STRUCTURAL CALCULATIONS
FOR THE
SOUNDBUILT HOMES RESIDENTIAL PROJECT
Plan L2-3006-3
February 12, 2024
Job No: 14-011
Location: Lot 20, Mountain Meadows
Yelm, Washington
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 886-1017 Black Diamond, WA 98010
0 0 0 04444////11112222////24242424
Copyright 2018, SEGA Engineers
STATEMENT OF WORK
SEGA Engineers was asked to provide a lateral loads analysis, shear wall
design, review of major framing members and foundation, and drawing red-lines
for a two-story wood framed single family residence. The roof framing is
manufactured trusses, the floor framing is 2x dimensional or open-web trusses,
and the foundation is typical concrete strip footings with a crawl space.
The application and use of these calculations is limited to a single site
referenced on the cover sheet. The cover sheet should have an original
signature in blue ink over the seal. The attached calculations may or may not
apply to other sites and the contractor assumes all responsibility and liability for
sites not expressly reviewed and approved. Please contact SEGA Engineers for
use at other sites.
SEGA Engineers will use that degree of care and skill ordinarily exercised under
similar circumstances by members of the engineering profession in this local. No
other warranty, either expressed or implied is made in connection with our
rending of professional services. For any dispute, claim, or action arising out of
this design, SEGA Engineers shall have liability limited to the amount of the total
fee received by SEGA Engineers.
Questions regarding the attached should be addressed to SEGA Engineers.
Greg Thesenvitz, PE/SE
SEGA Engineers
SEGA Engineers Project Plan L2-3006
Structural & Civil Consulting Engineers
Job No.14-011 By:GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date:04/01/21 Sht 1
Design Criteria
International Building Code (IBC), 2018
LOADS
Roof
DL 15 psf
LL 25 psf
Floor
DL 12 psf
LL 40 psf
Wind
Risk Category II
Design Wind Speed 110 mph (Vult)
Copyright 2021, SEGA Engineers
Design Wind Speed 110 mph (Vult)
Kzt 1.00
Exposure B
Seismic
Design Category D
SDS 1.00
Response Factor 6.5
CS =0.154
Importance Factor 1.00
Soil
Allowable Bearing 1,500 psf
Copyright 2021, SEGA Engineers
SEGA Engineers
/ Structural & Civil Consulting Engineers
22939 SE 292nd PL (360) 986-1017
Black Diamond, WA 98010
LOADS
ROOF
DL
FLOOR
Roofing (Comp)
'/2" OSB
2 x @ 24"
Insulation
5/8" GWB
Misc.
LL Snow, Pf
Reduction, Cs
7/12 pitch = 30 deg
Total Roof Load
DL Flooring
314" Plywood
FT @ 24" o.c.
5/8" GWB
Misc.
LL Residential
Total Floor Load
DECKS
DL 2 x Decking
2x10@16"oc
Misc
LL Residential
Total Deck Load
WALLS
DL Siding
1/2" Plywood
2x6@16"oc
Insul
'/2" GWB
Project L2-3006
Job No. 14-011 By: GAT
Checked Date:02/12/24 Sht 2
3.5 psf
1.8
3.5
1.1
2.8
1.5
14.2 psf
25 psf (115% Load Duration)
0.00 (Ct = 1.1, other surfaces)
39.2 psf
0.5 psf
2.3
3.3
2.8
1.5
10.4 psf
40 psf
50.4 psf
4.3 psf
2.8
1.5
8.6
60 psf
68.6 psf
3.5
1.5 psf
1.7
0.6
2.2
9.5 psf
Copyright 2024, SEGA Engineers
SEGA Engineers / PROJECT
/ structural & Civil Consulting Engineers
JOB !30. fFIGURED BY
22934 SE 292nd Place r
Black Diamond, Washington 98010
(360) 885-10I7 CHECKED BY DATE 0�/ SHEFir OF
DIC
Copyright 2014, $EGA Engineers
SEGA En ineers
PROJECT
Strnctnral & Civil Consulting Engineers
JOB NO. _ur' FIGURED BY rT T
22939 SE 292nd Place
Black Diamond, Washington 98010 (360) 886-1017 CHECKED BY DATELSHEET ,/t OF
r-7c" f" �— ' U� 2_j�
�'Lorv►C v, -f- �1� �.++ . r T CA Fri
L-
(O,b
to
(w ?° S.r',s,a,)
w
f " G�
zo. 3rG�
f-1� — OIL
(f-L 1 ��
w
V/7-w Ito Lvtr
3'la�� 1r'I� Esc -<--
C'o �r
IJ
5%z }-i -J-S -.e---
0
q0k
Copyright 2014, SEGA Engineers
4
SEGA En ineers
PROJECTS 3p0 —3�p 300
Structural & Civil Consulting Engineers L�-Z9��? �� ? ~�
22439 SE 292nd Place JOB NO. pf FIGURED BY 614-r
Black Diamond, Washington 98010 CHECKED BY DATE Z� 7 SHEETOF
(360) 886-1017
L4v
w Zlt ���sr} Aldo SgOfl
M' (Z' -( j s e) ` 2 � (" / it,
of-E e C-rM A (:P# J�o'�
)b
P ` � 3^
v� 1t7k
of S
(LD z_ �') z
G% �1/u)
r i �� WG
(z } -t OVL Rd —
An C-n
-'/ Z -6--
Copyright 2014, SEGA Engineers
SEGA EngineersEngineenj PROJECT-Z C�]' _ icy — s auk 3
Structural & Civil Consulting Engineers
_ �' o
22939 SE 292nd Place 7OB NO.F'1GURED BY
-••_
Black Diamond, Washington 98010 CHECKED BY DATE illr(i� SHEET/ OF
(360) 886-1017
'
Ws
!Z S r 5�S •
'3
^' L LAC S�pSL) !od � �C �0?j? = WSPi-,
M-
31,z.
/) �, 76 ),/ o^%*j,+ 2 4 k-
7"iFCit-�w -e. 6m q--(�F - ftA(L
3
0
Q
Copyright 2014, SEGA Engineers
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place
Black Diamond, WA 98010
Project Typical Ftg
Job No. By: GAT
(360) 886-1017 —7
Checked Date: 12/03/15 Sht.
Square Footing Design Ftg 36 x 36
Design Parameters
fe = 2,500 psi Fy = 40,000 psi
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Loads:
Cal DL = 2.4 kip (Service Load)
Col LL = 9.6 kip (Service Load)
Floor LL =
0
psf
Overburden =
0.0 in
(120 pcf assumed)
Slab Thick. =
0.0 in
(150 pcf assumed)
Size_ and Footing Pressure
h =
8.0 in
qn =
1.40
ksf
Req'd Area = 8.57 ft^2
Try 2.95 ft x 2.95 ft
Factored Net Soil Pressure = 2.13 ksf
All. q = 1,500 psf
< -- Ftg. Thickness
< Min. Ftg. Size
(1.2D + 1.6L)
Check for Two -Way Shear
Avg d = 4.00 in
Vu = 16.76 kips
bo = 40.00 in (Critical Shear Perimeter)
Be = 1 (Long Side/Short Side of Column)
phi VC = 27.20 kips
Phi Vc > Vu OK
Check for One-Wav Shear
Vu =
5.598
kips
Phi Vo =
12.04
kips
Phi Ve
>
Vu
Design Reinforcement
Mu =
4.71
kip-ft
As =
0.51
in^2
a =
0.27
in
Phi Mn =
5.58
kip-ft
Phi Mn
>
Mu
AS min = 0.51 inA2
OK
OK
OK
Use (3) - # 4 bars EW _Reinforcement
0.59 inA2
Copyright 2015, SEGA Engineers
SEGA Engineers
Structural & Civil Consulting Engineers
22939 SE 292nd Place (360) 886-1017
Black Diamond, WA 98010
Project Typical Ftg
Job No. By: GAT
Checked Date: 12/03/15 Sht.
Square Footing Design Ftg 42 x 42
Design Parameters
f'o = 2,500 psi Fy = 40,000 psi All. q = 1,500 psf
b = 6.0 in - short side of column
d = 6.0 in - long side of column
Loads:
Col DL = 3.2 kip (Service Load)
Cal LL = 12.8 kip (Service Load)
Floor LL = 0 psf
Overburden = 0.0 in (120 pcf assumed)
Slab Thick. = 0.0 in (150 pcf assumed)
_Size and Footing Pressure
h = 8.0 in < Ftg. Thickness
qn = 1.40 ksf
Req'd Area = 11.43 ft"2
Try 3.40 ft x 3.40 ft E Min. Ftg. Size
Factored Net Soil Pressure = 2.13 ksf (1.21D + 1.6L)
Check for Two -Way Shear
Avg d = 4.00 in
Vu = 22.84 kips
bo = 40.00 in (Critical Shear Perimeter)
Be = 1 (Long Side/Short Side of Column)
Phi Vr = 27.20 kips
Phi VC > Vu OK
Check for One -Way Shear.
Vu = 8.079 kips
Phi Ve = 13.87 kips
Phi V, > Vu OK
Design Reinforcement
Mu = 7.61 kip-ft
As = 0.70 in"2
a = 0.32 in
Phi Mn = 7.62 kip-ft
Phi Mn > Mu OK
AS min = 0.59 in^2 OK
Use (4) - # 4 bars EW _Reinforcement
0.79 in
Copyright 2015, SEGA Engineers
SEGA Engineers Project L2-3004 /- 30co(.a /-30o7
5tractural & Civil Consulting Engineers
Job No. 14-011 By: GAT
22939 SE 292nd PL (360) 886-1017
Black Diamond, WA 98010 Checked Date: 03/31/14 Sht. I
LATERAL. LOADS - (Alternate ASD)
SEISMIC
Maximum Base Shear, V = F SDs W Eq. 12.14-11
R
where,
F = 1.1 Two -Story Building
SAS = 1.00 SS = 1.5 Fa = 1.00 (Table 11.4-1, SS > 1.25)
R = 6.5 Table 12.14-1
W = Seismic Weight
For W:
Wroe (34ft) {55ft) (16psf)+ (2) (34ft+ 55ft) (4.0ft) (9.5psf) = 37kips
Wnoor = (40 ft) (54 ft) (14 psf) + (2) (40 ft + 54 ft) ( 8.5 ft) ( 9.5 psf) = 45 Kips
Wtocai = 82 kips
Design Base Shear, V =
(.169)
(82 kip) =
13.9 kip
E =
13.9 kip =
9.9 kip
1.4
WIND
Design Wind Pressure, P. = N
Kr PS30
Eq. 28.6-1, Sect. 28.6.3
where,
= 1.00
0 -15 ft
Exposure B
Figure 28.6-1
= 1.00
20 ft
= 1.00
25 ft
= 1.00
30 ft
K,, = 1.00
Section 26.8
pap = 17.7 psf
110 mph
Figure 28.6-1
(ASD)
Pp. 15 = (1.00)
(1.00)
(17.7 psf) =
17.70 psf
{ x 0.6 =
10.62 psf)
P20 = (1.00)
(1.00)
(17.7 psf) =
17.70 psf
(x 0.6 =
10.62 psf)
P25 = (1.00)
(1.00)
(17.7 psf) =
17.70 psf
(x 0.6 =
10.62 psf)
Pao = (1.00)
(1.00)
(17.7 psf) =
17.70 psf
{ x 0.6 =
10.62 psf)
Design Base Shear: (Wind)
Vfro= (40ft)
(10ft)
(17.7psf) +
(40 ft)
(5ft)
(17.7psf)
+ (34ft)
(5ft)
(17.7 psf) +
(34ft)
(5ft)
(17.7psf) =16.6x0.6
10.0kips
Vsy.= (60ft)
{10ft)
(17.7 psf) +
(57ft)
(5ft)
(17.7psf)
+ (50ft)
(5ft)
(17.7 psf) +
(19ft)
(5ft)
(17.7psf) =21.8x0.6
=13.1 kips
Therefore,
Wind Loads Govern for Lateral Design - Front/Back
Wind Loads Govern for Lateral Design - Side/Side
Copyright 2014, SEGA Engineers
SEGA En ineers
Structural & Civil Consulting Engineers PROJECT L Z - 300
22939 SE 242nd Place JOB NO. � W-Lo( j FIGURED BY �
Black Diamond, Washington 98010
(360) 886-1017 CHECKED BY DATE f ��'. SHEET i� OF ._
���•`t1� 1�� �'r 3'�-jj ` = 3 3�
Ir�L7103 41-
c~nsAZIS1
O
r
D
17rry 4S.-P}66v�5
zA
I
I
r
RCjaj
0
A
k
�'0'A` 4.n, 8 )
Copyright 2014, SEGA Engineers
SEGA Engineerbs_j �_
PROJECT 2 - c70I i2LP
Structural & Civil Consulting Engineers •• �••-
�p 1
22939 SE 292rad Place JOB NO. FIGURED BY „..
Black Diamond, Washington 98010 or
CHECKED BY DATE�//�4 SHEET+a
(360) 886-1017
s' �1
R�Vf �+ C--� Cy O) 1. P
7,&'4-grj`+ 4V - ZOr4��
fi:0Q0-
pI'll, 00
Sc�3S�MlIZI � �Zc��
j -':4 �
` 3, n (.,C�X3�
D
L' Sl it.. -
�fL U�� 3,Co�'�# 3 )(jot )l/a,��'���, �y3
At
11.31
M
k
Y F
Copyright 2014, SEGA Engineers
Y F
Copyright 2014, SEGA Engineers
SEGA Engineers PROJECT Z
Structural & Civil Consulting Engineers
JOB NO. rp FIGURED BY �T 22939 SE 292nd Place 11
Black Diamond, Washington 98010 CHECKED BY DATE f�,,/
(360) 886-1017 // Z SHEET [&F
Copyright 2014, SEGA Engineer _ .
S IE Engineers / PROJECT
Structural & Civil Consulting Engineers
22939 SE 292nd Place • Black Diamond, Washington 98010 JOB NO.
(36M 886-1017 • FAX 886-1016
CHECKED BY
L 2 - 3006
4 - ®11 FIGURED BY �;4T
DATE 02/12/24 SHEET 13 OF 13
�
ILA /j�\ jj�� //�\ (I�.� //�\
SI EA UJAL— KEY FLAN A�77
e
•
�LSTA24 - SEAM
\/
---------------
To roP PLATE.
(TTP OF 2�
UFj5QFT
A =
_ - __
D5C2 - GIRDER
TO 10P PLATE
�4
G C
i
i
4
n� LSTA36 - H R d SILL
.(D __ 7pf
1
L67A36 - HDR d SILL - cA, s (1TP. 2 PL S)
TO 3x BLOCKMG.
(TYP. 2 PEACE5)
2
LSTA36 - HDR ! SILL
_ - BEAM TO 3. BLOCKMG.
LTO TOP PLATE (TYP. 2 PLACES)
/'Lgoo'
3
G
A-L5TA24 - BEA9
G
TO TOP PLATE
MAIN FLOOR
e
HT520-BEAR
G
A = 1,362 SQ FT TO TOP PLATE
LSTA30 - TOP PLATE)
TO 3. BLOCKMG
LSTA30 -BEAM
rO TOP PLATE.
(TYP OF 2)
A = 640 5Q FT
0
0
GOFYRIGHT 2024, SEGA ENGINEERS
SHEAR WALL SCHEDULESHEAR WALL SCHEDULESHEAR WALL SCHEDULE
Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4)Mark Minimum Sheathing Anchor Remarks (4)
Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3)Sheathing (1)Nailing (1)Bolts (3)
1/" OSB or 5/" @ 60" o.c.A 1/2" OSB or 8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA1/2" OSB or 8d @ 6" o.c.5/8" @ 60" o.c.Qall = 230 plfA/2" OSB or 8d @ 6" o.c./8" @ 60" o.c.Qall = 230 plf
CDXCDXCDX
B 1/" OSB or 8d @ 4" o.c.5/" @ 32" o.c.Qall = 350 plfB1/2" OSB or 8d @ 4" o.c.5/8" @ 32" o.c.Qall = 350 plfB/2" OSB or 8d @ 4" o.c./8" @ 32" o.c.Qall = 350 plf
CDXCDXCDX
1 5C1/2" OSB or 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC1/2" OSB or 8d @ 3" o.c.5/8" @ 16" o.c.Qall = 450 plfC/2" OSB or 8d @ 3" o.c./8" @ 16" o.c.Qall = 450 plf
CDX Use minimum 3x studsCDXUse minimum 3x studsCDXUse minimum 3x studs
at abutting panel edgesat abutting panel edgesat abutting panel edges
and stagger nails.and stagger nails.and stagger nails.
R See Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for ConstructionRSee Detail 12/S2.0 for Construction
Notes:Notes:Notes:
1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing
Notes:
1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing1)All walls designated " " are shear walls. Exterior walls shall be sheathed with rated sheathing
(24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at (24/0, OSB or CDX) and nailed at all panel edges (Blocked) per schedule (uno). Nailing at
intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.intermediate framing to be at 12" oc. Nailing not called out shall be per IBC Table 2304.10.1.
2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear 2)Holdowns and other framing hardware by Simpson or equal to be used per plan. Ends of shear
walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).walls shall use double studs minimum (UNO).
3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"3)Use minimum of (2) bolts per sill piece with one bolt located not more than 12" nor less than 5"
from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.from each end of the piece. Embed bolts a minimum of 7" into concrete.
4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with4)Allowable loads are permitted to be increased by 40% for wind design in accordance with
AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.AF&PA SDPWS Table 4.3A.