Engineering CalcsCopyright 2024, SEGA Engineers
STRUCTURAL CALCULATIONS
FOR THE
SOUNDBUILT HOMES RESIDENTIAL PROJECT
Plan L2M-2482
January 21, 2024
Job No: 09-059
Location: Lots 201 - 398, Tahoma Terra
Yelm, Washington
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010
01 01 01 01////21212121////24242424
Copyright 2018, SEGA Engineers
STATEMENT OF WORK
SEGA Engineers was asked to provide a lateral loads analysis, shear wall
design, review of major framing members and foundation, and drawing red-lines
for a two-story wood framed single family residence. The roof framing is
manufactured trusses, the floor framing is 2x dimensional or open-web trusses,
and the foundation is typical concrete strip footings with a crawl space.
The application and use of these calculations is limited to a single site
referenced on the cover sheet. The cover sheet should have an original
signature in blue ink over the seal. The attached calculations may or may not
apply to other sites and the contractor assumes all responsibility and liability for
sites not expressly reviewed and approved. Please contact SEGA Engineers for
use at other sites.
SEGA Engineers will use that degree of care and skill ordinarily exercised under
similar circumstances by members of the engineering profession in this local. No
other warranty, either expressed or implied is made in connection with our
rending of professional services. For any dispute, claim, or action arising out of
this design, SEGA Engineers shall have liability limited to the amount of the total
fee received by SEGA Engineers.
Questions regarding the attached should be addressed to SEGA Engineers.
Greg Thesenvitz, PE/SE
SEGA Engineers
SEGA Engineers Project Plan L2-2482
Structural & Civil Consulting Engineers
Job No.09-059 By:GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date:05/18/21 Sht 1
Design Criteria
International Building Code (IBC), 2018
LOADS
Roof
DL 15 psf
LL 25 psf
Floor
DL 12 psf
LL 40 psf
Wind
Risk Category II
Design Wind Speed 110 mph (Vult)
Copyright 2021, SEGA Engineers
Design Wind Speed 110 mph (Vult)
Kzt 1.00
Exposure B
Seismic
Design Category D
SDS 1.00
Response Factor 6.5
CS =0.154
Importance Factor 1.00
Soil
Allowable Bearing 1,500 psf
Copyright 2021, SEGA Engineers
SEGA Engineers
/ Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010
LOADS
ROOF
DL Roofing (Camp)
'/z" OSB
2x @24"
Insulation
518" GWB
Misc.
FLOOR
LL Snow, Pf
Reduction, Cs
5112 pitch = 23 deg
Total Roof Load
DL Flooring
314'' Plywood
2x12@16"oc
$18" GWB
Misc.
LL Residential
Total Floor Load
DECKS
DL 2 x Decking
2x10@16"oc
Misc
WALLS
LL Residential
Total Deck Load
DL Siding
1I2" Plywood
2x6@16"oc
Insul
'12" GWB
Project 1-2-2482
Job No. 09-059 By: GAT
Checked Date:04/13117 Sht 2
3.5 psf
1.8
3.5
1.1
2.8
1.5
14.2 psf
25 psf (115% Load Duration)
0.00 (Ct = 1.1, other surfaces)
39.2 psf
0.5 psf
2.3
3.3
2.8
1.5
10.4 psf
40 psf
50.4 psf
4.3 psf
2.8
1.5
8.6
60 psf
68.6 psf
3.5
1.5 psf
1.7
0.6
2.2
9.5 psf
Copyright 2017, SEGA Engineers
SEGA En ineers
PROJECT
Structural & Civil Consulting Engineers
JOB NO. p� -rJ� FIGURED BY G,�
22939 5E 292nd Place
Black Diamond, Washington 9$010 CHECKED BY DATE �
{350} 856-1017 Zj SHEET3 OF
U
�K J ,�i/�• !elf-#�i'V {,v-.
•�. w
_ !
f
Copyright 2017, SEGA Engineers
SEGA Engineers- PROJECT e -t -
Structural & Civil Consulting Engineers - 7-4,5Z— la
22939 $E 292nd Place
JOB NO. 01 - p rc, FIGURED BY (�
- -- Black Diamond, Washington 98010 CHECKED BY DATE Mr//O/Z ( SHEET OF
(360) 886-1017
/ 1 n3
I-. ti
4s-
leg �'/C i-,' '
Coy u z k / �—
r 7-
i,t~
rat e�
z�� `Qo 5 GtZ�
'L7 10)( 4�U�4V -4) (L7-.) s
4r— ) 6�; S 4- 1 s: "' f
V ` 6,3f- 4Pu
S �J�
Copyright 2017, SEGA Engineers
SEGA En ineers
PROJECT / 'Z - Z 9 nz
Structural & Civil Consulting Engineers - - • •-•
22939 SE 292nd Place JOB NO. )rj FIGURED BY
Black Diamond, Washington 98010 CHECKED BY DATE SHEET SHEET 5 OF
(360) 886-1017
6ZA! I N 6- d foil e 1- h aa2.
P rz- -'60wtL
cgec /r plc
� " Cll � � (. 1�� � ` � � ►' 1 Loy f ��`�l-�i � =- �. �1F Y -��i z..r� �-
P +I
Gth `. � ) ock-Ps))'l00
2
�
S3a'6r� �, 1/ 1
��
77 5��ti 4 ,4--
M -C(-,7� )( 5 IZ1`) - ( �,rI')(0,� �, �" �G� 17, 7,�-f'
— s,z�
1 Z.d+
�A "'J'02!e
Arr
%- /
Copyright 2017, SEGA Engineers
�t-r/or• l-
jo-r
Dt
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Framing_- 17 ft Studs (cr)_
Side Bearing Wall
Design Criteria
Stud Height =
17 feet
Stud Spacing =
16 inches
Truss Spacing =
2 feet
Roof DL =
15 psf
Roof LL =
25 psf (snow)
Tributary Span =
15 feet
Wind Load = 10.6 psf
Member Size and Proberties
For DL + Wind
Project L2-2482
Job No. 09-059 By: GAT
Checked Date 04/13/17 Sht
I
w max = 10.60 psf
h = 17.0 ft
DL Force = 450 Ibs
Snow Load = 750 Ibs
Try 2 x 6 using HF - #2 @ 16 in oc <
Fb = 850 psi CF = 1.30 Cr = 1.35 (Table 2306.2.1)
Fbr = 1492 psi
F, = 1300 psi CF = 1.10
FEE = 283.5 psi le = 204 in d = 5.50 in
E = 1.30E+06 KIE = 0.30 c' = 0.80
P = 450 Ibs
f, = 55 psi
w = 14.1 Ibs/ft
M = 511 ft-Ibs
fb=810psi
For DL + 314Wind + 314Snow
P = 10131bs
fc = 123 psi
w = 10.6 Ibslft
M = 383 ft-Ibs
fb = 608 psi
Cp = 0.21
F,' = 296.3 psi
_ (Eq 16-12)
(Eq 16-13)
Combined
Axial Bending Total
0.03 + 0.67 = 0.71 OK
Axial Bending Total
0.17 + 0.72 = 0.89 OK
COPYRIGHT 2016, SEGA ENGINEERS
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Square Footing Design Ftg 36 x 36
Design Parameters
f', = 2,500 psi Fy = 40,000 psi
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Loads:
Col DL =
2.4
kip (Service Load)
Col LL =
9.6
kip (Service Load)
Floor LL =
0
psf
Overburden =
0.0 in
(120 pcf assumed)
Slab Thick. =
0.0 in
(150 pcf assumed)
Size and Footing Pressure
h=
8.0in
qn =
1.40
ksf
{q'd A.'ea _
8.57
ftA2
Project Typical Ftg
Job No.
By:
GAT
Checked
Date:
12/03/15
Sht. -7
All. 4 = 1,500 psf
--- — Ft4?. Thickness
Try
2.95 ft x
F�- rtorod Net Sail r?rasst!r3
2.13_ _ksf (1.2D + i. ,L)
4-,-:cue 'or Two -Way Sheer
Avg d =
4.00
in
V„ =
16.76
kips
bo =
40.00
in (Critical
Shear PariiA,�t; r)
B, =
1
(Long
Side/Short Side of Column)
phi V0 =
27.20
kips
Phi V,
>
V„
OK
Check for One -Way
Shear
V„ =
5.598
kips
Phi Vr =
12.04
kips
Pali V,
>
Vt,
OK
Design Reinforcement
Mt, =
4.71
kip-ft
As =
0.51
inA2
Use (3) - 4 bars EW
a =
0.27
in
0.59 in^2
Phi Mn =
5.58
kip-ft
Phi Mn
>
Mu
OK
AS min =
0.51
in^2
OK
Min. Ftq. Ste
< Reinforcement
Copyright 2015, SEGA Engineers
SEGA Engineers
Structural & Civil Consulting Engineers
Project L2-2482
Job No. 09-059 BY: GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date: 04/13/17 Sht.
LATERAL LOADS - (Alternate ASD)
SEISMIC
Maximum Base Shear, V = F SOS W Eq. 12.14-11
R
where,
F = 1.1 Two -Story Building
SOS = 1.00 Ss = 1.5 Fa = 1.00 (Table 11.4-1, SS > 1.25)
R = 6.5 Table 12.14-1
W = Seismic Weight
For W:
W,,f= (30ft) (52ft) (16psf)+ ( 2 ) (30ft+ 52ft) (4.0ft) (9.5psf) = 31 kips
Moor= (30ft) (52ft) (14psf) +(2) (30ft+ 52ft) (8.5ft) {9.5psf) = 35kips
Wow = 66 kips
Design Base Shear, V = (.169) (66 kip) - 11.2 kip
E = 11.2 kip - 8.0 kip
01ITS,
Design Wind Pressure, ps = Kn p530
Eq. 28.6-1, Sect. 28.6.3
where,
= 1.00
0 -15 ft
Exposure B
Figure 28.6-1
= 1.00
20 ft
= 1.00
25 ft
= 1.00
30 ft
Kn = 1.00
Section 26.8
p3o = 17.7 psf
110 mph
Figure 28.6-1
(ASD)
Po _ 15 = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
( x 0.6 =
10.62 psf)
P20 = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
( x 0.6 =
10.62 psf)
P25 = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
( x 0.6 =
10.62 psf)
Pao = ( 1.00 )
( 1.00 )
(17.7 psf)
= 17.70 psf
( x 0.6 =
10.62 psf)
Design Base Shear: (Wind)
Vfrb= (30ft) (10ft) (17.7psf) + (30ft) (5ft) (17.7psf)
+ (25ft) (5ft) (17.7psf) + (10ft) (5ft) (17.7psf) =11.1x0.6=6.6kips
V,v5 = (57 ft) (10ft) (17.7psf) + (55 ft) (5ft) (17.7psf)
+ (51 ft) (5ft) (17.7psf) + (45 ft) (5ft) (17.7 psf) =23.5 x 0.6 = 14.1 kips
Therefore, Seismic Loads Govern for Lateral Design - Front/Back
Wind Loads Govern for Lateral Design - Side/Side
Copyright 2017, SEGA Engineers
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010
LATERAL LOADS - (cont'd)
Distribute Seismic Loads Over Height
Maximum Base Shear, V = 8.0 k
F. = wx V (Eq. 12.14-12)
W
Fr,of= (31.2) (8.0k) = 3.8kip
(66.3)
Ffloor = (35.1 ) (8.0 k) = 4.2 kip
(66.3)
Fx = 8.0 kip
iect L2-2482
Job No. 09-059 Bv: GAT
Checked Date: 04/13/17 Sht. 9
Copyright 2017, SEGA Engineers
SEGA Engineers PROJECT L z - z 513
Structural & Civil Consulting Engineers
JOB NO. �9 - aS� FIGURED BY -
22939 SE 292nd Place _
Black Diamond, Washington 98010 1i'Z
(360) 886-1017 CHECKED BY DATE jZ3 SHEET/q OF
�:1 s2 A G L �
O'd "
Q
422
` Z P U
car
� �,� oyice'" ON
Copyright 2017, SEGA Engineers
SEGA Engineers PROJECT
Structural & Civil Consulting Engineers —
JOB NO. C)� FIGURED BY
22939 SE 292nd Place
Black Diamond, Washington 98010 CHECKED BY DATE/-] SHEET/P OF
(360) 886-1017
�iqe v4LL 'NP1 ,J �CdNT
� �4-t _ F
-Aoc�
�iooa
/ D
s L-1 r
POCF . V9 : dj , 1
Yn>1
--I. s C� %�—
c W430
` 64W 40 S 1 ` A-0 14 41
Copyright 2017, SEGA Engineers
SEGA En ineers PROJECT l z- z ;z S a
Structural & Civil Consulting Engineers
JOB NO. (9�;1 -0 S9 FIGURED BY r
22939 SE 292nd Place �!1
Black Diamond, Washington 98010 CHECKED BY DATE ot, SHEET !/ OF
(360) 886-1017 t
(6"-, )
z cto dPE,pig
-
/'-S�I� f' S , ` --� j`'
3
tZ-) 104' 1T t ,4A. m,t
4
1,7516r / S71I
Copyright 2017, SEGA Engineers
GA
E Engineers/ PROJECT
Structural & Civil Consulting Engineers
22939 SE 292nd Place • Black Diamond, Washington 98010 JOB NO.
(360) 886-1017 • FAX 886-1016
CHECKED BY
L2-24 6
013-059 FIGURED BY GAT
DATE 11/20/23 SHEET 12 OF 12
5PEAAR WALL KEY FLAN V
TO 3xEA39, OCKII SILL
TO 3z BLOCKING.
(1YP. 2 PLACES)
Li
A
UPPER FLOOR
A = 1,394 5Q FT
G -
h r^
LSTAA: HDR d SILL
�'", -
10 3BLOCKING.
(TYP. 2 PLACES)
S
�Aqe(1YP.
i4T,S,
2
3l
LSTA36 - HDR d SILL
TO 3z BLOCKING.
2 PLACES) LSTA30 - BEAY
TO TOP PLATE
L
J
3
LSTA36 - HDR d SILL
TO 3x BLOCKING.
�)
(TYP. 2 PLACES)
yt�p Jam`
—�-HTS20
4
B
- BEAM
TO TOP PLATE
MAIN FLOOR
A = I,000 SQ FT
OPTION
0
�sr
A = 301 SQ FT
0
A = 588 50 FT
0
A = 555 5Q FT
WAF115 x 5 5TRONGWALL. SEE
51MPSON PRODUCT CHIDE
WSWHIS x 5 STROWWALL. SEE
SIMf.iON PRODUCT GUIDE
WSWHIS x S STRONGWALL. 5EE
SIMPSON PRODUCT GUIDE
FOR PORTAL INSTALLATION.
FOR PORTAL INSTALLATION.
FOR PORTAL INSTALLATION.
COPYRIGHT 2023, 5EGA ENGINEERS
SHEAR WALL SCHEDULESHEAR WALL SCHEDULESHEAR WALL SCHEDULE
Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4)
Sheathing (1)Nailing (1)Bolts (2)Sheathing (1)Nailing (1)Bolts (2)Sheathing (1)Nailing (1)Bolts (2)
A 1/" OSB 8d @ 6" o.c.5/" @ 60" o.c.Q = 230 plfA1/2" OSB 8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA/2" OSB 8d @ 6" o.c./8" @ 60" o.c.Qall = 230 plf
or CDXor CDXor CDXor CDX
1 5B1/2" OSB 8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB1/2" OSB 8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB/2" OSB 8d @ 4" o.c./8" @ 32" o.c.Qall = 350 plf
or CDXor CDXor CDX
1/" OSB 5/" @ 16" o.c.Q = 450 plfC1/2" OSB 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC1/2" OSB 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC/2" OSB 8d @ 3" o.c./8" @ 16" o.c.Qall = 450 plf
or CDX Use minimum 3x studsor CDX Use minimum 3x studsor CDX Use minimum 3x studs
at abutting panel edgesat abutting panel edgesat abutting panel edges
and stagger edge nailing.and stagger edge nailing.and stagger edge nailing.
D 1/" OSB 8d @ 2" o.c.5/" @ 16" o.c.Q = 600 plfD1/2" OSB 8d @ 2" o.c.5/8" @ 16" o.c.Qall = 600 plfD/2" OSB 8d @ 2" o.c./8" @ 16" o.c.Qall = 600 plf28all
or CDX Use minimum 3x studsor CDX Use minimum 3x studsor CDX Use minimum 3x studs
at all panel edgesat all panel edgesat all panel edges
and stagger edge nailing.and stagger edge nailing.and stagger edge nailing.
Notes:Notes:Notes:
1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing
(24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at
intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.
2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear
walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).
3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"
from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.
4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with
AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.