAIN FLOOR SHEAR WALLS, HOLDOWNS,AND STRUCTURE "BUILDING A"SCALE : 14" = 1'-0"AMSOCT. 23, 2023PSE 23.0749955 TAHOMA BLVD SE YELM, WAPS F25WIND SPEED:WIND EXPOSURE:ROOF SNOW LOAD:DRAWN BY:ALL VARIATIONS FROM DIMENSIONSAND CONDITIONS SHOWN ON THEDRAWINGS SHALL BE REPORTED TOTHE DESIGNER FOR RESOLUTIONWITH THE ENGINEER PRIOR TOPROCEEDING WITH WORK; FAILURETO COMPLY BY THE CONTRACTORSHALL BE THEIR SOLERESPONSIBILITY FOR ANY COSTSNECESSARY FOR REMEDIAL WORK.REUSE OF DOCUMENTSUNAUTHORIZED ALTERATION OF ANYOF THE INFORMATION ON THISDOCUMENT WILL INVALIDATE THEDOCUMENT, ENGINEER'S SEAL ANDSIGNATURE. THE DESIGNS AND IDEASINCORPORATED HEREIN, AS A TOOLOF PROFESSIONAL SERVICE, IS THEPROPERTY OF PHILLIPS STRUCTURALENGINEERING, PLLC AND IS NOT TOBE USED IN PART OR IN WHOLE BYANY PARTY FOR ANY OTHERPROJECT WITHOUT WRITTENAUTHORIZATION FROM PHILLIPSSTRUCTURAL ENGINEERING, PLLC.SHEET NO:ORIGINALDRAWING DATE:PSE NUMBER:SCALE:REVISIONS PO Box 108, Milton, WA 98354Phone: (253) 344-1666www.PhillipsSE.comPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGDESIGNER:2018 IBC / ASCE 7-16B110 MPHN.T.S. (U.N.O.)REV. DELTA DATE REVISION DESCRIPTION KEIMIG10/23/2023MAIN FLOOR SHEARWALLS, HOLDOWNS,AND STRUCTURE ROOF TRUSSES BY OTHERSROOF FRAMING "BUILDING A"SCALE : 14" = 1'-0"ROOF FRAMINGAMSOCT. 23, 2023PSE 23.0749955 TAHOMA BLVD SE YELM, WAPS F25WIND SPEED:WIND EXPOSURE:ROOF SNOW LOAD:DRAWN BY:ALL VARIATIONS FROM DIMENSIONSAND CONDITIONS SHOWN ON THEDRAWINGS SHALL BE REPORTED TOTHE DESIGNER FOR RESOLUTIONWITH THE ENGINEER PRIOR TOPROCEEDING WITH WORK; FAILURETO COMPLY BY THE CONTRACTORSHALL BE THEIR SOLERESPONSIBILITY FOR ANY COSTSNECESSARY FOR REMEDIAL WORK.REUSE OF DOCUMENTSUNAUTHORIZED ALTERATION OF ANYOF THE INFORMATION ON THISDOCUMENT WILL INVALIDATE THEDOCUMENT, ENGINEER'S SEAL ANDSIGNATURE. THE DESIGNS AND IDEASINCORPORATED HEREIN, AS A TOOLOF PROFESSIONAL SERVICE, IS THEPROPERTY OF PHILLIPS STRUCTURALENGINEERING, PLLC AND IS NOT TOBE USED IN PART OR IN WHOLE BYANY PARTY FOR ANY OTHERPROJECT WITHOUT WRITTENAUTHORIZATION FROM PHILLIPSSTRUCTURAL ENGINEERING, PLLC.SHEET NO:ORIGINALDRAWING DATE:PSE NUMBER:SCALE:REVISIONS PO Box 108, Milton, WA 98354Phone: (253) 344-1666www.PhillipsSE.comPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGDESIGNER:2018 IBC / ASCE 7-16B110 MPHN.T.S. (U.N.O.)REV. DELTA DATE REVISION DESCRIPTION KEIMIG10/23/202318SD-111SD-228SD-128SD-128SD-130SD-126SD-18SD-226SD-116SD-110SD-218SD-110SD-210SD-216SD-130SD-126SD-1 STRUCTURALDETAILSAMSOCT. 23, 2023PSE 23.0749955 TAHOMA BLVD SE YELM, WAPSF25WIND SPEED:WIND EXPOSURE:ROOF SNOW LOAD:DRAWN BY:ALL VARIATIONS FROM DIMENSIONSAND CONDITIONS SHOWN ON THEDRAWINGS SHALL BE REPORTED TOTHE DESIGNER FOR RESOLUTIONWITH THE ENGINEER PRIOR TOPROCEEDING WITH WORK; FAILURETO COMPLY BY THE CONTRACTORSHALL BE THEIR SOLERESPONSIBILITY FOR ANY COSTSNECESSARY FOR REMEDIAL WORK.REUSE OF DOCUMENTSUNAUTHORIZED ALTERATION OF ANYOF THE INFORMATION ON THISDOCUMENT WILL INVALIDATE THEDOCUMENT, ENGINEER'S SEAL ANDSIGNATURE. THE DESIGNS AND IDEASINCORPORATED HEREIN, AS A TOOLOF PROFESSIONAL SERVICE, IS THEPROPERTY OF PHILLIPS STRUCTURALENGINEERING, PLLC AND IS NOT TOBE USED IN PART OR IN WHOLE BYANY PARTY FOR ANY OTHERPROJECT WITHOUT WRITTENAUTHORIZATION FROM PHILLIPSSTRUCTURAL ENGINEERING, PLLC.SHEET NO:ORIGINALDRAWING DATE:PSE NUMBER:SCALE:REVISIONS PO Box 108, Milton, WA 98354Phone: (253) 344-1666www.PhillipsSE.comPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGDESIGNER:2018 IBC / ASCE 7-16B110 MPHN.T.S. (U.N.O.)REV. DELTA DATE REVISION DESCRIPTION KEIMIG10/23/2023NOT USEDNOT USED STRUCTURALDETAILSAMSOCT. 23, 2023PSE 23.0749955 TAHOMA BLVD SE YELM, WAPS F25WIND SPEED:WIND EXPOSURE:ROOF SNOW LOAD:DRAWN BY:ALL VARIATIONS FROM DIMENSIONSAND CONDITIONS SHOWN ON THEDRAWINGS SHALL BE REPORTED TOTHE DESIGNER FOR RESOLUTIONWITH THE ENGINEER PRIOR TOPROCEEDING WITH WORK; FAILURETO COMPLY BY THE CONTRACTORSHALL BE THEIR SOLERESPONSIBILITY FOR ANY COSTSNECESSARY FOR REMEDIAL WORK.REUSE OF DOCUMENTSUNAUTHORIZED ALTERATION OF ANYOF THE INFORMATION ON THISDOCUMENT WILL INVALIDATE THEDOCUMENT, ENGINEER'S SEAL ANDSIGNATURE. THE DESIGNS AND IDEASINCORPORATED HEREIN, AS A TOOLOF PROFESSIONAL SERVICE, IS THEPROPERTY OF PHILLIPS STRUCTURALENGINEERING, PLLC AND IS NOT TOBE USED IN PART OR IN WHOLE BYANY PARTY FOR ANY OTHERPROJECT WITHOUT WRITTENAUTHORIZATION FROM PHILLIPSSTRUCTURAL ENGINEERING, PLLC.SHEET NO:ORIGINALDRAWING DATE:PSE NUMBER:SCALE:REVISIONS PO Box 108, Milton, WA 98354Phone: (253) 344-1666www.PhillipsSE.comPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGPHILLIPS STRUCTURAL ENGINEERINGDESIGNER:2018 IBC / ASCE 7-16B110 MPHN.T.S. (U.N.O.)REV. DELTA DATE REVISION DESCRIPTION KEIMIG10/23/202316SD-218SD-2N O T U S E D