PSE FINAL 105104560 TAHOMA TERRA 7&8 PH 3SITE
N
Vicinity Map
46.9407, -122.6361
Owner / Developer Contact Info
officeATTN:
TAHOMA TERRA HOLDINGS, LLC.
P.O. BOX 73790
PUYALLUP, WA 98373
EVAN MANN 253.820.7835
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
GAS
PHONE
CABLE TV
514593055 105104560
N/A 105105193
N/A 101175593
N/A 108156916
N/A N/A
N/A N/A
514593101 107063209
N/A 106395927
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Street Lights
Relocation
Removal
Temporary
Job Order
Distribution
Service Stubs
HP Svc/MSA
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, PER THE TRENCH
PROFILE, AND ALL EXCAVATIONS AT THE TRANSFORMER/HANDHOLE VAULT SITES
SUCH THAT PSE FACILITIES WILL MATCH FINAL GRADE. VAULT HOLES WILL HAVE
STABLE LEVEL BOTTOMS. CUSTOMER WILL PROVIDE 6" OF CRUSHED ROCK FOR
VAULT BEDDING. ALL TRENCHES WILL HAVE 6" OF WASHED SAND COVER AND 4"
BEDDING FOR ALL CONDUITS. THE CUSTOMER WILL PROVIDE SELECT BACKFILL, IF
REQUIRED, AND COMPACTION AS NECESSARY. THE CUSTOMER IS RESPONSIBLE FOR
DISPOSAL OF ALL NATIVE SPOILS NOT SUITABLE FOR USE AS BACKFILL. ALL
TRENCHES MAY BE JOINT WITH GAS, TELEPHONE AND TV CABLE.
ALL CABLES/CONDUITS TO BE INSTALLED IN CUSTOMER'S TRENCH AT THE DEPTH
INDICATED IN TRENCH DETAIL (DEPENDENT UPON SIZE OF CONDUIT BEING INSTALLED
TO MEET MIN 36" OF COVER). INSTALL CABLE ID TAGS AT EACH END OF THE PRIMARY
CABLES PER THE CIRCUIT ONE-LINE DIAGRAM.
UNLESS OTHERWISE SPECIFIED BY MUNICIPALITIES, INSTALL PVC (DB-120) ROAD
CROSSINGS AS INDICATED ON THE CROSSINGS CONDUIT TABLE & AS SHOWN ON
WORK SKETCH. CROSSINGS SHALL BE INSTALLED BY CUSTOMER/DEVELOPER PER
PUGET SOUND ENERGY STANDARDS.
AT SYMBOL: INSTALL UNDERGROUND PRIMARY CABLES IN
CONDUIT. CABLE LENGTH AND CONDUIT SIZE AS INDICATED ON PRIMARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL 600 VOLT UG SECONDARY CABLES IN
CONDUIT. CABLE/CONDUIT SIZE AND LENGTH AS INDICATED ON SECONDARY CABLE &
CONDUIT TABLE.
AT SYMBOL: INSTALL MINI-PAD HANDHOLE & PADMOUNT TRANSFORMER.
ADDITIONAL EQUIPMENT AS INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY PEDESTAL/HANDHOLE W/ (3)
MULTI-CONNECTORS. SIZE AS INDICATED ON SECONDARY HH/PEDESTAL TABLE.
(EXCAVATION: 3' SQ.)
AT SYMBOL: INSTALL JUNCTION BOX HANDHOLE. ADDITIONAL EQUIPMENT AS
INDICATED ON VAULT TABLE.
AT SYMBOL: INSTALL SECONDARY CABLE & CONDUIT STUB-OUT.
AT SYMBOL: INSTALL STREET LIGHTING STANDARD. SIZE AND TYPE OF
STANDARD/LUMINARIE AS INDICATED ON STREET LIGHTING TABLE. (CUSTOMER TO
EXCAVATE & INSTALL CORRUGATED STREET LIGHT TUBES FOR PLACEMENT OF THE
STREET LIGHT STANDARDS. )
INCLEMENT WEATHER CONDITIONS MAY CAUSE DELAYS IN CONSTRUCTION TIMES
AND DATES.
POWER GENERAL NOTES - PLAT PROJECT
10
5
1
0
4
5
6
0
10
7
0
6
3
2
0
9
Phone
INTOLIGHT Contact Information:
LARS LARSON
425.456.2701
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
L. BROWN 425.417.8620 .
A. DUNN .06.05.24
A. DUNN .06.05.24
D. WALKER .05.30.24
REDT # ( RW-134833 )YELM
TAHOMA TERRA 7&8 PH 3
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
P#78640000018, TAHOMA BLVD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A IP 344-60
107063209 105104560
N/A 1 OF 5
THURSTON 344 CIONC QSTHLE
23SE-T17N-R01E 280.038 283.041
1701E092 1701E104 1701E092 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
LINDA OLSON
425.462.3787
.
.
.
11.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:LEE BROWN
425.417.8620
Lee.Brown@pse.com
x
x
x x
...
...
...
EVAN@SOUNDBUILTHOMES.COM
TYPICAL NOTCH-OUT FOR TRANSFORMER,
NOT TO SCALE
& SECONDARY PEDESTAL/HANDHOLE
BACK OF EASEMENT
STANDARD
EASEMENT
LINE
ROW
10'
PL
1'
4' - 5'
Min.
1'
7'7'
TRANSFORMER
(WHEN PRESENT)
42"
45°42"
1'
45°
Pr
o
p
e
r
t
y
L
i
n
e
Road Side
Top View of Mainline Trench for
Single Stubout Location
4'
Pr
o
p
e
r
t
y
L
i
n
e
Road Side
Top View of Mainline Trench for Pedestal
or Double Stubout Location
42"45°
4'
45°
STUBOUT EXCAVATION DIMENSIONS
NOT TO SCALE
JOINT TRENCH DETAIL
NOT TO SCALE
JOINT TRENCH DETAIL
NOTES:
1. If the final backfill contains rocks greater than 8 inches in diameter , install 12 inches compacted sand shading across the full width of the trench. *
If the final backfill contains rocks 8 inches in diameter or smaller , install 6 inches compacted sand shading across the full width of the trench. *
2. Rocks greater than 10 inches diameter are not permitted in the final backfill.
3. Sand bedding is required under PSE gas pipe. Bedding is not required for the full width of the trench; it shall extend from the
side of the trench nearest to where the gas main/service is installed to a minimum of 6 inches on the opposite side of the gas line.
4. Utilities shall not be stacked over the gas line in the trench.
5. If wet utilities will be included in the trench, please contact PSE or local power company directly for clearance requirements.
6. Reduced clearance of 4 inches between power and communication, must have approval of the communications companies.
* Alternatives to full-width trench shading require PSE approval.
Primary & Secondary-Mainline Gas & Communications (NTS)
ROAD SIDE
NATIVE
SECONDARY POWER
PEDESTAL
MATERIAL
P/L
Power
Secondary
Power
Primary
Conduit
Tel. & TV
12" Min
12" Sand
Cover when
gas line is in
trench
Sand
6" or 12"
4" Sand Bedding
1'
36"
Cover
42"
Gas
12"
18"
Lower 2"
10"
Pedestal
PSE 10' FRONTAGE
EASEMENT
1'
Cover
ROAD SIDE
MINIPAD
MINIPAD
FIELD SIDE
VAULT
6" of crushed rock
(base for vault)
P/L
Power
Secondary
Power
Primary
Gas
12" Min Horizontal Separation
Communications
42" Min
21"1'
Feeder
38"
2"
4" Sand Bedding
12" Sand
Cover
36"
Cover
4" Sand Bedding
42"
6" Additional depth when
Feeder is required
PSE 10' FRONTAGE EASEMENT
1'
TRANSFORMER
Final
Backfill
Initial
Backfill
Trench Depth
42" - 48"
Primary
Dirt Pile
Final Grade
24" Min
36"
Min Cover
Over Power
48"
Max
Depth
Final Backfill
Gas
4" Sand Bedding
Property Line
intercept (depth varies).
SidewalkCurb
Location of roof drain
48" Typical
Width may vary per
Number of Utilities
and Conduits
6" or 12" Min Sand Shading
Over Gas after Compaction
12" Min
R/W or
Excavated
12" Typical
Power
Secondary
Power
TV & TEL
12" Min
12" Min
Separation
4,5
1,2
1
3
6
6" or 12" Min Sand Shading
Over Power after Compaction1
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED EQUIPMENT
TRANSFORMER
APPROVED
AREA
CO
M
B
U
S
T
I
B
L
E
B
U
I
L
D
I
N
G
W
A
L
L
S
&
R
O
O
F
10'
10'
10'
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
3' MIN
@ H1A, H1B, H2A, H2B, H3A, H4A, H5A,
H6A, H6B, H7A, H8A, H9A & H10A
SHALL BE STAGGERED
CONNECTOR BARS
IN THE FRONT
NEUTRALS SHALL BE 18"
16"
13"
12"10"
2"
10"
Pedestal will accept up to six 3" conduits
SEALED WITH FOAM
CONDUIT SHALL BE
120 PVC CONDUIT ELBOWS
TYPICAL 24" RADIUS DB
SIDE VIEW WITH CONDUIT
10"
18"
16"
13"
10"
2"
36"
FRONT VIEW WITH CONDUIT
SECONDARY PEDESTAL DETAIL
NOT TO SCALE
CLEAR WORKING SPACE FOR VAULTS
NOT TO SCALE
FIELD SIDE (PREFERRED)
ROAD SIDE (PREFERRED)
6' MIN
3'
MIN
3'
MIN
3' MIN
VAULT DETAIL @ V01, V03-V08 & V10
NOT TO SCALE
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
FRONT
FRONT
VAULT DETAIL @ V02 & V09
NOT TO SCALE
EXCAVATION: _____ CUBIC YARDS
3'-6"
SIDE VIEW
2"
6"
CRUSHED
ROCK
TOP VIEW
7'
7'
6 1/3
2"
Excavation - 19-1/2 cubic yards
SIDE VIEW
5'-4"Crushed
6"
Rock
TOP VIEW
9'
11'
7'-0"
4'-0"
1'
4'-8"
VAULT DETAIL @ J01-J03
NOT TO SCALE
496
497
498
499
500
501
502
503
504
505
506507
508509
518 519 520 521 522 523 524 525 526 527 528 529 530 531
532533534
535
536537
538
539540541
542
543
544
545
546
547
548
549510
511
512
513
514
515
516
517
550
551
552
553
554
555
WETLAND
WETLAND BUFFER
TAHOMA BLVD SE
DO
T
S
O
N
S
T
S
E
'C' ROAD
'B' ROAD
'A' ROAD
'F
'
R
O
A
D
'C'
R
O
A
D
'D
'
R
O
A
D
'G
'
R
O
A
D
'E
'
R
O
A
D
558
559
560
561
562
563
564
565566567568569
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585 586 587 588 589 590 591 592 593 594 595 596 597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614 615 616 617 618 619
620621622623624625
626 627 628 629 630 631 632
570
TRACT U
TRACT T
TRACT S
FUT: 2-2"
FUT: 1-4"
FUT: 2-2"
FUT: 1-4"
GAS
ONLY
5
6
'
90
'
56'
56
'
R57'
56
'
56'
56'
FEED YEL
25FUT: 2-4"
'A'
1" = 50'DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
L. BROWN 425.417.8620 .
A. DUNN .06.05.24
A. DUNN .06.05.24
D. WALKER .05.30.24
REDT # ( RW-134833 )YELM
TAHOMA TERRA 7&8 PH 3
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
P#78640000018, TAHOMA BLVD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A IP 344-60
107063209 105104560
1" = 50'2 OF 5
THURSTON 344 CIONC QSTHLE
23SE-T17N-R01E 280.038 283.041
1701E092 1701E104 1701E092 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
LINDA OLSON
425.462.3787
.
.
.
SITE PLAN
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
YEL-25
11.06.23
394 363 312
12 18 28
406 381 340
...
...
...
SCHED.SQ. FT.
MAX LRC =
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
J-BOX CABLE ENTRY DETAIL
NOT TO SCALE 12kV CABLE ROUTING
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
DEVELOPER TO COORDINATE WITH PSE
PROJECT MANGER & SERVICE PROVIDER
PRIOR TO EXCAVATING WITHIN 3' OF LOCATE
MARKS OF PSE ENERGIZED FACILITIES
CABLE/WIRE REMOVAL TABLE
SPAN ACTUAL LENGTH REMARKS
FROM TO CABLE TAG LENGTH CONDUIT WIRE
J04 V11
EGU815
EGU816
EGU817
615 -
CROSSING CONDUIT TABLE
X-ING
#
LOCATION GAS POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY LOCATION
SIZE
(IN)TYPE QTY
X01 LOT 596 LOT 595 10 40 1 S 4 DB120 2 85 ( )' SCL GAS MAIN, PRIMARY
X02 LOT 596 LOT 595 6 40 1 S 2 DB120 1 100 ( )' NCL GAS MAIN, PRIMARY
X03 LOT 596 LOT 598
6 40 1 W 4 DB120 1 85 ( )' ECL GAS MAIN, PRIMARY
----2 DB120 1 85 ( )' ECL PRIMARY
----3 DB120 1 85 ( )' ECL SECONDARY
X04 LOT 594 LOT 631
2 40 1 E 3 DB120 2 65 ( )' WCL GAS SVC, SECONDARY
----2 DB120 1 65 ( )' WCL ST. LIGHT
X05 LOT 592 LOT 629 2 40 1 E 3 DB120 2 65 ( )' WCL GAS SVC, SECONDARY
X06 LOT 590 LOT 628 2 40 1 W 3 DB120 2 65 ( )' ECL GAS SVC, SECONDARY
X07 LOT 589 LOT 626
2 40 1 W 3 DB120 1 65 ( )' ECL GAS SVC, SECONDARY
----2 DB120 1 65 ( )' ECL ST. LIGHT
X08 LOT 604 LOT 619
4 40 1 N 2 DB120 1 75 ( )' SCL GAS MAIN, PRIMARY
----3 DB120 1 75 ( )' SCL SECONDARY
X09 LOT 618 LOT 621 2 40 1 E 3 DB120 2 65 ( )' WCL GAS SVC, SECONDARY
X10 LOT 617 LOT 622 2 40 1 W 3 DB120 2 65 ( )' WCL GAS SVC, SECONDARY
X11 LOT 615 LOT 624 2 40 1 W 3 DB120 2 65 ( )' ECL GAS SVC, SECONDARY
X12 LOT 614 LOT 577 4 40 1 N GAS ONLY 75 ( )' SCL GAS MAIN
X13 LOT 574 LOT 613 2 40 1 S 3 DB120 2 65 ( )' NCL GAS SVC, SECONDARY
X14 LOT 572 LOT 611 2 40 1 S 3 DB120 2 65 ( )' NCL GAS SVC, SECONDARY
X15 'A'LOT 560 6 40 1 W 4 DB120 1 75 ( )' ECL GAS MAIN, PRIMARY
X16 LOT 561 LOT 607 2 40 1 E 3 DB120 1 65 ( )' WCL GAS SVC, SECONDARY
X17 LOT 563 LOT 608 2 40 1 E 3 DB120 1 65 ( )' WCL GAS SVC, SECONDARY
X18 LOT 564 LOT 608 2 40 1 W 3 DB120 1 65 ( )' WCL GAS SVC, SECONDARY
2" PVC PLUG /CAPS = 24 2" YELLOW SCH 40 PVC = 780 FT 2" DB120 GREY PVC = 390 FT 2" PVC PLUG /CAPS = 10
4" PVC PLUG /CAPS = 4 4" YELLOW SCH 40 PVC = 150 FT 3" DB120 GREY PVC = 1460 FT 3" PVC PLUG /CAPS = 44
6" PVC PLUG /CAPS = 6 6" YELLOW SCH 40 PVC = 260 FT 4" DB120 GREY PVC = 330 FT 4" PVC PLUG /CAPS = 8
10" PVC PLUG /CAPS = 2 10" YELLOW SCH 40 PVC = 85 FT
Developer Note:
The following Fault Current information MUST BE conveyed
to the builder of the units:
All units may require upgraded house electrical equipment as the
fault current at the meter base may exceed 10,000 amps.
FAULT CURRENT TABLE
1Ø PM TRANSFORMERS (240/120V)
120V WINDINGS 240V WINDINGS
LOCATION SIZE R/X MIN.
%Z
FAULT
CURRENT
MIN.
%Z
FAULT
CURRENT
V02 & V09 75kVA 0.5 2.30 36,200 AMPS 1.80 23,100 AMPS
DEDICATED FACILITIES (105104560) for Dedicated Stub Locations
SITE SPAN ADDITIONAL REMARKS LABOR UNITS
#FROM TO FOOTAGE
-H9A LOT 558 50 DED. CONDUIT & WIRE 2-36, 2-54A
-V10 LOT 567 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V10 LOT 568 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V10 LOT 569 50 DED. CONDUIT & WIRE 2-36, 2-54A
-V04 LOT 576 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 581 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 582 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V03 LOT 584 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V02 LOT 590 35 DED. CONDUIT & WIRE 2-36, 2-54A
-V06 LOT 599 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V07 LOT 604 30 DED. CONDUIT & WIRE 2-36, 2-54A
-V07 LOT 605 35 DED. CONDUIT & WIRE 2-36, 2-54A
-H10A LOT 609 30 DED. CONDUIT & WIRE 2-36, 2-54A
TOTAL FT=460
SITE SPECIFIC NOTES
AT IP1
-INTERCEPT EXISTING CONDUIT & RE-ROUTE TO J01 FROM J04
PER PRIMARY & CONDUIT TABLE (PAGE 3)
AT IP2
-INTERCEPT EXISTING CONDUIT & RE-ROUTE TO J01 FROM V11
PER PRIMARY & CONDUIT TABLE (PAGE 3)
CIRCUIT FEET ADDED: 3,900'
17 3,500
115 AMPS
CIRCUIT FEET REMOVED: 590'
LOAD BALANCE TO BE ACHIEVED THROUGH
FUTURE PHASES OF TAHOMA TERRA PLAT.
FEED YEL
25
AØEGU812
BØEGU813
CØEGU814
NEW 3Ø 1/O AL
EJT175-AØ
EJT176-BØ
EJT177-CØ
NEW 3Ø 1/O AL
EJT178-AØ
EJT179-BØ
EJT180-CØ
NEW 3Ø 1/O AL
EJT181-AØ
EJT182-BØ
EJT183-CØ
NEW 3Ø 1/O AL
EJT192-AØ
EJT193-BØ
EJT194-CØ
NEW 1/O AL
EJT196-AØ
NEW 1/O AL
EJT195-AØ
NEW 1/O AL
EJT188-CØ
NEW 1/O AL
EJT187-CØ
NEW 1/O AL
EJT186-CØ
NEW 1/O AL
EJT185-CØ
NEW 1/O AL
EJT184-CØ
NEW 1/O AL
EJT189-BØ
NEW 1/O AL
EJT190-BØ
NEW 1/O AL
EJT191-BØ
'A'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
L. BROWN 425.417.8620 .
A. DUNN .06.05.24
A. DUNN .06.05.24
D. WALKER .05.30.24
REDT # ( RW-134833 )YELM
TAHOMA TERRA 7&8 PH 3
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
P#78640000018, TAHOMA BLVD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A IP 344-60
107063209 105104560
AS SHOWN 3 OF 5
THURSTON 344 CIONC QSTHLE
23SE-T17N-R01E 280.038 283.041
1701E092 1701E104 1701E092 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
LINDA OLSON
425.462.3787
.
.
.
...
...
...
EX OVERHEAD CIRCUIT MAP 1701E104
SCALE: 6" = 1 MILE
NEW PRIMARY UNDERGROUND CIRCUIT ONE-LINE DIAGRAM
NOT TO SCALE
EX UNDERGROUND CIRCUIT MAP 1701E092
NOT TO SCALE
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT CABLE ASBUILT INFORMATION - FOREMAN COMPLETE
FROM TO SIZE
(IN)QTY.
DESIGN
LENGTH
(FT)
BENDS PULL
(LBS)
PULL
REV
(LBS)
CABLE SIZE
DESIGN
LENGTH
(FT)
PHASE - ID TAG RECORD RECORD PHASE TAPPED & ACTUAL FOOTAGE INSTALLED LUBRICANT (Gal.)
90°45°22°11°A B C MANUFACTURER COMPOUND YEAR NOTES CONDUIT CABLE EST.ACTUAL
IP1 J01 4 1 25 -2 --CONDUIT ONLY --
J04 J01 CABLE ONLY 514 400 3Ø 1/O AL JKT 535 EJT175 EJT176 EJT177 -3.7
J01 IP2 4 1 25 1 ---CONDUIT ONLY --
J01 V11 CABLE ONLY 312 293 3Ø 1/O AL JKT 125 EJT178 EJT179 EJT180 -0.9
J01 E01 4 2 155 ----CONDUIT ONLY
J01 J02 4 1 310 -4 --481 418 3Ø 1/O AL JKT 320 EJT181 EJT182 EJT183 -2.2
J02 V01 2 1 105 ----86 71 1/0 AL JKT 215 --EJT184 -0.9
V01 V02 2 1 165 ----94 94 1/0 AL JKT 175 --EJT185 -0.7
V02 V03 2 1 295 --9 -217 223 1/0 AL JKT 305 --EJT186 -1.2
V03 V04 2 1 240 ----109 109 1/0 AL JKT 250 --EJT187 -1.0
V04 V05 2 1 205 ----102 102 1/0 AL JKT 215 --EJT188 -0.9
J02 V06 2 1 90 1 ---101 89 1/0 AL JKT 175 -EJT189 --0.7
V06 V07 2 1 235 ----108 108 1/0 AL JKT 245 -EJT190 --1.0
V07 V08 2 1 270 1 ---157 181 1/0 AL JKT 355 -EJT191 --1.4
J02 E02 4 1 40 ----CONDUIT ONLY -FUT -
J02 E02 2 2 40 ----CONDUIT ONLY -FUT -
J02 J03 4 1 485 2 ---673 685 3Ø 1/O AL JKT 655 EJT192 EJT193 EJT194 -4.6
J03 V09 2 1 180 ----81 67 1/0 AL JKT 190 EJT195 ---0.8
V09 V10 2 1 265 ----114 114 1/0 AL JKT 275 EJT196 ---1.1
J03 E03 4 1 55 ----CONDUIT ONLY -FUT -
J03 E03 2 2 55 ----CONDUIT ONLY -FUT -
2" PVC (FT) & BENDS =2240 2 0 9 0 1/0 AL JKT TOTAL (FT) =2400
4" PVC (FT) & BENDS =1250 3 6 0 0 3Ø 1/0 AL JKT TOTAL (FT) =1635
SITE
SITE
FUT: 2-2"
FUT: 1-4"
FUT: 2-2"
FUT: 1-4"
558
559560
561
562
563
564
565566567568
569
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587 588 589 590 591 592 593 594 595 596 597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614 615 616 617 618 619
620621622623624625
626 627 628 629 630 631 632
570
FUT: 2-4"
'A'
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
L. BROWN 425.417.8620 .
A. DUNN .06.05.24
A. DUNN .06.05.24
D. WALKER .05.30.24
REDT # ( RW-134833 )YELM
TAHOMA TERRA 7&8 PH 3
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
P#78640000018, TAHOMA BLVD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A IP 344-60
107063209 105104560
N/A 4 OF 5
THURSTON 344 CIONC QSTHLE
23SE-T17N-R01E 280.038 283.041
1701E092 1701E104 1701E092 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
LINDA OLSON
425.462.3787
.
.
.
...
...
...
NOT TO SCALE
NEW CONDUIT DIAGRAM
1.
2.
3.
4.
5.
ALL STREET LIGHTING POLES ARE TO BE INSTALLED PER STANDARD
6375.4800 (page #2) IN THE "LINE WORK PRACTICES MANUAL".
ALL POLES (WOOD, CONCRETE OR FIBERGLASS) ARE TO BE SET
PLUMB AND EMBEDDED TO THE GROUND LINE MARKED ON THE
POLE.
BACKFILL AROUND POLE WITH 5/8" MINUS GRAVEL AND COMPACT IN
6" LIFTS. (PEA GRAVEL AND NATIVE SOILS ARE NOT ACCEPTABLE.)
APPROXIMATELY 1 CU. YD. OF 5/8" MINUS CRUSHED ROCK WILL BE
REQUIRED.
THE DEVELOPER IS REQUIRED TO SUPPLY AND INSTALL PLASTIC
(NON PAPER) STREET LIGHT TUBES (MINIMUM 18" DIAMETER) TO
AID IN THE INSTALLATION OF THE STREET LIGHTING POLES. THE
DEVELOPER MUST ALSO SUPPLY THE REQUIRED 5/8" MINUS
GRAVEL AT EACH STREET LIGHT LOCATION.
IN ALL SHOEBOX AND COBRAHEAD INSTALLATIONS, THE LUMINAIRE
MUST BE LEVELED.
DEVELOPER MUST SUPPLY DURABLE LID/COVER AT EACH STREET
LIGHT TUBE.
6.
NOT TO SCALE
STREET LIGHT TUBE DETAIL
Plan View Detail
of Street Light Tube
Wire Entrance
Slot
Street Light
Tube
Field
Side
Road
Side
Wire
Entrance Slot
45°
45°
Position 3" x 6" wire entrance slot 45 degrees
left or right from a line perpendicular to road-
way through center of tube.
Field Side
3" x 6" Wire
Entrance Slot
45°
45°
Street light tube
set 2" below grade.
Road Side
18" - 24" Minimum
Depending on
Pole Type
5'-0"
20"
26"
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
STREET LIGHT CIRCUITRY TABLE - 105105193
SITE
#FROM
CABLE INFO AS-BUILT
REMARKSTYPELFTYPELENGTH
SL1 H1A #6 CIC 130
SL2 H2A #6 CIC 135
SL3 H3A #6 CIC 45
SL4 V05 #6 CIC 60
SL5 V09 #6 CIC 85
SL6 H6B #6 CIC 65
TOTAL FT =520 TOTAL FT =
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS TRANSFORMER ID NUMBERS
(COMPANY ID)
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
V01 559332
146665
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 CØ
V02 559332
146649
54"x54"x38"
Unistrut HH
Matid: 7663002
75KVA MP TRF
120/240
Matid: 6247150
2 -
MINU1LL 6045.1010 CØ
V03 559317
146636
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 CØ
V04 559293
146635
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 CØ
V05 559273
146635
42"x48"x38"
Unistrut HH
Matid: 7663001
37.5KVA MP TRF
120/240
Matid: 6247050
1 1
MINU1SR 6045.1010 CØ
V06 559320
146680
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 BØ
V07 559297
146680
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
2 -
MINU1SL 6045.1010 BØ
V08 559300
146648
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
1 1
MINU1SR 6045.1010 BØ
V09 559274
146671
54"x54"x38"
Unistrut HH
Matid: 7663002
75KVA MP TRF
120/240
Matid: 6247150
2 -
MINU1LL 6045.1010 AØ
V10 559264
146648
42"x48"x38"
Unistrut HH
Matid: 7663001
50KVA MP TRF
120/240
Matid: 6247100
1 1
MINU1SR 6045.1010 AØ
J01 559342
146696
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
9 3
JBOX15L 6055.1030 3Ø
ELB10J 6041.1000
CAP (7630600)
J02 559331
146685
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
8 4
JBOX15L 6055.1030 3Ø
ELB10J 6041.1000
CAP (7630600)
J03 559280
146687
4'8"x7'x5'
w/2-3' Sq Doors
Matid: 7663200
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: 7625900
4 8
JBOX15L 6055.1030 3Ø
ELB10J 6041.1000
CAP (7630600)
Existing
V11
559346
146687
4'8"x4'8"x4'
w/20"x44" Hole
Matid: Existing
Cover: Existing
225KVA PM TRF
277/480
Matid: Existing
3 -
ELB10J 6041.1000 EX. 3Ø
Existing
J04
559330
146738
4'8"x7'x5'
w/2-3' Sq Doors
Matid: Existing
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: Existing
3 -
ELB10J 6041.1000 EX. 3Ø
SECONDARY HH/PEDESTAL TABLE
Site
Pedestal
or
Handhole
Number of
Positions
Required
Remarks
H1A PEDESTAL 6 - SEPL6 6050.1000
H1B PEDESTAL 5 - SEPL6 6050.1000
H2A PEDESTAL 5 - SEPL6 6050.1000
H2B PEDESTAL 3 - SEPS3 6050.1000
H3A PEDESTAL 4 - SEPS4 6050.1000
H4A PEDESTAL 5 - SEPL6 6050.1000
H5A PEDESTAL 5 - SEPL6 6050.1000
H6A PEDESTAL 3 - SEPS3 6050.1000
H6B PEDESTAL 4 - SEPS4 6050.1000
H7A PEDESTAL 5 - SEPL6 6050.1000
H8A PEDESTAL 5 - SEPL6 6050.1000
H9A PEDESTAL 4 - SEPS4 6050.1000
H10A PEDESTAL 4 - SEPS4 6050.1000
SECONDARY 3"
ST. LT. CIC #6
PRIMARY 2"
PRIMARY 4"
CONDUIT LEGEND
STREET LIGHT TABLE
SITE
#
POLE LUMINAIRE TUBE POLE BASE TYPE
(Direct Buried or
Basemount)
WO #BILLING
SCH.
SMART STREET
LIGHT NODE
TOTAL
CONN LOADGRID #TAG #TYPE MTG HT.ARM WATTS STYLE TUBE
LENGTH
TUBE
DIAMETER
SL1 559327
146672 GREEN CONC 30'6'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
SL2 559326
146642 GREEN CONC 30'8'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
SL3 559302
146637 GREEN CONC 30'8'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
SL4 559269
146637 GREEN CONC 30'8'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
SL5 559279
146677 GREEN CONC 30'8'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
SL6 559304
146679 GREEN CONC 30'8'47W LED CHFL 4K T3
YELM GREEN 5'18"DIRECT BURIED 105105194 51 120/240
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
L. BROWN 425.417.8620 .
A. DUNN .06.05.24
A. DUNN .06.05.24
D. WALKER .05.30.24
REDT # ( RW-134833 )YELM
TAHOMA TERRA 7&8 PH 3
3Ø PRIMARY U/G LINE EXTENSION - 75 S/F LOTS
P#78640000018, TAHOMA BLVD SE, YELM, WA 98597
PUGET SOUND ENERGY
N/A IP 344-60
107063209 105104560
N/A 5 OF 5
THURSTON 344 CIONC QSTHLE
23SE-T17N-R01E 280.038 283.041
1701E092 1701E104 1701E092 YEL-25
COMCAST
TED AXTELL
253.878.2794
LUMEN
DEWAYNE RICHERT
253.221.0133
RIGHT OF WAY
LINDA OLSON
425.462.3787
.
.
.
...
...
...
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SECONDARY CABLE & CONDUIT TABLE
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER Foreman - Complete
FROM TO (1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in)Design (ft)90°45°22°11°(Percent)(Percent)Actual Amount Installed Cable Conduit
V01 H1A 350 50 3 50 2 2.7 1.6 -
V01 H1B 350 50 3 50 2 2.7 1.6 -
H1A LOT 594 1/O 55 3 3.5 2.6 -
H1A LOT 595 1/O 55 3 3.5 2.6 -
H1A LOT 631 4/O 80 55 3 15 2 4.0 3.3 -
H1A LOT 632 4/O 85 55 3 20 3 4.1 3.4 -
H1B LOT 592 1/O 55 3 3.5 2.6 -
H1B LOT 593 1/O 55 3 3.5 2.6 -
H1B LOT 629 4/O 95 55 3 30 2 4.1 3.5 -
H1B LOT 630 4/O 100 55 3 35 3 4.2 3.5 -
V02 H2A 350 50 3 50 2 1.9 1.1 -
V02 H2B 350 150 3 150 2 3 2.5 1.8 -
V02 LOT 590 1/O 45 55 3 45 1 2.9 2.6 -
V02 LOT 591 1/O 50 55 3 50 1 2.9 2.7 -
V02 LOT 627 1/O 105 55 3 40 3 3.7 3.7 -
V02 LOT 628 1/O 100 55 3 35 2 3.6 3.6 -
H2A LOT 588 1/O 55 3 2.7 2.1 -
H2A LOT 589 1/O 55 3 2.7 2.1 -
H2A LOT 626 1/O 90 55 3 25 2 3.9 3.7 -
H2B LOT 586 1/O 10 55 3 10 1 3.4 2.9 -
H2B LOT 587 1/O 55 3 3.2 2.7 -
V03 H3A 350 130 3 130 2 3.1 2.1 -
V03 LOT 580 1/O 50 55 3 50 1 3.7 3.1 -
V03 LOT 581 1/O 45 55 3 45 1 3.6 3.1 -
V03 LOT 582 1/O 45 55 3 45 1 3.6 3.1 -
V03 LOT 583 1/O 50 55 3 50 1 3.7 3.1 -
V03 LOT 584 4/O 120 55 3 120 1 2 3.8 3.4 -
V03 LOT 585 4/O 125 100 3 125 1 2 3.8 3.4 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H3A LOT 578 1/O 55 3 3.9 3.1 -
H3A LOT 579 1/O 55 3 3.9 3.1 -
V04 H4A 350 95 3 95 2 3.0 1.9 -
V04 LOT 575 1/O 15 55 3 15 1 3.0 2.5 -
V04 LOT 576 1/O 40 55 3 40 1 3.3 3.0 -
V04 LOT 577 1/O 45 55 3 45 1 3.4 3.1 -
H4A LOT 573 1/O 55 3 3.7 2.9 -
H4A LOT 574 1/O 55 3 3.7 2.9 -
H4A LOT 612 4/O 85 55 3 20 3 4.3 3.7 -
H4A LOT 613 4/O 80 55 3 15 2 4.3 3.6 -
V05 H5A 350 45 3 45 2 2.7 2.1 -
V05 LOT 570 1/O 20 55 3 20 1 3.3 3.2 -
H5A LOT 571 1/O 55 3 3.4 3.1 -
H5A LOT 572 1/O 55 3 3.4 3.1 -
H5A LOT 610 4/O 90 55 3 25 3 3.7 3.5 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H5A LOT 611 4/O 85 55 3 20 2 3.6 3.5 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V06 H6A 350 175 3 110 3 3.2 2.4 -
V06 H6B 350 125 3 125 2 2.9 2.1 -
V06 LOT 598 1/O 15 55 3 15 1 3.0 2.5 -
V06 LOT 599 1/O 40 55 3 40 1 3.3 3.0 -
V06 LOT 600 1/O 45 55 3 45 1 3.4 3.1 -
H6A LOT 596 1/O 55 3 4.0 3.4 -
H6A LOT 597 1/O 55 3 4.0 3.4 -
H6B LOT 601 1/O 55 3 3.6 3.0 -
H6B LOT 602 1/O 55 3 3.6 3.0 -
V07 H7A 350 160 3 95 3 3.8 2.3 -
V07 LOT 603 1/O 45 55 3 45 1 3.6 3.1 -
V07 LOT 604 1/O 40 55 3 40 1 3.5 3.0 -
V07 LOT 605 1/O 50 55 3 50 1 3.7 3.1 -
V07 LOT 606 1/O 55 55 3 55 1 3.8 3.2 -
H7A LOT 618 1/O 55 3 4.5 3.3 -
H7A LOT 619 1/O 55 3 4.5 3.3 -
H7A LOT 620 4/O 90 55 3 25 3 4.8 3.7 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H7A LOT 621 4/O 85 55 3 20 2 4.7 3.6 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
V08 H8A 350 105 3 105 2 3.2 1.9 -
V08 LOT 614 1/O 15 55 3 15 1 3.2 2.5 -
V08 LOT 615 1/O 10 55 3 10 1 3.1 2.4 -
V08 LOT 624 1/O 80 55 3 15 1 4.1 3.7 -
V08 LOT 625 1/O 85 55 3 20 2 4.2 3.8 -
H8A LOT 616 1/O 55 3 4.0 2.9 -
H8A LOT 617 1/O 55 3 4.0 2.9 -
H8A LOT 622 4/O 80 55 3 15 2 4.6 3.7 -
H8A LOT 623 4/O 85 55 3 20 3 4.6 3.7 -
SECONDARY CABLE & CONDUIT TABLE (Cont.)
LOCATION
CABLE CONDUIT VOLTAGE ASBUILT INFORMATION
SIZE LENGTH ASSUMED SIZE LENGTH BENDS DROP FLICKER Foreman - Complete
FROM TO (1/O,4/O,350)Design (ft)Lot Corner to
Meter (ft)(in)Design (ft)90°45°22°11°(Percent)(Percent)Actual Amount Installed Cable Conduit
V09 H9A 350 135 3 135 2 1 2.6 1.7 -
V09 LOT 561 1/O 10 55 3 10 1 2.4 2.0 -
V09 LOT 562 1/O 15 55 3 15 1 2.5 2.1 -
V09 LOT 563 1/O 60 55 3 60 1 3.1 2.9 -
V09 LOT 564 1/O 110 55 3 110 1 3.8 3.8 -
V09 LOT 607 1/O 80 55 3 15 1 3.4 3.2 -
V09 LOT 608 4/O 145 55 3 80 2 3.2 3.2 -
H9A LOT 558 4/O 105 55 3 105 1 4.1 3.6 -
H9A LOT 559 1/O 55 3 3.4 2.6 -
H9A LOT 560 1/O 55 3 3.4 2.6 -
V10 H10A 350 90 3 90 2 2.6 1.8 -
V10 LOT 567 1/O 45 55 3 45 1 3.2 3.1 -
V10 LOT 568 1/O 45 55 3 45 1 3.2 3.1 -
V10 LOT 569 4/O 95 55 3 95 1 1 3.3 3.2 -
H10A LOT 609 4/O 125 55 3 60 2 3.8 3.6 "LABEL YELLOW TAG "MUST BE 4/0 TO MTR"
H10A LOT 565 1/O 55 3 3.3 2.8 -
H10A LOT 566 1/O 55 3 3.3 2.8 -
1/O UG Triplex (ft) =1555 3" PVC & BENDS (ft)=3240 103 0 9 0 11.1
4/O UG Triplex (ft) =1755 TOTAL QTS OF GLUE 11.1
350 UG Triplex (ft) =1360
CONTINUED AT RIGHT