Project NarrativeProject Narrative For this project we will be installing a new addressable fire alarmsystem in building A which will wire to all the out buildings that haverisers in them for monitoring. We will install a pull station at every riserto provide an activation point if the risers are being serviced. There willbe outdoor notification on all buildings with risers and only the buildingin alarm will be annunciating outdoor. We will be installing boosterpanels in building D and L for the outdoor notification devices.Monitoring will be handled using a Starlink sole path cell dialer. TheSBUS between the buildings will be ran using direct bury 16/4c wire.The SLC circuit will be ran using 16/2c wire and then the NAC circuitswill be ran using 14/2c wire. We will be installing 12vdc 18ah Batteriesin the main FACP and then 12vdc 7ah Batteries in the 2 booster panels. about this submittal please contact Brian Rudebeck at 360-801-5150 / brian@birdelectric.com For any questions and concerns please contact