Seismic Calculations - Tahoma Terra Storage Bldg BUSGS web services were down for some period of time and as a result this tool wasn't operational, resulting in timeout error. USGS web services are now operational so this tool should work as expected. Tahoma Terra Storage Facility Latitude, Longitude: 46.943057, -122.628062 Date 4/11/2024, 1:40:43 PM Design Code Reference Document ASCE7-10 Risk Category II Site Class D - Stiff Soil Type Value Description SS 1.252 MCER ground motion. (for 0.2 second period) S1 0.5 MCER ground motion. (for 1.0s period) SMS 1.252 Site-modified spectral acceleration value SM1 0.75 Site-modified spectral acceleration value SDS 0.834 Numeric seismic design value at 0.2 second SA SD1 0.5 Numeric seismic design value at 1.0 second SA Type Value Description SDC D Seismic design category Fa 1 Site amplification factor at 0.2 second Fv 1.5 Site amplification factor at 1.0 second PGA 0.5 MCEG peak ground acceleration FPGA 1 Site amplification factor at PGA PGAM 0.5 Site modified peak ground acceleration TL 16 Long-period transition period in seconds SsRT 1.252 Probabilistic risk-targeted ground motion. (0.2 second) SsUH 1.271 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration SsD 1.5 Factored deterministic acceleration value. (0.2 second) S1RT 0.5 Probabilistic risk-targeted ground motion. (1.0 second) S1UH 0.531 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration. S1D 0.6 Factored deterministic acceleration value. (1.0 second) PGAd 0.5 Factored deterministic acceleration value. (Peak Ground Acceleration) 05/10/2024 Type Value Description PGAUH 0.519 Uniform-hazard (2% probability of exceedance in 50 years) Peak Ground Acceleration CRS 0.985 Mapped value of the risk coefficient at short periods CR1 0.941 Mapped value of the risk coefficient at a period of 1 s CV Vertical coefficient Corporation Sprinkler A Fire Fax 253.853.5890 Phone 253.853.7780 2709 JAHN AVE NW, SUITE H2 Gig Harbor, WA. 98335-1735 Cont. Lic. # SPRINFP011LS TOLBrace™ Seismic Bracing Calculations Project Address: Fastener Information TOLCO™ Brace Components Seismic Brace Assembly Detail Brace Information Brace Type TOLCO™ Component Listed Load Adjusted Load *Calculation Based on CONCENTRIC Loading 7' 0" (2.134 m) Angle of Brace L/R Value Least Rad. of Gyration Type of Brace Max Horizontal Load Maximum Brace Length Diameter of Brace Diameter Orientation to Connecting Surface Length Type Fastener Maximum Load Main Size Type/Sch. 2.5"Mega-Flow Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) Spacing (ft) Prying Factor 20 Sch.40 200 0.42" (11 mm) 926 lbs (420 kg) 1" 30° Min. NFPA Type D Bolt 1/2n. (12 mm) 1450 lbs (658 kg) N/A N/A Fig. 1001 Clamp 1600 lbs (726 kg)800 lbs (363 kg) Fig.980 Universal Swivel 2015 lbs (914 kg)1007 lbs (457 kg) See Fastener Information Lateral [X]Longitudinal [ ]4-Way [ ] 2.5" (65 mm)Mega-Flow 20 ft (6.1 m)20 ft (6.1 m)5 lb/ft (7.44 kg/m)100 lbs (45 kg) 1.25" (32 mm)Sch. 7 178.5 ft (54.4 m)178.5 ft (54.4 m)1.87 lb/ft (2.78 kg/m)334 lbs (152 kg) 1.25" (32 mm)Eddy-Flow 105 ft (32 m)105 ft (32 m)2.02 lb/ft (3.01 kg/m)212 lbs (96 kg) Tahoma Blvd Yelm, WA 98597 Job # 24-012CM Calculations based on 2016 NFPA Pamphlet #13 438 lbs (199 kg) 465 lb (210 kg) Tahoma Terra Storage Bldg B Contractor:Sprinx Fire Protetion, Inc. Address:2709 Jahn Ave NW Suite H2 Gig Harbor, WA 98335 Phone:(253)853-7780 License:SPRINFP011LS Subtotal Weight 646 lbs (293 kg) Wp (incl. 15%)743 lbs (337 kg) *Please Note: These calculations are for TOLCO™ components only. Use of any other components voids these calculations and the listing of the assembly. Sprinkler System Load Calculation (Fpw = CpWp) Cp =0.59 Diameter Type Length Total Length Weight Per Unit Length Total Weight {TOLBrace™ Version 8}Use of TOLBrace™ is subject to terms and conditions per the end user license agreement V8.8.137 Brace Identification on Plans LATERAL BRACE "A" 2.5" MegaFlow Pipe (63.5 mm)20 ft (6.1 m) 1.25" Sch.7 Steel Pipe (31.75 mm)178.5 ft (54.4 m) 1.25" EddyFlow Pipe (31.75 mm)105 ft (32 m) TOLBrace™ Seismic Calculations Brace Identification Brace Type (Per NFPA#13) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener LATERAL BRACE "A" NFPA Type D 20' 0" (6.1 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 30° 1/2 (12mm) Bolt N/A Summary of Pipe within Zone of Influence Allowance for Heads and Fittings Conclusions Total Adjusted Load of Pipe in Zone of Influence Material Capacity Fastener Capacity Fig. 1001 Clamp Fig.980 Universal Swivel Structural Member Calculations prepared by 15% 438 lbs (199 kg) 926 lbs (420 kg) 1450 lbs (658 kg) 800 lbs (363 kg) 1007 lbs (457 kg) 8" Z-PURLIN WITH 12" UNI-STRUT BACKER Joseph Faulkner * The description of the Structural Member is for informational purposes only. TOLBrace™ software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace™ 8 Visit us at www.tolco.com Tahoma Blvd Tahoma Terra Storage Bldg B Job # 24-012CM 2.5" MegaFlow PipeBraced Pipe (ft) G-Factor Used 0.59 Corporation Sprinkler A Fire Fax 253.853.5890 Phone 253.853.7780 2709 JAHN AVE NW, SUITE H2 Gig Harbor, WA. 98335-1735 Cont. Lic. # SPRINFP011LS TOLBrace™ Seismic Bracing Calculations Project Address: Fastener Information TOLCO™ Brace Components Seismic Brace Assembly Detail Brace Information Brace Type TOLCO™ Component Listed Load Adjusted Load *Calculation Based on CONCENTRIC Loading 7' 0" (2.134 m) Angle of Brace L/R Value Least Rad. of Gyration Type of Brace Max Horizontal Load Maximum Brace Length Diameter of Brace Diameter Orientation to Connecting Surface Length Type Fastener Maximum Load Main Size Type/Sch. 2.5"Mega-Flow Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) Spacing (ft) Prying Factor 71 Sch.40 200 0.42" (11 mm) 926 lbs (420 kg) 1" 30° Min. NFPA Type D Bolt 1/2n. (12 mm) 1450 lbs (658 kg) N/A N/A Fig. 4L Clamp 2015 lbs (914 kg)1007 lbs (457 kg) Fig.980 Universal Swivel 2015 lbs (914 kg)1007 lbs (457 kg) See Fastener Information Lateral [ ]Longitudinal [X]4-Way [ ] 2.5" (65 mm)Mega-Flow 71 ft (21.6 m)71 ft (21.6 m)5 lb/ft (7.44 kg/m)355 lbs (161 kg) Tahoma Blvd Yelm, WA 98597 Job # 24-012CM Calculations based on 2016 NFPA Pamphlet #13 241 lbs (109 kg) N/A Tahoma Terra Storage Bldg B Contractor:Sprinx Fire Protetion, Inc. Address:2709 Jahn Ave NW Suite H2 Gig Harbor, WA 98335 Phone:(253)853-7780 License:SPRINFP011LS Subtotal Weight 355 lbs (161 kg) Wp (incl. 15%)408 lbs (185 kg) *Please Note: These calculations are for TOLCO™ components only. Use of any other components voids these calculations and the listing of the assembly. Sprinkler System Load Calculation (Fpw = CpWp) Cp =0.59 Diameter Type Length Total Length Weight Per Unit Length Total Weight {TOLBrace™ Version 8}Use of TOLBrace™ is subject to terms and conditions per the end user license agreement V8.8.137 Brace Identification on Plans LONGITUDINAL BRACE "B" 2.5" MegaFlow Pipe (63.5 mm)71 ft (21.6 m) TOLBrace™ Seismic Calculations Brace Identification Brace Type (Per NFPA#13) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener LONGITUDINAL BRACE "B" NFPA Type D 71' 0" (21.64 m) Longitudinal 1" Sch.40 7' 0" (2.13 m) 200 30° 1/2 (12mm) Bolt N/A Summary of Pipe within Zone of Influence Allowance for Heads and Fittings Conclusions Total Adjusted Load of Pipe in Zone of Influence Material Capacity Fastener Capacity Fig. 4L Clamp Fig.980 Universal Swivel Structural Member Calculations prepared by 15% 241 lbs (109 kg) 926 lbs (420 kg) 1450 lbs (658 kg) 1007 lbs (457 kg) 1007 lbs (457 kg) 8" Z-PURLIN WITH 12" UNI-STRUT BACKER Joseph Faulkner * The description of the Structural Member is for informational purposes only. TOLBrace™ software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace™ 8 Visit us at www.tolco.com Tahoma Blvd Tahoma Terra Storage Bldg B Job # 24-012CM 2.5" MegaFlow PipeBraced Pipe (ft) G-Factor Used 0.59