VS 28 ADU ENGINEERING CALCULATIONS1 of 42 TABLE OF CONTENTS Project and Site Information ........................................................................................................... -Engineering Methods Explanation (2018 IBC Lateral and Gravity Engineering Calculations Package For Plans Examiner) -Wind Speed Determination - Applied Technology Council -Seismic1 Spectral Response - Applied Technology Council -Satellite Image of Building Site and Surrounding Area -Snow Load Calculation (with Normalized Ground Snow Load Chart if Over 30 psf) Lateral Analysis ................................................................................................................................ -Project Lateral Information - Design Settings and Site Information -Woodworks® Shearwall Lateral Analysis - Layout and Uplift by Floor -Design Summary - Shear Wall Design and Hold Downs -Shear Results for Wind - Critical Response Summary -Shear Results for Seismic - Critical Response Summary -Simpson Strong Wall Design Criteria and Anchorage Calculations (if specified) -Plan Specific Lateral Items Gravity Load Analysis ..................................................................................................................... -Forte® Job Summary Report - List of Beams and Headers -Member Reports - Individual Beams and Headers -Post Capacities Tables -Plan Specific Gravity Items Foundation ........................................................................................................................................ -1500 PSF Reinforced Concrete Pad Calculations -Continuous Concrete Footing with Stem Point Load Engineering -Restrained Retaining Walls if Present -Unrestrained Retaining Walls if Present -Plan Specific Foundation Items 1 2018 International Building Code (IBC) 2 of 42 2018 IBC Lateral and Gravity Engineering Calculations Package For Plans Examiner This engineering calculations package contains the lateral and gravity load engineering as noted in the engineering scope. All engineered load bearing structural members are specified on the full size engineering sheets. The enclosed engineering calculations document the engineering analysis. The engineering calculations are not required to be referenced onsite for construction. These calculations are to demonstrate to the Plans Examiner that the engineering was completed following the 2018 IBC. The cover sheet of the engineering specifies the engineering scope as lateral and gravity load engineering. LATERAL ENGINEERING: Lateral engineering involves determining what the seismic and wind loads are according to ASCE 7-16. Applying these loads to the structure, and determining the design of the lateral structural elements to resist these loads. The structural elements are sheathing, nailing, holdowns, and the connections between loaded members and shear resisting elements. Lateral load modeling was completed with Wood Works Design Office 12 (www.woodworks- software.com 800-844-1275). Wood Works was developed in conjunction with the American Forest & Paper Association. The AF&PA is the same professional organization that produces the National Design Specification (NDS) for Wood Construction, the Allowable Stress Design (ASD) manual for engineered wood construction, Wood Frame Construction Manual (WFCM) for one-and two-family dwellings, and the Load and Resistance Factor Design (LFRD) manual for engineered wood construction. The AF&PA "wrote the manuals" all engineers use. Seismic: Seismic load engineering follows the ASCE 7-16 12.8 equivalent lateral force procedure. Per ASCE 7 the analysis consists of the application of equivalent static lateral forces to a linear mathematical model of the structure. The total forces applied in each direction are the total base shear. Refer to ASCE 7-16 12.8 for a detailed description of this procedure. The engineering calculations include a USGS determination of the seismic spectral response accelerations. These numbers, S1 and Ss, are used in the lateral model to determine seismic loading to the shearwalls. Woodworks Design Office was used to make the linear mathematical model specified by ASCE 7-16 section 12.8. Wind: Wind load engineering follows the ASCE 7-16 Directional method for all heights. The wind loading is determined from the wind exposure and wind speed. This loading is applied to surfaces of the structure as modeled. Total loadings for each shear line, wall line, and full height shearwall are determined. Required shear strengths for each shearwall are calculated then sheathing and nailing patterns are chosen to resist design loads. Holdowns are applied where the nailing of the OSB sheathing to the mudsill or lower floor is not adequate to resist shear panel overturning. GRAVITY LOAD ENGINEERING: Gravity loads from snow, structure, occupants, etc. meeting the requirements of the 2018 IBC have been traced through the structure. Refer to the legend on the engineering sheets showing how the point and line loads are depicted. All loads are supported and traced through the structure. Load supporting members have been numbered for reference back to the engineering calculations. Loads to the foundation or soil have reinforced footings specified where required. 3 of 42 ASCE 7 Hazards Report Address: No Address at This Location Standard:ASCE/SEI 7-16 Latitude:46.93562 Risk Category:II Longitude:-122.61306 Soil Class:D - Default (see Section 11.4.3) Elevation:351.31595764630976 ft (NAVD 88) Wind Results: Wind Speed 97 Vmph 10-year MRI 67 Vmph 25-year MRI 73 Vmph 50-year MRI 77 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2 Date Accessed: Mon Aug 21 2023 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2. Page 1 of 4https://asce7hazardtool.online/Mon Aug 21 20234 of 42 SS : 1.286 S1 : 0.466 F a : 1.2 F v : N/A SMS : 1.544 SM1 : N/A SDS : 1.029 SD1 : N/A T L : 16 PGA : 0.512 PGA M : 0.614 F PGA : 1.2 Ie : 1 C v : 1.357 Seismic Site Soil Class: Results: Data Accessed: Date Source: D - Default (see Section 11.4.3) USGS Seismic Design Maps Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Mon Aug 21 2023 Page 2 of 4https://asce7hazardtool.online/Mon Aug 21 20235 of 42 Flood Results: Data Source: Date Accessed: FIRM Panel: Insurance Study Note: Flood Zone Categorization: X (unshaded) Base Flood Elevation: FEMA National Flood Hazard Layer - Effective Flood Hazard Layer for US, where modernized (https://msc.fema.gov/portal/search) Mon Aug 21 2023 If available, download FIRM panel here Download FEMA Flood Insurance Study for this area here Page 3 of 4https://asce7hazardtool.online/Mon Aug 21 20236 of 42 The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE 7 Hazard Tool. Page 4 of 4https://asce7hazardtool.online/Mon Aug 21 20237 of 42 Hodge Engineering, Inc. John E. Hodge P. E. 3733 Rosedale St, Suite 200, Gig Harbor, WA 98335 (253) 857-7055 ASCE 7-16: Snow Loading Calculation Site: Lot 28 – 10408 Calder St SE, Yelm, WA 98597 Plan: Vista in Yelm - ADU Job: 230370 Three resources for determining snow load: 1. Snow Load Analysis for Washington; 2nd Edition by the Structural Engineers Association of Washington (SEAW). “This edition provides a large color map for each half of the state, with normalized ground snow load isolines and elevation contours to help readily determine the ground snow load anywhere in the state”. 2. WABO/SEAW White Paper #8 “Guidelines for Determining Snow Loads in Washington State” available on www.seaw.org/publications 3. ASCE 7-16 Chapter 7 Snow Loads Ground Snow Load pg: (ASCE 7-16 7.2 Extreme value statistical analysis using 2% annual probability of being exceeded) Normalized ground snow load (NGSL) = 0.050 Lot Elevation = 355 ft. from Google Earth 1. Ground snow load = NGSL x elevation = 0.050 * 355 = 18 psf = pg 2. SEAW Snow Load Analysis for Washington Appendix A = Yelm – 18 PSF (@340 FT) Roof Snow Load pf: ASCE 7-16 7.3 Flat roof snow load pf = 0.7CeCtIspg ASCE 7-16 7.3.1 Ce is the exposure factor = 1.0 for partially exposed structure (table 7.3-1) ASCE 7-16 7.3.2 Ct is the thermal factor = 1.1 for heated residences (table 7.3-2) ASCE 7-16 7.3.3 Is is the importance factor = 1.0 for residences (table 1.5-1) ASCE 7-16 7.4 Sloped roof snow loads - no roof slope reduction Cs taken unless noted otherwise ASCE 7-16 7.6 Trussed roof or slope exceeding 7:12 – no unbalanced snow loading pf = 0.7CeCtIpg = 0.7 * 1.0 * 1.1 * 1.0 * 18 pg = 14 psf Flat Roof Snow Load Minimum roof snow load 25 psf., U.N.O. “Snow load to be approved by the authority having jurisdiction…” ASCE 7-16 7.2 8 of 42 WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN WoodWorks® Shearwalls 2019 (Update 3) LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 Project Information DESIGN SETTINGS Design Code IBC 2018/AWC SDPWS 2015 Wind Standard ASCE 7-16 Directional (All heights) Seismic Standard ASCE 7-16 Load Combinations For Design (ASD) 0.70 Seismic 0.60 Wind For Deflection (Strength) 1.00 Seismic 1.00 Wind Building Code Capacity Modification Wind Seismic 1.00 1.00 Service Conditions and Load Duration Duration Factor 1.60 Temperature Range T<=100F Moisture Content Fabrication Service 19% (<=19%)10% (<=19%) Max Shearwall Offset [ft] Plan (within story) 4.00 Elevation (between stories) - Maximum Height-to-width Ratio Wood panels Wind Seismic Fiberboard Lumber Wind Seismic Gypsum Blocked Unblocked 3.5 3.5 - - - - - Ignore non-wood-panel shear resistance contribution... Wind Seismic when comb'd w/ wood panels Always Forces based on... Hold-downs Applied loads Drag struts Applied loads Shearwall relative rigidity: Wall capacity Perforated shearwall Co factor: SDPWS Equation 4.3-5 Non-identical materials and construction on the shearline: Not allowed Deflection Equation: 4-term from SDPWS C4.3.2-1 Drift limit for wind design: 1 / 500 story height Force-transfer strap: Continuous at top of highest opening and bottom of lowest SITE INFORMATION Risk Category Category II - All others Wind ASCE 7-16 Directional (All heights) Seismic ASCE 7-16 12.8 Equivalent Lateral Force Procedure Design Wind Speed 97 mph Exposure Exposure B Enclosure Enclosed Structure Type Regular Building System Bearing Wall Design Category D Site Class D Topographic Information [ft] Shape - Height - Length - Site Location: - Elev: 350ft Rigid building - Static analysis Spectral Response Acceleration S1: 0.466g Ss: 1.286g Fundamental Period E-W N-S T Used 0.128s 0.128s Approximate Ta 0.128s 0.128s Maximum T 0.180s 0.180s Response Factor R 6.50 6.50 Fa: 1.20 Fv: 1.83 Case 2 N-S loadsE-W loads Eccentricity (%)15 15 Loaded at 75% Min Wind Loads: Walls Roofs 16 psf 8 psf Serviceability Wind Speed 86 mph 1 9 of 42 WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN WoodWorks® Shearwalls 2019 (Update 3)LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 09:54:48 0'1.67'3.33'5'6.67'8.33'10'11.67'13.33'15'16.67'18.33'20'21.67'23.33'25'26.67'28.33'30'31.67'33.33'35'36.67'38.33'40'41.67' -5' -3.33' -1.67' 0' 1.67' 3.33' 5' 6.67' 8.33' 10' 11.67' 13.33' 15' 16.67' 18.33' 20' 21.67' 23.33' 25' 26.67' 28.33' 30' 31.67' 33.33' B-1 3-1A-21-1A-1 2-11404 140458985687458985687410581058266383390335266383390335161316136946941720 1720627627Loads: Directional Case 1 Wind (W); Forces: 0.6W + 0.6D; Flexible distribution Vertical element required C Compression force exists Factored holddown force (lbs) Factored shearline force (lbs) Applied point load or discontinuous shearline force (lbs) Unfactored uplift wind load (plf,lbs) Unfactored dead load (plf,lbs) Unfactored applied shear load (plf) Level 1 of 1 10 of 42 WoodWorks® Shearwalls SOFTWARE FOR WOOD DESIGN WoodWorks® Shearwalls 2019 (Update 3)LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 09:54:48 0'1.67'3.33'5'6.67'8.33'10'11.67'13.33'15'16.67'18.33'20'21.67'23.33'25'26.67'28.33'30'31.67'33.33'35'36.67'38.33'40'41.67' -5' -3.33' -1.67' 0' 1.67' 3.33' 5' 6.67' 8.33' 10' 11.67' 13.33' 15' 16.67' 18.33' 20' 21.67' 23.33' 25' 26.67' 28.33' 30' 31.67' 33.33' B-1 3-1A-21-1A-1 2-11837770111911437701119114316154075845955124075845955121636704704 1816662662Loads: Seismic (Qe); Forces: 0.7E + 0.6D; E = pQe + 0.2 Sds D; p(NS) = 1.0; p(EW) = 1.0; Sds = 1.0; Flexible distribution Vertical element required C Compression force exists Factored holddown force (lbs) Factored shearline force (lbs) Applied point load or discontinuous shearline force (lbs) Unfactored dead load (plf,lbs) Unfactored applied shear load (plf) Level 1 of 1 11 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 Structural Data STORY INFORMATION Hold-down Story Floor/Ceiling Wall Length subject to Bolt Elev [ft]Depth [in]Height [ft]shrinkage [in]length [in] Ceiling 12.00 0.0 Level 1 3.00 12.0 9.00 15.7 16.5 Foundation 2.00 BLOCK and ROOF INFORMATION Block Roof Panels Dimensions [ft]Face Type Slope Overhang [ft] Block 1 1 Story E-W Ridge Location X,Y =0.00 4.00 North Side 22.6 2.00 Extent X,Y =40.00 28.00 South Side 22.6 2.00 Ridge Y Location, Offset 18.00 0.00 East Gable 90.0 2.00 Ridge Elevation, Height 17.83 5.83 West Gable 90.0 2.00 Block 2 1 Story N-S Ridge Location X,Y =22.50 0.00 North Joined 157.4 2.00 Extent X,Y =17.50 4.00 South Gable 90.0 2.00 Ridge X Location, Offset 31.25 0.00 East Side 26.6 2.00 Ridge Elevation, Height 16.37 4.37 West Side 26.6 2.00 Block 3 1 Story N-S Ridge Location X,Y =22.50 -1.50 North Joined 90.0 2.00 Extent X,Y =5.00 1.50 South Gable 90.0 2.00 Ridge X Location, Offset 25.00 0.00 East Side 26.6 2.00 Ridge Elevation, Height 13.25 1.25 West Side 26.6 2.00 2 12 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 SHEATHING MATERIALS by WALL GROUP Sheathing Fasteners Apply Grp Surf Material Ratng Thick GU Ply Or Gvtv Size Type Df Eg Fd Bk Notes in in lbs/in in in 1 Ext Struct I OSB 24/16 7/16 --Vert 83500 8d Nail N 6 12 Y 1,3 Legend: Grp – Wall Design Group number, used to reference wall in other tables (created by program) Surf – Exterior or interior surface when applied to exterior wall Ratng – Span rating, see SDPWS Table C4.2.2.2C Thick – Nominal panel thickness GU - Gypsum underlay thickness Ply – Number of plies (or layers) in construction of plywood sheets Or – Orientation of longer dimension of sheathing panels Gvtv – Shear stiffness in lb/in. of depth from SDPWS Tables C4.2.2A-B Type – Fastener type from SDPWS Tables 4.3A-D: Nail – common wire nail for structural panels and lumber, cooler or gypsum wallboard nail for GWB, plasterboard nail for gypsum lath, galvanised nail for gypsum sheathing; Box - box nail; Casing – casing nail; Roof – roofing nail; Screw – drywall screw Size - Common, box, and casing nails: refer to SDPWS Table A1 (casing sizes = box sizes). Gauges: 11 ga = 0.120” x 1-3/4” (gypsum sheathing, 25/32” fiberboard ), 1-1/2” (lath & plaster, 1/2” fiberboard); 13 ga plasterboard = 0.92” x 1- 1/8”. Cooler or gypsum wallboard nail: 5d = .086” x 1-5/8”; 6d = .092” x 1-7/8”; 8d = .113” x 2-3/8”; 6/8d = 6d base ply, 8d face ply for 2-ply GWB. Drywall screws: No. 6, 1-1/4” long. 5/8” gypsum sheathing can also use 6d cooler or GWB nail Df – Deformed nails ( threaded or spiral), with increased withdrawal capacity Eg – Panel edge fastener spacing Fd – Field spacing interior to panels Bk – Sheathing is nailed to blocking at all panel edges; Y(es) or N(o) Apply Notes – Notes below table legend which apply to sheathing side Notes: 1.Capacity has been reduced for framing specific gravity according to SDPWS T4.3A Note 3. 3. Shear capacity for current design has been increased to the value for 15/32" sheathing with same nailing because stud spacing is 16" max. or panel orientation is horizontal. See SDPWS T4.3A Note 2. FRAMING MATERIALS and STANDARD WALL by WALL GROUP Wall Species Grade b d Spcg SG E Standard Wall Grp in in in psi^6 1 Hem-Fir Stud 1.50 5.50 16 0.43 1.20 Legend: Wall Grp – Wall Design Group b – Stud breadth (thickness) d – Stud depth (width) Spcg – Maximum on-centre spacing of studs for design, actual spacing may be less. SG – Specific gravity E – Modulus of elasticity Standard Wall - Standard wall designed as group. Notes: Check manufacture requirements for stud size, grade and specific gravity (G) for all shearwall hold-downs. 3 13 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 SHEARLINE, WALL and OPENING DIMENSIONS North-south Type Wall Location Extent [ft]Length FHS Aspect Height Shearlines Group X [ft]Start End [ft] [ft] Ratio [ft] Line 1 Level 1 Line 1 Seg 1 0.00 4.00 32.00 28.00 28.00 - 9.00 Wall 1-1 Seg 1 0.00 4.00 32.00 28.00 28.00 0.32 - Line 2 Level 1 Line 2 NSW 27.58 0.00 4.00 4.00 0.00 - 9.00 Wall 2-1 NSW 27.58 0.00 4.00 4.00 0.00 1.00 - Line 3 Level 1 Line 3 Seg 1 40.00 0.00 32.00 32.00 32.00 - 9.00 Wall 3-1 Seg 1 40.00 0.00 32.00 32.00 32.00 0.28 - East-west Type Wall Location Extent [ft]Length FHS Aspect Height Shearlines Group Y [ft]Start End [ft] [ft] Ratio [ft] Line A Level 1 Line A 1 2.76 0.00 40.00 40.00 16.25 - 9.00 Wall A-1 Seg 1 4.00 0.00 27.58 27.58 16.25 - - Segment 1 -- 0.00 2.92 2.92 - 3.09 - Opening 1 -- 2.92 7.92 5.00 - - 3.00 Segment 2 -- 7.92 16.25 8.33 - 1.08 - Opening 2 -- 16.25 18.75 2.50 - - 3.00 Segment 3 -- 18.75 23.75 5.00 - 1.80 - Opening 3 -- 23.75 26.75 3.00 - - 3.00 Segment 4 -- 26.75 27.58 0.83 - 10.80 - Wall A-2 Seg 1 0.00 27.58 40.00 12.42 0.00 - - Segment 1 -- 27.58 29.75 2.17 - 4.15 - Opening 1 -- 29.75 37.75 8.00 - - 3.00 Segment 2 -- 37.75 40.00 2.25 - 4.00 - Line B Level 1 Line B 1 32.00 0.00 40.00 40.00 27.00 - 9.00 Wall B-1 Seg 1 32.00 0.00 40.00 40.00 27.00 - - Segment 1 -- 0.00 2.92 2.92 - 3.09 - Opening 1 -- 2.92 7.92 5.00 - - 3.00 Segment 2 -- 7.92 21.50 13.58 - 0.66 - Opening 2 -- 21.50 27.50 6.00 - - 3.00 Segment 3 -- 27.50 34.25 6.75 - 1.33 - Opening 3 -- 34.25 36.25 2.00 - - 3.00 Segment 4 -- 36.25 40.00 3.75 - 2.40 - Legend: Type - Seg = segmented, Prf = perforated, FT = force-transfer, NSW = non-shearwall Location - Dimension perpendicular to wall FHS - Length of full-height sheathing used to resist shear force. For perforated walls, it is based on the factored segments Li defined in SDPWS 4.3.4.3 Aspect Ratio – Ratio of wall height to segment length (h/bs), for force-transfer walls, the aspect ratio of the central pier Wall Group - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall If two wall group numbers listed, they are for rigid diaphragm and flexible diaphragm design. 4 14 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 Design Summary SHEARWALL DESIGN Wind Shear Loads, Flexible Diaphragm All shearwalls have sufficient design capacity. Components and Cladding Wind Loads, Out-of-plane Sheathing All shearwalls have sufficient design capacity. Components and Cladding Wind Loads, Nail Withdrawal All shearwalls have sufficient design capacity. Seismic Loads, Flexible Diaphragm All shearwalls have sufficient design capacity. HOLDDOWN DESIGN Wind Loads, Flexible Diaphragm All hold-downs have sufficient design capacity. Seismic Loads, Flexible Diaphragm All hold-downs have sufficient design capacity. Refer to the Deflection table for possible issues regarding fastener slippage (SDPWS Table C4.2.2D) for walls that otherwise pass. 5 15 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 Flexible Diaphragm Wind Design ASCE 7 Directional (All Heights) Loads SHEAR RESULTS N-S W For ASD Shear Force [plf]Asp-Cub Allowable Shear [plf]Resp. Shearlines Gp Dir v vmax/vft V [lbs]Int Ext Int Ext Co C Cmb V [lbs]Ratio Line 1 Level 1 Ln1, Lev1 1 Both 57.6 - 1613 - 1.0 - 365 - 365 10208 0.16 Line 3 Ln3, Lev1 1 Both 53.8 - 1720 - 1.0 - 365 - 365 11666 0.15 E-W W For ASD Shear Force [plf]Asp-Cub Allowable Shear [plf]Resp. Shearlines Gp Dir v vmax/vft V [lbs]Int Ext Int Ext Co C Cmb V [lbs]Ratio Line A Level 1 LnA, Lev1 - Both - - 1404 - - - 365 - - 5550 - Wall A-1 1 Both - - 1404 - 1.0 - 365 - - 5550 - Seg. 1 - Both 59.8 0.0 174 - .65 - 236 - 236 689 0.25 Seg. 2 - Both 92.3 0.0 769 - 1.0 - 365 - 365 3038 0.25 Seg. 3 - Both 92.3 0.0 461 - 1.0 - 365 - 365 1823 0.25 Seg. 4 - Both 0.0 0.0 0 - 1.0 - 365 - 365 - - Wall A-2 1 Both 0.0 - 0 - 1.0 - 365 - - - - Line B LnB, Lev1 - Both - - 1058 - - - 365 - - 9241 - Wall B-1 1 Both - - 1058 - 1.0 - 365 - - 9241 - Seg. 1 - Both 27.1 0.0 79 - .65 - 236 - 236 689 0.11 Seg. 2 - Both 41.8 0.0 567 - 1.0 - 365 - 365 4952 0.11 Seg. 3 - Both 41.8 0.0 282 - 1.0 - 365 - 365 2461 0.11 Seg. 4 - Both 34.8 0.0 130 - .83 - 304 - 304 1139 0.11 Legend: W Gp - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall. "^" means that this wall is critical for all walls in the Standard Wall group. For Dir - Direction of wind force along shearline. v - Design shear force on segment = ASD-factored shear force per unit length of full-height sheathing (FHS) vmax/vft - Perforated walls: Collector and in-plane anchorage force as per SDPWS eqn. 4.3-9 = V/FHS/Co. FHS is factored for narrow segments as per 4.3.4.3 Force-transfer walls: Shear force in piers above and below either openings or piers beside opening(s). Aspect ratio factor does not apply to these piers. V - ASD factored shear force. For shearline: total shearline force. For wall: total of all segments on wall. For segment: force on segment Asp/Cub – For wall: Unblocked structural wood panel factor Cub from SDPWS 4.3.3.2. For segment or force-transfer pier: Aspect ratio adjustment from SDPWS 4.3.3.4.1 Int - Unit shear capacity of interior sheathing; Ext - Unit shear capacity of exterior sheathing. For wall: Unfactored. For segment: Include Cub factor and aspect ratio adjustments. Co - Adjustment factor for perforated walls from SDPWS Equation 4.3-5. C - Sheathing combination rule, A = Add capacities, S = Strongest side or twice weakest, G = Stiffness-based using SDPWS 4.3-3. Cmb - Combined interior and exterior unit shear capacity including perforated wall factor Co. V – Total factored shear capacity of shearline, wall or segment. Crit Resp – Response ratio = v/Cmb = design shear force/unit shear capacity. "S" indicates that the wind design criterion was critical in selecting wall. Notes: Refer to Elevation View diagrams for individual level for uplift anchorage force t for perforated walls given by SDPWS 4.3.6.4.2,4. 6 16 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 Flexible Diaphragm Seismic Design SEISMIC INFORMATION Level Mass Area Story Shear [lbs]Diaphragm Force [lbs] [lbs][sq.ft]E-W N-S E-W:Fpx Design N-S:Fpx Design 1 32053 1169.7 4931 4931 4617 4617 4617 4617 All 32053 - 4931 4931 - - - - Legend: Mass – Sum of all generated and input building masses on level = wx in ASCE 7 equation 12.8-12. Story Shear – Total unfactored (strength-level) shear force induced at level x, = Fx in ASCE 7 equation 12.8-11. Diaphragm Force – Minimum ASD-factored force for diaphragm design, used by Shearwalls only for drag strut forces, as per Exception to 12.10.2.1. Fpx is from Eqns. 12.10-1, -2, and -3. Design = The greater of the story shear and Fpx + transfer forces from discontinuous shearlines, factored by overstrength (omega) as per 12.10.1.1. Omega = 2.5 as per 12.2-1. Redundancy Factor p (rho): E-W 1.00, N-S 1.00 Automatically calculated according to ASCE 7 12.3.4.2. Vertical Earthquake Load Ev Ev = 0.2 Sds D; Sds = 1.00; Ev = 0.200 D unfactored; 0.140 D factored; total dead load factor: 0.6 - 0.140 = 0.460 tension, 1.0 + 0.140 = 1.140 compression. 7 17 of 42 WoodWorks® Shearwalls LATERAL ANALYSIS - 230370.wsw Aug. 22, 2023 14:18:55 SHEAR RESULTS (flexible seismic design) N-S W For ASD Shear Force [plf]Asp-Cub Allowable Shear [plf]Resp. Shearlines Gp Dir v vmax/vft V [lbs]Int Ext Int Ext Co C Cmb V [lbs]Ratio Line 1 Level 1 Ln1, Lev1 1 Both 58.4 - 1636 - 1.0 - 260 - 260 7291 0.22 Line 3 Ln3, Lev1 1 Both 56.7 - 1816 - 1.0 - 260 - 260 8333 0.22 E-W W For ASD Shear Force [plf]Asp-Cub Allowable Shear [plf]Resp. Shearlines Gp Dir v vmax/vft V [lbs]Int Ext Int Ext Co C Cmb V [lbs]Ratio Line A Level 1 LnA, Lev1 - Both - - 1837 - - - 260 - - 3964 - Wall A-1 1^Both - - 1837 - 1.0 - 260 - - 3964 - Seg. 1 - Both 78.2 0.0 228 - .65 - 169 - 169 492 0.46 Seg. 2 - Both 120.7 0.0 1005 - 1.0 - 260 - 260 2170 0.46 Seg. 3 - Both 120.7 0.0 603 - 1.0 - 260 - 260 1302 0.46 Seg. 4 - Both 0.0 0.0 0 - 1.0 - 260 - 260 - - Wall A-2 1 Both 0.0 - 0 - 1.0 - 260 - - - - Line B LnB, Lev1 - Both - - 1615 - - - 260 - - 6601 - Wall B-1 1 Both - - 1615 - 1.0 - 260 - - 6601 - Seg. 1 - Both 41.3 0.0 120 - .65 - 169 - 169 492 0.24 Seg. 2 - Both 63.7 0.0 865 - 1.0 - 260 - 260 3537 0.24 Seg. 3 - Both 63.7 0.0 430 - 1.0 - 260 - 260 1758 0.24 Seg. 4 - Both 53.1 0.0 199 - .83 - 217 - 217 814 0.24 Legend: W Gp - Wall design group defined in Sheathing and Framing Materials tables, where it shows associated Standard Wall. "^" means that this wall is critical for all walls in the Standard Wall group. For Dir – Direction of seismic force along shearline. v - Design shear force on segment = ASD-factored shear force per unit length of full-height sheathing (FHS) vmax/vft - Perforated walls: Collector and in-plane anchorage force as per SDPWS eqn. 4.3-9 = V/FHS/Co. FHS is factored for narrow segments as per 4.3.4.3 Force-transfer walls: Shear force in piers above and below either openings or piers beside opening(s). Aspect ratio factor does not apply to these piers. V - ASD factored shear force. For shearline: total shearline force. For wall: total of all segments on wall. For segment: force on segment Asp/Cub – For wall: Unblocked structural wood panel factor Cub from SDPWS 4.3.3.2. For segment or force-transfer pier: Aspect ratio adjustment from SDPWS 4.3.3.4.1 Int - Unit shear capacity of interior sheathing; Ext - Unit shear capacity of exterior sheathing. For wall: Unfactored. For segment: Include Cub factor and aspect ratio adjustments. Co - Adjustment factor for perforated walls from SDPWS Equation 4.3-5. C - Sheathing combination rule, A = Add capacities, S = Strongest side or twice weakest, G = Stiffness-based using SDPWS 4.3-3. Cmb - Combined interior and exterior unit shear capacity including perforated wall factor Co. V – Total factored shear capacity of shearline, wall or segment. Crit Resp – Response ratio = v/Cmb = design shear force/unit shear capacity. "W" indicates that the wind design criterion was critical in selecting wall. Notes: Refer to Elevation View diagrams for individual level for uplift anchorage force t for perforated walls given by SDPWS 4.3.6.4.2,4. 8 18 of 42 ROOF FRAMING Member Name Results Current Solution Comments R1 Passed 1 piece(s) 4 x 6 DF No.2 R2 Passed 1 piece(s) 4 x 8 DF No.2 R3 Passed 1 piece(s) 4 x 8 DF No.2 R4 Passed 1 piece(s) 4 x 6 DF No.2 R5 Passed 1 piece(s) 4 x 6 DF No.2 R6 Passed 1 piece(s) 4 x 12 DF No.2 R7 Passed 1 piece(s) 6 x 8 DF No.2 FLOOR FRAMING Member Name Results Current Solution Comments M1 Passed 1 piece(s) 4 x 10 DF No.2 M2 Passed 1 piece(s) 4 x 10 DF No.2 M3 Passed 1 piece(s) 2 x 10 HF No.2 @ 16" OC 230370 - BEAM CALCULATIONS JOB SUMMARY REPORT ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6 File Name: 230370 - BEAM CALCULATIONS Page 1 / 1119 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)702 @ 0 3281 (1.50")Passed (21%)--1.0 D + 1.0 S (All Spans) Shear (lbs)338 @ 7"2657 Passed (13%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)395 @ 1' 1 1/2"1979 Passed (20%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.003 @ 1' 1 1/2"0.075 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.005 @ 1' 1 1/2"0.112 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"280 422 702 None 2 - Trimmer - HF 1.50"1.50"1.50"280 422 702 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)2' 3" o/c Bottom Edge (Lu)2' 3" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 2' 3"N/A 4.9 -- 1 - Uniform (PSF)0 to 2' 3"15'16.2 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R1 1 piece(s) 4 x 6 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 2 / 1120 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)1954 @ 0 3281 (1.50")Passed (60%)--1.0 D + 1.0 S (All Spans) Shear (lbs)1498 @ 8 3/4"3502 Passed (43%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)3053 @ 3' 1 1/2"3438 Passed (89%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.072 @ 3' 1 1/2"0.208 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.121 @ 3' 1 1/2"0.313 Passed (L/621)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"782 1172 1954 None 2 - Trimmer - HF 1.50"1.50"1.50"782 1172 1954 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)6' 3" o/c Bottom Edge (Lu)6' 3" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 6' 3"N/A 6.4 -- 1 - Uniform (PSF)0 to 6' 3"15'16.2 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R2 1 piece(s) 4 x 8 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 3 / 1121 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)1641 @ 0 3281 (1.50")Passed (50%)--1.0 D + 1.0 S (All Spans) Shear (lbs)1185 @ 8 3/4"3502 Passed (34%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)2154 @ 2' 7 1/2"3438 Passed (63%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.036 @ 2' 7 1/2"0.175 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.060 @ 2' 7 1/2"0.262 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"657 984 1641 None 2 - Trimmer - HF 1.50"1.50"1.50"657 984 1641 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)5' 3" o/c Bottom Edge (Lu)5' 3" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 5' 3"N/A 6.4 -- 1 - Uniform (PSF)0 to 5' 3"15'16.2 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R3 1 piece(s) 4 x 8 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 4 / 1122 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)857 @ 0 3281 (1.50")Passed (26%)--1.0 D + 1.0 S (All Spans) Shear (lbs)494 @ 7"2657 Passed (19%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)590 @ 1' 4 1/2"1979 Passed (30%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.006 @ 1' 4 1/2"0.092 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.010 @ 1' 4 1/2"0.138 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"342 516 857 None 2 - Trimmer - HF 1.50"1.50"1.50"342 516 857 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)2' 9" o/c Bottom Edge (Lu)2' 9" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 2' 9"N/A 4.9 -- 1 - Uniform (PSF)0 to 2' 9"15'16.2 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R4 1 piece(s) 4 x 6 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 5 / 1123 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)1013 @ 0 3281 (1.50")Passed (31%)--1.0 D + 1.0 S (All Spans) Shear (lbs)650 @ 7"2657 Passed (24%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)823 @ 1' 7 1/2"1979 Passed (42%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.012 @ 1' 7 1/2"0.108 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.020 @ 1' 7 1/2"0.162 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"404 609 1013 None 2 - Trimmer - HF 1.50"1.50"1.50"404 609 1013 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)3' 3" o/c Bottom Edge (Lu)3' 3" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 3' 3"N/A 4.9 -- 1 - Uniform (PSF)0 to 3' 3"15'16.2 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R5 1 piece(s) 4 x 6 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 6 / 1124 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)386 @ 0 3281 (1.50")Passed (12%)--1.0 D + 1.0 S (All Spans) Shear (lbs)286 @ 1' 3/4"5434 Passed (5%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)796 @ 4' 1 1/2"7004 Passed (11%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.008 @ 4' 1 1/2"0.275 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.015 @ 4' 1 1/2"0.412 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Wall Member Type : Header Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Trimmer - HF 1.50"1.50"1.50"180 206 386 None 2 - Trimmer - HF 1.50"1.50"1.50"180 206 386 None •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)8' 3" o/c Bottom Edge (Lu)8' 3" o/c Dead Snow Vertical Loads Location Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 8' 3"N/A 10.0 -- 1 - Uniform (PSF)0 to 8' 3"2'16.8 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R6 1 piece(s) 4 x 12 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 7 / 1125 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)463 @ 4"12251 (5.50")Passed (4%)--1.0 D + 1.0 S (All Spans) Shear (lbs)294 @ 1' 1"5376 Passed (5%)1.15 1.0 D + 1.0 S (All Spans) Moment (Ft-lbs)540 @ 2' 11 1/2"3706 Passed (15%)1.15 1.0 D + 1.0 S (All Spans) Live Load Defl. (in)0.006 @ 2' 11 1/2"0.262 Passed (L/999+)--1.0 D + 1.0 S (All Spans) Total Load Defl. (in)0.011 @ 2' 11 1/2"0.350 Passed (L/999+)--1.0 D + 1.0 S (All Spans) System : Roof Member Type : Drop Beam Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD Member Pitch : 0/12 •Deflection criteria: LL (L/240) and TL (L/180). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. • Blocking Panels are assumed to carry no loads applied directly above them and the full load is applied to the member being designed. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Snow Factored Accessories 1 - Stud wall - HF 5.50"5.50"1.50"205 259 463 Blocking 2 - Stud wall - HF 5.50"5.50"1.50"205 259 463 Blocking •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)5' 11" o/c Bottom Edge (Lu)5' 11" o/c Dead Snow Vertical Loads Location (Side)Tributary Width (0.90)(1.15)Comments 0 - Self Weight (PLF)0 to 5' 11"N/A 10.4 -- 1 - Uniform (PSF)0 to 5' 11" (Top)3' 6"16.8 25.0 ROOF Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED ROOF FRAMING, R7 1 piece(s) 6 x 8 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 8 / 1126 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)1550 @ 2"4961 (3.50")Passed (31%)--1.0 D + 1.0 L (All Spans) Shear (lbs)912 @ 1' 3/4"3885 Passed (23%)1.00 1.0 D + 1.0 L (All Spans) Moment (Ft-lbs)1752 @ 2' 7"4492 Passed (39%)1.00 1.0 D + 1.0 L (All Spans) Live Load Defl. (in)0.016 @ 2' 7"0.161 Passed (L/999+)--1.0 D + 1.0 L (All Spans) Total Load Defl. (in)0.020 @ 2' 7"0.242 Passed (L/999+)--1.0 D + 1.0 L (All Spans) System : Floor Member Type : Drop Beam Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. • Blocking Panels are assumed to carry no loads applied directly above them and the full load is applied to the member being designed. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Floor Live Factored Accessories 1 - Stud wall - HF 3.50"3.50"1.50"327 1223 1550 Blocking 2 - Stud wall - HF 3.50"3.50"1.50"327 1223 1550 Blocking •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)5' 2" o/c Bottom Edge (Lu)5' 2" o/c Dead Floor Live Vertical Loads Location (Side)Tributary Width (0.90)(1.00)Comments 0 - Self Weight (PLF)0 to 5' 2"N/A 8.2 -- 1 - Uniform (PSF)0 to 5' 2" (Front)11' 10"10.0 40.0 FLOOR Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED FLOOR FRAMING, M1 1 piece(s) 4 x 10 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 9 / 1127 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)2350 @ 1' 3 3/4"4961 (3.50")Passed (47%)--1.0 D + 1.0 L (All Spans) Shear (lbs)1012 @ 2' 2 3/4"3885 Passed (26%)1.00 1.0 D + 1.0 L (All Spans) Moment (Ft-lbs)1713 @ 3' 9 5/16"4492 Passed (38%)1.00 1.0 D + 1.0 L (Alt Spans) Live Load Defl. (in)0.016 @ 3' 8 7/8"0.162 Passed (L/999+)--1.0 D + 1.0 L (Alt Spans) Total Load Defl. (in)0.020 @ 3' 9"0.243 Passed (L/999+)--1.0 D + 1.0 L (Alt Spans) System : Floor Member Type : Drop Beam Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/360) and TL (L/240). •Overhang deflection criteria: LL (2L/360) and TL (2L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •Applicable calculations are based on NDS. • Blocking Panels are assumed to carry no loads applied directly above them and the full load is applied to the member being designed. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Floor Live Factored Accessories 1 - Stud wall - HF 3.50"3.50"1.66"496 1854 2350 Blocking 2 - Stud wall - HF 3.50"3.50"1.50"306 1228/-84 1533 Blocking •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)6' 4" o/c Bottom Edge (Lu)6' 4" o/c Dead Floor Live Vertical Loads Location (Side)Tributary Width (0.90)(1.00)Comments 0 - Self Weight (PLF)0 to 6' 4"N/A 8.2 -- 1 - Uniform (PSF)0 to 6' 4" (Front)11' 10"10.0 40.0 FLOOR Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED FLOOR FRAMING, M2 1 piece(s) 4 x 10 DF No.2 ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 10 / 1128 of 42 Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) Member Reaction (lbs)382 @ 2 1/2"1367 (2.25")Passed (28%)--1.0 D + 1.0 L (All Spans) Shear (lbs)318 @ 1' 3/4"1388 Passed (23%)1.00 1.0 D + 1.0 L (All Spans) Moment (Ft-lbs)1055 @ 5' 10"1917 Passed (55%)1.00 1.0 D + 1.0 L (All Spans) Live Load Defl. (in)0.149 @ 5' 10"0.281 Passed (L/903)--1.0 D + 1.0 L (All Spans) Total Load Defl. (in)0.187 @ 5' 10"0.563 Passed (L/723)--1.0 D + 1.0 L (All Spans) TJ-Pro™ Rating N/A N/A N/A --N/A System : Floor Member Type : Joist Building Use : Residential Building Code : IBC 2018 Design Methodology : ASD •Deflection criteria: LL (L/480) and TL (L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •A 15% increase in the moment capacity has been added to account for repetitive member usage. •Applicable calculations are based on NDS. •No composite action between deck and joist was considered in analysis. • Rim Board is assumed to carry all loads applied directly above it, bypassing the member being designed. Bearing Length Loads to Supports (lbs) Supports Total Available Required Dead Floor Live Factored Accessories 1 - Stud wall - HF 3.50"2.25"1.50"78 311 389 1 1/4" Rim Board 2 - Stud wall - HF 3.50"2.25"1.50"78 311 389 1 1/4" Rim Board •Maximum allowable bracing intervals based on applied load. Lateral Bracing Bracing Intervals Comments Top Edge (Lu)9' 9" o/c Bottom Edge (Lu)11' 6" o/c Dead Floor Live Vertical Load Location (Side)Spacing (0.90)(1.00)Comments 1 - Uniform (PSF)0 to 11' 8"16"10.0 40.0 FLOOR Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator Weyerhaeuser Notes All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal. MEMBER REPORT PASSED FLOOR FRAMING, M3 1 piece(s) 2 x 10 HF No.2 @ 16" OC ForteWEB Software Operator Job Notes 8/22/2023 9:19:38 PM UTCAlec Hodge Hodge Engineering (253) 857-7055 alechodge@live.com ForteWEB v3.6, Engine: V8.3.0.43, Data: V8.1.4.1 File Name: 230370 - BEAM CALCULATIONS Page 11 / 1129 of 42 30 of 42 General Footing HODGE ENGINEERING INCLic. # : KW-06007122 DESCRIPTION:24" footing - 1500 psf soil Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . Code References Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2018 General Information Material Properties Soil Design Values 1.50 Analysis Settings 250.0ksi No ksfAllowable Soil Bearing = = 2.50 60.0 3,122.0 145.0 =0.30 Flexure =0.90 Shear = Valuesj 0.00180 Soil Passive Resistance (for Sliding) 1.0 = Increases based on footing plan dimension Add Pedestal Wt for Soil Pressure No: Use Pedestal wt for stability, mom & shear No: Allowable pressure increase per foot of depth =ksfwhen max. length or width is greater than =ft : = Add Ftg Wt for Soil Pressure Yes Yes:Use ftg wt for stability, moments & shears when footing base is below ft pcf Increase Bearing By Footing Weight =pcf Min. Overturning Safety Factor = : 1 Increases based on footing Depth0.750 = Soil/Concrete Friction Coeff. Ec : Concrete Elastic Modulus = =Footing base depth below soil surface ft =Allow press. increase per foot of depth ksf = : 11.0Min. Sliding Safety Factor = = Concrete Density = Min Allow % Temp Reinf. ksif'c : Concrete 28 day strength fy : Rebar Yield ksi Min Steel % Bending Reinf. # Dimensions Width parallel to X-X Axis 2.0 ft Length parallel to Z-Z Axis = 2.0 ft =Pedestal dimensions... px : parallel to X-X Axis in pz : parallel to Z-Z Axis in Height == in Footing Thickness = 8.0 in= Rebar Centerline to Edge of Concrete...=inat Bottom of footing 3.0 Reinforcing # Bars parallel to X-X Axis Reinforcing Bar Size = 4Number of Bars = 2.0 Bars parallel to Z-Z Axis Reinforcing Bar Size =4Number of Bars =2.0 Bandwidth Distribution Check (ACI 15.4.4.2) Direction Requiring Closer Separation n/a # Bars required within zone n/a # Bars required on each side of zone n/a Applied Loads 2.50 3.0 D Lr ksf L S P : Column Load OB : Overburden = k W E M-zz V-x = =k V-z k M-xx = k-ft= k-ft H = 31 of 42 General Footing HODGE ENGINEERING INCLic. # : KW-06007122 DESCRIPTION:24" footing - 1500 psf soil Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . PASS n/a Sliding - X-X 0.0k 0.0k No Sliding PASS n/a Sliding - Z-Z 0.0k 0.0k No Sliding DESIGN SUMMARY Design OK Governing Load CombinationMin. Ratio Item Applied Capacity PASS 0.9813 Soil Bearing 1.472ksf 1.50ksf +D+S PASS n/a Overturning - X-X 0.0k-ft 0.0k-ft No Overturning PASS n/a Overturning - Z-Z 0.0k-ft 0.0k-ft No Overturning PASS n/a Uplift 0.0k 0.0k No Uplift PASS 0.2505 Z Flexure (+X)1.074k-ft/ft 4.288k-ft/ft +1.20D+1.60S PASS 0.2505 Z Flexure (-X)1.074k-ft/ft 4.288k-ft/ft +1.20D+1.60S PASS 0.2505 X Flexure (+Z)1.074k-ft/ft 4.288k-ft/ft +1.20D+1.60S PASS 0.2505 X Flexure (-Z)1.074k-ft/ft 4.288k-ft/ft +1.20D+1.60S PASS 0.2769 1-way Shear (+X)20.770psi 75.0psi +1.20D+1.60S PASS 0.2769 1-way Shear (-X)20.770psi 75.0psi +1.20D+1.60S PASS 0.2769 1-way Shear (+Z)20.770psi 75.0psi +1.20D+1.60S PASS 0.2769 1-way Shear (-Z)20.770psi 75.0psi +1.20D+1.60S PASS 0.5289 2-way Punching 79.334psi 150.0psi +1.20D+1.60S Detailed Results Rotation Axis &ZeccXecc Actual Soil Bearing Stress @ Location Actual / Allow Soil Bearing (in)Gross Allowable Bottom Left Top Left Top Right Bottom Right RatioLoad Combination... , D Only 0.000 , 0.0 deg CCW 1.50 0.72170.7217 0.7217 0.7217 0.4810.00.0 , +D+S 0.000 , 0.0 deg CCW 1.50 1.4721.472 1.472 1.472 0.9810.00.0 , +D+0.750S 0.000 , 0.0 deg CCW 1.50 1.2841.284 1.284 1.284 0.8560.00.0 , +0.60D 0.000 , 0.0 deg CCW 1.50 0.43300.4330 0.4330 0.4330 0.2890.00.0 Rotation Axis & Overturning Stability Load Combination...StatusOverturning Moment Resisting Moment Stability Ratio Footing Has NO Overturning Force Application Axis Sliding Stability All units k Load Combination...StatusSliding Force Resisting Force Stability Ratio Footing Has NO Sliding Flexure Axis & Load Combination in^2 in^2 in^2 k-ft As Req'd Footing Flexure Tension k-ft Actual As StatusMu Side Surface Gvrn. As Phi*Mn X-X, +1.40D 0.5254 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.40D 0.5254 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D 0.4503 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D 0.4503 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+0.50S 0.6453 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+0.50S 0.6453 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+1.60S 1.074 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+1.60S 1.074 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+0.70S 0.7233 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +1.20D+0.70S 0.7233 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +0.90D 0.3377 +Z Bottom 0.1728 Min Temp %0.20 4.288 OK X-X, +0.90D 0.3377 -Z Bottom 0.1728 Min Temp %0.20 4.288 OK Z-Z, +1.40D 0.5254 -X Bottom 0.1728 Min Temp %0.20 4.288 OK Z-Z, +1.40D 0.5254 +X Bottom 0.1728 Min Temp %0.20 4.288 OK Z-Z, +1.20D 0.4503 -X Bottom 0.1728 Min Temp %0.20 4.288 OK Z-Z, +1.20D 0.4503 +X Bottom 0.1728 Min Temp %0.20 4.288 OK 32 of 42 Concrete Beam HODGE ENGINEERING INCLic. # : KW-06007122 DESCRIPTION:12" footing with 6" stem wall 1500 psf soil, 2500 psi concrete Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . CODE REFERENCES Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : IBC 2018 Material Properties 2.50 7.50 145.0 Elastic Modulus 3,122.0 ksi 1 60.0 29,000.0 40.0 29,000.0 3= =0.90 0.750 f'c ksi fy - Main Rebar ksi Density 1/2 = fr = f'c *375.0 pcf E - Main Rebar ksi psi =1.0lLtWt Factor Fy - Stirrups ksi == = E - Stirrups ksi b 0.850 == = Shear : Stirrup Bar Size # Number of Resisting Legs Per Stirrup Phi Values Flexure : y f .Cross Section & Reinforcing Details Inverted Tee Section, Stem Width = 6.0 in, Total Height = 18.0 in, Top Flange Width = 12.0 in, Flange Thickness = 6.0 in Span #1 Reinforcing.... 2-#4 at 3.0 in from Bottom, from 0.0 to 5.0 ft in this span 1-#4 at 3.0 in from Top, from 0.0 to 5.0 ft in this span . Beam self weight calculated and added to loads Load for Span Number 1 Uniform Load : D = 0.0150, S = 0.030 ksf, Tributary Width = 15.0 ft, (Roof) Uniform Load : D = 0.010, L = 0.040 ksf, Tributary Width = 7.0 ft, (Floor) Point Load : D = 3.0, S = 7.0 k @ 2.50 ft .Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.892 : 1 Span # where maximum occurs Span # 1 Location of maximum on span 2.505 ft Mn * Phi : Allowable 25.551 k-ft Typical SectionSection used for this span Mu : Applied 22.804 k-ft Maximum Deflection 0 <360.0 9596 Ratio =0 <180.0 Max Downward Transient Deflection 0.003 in 19795Ratio =>=360.0 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.006 in Ratio =>=180.0Max Upward Total Deflection 0.000 in . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Overall MAXimum 7.225 7.225 Overall MINimum 0.700 0.700 D Only 2.600 2.600 +D+L 3.300 3.300 +D+S 7.225 7.225 +D+0.750L 3.125 3.125 +D+0.750L+0.750S 6.594 6.594 +0.60D 1.560 1.560 L Only 0.700 0.700 S Only 4.625 4.625 . 33 of 42 Concrete Beam HODGE ENGINEERING INCLic. # : KW-06007122 DESCRIPTION:12" footing with 6" stem wall 1500 psf soil, 2500 psi concrete Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . Span # Bending Stress Results ( k-ft )Location (ft)Load Combination Mu : Max Stress RatioSegmentPhi*Mnxalong Beam +1.20D+0.50L+0.50S Span # 1 1 5.000 11.65 25.55 0.46 +1.20D+0.50L+0.70S Span # 1 1 5.000 13.68 25.55 0.54 +0.90D Span # 1 1 5.000 4.61 25.55 0.18 . Location in Span (ft)Load CombinationMax. "-" Defl (in) Location in Span (ft)Load Combination Span Max. "+" Defl (in) Overall Maximum Deflections +D+S 1 0.0063 2.500 0.0000 0.000 34 of 42 Concrete Beam HODGE ENGINEERING INCLic. # : KW-06007122 Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . DESCRIPTION: 15" footing with 8" stem wall 1500 psf soil, 2500 psi concrete CODE REFERENCES Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : IBC 2018 Material Properties 2.50 7.50 145.0 Elastic Modulus 3,122.0 ksi 1 60.0 29,000.0 40.0 29,000.0 3= =0.90 0.750 f'c ksi fy - Main Rebar ksi Density 1/2 = fr = f'c *375.0 pcf E - Main Rebar ksi psi =1.0lLtWt Factor Fy - Stirrups ksi == = E - Stirrups ksi b 0.850 == = Shear : Stirrup Bar Size # Number of Resisting Legs Per Stirrup Phi Values Flexure : y f .Cross Section & Reinforcing Details Inverted Tee Section, Stem Width = 8.0 in, Total Height = 18.0 in, Top Flange Width = 15.0 in, Flange Thickness = 6.0 in Span #1 Reinforcing.... 2-#4 at 3.0 in from Bottom, from 0.0 to 5.0 ft in this span 1-#4 at 3.0 in from Top, from 0.0 to 5.0 ft in this span . Beam self weight calculated and added to loads Load for Span Number 1 Uniform Load : D = 0.0150, S = 0.030 ksf, Tributary Width = 15.0 ft, (Roof) Uniform Load : D = 0.010, L = 0.040 ksf, Tributary Width = 7.0 ft, (Floor) Point Load : D = 3.0, S = 7.0 k @ 2.50 ft, (Point Load) .Design OKDESIGN SUMMARY Maximum Bending Stress Ratio =0.868 : 1 Span # where maximum occurs Span # 1 Location of maximum on span 2.495 ft Mn * Phi : Allowable 26.452 k-ft Typical SectionSection used for this span Mu : Applied 22.962 k-ft Maximum Deflection 0 <360.0 16719 Ratio =0 <180.0 Max Downward Transient Deflection 0.002 in 25683Ratio =>=360.0 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.004 in Ratio =>=180.0Max Upward Total Deflection 0.000 in . Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Overall MAXimum 7.331 7.331 Overall MINimum 0.700 0.700 D Only 2.706 2.706 +D+L 3.406 3.406 +D+S 7.331 7.331 +D+0.750L 3.231 3.231 +D+0.750L+0.750S 6.699 6.699 +0.60D 1.623 1.623 L Only 0.700 0.700 S Only 4.625 4.625 . 35 of 42 Concrete Beam HODGE ENGINEERING INCLic. # : KW-06007122 DESCRIPTION: 15" footing with 8" stem wall 1500 psf soil, 2500 psi concrete Hodge Engineering, Inc 3733 Rosedale St. Suite 200 Gig Harbor, WA. 98335 253-857-7055 Software copyright ENERCALC, INC. 1983-2019, Build:12.19.11.30 . File = C:\Users\JOHNHO~1\DOCUME~1\ENERCA~1\2018 Footing Pad Calcs.ec6 . Span # Bending Stress Results ( k-ft )Location (ft)Load Combination Mu : Max Stress RatioSegmentPhi*Mnxalong Beam +1.20D+0.50L+0.50S Span # 1 1 5.000 11.81 26.45 0.45 +1.20D+0.50L+0.70S Span # 1 1 5.000 13.84 26.45 0.52 +0.90D Span # 1 1 5.000 4.73 26.45 0.18 . Location in Span (ft)Load CombinationMax. "-" Defl (in) Location in Span (ft)Load Combination Span Max. "+" Defl (in) Overall Maximum Deflections +D+S 1 0.0036 2.500 0.0000 0.000 36 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :6' Unrestrained 40 psf Surcharge Dsgnr:JEH Page : 1 Description.... 6' Unrestrained wall This Wall in File: C:\Users\johnhodge\Documents\RetainPro 10 Project Files\unrestrained walls 2.RPX RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained 6.00 0.50 0.00 12.00 1,500.0 35.0 0.0 300.0 Criteria Soil Data Retained Height =ft Wall height above soil =ft Active Heel Pressure =psf/ftSlope Behind Wall Height of Soil over Toe in Water height over heel =ft = = 110.00= pcf = Soil Density, Heel = Passive Pressure = psf/ft Allow Soil Bearing = psf Soil Density, Toe 110.00pcf Footing||Soil Friction =0.350 Soil height to ignore for passive pressure = 0.00in Equivalent Fluid Pressure Method Surcharge Loads Adjacent Footing Load Load Type 40.0 Lateral Load = 0.0#/ft 0.0 100.0 200.0 0.0 Axial Load Applied to Stem Wall to Ftg CL Dist =0.00ft Wind on Exposed Stem psf0.0= Lateral Load Applied to Stem Surcharge Over Heel =psf Adjacent Footing Load =0.0lbs Axial Dead Load (Service Level) =lbs Footing Type Line Load Surcharge Over Toe psf Footing Width =0.00ft...Height to Top =0.00ft Eccentricity =0.00in...Height to Bottom = 0.00ft Used To Resist Sliding & Overturning Used for Sliding & Overturning = 0.0ft Axial Live Load = Base Above/Below Soil lbs = Axial Load Eccentricity ==Poisson's Ratio 0.300 at Back of Wall in (Service Level) Wind (W)= Design Summary Wall Stability Ratios Overturning =2.07OK Sliding =1.55OK Total Bearing Load =2,391lbs ...resultant ecc. =6.69in Soil Pressure @ Toe =1,488psf OK Soil Pressure @ Heel =0psf OK Allowable =1,500 psf Soil Pressure Less Than Allowable ACI Factored @ Toe =2,083psf ACI Factored @ Heel =0psf Footing Shear @ Toe =19.0psi OK Footing Shear @ Heel =9.2psi OK Allowable =75.0psi Sliding Calcs Lateral Sliding Force =883.3lbs less 100% Passive Force less 100% Friction Force Added Force Req'd ....for 1.5 Stability = 0.0= 766.8 600.0 = = 0.0 - lbs lbs lbs OK lbs OK - Masonry Block Type =Medium Weight Stem Construction 3rd 2nd Stem OKStem OK Stem OK Bottom Shear.....Actual Design Height Above Ftg =3.50ft 1.00 0.00 Wall Material Above "Ht" =Concrete Concrete Concrete Thickness =8.00 8.00 8.00 Rebar Size =###4 4 4 Rebar Spacing = 12.00 12.00 12.00 Rebar Placed at =Center Center Center Design Data fb/FB + fa/Fa =0.061 0.419 0.703 Total Force @ Section =l bs Moment....Actual =ft-# Moment.....Allowable =3,387.6 3,387.6 3,387.6ft-# =p si Shear.....Allowable =75.0 75.0psi 75.0 Wall Weight = 100.0 100.0psf 100.0 Rebar Depth 'd'= 4.00in 4.00 4.00 Masonry Data f'm =psi Fs =psi Solid Grouting = Modular Ratio 'n'= Short Term Factor = Equiv. Solid Thick.= Concrete Data f'c =2,500.0 2,500.0psi 2,500.0 Fy =60,000.0 60,000.0 Masonry Design Method ASD= Load Factors Building Code IBC 2018,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 psi 60,000.0 Service Level = 225.9 801.8lbs 1,130.2Strength Level Service Level Strength Level = 209.5 1,421.2 2,382.5ft-# Service Level Strength Level = 4.7 16.7 23.5psi Design Method = LRFD LRFD LRFD Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Anet (Masonry)=in2 37 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :6' Unrestrained 40 psf Surcharge Dsgnr:JEH Page : 2 Description.... 6' Unrestrained wall This Wall in File: C:\Users\johnhodge\Documents\RetainPro 10 Project Files\unrestrained walls 2.RPX RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained Concrete Stem Rebar Area Details 3rd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.0126 in2/ft (4/3) * As :0.0169 in2/ft Min Stem T&S Reinf Area 0.576 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.1728 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.2 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ 2nd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.0858 in2/ft (4/3) * As :0.1144 in2/ft Min Stem T&S Reinf Area 0.480 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.1728 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.2 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ Bottom Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.1438 in2/ft (4/3) * As :0.1918 in2/ft Min Stem T&S Reinf Area 0.192 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.16 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.2 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in 1.30 1.96 9.00 Footing Torsion, Tu ==ft-lbs0 .00Min. As % Footing Allow. Torsion, phi Tu 0.0018 =ft-lbs Footing Data If torsion exceeds allowable, provide f'c 0.00 = 2,500psi Toe Width =ft Heel Width = Key Distance from Toe Key Depth Key Width =in =in = 8.00 3.00 1.30ft Footing Thickness =in 3.26= Cover @ Top =2.00 in@ Btm.=3.00in Total Footing Width =150.00pcfFooting Concrete Density Fy=60,000psi Footing Design Results Key: = phiMn = phi'5'lambda'sqrt(fc)'Sm Factored Pressure Mu' : Upward Mu' : Downward Mu: Design Actual 1-Way Shear Allow 1-Way Shear Toe:#4@ 12.34 in, #5@ 19.13 in, #6@ 27.16 in, #7@ 37.03 in, #8@ 48.76 in, #9@ 6 phiMn = phi'5'lambda'sqrt(fc)'Sm =# 4 @ 13.89 in = = = = = 2,083 18,171 2,691 1,290 19.05 75.00 Heel: 0 211 831 620 9.24 40.00 HeelToe psf ft-# ft-# ft-# psi psi Heel Reinforcing =None Spec'd Other Acceptable Sizes & Spacings Key Reinforcing Toe Reinforcing =# 4 @ 12.00 in Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars: 0.63 0.19 #4@ 12.35 in #5@ 19.14 in #6@ 27.16 in in2 in2 /ft If two layers of horizontal bars: #4@ 24.69 in #5@ 38.27 in #6@ 54.32 in supplemental design for footing torsion. 38 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :8' Unrestrained 40 psf Surcharge Dsgnr:JEH Page : 1 Description.... 8' Unrestrained wall 40 psf surcharge This Wall in File: C:\Users\johnhodge\Documents\RetainPro 10 Project Files\unrestrained walls 2.RPX RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained 8.00 0.50 0.00 12.00 1,515.0 35.0 0.0 300.0 Criteria Soil Data Retained Height =ft Wall height above soil =ft Active Heel Pressure =psf/ftSlope Behind Wall Height of Soil over Toe in Water height over heel =ft = = 110.00= pcf = Soil Density, Heel = Passive Pressure = psf/ft Allow Soil Bearing = psf Soil Density, Toe 110.00pcf Footing||Soil Friction =0.350 Soil height to ignore for passive pressure = 0.00in Equivalent Fluid Pressure Method Surcharge Loads Adjacent Footing Load Load Type 40.0 Lateral Load = 0.0#/ft 0.0 100.0 200.0 0.0 Axial Load Applied to Stem Wall to Ftg CL Dist =0.00ft Wind on Exposed Stem psf0.0= Lateral Load Applied to Stem Surcharge Over Heel =psf Adjacent Footing Load =0.0lbs Axial Dead Load (Service Level) =lbs Footing Type Line Load Surcharge Over Toe psf Footing Width =0.00ft...Height to Top =0.00ft Eccentricity =0.00in...Height to Bottom = 0.00ft Used To Resist Sliding & Overturning Used for Sliding & Overturning = 0.0ft Axial Live Load = Base Above/Below Soil lbs = Axial Load Eccentricity ==Poisson's Ratio 0.300 at Back of Wall in (Service Level) Wind (W)= Design Summary Wall Stability Ratios Overturning =2.38OK Sliding =1.53OK Total Bearing Load =4,030lbs ...resultant ecc. =7.50in Soil Pressure @ Toe =1,514psf OK Soil Pressure @ Heel =179psf OK Allowable =1,515 psf Soil Pressure Less Than Allowable ACI Factored @ Toe =2,120psf ACI Factored @ Heel =251psf Footing Shear @ Toe =19.7psi OK Footing Shear @ Heel =11.6psi OK Allowable =75.0psi Sliding Calcs Lateral Sliding Force =1,532.0lbs less 100% Passive Force less 100% Friction Force Added Force Req'd ....for 1.5 Stability = 0.0= 1,340.3 1,001.0 = = 0.0 - lbs lbs lbs OK lbs OK - Masonry Block Type =Medium Weight Stem Construction 3rd 2nd Stem OKStem OK Stem OK Bottom Shear.....Actual Design Height Above Ftg =3.50ft 1.00 0.00 Wall Material Above "Ht" =Concrete Concrete Concrete Thickness =8.00 8.00 8.00 Rebar Size =###5 5 5 Rebar Spacing = 12.00 12.00 10.75 Rebar Placed at =Center Center Center Design Data fb/FB + fa/Fa =0.208 0.729 0.970 Total Force @ Section =l bs Moment....Actual =ft-# Moment.....Allowable =5,069.7 5,069.7 5,593.0ft-# =p si Shear.....Allowable =75.0 75.0psi 75.0 Wall Weight = 100.0 100.0psf 100.0 Rebar Depth 'd'= 4.00in 4.00 4.00 Masonry Data f'm =psi Fs =psi Solid Grouting = Modular Ratio 'n'= Short Term Factor = Equiv. Solid Thick.= Concrete Data f'c =2,500.0 2,500.0psi 2,500.0 Fy =60,000.0 60,000.0 Masonry Design Method ASD= Load Factors Building Code IBC 2018,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 psi 60,000.0 Service Level = 658.6 1,514.5lbs 1,954.9Strength Level Service Level Strength Level = 1,056.7 3,700.2 5,430.3ft-# Service Level Strength Level = 13.7 31.6 40.7psi Design Method = LRFD LRFD LRFD Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Anet (Masonry)=in2 39 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :8' Unrestrained 40 psf Surcharge Dsgnr:JEH Page : 2 Description.... 8' Unrestrained wall 40 psf surcharge This Wall in File: C:\Users\johnhodge\Documents\RetainPro 10 Project Files\unrestrained walls 2.RPX RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained Concrete Stem Rebar Area Details 3rd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.0638 in2/ft (4/3) * As :0.0851 in2/ft Min Stem T&S Reinf Area 0.960 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.1728 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.31 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ 2nd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.2234 in2/ft (4/3) * As :0.2978 in2/ft Min Stem T&S Reinf Area 0.480 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.2234 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.31 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ Bottom Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.3278 in2/ft (4/3) * As :0.4371 in2/ft Min Stem T&S Reinf Area 0.192 in2 200bd/fy : 200(12)(4)/60000 :0.16 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.3278 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.346 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.5419 in2/ft #6@ 27.50 in #6@ 55.00 in 2.05 2.71 12.00 Footing Torsion, Tu ==ft-lbs0 .00Min. As % Footing Allow. Torsion, phi Tu 0.0018 =ft-lbs Footing Data If torsion exceeds allowable, provide f'c 0.00 = 2,500psi Toe Width =ft Heel Width = Key Distance from Toe Key Depth Key Width =in =in = 8.00 7.00 2.05ft Footing Thickness =in 4.76= Cover @ Top =2.00 in@ Btm.=3.00in Total Footing Width =150.00pcfFooting Concrete Density Fy=60,000psi Footing Design Results Key: = #4@ 13.88 in, #5@ 18 in, #6@ 18 in, #7@ 18 in, #8@ 18 i Factored Pressure Mu' : Upward Mu' : Downward Mu: Design Actual 1-Way Shear Allow 1-Way Shear Toe:#4@ 9.25 in, #5@ 14.35 in, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 #4@ 9.25 in, #5@ 14.35 in, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 =# 4 @ 13.89 in = = = = = 2,120 46,526 7,837 3,224 19.69 75.00 Heel: 251 1,086 2,721 1,635 11.62 75.00 HeelToe psf ft-# ft-# ft-# psi psi Heel Reinforcing =# 4 @ 18.00 in Other Acceptable Sizes & Spacings Key Reinforcing Toe Reinforcing =# 4 @ 9.26 in Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars: 1.23 0.26 #4@ 9.26 in #5@ 14.35 in #6@ 20.37 in in2 in2 /ft If two layers of horizontal bars: #4@ 18.52 in #5@ 28.70 in #6@ 40.74 in supplemental design for footing torsion. 40 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :10' Unrestrained 40 psf Surcharge Page : 1 Dsgnr:JEH Date: 11 JUN 2021 Description.... 10' Unrestrained wall with 40 psf surcharge This Wall in File: c:\users\johnhodge\documents\retainpro 10 project files\unrestrained walls 2.rpx RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained 10.00 0.50 0.00 12.00 1,500.0 35.0 0.0 300.0 Criteria Soil Data Retained Height =ft Wall height above soil =ft Active Heel Pressure =psf/ftSlope Behind Wall Height of Soil over Toe in Water height over heel =ft = = 110.00= pcf = Soil Density, Heel = Passive Pressure = psf/ft Allow Soil Bearing = psf Soil Density, Toe 110.00pcf Footing||Soil Friction =0.350 Soil height to ignore for passive pressure = 0.00in Equivalent Fluid Pressure Method Surcharge Loads Adjacent Footing Load Load Type 40.0 Lateral Load = 0.0#/ft 0.0 0.0 0.0 0.0 Axial Load Applied to Stem Wall to Ftg CL Dist =0.00ft Wind on Exposed Stem psf0.0= Lateral Load Applied to Stem Surcharge Over Heel =psf Adjacent Footing Load =0.0lbs Axial Dead Load (Service Level) =lbs Footing Type Line Load Surcharge Over Toe psf Footing Width =0.00ft...Height to Top =0.00ft Eccentricity =0.00in...Height to Bottom = 0.00ft Used To Resist Sliding & Overturning Used for Sliding & Overturning = 0.0ft Axial Live Load = Base Above/Below Soil lbs = Axial Load Eccentricity ==Poisson's Ratio 0.300 at Back of Wall in (Service Level) Wind (W)= Design Summary Wall Stability Ratios Overturning =2.64OK Sliding =1.53OK Total Bearing Load =5,600lbs ...resultant ecc. =7.60in Soil Pressure @ Toe =1,438psf OK Soil Pressure @ Heel =351psf OK Allowable =1,500 psf Soil Pressure Less Than Allowable ACI Factored @ Toe =2,014psf ACI Factored @ Heel =492psf Footing Shear @ Toe =28.7psi OK Footing Shear @ Heel =18.0psi OK Allowable =75.0psi Sliding Calcs Lateral Sliding Force =2,257.5lbs less 100% Passive Force less 100% Friction Force Added Force Req'd ....for 1.5 Stability = 0.0= 1,960.1 1,504.2 = = 0.0 - lbs lbs lbs OK lbs OK - Masonry Block Type =Medium Weight Stem Construction 3rd 2nd Stem OKStem OK Stem OK Bottom Shear.....Actual Design Height Above Ftg =3.50ft 1.00 0.00 Wall Material Above "Ht" =Concrete Concrete Concrete Thickness =8.00 8.00 8.00 Rebar Size =###5 5 5 Rebar Spacing = 9.00 9.00 9.00 Rebar Placed at = 6.25 i 6.25 i 6.25 i Design Data fb/FB + fa/Fa =0.279 0.711 0.965 Total Force @ Section =l bs Moment....Actual =ft-# Moment.....Allowable =10,717.8 10,717.8 10,717.8ft-# =p si Shear.....Allowable =75.0 75.0psi 75.0 Wall Weight = 100.0 100.0psf 100.0 Rebar Depth 'd'= 6.25in 6.25 6.25 Masonry Data f'm =psi Fs =psi Solid Grouting = Modular Ratio 'n'= Short Term Factor = Equiv. Solid Thick.= Concrete Data f'c =2,500.0 2,500.0psi 2,500.0 Fy =60,000.0 60,000.0 Masonry Design Method ASD= Load Factors Building Code IBC 2018,ACI Dead Load 1.200 Live Load 1.600 Earth, H 1.600 Wind, W 1.000 Seismic, E 1.000 psi 60,000.0 Service Level = 1,315.4 2,451.3lbs 3,003.6Strength Level Service Level Strength Level = 2,993.3 7,628.7 10,351.5ft-# Service Level Strength Level = 17.5 32.7 40.0psi Design Method = LRFD LRFD LRFD Vertical component of active lateral soil pressure IS NOT considered in the calculation of soil bearing Anet (Masonry)=in2 41 of 42 Hodge Engineering, Inc. 3733 Rosedale St. Ste. 200 Gig Harbor, WA. 98335 Title :10' Unrestrained 40 psf Surcharge Page : 2 Dsgnr:JEH Date: 11 JUN 2021 Description.... 10' Unrestrained wall with 40 psf surcharge This Wall in File: c:\users\johnhodge\documents\retainpro 10 project files\unrestrained walls 2.rpx RetainPro (c) 1987-2019, Build 11.20.03.31 Cantilevered Retaining Wall Code: IBC 2018,ACI 318-14,TMS 402-16License : KW-06053958License To : HODGE ENGINEERING Project Name/Number : unrestrained Concrete Stem Rebar Area Details 3rd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.1121 in2/ft (4/3) * As :0.1495 in2/ft Min Stem T&S Reinf Area 1.344 in2 200bd/fy : 200(12)(6.25)/60000 :0.25 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.1728 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.4133 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.8467 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ 2nd Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.2858 in2/ft (4/3) * As :0.3811 in2/ft Min Stem T&S Reinf Area 0.480 in2 200bd/fy : 200(12)(6.25)/60000 :0.25 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.2858 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.4133 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.8467 in2/ft #6@ 27.50 in #6@ 55.00 in ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ Bottom Stem Vertical Reinforcing Horizontal Reinforcing As (based on applied moment) :0.3878 in2/ft (4/3) * As :0.5171 in2/ft Min Stem T&S Reinf Area 0.192 in2 200bd/fy : 200(12)(6.25)/60000 :0.25 in2/ft Min Stem T&S Reinf Area per ft of stem Height : 0.192 in2/ft 0.0018bh : 0.0018(12)(8) :0.1728 in2/ft Horizontal Reinforcing Options : ============One layer of : Two layers of : Required Area :0.3878 in2/ft #4@ 12.50 in #4@ 25.00 in Provided Area :0.4133 in2/ft #5@ 19.38 in #5@ 38.75 in Maximum Area :0.8467 in2/ft #6@ 27.50 in #6@ 55.00 in 2.80 3.46 12.00 Footing Torsion, Tu ==ft-lbs0 .00Min. As % Footing Allow. Torsion, phi Tu 0.0018 =ft-lbs Footing Data If torsion exceeds allowable, provide f'c 0.00 = 2,500psi Toe Width =ft Heel Width = Key Distance from Toe Key Depth Key Width =in =in = 8.00 14.00 2.80ft Footing Thickness =in 6.26= Cover @ Top =2.00 in@ Btm.=3.00in Total Footing Width =150.00pcfFooting Concrete Density Fy=60,000psi Footing Design Results Key: = #4@ 13.88 in, #5@ 18 in, #6@ 18 in, #7@ 18 in, #8@ 18 i Factored Pressure Mu' : Upward Mu' : Downward Mu: Design Actual 1-Way Shear Allow 1-Way Shear Toe:#4@ 9.25 in, #5@ 14.35 in, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 #4@ 9.25 in, #5@ 14.35 in, #6@ 20.37 in, #7@ 27.77 in, #8@ 36.57 in, #9@ 46 =# 4 @ 13.88 in = = = = = 2,014 83,819 14,633 5,766 28.73 75.00 Heel: 492 2,808 6,113 3,305 17.96 75.00 HeelToe psf ft-# ft-# ft-# psi psi Heel Reinforcing =# 4 @ 9.26 in Other Acceptable Sizes & Spacings Key Reinforcing Toe Reinforcing =# 4 @ 9.25 in Min footing T&S reinf Area Min footing T&S reinf Area per foot If one layer of horizontal bars: 1.62 0.26 #4@ 9.26 in #5@ 14.35 in #6@ 20.37 in in2 in2 /ft If two layers of horizontal bars: #4@ 18.52 in #5@ 28.70 in #6@ 40.74 in supplemental design for footing torsion. 42 of 42