2021.0028-2021.0028 YELM APTS - BLDG 1 FIRE - 07-26-2022-approvedA 16 FPLR 2 SLC ADDRESSABLE CIRCUIT
B 14 FPLR 2 NOTIFICATION CIRCUIT
C 16 CI-FPLR SHIELDED 2 FIREFIGHTER PHONE VOICE CIRCUIT
D 16 CI-FPLR SHIELDED 2 FIREFIGHTER PHONE SLC CIRCUIT
E 16 FPLR 4 ANNUCIATOR CIRCUIT W/ 24VDC POWER
F 18 CMR 2 2-WAY COMMUNICATION SYSTEM POWER
G 18 TWISTED SHIELDED 2-PAIR CMR 2 2-WAY COMMUNICATION SYSTEM VOICE
H 24 CAT 5 CMP 8 TELCO SERVICE CONNECTION
I 16 TWISTED SHIELDED 2 VOICE EVACUATION SPEAKER CIRCUIT
J 14 FPLP 2 24VDC AUX POWER CIRCUIT
TAHOMA APARTMENTS
BUILDING 1
15035 BERRY VALLEY RD. SE
YELM, WA 98597
HVAC CONTRACTOR SHALL PROVIDE, INSTALL AND PROVIDE POWER TO ANY REQUIRED DUCT
DETECTORS. HVAC CONTRACTOR SHALL ALSO MAKE ALL CONNECTIONS AND TERMINATIONS TO HVAC
SYSTEMS TO FACILITATE FAN SHUT DOWN FROM DUCT DETECTORS AND HVAC CONTRACTOR SHALL
ALSO MAKE AVAILABLE A COMMON TERMINATION POINT FOR CONNECTION TO THE FIRE ALARM
SYSTEM TO FACILITATE FAN SHUT DOWN UPON RECEIPT OF A GENERAL FIRE ALARM IF SUCH A
FUNCTION IS REQUIRED PER APPLICABLE BUILDING CODES.
ELEVATOR CONTRACTOR SHALL MAKE ALL NECESSARY CONTROL CONNECTIONS INSIDE ELEVATOR
CONTROL EQUIPMENT AND PROVIDE A REPRESENTATIVE IN A TIMELY MANNER TO FACILATE AN
ELEVATOR SYSTEMS PRETEST PRIOR TO REQUESTING AN ELEVATOR SYSTEMS FINAL INSPECTION,
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED 120V 20 AMP DEDICATED CIRCUITS AS
NECESSARY TO POWER ALL FIRE ALARM CONTROL EQUIPMENT AND LABEL ELECTRICAL SERVICE
PANEL CLEARLY IN RED TO INDICATE FIRE ALARM POWER CIRCUITS. ALL FIRE ALARM POWER CIRCUIT
BREAKERS WILL HAVE LOCK OUT DEVICES INSTALLED BY ELECTRICAL CONTRACTOR.
ELECTRICAL CONTRACTOR SHALL PROVIDE AND TERMINATE ALL REQUIRED CONNECTIONS TO SMOKE
DAMPERS IF PRESENT AND PROVIDE AND TERMINATE THE LINE VOLTAGE POWER CONNECTIONS TO A
24VDC COIL RELAY LOCATED AT THE FIRE ALARM CONTROL PANEL TO FACILITATE CONNECTION TO
SAID RELAY FOR THE PURPOSE OF ACTIVATING SMOKE DAMPER UPON RECEIPT OF GENERAL FIRE
ALARM
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT NECESSARY TO FACILITATE ACCESS TO
OTHERWISE UNREACHABLE PORTIONS OF THE STRUCTURE AND/ OR LOCATIONS DETACHED FROM THE
STRUCTURE THAT REQUIRE CONNECTION TO FIRE ALARM SYSTEM INCLUDING BUT NOT LIMITED TO
SPRINKLER SYSTEM POST INDICATOR, VALVES REMOTE WATER SUPPLY PITS THAT WILL CONTAIN
TAMPER SWITCHES, ETC.
6)ELECTRICAL CONTRACTOR SHALL PROVIDE ALL BOXES AND HARDWARE NECESSARY TO FACILITATE
ABOVE LISTED ELECTRICAL SCOPE OF SYSTEMS INTEGRATION.
GENERAL CONTRACTOR SHALL COORDINATE AND BE MADE RESPONSIBLE FOR THE COMPLETION OF
ALL TRADES INVOLVED IN THE FIRE ALARM SYSTEM INSTALLATION PROCESS. GENERAL CONTRACTOR
SHALL ADHERE TO THE REQUIREMENTS OF THE BELOW LISTED FIRE ALARM SYSTEMS COMPLETION
CHECK LIST AND THIS SECTION AND WILL ENSURE ALL ASPECTS OF WORK HAVE BEEN COMPLETED
PRIOR TO REQUESTING A FINAL FIRE ALARM SYSTEMS INSPECTION.
THESE DRAWINGS RELATE TO FIRE ALARM INSTALLATION ONLY AND IN NO WAY SHOULD BE
CONSTRUED AS GENERAL CONSTRUCTION DOCUMENTS OR AN ADDENDUM TO ANY OTHER
CONSTRUCTION DRAWINGS.
ALL CIRCUITS TO BE CLASS B SUPERVISION, FIRE ALARM SYSTEM TO REPORT BY DEVICE
ADDRESSABLE POINT IN MULTIPLEX SYSTEM OR BY ZONE IN CONVENTIONAL SYSTEMS AS NOTED IN
SUBMITTAL DOCUMENTS AND THIS PAGE
ALL WIRING TO BE FIRE POWER LIMITED AND PROPERLY RATED FOR INSTALLATION ENVIRONMENT
SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSER THAN 36" TO ANY HVAC INLET/OUTLET
AREA SMOKE DETECTORS SHALL NOT BE INSTALLED MORE THAN 30' APART CENTER TO CENTER AND
NO MORE THAN 15' FROM ANY WALL OR PROTECTED AREA
CORRIDOR SMOKE DETECTORS SHALL NOT BE INSTALLED MORE THAN 42' APART CENTER TO CENTER
AND NO MORE THAN 15' FROM ANY WALL OR PROTECTED AREA
ALL WALL MOUNTED NOTIFICATION AND INITIATING DEVICES SHALL BE MOUNTED PER MOUNTING
DETAIL ON THIS PAGE
FACP TO BE OPERATED AT A TEMPERATURE NO LOWER THAN 32 DEGREES
GENERAL NOTES
INSTALLATION NOTES PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA000
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542COVER PAGE
SHEET INDEX
SHEET NUMBER SHEET TYPE
FA000 COVER PAGE
FA001 DETAILS
FA002 BATTERY CALCS
FA003 BATTERY CALCS
FA004 BATTERY CALCS
FA005 RISER
FA100 FLOOR PLAN
WIRE LEGEND
WIRE CALLOUT SIZE-IN./AWG TYPE #CONDUCTORS FUNCTION
P
AMM 2
1 SMOKE DETECTOR
ADDRESSABLE GAMEWELL ASD-PL2F 3-0 NL ON 4 SQ DP N/A-3.0 RING
PULL STATION GAMEWELL MS-7AF SG NL ON-4 SQ DP N/A-SG RING
WATERFLOW SWITCH
VALVE TAMPER SWITCH
AND PIV VALVE
DUAL INPUT MONITOR
MODULE
WEATHERPROOF
WALL MOUNT HORN STROBE
EXTERIOR BELL AND STROBE
FIRE ALARM CONTROL PANELFACP
N/A N/A BY OTHERS BY OTHERS
N/A N/A BY OTHERS BY OTHERS
GAMEWELL AMM-2IF 2G NL ON-4 SQ DP N/A-2G RING
SYSTEM SENSOR P2WL SG NL ON-4 SQ DP N/A-SG RING
SYSTEM SENSOR DG WP MANUFACTURER
SUPPLIED BOXSSM24-10
GAMEWELL SURFACE RECESSED N/AGWF-7075
1
1
3
2
1
1
1
QTY SYMBOL DESCRIPTION MANUFACTURER MODEL #MOUNT DEVICE MOUNT ACC.
SYMBOL LEGEND
WP
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:19 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA001
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542SHEET_NAME
BLDG 1
THIS PERMIT
BLDG 3 BLDG 4 TAHOMA BOULEVARD SEGRAVELBLDG 2
NOT TO SCALE
SITE PLAN
PIV LOCATION
3/4" PVC TO
SPRINKLER
RISER ROOM
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:21 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA002
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542SHEET_NAME
CABINETINNER DOOR REDGREENGRAYBROWNREDGREENGRAYBROWNNO C NC
RELAY
2
NO C NC
RELAY
1
NO C NC
TROUBLE
-+-+
SLC
IN
SLC
OUT
-+-+A B
SBUS
-+
NAC 1
-+
NAC 2SLC
PROG
MODEL
#7860
MODEL
#7860
CONNECTION OF TELEPHONE LINES
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:21 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA003
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542SHEET_NAME
TYPICAL NAC DEVICE CONNECTION FROM FACPTYPICAL NAC DEVICE CONNECTION FROM BPS
1A-1 1A-2
EOL
2A-22A-1
120VAC DEDICATED
CIRCUIT
NEUTRAL
GROUND
HOT
TO PM-9 TB2-2
TO PM-9 TB2-1
PSN-106
POTTER BOOSTER PANEL SUPPLY
EOL
EOL
ASD-PL2F SMOKE DETECTOR ATD-2LF HEAT DETECTOR
T6
T7 T2
T1
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
AOM-2RF
NORMALLY
OPEN 1
IF ANY WIRING TO TERMINALS 3-9 IS NOT POWER LIMITED,
THE CB500 BARRIER IS REQUIRED. THE CB500 INCLUDES
A NON POWER LIMITED LABEL, WHICH MUST BE PLACED
OVER THE POWER LIMITED TERMINAL INFO. ON THE NAME
PLATE.
9
8
7
6
5
0
1
2
3
4
AMM 4F
TYPICAL SLC DEVICE CONNECTIONS
1 2 3 4
MS-7 PULL STATION
TYPICAL SPRINKLER
DEVICE CONNECTION
3
2
1 3
2
1
47K
EOL
DNR DUCT DETECTOR
TEST COIL +
TEST COIL -
COMM +
OUT (CONV ONLY) +
COMM -
RA/RTS -
RA +
RTS +
TEST COIL +
TEST COIL -
COMM +
OUT (CONV ONLY) +
COMM -
RA/RTS -
RA +
RTS +
RTS151KEY
REMOTE TEST
STATION
1
2
3
4
5
JUMPER
- SLC OUT
AMM-21F
DUAL MONITOR MODULE
9
8
7
6
5
0
1
2
3
4
47K
EOL
47K
EOL
H
L
TO NEXT
SLC DEVICE
TYPICAL SPRINKLER
DEVICE CONNECTIONS
0 151413
12
11
10
9
8765
4
3
2
1 0
9
8765
4
3
2
1
TO SLC
LOOP
(-)(+)
(+)(-)
AMM-2F
+-+-
47K EOL
+ SLC OUT
TO GWF - 7075
TYPICAL NAC DEVICE CONNECTION FROM FACPTYPICAL NAC DEVICE CONNECTION FROM BPS
1A-1 1A-2
EOL
2A-22A-1
120VAC DEDICATED
CIRCUIT
NEUTRAL
GROUND
HOT
TO PM-9 TB2-2
TO PM-9 TB2-1
PSN-106
POTTER BOOSTER PANEL SUPPLY
EOL
EOL
ASD-PL2F SMOKE DETECTOR ATD-2LF HEAT DETECTOR
T6
T7 T2
T1
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
AOM-2RF
NORMALLY
OPEN 1
IF ANY WIRING TO TERMINALS 3-9 IS NOT POWER LIMITED,
THE CB500 BARRIER IS REQUIRED. THE CB500 INCLUDES
A NON POWER LIMITED LABEL, WHICH MUST BE PLACED
OVER THE POWER LIMITED TERMINAL INFO. ON THE NAME
PLATE.
9
8
7
6
5
0
1
2
3
4
AMM 4F
TYPICAL SLC DEVICE CONNECTIONS
1 2 3 4
MS-7 PULL STATION
TYPICAL SPRINKLER
DEVICE CONNECTION
3
2
1 3
2
1
47K
EOL
DNR DUCT DETECTOR
TEST COIL +
TEST COIL -
COMM +
OUT (CONV ONLY) +
COMM -
RA/RTS -
RA +
RTS +
TEST COIL +
TEST COIL -
COMM +
OUT (CONV ONLY) +
COMM -
RA/RTS -
RA +
RTS +
RTS151KEY
REMOTE TEST
STATION
1
2
3
4
5
JUMPER
- SLC OUT
AMM-21F
DUAL MONITOR MODULE
9
8
7
6
5
0
1
2
3
4
47K
EOL
47K
EOL
H
L
TO NEXT
SLC DEVICE
TYPICAL SPRINKLER
DEVICE CONNECTIONS
0 151413
12
11
10
9
8765
4
3
2
1 0
9
8765
4
3
2
1
TO SLC
LOOP
(-)(+)
(+)(-)
AMM-2F
+-+-
47K EOL
+ SLC OUT
TO GWF - 7075
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:22 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA004
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542SHEET_NAME
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:22 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
FACP
B
1-1
110CD
WP
EOL
5.1K
P
AMM 2
A
A
4.7K
EOL
4.7K
EOL
4.7K
EOL
WATERFLOWBACKFLOW INBACKFLOW OUTA
B
4.7K
EOL
AMM 2
4.7K
EOL
4.7K
EOL
A
TO TELCO (2) LINES BY OTHERS
TO 120 VAC DEDICATED
CIRCUIT BY OTHERS
LEVEL 2
LEVEL 1
POST INDICATOR VALVE (PIV)PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA005
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542SHEET_NAME
FIRE ALARM DEVICE MOUNTING HEIGHT DETAIL
MINI HORN APPLIANCE 90" AF.F.. AND AT LEAST
6" DOWN FROM CEILING
HORN/STROBE - STROBE APPLIANCE 80" A.F.F.
LOW FREQUENCY - STROBE APPLIANCE IN
SLEEPING AREA 28" DOWN FROM CEILING AND
WITHIN 16' OF PILLOW-MUST BE 110 CD
MANUAL PULL STATION 48" A.F.F. TOP OF BOX
P
M
LF
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:24 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
4.7K
EOL
1-1
110CD
4.7K
EOL
WP
FACP
P
B
AMM 2 AMM 2
PIV
3/4" PVC W/ (2) 18 AWG
STRANDED TYPE THWN
B
4.7K
EOL
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA100
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542BLDG 1 MAIN FLOOR
1/8" = 1'-0"
BLDG 1 MAIN FLOOR
2"
GRADE
2"2"
GRADE
1½"1½"2"2"2"12"2"2"6" 120VAC ALARM BELL TO BE
CONNECTED TO WATER FLOW
SWITCH. (INSTALLATION AND
WIRING BY OTHERS)
2" CHECK VALVE
2" MALE ADAPTOR
FSI START 2" MALE ADAPTOR
FSI START
1" MALE ADAPTOR
2" FEMALE ADAPTOR
RISER NOTES
1 - ALL CONTROL VALVE HANDLE TO BE REMOVED
AND PLACED IN HEAD BOX AT TIME OF FINAL
2 - WIRING OF FLOW SWITCH AND BELL TO BE BY OTHERS
3 - 2" SUPPLY LINE TO BE PROVIDED BY OTHERS
RISER LEGEND
1 - 2" WATER SUPPLY LINE
2 - 2" DERINGER 30 (DCDA)
3 - WATER FLOW ALARM SWITCH WIRED TO ALARM BELL
4 - WATER PRESSURE GAUGE
5 - 1" VALVE FOR DRAIN
6 - 1" DRAIN LINE PIPED TO EXTERIOR OF BUILDING
7 - UPRIGHT SPRINKLER TO PROTECT RISER
8 - 6" ALARM BELL INSTALLED ON EXTERIOR OF BUILDING
9 - 2" CHECK VALVE
10 - TO REMOTE FDC (BY OTHERS)
N.T.S.
SPRINKLER RISER DETAIL
AMM 2
47K EOL
47K EOL
47K EOL A
WATER FLOW SWITCH
BACK FLOW IN
BACK FLOW OUT
GAMEWELL
7075 FACP
15.12" x 12.71"
A
A
A
A
P MAIN
PULL
TO 120 VAC DEDICATED CIRCUIT
TO TELCO (2) LINES BY OTHERS
6' A.F.F.
N.T.S.
FIRE ALARM RISER DETAIL B
47K
EOL
AMM 2
47K EOL A
POST INDICATOR VALVE (PIV)
A
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:24 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings
PROJECT NAMEPROJECT TYPEPROJECT LOCATIONPROJECT NUMBER
SHEET NAME
DRAWN DATE
DRAWING NUMBER
CITY APPROVAL STAMP
DESIGNER OF RECORD
FA101
CW
LC220007
07-20-2022PLAN SET NOTESTAHOMA APARTMENTS BLDG 1FIRE ALARM15035 BERRY VALLEY ROAD SEYELM, WA 985971234567NICET Certifcation Number: 148653
Engineering Technician, Level III
Paul J. Powloski
Authorizing Signature: ______________________
Fire Alarm Systems PUYALSOKNELUPPA11409 58Th Ave E-Puyallup, WA. PH 253-848-6998 FX 253-848-0542BLDG 1 SECOND FLOOR
1/8" = 1'-0"
BLDG 1 SECOND FLOOR
L:\(2) ACTIVE JOBS\X - YELM APARTMENTS - SCHUUR BROS, KORY\(5) DESIGNS\(1) FIRE ALARM\BLDG 1\YELM APTS - BLDG 1 FIRE - 07-11-2022.dwg, 7/26/2022 8:01:24 AMTOWNZEN & ASSOCIATES
REVIEWED FOR CODE COMPLIANCE
The plans submitted for review have been reviewed in
accordance with local and state applicable standards. This
does not relieve the applicant of the responsibility of
compliance with the applicable codes.
4
09/13/2022
No Comments
Comments Noted
on drawings