2021.0028-2021.0028 7677 - Tahoma Blvd Apts - Bldg 1 - Sprinkler Plan-approvedBATT TYPE INSULATION TENTED OVER ALL
ATTIC SPRINKLER PIPE (BY OTHERS)9'-0"9'-0"FLOOR LINE
R-10 RIGID INSUL
TOP OF SLAB
12
SAND AND GRAVEL BASE.
2 X 4 STUDS AT 16" O.C. WITH 5/8" GYP. BD.
MANUF. TRUSSES
MANUF. TRUSSES
(WARM SIDE)
GABLE END VENT
2X6 OVERFRAME
4
TOP PLATE
FLOOR LINE
RUN 24" MIN BELOW
4" CONC. SLAB W/ 6 MIL. VAPOR
RUN 24" MIN BELOW
INTERIOR WALLS-
GABLE-END
PER TRUSS MANUF
24" O.C. MAX
VAPOR BARRIER
@ 24" O.C.
12
TOP PLATE
SEE STRUCTURAL
TOP OF SLAB
4
BARRIER OVER 4" COMPACT
R-10 RIGID INSUL
UNLESS OTHERWISE NOTED.
24" O.C. MAX
2 X 6 STUDS AT 16" O.C. @ RESTROOMS
SEE EXT ELEVATIONS
GIRDER TRUSS
R-49 INSULATION W/ CONT.
UNIT B
KITCHEN LIVING
LIVING
KITCHEN
LIVINGKITCHEN
UNIT BUNIT B
KITCHEN
LIVING
UNIT B
32280.4'
2-BED UNIT
UNIT 2B 2-BED UNIT
UNIT 2D
2-BED UNIT
UNIT 2A 2-BED UNIT
UNIT 2C
32280.4'
UP
UP
W D
D
W D
D
W
W 1¼ -DN1¼ -DN1¼ -DN1¼ -DN1002
1001
1004 1003
1
1
1
11
1
1111
1
1
1
11
11
11
111
1 111
1
1 1 111111 11
111 11
111
111
1 1111
1 11
11
11
111
1
11
111
11
1 11
11111
1 11 1 11
1
1
111 111
1
1
1111
111122
120
101
102
121
103
8'-0" CLG
BEDROOM
KITCHEN
9'-0" CLG
WIC
9'-0" CLG
MSTR
<55FT²
LIVING ROOM
BEDROOM 3
LIVING ROOM
BEDROOM BEDROOM
9'-0" CLG
9'-0" CLG
MSTR
8'-0" CLG
LIVING ROOM
9'-0" CLG
BEDROOM 3
<55FT²
UTILITY
BATH
LIVING ROOM
WIC
BATH
UTILITY
MSTR
WICBEDROOM 3
MSTR
9'-0" CLG
9'-0" CLG
BATHBATH
WIC
9'-0" CLG
UTILITY
BATH
<55FT²
UTILITY
KITCHEN
9'-0" CLG
BATHBATH
9'-0" CLG
BEDROOM 3
8'-0" CLG
9'-0" CLG
9'-0" CLG
<55FT²
BEDROOM
8'-0" CLG
KITCHENKITCHEN
BATH
CONC.PATIO
CONC.PATIO CONC.
PATIO
PATIO
CONC.
2
(UNDERGROUND)
1FP1
2-BED UNIT
UNIT D
*1B
TYPE 'B' UNIT
2-BED UNIT
UNIT D
*1D
TYPE 'B' UNIT
2-BED UNIT
UNIT D
*1A
TYPE 'B' UNIT
2-BED UNIT
UNIT D
*1C
TYPE 'B' UNIT
32280.4'
UP
UP
D
W
W W
W
D
D
D 2 -DN112 2 -DN1112 -UP1
1
1
1
11¼11111
1
1
11
1
1
11
11¼
1 11¼
1
111 11
1111¼1¼1¼111
1
1¼1¼1¼1¼1
1
1 11¼11
1
11
1
11
11
11
11¼
1 1¼1¼1¼11
11
11
1 1¼1111111111¼1¼11¼111111111¼1¼1½1½1½1½1½1½1½
1½1¼107
106
124
123
108 105
109 104
110 1¼ -UP1¼ -UP1¼ -UP1¼ -UPMSTRBEDROOM
9'-0" CLG
8'-0" CLGBEDROOM 39'-0" CLG
WIC
BATH<55FT²BATH
LIVING ROOM
9'-0" CLG
KITCHENUTILITY
9'-0" CLG
<55FT²
BEDROOM 3
BEDROOM
UTILITY LIVING ROOM
BATH
WIC
MSTR
KITCHEN
BATH
8'-0" CLG
9'-0" CLG
BEDROOM
9'-0" CLG
9'-0" CLG
BEDROOM 3
BEDROOM
MSTR
LIVING ROOM
BEDROOM 3
UTILITY
LIVING ROOM
BATH
WIC
MSTR
9'-0" CLG
BATH
WIC
UTILITY
<55FT²
KITCHEN
BATH
9'-0" CLG8'-0" CLG
9'-0" CLG
8'-0" CLG
KITCHEN
BATH
CONC.PATIO
CONC.PATIO PATIOCONC.
CONC.PATIO
<55FT²
9'-0" CLG9'-0" CLG GRAVEL91' PVC211' PVC6"6"61' PVC2"TAHOMA BOULEVARD SE105' DI 52
30' DI 52
33' PVC
1
0
5
'
D
I
5
2
27' DI 526' DI 5256' PVC10' PVC
178' PVC52' PVC224' PVC
127' PVC32' PVC2"7' PVC
2"
10' PVC 6"6"
8
"6"6"
6"6"6"
2"2"2"30' PVC9' PVC
2"2"2"
6"
4 -
1" MALE ADAPTER
2" DERINGER 30 (DCDA)
WIRING OF FLOW SWITCH AND BELL TO BE BY OTHERS
(INSTALLATION AND
6
ALL CONTROL VALVE HANDLES TO BE REMOVED2
RISER LEGEND
2"2"1" VALVE FOR DRAIN5 -
GRADE
1 -
2" FEMALE ADAPTER
2 -
7
1 -
3
2"2"2" CHECK VALVE
2" MALE ADAPTER
2"
1½"11" DRAIN LINE PIPED TO EXTERIOR OF BUILDING
FSI START
6 -
2 -
2" SUPPLY LINE TO BE PROVIDED BY OTHERS
WIRING BY OTHERS)
8
RISER NOTES
6" 120VAC ALARM BELL
4
7 -2"1½"2"3'-0"WATER PRESSURE GAUGE
8 -9 -
3 -
GRADE
3 -
WATER FLOW SWITCH.2" WATER SUPPLY LINE
AND PLACED IN HEAD BOX AT TIME OF FINAL
TO BE CONNECTED TO
5
UPRIGHT SPRINKLER TO PROTECT RISER
1
6" ALARM BELL INSTALLED ON EXTERIOR OF BUILDING
9
WATER FLOW ALARM SWITCH WIRED TO ALARM BELL
2" CHECK VALVE
2"
10 -TO REMOTE FDC (BY OTHERS)
10
FSI START2" MALE ADAPTER 2"SCOPE OF WORK:
INSTALL NEW NFPA 13R FIRE SPRINKLER SYSTEM THROUGHOUT NEW RESIDENCE PER NFPA 13R (2019)
GENERAL NOTES:
1. IT IS THE RESPONSIBILITY OF THE OWNER TO MAINTAIN THE INTEGRITY OF THE SPRINKLER SYSTEM.
2. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL AND/OR FM APPROVED.
3. ALL SYSTEM PIPING SHALL BE TESTED AT STATIC PRESSURE PER NFPA 13D.
4. PIPE HANGER AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA #13D (2019).
5. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS
PROTECTED BY A WET PIPE SPRINKLER SYSTEM.
6. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE
RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL REPRESENTATIVE.
7. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS.
DESIGN NOTES:
1. RISER ASSEMBLY LOCATED IN ATTACHED RISER ROOM (FSI START POINT).
2. SYSTEM TO BE DESIGNED IN ACCORDANCE WITH NFPA #13R MULTI FAMILY RESIDENCE.
3. PLAN SUBMITTAL TO AND APPROVAL BY CITY OF YELM.
4. MATERIALS PER NFPA #13R STANDARDS AS SELECTED BY FSI.
5. TESTING PER NFPA #13R AND CITY OF YELM.
6. TYPICAL HANGERS TO BE TOLCO FIG. 24, 28M & 29 UNLESS NOTED OTHERWISE
FIELD NOTES:
1. ALL NEW PIPE IS TO BE CPVC.
2. ALL NEW FITTINGS ARE TO BE CPVC.
3. DESIGN CRITERIA TO BE BASED ON NFPA 13R:
A. SPRINKLER SPACING NOT TO EXCEED (16' X 16') OR (8') OFF OF WALLS MAXIMUM.
B. MINIMUM PRESSURE AND FLOW FOR SPRINKLERS SPACED 16' X 16' = 13 GPM @ 7 PSI.
TOLCO FIG. #28M
NTS
HANGER TYPE CP
ATTIC INSULATION (BY OTHERS).
BOTTOM CHORD OF TRUSS
USE BATT TYPE INSULATION
GWB CEILING
(BY OTHERS). USE BATT TYPE
TENT FIRE SPRINKER PIPEBEFORE INSULATING ATTIC
WET PIPE FREEZE
CPVC FIRE SPRINKLER PIPE
FOR TENTING
INSULATION FOR TENTING.
NTS
PROTECTION DETAIL
TOLCO FIG. #24
NTS
HANGER TYPE CP
NTS
HANGER TYPE CP
TOLCO FIG. #29
FP1
1
½"8QR½"155QRWHC. PENDBRC. PEND200804.9BR4.9WHN/A1551QR½"BR5.61"QR155CH8CH5.61"RA1664DRY ECSWQR155RELIABLECH6CHDRY HSWVK494VIKINGVIKINGVK494VIKNGVK178UPRIGHTVIKINGVK4674.9REVISIONS:
REV#
DATE:
SCALE:
DATE BY
HANGER LEGEND:
DESCRIPTION
AHJ:
CONTRACT WITH:
SHEET NUMBER:
REVIEWED BY:
DRAWN BY:
JOB NUMBER:
DRAWING SYMBOLS:QTY103SPRINKLER LEGENDSYMMFRSINRESPTYPEKTEMPTHRDFINISHESCTOTAL THIS PROJECT =T
D TOP BEAM CLAMP W/ STRAP
H
X -
S SAMMY SUPER SCREW (GST20/30)
TRAPEZE
CP CPVC HANGER
HILTI KWIK HUS-EZ
SD SAMMY SIDEWINDER (SWDR 516)
(SEE CHART)
- ELEVATION
- CENTERLINE
A.1
- HYDRAULIC NODE
- WELDED - FLEXIBLE GROOVED
FFAFF
CC
DATUMDATUM
1
COUPLING
- BRANCHLINE
- ELEVATION10'-10"- SEISMIC BRACE LL
TSTS
DECK
PIPE TAG
DECK
& LENGTH CUT
#1 NUMBER
- CENTERLINE
9'-0- PIPE HANGER - PIPE SIZE
- RIGID GROOVED
CAC
LL0'-10"0'-10"OF PIPE TOOF PIPE TO
COUPLING
AS NOTED
CCS
05/17/22
7677
CITY OF YELM
JNZ
FP1 OF 1 YELM, WA 9859715035 BERRY VALLEY ROAD SETAHOMA BLVD APARTMENTSPUYALLUP, WA 98371
SCHUUR BROS INC
GC: JERRY SCHUUR - 253-651-3786
PO BOX 597
1524 45TH STREET EAST,
SUITE 102
SUMNER, WA 98390
(253) 826-0099WWW.FIRESPRINKLERSINC.COM
BUILDING SECTION A
SCALE: NTS
SCALE: 1/8" = 1'-0"NORTHVICINITY MAP
NORTHSCALE: 1/8" = 1'-0"
MAIN FLOOR - SPRINKLER PIPING PLAN
NORTHSCALE: NTS
UPPER FLOOR - SPRINKLER PIPING PLAN
SCALE: NTSNORTH
BUILDING 1 SITE PLAN
SCALE: NTS
RISER DETAIL
HYDRAULICALLY DESIGNED
GPM FLOWING:
54
1130
56
HYDRAULICALLY DESIGNED
DATE & TIME:
THIS SYSTEM IS NOT
RESIDUAL:
-
THIS SYSTEM IS
STATIC:
- FLOW TEST -
HYDRAULIC DESIGN INFO
"OFFSET" HANGER & RESTRAINER
HARDENED HEX HEAD SELF THREADING SCREWIS FURNISHED WITH THE HANGER AND IS THEMINIMUM FASTENER SIZE ACCEPTABLE
FOR CPVC AND IPS PIPE
HARDENED HEX HEAD SELF THREADING SCREWIS FURNISHED WITH THE HANGER AND IS THEMINIMUM FASTENER SIZE ACCEPTABLE
CPVC DOUBLE FASTENER STRAP TYPE HANGER "DOUBLE OFFSET" HANGER & RESTRAINER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
WA CL# FIRESI*988RJ
X
GATE VALVE (BY OTHERS)
2½" X 2½" SINGLE OUTLET OPEN SNOOT FDC (BY OTHERS)
+/- 175' OF 2" PVC SUPPLY (BY OTHERS)
DCDA LOCATED INSIDE RISER ROOM
FIRE SPRINKLER RISER ROOM W/ KNOX BOX (BY OTHERS)
FIRE HYDRANT
EXISTING 8" WATER MAIN
(EFFECTIVE POINT
OF FLOW TEST)
6" PVC SITE SUPPLY
(BY OTHERS)
FIRE HYDRANT (BY OTHERS)
YARD POST INDICATING VALVE (BY OTHERS)
BLDG 3BLDG 2
THIS PERMIT
BLDG 4
BLDG 1
115
116
117
118
1
111
110
112
113
114
112
SITE
16' X 16'
RESIDUAL:
HYDRAULIC DESIGN INFO
52.60 GPM @ 44.507 PSI
THIS AREA HAS BEEN HYDRAULICALLY CALCULATEDTO DELIVER A RESIDENTIAL COVERAGE (NFPA 13D)
OF:
REMOTE AREA #1
MAX AREA/HEAD:
SYSTEM DEMAND:
DENSITY:
K-FACTOR:
HYDRAULICALLY DESIGNED
THIS SYSTEM IS
54
HYDRAULICALLY DESIGNED
AREA 1
56
.05 GPM / SQ FT
-DATE & TIME:
4.9K
13 GPM @ 7.0 PSI USING 16' X 16' HEAD SPACING
GPM FLOWING:
- SYSTEM DESIGN -
- FLOW TEST -
REMOTE AREA:
THIS SYSTEM IS NOT
STATIC:
1130
Christopher Cameron Smith
0087-0618-C Level 3
Fire Sprinklers Incorporated
FIRESI*988RJ
05/23/2022Detail provided by
applicant.
NFPA 13R-Section 6.8.9 requires piping shall be provided
downstream of all back flow prevention valves for forward flow
tests at at a minimum flow rate of the system demand.
TOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
06/23/2022
4
No Comments
Comments Noted
on drawings