Yelm Boys & Girls SubmittalsProduct Data
This unit has been designed utilizing Carrier’s Puron refrigerant. The
environmentally sound refrigerant allows you to make a responsible
decision in the protection of the earth’s ozone layer.
NOTE: Ratings contained in this document are subject to change at any
time. Always refer to the AHRI directory (www.ahridirectory.org) for
the most up-to-date ratings information.
Industry leading Features / Benefits
Efficiency
•13.8 - 16.5 SEER2 (14 - 18.0 SEER) /
11.2 – 14.0 EER2 (11.2 - 14.5 EER)
•Microtube Technology refrigeration system
•Indoor air quality accessories available
Reliability
•Puron refrigerant - environmentally sound, won’t deplete the ozone
layer and low lifetime service cost.
•Scroll compressor
•Internal pressure relief valve
•Internal thermal overload
•Filter drier
Durability
WeatherArmor™ Ultra Protection Package:
• Solid, Durable sheet metal construction
•Steel louver coil guard
•Baked-on, complete outer coverage, powder paint
Applications
•Long–line – up to 250 feet (76.20 m) total equivalent length, up to 200
feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.4 m)
evaporator above condenser (See Long Line Guide for more
information.)
•Low ambient cooling (down to 0°F / -18°C ) with approved low
ambient accessory kits.
24SPA6
Performance Series Single-Stage Air Conditioner
with Puron® Refrigerant
1-1/2 To 5 Tons
STANDARD FEATURES
Features 18 24 30 36 42 43 48 49 60 61
Puron Refrigerant X X X X X X X X X X
SEER2
(Range depending on indoor combination)14.3 - 16 14.3 - 16 14.3 - 16 14.3 - 16 13.8 - 15 14.3 - 16 13.8 - 15 14 - 16 13.8 - 15 14 - 16
Scroll Compressor X X X X X X X X X X
Field Installed Filter Drier X X X X X X X X X X
Front Seating Service Valves X X X X X X X X X X
Internal Pressure Relief Valve X X X X X X X X X X
Internal Thermal Overload X X X X X X X X X X
Long Line Capability X X X X X X X X X X
Low Ambient Capability with Kit X X X X X X X X X X
High Pressure Switch X X X X X X X X X X
Low Pressure Switch X X X X X X X X X X
Compressor Sound Blanket X X X X X X X X X X
Louvered Coil Guard X X X X X X X X X X
24SPA6: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
Model Number Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12
N N A A A/N N N N A/N A/N A/N N
2 4 S P A 6 1 8 W 0 0 3
Product Series
/ Refrigerant Design Type Tier Major
Series SEER2 Cooling
Capacity Region Feature Special Feature Voltage
24 =AC w/
R-410A S = Single Stage P = Performance
Series A=Initial 6 = 16 SEER2 1,000 Btuh
(nominal)
W = Standard
SW AC 0=Standard 0=Standard 3=208/230-1
CATALOG ORDERING NUMBERS
Size Model Number
18 24SPA618W003
24 24SPA624W003
30 24SPA630W003
36 24SPA636W003
42 24SPA642W003
43 24SPA643W003
48 24SPA648W003
49 24SPA649W003
60 24SPA660W003
61 24SPA6610W003
Physical Data
Unit Size 18 24 30 36 42 43 48 49 60 61
Compressor Type Scroll
REFRIGERANT Puron (R-410A)
Control TXV (Puron Hard Shutoff)
Factory Charge lb (kg)*
*. For 15 ft. Line Set
4.70 (2.13)5.60 (2.54)6.60 (2.99)6.80 (3.08)8.10 (3.67)11.70 (5.31)8.10 (3.67)12.40 (5.62)10.10 (4.58)14.50 (6.58)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM)2050 2600 2575 3700 3890 3223 3890 4090 4260 4320
Motor HP 1/12 1/10 1/10 1/4 1/4 1/12 1/4 1/3 1/4 1/3
Motor RPM 1100 1100 1100 1100 1100 800 1100 800 1100 800
COND COIL
Face Area (Sq ft)11.5 14.7 19.4 21.5 17.2 25.15 17.2 30.1 21.5 30.1
Fins per In.25 25 25 25 20 20 20 20 20 20
Rows 1 1 1 1 2 2 2 2 2 2
Circuits 3 4 5 6 8 8 8 10 9 12
VALVE CONNECT. (In. ID)
Vapor 3/4 3/4 3/4 7/8 7/8 7/8”7/8 7/8 7/8 7/8
Liquid 3/8"
REFRIGERANT TUBES* (In. OD)
Rated Vapor†
†.Units are rated with 25 ft. (7.6m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
3/4 3/4 3/4 7/8 7/8 7/8”7/8 7/8 1 1/8 1 1/8
Rated Liquid Line‡
‡.See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables
3/8"
24SPA6: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
REFRIGERANT PIPING LENGTH LIMITATIONS
Liquid Line Sizing and Maximum Total Equivalent Lengths for Cooling Only Systems with Puron®
Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor and outdoor
units.
See Table below for liquid line sizing and maximum lengths :
-- = outside acceptable range
Table 1 – Maximum Total Equivalent Length*
Outdoor Unit BELOW Indoor Unit
*.Maximum actual length not to exceed 200 ft (61 m)
Size Liquid Line
Connection
Liquid
Line Diam.
w/ TXV
AC with Puron Refrigerant Maximum Total Equivalent Length†: Outdoor unit BELOW Indoor
Vertical Separation ft (m)
†.Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
0-5
(0-1.5)
6-10
(1.8-3.0)
11-20
(3.4-6.1)
21-30
(6.4-9.1)
31-40
(9.4-12.2)
41-50
(12.5-15.2)
51-60
(15.5-18.3)
61-70
(18.6-21.3)
71-80
(21.6-24.4)
18 3/8
1/4 150 150 125 100 100 75 ------
5/16 250*250*250*250*250*250*250*225*150
3/8 250*250*250*250*250*250*250*250*250*
24 3/8
1/4 75 75 75 50 50 --------
5/16 250*250*250*250*250*225*175 125 100
3/8 250*250*250*250*250*250*250*250*250*
30 3/8
1/4 30 ----------------
5/16 175 225*200 175 125 100 75 ----
3/8 250*250*250*250*250*250*250*250*250*
36 3/8 5/16 175 150 150 100 100 100 75 ----
3//8 250*250*250*250*250*250*250*250*250*
42, 43 3/8 5/16 125 100 100 75 75 50 ------
3/8 250*250*250*250*250*250*250*250*150
48, 49 3/8 3/8 250*250*250*250*250*250*230 160 --
60, 61 3/8 3/8 250*250*250*225*190 150 110 ----
Table 2 – Maximum* Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
*.Maximum actual length not to exceed 200 ft (61 m)
Size Liquid Line
Connection
Liquid Line
Diam.
w/ TXV
AC with Puron Refrigerant Maximum Total Equivalent Length†: Outdoor unit ABOVE Indoor
Vertical Separation ft (m)
†.Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
-- = Outside acceptable range
25
(7.6)
26-50
(7.9-15.2)
51-75
(15.5-22.9)
76-100
(23.2-30.5)
101-125
(30.8-38.1)
126-150
(38.4-45.7)
151-175
(46.0-53.3)
176-200
(53.6-61.0)
18 3/8
1/4 175 250*250*250*250*250*250*250*
5/16 250*250*250*250*250*250*250*250*
3/8 250*250*250*250*250*250*250*250*
24 3/8
1/4 100 125 175 200 225*250*250*250*
5/16 250*250*250*250*250*250*250*250*
3/8 250*250*250*250*250*250*250*250*
30 3/8
1/4 30 --------------
5/16 250*250*250*250*250*250*250*250*
3/8 250*250*250*250*250*250*250*250*
36 3/8 5/16 225*250*250*250*250*250*250*250*
3/8 250*250*250*250*250*250*250*250*
42, 43 3/8 5/16 175 200 250*250*250*250*250*250*
3/8 250*250*250*250*250*250*250*250*
48, 49 3/8 3/8 250*250*250*250*250*250*250*250*
60, 61 3/8 3/8 250*250*250*250*250*250*250*250*
24SPA6: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz.(266.16 g). When using other length or diameter
liquid lines, charge adjustments are required per the chart above.
Charging Formula:
[(Lineset oz/ft X total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of lineset* using existing 1/4“ liquid line. What charge adjustment is required?
Formula:(.27 oz/ft X 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula:(.40 oz/ft. X 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
NOTE: Conditions must be favorable for charging by subcooling method. Indoor temperature must be 70°F to 80°F (21°C to 27°C), and outdoor
temperature must be 70°F to 100°F (21°C to 38°C). If outside these conditions, adjust charge for long linesets by weigh-in method.
* When applicable. Refer to Physical Data Table in this PD and to the Installation Instructions for more information.
Long Line Applications
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant
management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the
liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
Note: See Residential Piping and Long Line Guideline for details
Table 3 – Refrigerant Charge Adjustments
Liquid Line Size Puron Charge oz/ft (g/m)
3/8 0.60 (17.74)
(Factory charge for lineset = 9 oz / 266.16 g)
5/16 0.40 (11.83)
1/4 0.27 (7.98)
Table 4 – AC with Puron® Refrigerant Long Line Description ft (m) Beyond these lengths, a TXV is required
Total Length Outdoor Unit Above or Below Indoor Unit
TXV required beyond 50 ft. (15.2 m)TXV required beyond 20 ft. (6.1 m)
Table 5 – AC with Puron® Refrigerant Long Line Description ft (m) (Beyond these lengths, long line accessories are required)
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1/4 + TXV No accessories needed within allowed
lengths
No accessories needed within
allowed lengths 175 (53.3)
5/16 + TXV 120 (36.6)50 (15.2) vertical or 120 (36.6) total 120 (36.6)
3/8 + TXV 80 (24.4)35 (10.7) vertical or 80 (24.4) total 80 (24.4)
24SPA6: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line diameters
shown in the chart below are acceptable for AC systems with Puron® refrigerant:
Table 6 – Vapor Line Sizing and Cooling Capacity Losses — Puron® Refrigerant 1-Stage Air Conditioner Applications
Unit
Nominal
Size (Btuh)
Maximum
Liquid Line
Diameters
(In. OD)
Vapor Line
Diameters
(In. OD)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
1-Stage AC with Puron®
26-50
(7.9-15.2)
51-80
(15.5-24.4)
81-100
(24.7-30.5)
101-125
(30.8-38.1)
126-150
(38.4-45.7)
151-175
(46.0-53.3)
176-200
(53.6-61.0)
201-225
(61.3-68.6)
226-250
(68.9-76.2)
18 3/8
1/2 1 2 3 5 6 7 8 9 11
5/8 0 1 1 1 2 2 2 3 3
3/4 0 0 0 0 1 1 1 1 1
24 3/8
5/8 0 1 2 2 3 3 4 5 5
3/4 0 0 1 1 1 1 1 2 2
7/8 0 0 0 0 0 1 1 1 1
30 3/8
5/8 1 2 3 3 4 5 6 7 8
3/4 0 0 1 1 1 2 2 2 3
7/8 0 0 0 0 1 1 1 1 1
36 3/8
5/8 1 2 4 5 6 8 9 10 12
3/4 0 1 1 2 2 3 3 4 4
7/8 0 0 0 1 1 1 1 2 2
42, 43 3/8
3/4 0 1 2 2 3 4 4 5 6
7/8 0 0 1 1 1 2 2 2 3
1 1/8 0 0 0 0 0 0 0 0 0
48, 49 3/8
3/4 0 1 2 3 4 5 5 6 7
7/8 0 0 1 1 2 2 2 3 3
1 1/8 0 0 0 0 0 0 0 1 1
60, 61 3/8
3/4 1 2 4 5 6 7 9 10 11
7/8 0 1 2 2 3 4 4 5 5
1 1/8 0 0 0 1 1 1 1 1 1
Applications in this area may be long line and may have height restrictions. See the Residential Piping and Long Line Guideline.
24SPA6: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
AHRI RATINGS
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Ratings Database here: www.MyCarrierRatings.com
FLA- Full Load Amps
LRA - Locked Rotor Amps
MCA- Minimum Circuit Amps
RLA- Rated Load Amps
NOTE:Control circuit is 24V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with requirements of ASHRAE Standards 90.1
Short Circuit Current Rating (SCCR): 5kA rms
NOTE: Tested in compliance with AHRI 270 but not listed with AHRI.
Electrical Data
UNIT SIZE V/PH OPER VOLTS*
*.Permissible limits of the voltage range at which the unit will operate satisfactorily
COMPR FAN MCA MAX FUSE† or CKT BRK
AMPS
†.Time-Delay fuse.
MAX MIN LRA RLA FLA
18
208/230/1 253 197
42.6 8.8 0.4 11.4 20
24 59.5 10.9 0.6 14.2 20
30 71.3 11.7 0.6 15.2 25
36 80.1 12.2 1.4 16.7 25
42 120.0 25.0 1.52 32.8 50
43 109.0 16.7 0.50 21.4 35
48 120.0 25.0 1.52 32.8 50
49 124.0 18.5 2.80 25.9 40
60 150.0 25.6 1.40 33.4 50
61 140.6 26.3 2.80 35.7 50
A–Weighted Sound Power (dBA)
UNIT SIZE STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18 74 65.7 66.5 66.5 66.0 62.2 59.6 55.2
24 72 66.9 66.7 69.2 68.4 62.1 59.8 56.8
30 72 68.0 67.4 68.1 68.8 63.5 60.2 55.1
36 74 70.2 70.7 69.3 66.2 61.4 58.8 52.9
42 74 73.6 72.9 71.3 70.0 63.4 60.1 55.1
43 70 72.0 66.0 67.0 65.0 62.0 60.0 55.0
48 74 73.6 72.9 71.3 70.0 63.4 60.1 55.1
49 72 67.5 64.3 67.8 66.2 59.8 56.7 51.8
60 74 69.9 72.5 71.1 68.9 63.6 59.9 59.0
61 72 64.9 71.5 68.4 69.9 60.3 57.4 54.1
Charging Subcooling (TXV-Type Expansion Device)
UNIT SIZE REQUIRED SUBCOOLING (°F)Indoor
18 7
TXV
24 9
30 10
36 8
42 10
43 12
48 10
49 8
60 14
61 9
24SPA6: Product DataManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
DIMENSIONS
Product Data
A06009Fig. 1 – CAPMP
The CAPMP evaporator coil incorporates proven standards for reliable
system operation and performance throughout the life of this quality Air
Conditioner or Heat Pump system. These quality evaporator coils,
manufactured and installed as part of a total comfort system, provide
AHRI-rated performance ratings and are additionally listed with UL and
c-UL.
This coil is available for use with R-410A Puron® Refrigerant only. It is
a cased A-coil that is housed in a durable, 24-gauge, pre-painted taupe
metallic cabinet. The fully insulated cabinet (foil faced with R-2.1
insulation properties) provides for quiet efficient operation of the
evaporator coil. This multipoise coil offers the most in installation
application flexibility; one coil for a variety of applications with fewer
SKUs to stock.
DESIGN FEATURES
Performance
Designed with performance in mind, this new A-coil offers low pressure
drops to enhance system performance and airflow characteristics.
Thermostatic Expansion Valves (TXV)
All coils have refrigerant-specific, factory-installed TXVs.
Durable Condensate Pans (2)
The corrosion-resistant drain pans, one for vertical applications and one
for horizontal, are designed in a “fiberglass reinforced thermoset
polyester” material (FRTP) that offers unsurpassed pan strength. It is
engineered with proper slope in both pans to help ensure water drainage,
improved moisture removal, and home comfort.
Refrigerant Connections
Provided with industry proven sweat connections for leak-free operation
to maintain system reliability. The side mounting tubing to the coil slabs
allows for easy cleaning/servicing of the coils, as well as easy access to
the TXV.
Burst Pressure
Meets or exceeds burst pressure of 2100 psi, which is at least three to
five times the pressure it would see in actual application.
UV Knockouts
This cased coil comes with factory-installed UV knockouts for quick and
easy installation of UV lights.
Serviceability
Comes with a “split delta plate” for easy, quick access to the coil for
service and cleaning. Also, after the door is removed, the coil is
removable from the front of the unit without use of any tools.
CAPMP
Evaporator Coil
A Coil, Cased, Multipoise
CAPMP: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
MODEL NUMBER NOMENCLATURE
A221610
1 2 3 4 5 6 7 8 9 10 11 12
C A P M P 3 6 1 7 A L A
Product VariationsC = Coil A = Basic
Type Tubing Design
L = AluminumA = A Coil
Refrigerant Type
P = Puron® Refrigerant (R-410A) TXV Revision LevelA = 1st
Coil Configuration Cabinet Width
14 = 14-in (356 mm)
17 = 17-in (432 mm)
21 = 21-in (536 mm)
24 = 24-in (610 mm)
M = Multipoise
Cabinet FinishP = Painted Unit Capacity19 = 1 1/2 Ton
24 = 2 Ton
25 = 2 Ton
30 = 2-1/2 Ton
36 = 3 Ton
37 = 3 Ton
42 = 3-1/2 Ton
43 = 3-1/2 Ton
48 = 4 Ton
60 = 5 Ton
61 = 5 Ton
Use of the AHRI Certified TM Mark indicates
a manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org.
REGISTERED
ISO 9001:2000
CAPMP: Product DataManufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
DIMENSIONS (1 of 2)
A190313
Product Data
A11263Representative drawing only. Some product models may vary.
The 59SC6A Multipoise Comfort™Condensing Gas Furnace features
year-round electrical efficiency when paired with a compatible
condensing unit. Energy efficiency is at the heart of this furnace with up
to 97.0% AFUE, gas efficiency and the electrically-efficient
fixed-speeds, constant torque (MCT) ECM blower motor. Improved
serviceability with the 3 digit status display and NFC enabled board
allowing setup via the service tech app. This gas furnace also features
4-way multipoise installation flexibility, and is available in eleven model
sizes. All sizes except the 26,000 BTUh model can be vented for direct
vent/two-pipe, ventilated combustion air, or single-pipe applications.
The 26,000 BTUh model can use the same 2-pipe venting system using
outside air for combustion, but is not considered direct-vent. All sizes
are design certified in Canada, and select sizes are certified for
mobile/manufactured home use with conversion kit accessory.
PERFORMANCE
• Multi 18-speed, constant torque (MCT) ECM blower motor for
electrically efficient operation all year long in heating, cooling and
continuous fan operation.
• Enhanced diagnostics with easy to read 3-digit display for faults and
status.
• Single-speed inducer motor, and single-stage gas valve.
• Silicon Nitride PowerHeat
™ Hot Surface Igniter.
• Dual fuel capable HybridHeat
™ with a compatible heat pump and
thermostat for energy-saving heating performance
• Adjustable blower speed for heating and cooling.
• Aluminized-steel primary heat exchanger.
• Stainless-steel condensing secondary heat exchanger.
INSTALLATION FLEXIBILITY
• On-board NFC antenna makes setup a tap away when using the
Carrier service technician app.
• 4-way multipoise design for upflow, downflow or horizontal
installation, with unique vent elbow for optional venting
through-the-cabinet downflow venting capability.
• Factory-configured ready for upflow applications.
• Ideal height 35” (889 mm) cabinet: short enough for taller coils, but
still allows enough room for service.
• Two-pipe venting, single-pipe venting or ventilated combustion air.
APPLICATIONS
• Approved for Twinning applications with manufacturer’s approved
accessory kit.
• Approved for Manufactured Housing/Mobile Home applications with
MH accessory kit.
• Convertible to propane with gas conversion accessory kit.
CERTIFICATIONS
• All sizes meet ENERGY STAR
® Version 4.1 criteria for gas furnaces:
95%+ AFUE.
• Cabinet air leakage less than 2.0% at 1.0 in. w.c. and cabinet air
leakage less than 1.4% at 0.5 in. w.c. when tested in accordance with
ASHRAE standard 193.
• All sizes can be installed in air quality management districts with a 40
ng/J NOx emissions requirements.
•
A200351
59SC6A
Comfort™ 96, Single-Stage, Multi 18-Speed ECM,
Condensing Gas Furnace
WARNING!
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
This furnace is not designed for use in recreation vehicles or outdoors.
This furnace is designed for use in manufactured (Mobile) homes
when an optional Mobile Home accessory kit is installed.
Failure to follow this warning could result in personal injury, death,
and/or property damage.
59SC6A: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
A210796
Dimensional Drawing
Dimensions
FURNACE SIZE A B C D SHIP WT.
LB (KG)CABINET WIDTH OUTLET WIDTH BOTTOM INLET WIDTH AIR INTAKE
026M14--10 14-3/16 (361) 12-1/2 (319)12-9/16 (322)7-1/8 (181)119 (54)
040M14--10 14-3/16 (361) 12-1/2 (319)12-9/16 (322)7-1/8 (181)123 (56)
040M17--12 17-1/2 (445)15-7/8 (403)16 (406)8-3/4 (222)130 (59)
060M14--12 14-3/16 (361) 12-1/2 (319)12-9/16 (322)7-1/8 (181)129 (59)
060M17--16 17-1/2 (445)15-7/8 (403)16 (406)8-3/4 (222)142 (64)
080M17--16 17-1/2 (445)15-7/8 (403)16 (406)8-3/4 (222)150 (68)
080M21--20 21 (533)19-3/8 (492)19-1/2 (495)10-1/2 (267)158 (72)
100M21--20 21 (533)19-3/8 (492)19-1/2 (495)10-1/2 (267)167 (76)
100M21--22 21 (533)19-3/8 (492)19-1/2 (495)10-1/2 (267)167 (76)
120M24--22 24-1/2 (622)22-7/8 (581)23 (584)12-1/4 (311)181 (82)
140M24--22 24-1/2 (622)22-7/8 (581)23 (584)12-1/4 (311)189 (86)
59SC6A: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
MODEL NUMBER NOMENCLATURE
A220581
FURNACE COMPONENTS
A190145For California Residents:
If installed with a manufactured (mobile) home conversion kit in
SCAQMD: This furnace does not meet the SCAQMD Rule 1111 14 ng/J
NOx emission limit, and thus is subject to a mitigation fee of up to $450.
This furnace is not eligible for the Clean Air Furnace Rebate Program:
www.CleanAirFurnaceRebate.com
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
The furnace should be sized to provide 100 percent of the design heating
load requirement plus any margin that occurs because of furnace model
size capacity increments. None of the furnace model sizes can be used if
the heating load is 12,000 BTUh or lower. Use Air Conditioning
Contractors of America (Manual J and S); American Society of Heating,
Refrigerating, and Air-Conditioning Engineers; or other approved
engineering method to calculate heating load estimates and select the
furnace. Excessive oversizing of the furnace may cause the furnace
and/or vent to fail prematurely, customer discomfort and/or vent
freezing.
Failure to follow these guidelines is considered faulty installation and/or
misapplication of the furnace; and resulting failure, damage, or repairs
may impact warranty coverage.
1, 2
Gas Furnace
59
3
Heating Stages
M
4
Tier
N
5
Min. AFUE/NOx
7
6
Major
Series
B
7, 8, 9
Heating Input
060
10
Motor Type
E
11, 12
Width
17
13
Voltage
(1-phase)
1
14
Minor Series
1
15, 16
Airflow
16
|||||| |||||
58 = 80%
Non-Condensing
59 = 90%+
Condensing M = Modulating
T = Two Stage
S = Single Stage
C = Single Stage
Communicating
1
2
3
---
08 = 800 CFM
10 = 1000 CFM
12 =1200 CFM
14 = 1400 CFM
16 = 1600 CFM
20 = 2000 CFM
22 = 2200 CFM
B = Base
C = Comfort
E = Export
N = Infinity
P = Performance
U = Ultra Low
Nox
0 = 80%
1 = 80% Low NOx
(Not Ultra Low
NOx)
2 = 92%
5 = 95%
6 = 96%
7 = 97%
8 = 98%
1 = 110V/60Hz
2 = 230V/50Hz
C = Constant Airflow
Variable- Speed
(VCA) ECM
V = Variable-Speed
(VCT) PWM
M = Multi 18-Speed
Constant Torque
(MCT) ECM
026 = 26,000 BTU
040 = 40,000 BTU
060 = 60,000 BTU
---
155 = 155,000 BTU
A
B
C
---
14 - 14.2"
17 - 17.5"
21 - 21.0"
24 - 24.5"
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
GAS VALVE
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
FURNACE
CONTROL
BOARD
MANUAL RESET
ROLLOUT SWITCH
FLAME
SENSOR
MANUAL RESET
ROLLOUT SWITCHGAS BURNER
HOT SURFACE
IGNITER
INDUCER MOTOR
ASSEMBLY
BLOWER AND
MOTOR
BLOWER DOOR
SAFETY SWITCH
POSITION CLEARANCE
REAR 0
FRONT (Combustion air openings in
furnace and in structure)1 in. (25 mm)
Required for service *24 in. (610 mm)
*. Consult local building codes
All Sides of Supply Plenum *1 in. (25 mm)
Sides 0
Vent 0
Top of Furnace 1 in. (25 mm)
59SC6A: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
SPECIFICATIONS
Unit Size 026M14--10 040M14--10 040M17--12 060M14--12 060M17--16
080M17--16
HEATING AND CAPACITY AND EFFICIENCY
Input BTUh*
*. Gas input ratings are certified for elevations to 2000 ft. (610 M). In USA, For elevations above 2000 ft (610 M), reduce ratings 4 percent for each 1000 ft (305 M) above sea
level. Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 Table F.4 or furnace installation instructions.
26,000 40,000 40,000 60,000 60,000 80,000
Output Capacity (BTUh)†)
†. Capacity in accordance with U.S. Government DOE test procedures.
25,000 39,000 39,000 56,000 58,000 78,000
Certified Temperature Rise Range - °F (°C)25-55
(14-31)
40-70
(22-39)
40-70
(22-39)
35-65
(19-36)
40-70
(22-39)
40-70
(22-39)
AFUE Upflow/Hz 96.0% 96.0% 96.7% 95.0% 97.0% 97.0%
Downflow 95.0% 95.0% 95.0% 95.0% 95.0% 95.0%
AIRFLOW CAPACITY AND BLOWER DATA
Rated Certified External
Static Pressure
Heating 0.10 0.10 0.10 0.12 0.12 0.12
Cooling 0.50 0.50 0.50 0.50 0.50 0.50
Airflow CFM @ Rated ESP
(CFM)‡
‡. Airflow shown is for bottom only return-air supply for the as-shipped speed tap. For air delivery above 1800 CFM, see Air Delivery table for other options. A filter is required
for each return-air supply. An airflow reduction of up to 7 percent may occur when using the factory-specified 4-5/16-in. (110 mm) wide, high efficiency media filter.
Heating 620 705 700 945 1030 1290
Cooling 175-970 155-1000 160-1075 200-1165 315-1580 370-1625
Direct Drive Motor HP 1/3 1/2 1/2 1/2 3/4 3/4
Motor Full Load Amps 4.4 6.3 6.7 6.3 8.8 9.2
Heating Blower Control (Htg OFF-Delay)Adjustable: 90, 120 (factory-set), 150, 180 seconds
Cooling Blower Control (Clg OFF-Delay)Adjustable: 90 (factory-set), 5, 30 seconds
Blower Wheel Diameter x Width - In. (mm)11x7
(279x178)
11x7
(279x178)
11x8
(279x203)
11x7
(279x178)
11x8
(279x203)
11x8
(279x203)
Air Filtration System Field Supplied Filter
Filter used for Certified Watt Data 325531-40**
**. See Accessory List for part numbers available.
ELECTRICAL DATA
Unit Volts-Hertz-Phase 115-60-1
Operating Voltage Range Min-Max 104-127
Maximum Unit Amps 5.2 7.0 7.4 7.1 10.1 10.0
Unit Ampacity 7.5 9.7 10.2 9.8 13.6 13.4
Maximum Wire Length (Measure 1 way in Ft/M)50/15.2 38/11.7 36/11.1 38/11.5 27/8.3 27/8.4
Minimum Wire Size AWG 14 14 14 14 14 14
Max. Fuse/Ckt Bk Size
(Time-Delay Type
Recommended)
Amps 15 15 15 15 15 15
Transformer Capacity (24 VAC output)40VA
External Control Power
Available
Heating 12VA
Cooling 35VA
GAS CONTROLS
Burners 2 2 3 3 4 4
Gas Connection Size 1/2 in. NPT
Gas Valve (Redundant)Mfr White Rodgers™
Min. inlet pressure (in.w.c.)4.5 (Natural Gas)
Max. inlet pressure (in.w.c.)13.6 (Natural Gas)
Ignition Device Silicon Nitride
Factory installed orifice Size 44
CONNECTIONS
Communication System None
Thermostat Connections G,C, W, Y, R
Accessory Connections EAC-1 (115 VAC); HUM (24 VAC); 1-STG AC (via Y)