Fire Sprinkler Drawings-Tahoma Terra Storage Bldg A REV1TOPOGRAPHIC NOTE: THE EXISTING TOPOGRAPHIC DATA SHOWN ON THESE DRAWINGS HAS BEEN PREPARED, IN PART, BASED UPON INFORMATION FURNISHED BY OTHERS. WHILE THIS INFORMATION IS BELIEVED TO BE RELIABLE, HGP CANNOT ENSURE ITS ACCURACY AND THUS IS NOT RESPONSIBLE FOR THE ACCURACY OF THAT INFORMATION OR FOR ANY ERRORS OR OMISSIONS WHICH MAY HAVE BEEN INCORPORATED INTO THESE DRAWINGS AS A RESULT. PROJECT INFORMATION: COMMERCIAL SELF -STORAGE FACILITY WITH 12 BUILDINGS. BUILDINGS A, B, C, D, H, J, K, L ARE FULLY SPRINKLERED BUILDINGS E, F, G, M ARE NON-SPRINKLERED. FLOW TEST INFORMATION STATIC 55 PSI RESIDUAL 42 PSI z T m FLOWING 3227 GPM LOCATION Longmire St & Tahoma Blvd 8" WATERMAIN MODEL ID530 p DATE OF TEST # I� BY WHO CITY OF- YELM 'FFA Er STO UNIT (TYP) /rrrrrrirrsrirrirrir,�irirr/rr� � �rrirrirririoiorri�%/riririorrirrirrriririrrirri,sir/����riririorrirrirrriririi r airirrririorirr/% � 6 � - ® '� ® p/ririrrirririr .rvrv.� �.�riorirririarioririorrriririrrririrrrirririrririoriaia � �irirrirrirrirrrir.� � .�� U/r 6 � � � �rrircr�irrirrirrr/ SPRINKLER FIRE SPRINKLER ROOM RISER ROOM o®M I ® o • / - FIRE SPRINKLER011 IIIIIIIIIII IIIIIIII` / ® RISER ROOM i O i lolj° uulll BLDG C e BLDG D BLDG H _ BLDG J I/IIIIIIIIIII i IIIII O FIRE SPRINKLER C RISER ROOM D 22 /IIIIIIIII II IIIIIIIII FIR R SERI Roots �Illlljlll �rrrra sirrir� far ri ao/a I I 6 firiiirrirrirrriririrrirriiiririiiiiriririiiiirirririrrririrre I //riiiririiiiiriririiiiirirririarriririarrirririiiiid/e • / IIIII IIIII' �/rirrririrrirriiiriririiiiiririiiiirriririrrirrirrirrirriririiria�riiiiirirrirrairirirrirrirririiiiiiiiririiiiirirr/rrairirir� oiirirririiiiiiiiririiiiirirrrraioiririrrrirririiiiiiiiririiiiiririiirraiaiririavrrraimYiiriririiiiiririiiiiri /rise-fiiririrroirirririiiiiririiiiiiiirirrriarrirriaririrririiiiiririiiiiiiiririiirriarirriaririrro I I O C CITY OF YELM VERTICAL DATUM MERIDIAN HORIZONTAL DATUM PLAT OF TAHOMA TERRA PHASE 2, DIVISION 2 UNDER NGVD 29 PER T.C.H.P.N. #1252BM BASED ON THRUSTON COUNTY HIGH PRECISION AUDITOR'S FILE NO. 4620459 NETWORK CONTROL POINT NO. 125213M, 3" BRASS CAP AT THE NW CORNER OF THE INTERSECTION OF YELM HIGHWAY AND KILLION ROAD ELEVATION = 246.39 (NGVD) FIRE HYDRANT (TYP) a/r//—///r/r////o////air/r///ar/r/r _ x 1 IIII IIIII - O p�`' ®J L _ BLDG 'B' III IIIIIIIIIIII oil III � I e - I I III ;/slaw.rrirririr,.rrrrrr.�iariarriorirrirrirmo�mi� mrm.���,y�����,y�,y�����,y......,�.,�..... p../ 7/orirrr .rr.aary.r�rriririrrirrirrirrirriririrrrir.rriririrr/cr.�..r.�.r.�.rrc�..rr..rvr/rraririrircraaa+rr/rririrrirrirrriri.�iairirrririrrrirrirrrrrrirrririricrrrrrririorririorrri it I FI >m �j e j RSE SPRINKLER / ­ BLDG'K' RISER ROOM � � RIER ROOM x BLDG'L' � VVIWII� RISER ROOMLER � � / 8 � @ 6 �I I/rriririiiiirirriririrrririrra� �Qao�.�� 6rirrriaeir// raeirrririr/ /ririiiiiririi/ �rirririrrr/� /irrirrirri/a rrirr rr /alai /rr /rrirriiirir/ Gririirrrrr 6irririrrri/< iirirror s � _- � BLDG 'A' _ 0 / - sir/6. I si�ra e �yy _ — - s - E 4� 48 t .T I R o i x 50 25 0 50 100 SCALE: 1"=50' LEGEND NEW WATER MAIN NEW BUILDING FIRE LINE NEW WATER SERVICE LINE H NEW WATER VALVE NEW HYDRANT e NEW PIV NEW FDC pip NEW TEE NEW BEND W/ BLOCKING NEW REDUCER NEW WATER METER I 0 NEW RPBA IRRIGATION METER (TYP) 4" SCH 40 CONDUIT W/ TRACER WIRE FOR IRRIGATION CROSSING (TYP) o / ® I CONNECT TO EXISTING — - 10" WATERMAIN STUB IC EXISTING 10 rFA a W A_ O o p /6� = WATERMAIN STUB si \ \ F \w \ I,y \RW \ R W " MilR �- - U,�i D� - _ _ - - •_ ___ - - _ _ - --` _ - - _ _- --_- - _ - - _ - -- '_ - - - - - _ - . _ _ -_ -_ -_ - -_ _ _ _ _ - _ - - - - - EXISTING 6" EXISTING 10" o' WATERMAIN STUBw WATERMAIN O -5r— STUB els VV p - - - - - - - - ' - _ _ -_ STEA \ ---"W RW RW _� U (j) . I n (_ I> e. • ¢' - - - - - - - - - RW RW RW = ' (!7 : � P Cn 1> g a � � . e \ O IN W RW RW S 2 =(n CO W RW RW RW RW RW 4 = _ . CP ,D - \. O I / STEP -W RW MN _ - -- - - - All / w w w W w Mb U 1 _ _ + O U) Dxvl / s a w W M 25480 STE EXISTING FIRE STEP TAHOMA BLVD SE _ �. `~ HYDRANT (TYP) FDC TYP —STEP CONNECT TO EXISTING (TYP) I 10" WATERMAIN STUB — — — _ _ >0p;�o\M _/ / vJ \ \ I WATER METER PIV (TYP) ( ) 8WATERMAIN TYP " / / FIRE HYDRANT (TYP) � \d31 � 41 D.I. FIRE SPRINKLER LINE(TYP)MULTI-FAMILY \ S Q f I (TYP) BUILDING (TYP) \ / 3 A \ M I 6sue_ Wmw e C� ° < OVERALL SITE PLAN SCALE: 1 " = W-0" 0 25' 50' 100, IPROJECT INORTH NOTE: THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE LOCATION AND PROTECTION OF ALL EXISTING UTILITIES. THE CONTRACTOR SHALL VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION BY CALLING THE UNDERGROUND LOCATE LINE AT 811 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION. THIS DRAWING DOES NOT REPRESENT A RECORD DOCUMENT b F \ \ i • II Z III Qs = Nm W. z.l� � 3d d s d I i m� m a \ A \ , as UNLESS CERTIFIED BY HATTON GODAT PANTIER. \ � WATER SYSTEM MAP ANY ALTERATIONS TO THE DESIGN SHOWN HEREON MUST BE 1 EILI EIL1300 EILI REVIEWED AND APPROVED BY HATTON GODAT PANTIER. wO�cn omW91 \ j I�\I� I CONNECT TO EXISTING 6" WATERMAIN STUB \ FIRE HYDRANT (TYP) II I I II I -- ----- FDC (TYP) I - PIV (TYP) 8" WATERMAIN (TYP) I I I I I I� I WA STATE LEVEL U INSTALLATION COMPANY INFO: Hoffman Construction, Inc. 159 16th Street East, Suite 101 Pacific, WA 98047-5005 PHONE: 360-825-9797 Randy Hoffman Certification #3966-0899-D Certification Level: U Contractor # HOFFMC1931 D9 CV u, CD O S (O cc) Cr w r- ^ cc) 0' Z Q CV N LLi > 3 c o Q _ 0— zQ� 0 Q= a C)) CV LL U LL U C] LU Q < Q m O 0 p� U) Q Q. c Q LU 3 L_ � tirn Y 0 W 0O rn LO z CO E WILL Q a 22�� sC) LU a N 0 0 �_ z o Q Q W LL a H H } "' o � �p -U O Y O o } cO 00 R Of a ¢ c� F Q c� U U 5W y U A G. E- z Zo 0 H rn w W w x A W U s CQ w o F C\2 Ln 1-1CQ U a U) U N (Y IZ co z Z O M o w 0 Q E.. c7 a 00 U LL � LU c a C� U' rn N o Q co Z m O M U a C\I Q U X N W } > _U U m Q } LO a N 0 } a a s 0- U U w U) O � LLJ Z Ld p H Q C) d m N Z O CL �0 2 a I o as as a a) Q a �D �D IL. " 'p an a x x Q" E- w "' r4 td E- E- w Z 04o -d w w z p x L) A w� x CQ't P,it x w w Om ao 0 I__I WA. STATE LEVEL 3 STAMP Expires f WASHINGTON STATE oEC37, 2a CERTIFICATE OF COMPETENCY FIRE SPRINKLER SYSTEMS � Joseph G.Faulkner 9491-0699-CEG Level 5prinx Fire Protection, Inc. PRINFP011L i 5/24/2024; �a e��� I SCALE: 1" = 40'-0" Project No. 24-012CM Sheet Title: OVERALL SITE PLAN Sheet Number: FP- 1 0 • File:Tahoma Terra Storage Site FP.dwg 170 LF 8" PVC WATER 13+28.57, 2.50' RT (W) INSTALL 1 - 8" 45' BEND (MJxFL) 1 - 8" TEE (FL) 1 - 8" ADAPTER (FLxMJ) BLOCKING INSTALL 1 - 4"x 21/2"x2'/2" FDC (CONTRACTOR TO INSTALL 1 - 8"x4" TEE CLEARLY LABEL "BLDG A") (MJ) 17 LF 4" D.I. FIRELINE TO BLDG A BLOCKING 13+34.58, 79.00' LT (W) _ INSTALL 1 - HYDT ASSEMBLY (STD DRAWING 4-7) BLOCKING 30 LF 8" PVC WATER 13+34.58, 51.81' LT (W) INSTALL 1 - 8"x4" TEE (MJ) 1- 4" 45 DEG ELL (MJ) 65 LF 4" D.I. FIRELINE TO BLDG B BLOCKING 12+27.55, 39.00' RT (W) INSTALL 1 - 1-1/2" WATER METER / �P5 (COFFEE SHOP) 1 - RPBA \,\ 7 LF 8" Pvc BLDG 'A' `\ WATER \ 55 LF 4" DI FDC LINE \\ O FROM BLDG A RISER COFFEE ROOM TO FDC ? SHOP \\ F.D.C. LINE FLANGE TO 1'-0" AFF \ FIRE SPRINKLER RISER ROOM \\\ FIRE SPRINKLER WET SYSTEM 4" FLANGES TO 1'-0" AFF VAN ----- - -- 0 8.1 Tz DCDA LOCATED INSIDE BUILDING / 8" WATER MAIN 13+00 OF BI LINE SPRINKLER I R ROOM I I I ANGE TO 1'-0" AFF _ BLDG 'B' SPRINKLER SYSTEM w 11+74.72, 2.50' RT (W) INSTALL Q1 - 8"x4" TEE (MJxFL) w 1 - 4" GV (FLxMJ) >_ 31 LF 4" D.I. PIPE BLOCKING 18 LF 8" PVC QWATER 07 Lu11+24.96, 2.50' RT (W) (� INSTALL w 1 - 8" 11-1/4' BEND (MJ) C6 BLOCKING UJ(STD DWG 4-13) 0 Z ^ CID �( 'ZX 12+00 �000\ SEE FIRE 117 LF 8" PVC J I I \ PROTECTION PLANS WATER / 12+52.23, 18.00' LT (W) INSTALL N 594055.33 E 1108785.12 1 - 5/8" WATER METER INSTALL 1 - 4"x 21/2"x21/2" FDC (RETAIL BLDG) (CONTRACTOR TO CLEARLY 1 - RPBA LABEL "BLDG B") FIRE SPRINKLER LINE DCDA 12+53.22, 26.00' LT (W) J INSIDE BUILDING INSTALL (SEE MECHANICAL PLANS, TYP) 1 - 5/8" WATER IRRIGATION 11+92.97, 16.83' LT (W) w/ DCVA/BACKFLOW PREVENTER INSTALL TO BE INSTALLED BY LANDSCAPE CONTRACTOR 1-FDC (SEE LANDSCAPE PLAN) (CONTRACTOR TO CLEARLY LABEL BLDG ADDRESS) BUILDING "A" FIRE PROTECTION SITE PLAN V SCALE: 1 " = 30'-019 PROJECT NORTH 0 15' 30' 60' BLDG 'A' NN N \ F.D.C. LINE \ 4" FLANGE TO 1'-0" AFF FIRE SPRINKLER \ RISER ROOM FIRE SPRINKLER WET SYSTEM SPRK RM 4" FLANGES TO 1'-0" AFF 6,. tv a 8" WATER MAIN 1_I_L Q F.D.C. BUILDING 'A' N Ix COFFEE , SHOP �BLDG "A" ENLARGED FIRE PROTECTION SITE PLAN (aV SCALE: 1 if = 10'-0" PROJECT NORTH 0 5' 10, 20' 0 D 8" WATER MAIN 11+05.64, 6.22' RT (W)= 10+06.49, 1.59' RT (E) INSTALL 1 - 8" TEE (FL) 1 - 8" ADAPTER (FLxMJ) 1 - 8" GV (FLxMJ) 1 - 8" GV (FL) 1 - 8" 22-1/20 BEND (FL) 1 - 8" 11-1/4' BEND (FLxMJ) BLOCKING EXISTING FIRE HYDRANT (TYP) \ 3 o Via b ��a _t C/L INT 10+00.0 11+03.2 (W) N� TORAGE FICE 52 LF 8" PVC WATER �11+78.95, 2.50' RT (W) INSTALL 1- 8"x6" TEE (MJxFL) 1- 6" GV (FLxRMJ) (STD DWG 4-11) 1-HYDT ASSEMBLY (STD DWG 4-7) (11+78.95, 18.50'RT) BLOCKING —11+74.72, 31.39' LT (W) INSTALL 1 - 4" GV w/ POST INDICATOR BLOCKING I 36 LF 8" PVC WATER 11+31.91, 41.46' LT (W) INSTALL 1 - 5/8" WATER METER (STORAGE OFFICE) 1 - RPBA APPROXIMATE LOCATION OF �0P EXISTING 10" WATERMAIN QP EXISTING 10" WATER STUB CITY OF YELM VERTICAL DATUM MERIDIAN HORIZONTAL DATUM PLAT OF TAHOMA TERRA PHASE 2, DIVISION 2 UNDER NGVD 29 PER T.C.H.P.N. #1252BM BASED ON THRUSTON COUNTY HIGH PRECISION AUDITOR'S FILE NO. 4620459 NETWORK CONTROL POINT NO. 1252BM, 3" BRASS CAP AT THE NW CORNER OF THE INTERSECTION OF YELM HIGHWAY AND KILLION ROAD ELEVATION = 246.39 (NGVD) � / a RW L INT 10 00,00 (W)= RW D N 90867.32 V, RW RW E 110 11 C E 5 / S� J - RE ' M1 'NG N 5ZE \� O \ \U3 S 10+69.51, 5.50' RT �m (W) REMOVE EXISTING CAP & BLOWOFF INSTALL 1 - 10"x8" REDUCER CONTRACTOR TO FIELD VERIFY BLOCKING LOCATION, DEPTH, SIZE & FITTINGS REQUIRED PRIOR TO CONSTRUCTION. 4" SCH 40 CONDUIT W/ TRACER WIRE FOR IRRIGATION CROSSING (TYP) 10+73.97, 17.00' LT (W) INSTALL 1 - 5/8" WATER IRRIGATION w/ DCVA/BACKFLOW PREVENTER TO BE INSTALLED BY LANDSCAPE CONTRACTOR (SEE LANDSCAPE PLAN) 4"x 2-1/2% FIRE DEPARTMENT INLET CONNECTION 36"-42" SINGLE STRAP SADDLE FORD FS101 OR APPROVED EQUAL WRAP GALVANIZED PIPE WITH 3M TAPE OR EQUAL FROM FLANGE TO 6" ABOVE GROUND LEVEL THRUST BLOCK 30 15 0 30 60 SCALE: 1" = 30' NORTH T I I > U) w —1 �< I� 0 O�GM�RF / N.T.S. KEY MAP FDC IDENTIFICATION PLATE _RAISED LETTERS "AUTO SPRK" & BUILDING ADDRESS NUMBERS 4" GALVANIZED PIPE - 18" X 18" X 8" CONC. BLOCK OPTIONAL SUPPORT GRADE /- IF BALL DRIP IS NEEDED INSTALL 1-1/2" WASHED ROCK TO AID DRAINAGE INSTALL A 3/4" GRAVITY BALL DRIP AMERICAN FLOW OR APPROVED EQUAL AND A 3/4" BRASS 90- ELL ' BELOW THE FREEZE LINE IF DDCVA IS IN THE ✓ BUILDING AND ABOVE THE FDC �D.I. FL X MJ 90' BEND DI PIPE TO BUILDING, SEE APPROVED CIVIL OR SPRINKLER SITE PLAN MEGAPLUG RESTRAINED JOINT 13 FIRE DEPARTMENT CONNECTION (FDC) C7 NTS UNDERGROUND NOTES: 1) ALL UNDERGROUND BY OTHERS. Contractor to be State Licensed and Certified to install Underground Piping Per WAC 212-80. 2) Pipe type and class to meet Local Jurisdiction Approval. 3) All underground piping shall have a Minimum 3'-0" Bury. 4) All underground piping shall be U.L. Listed and/or FM Approved for Fire Protection. 5) All underground piping shall be rodded and/or blocked in accordance with the specifications and NFPA 24. 6) All underground piping shall be Hydrostatically tested at not less than 200 PSI for two hours in accordance with NFPA 24. 7) All underground piping shall be flushed in accordance with NFPA 24. Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets. 4" - 390 GPM 1011 - 21400 GPM 6" - 880 GPM 12" - 3,520 GPM 8" - 1,560 GPM 8) All underground installation and testing to be witnessed by the local authority having jurisdiction. 9) Where pipes passes through holes in foundations, walls, or floors, the holes or sleeve shall be sized 4 in. larger than the supply pipe size on pipes sized 4" or larger. 4" GRV O 900 ELBOW 411 TO SYSTEM " RISER MANIFOLD W/: VERB I �OR (1) DRAIN AND TEST (2) FLOW SWITCH EXTERIOR 6" 24V (3) WATER GAUGE AC ALARM BELL =v 0 (4) SIGNS ON BODY `^ (5) PRV- KIT 4" I LAD oox *Pressure Relief 0 10" Valve installed on a ' System Riser -or- at Inspectors Test 4" DERINGER 30 DOUBLE CHECK Valve. See Detail 'I - DETECTOR ASSEMBLY INDOOR ®• � VERTICAL INSTALLATION w/(2) = BOR "` BUTTERFLY TAMPER SWITCHES Q 2%" ANGLE HOSE ` o W VALVE FOR FORWARD FLOW W .g TESTING OF DCVA. 4" GROOVED KMS CHECK VALVE rrw v = _ 4" FLANGE x GROOVED 4' FD.0 LINE ADAPTER _ _ MJ ELBOW 4" SJPPLY LINE Z3 M/ResBaO rained Q wrRestrained L E� 411 Flange Adapter Flange Adapters CTES)�)IRE LINE BY OTHERS THRUST BLOCK TH%ST BLOCK UNDERGROUND STUB U P (PER NFPA 24) (PER NFPA 24) THE FIRE 5UPPLY LINE 4 FD.C. LINE RISER DETAIL INSTALLED BY OTHERS. N.T.S. I -RD c� Lo o CD S c) co a w ^ 23 -- M co co Nco co �c4M Co MINIMUM Q >3 � a oL� O Z�r L _b Q Q = N a r-(D W f r1 N Z c) O FLANGE 1'-0" AFF � � c) M IL ILL. � PIPE SLEEVE THRU SLAB SLAB LEVEL EXT. WALL MAINTAIN 2" GAP AROUND m (D � FIRE LINE W Z_ W >� m O o o � 1 I_I=1 I I-1 I I—III-1 I I —I 11=1 IT=1 J=J=ll III- a � Q Q. c 3 i — o CONC. FOOTING --''- o Q> J I- W an Lu ATR & TIE BOLTS OR- MEGA -LUG ! W O) LID Y Z RETAINERS TO RESTRAIN , U.G. PIPING H O COQ 0-)00 LL VERTICAL PIPING THRUST BLOCK (PER C94E OR SLEEVE Q Q >> > W (n cn r �1 O T FOOTING LU o NFPA 24) IF REQUIRED 1 z O Q Q W ILL. a UNDERGROUND STUB UPW/ROD ~ ~ } co LO N cu U Y p �l a ¢ ZZ U U c) F ai FLOW TEST INFORMATION STATIC 55 PSI RESIDUAL 42 PSI FLOWING 3227 GPM LOCATION Longmire St & Tahoma Blvd DATE OF TEST MODEL ID#530 BY WHO CITY OF YELM Ga rK 3r rnpu _ %^ �lpuntaln 'Tibw ME68�+4r ' 91c w.ry 4f '+y 'Tty Con ulry Commuidtles �S[eele r3irr•' - Itifrlingk-n Gr"-n B8Q Car:lr•ar.y tosr ■ ;A Sr 4 Celmron Area SE he Lnfl Lamar cs9 Carc an d1147Gt1iRipaio r Gave and truck Regalr o-Swd Pea' Yalm HI Schaal Q `, _ rearru � T YEIm YBlerinary MCSpilal r �. 4 YAl \ L I�l1Pr19 YnllaflFl r ClaruI E" TT ` Centre at Yehm 9 SIT •�_;. Gee Gee s Q�dting Yeim MrGtlle SG t ..I. S1ace l Gmgan. imp MCDGnalds gk s # `t... + ; �SArnndlglry 1AInlalufg '� lti �z• I# Ap Ic01 Puddles s N(MnA,e S ~ Vis and Pas Fvmly Dhei9 Tat-p a Terra 6Y Tahorm Val l r SCLFKlbuA1 H9meS y, .� ulC Gnif Cnuf � { Velm City Park peel6 PtLo 0atoft a�rw 3Rlashflw fii YN JIif Ay Oaks A w"Ir rews . Hk�uetr . Wer�ldri 'Pill& M!eedom SCoepera ' W Brick PaYer5 VICINITY MAP N.T.S. WA STATE LEVEL U INSTALLATION COMPANY INFO: Hoffman Construction, Inc. 159 16th Street East, Suite 101 Pacific, WA 98047-5005 PHONE: 360-825-9797 Randy Hoffman Certification #3966-0899-D Certification Level: U Contractor # HOFFMC1931 D9 CIO b A w Cn Z Zo o� � w W w x 1 A G= A w s P4 w o E-F A CQ 1-1 in U a Cn U N � W ' M Z Z O M W Q E.. c7 W co U U_ W co C� 00 N 0 CD Q C) Z m O M (aj Q U X N W } > LL J LL (_n U m Q } LO a N O } 0- 0- 0- 0- U U w u) O LLJI w c ~ Q U a- o N a Z OS a_ C0 L) C) p o f>~ a o a) Q � O 'a � Cr � s; Q" a an a M r° w "' tdE- �W� Z i o n w w z '� � p x �' U A 2 124 W> �+ x W 4D a a,a,a� � a O m � o I__I WA. STATE LEVEL 3 STAMP Expires WASHINGTON STATE a - DEC 31, 24 CERTIFICATE OF COMPETENCY FIRE SPRINKLER SYSTEMS Joseph G. Faulkner 9491-0699-CEG Level Sprinx Fire Protection, Inc. PRINFP011L 5 24 202 ------ g---r---------- �--e--- N SCALE: 1" = 40'-0" Project No. 24-012CM Sheet Title: BLDG "A" Sheet Number: FP- 1 1 • File:Tahoma Terra Storage Site FP RB 3 L4 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 SL O P E FB 1 FB1 RB 1 RB 1 SLOPE SLOPE RB 1 RB 1 SLOPE SLOPE RB 1 RB 1 SLOPE SLOPE RB 1 RB 1 RB 1 RB 1 S L O P E RB 1 RB 1 RB 1 RB 1 RB 1 RB 1 RI D G E RB 1 RI D G E RI D G E RIDGE RIDGE H1 RID G E ° ° RIDGERIDGE +11'-4"+11'-4" Co r p o r a t i o n Sp r i n k l e r A F i r e Fa x 2 5 3 . 8 5 3 . 5 8 9 0 Ph o n e 2 5 3 . 8 5 3 . 7 7 8 0 27 0 9 J A H N A V E , N W , S U I T E H 2 Gi g H a r b o r , W A . 9 8 3 3 5 - 1 7 3 5 Co n t . L i c . # S P R I N F P 0 1 1 L S FI R E S P R I N K L E R D R A W I N G SCALE: 1/8" = 1'-0" WA. STATE LEVEL 3 STAMP File:Tahoma Terra Storage Bldg A FP.dwg TA H O M A T E R R A S T O R A G E B U I L D I N G " A " TA H O M A B O U L E V A R D YE L M , W A 9 8 5 9 7 05 / 1 0 / 2 0 2 4 PA C I F I C S T O R A G E P A R T N E R S , L L C P. O . B O X 7 3 7 9 0 PU Y A L L U P , W A 9 8 3 7 3 PA P CI T Y O F Y E L M B L D G / F I R E O F F I C I A L (3 6 0 ) 3 3 9 - 2 0 9 5 BW / J G F FP-2.0 BLDG "A" Sheet Number: Sheet Title: Project No.24-012CM SCALE: 1/8" = 1'-0"0 16'8' PROJECT NORTH BUILDING "A" 1ST FLOOR FIRE SPRINKLER PLAN 4' (2 5 3 ) 2 2 3 - 7 4 3 2 CH R I S V A C C A R O TYCO TY-3131 TY-FRB, QR K=5.6, 1/2" NPT, (55,6 mm) 2-3/16" BRASS UPRIGHT ºF STEEL Z-PURLIN MAIN HANGER ROD TRAPEZE NTS H32S TRAPEZE PIPE, SIZED ALL-THREAD ROD, SIZED PER NFPA #13 AND NUTS (TYPICAL) PER NFPA #13 STEEL SWDR 1" ADJUSTABLE RING HANGER SAMMY SCREW SIDEWINDER FIG. 200 HANGER DETAIL PER NFPA #13 ALL-THREAD ROD, SIZED PIPE RING SAMMY STEEL SIDEWINDER SWDR 1" W/NUT, OR EQUAL. 4"∅ MAX BRANCH LINE METAL ROOF DECK 3/8"Ø x 0-8" ALL THREADED ROD 'Z' PURLIN Notes:______________________________________________________________________________________________________________________________________________________________________________ 1. SYSTEM TYPE: WET SYSTEM THROUGHOUT STORAGE BUILDINGS A, B, C, D, H, J, K, L. BUILDINGS ARE CONSTRUCTED OF ALL NON-COMBUSTIBLE TYPE V-B CONSTRUCTION MATERIALS. NO VOID SPACES ABOVE CEILINGS THAT WILL REQUIRE SPRINKLER PROTECTION. SPRINKLER SYSTEM DESIGNED AND INSTALLED PER NFPA-13, ORDINARY HAZARD GROUP 2 OCCUPANCY THROUGHOUT EACH BUILDING. NO HIGH PILE STORAGE, FLAMMABLE LIQUIDS OR HIGHLY COMBUSTIBLE MATERIAL STORED ON FACILITY. PROPOSAL BASED ON PROVIDING A FIRE SPRINKLER HEAD IN EACH STORAGE UNIT. OWNER MUST MAINTAIN STORAGE HEIGHTS TO 18” BELOW FIRE SPRINKLER HEAD DEFLECTORS. 2. CONSTRUCTION TYPE: V-B NON-COMBUSTIBLE, UNOBSTRUCTED. 3. SPRINKLER SYSTEM DESIGNED, INSTALLED, BRACED AND TESTED PER NFPA-13 (2016). 4. ALL MATERIAL SHALL BE NEW AND U.L. LISTED AND F.M. APPROVED. 5. IN LOCALITIES SUBJECT TO FREEZING CONDITIONS, IT IS THE CONTRACTORS & OWNERS RESPONSIBILITY TO INSULATE WET SYSTEMS PROPERLY & TO PROVIDE HEAT THROUGHOUT THE WET PIPE SPRINKLER AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE AND OTHER TYPES OF VALVE CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. 6. SPRINX FIRE PROTECTION SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM OR ANY APPURTENANCES THEREOF. SPRINX FIRE PROTECTION STARTS AT A 6" FLANGE CONNECTION 1'-0" AFF. 7. ALL ELECTRICAL, PAINTING, FURRING, CUTTING OR PATCHING TO BE BY OTHERS. 8. PIPE SIZING PER NFPA-13, SYSTEM HYDRAULICALLY CALCULATED. 9. EARTHQUAKE BRACING PER NFPA-13 (2016) 10. ONLY NEW SPRINKLERS SHALL BE EMPLOYED IN THE INSTALLATION OF THE SPRINKLER SYSTEM. 11. A STOCK OF SPARE SPRINKLERS OF EACH STYLE, TYPE, AND TEMP. RATING ALONG WITH A SPRINKLER HEAD WRENCH SHALL BE LOCATED AT THE MAIN RISER. 12. ALL MAINS PIPING 21 2"- 4" IN SIZE TO BE BULL MOOSE TUBE EDDY FLOW THINWALL PIPE. ALL MAIN PIPING TO HAVE FIRELOCK GROOVED FITTINGS WITH WELDED OUTLETS 13. ALL LINE PIPING 1" - 1-1/4 " IN SIZE TO BE SCH-40, THREADED PIPE, WITH CAST OR DUCTILE IRON THREADED FITTINGS. GRID OR TREE LINE PIPING 1-1/2 " - 2" TO BE BULL MOOSE TUBE EDDY FLOW THINWALL PIPE. 14. LOWER FLOOR PIPE HANGERS TO BE HILTI KWIK CAST-IN ANCHORS KCS-WF, OR CEILING FLANGES IMBEDDED IN CONCRETE ROD AND RINGS. 15. UPPER FLOOR OR SINGLE STORY BUILDING HANGERS TO BE STEEL SAMMY SIDEWINDERS SWDR-1", ROD AND RINGS. (SEE HANGER DETAILS) 16. ALL PIPE DIMENSIONS ARE CENTER TO CENTER LENGTHS. 17. ALL ABOVE GROUND PIPING TO BE HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS. TESTING AND PIPE INSTALLATION INSPECTED BY LOCAL FIRE MARSHAL. 18. TOTAL AREA PROTECTED BY WET PIPE SYSTEM BUILDING "A" 12,602 SQ. FT. 19. OWNER TO MAINTAIN STORAGE TO A MINIMUM 18" BELOW FIRE SPRINKLER SYSTEM. OWNER TO INSTALL METAL BAFFLE IF SPRINKLERS ARE LESS THAN 6'-0" SPACES. OWNER TO ENSURE EXTRA HAZARD MATERIALS ARE NOT STORED IN FACILITY. ATTACHMENT TO STRUCTURE : ATTACH WITH 1/2" X 6" ALL THREAD ROD ATTACHED TO: TOP CHORD OF Z-PURLIN WITH UNI-STRUT BACKER & 1/2" NUTS AND WASHERS 1 1/4" SCHEDULE 40 PIPE UP TO 9'-0" LONG 1" SCHEDULE 40 PIPE UP TO 7'-0" LONG TOLCO FIG. 980 SWIVEL UNIV. SWAY BRACE ATTACHMENT TOLCO FIG. 1001 FAST CLAMP MATERIAL : ATTACH TO STEEL I-BEAM WITH TOLCO FIG.828 - OR - Hydraulically Calculated System This system as shown on company print no dated for contract noat is designed to discharge at a rate of GPM (Lmin) per sq ft (m2) of floor area over a maximum area of sq ft (m2) when supplied GPM (L/min)with water at the rate of at psi (bars) at the base of the riser Hose stream allowance of GPM (L/min) is included in the above. Occupancy Classification Commodity Classification Maximum Storate Height Installed By: SPRINX FIRE PROT, INC. FP-2.0 04/11/2024 TAHOMA TERRA BLDG-A REMOTE AREA#1 24-012CMBUILDING A STORAGE .20 956 315.91 42.86 250 ORDINARY GP-2 I-III 8'-0" SPRINX FIRE PROTECTION, INC. Hydraulically Calculated System This system as shown on company print no dated for contract noat is designed to discharge at a rate of GPM (Lmin) per sq ft (m2) of floor area over a maximum area of sq ft (m2) when supplied GPM (L/min)with water at the rate of at psi (bars) at the base of the riser Hose stream allowance of GPM (L/min) is included in the above. Occupancy Classification Commodity Classification Maximum Storate Height Installed By: SPRINX FIRE PROT, INC. FP-2.0 04/11/2024 TAHOMA TERRA BLDG-A REMOTE AREA#2 24-012CM 1ST FL OFFICE .10 921 199.01 26.35 100 LIGHT HAZARD I-III N/A SPRINX FIRE PROTECTION, INC. 05/10/2024 Co r p o r a t i o n Sp r i n k l e r A F i r e Fa x 2 5 3 . 8 5 3 . 5 8 9 0 Ph o n e 2 5 3 . 8 5 3 . 7 7 8 0 27 0 9 J A H N A V E , N W , S U I T E H 2 Gi g H a r b o r , W A . 9 8 3 3 5 - 1 7 3 5 Co n t . L i c . # S P R I N F P 0 1 1 L S FI R E S P R I N K L E R D R A W I N G SCALE: 1/8" = 1'-0" WA. STATE LEVEL 3 STAMP File:Tahoma Terra Storage Bldg A FP.dwg TA H O M A T E R R A S T O R A G E B U I L D I N G " A " TA H O M A B O U L E V A R D YE L M , W A 9 8 5 9 7 05 / 1 0 / 2 0 2 4 PA C I F I C S T O R A G E P A R T N E R S , L L C P. O . B O X 7 3 7 9 0 PU Y A L L U P , W A 9 8 3 7 3 PA P CI T Y O F Y E L M B L D G / F I R E O F F I C I A L (3 6 0 ) 3 3 9 - 2 0 9 5 BW / J G F FP-3.0 BLDG "A" Sheet Number: Sheet Title: Project No.24-012CM SCALE: 1/8" = 1'-0"0 16'8' BUILDING "A" STORAGE ELEVATION 4' (2 5 3 ) 2 2 3 - 7 4 3 2 CH R I S V A C C A R O TYCO TY-3131 TY-FRB, QR K=5.6, 1/2" NPT, (55,6 mm) 2-3/16" BRASS UPRIGHT SCALE: 1/8" = 1'-0"0 16'8' BUILDING "A" OFFICE SECTIONS 4' SCALE: 1/8" = 1'-0"0 16'8' BUILDING "A" STORAGE SECTION 4' OFFICE MAIN HANGERS OFFICE LINE HANGERS ATTACHMENT TO STRUCTURE : ATTACH WITH 1/2" X 6" ALL THREAD ROD ATTACHED TO: TOP CHORD OF TRUSS WITH 2 x BACKER BOARD & 1/2" NUTS AND WASHERS 1 1/4" SCHEDULE 40 PIPE UP TO 9'-0" LONG 1" SCHEDULE 40 PIPE UP TO 7'-0" LONG TOLCO FIG. 980 SWIVEL UNIV. SWAY BRACE ATTACHMENT TOLCO FIG. 1001 FAST CLAMP MATERIAL : ATTACH TO STEEL I-BEAM WITH TOLCO FIG.828 - OR - SCALE: 1/8" = 1'-0"0 16'8' PROJECT NORTH BUILDING "A" 2ND FLOOR FIRE SPRINKLER PLAN 4' Hydraulically Calculated System This system as shown on company print no dated for contract noat is designed to discharge at a rate of GPM (Lmin) per sq ft (m2) of floor area over a maximum area of sq ft (m2) when supplied GPM (L/min)with water at the rate of at psi (bars) at the base of the riser Hose stream allowance of GPM (L/min) is included in the above. Occupancy Classification Commodity Classification Maximum Storate Height Installed By: SPRINX FIRE PROT, INC. FP-2.0 04/11/2024 TAHOMA TERRA BLDG-A REMOTE AREA#2 24-012CMBUILDING A ATTIC VOID .10 5- ATTIC SPRK SPEC. APPL 125.36 44.05 100 LIGHT HAZARD I-III N/A SPRINX FIRE PROTECTION, INC. 05/10/2024