Loading...
Hydraulic Calculations- Tahoma Terra Storage Building KSprinx Fire Protection, Inc. 2709 Jahn Ave NW Suite H2 Gig Harbor, WA 98335 (253)853-7780 Job Name : Tahoma Terra Storage Bldg K RA#1 Drawing : FP2.0 Location : Tahoma BLVD, Yelm WA Remote Area : #1 Contract : 24-012CM Data File : Tahoma Terra Storage Bldg K FP Area 1.WXF Date/Time : 05/09/2024 - 12:02 PM Computer Programs by Hydratec Inc. Revision: 50.5520.727 05/10/2024 Sprinx Fire Protection, Inc.Page 1 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 HYDRAULIC CALCULATIONS for JOB NAME Tahoma Terra Storage Building "K" RA #1 Location Tahoma BLVD, Yelm WA Drawing #FP2.0 Contract #24-012CM Date 05/09/2024 DESIGN Remote area ##1 Remote area location SOUTH END STORAGE UNITS Occupancy classification ORDINARY HAZ. GP-2 Density 0.2 - Gpm/SqFt Area of application 1000 - SqFt Coverage/sprinkler 130 - SqFt Type of sprinkler calculated QR BRASS UPRIGHT K=5.6 # Sprinklers calculated 8 In-rack demand 0 - GPM Hose streams 250 - GPM Total water required (including hose streams)454.163 - GPM @ 41.2924 - Psi Type of system WET STEEL Volume of system (dry or pre-action)N/A - Gal WATER SUPPLY INFORMATION Test date 2023 Location Site Location Source of info City of Yelm Water Dept CONTRACTOR INFO Sprinx Fire Protection, Inc. Address 2709 Jahn Ave NW / Suite H2 / Gig Harbor, WA 98335 Phone #(253)853-7780 Name of designer Brian Walder Authority having jurisdiction City of Yelm, WA NOTES: QR AREA REDUCTION 38.5% REDUCTION 11'-0" CEILINGS text1(35) - invisible Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 2 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 400 800 1200 1600 2000 2400 2800 3200 3600 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure : 55 C2 - Residual Pressure: 42 C2 - Residual Flow : 3227 D1 - Elevation : 4.548 D2 - System Flow : 204.163 D2 - System Pressure : 41.292 Hose ( Demand ) : 250 D3 - System Demand : 454.163 Safety Margin : 13.362 D1 D2 D3 Water Supply Curve Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 3 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 25 101.4 204.2 204.2 204.2 1 ¬2 ¬3 ¬4 ¬5 ¬6 ¬7 ¬TOR¬BOR¬TEST 50.7 152.7 204.2 204.2 25.7 8 ¬2 - |50.7 25 | 9 ¬3 25.7 10 ¬3 - |101.4 25.6| 11 ¬4 25.6 12 ¬4 - |152.7 25.7| 13 ¬5 25.7 14 ¬5 Flow Diagram Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 4 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 V 90' Ell Firelock #001 0 0 0 0 0 3.5 4.3 5 0 6.8 8.5 10 13 4.5 5.1 0 0 0 0 0 X 90'Tee-BranchFirelock002 0 0 0 0 0 8.5 10.8 13 0 16 21 25 33 9.3 11 0 0 0 0 0 Zdi Deringer 30 DCDA II Vert Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 5 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 55.0 42 3227.0 54.654 454.16 41.292 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 1 10.5 5.6 19.93 25.0 0.2 125 2 9.0 21.47 3 9.0 21.5 4 9.0 21.59 5 9.0 21.79 6 9.0 31.4 7 9.0 32.26 TOR 9.0 32.55 BOR 1.0 40.19 TEST 0.0 41.29 250.0 8 9.0 5.6 21.08 25.71 0.2 125 9 10.5 5.6 19.95 25.02 0.2 125 10 9.0 5.6 21.1 25.72 0.2 125 11 9.0 5.6 20.93 25.62 0.2 125 12 9.0 5.6 20.93 25.62 0.2 125 13 9.0 5.6 21.12 25.74 0.2 125 14 9.0 5.6 21.12 25.74 0.2 125 Flow Summary - NFPA Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 6 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 1 10.500 5.60 25.00 1.25 T 6.0 11.250 120 19.930 to 6.000 0.650 2 9 25.0 1.38 17.250 0.0517 0.892 Vel = 5.36 2 9 25.71 3 10.000 120 21.472 to 0.0 3 9 50.71 3.334 10.000 0.0026 0.026 Vel = 1.86 3 9 50.74 3 10.000 120 21.498 to 0.0 4 9 101.45 3.334 10.000 0.0094 0.094 Vel = 3.73 4 9 51.24 3 10.000 120 21.592 to 0.0 5 9 152.69 3.334 10.000 0.0200 0.200 Vel = 5.61 5 9 51.47 3 280.000 120 21.792 to 0.0 6 9 204.16 3.334 280.000 0.0343 9.604 Vel = 7.50 6 9 0.0 3 X 19.489 5.830 120 31.396 to 19.489 0.0 7 9 204.16 3.334 25.319 0.0343 0.868 Vel = 7.50 7 9 0.0 4 2V 18.954 10.310 120 32.264 to 18.954 0.0 TOR 9 204.16 4.31 29.264 0.0098 0.287 Vel = 4.49 TOR 9 0.0 4 V 9.477 9.000 120 32.551 to Zdi 0.0 9.477 7.453 * * Fixed Loss = 3.988 BOR 1 204.16 4.31 18.477 0.0099 0.182 Vel = 4.49 BOR 1 0.0 4 E 14.534 25.000 140 40.186 to G 2.907 46.508 0.433 TEST 0 204.16 4.1 T 29.067 71.508 0.0094 0.673 Vel = 4.96 250.00 Qa = 250.00 TEST 454.16 41.292 K Factor = 70.68 8 9 5.60 25.71 1.25 T 6.0 1.250 120 21.077 to 6.000 0.0 2 9 25.71 1.38 7.250 0.0545 0.395 Vel = 5.51 0.0 2 25.71 21.472 K Factor = 5.55 9 10.500 5.60 25.02 1.25 T 6.0 11.250 120 19.955 to 6.000 0.650 3 9 25.02 1.38 17.250 0.0518 0.893 Vel = 5.37 0.0 3 25.02 21.498 K Factor = 5.40 10 9 5.60 25.72 1.25 T 6.0 1.250 120 21.102 to 6.000 0.0 3 9 25.72 1.38 7.250 0.0546 0.396 Vel = 5.52 0.0 3 25.72 21.498 K Factor = 5.55 11 9 5.60 25.62 1.25 T 6.0 6.250 120 20.929 to 6.000 0.0 4 9 25.62 1.38 12.250 0.0541 0.663 Vel = 5.50 0.0 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.5520.727 Sprinx Fire Protection, Inc.Page 7 Tahoma Terra Storage Bldg K RA#1 Date 5/9/2024 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 4 25.62 21.592 K Factor = 5.51 12 9 5.60 25.62 1.25 T 6.0 6.250 120 20.929 to 6.000 0.0 4 9 25.62 1.38 12.250 0.0541 0.663 Vel = 5.50 0.0 4 25.62 21.592 K Factor = 5.51 13 9 5.60 25.74 1.25 T 6.0 6.250 120 21.124 to 6.000 0.0 5 9 25.74 1.38 12.250 0.0545 0.668 Vel = 5.52 0.0 5 25.74 21.792 K Factor = 5.51 14 9 5.60 25.74 1.25 T 6.0 6.250 120 21.124 to 6.000 0.0 5 9 25.74 1.38 12.250 0.0545 0.668 Vel = 5.52 0.0 5 25.74 21.792 K Factor = 5.51 Final Calculations : Hazen-Williams Computer Programs by Hydratec Inc. Revision: 50.5520.727 FLOW TEST DATA USED FOR CALCULATIONS