Circle K - Yelm (Yelm & Killion), WA - Electrical OTPREVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E0.0
PROJECT NUMBER: 24212
ELECTRICAL
COVER SHEET
AND LEGEND
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
2023 NATIONAL ELECTRICAL CODE W/ WASHINGTON STATE AMENDMENTS
2021 WASHINGTON STATE BUILDING CODE
2021 WASHINGTON STATE FUEL GAS CODE
2021 WASHINGTON STATE FIRE CODE
2021 WASHINGTON STATE ENERGY CODE
CODE COMPLIANCE INFORMATION
SD
J
OS2S
OSS
3S
DS
MS
KS
S STANDARD 20A, SINGLE PHASE SPST TOGGLE SWITCH
SMOKE DETECTOR / DUCT SMOKE DETECTOR
HORN / STROBE, CANDELA AS INDICATED, COORDINATE WITH FIRE ALARM PLANS
ABBREVIATIONS
SURFACE MOUNTED PANELBOARD, REFERENCE PANEL SCHEDULE FOR RATINGS AND COMPONENTS
FLUSH MOUNTED PANELBOARD, REFERENCE PANEL SCHEDULE FOR RATINGS AND COMPONENTS
TELEPHONE OUTLET WITH (2) RJ45 PORTS U.O.N., PROVIDE 3/4"C TO ACCESSIBLE CEILING SPACE
OR AS OTHERWISE INDICATED
DISCONNECT SWITCH, AMPS, POLES AND FUSE SIZE AS SHO WN (FUSE SIZE CALLED OUT IF REQUIRED)
STANDARD 20A, 120V 1PH GROUNDING TYPE SIMPLEX RECEPTACLE
JUNCTION BOX. SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS AND / OR
CONDUCTORS PASSING THROUGH. (WALL MOUNTED/CEILING MOUNTED)
KEYED SWITCH
DIMMER SWITCH, SINGLE PHASE SLIDING TYPE SWITCH. LUTRON "NOVA-T" SERIES OR APPROVED
EQUAL. PROVIDE SEPARATE NEUTRAL FOR EACH DIMMER CIRCUIT.
MANUAL MOTOR SWITCH
3-WAY SWITCH
LIGHT FIXTURE, NIGHT LIGHT
LIGHT FIXTURE
(WALL MOUNTED/CEILING MOUNTED)
LIGHT FIXTURE
(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
SYMBOL DESCRIPTION
SINGLE POLE OCCUPANCY
SENSOR SWITCH
DOUBLE POLE OCCUPANCY
SENSOR SWITCH
EXIT SIGN, WITHOUT OR WITH INTEGRATED EMERGENCY LIGHTING
(WALL MOUNTED/CEILING MOUNTED)
EMERGENCY LIGHT
(WALL MOUNTED/CEILING MOUNTED)
a, b, c LOWER CASE LETTERS INDICATE
SWITCHING CONFIGURATION
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
C CONDUIT
CCT CIRCUIT
CF CEILING FAN
CW CASH WRAP
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMERGENCY LIGHTING FIXTURE
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
G GROUND
GFEP GROUND FAULT EQUIPMENT
PROTECTION
GFI GROUND FAULT CIRCUIT
INTERRUPTER
IG ISOLATED GROUND
ELECTRICAL SYMBOLS LEGEND
LCU LIGHTING CONTROL
UNIT
NL NIGHT LIGHT
NTS NOT TO SCALE
REC REFRIGERATION
ELECTRICAL
CONTRACTOR
RC REFRIGERATION
CONTRACTOR
RH RADIANT HEATER
SC SECURITY CAMERA
TR TAMPER RESISTANT
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED
OTHERWISE
WH WATER HEATER
WP WEATHER PROOF
WR WEATHER RESISTANT
INV EMERGENCY POWER INVERTER
PE CEILING MOUNTED LINE VOLTAGE PHOTOCELL SENSOR, LEVITON "PCCSD-W" OR EQUAL.
CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR, LEVITO N ODC05-MDW OR EQUAL.
STANDARD 20A, 120V 1PH GROUNDING TYPE DUPLEX RECEPTACLE
STANDARD 20A, 120V 1PH GROUNDING TYPE QUADRUPLEX RECEPTACLE
STANDARD 20A, 120V 1PH GROUNDING "GROUND FAULT INTERRUPTER" GFI RECEPTACLE
STANDARD 20A, 120V 1PH ISOLATED GROUND TYPE DUPLEX RECEPTACLE, ORANGE IN COLOR
STANDARD 20A, 120V 1PH GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED IN FLUSH FLOOR
OUTLET BOX
STANDARD 20A, 120V 1PH GROUNDING TYPE QUADRUPLEX RECEPTACLE MOUNTED IN FLUSH
FLOOR OUTLET BOX
SPECIAL RECEPTACLE - VERIFY NEMA CONFIGURATION WITH INSTALLED EQUIPMENT
MANUFACTURER REQUIREMENTS.
CEILING MOUNTED RECEPTACLE, STANDARD 20A, 120V 1PH GROUNDING TYPE DUPLEX RECEPTACLE
SD
110cd
DATA OUTLET WITH (2) RJ45 PORTS U.O.N., PROVIDE 3/4"C TO ACCESSIBLE CEILING SPACE OR AS
OTHERWISE INDICATED
COMBINATION TELEPHONE / DATA OUTLET WITH (4) RJ45 PORTS U.O.N., PROVIDE (2) 3/4"C TO
ACCESSIBLE CEILING SPACE OR AS OTHERWISE INDICATED
SECURITY CAMERA BY OTHERS.
ALL LIGHTING FIXTURES ARE SUPPLIED BY CIRCLE K, INSTALLED BY THE ELECTRICAL CONTRACTOR
LIGHTING FIXTURE SCHEDULE
TYPE ITEM TYPE DESCRIPTION MANUFACTURER MODEL LAMP WATTS VOLTAGE COMMENTS COUNT
A INTERIOR LIGHTING 2'x4' H.E. TROFFER CREE RLA-FLX24-50L-940-CRV-10V10-UNV LED 41 W 120 V 43
AE INTERIOR LIGHTING 2'x4' H.E. TROFFER WITH BATTERY CREE RLA-FLX24-50L-940-CRV-10V10-UNV-EB LED 41 W 120 V WITH EMERGENCY BALLAST 11
B INTERIOR LIGHTING 6" RECESSED DOWNLIGHT CREE RLA-LR6X-18L-40K LED 21 W 120 V 25
C INTERIOR LIGHTING 2'x2' H.E. TROFFER CREE RLA-FLX22-40L-940-CRV-10V10-UNV LED 33 W 120 V 10
CE INTERIOR LIGHTING 2'x2' H.E. TROFFER WITH BATTERY CREE RLA-FLX22-40L-940-CRV-10V10-UNV-EB LED 33 W 120 V WITH EMERGENCY BALLAST 2
D INTERIOR LIGHTING 4' GASKETED WRAP AROUND CREE RLA-WS4-C-40L-LRA-40K-8-UL LED 30 W 120 V 4
DE INTERIOR LIGHTING 4' GASKETED WRAP AROUND WITH BATTERY CREE RLA-WS4-C-40L-LRA-40K-8-UL+ LIGHT ALARMS LALDR-14 LED 30 W 120 V 3
J INTERIOR LIGHTING 8' LED LINEAR FIXTURE CREE RLA -LS8-120L-950-R-UL-10V LED 92 W 120 V 5
JE INTERIOR LIGHTING 8' LED LINEAR FIXTURE WITH BATTERY CREE RLA -LS8-120L-950-R-UL-10V-EB1 LED 92 W 120 V 1
K INTERIOR LIGHTING 4' LED LINEAR FIXTURE CREE RLA-LS4-60L-950-R-UL-10V LED 44 W 120 V 4
A3B EXTERIOR SITE LIGHTING SINGLE MEDIUM EXTERIOR POLE FIXTURE LITHONIA RSX2 LED P2 50K R3 MVOLT SPA HS FAO LED 114 W 120 V 4
A4B EXTERIOR SITE LIGHTING SINGLE MEDIUM EXTERIOR POLE FIXTURE LITHONIA RSX2 LED P2 50K R4S MVOLT SPA HS FAO LED 114 W 120 V 8
INV EXTERIOR SITE LIGHTING EMERGENCY BATTERY BACKUP FOR EXT DOWNLIGHTS - 90 MIN DUAL-LITE LG125T1AO LED 21 W 120 V 1
L EXTERIOR SITE LIGHTING 6" RECESSED DOWNLIGHT LITHONIA LBR6 ALO2 20LM SWW1 (4000K) AR LSS MWD 90CRI WL LED 25 W 120 V VERIFY COLOR AND FINISH WITH ARCH/OWNER 11
WP EXTERIOR SITE LIGHTING EXT. WALL PACK ("EM" - INVERTER BACK-UP) LITHONIA ARC2 LED P5 50K MVOLT LED 51 W 120 V VERIFY COLOR AND FINISH WITH ARCH/OWNER 9
EM EMERGENCY LIGHTING LED EMERGENCY DUAL HEAD LIGHTALARMS RLA-LCA-2LED LED 12 W 120 V 4
EX EMERGENCY LIGHTING LED EXIT SIGN / EMERGENCY LIGHT COMBO LIGHTALARMS RLA-UQLXN500X-2LED LED 12 W 120 V 4
W EMERGENCY LIGHTING WET-LISTED EMERGENCY REMOTE DUAL HEAD LIGHTALARMS CAM-SD-XX LED 2 W 120 V (2) 1W HEADS GRAY FINISH 2
CAN1 CANOPY LIGHTING CANOPY LIGHT LITHONIA XPCNY LED ALO2-13L SWW2-50K FPCL MVOLT DWHXD M3 LED 91 W 208 V CANOPY LIGHT 14
CAN2 CANOPY LIGHTING CANOPY LIGHT LITHONIA XPCNY LED ALO2-13L SWW2-50K FTL MVOLT DWHXD M3 LED 89 W 208 V CANOPY LIGHT 14
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
1.SECTION 16010 -BASIC ELECTRICAL REQUIREMENTS
A.THE WORK OF EACH OF THE ELECTRICAL SECTIONS INCLUDES FURNISHING AND INSTALLING THE MATERIAL, EQUIPMENT,
AND SYSTEMS COMPLETE AS SPECIFIED AND/OR INDICATED ON THE DRAWINGS. THE ELECTRICAL INSTALLATIONS, WHEN
FINISHED, SHALL BE COMPLETE AND COORDINATED, READY FOR SATISFACTORY SERVICE.
B.THE WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT ACCORDANCE WITH ALL APPLICABLE MUNICIPAL, STATE
AND OTHER LOCAL CODES, THE 2023 EDITION OF THE NATIONAL ELECTRICAL CODE WITH WASHINGTON STATE
AMENDMENTS AND THE 2010 ADA STANDARDS.
C.THE CONTRACTOR SHALL MAKE APPLICATION AND PAY FOR ALL PERMITS, LICENSES AND INSPECTIONS AS REQUIRED
UNDER THE ABOVE CODES.
D.THE GENERAL ARRANGEMENT OF CONDUIT, WIRING AND EQUIPMENT SHALL BE AS IDENTIFIED ON THE CONTRACT
DRAWINGS. THE CONTRACTOR SHALL CAREFULLY INVESTIGATE THE SITE, STRUCTURAL, AND FINISH CONDITIONS
AFFECTING HIS WORK AND SHALL ARRANGE SUCH WORK ACCO RDINGLY, PROVIDING SUCH FITTINGS AND ACCESSORIES
AS MAY BE REQUIRED TO MEET SUCH CONDITIONS.
E.THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND SERVICES NECESSARY FOR AND
REASONABLY INCIDENTAL TO THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK AND RELATED SYSTEMS AS
INDICATED ON THE DRAWINGS OR AS NECESSARY TO PROVIDE A COMPLETE SYSTEM.
F.THE CONTRACTOR SHALL PROVIDE ALL NECESSARY TEMPORARY WIRING, LIGHTING AND CONSTRUCTION POWER FOR ALL
TRADES AS REQUIRED TO COMPLETE THE PROJECT.
G.ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND COMPLETED IN A FIRST CLASS WORKMANLIKE MANNER. ALL
MATERIALS SHALL BE NEW AND THE BEST OF THEIR RESPECTIVE KINDS. ALL EQUIPMENT AND SYSTEMS SHALL BE
APPROVED BY UL OR SIMILAR NATIONALLY ACCEPTED TESTING AGENCY SUCH AS ETL TESTING LABORATORIES.
H.THE CONTRACTOR SHALL VISIT THE SITE AND OBSERVE THE CONDITIONS UNDER WHICH THE WORK SHALL BE
COMPLETED. NO ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONTRACT FOR ANY ERROR OR NEGLIGENCE IN THE
CONTRACTOR'S PART.
I.THE CONTRACTOR SHALL SUBMIT DETAILED DIMENSIONED SHOP DRAWINGS, TOGETHER WITH WIRING DIAGRAMS,
SPECIFICATIONS, OPERATING DATA, AND/OR CATALOG CUTS FOR ALL EQUIPMENT.
J.A THOROUGH TEST SHALL BE MADE PRIOR TO ENERGIZING THE SYSTEM TO DEMONSTRATE THAT THE SYSTEM IS
ENTIRELY FREE FROM GROUND FAULTS, SHORT CIRCUITS, AND OPEN CIRCUITS; THAT THE RESISTANCE TO GROUND OF
ALL NON-GROUNDED CIRCUITS, BEFORE AND AFTER CONNECTION OF EQUIPMENT MEETS THE REQUIREMENTS OF THE
NATIONAL ELECTRICAL CODE AND IEEE STANDARDS/RECOMMENDATIONS.
K.IDENTIFY ALL MOTOR STARTERS, SWITCHES, CONTROLS, PANELBOARDS, SWITCHBOARDS, TERMINAL BOARDS, CONTROL
CENTERS AND OTHER EQUIPMENT. IDENTIFICATION PLATES SHALL BE LAMINATED PLASTIC, BLACK AND WHITE ENGRAVED
LETTERS. LETTERING FOR CONTROL CENTERS, CONTROL PANELS, METERING AND INSTRUMENT PANELS SHALL BE 3/8"
HIGH.
L.THE MATERIAL AND WORKMANSHIP OF ALL PARTS OF THE ELECTRICAL INSTALLATION SPECIFIED HEREIN SHALL BE
GUARANTEED UNCONDITIONALLY FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL CERTIFICATE OF OCCUPANCY OR
GRAND OPENING, WHICH EVER COMES FIRST.
M.UPON COMPLETION OF THE ELECTRICAL INSTALLATION, THE CONTRACTOR SHALL DELIVER TO THE OWNER ONE SET OF
SCANNED DIGITAL PRINTS OF ELECTRICAL CONTRACT DRAWINGS WHICH SHALL BE LEGIBLY MARKED IN RED TO SHOW
ALL ADDITIONS, CHANGES AND DEPARTURES OF THE INSTALLATION AS COMPARED WITH THE ORIGINAL DESIGN. THEY
SHALL BE SUITABLE FOR USE IN PREPARATION OF RECORD DRAWINGS.
N.THE CONTRACTOR SHALL PREPARE A RECORD AND INFORMATION MANUAL. THE MANUAL SHALL BE SCANNED INTO A
DIGITAL FORMAT AND FORWARDED TO CIRCLE K CONSTRUCTION. PROVIDE THE FOLLOWING DATA IN THE RECORD AND
INFORMATION MANUAL:
1)CUT SHEETS OF ALL EQUIPMENT WITH TECHNICAL SPECIFICATIONS.
2)OPERATION AND MAINTENANCE PROCEDURES.
3)SERVICING INSTRUCTIONS.
4)COPIES OF PANELBOARD DIRECTORIES.
5)COPIES OF WARRANTIES.
6)LIST OF LAMPS SHOWING QUANTITY, TYPE, WATTAGE, MANUFACTURER, CATALOG NUMBER, ETC.,
FOR EACH FIXTURE TYPE.
7)COPIES OF TEST REPORTS.
O.EXACT LOCATIONS OF OUTLETS SHALL BE COORDINATED WITH DOOR SWINGS AND VARIOUS PROTRUSIONS. MOUNTING
HEIGHTS OF THE VARIOUS ELECTRICAL DEVICES SHALL BE AS FOLLOWS:
SWITCHES 46" AFF TO CENTER OF BOX
RECEPTACLES 20" AFF TO CENTER OF BOX
TELEPHONE OUTLETS 20" AFF TO CENTER OF BOX
EXIT LIGHTS CENTERED BETWEEN CEILING AND TOP OF DOOR (UP TO 1'-0" ABOVE DOOR),
SURFACE OR CEILING MOUNTED AS SHOWN
DISCONNECTING SWITCHES 52" AFF TO CENTER OF SWITCH
P.PROVIDE A DISCONNECT SWITCH FOR EACH MOTOR AS SHOWN ON THE DRAWINGS SIZED AS REQUIRED TO MEET THE
NEC AND PROVIDE ALL WIRING CONNECTIONS FROM SOURCE. PROVIDE REQUIRED VOLTAGE.
Q.SEAL ALL CONDUIT PENETRATIONS THRU RATED WALLS AND FLOORS TO MAINTAIN FIRE INTEGRITY. REFER TO
ARCHITECTURAL DRAWING FOR FIRE WALL LOCATIONS.
R.ELECTRICAL CONTRACTOR SHALL VERIFY ALL VOLTAGES OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR
PRIOR TO ROUGH-IN.
2.SECTION 16050 -BASIC ELECTRICAL MATERIALS AND METHODS
A.INSTALL ALL WIRING CONDUIT EXCEPT AS OTHERWISE INDICATED. MINIMUM CONDUIT SIZE SHALL BE 3/4". ALL CONDUIT
EMBEDDED IN CONCRETE SHALL BE 3/4" MINIMUM. INSTALL ALL CONDUIT CONCEALED UNLESS ON UNFINISHED WALLS,
ON UNFURRED CEILINGS OR MECHANICAL EQUIPMENT SPACES. PROVIDE CONDUIT AS FOLLOWS:
1)RIGID STEEL CONDUIT FOR WORK EXPOSED TO WEATHER OR EMBEDDED IN CONCRETE OR MASONRY.
2)GALVANIZED ELECTRICAL METALLIC TUBING (EMT) FOR INTERIOR EXPOSED WORK, CONCEALED WORK
ABOVE SUSPENDED CEILINGS, AND WITHIN INTERIOR PARTITIONS OR NON-MASONRY WALLS.
3)FLEXIBLE METAL CONDUIT IN SHORT LENGTHS (6' MAXIMUM) FOR THE CONNECTION OF RECESSED
LIGHTING FIXTURES AND MOTORS.
4)LIQUID TIGHT FLEXIBLE METAL CONDUIT WHEREVER MOISTURE MAY BE PRESENT AND MOTORS IN
MECHANICAL EQUIPMENT SPACES.
5)POLYVINYLCHLORIDE (PVC) SCHEDULE 40 AND 80 CONDUIT WITH GROUND CONDUCTOR FOR
UNDERGROUND OUTSIDE OF BUILDING (SITE) INSTALLATION AS PERMITTED BY NEC ARTICLE 352.
B.INSTALL CONDUITS PARALLEL AND PERPENDICULAR TO WALLS AND INTERIOR SURFACES. CLEAN AND PLUG AND
PROVIDE A PULL LINE IN EACH CONDUIT LEFT EMPTY. USE MANUFACTURED ELBOWS AND SCREW JOINTED CONDUIT
FITTINGS. USE CAPPED BUSHINGS OR "PUSH PENNY" PLUGS. ALL FITTINGS SHALL BE STEEL OR MALLEABLE IRON. ALL
EMT FITTINGS SHALL BE COMPRESSION TYPE.
C.ALL OUTLET, SWITCH AND JUNCTION BOXES, SHALL BE STAINLESS STEEL BY STEEL CITY, RACO, APPLETON, VALEN, OR
EQUIVALENT. OUTLET BOXES IN CONCRETE CONSTRUCTION SHALL BE OCTAGONAL. NO "THRU-WALL" BOXES SHALL BE
USED IN PARTITIONS. ALL BOXES SHALL BE FURNISHED WITH APPROPRIATE COVERS.
D.JUNCTION AND PULL BOXES SHALL BE FURNISHED AND INSTALLED AS INDICATED OR WHERE REQUIRED TO FACILITATE
PULLING OF WIRES OR CABLES. BOXES FOR EXTERIOR WORK SHALL BE CAST ALUMINUM OR GALVANIZED CAST IRON TYPE
WITH THREADED HUBS, UNLESS OTHERWISE DIRECTED. GASKETED COVER PLATES SHALL BE FURNISHED FOR OUTDOOR
INSTALLATIONS.
E.BUILDING WIRE, UNLESS OTHERWISE INDICATED, SHALL BE COPPER, 600 VOLT, TYPE THWN/THHN INSULATION, #12 AWG
MINIMUM, FOR INTERIOR AND EXTERIOR USE. FOR BRANCH CIRCUITS TYPE MC (METAL CLAD) CABLE MAY BE USED WHERE
PERMITTED BY THE NEC AND LOCAL CODES. NO ROMEX OR AC (BX) CABLE WILL BE ALLOWED ON THE PROJECT.
F.MINIMUM WIRE SIZE SHALL BE NUMBER TWELVE (12) AWG. NO SPLICES SHALL BE MADE EXCEPT WITHIN OUTLET OR
JUNCTION BOXES. WIRES NUMBER EIGHT (8) AWG AND LARGER SHALL BE STRANDED. WIRES AND CABLES SHALL BE
MANUFACTURED BY PIRELLI, ROYAL, TRIANGLE OR EQUIVALENT.
G.THE COLOR CODING SYSTEM LISTED BELOW SHALL BE USED THROUGHOUT THE BUILDING:
SYSTEM PHASE A PHASE B PHASE C NEUTRAL GROUND ISOLATED GROUND
120/208V BLACK RED BLUE WHITE GREEN GREEN/YELLOW
277/480V BROWN ORANGE YELLOW GRAY GREEN GREEN/YELLOW
H.THE WIRE SIZE INDICATED IN THE HOMERUN SHALL BE USED THROUGH THE CIRCUIT.
I.PROVIDE DISCONNECT SWITCHES WHERE INDICATED AND AS REQUIRED. SWITCHES SHALL BE OF SIZE, NUMBER OF
POLES AND FUSED OR NONFUSED, AS REQUIRED FOR JOB CONDITIONS AND THE NATIONAL ELECTRICAL CODE. ALL
SAFETY SWITCHES SHALL BE NEMA I ENCLOSURE "HD" WITH INTERLOCKING COVER AND HANDLE, MANUFACTURED BY
SQUARE "D" OR APPROVED EQUAL. PROVIDE NEMA 3R ENCLOSURES WHERE REQUIRED.
J.PROVIDE STARTERS AND CONTROL WIRING AS INDICATED ON THE DRAWINGS, OR SPECIFIED HEREIN. ALL TEMPERATURE
CONTROL WIRING AND COMPONENTS SHALL BE UNDER DIVISION 15.
K.PROVIDE THERMAL MANUAL MOTOR STARTING SWITCHES FOR FRACTIONAL HORSEPOWER, SINGLE PHASE MOTORS. THE
STARTERS SHALL BE SQUARE D COMPANY, CLASS 2510, ALLEN BRADLEY BULLETIN 600, OR APPROVED EQUAL FOR SING LE
SPEED MOTORS. ENCLOSURES SHALL BE NEMA I FOR INTERIOR USE AND NEMA 3R FOR EXTERIOR USE.
L.THREE PHASE MOTOR STARTERS SHALL BE 3 POLE, FULL-VOLTAGE, MAGNETIC TYPE. ENCLOSURES SHALL BE NEMA I FOR
INTERIOR USE AND NEMA 3R FOR EXTERIOR USE. PROVIDE HOA SWITCH WHEN AUTOMATICALLY CONTROLLED, PILOT
INDICATING LIGHT, CONTROL TRANSFORMER, AND NO/NC AUXILIARY CONTACTS. STARTERS SHALL BE SQUARE D
COMPANY, CLASS 8536 AND CLASS 8538 COMBINATION TYPE OR APPROVED EQUAL.
M.WIRING DEVICES SHALL BE ARROW HART, GENERAL ELECTRIC, P & S LEVITON OR HUBBELL:
1)WALL SWITCHES: ARROW HART 1991. THREE AND FOUR-WAY SWITCHES SHALL BE OF THE SAME
MANUFACTURER AND GRADE.
2)RECEPTACLES: ARROW HART 5362 FOR 20 AMPERES. GFCI SHALL BE #GFCS20 RATED 20 AMPERE, 120 VOLT.
PROVIDE TAMPER RESISTANT AND MOISTURE RESISTANT TYPE WHERE REQUIRED BY NEC.
3)DIMMERS: 600/1000/1500/2000 WATTS AS REQUIRED BY JOB CONDITIONS. LUTRON 'NOVA' SERIES OR EQUAL.
4)DEVICE PLATES: ARROW HART SWITCH PLATES SI-S6 SERIES. ARROW HART RECEPTACLE PLATES S8.
ARROW HART TELEPHONE BLANK PLATES S14.
N.MOUNT WEATHERPROOF DEVICES IN CAST METAL BOXES WITH GASKETED, SPRING-HINGED LID-TYPE LOCKING COVERS
HAVING CORROSION-RESISTANT FINISH.
O.THE ENTIRE ELECTRICAL SYSTEM SHALL BE SOLIDLY GROUNDED INCLUDING MAIN SERVICE EQUIPMENT, DISCONNECT
SWITCHES, WIRING TROUGHS AND PULL BOXES, CONDUIT SYSTEM, OUTLET BOXES, MOTORS, ELECTRIC HEATING
EQUIPMENT, LIGHTING FIXTURES, TRANSFORMERS, EMERGENCY SYSTEMS, UPS SYSTEMS, AND FIRE ALARM SYSTEMS.
P.PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN ALL BRANCH CIRCUITS AND FEEDERS SIZED IN ACCORDANCE WITH
THE NEC TABLE 250.112.
Q.ALL BRANCH CIRCUITS SHALL BE RUN CONCEALED IN EXISTING AND NEW WALLS. CUT AND PATCH EXISTING WALLS AND
SURFACES AS REQUIRED.
R.ALL D.C. WIRING SHALL BE #10 AWG MINIMUM.
S.GROUND, PHASE AND NEUTRAL CONDUCTORS SHALL BE PIG -TAILED IN OUTLET BOXES OR MULTI-OUTLET ASSEMBLY FOR
RECEPTACLES SO THAT GROUND AND ELECTRICAL SERVICE W ILL NOT BE DISRUPTED TO OTHER RECEPTACLES ON THE
SAME MULTI-WIRE CIRCUIT IF RECEPTACLE IS REMOVED.
3.SECTION 16400 -SERVICE AND DISTRIBUTION
A.COORDINATE ALL SERVICE ENTRANCE WORK WITH THE ELECTRIC UTILITY.
B.DISTRIBUTE POWER AT 120/208V, 3 PHASE, 4 WIRE, LED LIGHTING, AIR CONDITIONING, ELECTRIC HEATING, MOTOR
CIRCUITS, AND 120/208V FOR RECEPTACLES, INCANDESCENT LIGHTS AND SMALL MOTORS.
C.PANELBOARDS SHALL BE 120/208 VOLTS, THREE PHASE EMPLOYING BREAKERS MINIMUM 10,000 SYMMETRICAL AIC AT
120 VOLTS. FURNISH PANELBOARDS AS INDICATED ON DRAWINGS E6.0, E7.0 AND E7.1.
D.PANELBOARDS SHALL BE FACTORY ASSEMBLED WITH BOLT-ON TYPE CIRCUIT BREAKERS. BUSS SHALL BE ALUMINUM.
PROVIDE 50% GROUND BUS BAR. PANELS CONNECTED TO K-RATED TRANSFORMERS SHALL HAVE 200% RATED NEUTRAL
BUS BARS.
E.PROVIDE THREE (3) 3/4 INCH SPARE CONDUITS FROM EACH RECESSED PANEL TO THE CEILING SPACE.
F.FUSES FOR SERVICE ENTRANCE EQUIPMENT SHALL BE U.L. LISTED CLASS L, J, OR RKI. FUSES FOR FEEDER CIRCUITS AND
PANELBOARDS SHALL BE U.L. CLASS RKI FAST-ACTING TYPE. FUSES FOR MOTOR OVERCURRENT, MOTOR CONTROLLER,
AND TRANSFORMER PROTECTION SHALL BE DUAL-ELEMENT, U.L. CLASS RKI TIME-DELAY TYPE.
G.PROVIDE ENERGY EFFICIENT, NEMA TP-1, SELF-COOLED, DRY TYPE TRANSFORMERS OF KVA, PHASE, "K" AND VOLTAGE
RATINGS AS INDICATED. TRANSFORMERS 15 KVA AND LESS SHALL HAVE A CLASS F INSULATION, 115 DEGREES C RISE.
TRANSFORMERS ABOVE 15 KVA SHALL HAVE CLASS H INSULATION, 115 DEGREE C RISE. PROVIDE FOUR 2-1/2 TAPS BELOW
TWO 2-1/2 TAPS ABOVE RATED PRIMARY VOLTAGE. TRANSFORMERS OF 150 KVA AND LESS SHALL BE RATED 45 DB,
LARGER TRANSFORMERS SHALL BE RATED 55 DB. NEUTRALS AND NEUTRAL CONNECTIONS OF ALL "K" RATED DRY TYPE
TRANSFORMERS SHALL BE 200% OF THE PHASE CONDUCTOR SIZE. TRANSFORMER SHALL BE HEVI-DUTY ELECTRIC
COMPANY, GENERAL ELECTRIC, SORGEL, ACME OR HOWARD INDUSTRIES.
4.SECTION 16500 -LIGHTING
A.PROVIDE A COMPLETE LIGHTING FIXTURE AT EACH LOCATION INDICATED ON THE DRAWINGS. FIXTURES SHALL BE
SPECIFIED ON THE LIGHTING FIXTURE SCHEDULE ON THE DRAWINGS.
B.ALL PLASTIC DIFFUSERS SHALL BE 100 PERCENT VIRGIN ACRYLIC (NOMINAL .125 INCH THICK) AND ALL LEXAN DIFFUSERS
SHALL BE LEXAN TYPE MR-4000, OR EQUAL.
C.8-FOOT TANDEM UNITS MAY BE USED IN LIEU OF 4 FOOT UNITS IN CONTINUOUS ROWS.
D.THE CONTRACTOR SHALL CONSULT THE CEILING CONTRACTOR AND ARCHITECT'S DRAWINGS FOR APPROVED REFLECTED
CEILING PLANS BEFORE ORDERING FIXTURES TO INSURE THAT ALL ARE COMPATIBLE WITH THE CEILING SYSTEM AND
PROPERLY LOCATED. VERIFY THAT ADEQUATE CLEARANCE FO R INSTALLATION, MAINTENANCE, AND HEAT DISSIPATION IS
AVAILABLE.
E.PROVIDE A MINIMUM OF TWO (2) GALVANIZED STEEL #12 GAUGE HANGER WIRES (ALTERNATE CORNERS) ON ALL
RECESSED FIXTURES.
F.CONTRACTOR SHALL PROVIDE ADDITIONAL EXIT LIGHTS AND EMERGENCY BATTERY PACK WITH DUAL HEADS AS NEEDED
TO MEET FIRE MARSHAL'S WALK-THROUGH AND ACCEPTANCE.
G.CONNECT EXIT LIGHTS, EMERGENCY BATTERY UNITS AND NIGHT LIGHTS (NL) TO UNSWITCHED PORTION OF LIGHTING
CIRCUIT SERVING RESPECTIVE AREA.
5.SECTION 16700 -COMMUNICATION SYSTEMS
A.TELEPHONE SERVICE SHALL BE INSTALLED BY THE TELEPHO NE COMPANY.
B.PROVIDE WALL OUTLETS IN 4" SQUARE 2-1/8" DEEP BOX WITH RAISED SINGLE GANG COVERS EQUIPPED WITH BLANK
STAINLESS STEEL DEVICE PLATES. EXTEND 3/4" EMPTY CONDUIT FROM EACH OUTLET TO THE CEILING SPACE AND
TERMINATE WITH INSULATED BUSHINGS. PROVIDE NYLON PULL WIRE IN ALL CONDUITS LEFT EMPTY.
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E0.1
PROJECT NUMBER: 24212
ELECTRICAL
SPECIFICATIONS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
W/C
ONCAVE
S
E
A
T
S
SG
150D O
R S
G
150P
WABA
S
H
VAL
LEY
46" R
OUND T
ABL
E
W/C
ONCAVE
S
E
A
T
S
SG
150D O
R S
G
150P
WABA
S
H
VAL
LEY
46" R
OUND T
ABL
E
SHUT- O FF SHUT- O FF
EXTERI O R RO O FACCE SS LAD DER
W
12
K
D
I
E
S
E
L
(
1
0
'
D
I
A
.
)
8K CK CHOICE12K SUL
20K REGULAR
JJJJJJ
J
J J
J
JJ
J
JJJJJ
J
J
J
J
1
0
'
-
0
"
SLEEVE DRIVE
SLEEVE DRIVE
C - 29
6
G -2 G -6 G -10 G -14 G -18 G -26
REFERENCE DETAIL
5-E1.1 FOR ENLARGED
DISPENSER DETAIL, TYP
A3B
A4B
A4B
A4B
A4B
3/4"C,2#10,#10G
3/4"C,2#10,#10G
A - 2,4
1"C,4#10,2#10G
7
A - 6,8
1"C,4#10,2#10G
7
C - 17
3/4"C,2#10,#10G
8
T
9
10
1112TYP
13 14
15
16
17
1814
1914
20 TYP
21
2122
G - 1,3
22
21
21
21 22
G - 17,19
21
21 22
23 23
2TYP
24
25
1
1
3/4"C,2#8,#8G2122
G - 13,15
21 G - 5,7
G - 9,11 21
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
11 26
A3B
A4B
A - 22
A3B
A - 20
A4B
A3B
1
ROUTE A-4 VIA
LIGHTING CONTROL
ROUTE A-8 VIA
LIGHTING CONTROL
1
G -30 G -34
3/4"C,2#10,
1#10 GR
3/4"C,2#10,
1#10 GR
1
0' - 0"
2
0' - 0"
2 0 ' - 0 "
23
A4B
A4B
G -22REFERENCE DETAIL
3-E1.1 FOR LIGHT POLE
BASE DETAIL, TYP
CAN2 CAN2
CAN1CAN1 CAN1 CAN1
CAN2CAN2 CAN2 CAN2
CAN1CAN1 CAN1 CAN1
CAN2CAN2 CAN2 CAN2
CAN1CAN1
CAN2 CAN2
CAN1CAN1 CAN1 CAN1
CAN2CAN2
A-13,15
A-13,15A-13,15
A-13,15A-13,15
A-13,15A-13,15
A-13,15A-13,15
A-13,15
A-13,15
A-13,15A-13,15
A-13,15A-9,11
A-9,11A-9,11
A-9,11A-9,11
A-9,11A-9,11
A-9,11A-9,11
A-9,11
A-9,11
A-9,11A-9,11
A-9,11
A - 13,15A - 9,11
11
2 TYP
2#10,#10G,3/4"C 2#10,#10G,3/4"C
14
'
-
0
"
TYP TYP
TY
P
TY
P
TY
P
A - 5
A - 1,3
A - 1
A - 5
A - 5
A - 5
A - 5
A - 5A - 5
3 3
4
TYP
5
5
2#10,#10G,3/4"C
5'
-
0
"
5'
-
0
"
2#12,#12G,3/4"C
7' - 0"7' - 0"
A -1
27TYP
1
1
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E1.0
PROJECT NUMBER: 24212
ELECTRICAL SITE
PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
1" = 20'-0"
1 ELECTRICAL SITE PLAN
1" = 10'-0"
2 CANOPY LIGHTING PLAN
KEYNOTES
1 SITE LIGHTING CIRCUITS SHALL BE ROUTED VIA
20A ELECTRICALLY HELD LIGHTING
CONTACTORS CONTROLLED BY THE 'EPO'
SWITCHES AND PHOTOCELL. 'EPO' SWITCHES
LOCATED AT THE FUEL CANOPY AND STORE ON
THE SITE. REFERENCE DETAIL 2/E6.0.
2 PROVIDE SEAL-OFF FITTINGS AT EACH END OF
CONDUIT IN CONJUNCTION WITH / G.V.R.
DISPENSER MANUAL. REFERENCE DETAIL 4/E1.1.
3 PROVIDE AND INSTALL WP JUNCTION BOXES IN
CANOPY FOR WHITE SPEAKERS. MAKE
CONNECTIONS TO CONDUITS PROVIDED IN
CANOPY COLUMN.
4 CANOPY EYEBROW LED STRIP LIGHTS. ONE
DOUBLE KWIK BOX POWER CONNECTION PER
EACH GROUP OF FOUR SECTIONS.
5 WP JUNCTION BOX FOR COMPLETE CONNECTION
OF CANOPY SIGN. VERIFY EXACT LOCATION IN
FIELD.
6 PROVIDE WEATHERPROOF DISCONNECT SWITCH
FOR WATER / AIR FILL STATION. VERIFY EXACT
LOCATION IN FIELD, AND VERIFY REQUIREMENTS
PRIOR TO ROUGH-IN
7 PROVIDE WEATHERPROOF DISCONNECT
SWITCH. COORDINATE EXACT CONNECTION AND
WIRING REQUIREMENTS WITH SIGN
CONTRACTOR AND FINAL SECTION PRIOR TO
INSTALLATION. PROVIDE (2) 1" CONDUITS, ONE
FOR POWER AND ONE FOR PHONE AND
COMMUNICATION.
8 HEAT TRACE TO BE PROVIDED FOR BACKFLOW
PREVENTER IN COLD REGION.
9 PROVIDE HOUSEKEEPING PAD FOR POWER CO.
PAD MOUNTED TRANSFORMER PER UTILITY
COMPANY REQUIREMENTS.
10 REFER TO ONE-LINE DIAGRAM FOR CONDUCTOR
AND CONDUIT SIZES. VERIFY WITH POWER
COMPANY.
11 FUEL DISPENSER CONDUITS FOR POWER,
INTERCOM, CRIND DATA AND SENSORS.
REFERENCE DETAIL 5/E1.1 AND FUEL SYSTEM
VENDOR DRAWINGS.
12 (1) 3/4" CONDUIT AND (3) 1" CONDUITS FROM
ELECTRICAL ROOM / MECHANICAL ROOM, TO
CLOSEST CANOPY COLUMN. ROUTE CONDUITS
UP TO CANOPY DECK FOR SPEAKER/SECURITY
CAMERA CONNECTIONS. PROVIDE PULL
STRINGS IN ALL CONDUITS.
13 CLASS 1 DIVISION 2 HAZARDOUS AREA:
OUTDOOR DISPENSING DEVICE: UP TO 18" OF
DISPENSER ENCLOSURE, EXTENDING 20 FT.
HORIZONTALLY IN ALL DIRECTIONS FROM
DISPENSER ENCLOSURE. PER NEC TABLE
514.3(8)(1).
14 ALL WIRING IN THIS AREA INCLUDING BELOW
GRADE SHALL BE INSTALLED IN RIGID CONDUIT
PER NEC ARTICLE 514.8. HOWEVER, PER NEC
514.8 EXCEPTION 2, NONMETALLIC RIGID
CONDUIT (PVC) HAVING A MINIMUM OF 24" OF
GROUND COVER IS ALLOWED. IN ADDITION,
THREADED RIGID METAL CONDUIT OR
THREADED STEEL INTERMEDIATE METAL
CONDUIT SHALL BE USED FOR THE LAST 2 FEET
OF THE UNDERGROUND RUN TO EMERGENCE
OR TO THE POINT OF CONNECTION TO THE
ABOVE GROUND RACEWAY, AND AN EQUIPMENT
GROUNDING CONDUCTOR SHALL BE INCLUDED.
PROVIDE ALL EXPLOSION PROOF FITTINGS AND
SEALS NECESSARY TO COMPLETE CONDUIT
SYSTEMS. NO SUBSTITUTIONS SHALL BE MADE
UNLESS APPROVED BY THE AUTHORITY HAVING
JURISDICTION. PROVIDE EXPLOSION PROOF
JUNCTION BOXES (CROUSE HINDS) MODEL
GUP215 WITH 0302 'O' RING OR OWNER
APPROVED EQUAL.
15 CLASS 1 DIVISION 1 HAZARDOUS AREA:
UNDERGROUND TANK VENT: WITHIN 5 FT. OF
OPEN END OF VENT, EXTENDING IN ALL
DIRECTIONS. PER NEC TABLE 514.3(B)(1).
16 CLASS 1 DIVISION 2 HAZARDOUS AREA:
UNDERGROUND TANK VENT: BETWEEN 5 FT. AND
10 FT. OF OPEN END OF VENT, EXTENDING IN ALL
DIRECTIONS. PER NEC TABLE 514.3(B)(1).
17 VENT RISERS FROM TANKS.
18 CLASS 1 DIVISION 2 HAZARDOUS AREA:
UNDERGROUND TANK FILL OPENING: UP TO 18"
ABOVE GRADE LEVEL, EXTENDING 5 FT.
HORIZONTALLY IN ALL DIRECTIONS FROM ANY
LOOSE-FILL CONNECTION. PER NEC TABLE
514.3(B)(1).
19 CLASS 1 DIVISION 1 HAZARDOUS AREA:
UNDERGROUND TANK: INSIDE TANK - ENTIRE
INSIDE VOLUME. FILL OPENING - ENTIRE SPACE
WITHIN ANY PIT OR BOX BELOW GRADE LEVEL.
PER NEC TABLE 514.3(B)(1).
20 TANK FILL STATION.
21 3/4" CONDUIT FOR POWER/STP CONTROL.
REFERENCE DETAIL 1/E1.0 FOR POWER CIRCUIT
DESIGNATION, CONDUIT AND WIRE SIZE.
PROVIDE 4#12 THWN2 FOR STP AUTHORIZATION.
VERIFY STP AUTHORIZATION CONDUCTOR
QUANTITY, SIZE AND TYPE PER DISPENSER WITH
FUEL VENDOR DRAWINGS.
22 3/4" CONDUIT FOR TANK MOTION SENSORS.
INSTALL CONDUIT TO SUMP AND INTERSTITIAL
SENSORS AT TANKS. REFERENCE FUEL SYSTEM
VENDOR DRAWINGS FOR CONDUCTORS TO BE
INSTALLED TO SENSORS.
23 "EMERGENCY POWER OFF" SWITCH PER NEC
ARTICLE 514.11. PROVIDE SIGNAGE PER IFC
SECTION 2204, 2205 (VERIFY EXACT LOCATION
WITH CIRCLE 'K' CONSTRUCTION MANAGER).
24 SERVICE ENTRANCE DISCONNECT PER UTILITY
REQUIREMENTS.
25 (2) 4" EMPTY CONDUITS FOR TELEPHONE
SERVICE. VERIFY EXACT QUANTITY AND SIZE
WITH SERVING TELEPHONE COMPANY.
26 STORE ELECTRICIAN SHALL ROUGH IN CONDUIT
AT ELECTRICAL ROOM AND RUN TO PETROLEUM
ELECTRICIAN'S POINT OF INTERCEPTION 30 FEET
FROM FRONT OF STORE. PETROLEUM
ELECTRICIAN SHALL INTERCEPT CONDUIT AND
COMPLETE RUNS TO DISPENSERS, CANOPY AND
FUEL TANKS. PETROLEUM ELECTRICIAN SHALL
FURNISH AND INSTALL ALL WIRING. REFERENCE
FUEL SYSTEM VENDOR DRAWINGS FOR ALL
REQUIRED CONDUIT, WIRE AND CIRCUITRY.
27 CANOPY GROUNDING: REFERENCE DETAILS 1 &
2/E1.1.
GENERAL NOTES
1. ALL EXTERIOR DEVICES SHALL BE WEATHERPROOF.
2. ALL FUEL ISLAND CONDUIT SHALL BE ROUTED TO THE
RESPECTIVE PANELS AND / OR TO THE FUEL CONTROL
PANELS LOCATED IN THE MANAGER'S OFFICE /
STORAGE ROOM.
3. PROVIDE EMPTY CONDUITS WITH PULL STRING.
ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
ELECTRICAL UTILITY COMPANY FOR THE EXACT
LOCATION OF ALL PRIMARY SERVICE EQUIPMENT,
TRENCH LOCATIONS, TRANSFORMER LOCATION,
METER LOCATION, ETC.
4. ELECTRICAL CONTRACTOR SHALL PROVIDE
NECESSARY SECONDARY CONDUITS, POWER
TRENCHING, BACKFILL, CONCRETE PADS FOR
TRANSFORMERS AND SERVICE EQUIPMENT AND
CONDUIT STUBS INTO TRENCH AS REQUIRED BY
ELECTRICAL UTILITY COMPANY SPECIFICATIONS.
5. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
TELEPHONE UTILITY COMPANY FOR THE EXACT
LOCATION OF ALL PRIMARY SERVICE EQUIPMENT,
SERVICE EQUIPMENT, TRENCH LOCATIONS, ETC.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
NECESSARY TELEPHONE TRENCHING, BACKFILL AND
CONDUIT STUBS INTO TRENCH AS REQUIRED BY
TELEPHONE UTILITY COMPANY SPECIFICATIONS.
7. ALL WIRING OUTSIDE SHALL BE A MINIMUM OF #10
COPPER WITH TYPE 'XHHW-2' INSULATION FOR
UNDERGROUND CIRCUIT RUN IN PVC, PROVIDE A #10
COPPER BOND IN ADDITION TO CIRCUIT CONDUCTORS.
8. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
COORDINATION AND COMPLIANCE WITH THE UTILITY
COMPANY'S REQUIREMENTS. WITHIN TWO WEEKS
AFTER AWARD OF CONTRACT, SUBMIT (2) COMPLETE
SETS OFF PLANS, INCLUDING PLOT OF SURVEY, TO
UTILITY COMPANY FOR COORDINATION. ROUTING OF
INCOMING POWER AND TELEPHONE SERVICE SHOWN
ARE FOR ESTIMATING PURPOSES ONLY. ACTUAL
ROUTING, CONDUIT, TRENCH AND PAD
REQUIREMENTS SHALL BE AS SPECIFIED BY THE
UTILITY COMPANY. CONFIRM ALL REQUIREMENTS
WITH UTILITIES PRIOR TO INSTALLATION..
9. ALL UNDERGROUND CABLE, PIPE AND CONDUITS
SHALL BE DETECTABLE (METALLIC) OR HAVE A
DETECTABLE UNDERGROUND DEVICE INSTALLED PER
LOCAL CODES.
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
J
METAL FRAME
COMPRESSION LUG OR
EXOTHERMIC WELD GROUNDING
CONNECTION. TYPICAL.
BONDING JUMPER, TYPICAL
SE
E
E
L
E
C
T
.
&
P
H
O
T
O
M
E
T
R
I
C
#3/0 AWG
LUMINAIRE,
REFERENCE SITE
LIGHTING VENDOR PLAN
SQUARE STEEL POLE WITH FINISH TO
MATCH FIXTURE AND BE APPLIED BY
MFR. CEM-TEK OR EQUAL. WIND LOAD
RATING -97 MPH AB'S AS REQUIRED BY
MFR. (MIN 24' EMBED) GROUND LUG
FOR BOND CONDUCTORS (INSIDE POLE
ACCESSIBLE FROM HANDHOLE)
HANDHOLE
3'
-0"
23
'
M
A
X
.
C
O
M
M
E
R
C
I
A
L
A
R
E
A
15
'
M
A
X
.
N
E
X
T
T
O
R
E
S
I
D
E
N
T
I
A
L
A
R
E
A
FINISHED GRADE
NOTE:
SEE STRUCTURAL
FOR LIGHT POLE
BASE REINFORCING
LIQUID SEALANT
FILLER OPENING
WITH CAP POWER AND
COMMUNICATION
WIRING
TO FIT500
ENCLOSURE
SEALING
FITTING
CONDUIT
SEALANT
GROUND
LEVEL
TO SITE POWER AND
SITE CONTROLLER
CONDUIT ENTERING THE
HAZARDOUS AREA MUST
HAVE A SEAL-OFF INSTALLED
+18" ABOVE GRADE TO
PREVENT LIQUID OR FUMES
FROM ENTERING THE AREA
REF DETAIL 1-E1.0 FOR
CIRCUIT DESIGNATION
1
23
4
5
TYP
FUEL DISPENSER.
COORDINATE CONDUIT ENTRANCE
LOCATIONS WITH MANUFACTURER
INSTRUCTIONS20' - 0 "
C L A S S I F I E D A R E A R A D I U S
LOW VOLTAGE SECTION FUEL CONTROLS,
PANELS A, B &G PANELS MDP, C, D, E LIGHTING
CNTRL, PANEL U
DISPENSER LOW
VOLTAGE CONTROLS AND
MONITORING CONDUITS
FUEL TANK SENSOR
CONDUITS
DISPENSER POWER
CONDUITS
FUEL TANK POWER
CONDUITS
FUEL CANOPY LIGHTING
AND SIGNAGE POWER
CONDUITS
13' - 9"
1'
-
0
"
INTEGRATED SWITCHGEAR
DETAIL IS DIAGRAMMATIC IN NATURE.
REFERENCE FUEL VENDOR DRAWINGS FOR EXACT QUANTITY AND
SIZE OF REQUIRED DISPENSER, TANK AND CANOPY CONDUITS.
REFERENCE SWITCHGEAR VENDOR DRAWINGS FOR EXACT LOCATION
OF CONDUIT ENTRY LOCATIONS IN SWITCHGEAR SECTIONS.
FUEL CANOPY SPEAKER
AND SECURITY CAMERA
CONDUITS
GAS CANOPY STEEL
COLUMN (TYPICAL)
#3/0 CU, EQUIPOTENTIAL
GROUND (TYPICAL)
GROUND
ROD
GROUND
ROD
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E1.1
PROJECT NUMBER: 24212
ELECTRICAL SITE
PLAN DETAILS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
KEYNOTES
1 PROVIDE SEAL-OFF FITTINGS AT EACH END OF
CONDUIT IN CONJUNCTION WITH / G.V.R.
DISPENSER MANUAL. REFERENCE DETAIL 4/E1.1.
2 3/4" CONDUIT FOR POWER/STP CONTROL.
REFERENCE DETAIL 1/E1.0 FOR POWER CIRCUIT
DESIGNATION, CONDUIT AND WIRE SIZE.
PROVIDE 4#12 THWN2 FOR STP AUTHORIZATION.
VERIFY STP AUTHORIZATION CONDUCTOR
QUANTITY, SIZE AND TYPE PER DISPENSER WITH
FUEL VENDOR DRAWINGS.
3 3/4" CONDUIT FOR DISPENSER MONITORING
SENSOR IN DISPENSER SUMP. REFERENCE
FUEL SYSTEM VENDOR DRAWINGS FOR
QUANTITY AND TYPE OF CONDUCTORS TO BE
INSTALLED.
4 3/4" CONDUIT TO SWITCHGEAR LOW VOLTAGE
SECTION FOR DISPENSER INTERCOM.
REFERENCE FUEL SYSTEM VENDOR DRAWINGS
FOR QUANTITY AND TYPE OF CONDUCTORS TO
BE INSTALLED PER DISPENSER.
5 3/4" CONDUIT FOR CRIND DATA. REFERENCE
FUEL SYSTEM VENDOR DRAWINGS FOR
QUANTITY AND TYPE OF CONDUCTORS TO BE
INSTALLED PER DISPENSER.
N.T.S.
2 CANOPY GROUNDING
N.T.S.
3 LIGHT POLE BASE
N.T.S.
4 SEAL OFF DETAIL
3/16" = 1'-0"
5 FUEL DISPENSER ENLARGED
1/2" = 1'-0"
6 SITE FUEL EQUIPMENT CONDUIT ROUGH-IN
N.T.S.
1 CANOPY GROUNDING DETAIL
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
1.8 3.2 5.3 6.8 8.0 7.7 6.6 5.1 3.3 2.5 2.8 4.1 5.8 7.2 8.2 7.4 6.0 4.3 2.5 2.0 2.5
1.5 2.6 4.2 5.6 6.1 6.7 6.6 6.1 5.8 4.5 3.8 4.0 5.3 6.0 6.4 6.8 6.5 5.8 5.1 3.4 2.8 3.9 4.6
1.6 2.4 3.4 4.7 5.5 5.6 5.7 5.8 5.9 6.0 5.6 5.1 5.3 5.9 5.9 5.9 5.8 5.7 5.6 5.2 4.1 3.4 4.3 5.6 5.7
3.9 3.1 4.5 6.7 8.4 9.4 9.7 9.8 10.0 9.9 10.0 10.1 9.9 10.0 10.0 9.9 9.9 9.9 9.7 9.5 8.8 7.5 5.9 5.3 6.5 7.8
8.5 8.9 6.7 6.1 10.7 23.0 29.1 30.3 31.0 31.2 31.1 31.4 31.6 31.2 31.9 31.5 31.7 31.8 31.6 31.7 31.5 30.6 29.6 26.3 17.1 8.2 7.4 8.2
6.2 9.1 7.5 7.8 7.8 12.3 7.6 7.1
1.9 4.6 6.8 6.1 4.9 7.4 13.6 7.4 6.1
4.7 2.6 2.0 2.8 3.9 3.0 2.9 6.1 11.0 6.0 4.4 1.8
9.3 7.6 4.6 2.5 1.8 1.7 1.7 2.3 4.1 9.1 16.1 20.1 21.8 22.1 22.2 22.6 22.3 22.4 22.7 22.4 22.4 22.3 22.3 22.3 22.2 22.1 22.0 20.3 18.1 13.1 6.3 4.0 3.1 1.9
7.8 8.7 6.9 5.6 2.4 1.6 1.4 1.4 1.9 2.9 5.0 7.3 9.0 9.9 10.3 10.4 10.4 10.5 10.5 10.5 10.5 10.5 10.5 10.4 10.5 10.5 10.2 10.1 9.5 8.1 6.0 3.9 3.1 4.0 4.7 4.2
2.1 1.1 1.2 3.0 5.9 7.2 6.2 4.1 2.1 1.4 1.1 1.6 2.3 2.9 3.3 4.1 4.9 5.3 5.7 5.8 5.7 5.8 5.8 5.7 5.7 5.7 5.7 5.8 5.9 5.9 5.8 5.6 5.2 4.4 3.5 2.8 2.9 5.2 6.9 6.7
5.3 5.5 2.5 1.6 2.2 4.3 6.3 7.3 5.1 2.6 1.1 1.1 4.2 5.3 5.0 3.0 2.7 3.0 3.3 3.6 3.8 3.8 3.6 3.4 3.3 3.3 3.3 3.4 3.6 4.0 4.3 4.5 4.3 3.8 3.4 2.9 2.6 3.1 6.1 9.2 9.9
5.0 8.2 6.5 5.1 2.4 2.4 5.2 6.8 7.9 7.6 3.6 7.1 8.1 6.7 3.2 2.2 2.4 2.8 3.5 4.4 4.4 3.3 2.6 2.2 2.1 2.2 2.5 3.1 4.4 5.7 6.0 5.9 5.4 5.4 5.0 4.2 4.0 3.3
8.8 8.3 6.6 3.5 2.7 5.3 7.7 10.0 6.4 8.5 9.0 6.5 3.2 2.1 2.6 3.6 5.3 8.8 8.9 4.4 2.3 1.8 1.6 1.7 2.1 3.4 7.4 11.2 9.2 8.0 7.5 7.4 6.9 5.9 4.9 3.2
6.4 4.2 2.5 2.0 3.3 6.0 6.3 7.7 6.8 3.2 2.4 3.5 6.4 7.4 9.0 15.0 12.2 10.3 9.8 9.5 10.3 10.4 10.2 14.4 13.5 8.5 9.3 8.4 8.2 7.4 5.0 3.4 1.8
1.6 1.2 1.1 1.1 3.5 5.3 5.6 9.4 5.2
2.7 6.3 7.0 3.7 1.8 1.6
2.2 5.3 5.4
3.4 7.8 6.5
5.0 8.5 5.8
34 38 41 45 45 46 46 44 45 47 47 46 46 44 46 46 47 46 45 45 47 47 46 46 44 46 47 47 46 45 44 46 46 45 45 41 38 34
40 33 36 45 53 53 45 36 41 55 53 54 43 0 45 54 53 49 39 39 49 53 54 45 0 43 54 53 54 41 36 45 53 53 45 36 32 40
39 38 41 53 53 53 53 43 46 54 53 54 54 27 54 54 54 54 45 45 54 54 54 54 27 54 54 53 54 46 42 53 53 52 53 41 37 39
36 30 40 42 48 49 49 51 47 50 51 50 48 51 49 50 51 50 52 52 50 51 50 49 51 48 50 51 50 47 51 49 49 48 42 39 31 35
34 38 41 47 44 45 48 47 48 46 45 46 48 47 48 46 45 48 47 47 48 45 46 48 47 48 46 45 46 47 47 48 44 44 46 40 37 33
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.4 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.5 0.8 1.2 1.2 0.8 0.6 0.5 0.5 0.5 0.5 0.6 1.0 1.3 1.0 0.6 0.5 0.5 0.5 0.6 0.6 0.3 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.4 0.5 0.7 1.1 2.0 3.6 3.2 1.7 1.2 0.9 0.9 0.9 1.0 1.3 2.4 3.8 2.7 1.4 0.9 0.8 0.9 1.2 1.3 0.6 0.2 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.4 0.6 1.0 2.7 1.4 0.3 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.4 0.6 0.9 3.4 0.6 0.3 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.2 0.4 0.6 0.9 1.1 1.3 0.5 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.2 0.3 1.1 2.1 4.3 2.9 0.9 0.3 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.3 0.7 2.3 3.3 1.1 0.3 0.2 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.3 0.4 0.9 2.2 0.8 0.3 0.2 0.2 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.2 0.2 0.1 0.1 0.2 0.1 0.3 0.5 0.6 0.7 1.9 2.1 0.8 0.5 0.4 0.3 0.2 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.2 0.3 0.3 0.3 0.3 0.3 0.5 1.4 2.0 0.9 0.7 0.6 0.4 0.3 0.2 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.2 0.4 0.5 0.5 0.4 0.5 1.1 3.2 1.2 1.1 0.8 0.6 0.4 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.3 0.6 0.8 0.7 0.7 0.8 2.6 4.1 2.2 0.9 0.5 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.4 1.2 2.5 6.3 3.3 1.1 0.5 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.6 3.1 7.2 3.2 0.8 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.5 0.9 1.7 3.4 3.5 1.8 0.7 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.5 2.2 1.4 0.8 2.1 2.1 1.4 0.8 0.4 0.2 0.1 0.1 0.1 0.0
0.0 0.1 0.2 1.2 2.3 3.0 0.4 0.9 0.7 1.5 1.1 0.7 0.5 0.4 0.2 0.2 0.1 0.1 0.0
0.0 0.1 0.1 0.3 0.7 1.2 0.9 0.9 0.6 0.5 0.6 1.1 4.0 3.6 4.7 10.3 11.9 6.7 3.8 2.8 1.6 1.1 0.8 0.7 0.7 0.6 0.5 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.1 0.2 0.3 0.4 0.5 0.5 0.4 0.4 0.3 0.3 0.4 0.5 0.3 6.9 6.7 5.2 7.5 6.3 7.7 5.0 2.2 1.4 1.2 1.5 1.9 1.0 0.6 0.4 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.4 0.2 9.3 7.4 4.6 4.5 3.2 4.0 3.4 1.9 1.3 1.8 4.2 5.6 2.6 0.9 0.4 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.3 1.3 4.5 7.5 7.5 5.5 4.0 6.3 5.2 7.0 4.4 1.8 1.2 1.9 5.0 7.4 3.0 0.9 0.4 0.2 0.1 0.1 0.0
0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.3 0.7 1.5 1.7 1.7 3.5 9.5 8.8 11.2 5.5 1.7 0.8 1.4 4.7 7.5 2.4 0.4 0.2 0.1 0.1 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.3 0.5 1.0 2.4 5.7 5.0 1.8 6.0 9.2 4.9 4.8 9.3 6.7 4.0 7.6 8.3 3.0 3.2 5.7 3.5 1.2 0.6 0.4 0.7 1.5 1.9 1.0 0.4 0.2 0.1 0.0 0.0
0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.2 0.3 0.6 1.2 1.9 1.9 2.6 6.3 9.0 5.7 5.7 9.2 7.2 4.9 7.8 8.2 3.6 1.8 1.8 1.4 0.7 0.4 0.2 0.2 0.3 0.3 0.2 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.2 0.3 0.5 0.7 0.8 1.4 2.4 3.0 2.6 2.7 3.2 2.9 2.5 2.9 2.8 1.6 1.0 0.7 0.6 0.4 0.2 0.1 0.1 0.1 0.1 0.1 0.0 0.0
0.0 0.1 0.1 0.1 0.2 0.3 0.3 0.4 0.6 0.8 0.9 1.0 1.0 1.1 1.0 1.0 1.0 0.9 0.7 0.4 0.3 0.3 0.2 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.3 0.2 0.2 0.1 0.1 0.1 0.1 0.0 0.0 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.1 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0
41
L
42
L
43
L
44
L
45
L
46
L
47
L
48
L
49
L
50
L
51
L
77
WP
78
WP
79
WP
80
WP
81
WP
82
WP
83
WP
84
WP
85
WP
1
A3B
2
A3B
3
A3B
4
A3B
5
A4B
6
A4B
7
A4B
8
A4B
9
A4B
10
A4B
11
A4B
12
A4B
13
CAN1
14
CAN1
15
CAN1
16
CAN1
17
CAN1
18
CAN1
19
CAN1
20
CAN1
21
CAN1
22
CAN1
23
CAN1
24
CAN1
25
CAN1
26
CAN1
27
CAN2
28
CAN2
29
CAN2
30
CAN2
31
CAN2
32
CAN2
33
CAN2
34
CAN2
35
CAN2
36
CAN2
37
CAN2
38
CAN2
39
CAN2
40
CAN2
52
SF04
53
SF04
54
SF04
55
SF04
56
SF04
57
SF04
58
SF04
59
SF04
60
SF12
61
SF12
62
SF12
63
SF12
64
SF12
65
SF12
66
SF12
67
SF12
68
SF12
69
SF12
70
SF12
71
SF12
72
SF12
73
SF12
74
SF12
75
SF12
76
SF12
LUMINAIRE SCHEDULE
SYMBOL QTY LABEL ARRANGEMENT LUMENS LLF BUG RATING WATTS/LUMINAIRE TOTAL WATTS MANUFACTURER CATALOG LOGIC
4 A3B Single 12072 1.030 B1-U0-G2 114.07 456.28 Lithonia Lighting RSX2 LED P2 50K R3 MVOLT SPA HS FAO
8 A4B Single 11790 1.030 B1-U0-G3 114.07 912.56 Lithonia Lighting RSX2 LED P2 50K R4S MVOLT SPA HS FAO
14 CAN1 Single 14198 1.030 B3-U0-G1 91.38 1279.32 Lithonia Lighting XPCNY LED ALO2-13L SWW2-50K FPCL MVOLT DWHXD M3
14 CAN2 Single 14940 1.030 B3-U0-G2 88.88 1244.32 Lithonia Lighting XPCNY LED ALO2-13L SWW2-50K FTL MVOLT DWHXD M3
11 L SINGLE 2238 1.030 N.A. 25.15 276.65 Lithonia Lighting LBR6 ALO2 20LM SWW1 (4000K) AR LSS MWD 90CRI WL
8 SF04 SF 4FT 110 1.000 N.A. 1.04 116.48 P-LED PL-OP2-PD324-P-NW
17 SF12 SF 12FT_1 110 1.000 N.A. 1.04 777.92 P-LED PL-OP2-PD324-P-NW
9 WP SINGLE 6659 1.030 B1-U0-G1 51.2609 461.348 Lithonia Lighting ARC2 LED P5 50K MVOLT
FOOTCANDLE LEVELS CALCULATED AT GRADE USING INITIAL LUMEN VALUES
LABEL AVG MAX MIN AVG/MIN MAX/MIN
PAVED AREA 7.40 31.9 1.1 6.73 29.00
UNDER CANOPY 45.68 55 0 N.A. N.A.
UNDEVINED 0.81 11.9 0.0 N.A. N.A.
LUMINAIRE LOCATION SUMMARY
LUM NO.LABEL MTG. HT.
1 A3B 18
2 A3B 18
3 A3B 18
4 A3B 18
5 A4B 18
6 A4B 18
7 A4B 18
8 A4B 18
9 A4B 18
10 A4B 18
11 A4B 18
12 A4B 18
13 CAN1 15.5
14 CAN1 15.5
15 CAN1 15.5
16 CAN1 15.5
17 CAN1 15.5
18 CAN1 15.5
19 CAN1 15.5
20 CAN1 15.5
21 CAN1 15.5
22 CAN1 15.5
23 CAN1 15.5
24 CAN1 15.5
25 CAN1 15.5
26 CAN1 15.5
27 CAN2 15.5
28 CAN2 15.5
29 CAN2 15.5
30 CAN2 15.5
31 CAN2 15.5
32 CAN2 15.5
33 CAN2 15.5
34 CAN2 15.5
35 CAN2 15.5
36 CAN2 15.5
37 CAN2 15.5
38 CAN2 15.5
39 CAN2 15.5
40 CAN2 15.5
41 L 12
42 L 12
43 L 12
LUMINAIRE LOCATION SUMMARY
LUM NO. LABEL MTG. HT.
44 L 12
45 L 12
46 L 12
47 L 12
48 L 12
49 L 12
50 L 12
51 L 12
52 SF04 18.5
53 SF04 18.5
54 SF04 18.5
55 SF04 18.5
56 SF04 18.5
57 SF04 18.5
58 SF04 18.5
59 SF04 18.5
60 SF12 18.5
61 SF12 18.5
62 SF12 18.5
63 SF12 18.5
64 SF12 18.5
65 SF12 18.5
66 SF12 18.5
67 SF12 18.5
68 SF12 18.5
69 SF12 18.5
70 SF12 18.5
71 SF12 18.5
72 SF12 18.5
73 SF12 18.5
74 SF12 18.5
75 SF12 18.5
76 SF12 18.5
77 WP 14.5
78 WP 14.5
79 WP 14.5
80 WP 14.5
81 WP 14.5
82 WP 14.5
83 WP 14.5
84 WP 14.5
85 WP 14.5
NOTE:
- ALL AREA LIGHTS ON NEW 15 FT. POLE MOUNTED ON 3 FT. CONCRETE BASE
NA TURA L GRO UND NA TURA L GRO UND
NA TURA L GRO UND
A S P H A LT S U R F A C E
~
~
W/CO
NCAVE SE
ATS
SG150D OR SG
150P
WABASH VA
LLEY
46" RO
UND TA
BLE
W/CO
NCAVE SE
ATS
SG150D OR SG
150P
WABASH VA
LLEY
46" RO
UND TA
BLE
SHUT- OFF SHUT- OFF
EXTERIO R ROO FACCESS LADDER
TRANSFORMER
PAD (APPROX)
APPROX
LOCATION
OF GREASE
TRAP; 3
INCH
INTERNAL
DROP
EXCAVATION HOLE
K I L L I O N R O A D S E
(MAJOR COLLECTOR)
Y E L
M
A V E N
U
E / S R
5 1 0
(
M
IN
O
R A
R
T
E
RIA
L)
(ACCESS ROAD)
TRANSFORMER
PAD (APPROX)
W
12
K
D
I
E
S
E
L
(
1
0
'
D
I
A
.
)
8K CK CHOICE12K SUL
20K REGULAR
E XCE PTION
20' B.S.L.20' B.S.L.
2 0' B .S.L.
15' B.S.L.
15' B.S.L.
15' B.S.L.
15' B.S.L.
15' B.S.L.
8.5'
6.0'
3.9'
E
E
W
*
*
*
S 39 °01'29"W 1 99.78'
S88°15'36"E 433.15'
413.15'147.35'
(151')
N 4 7 °0 4'2 9 "E 9 1.2 4'(9 5.0 0')
S
5
0
°23'1
2"E 6
07.8
6'
S
5
0
°23'1
2"E 1
04.4
7'(1
07')
S
5
0
°23'1
2"E 6
07.8
6'
N01°30'23"E 437.31'
E
E
E
E
E
E
E
G
G
G
G
G
G
G
G
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
8"S
D
1 2"S D
12"SD
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
L/S
MAG NAIL WITH
WASHER MARKED
"E-TRUE LS 2422 1"
[N4 7°0 4'2 9"E 2 .33 ']
1/2" REBAR WITH
CAP IL LEGIBLE
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
E/T
T
T
T
T
T
T
T
T
T
(#3926418)
EASEMENT
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E1.2
PROJECT NUMBER: 24212
ELECTRICAL SITE
PHOTOMETRIC
PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
N.T.S.
1 ELECTRICAL SITE PHOTOMETRIC PLAN
FOR
INFORMATION
ONLY
OTP 11/12/24
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E1.3
PROJECT NUMBER: 24212
EXTERIOR LIGHT
FIXTURE CUT
SHEETS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
TYPE "A3B" & "A4B" LIGHT FIXTURE TYPE "CAN1" & "CAN2" LIGHT FIXTURE TYPE "L" LIGHT FIXTURE TYPE "WP" LIGHT FIXTURE
FOR
INFORMATION
ONLY
OTP 11/12/24
KB
J
J
JJ
J
J
J
J
J
J
JJ
J
J
J
J
JJ
SM
SM
SM SM
SM
J
JJ
JJ
J
J
SM
J J
J
C
-
1
,
3
C
-
2
,
4
C
-
6
,
8
B
-
2
2
C
-
3
2
B - 15
B - 1
B - 3
B - 5
B - 4
B - 6
B - 2
C
-
1
0
A
-
2
5
9'-10"
9'-10"
E
-
3
9
C
-
2
5
D
-
3
0
FF
-3
B - 23
B
-
2
0
,
2
1
+90"
+48"
+90"
+48"
+90"
+48"
C - 34
9'-10"
U - 2
U - 4
6'-6"
U - 7
U - 5
B - 10
B - 9
B - 12,14
B - 11,13
B
-
3
3
B
-
3
1
B
-
4
0
B
-
3
2
B
-
4
2
B
-
3
6
C
-
2
3
C
-
2
4
,
2
6
D
-
3
8
,
4
0
B - 17
C
-
3
3
C
-
3
5
A - 38,40,42
D
-
2
5
C - 30
+4
4
"
A - 24
SURFACE MOUNT
AT CEILING, TYP
EXTERIOR ROOF
ACCESS LADDER
B - 7
D - 26
FF-1
+18"+18"
+30"+36"
+30"
+30"
+30"
+30"
D - 7
D
-
1
9
D - 12,15
D - 15
D
-
1
0
D
-
4
2
WP E - 31,33
D - 23
C - 36
B
-
1
8
D
-
5
B - 16
D
-
1
7
,
1
9
9'
-10
"
A - 23
A - 32
A - 37
C - 31
WP
(PART 1/2)
B - 7 (PART 2/2)
9'-10"C - 9
(PART 1/2)
(PART 2/2)
C - 9
D - 14D - 16
+48"
+48"
C - 27
D - 3
D - 6
B - 37,39,41
B - 25,27,29
C - 37,39,41
D - 27,29
D - 9
U - 3
C - 40
U - 6
1TYP
22
TYP
3 TYP
4
5
6
7
8TYP
99
10
TYP
11
12TYP OF 2 A - 19
D - 8
1313
13
14
TYP
INTERIOR E-STOP/CASHIER
CONTROL PANEL MOUNTED UNDER
COUNTER, FIELD VERIFY LOCATION
WITH CONSTRUCTION MANAGER
A - 28
WP
WP
WP
WP
WP
WP WP D - 21
DOOR POINT OF ELECTRICAL
CONNECTION, TYP
+4
4
"
+4
4
"
+30"+36"
FF
-
2
15
16
9'
-10
"
15
17
1818
4
E
-
4
1
D
-
1
1
+ 88"
C - 21
+ 88"
+ 88"
19
WP
EVAPORATOR
COIL, TYP
D - 1
+24"
+24"
+24"+24"
+42"+42"
2020
D - 35 D - 37
B - 35
C - 38
U - 8
U - 1
SPLIT QUAD,
CIRCUIT EACH HALF
TO ONE CIRCUIT
WP WP
C - 42
WALK-IN
COOLER
104
BACK ROOM
109
STORAGE
ROOM
103
COLD VAULT
105WALK-IN
FREEZER
106
SALES FLOOR
107
MEN'S
RESTROOM
102
PREP AREA
110
CASHIER
108
STORE SERVICE
ENTRANCE DISCONNECT
UTILITY CT CABINET / METER
PER UTILITY REQUIREMENTS
DI
S
T
R
I
B
U
T
I
O
N
P
A
N
E
L
D
P
1"C,3#4,#8G
99
3/4"C,2#10,
#10G
3/4"C,3#10,#10G
21
22
WOMEN'S
RESTROOM
101
D
-
2
8
23
24 25
21
E - 42
E - 40
C - 19
26
+ 10"
C - 20,22
3/4"C,3#10,#10G
FUEL DISPENSER
CONDUITS
INTERCOM G-39
DISTRIBUTION DATA G-41
DISTRIBUTION PANEL DP IS
AN INTEGRATED
ASSEMBLY INCLUDING
PANELS A, B, C, D, E, G & U.
REFERENCE VENDOR
SHEETS
27
25
24
28
29 SITE LIGHTING AND
FUEL CANOPY
LIGHTING CONDUITS
G - 37
30+36"
+4
4
"
B - 24
B
-
8
C
-
1
1
C
-
1
2
D - 2,4
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E2.0
PROJECT NUMBER: 24212
ELECTRICAL
FLOOR PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
1. ALL ELECTRICAL DEVICES SHALL BE
WEATHERPROOF.
2. ALL 125V THROUGH 250V RECEPTACLES SUPPLIED
BY SINGLE-PHASE BRANCH CIRCUITS RATED 150V OR
LESS TO GROUND, 50A OR LESS, AND ALL
RECEPTACLES SUPPLIED BY THREE-PHASE CIRCUITS
RATED 150V OR LESS TO GROUND, 100A OR LESS
LOCATED AT FOOD PREPARATION, FOOD SERVICE OR
BEVERAGE COUNTERS SHALL BE PROTECTED BY A
READILY ACCESSIBLE GFCI DEVICE PER NEC 210.8(B)
(2). GFCI DEVICE MAY BE LOCATED EITHER IN A
RECEPTACLE OR CIRCUIT BREAKER. FACE PLATE OF
RECEPTACLE CONTROLLED BY GFCI DEVICE SHALL
BE MARKED WITH GFCI PROTECTED SYMBOL.
3. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH
PULL STRINGS.
4. REFER TO DRAWING A1.5 FOR EQUIPMENT SCHEDULE
AND TERMINATION REQUIREMENTS. REFER TO
ARCHITECTURAL DRAWINGS FOR ISLAND DETAILS.
5. ALL EQUIPMENT WITH REMOTE CONDENSERS
MOUNTED ON THE ROOF SHALL HAVE 1/2" EMPTY
CONDUIT (SEE POWER GENERAL NOTE 3) BETWEEN
THE EQUIPMENT AND THE REMOTE CONDENSER FOR
CONTROL CIRCUITS.
6. ELECTRICAL CONTRACTOR SHALL VERIFY ALL
EQUIPMENT CONNECTIONS, MOUNTING HEIGHTS AND
CORD REQUIREMENTS WITH EQUIPMENT
MANUFACTURER PRIOR TO INSTALLATION. ALL
EQUIPMENT SHALL BE LISTED FOR ITS INTENDED USE
PER NEC ART. 400.7.
7. PROVIDE HEAT TAPE FOR ALL EXPOSED PIPING. HEAT
TAPE TO BE FROM THE SAME CIRCUIT SERVING
EQUIPMENT. SEE MECHANICAL SHEETS FOR DETAILS.
8. ELECTRICAL CONVEYANCES FROM BREAKERS TO
OUTLET OR FIXTURE SHALL BE ENCLOSED WITHIN
CEILING SPACE, FINISHED WALLS OR CABINETRY AND
NOT EXPOSED. CODE 6-201.12.
9. PROVIDE POWER TO SMOKE DAMPER WITH
DISCONNECT. COORDINATE WITH MECHANICAL FOR
LOCATION. CIRCUIT NUMBER IS A-39.
POWER GENERAL NOTES
3/16" = 1'-0"
1 ELECTRICAL FLOOR PLAN
KEYNOTES
24 (1) 1" EMPTY CONDUIT WITH PULL STRING FOR INTERCOM
FROM PANEL DP LOW VOLTAGE SECTION 1 TO CHECKOUT.
REFERENCE DP MANUFACTURER INFORMATION.
25 (1) 2" EMPTY CONDUIT WITH PULL STRING FROM PANEL DP
LOW VOLTAGE SECTION 1 TO CHECKOUT CABINET.
REFERENCE DP MANUFACTURER INFORMATION.
26 WINE RACK RECEPTACLES: REFERENCE MANUFACTURER
INSTRUCTION FOR EXACT LOCATION OF RECEPTACLES
WITHIN DISPLAY.
27 (1) 2" EMPTY CONDUIT WITH PULL STRING TO MANAGER'S
DESK.
28 FUEL ISLAND DISPENSER / FUEL TANK POWER, CONTROL
AND MONITORING CONDUIT ENTRANCES. REFERENCE
SHEET E1.0, DETAILS 5/E1.1, 6/E1.1 AND FUEL SYSTEM
VENDOR DRAWINGS.
29 CONDUIT ENTRY POINT FOR FUEL CANOPY LIGHTING /
SIGNAGE AND SITE LIGHTING CONDUIT(S). REFERENCE
SHEETS E1.0 AND E1.1.
30 VEEDER ROOT TLS450 MONITOR SYSTEM. PROVIDE (4) 1"
CONDUITS WITH PULL STRING STUBBED UP +30" AFF AT
MONITOR LOCATION, ROUTED UNDERSLAB TO LOW
VOLTAGE CONTROL SECTION 1 IN SWITCHGEAR DP.
REFERENCE SWITCHGEAR VENDOR DRAWINGS FOR LOW
VOLTAGE SECTION LOCATION. VEEDER ROOT MONITOR
CONSOLE TO BE INSTALLED +48" AFF TO CENTER BY
PETROLEUM SYSTEMS ELECTRICIAN. COORDINATE EXACT
LOCATION WITH PETROLEUM SYSTEMS ELECTRICIAN.
KEYNOTES
12 MOUNT RECEPTACLE TO ACCESSIBLE CEILING IN COOLER /
BEER CAVE FOR LOW VOLTAGE SIGNAGE. SEAL SLEEVE
WITH POLY SILICON CAULKING TO PREVENT MOISTURE AND
AIR FROM ENTERING AND DAMAGING THE TRANSFORMER
AND LOW VOLTAGE WIRING.
13 PROVIDE JUNCTION BOX WITH DUPLEX RECEPTACLE FOR
PLUG IN ABOVE THE CEILING GRID.
14 PROVIDE JUNCTION BOX ABOVE CEILING FOR HARDWIRED
ELECTRICAL CONNECTION.
15 COOLER EVAPORATOR. PROVIDE 20A 250V 1P +
EQUIPMENT GROUND, FUSIBLE HEAVY DUTY SAFETY
SWITCH IN NEMA 3R ENCLOSURE. PROVIDE 2#12 1#12 GND,
IN 3/4" CONDUIT. PROVIDE SEAL-OFF DEVICE PER NEC 300.7
AND PROVIDE GROUND FAULT PROTECTION FOR HEAT
TRACE PER NEC 427.22. PROVIDE WP GFCI RECEPTACLE
FOR MAINTENANCE.
16 CO2 ALARM STROBE JUNCTION BOX. SINGLE GANG
JUNCTION BOX MOUNTED 8" BELOW CEILING CENTERED ON
DOOR WITH CONDUIT TO ACCESSIBLE BACKROOM CEILING
SPACE FOR LOW VOLTAGE COMMUNICATION WIRING BY
OTHERS.
17 FREEZER EVAPORATOR. PROVIDE 20A 250V 2P +
EQUIPMENT GROUND, FUSIBLE HEAVY DUTY SAFETY
SWITCH IN NEMA 3R ENCLOSURE. PROVIDE 2#12 1#12 GND,
IN 3/4" CONDUIT. PROVIDE SEAL-OFF DEVICE PER NEC 300.7
AND PROVIDE GROUND FAULT PROTECTION FOR HEAT
TRACE PER NEC 427.22. PROVIDE WP GFCI RECEPTACLE
FOR MAINTENANCE.
18 PROVIDE FLUSH MOUNT RECEPTACLE IN CEILING FOR
WINDOW DISPLAYS.
19 JUNCTION BOX AND RECEPTACLE FOR CO2 MONITOR
CONTROL PANEL. CATEGORY 5 CONTROL WIRING TO BE
CONCEALED WITHIN WALL. NO EXPOSED WIRING IN SALES
AREA.
20 HAND DRYER: INSTALL PER MANUFACTURER
INSTRUCTIONS.
21 PROVIDE (1) 2" EMPTY CONDUIT WITH PULL STRING FROM
CHECKOUT ISLAND TO CHECKOUT CABINET.
22 PROVIDE (1) 2" EMPTY CONDUIT WITH PULL STRING FROM
CHECKOUT ISLAND TO NETWORK RACK.
23 (1) 2" EMPTY CONDUIT WITH PULL STRING FROM CHECKOUT
CABINET TO MANAGER'S DESK.
KEYNOTES
1 JUNCTION BOX FOR AUTOMATIC FLUSH SENSOR.
COORDINATE EXACT MOUNTING HEIGHT WITH
MANUFACTURER INSTRUCTIONS AND PLUMBING
CONTRACTOR.
2 PROVIDE NEMA L15 SPECIAL OUTLET AND MATCHING
CORD/PLUG FOR COMPLETE CONNECTION OF EQUIPMENT.
3 PROVIDE FLUSH RECESSED HUBBELL FLOOR BOX WITH
BRASS COVER PLATE FOR POWER TO DISPLAYS AND
EQUIPMENT.
4 JUNCTION BOX WITH (1) 3/4" EMPTY CONDUIT TO NETWORK
SWITCH IN OFFICE AREA FOR ATM DATA.
5 PROVIDE AND INSTALL CONDUIT(S) UNDER SLAB FROM THE
PANELS IN THE BACK OF THE HOUSE TO THE FOOD PREP
AREA IN FRONT OF STORE. TRANSITION FROM PVC TO GRC
90 DEGREE ELL TO STUB-UP THROUGH SLAB AND
CONTINUE CIRCUIT TO EQUIPMENT RECEPTACLE USING
ARMORED FLEX. PROVIDE A MEANS OF MOUNTING FOR
RECEPTACLE UNDER THE EQUIPMENT. CONFIRM EXACT
LOCATION AND REQUIREMENTS WITH OWNER PRIOR TO
INSTALLATION.
6 PROVIDE CEILING MOUNTED RECEPTACLE FOR NEON
SIGNAGE AT COLD VAULT.
7 PROVIDE JUNCTION BOX FOR HARD WIRE CONNECTION TO
RE-CIRC PUMP AND AQUA-STAT TIMER. PROVIDE MOTOR
RATED SWITCH PER 422.31 (C). VERIFY EXACT LOCATION
AND MOUNTING HEIGHT PRIOR TO ROUGH-IN.
8 PROVIDE 3/4" CONDUIT UNDER SLAB FROM CASEWORK
BACK TO WALL FOR 120V POWER TO FLOOR BOXES. ROUTE
IN FIELD TO NEAREST ACCESSIBLE POINT AND MINIMIZE
INTERFERENCES. REFER TO ARCHITECTURAL PLANS FOR
MORE INFORMATION.
9 PROVIDE SPECIAL OUTLET FOR COMPLETE CONNECTION
OF EQUIPMENT. VERIFY EXACT NEMA CONFIGURATION
WITH SUPPLED EQUIPMENT.
10 WATER HEATER AT 208V 3PH. PROVIDE 100A 250V
3P+EQUIPMENT GROUND, NON-FUSIBLE DISCONNECT
SWITCH INSTALLED IN READILY ACCESSIBLE LOCATION.
11 E.C. SHALL PROVIDE A HEAT TAPE FOR RECEPTACLES.
CONNECT TO RECEPTACLE CIRCUIT WITH 2#12, 1#12 GND IN
3/4" CONDUIT. COORDINATE EXACT REQUIREMENTS WITH
MECHANICAL CONTRACTOR.
NOTE:
REFER TO SHEETS A1.5.1 AND A1.5.2 FOR
ADDITIONAL EQUIPMENT ELECTRICAL
INFORMATION AND REQUIREMENTS.
COORDINATE ROUTING OF BRANCH CIRCUITS IN SIPS
PANEL WITH VENDOR INSTALLED CHASES OR IN FURRED
OUT WALLS. CIRCUITS SHALL NOT BE ROUTED EXPOSED
ON SIPS PANELS OR WALLS. MINIMAL CUTTING OF SIPS
PANELS FOR RECESSED BOXES OR DEVICES IS ALLOWED.
COORDINATE LOCATIONS WITH PANEL MANUFACTURER
SECURITY CAMERAS AND MONITORS ARE FURNISHED AND
INSTALLED BY OTHERS. CONTRACTOR TO PROVIDE ALL
PENETRATIONS AND WIRING IN ACCORDANCE WITH LOCAL
CODE. SECURITY CONTRACTOR IS RESPONSIBLE FOR LOW
VOLTAGE PERMITTING AND INSPECTIONS. ALL
PENETRATIONS IN EXTERIOR WALLS AND WALK-IN COOLERS
SHALL BE SEALED PER SPECIFICATIONS. CONTRACTOR TO
COORDINATE WITH SECURITY SYSTEM INSTALLER.
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
SD SD
J
PE
C - 5
WP
WP
WP WP
1
EXTERIOR ROOF
ACCESS LADDER
E - 2,4,6
E - 8,10,12
ISLAND
MERCH.
ICE
MACHINE
ICE
MACHINE
ICE
MACHINE
E - 7,9,11
E - 13,15,17
3/4"C,3#10,1#10G
30AS/30AF, NEMA 3R
E - 19,21,23
E - 25,27,29
E - 14,16,18
E - 20,22,24
3/4"C,3#10,1#10G
30AS/20AF, NEMA 3R
3/4"C,3#12,1#12G
30AS/20AF, NEMA 3R
3/4"C,3#8,1#10G
60AS/50AF, NEMA 3R
3/4"C,3#10,1#10G
30AS/20AF, NEMA 3R
WALK-IN
FREEZER
WALK-IN
COOLER
COLD
VAULT
ZERO ZONE
FREEZER
B - 19
DP - 7
DP - 8
WP 2
1
3
4
5
4
4
6
6
1"C,3#3,1#8G
4
7
7
3/4"C,3#10,1#10G
30AS/25AF, NEMA 3R
3/4"C,3#10,1#10G
30AS/25AF, NEMA 3R
3/4"C,3#10,1#10G
30AS/25AF, NEMA 3R
1 - 1 1/2"C,3#1/0,1#6G
5
OAU1 RTU1
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E4.0
PROJECT NUMBER: 24212
ROOF POWER
PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
3/16" = 1'-0"
1 ROOF POWER PLAN
KEYNOTES
1 WP, GFCI WEATHER RESISTANT RECEPTACLE ON
ROOF.
2 WP JUNCTION BOX ON ROOF FOR SATELLITE
DISH WITH 1" EMPTY CONDUIT TO CASHIER
COUNTER LOTTO MACHINE. VERIFY EXACT
LOCATION OF SATELLITE DISH IN FIELD.
3 MOUNT PHOTOCELL TO INTERIOR WALL OF
PARAPET. ROUTE CONDUIT THROUGH PARAPET
WALL TO LIGHTING CONTROL. DETAIL 2/E6.0.
4 ROOF TOP UNIT IS PROVIDED WITH
MANUFACTURER FACTORY INSTALLED
DISCONNECT AND GFI MAINTENANCE
RECEPTACLE. CIRCUIT AS SHOWN.
5 DUCT SMOKE DETECTOR.
6 WP GFCI RECEPTACLE FOR MAINTENANCE.
MOUNT ADJACENT TO DISCONNECT.
7 EXTEND CONDUIT AND WIRE TO THERMOSTAT
FOR LINE VOLTAGE CONNECTION. COORDINATE
WITH MECHANICAL CONTRACTOR.
1. ALL EXTERIOR DEVICES SHALL BE WEATHERPROOF
RATED.
2. ALL EQUIPMENT WITH REMOTE CONDENSERS
MOUNTED ON THE ROOF SHALL HAVE (1) 1/2" EMPTY
CONDUIT BETWEEN THE EQUIPMENT AND THE
REMOTE CONDENSER FOR CONTROL CIRCUITS.
3. ROUTE CONDUIT(S) FOR CONDENSERS THROUGH
SAME WEATHERPROOF GOOSENECK USED FOR
CONDENSATE PIPING - REFER TO DETAIL #2 ON
SHEET M1.2.1.
4. SEAL ALL BUILDING PENETRATIONS.
5. HEAT TRACE TO BE PROVIDED IN COLD REGIONS.
ROOF POWER
GENERAL NOTES
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
J J
J
J
J
J
J
J J
J J
JJJ
J
J
J
J
J
J J J J J
J J J J J
J
J
J
J J
J J
J
J
IN
V
SM
J
JJ
J
J J
S
J J
J
J
J
J
J
PE
PE
PE
PE
PE
PE
PE
J
J
J J
A B
2
1
a b a
b
a
a
a
a
a
b
b
b
b
b
b
ba
a
b a
b
b a
a
a
a
a
a
a
1
2
c c
c
c
c
c d d
dd
NL/EM
NL/EM
NL/EM
NL/EM
NL/EM NL/EM NL/EM
NL/EM
NL/EM
NL/EM
NL/EM
NL/EMNL/EM
NL/EM
33
3
333
3
3
3
3
3
3
3
3
DAYLIGHT ZONE
SECONDARY DAYLIGHT ZONE
DAYLIGHT
ZONE LIMIT
SECONDARY
DAYLIGHT
ZONE LIMIT
DAYLIGHT ZONE
SECONDARY DAYLIGHT ZONE
DAYLIGHT ZONE
SECONDARY
DAYLIGHT ZONE
A - 17
VIA 'c' & 'd'
NL/EM 3
VIA 'a' & 'b'
EX
e e e
A - 30
A - 16
VIA 'e'
EX
INVERTER
A - 33
LOGO
SIGN
14'-6" AGL
4
14'-6" AGL
14'-6" AGL
14'-6" AGL 14'-6" AGL14'-6" AGL
14'-6" AGL
WP
A - 27
A - 21
5
5
A - 14
K
J
EX
W
EX
L
B
B
B
B
BB
EM
EM EM
BBBB
B B B
B
EM
A A
AAE
A AE
A A
AE
AA
A
A A
A
A C C C
CECCE
C
C
C C C C
A
AE A A
AA
A
A
AE
A
AAA
A AE AA
AE
A A
A
AAEA
DDEDDED
AD
DE
AA
K
J
W
8'-0" AFF
10'-6" AFF
A
A
A
b
a
b
AE
BB
AE
LL
L
LLLLL
LL
BBB
A
A
A
TO INVERTER
A - 10
TO FRONT
ENTRANCE
LIGHTS
VIA LIGHTING
CONTROLS
e e
BB
NL/EM 3
JJ
J JE
K
K
NL/EM
3
WP
WP
WPWPWP
WP
WP
B
66
AE
A a A a
7 VIA LIGHTING CONTROLS
SALES FLOOR
107
WALK-IN
COOLER
104
BACK ROOM
109
COLD VAULT
105
STORAGE
ROOM
103
WALK-IN
FREEZER
106
MEN'S
RESTROOM
102
CASHIER
108
PREP AREA
110
7
WOMEN'S
RESTROOM
101
4
B B
14'-6" AGL
WP
14'-6" AGL
WP
B
ON
OFF
A-30
a
CIRCUIT CONTROLLED (TYP.)
CONTROL IDENTIFICATION
ON
OFF
A-30
b
ON
OFF
A-17
c
ON
OFF
A-17
d
ON
OFF
A-16
e
TS
C
MULTI-POLE LIGHTING
CONTACTOR OR TIME
SWITCH
TO EXTERIOR
FIXTURES TYPE L120V
120V
EXTERIOR AUTOMATIC
LIGHTING CONTROLS
NEUTRAL
120V
120V
UNSWITCHED
BRANCH
CIRCUIT
TO EXTERIOR EGRESS
FIXTURES TYPE W
EMERGENCY
BATTERY
SWITCHED
BRANCH
CIRCUIT
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E5.0
PROJECT NUMBER: 24212
LIGHTING PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
3/16" = 1'-0"
1 ELECTRICAL LIGHTING PLAN
N.T.S.
2 SWITCHBANK DETAIL
N.T.S.
3 EXTERIOR EMERGENCY LIGHTING DETAIL
KEYNOTES
1 REFER TO SWITCH BANK DETAIL 2/E5.0 FOR
SWITCHING OF SALES FLOOR LIGHTING. VERIFY
FINAL LOCATION WITH OWNER.
2 REFER TO ARCHITECTURAL SHEETS FOR
ACCESS PANEL FOR SIGNAGE IN THIS SOFFIT
AREA.
3 PROVIDE WITH EMERGENCY BATTERY BACK-UP
BALLAST - BODINE B50.
4 PROVIDE HIGHLITES EMERGENCY BATTERY
PACK - PCF 250 - BLACK IN COLOR (SEE DETAIL
3/E5.0)
5 PROVIDE TEMPERATURE SEAL / FIRE STOP FOR
ALL CONDUITS AND HOME RUNS IN THESE
AREAS PER NEC 300.7.
6 RESTROOM OCCUPANCY SENSOR: SET SENSOR
FOR 20 MINUTE TIME DELAY
7 ROUTE CIRCUIT VIA PHOTOCELL CONTROLLED
CONTACTOR. REFERENCE DETAIL 2/E6.0.
A. COORDINATE ALL WORK WITH OTHER TRADES AND
THE PROJECT MANAGER.
B. VERIFY LOCATION AND MOUNTING HEIGHT OF ALL
LIGHT FIXTURES WITH THE ARCHITECT / OWNER
PRIOR TO ROUGH-IN.
C. THE EXIT, EMERGENCY AND NIGHT LIGHT FIXTURES
SHALL NOT BE SWITCHED.
D. RGS CONDUIT SHALL BE USED IN ALL EXTERIOR
LOCATIONS.
E. MINIMUM CONDUIT SIZE SHALL BE 1/2".
F. MINIMUM WIRE SIZE SHALL BE #12 THHN/THWN CU.
G. ALL EXTERIOR LIGHT FIXTURES SHALL BE
CONTROLLED VIA PHOTOCELL. REFERENCE DETAIL
2/E6.0.
H. REFER TO THE PANEL SCHEDULES ON SHEETS E7.0
AND E7.1 FOR LOAD DESIGNATIONS. THERE SHALL
BE NO SHARED NEUTRALS.
I. CONDUIT(S) SHALL NOT BE ROUTED EXPOSED ON
ANY EXTERIOR OR INTERIOR WALL.
J. ALL EXTERIOR DEVICES SHALL BE WEATHERPROOF
RATED.
K. REFER TO SHEET E0.0 FOR THE LIGHT FIXTURE
SCHEDULE.
L. PROVIDE STAINLESS STEEL SWITCH COVERS FOR
ALL CUSTOMER ACCESSIBLE AREAS. (RESTROOMS,
HALLWAY, COOLER, SALES AREA).
M. ALL EMERGENCY EQUIPMENT SHALL BE LISTED TO
UL924 AND BE INSTALLED PER NEC 700.
N. OCCUPANCY SENSORS SHALL BE SET TO MAXIMUM
DELAY PER MANUFACTURER INSTRUCTIONS.
LIGHTING GENERAL NOTES
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E5.1
PROJECT NUMBER: 24212
LIGHTING
COMPLIANCE
REPORT
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
20/1
L
N
A-12
NC
'EPO' -EMERGENCY
POWER OFF SWITCH
A-4
A-8
A-10
A-33
A-5
A-20
A-22
SPARE
LTG MONUMENT SIGN
LTG MONUMENT SIGN
LTG EXTERIOR
LTG FRONT LOGO SIGN
LTG CANOPY EYEBROW
LTG PARKING LOT
LTG PARKING LOT
SPARE
NC
PHOTOCELL "TORK"
2100 SERIES, MOUNT
ON ROOF, AIM NORTH
A-9
A-11
A-13
A-15
TO CANOPY
LIGHTING
TO CANOPY
LIGHTING
SPARE SPARE
A-1
A-3
SPARE
CANOPY SIGN
CANOPY SIGN
SPARE
REFERENCE VENDOR EQUIPMENT DRAWINGS
FOR EXACT CONTROL WIRING DIAGRAMS AND
CONTRACTOR WIRED EQUIPMENT
30-AMP, 4-POLE, 250V,
ELECTRICALLY HELD LIGHTING
CONTACTOR FACTORY
INSTALLED IN SWITCHGEAR DP,
TYP OF 4. REFERENCE VENDOR
DRAWINGS.
#3/0 CU. EQUIP. BOND
N
G
#3/0 CU. MAIN
BONDING JUMPER
#3/0 CU. TO
BUILDING STEEL
#6 BARE CU. TO 3/8"x10'
GROUND ROD TRIAD
#4 CU. UFER GROUND
#3 CU. BOND TO
METALLIC COLD WATER PIPING
SYSTEMS / FIRE SPRINKLER /
COMPRESSED AIR PIPING
#3 CU. BOND TO METALLIC
GAS PIPING SYSTEMS
PORTABLE
GENERATOR
(NOT PROVIDED)
MCT.
C-STORE
SERVICE ENTRANCE
DISCONNECT
1,000A, 120/208V-3PH-4W,
65K AIC RMS, NEMA 3R
REFER TO
GROUND
DETAIL
3/E6.0.
MAIN
BONDING
JUMPER
#3/0 AWG CU
1000A
F2X
1000A
MAIN BREAKER AND
GENERATOR
BREAKER
FURNISHED WITH
KIRK-KEY
INTERLOCK,
REF VENDOR
EQUIPMENT
DRAWINGS
PORTABLE GENERATOR
CONNECTION
TO UTILITY TRANSFORMER.
TRANSFORMER SHALL BE
PROVIDED AND SIZED BY
UTILITY COMPANY.
PROVIDE 3 -3"C,
4-400KCMIL EACH
PER 2023 NEC 110.24 SERVICE
EQUIPMENT LEGIBLY MARKED IN THE
FIELD WITH MAXIMUM AVAILABLE FAULT
CURRENT AND INCLUDE THE DATE THE
FAULT CURRENT CALCULATION WAS
PERFORMED ON EQUIPMENT.
NOTE:
CONTRACTOR SHALL FURNISH
INSTALLATION MANUAL FOR EACH
EQUIPMENT SUCH AS PANELBOARD,
CONTROL EQUIPMENT, ETC.SERIES RATING GENERAL NOTES
1.THE MOTOR CONTRIBUTION TO THE FAULT CURRENT MEETS
THE 1% CRITERIA STATED IN NEC 240.86(C)
2.NO DESIGN CHANGES MAY BE MADE TO THE SYSTEM WITHOUT
THE PRIOR APPROVAL OF THE DESIGN ELECTRICAL ENGINEER
AND THE ELECTRICAL INSPECTOR.
ONE-LINE KEYNOTES
1.THIS SERVICE IS A SERIES RATED SYSTEM: 2-TIER 65/10. ALL
SERVICE ENTRANCE EQUIPMENT SYSTEM COMPONENTS SHALL
BE RATED 65K, WITH SERIES RATED DOWNSTREAM.
2.CONTRACTOR SHALL LABEL SERVICE ENTRANCE EQUIPMENT
"CAUTION -SERIES RATED SYSTEM (65). 65,000 AMPS
AVAILABLE IDENTIFIED REPLACEMENT COMPONENT REQUIRED."
IN ACCORDANCE WITH NEC 110.22.
3.CONTRACTOR SHALL LABEL PANEL(S) "CAUTION -SERIES RATED
SYSTEM ("X"). "X" AMPS AVAILABLE IDENTIFIED REPLACEMENT
COMPONENT REQUIRED IN ACCORDANCE WITH NEC 110.22".
(REFER TO SHORT CIRCUIT CALCULATIONS FOR ACTUAL AMPS
TO BE LABELED).
4.CIRCUIT BREAKERS SHALL BE A BOLT-ON TYPE U.L. LISTED
SERIES RATED COMBINATION WITH THE BREAKERS AT
DISTRIBUTION PANEL "DP".
5.REFER TO E4.0 ROOF POWER PLAN FOR WIRE AND CONDUIT SIZE
FOR ROOF TOP UNITS.
6.MAXIMUM CIRCUIT BREAKER HEIGHT EQUAL TO 6'-7" AFF OR
AFG.
1
3 -3"C, 4-400KCMIL,
1#2/0 GR EACH
METER / CT CABINET
PER UTILITY
REQUIREMENTS
3 -3"C, 4-400KCMIL,
EACH
#12CU.
(8-FT MIN.)
TIMECLOCK AND LTG.
CONTROL RELAYS
F9X
NOTE: FEEDERS FROM PANEL DP TO
PANEL BOARDS SHOWN DASHED ARE
FACTORY INSTALLED. REFERENCE
SWITCHGEAR VENDOR DRAWINGS.
6KVA POWER
CONDITIONER
SECTION #2 SECTION #3 SECTION #4
47"
F4
F8
F5 F7
PANEL
'G'
PANEL
'B'
PANEL PANEL
'E'
208/120V
3PH, 4W
208/120V
3PH, 4W
208/120V
3PH, 4W
208/120V
3PH, 4W
24"
SECTION #1
47"
F3-F8
FUEL CONTROLS
F3
PANEL
'A'
208/120V
3PH, 4W
F6
PANEL
'D'
208/120V
3PH, 4W
'C'
47"
F10X
'DP' DISTRIBUTION PANELTC
C
2
3 4 3 4 3 4
3 4
6
PNL 'C'
PANEL 'DP'
225/3 225/3
225/3
125/3
30/3
225/3225/3
90/3 5
5
PNL 'A'
PNL 'B'
PNL 'G'
RTU1
PNL 'E'
PNL 'D'
OAU1
SPD150/3
RS
E
-1
RS
E
-1
SP
D
------
FUEL
CONTROLS
F10
PANEL
'U'
240/120V
LIGHTING
CONTACTOR
CONTROLS
F1X
U1
X
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E6.0
PROJECT NUMBER: 24212
CALCULATIONS
AND
SCHEMATICS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
N.T.S.
2 LIGHTING CONTROL DIAGRAM
N.T.S.
3 GROUNDING DETAIL - 1000 AMP SERVICE
N.T.S.
1 RISER DIAGRAM
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E7.0
PROJECT NUMBER: 24212
PANEL
SCHEDULES
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
1. TERMINATE GROUND ON ISOLATED GROUND BUS.
2. INSTALL LOCKING DEVICE ON BREAKER PER NEC
(LOCK-OFF FOR MAINTENANCE).
3. INSTALL LOCKING DEVICE ON BREAKER PER NEC
(LOCK-ON FOR CRITICAL LOAD).
4. GFI BREAKER FOR PERSONNEL PROTECTION (5MA).
5. REFER TO ONE-LINE DIAGRAM FOR CONDUCTOR
SIZES.
6. PROVIDE LOCK-OFF DEVICE TO SIMULTANEOUSLY
DISCONNECT ALL UNGROUNDED CONDUCTORS PER
NEC.
7. FIRE ALARM CIRCUIT. PROVIDE RED MARKING AND
LABEL "FIRE ALARM CIRCUIT CONTROL" ON BREAKER.
8. OPTIONAL EQUIPMENT: REVISE TO FILLER SPACE IF
NOT USED ON SITE.
9. FACTORY INSTALLED WIRING IN UNITIZED
SWITCHGEAR.
PANELBOARD
CIRCUIT NOTES
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 11.55 125.00% 14.44 Spare Capacity Percent:57
9 Computer Outlets 0.00 0.00% 0.00 Spare Capacity:97 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 0.00 0.00% 0.00
4 Motors 0.00 0.00% 0.00 Total Est. Demand:128 A
3 Special Loads 24.30 100.00% 24.30 Total Conn.:117 A
2 Receptacles 1.56 100.00% 1.56 Total Est. Demand:46.17
1 Lighting - Continuous 4.69 125.00% 5.87 Total Conn. Load:42.10
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:117 A 123 A 112 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:13.98 14.69 13.44 kVA
41 -- FILLER SPACE -- -- 1 -- 8.00 42
39 2 SMOKE DAMPER POWER 3,7 20 A 1 0.18 8.00 40
37 2 IRRIGATION CONTROLS 20 A 1 0.30 8.00
3 90 A WATER HEATER 3
38
35 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 36
33 10 CIRCLE K FRONT LOGO SIGN 20 A 1 0.60 -- 1 -- -- FILLER SPACE -- 34
31 -- FILLER SPACE -- -- 1 -- 0.18 1 20 A DOOR CHIME 2 32
29 -- SPARE -- 20 A 1 0.00 1.80 1 20 A LTG. SALES FLOOR 1 30
27 10; 1 LTG. RESTROOMS / STOCKROOM 20 A 1 0.69 0.08 1 20 A LTG/HTR COLD VAULT DOORS 1 28
25 2 LED FRAME - COFFEE 20 A 1 0.15 0.00 1 20 A -- SPARE -- 26
23 2 LED FRAME - FOOD 20 A 1 0.10 0.60 1 20 A LTG/HTR WALK-IN CLR DOORS 1 24
21 10; 1 LTG. COOLER / COLD VAULT 20 A 1 0.15 0.62 1 20 A LTG. EXTERIOR PARKING - POLES 10 22
19 2 LTG. COOLER SIGNS 20 A 1 0.65 0.62 1 20 A LTG. EXTERIOR PARKING - POLES 10 20
17 1 LIGHTING CASHIER / PREP 20 A 1 0.53 0.00 1 20 A -- SPARE -- 18
15 0.60 0.48 1 20 A LTG. COFFEE & DRINKS 1 16
13 10 FUEL CANOPY LIGHTING 20 A 2
0.60 0.35 1 20 A LTG. BACK ROOM / OFFICE 10; 1 14
11 0.60 0.30 1 20 A MISC. - LTG CONTACTOR 3 12
9 10 FUEL CANOPY LIGHTING 20 A 2
0.60 0.50 1 20 A LTG. EXTERIOR BUILDING 10; 1 10
7 -- FILLER SPACE -- -- 1 -- 0.96 1 20 A LTG. - MONUMENT SIGN - LOGO 10 8
5 10 FUEL CANOPY EYEBROW 20 A 1 0.54 0.96 1 20 A LTG. - MONUMENT SIGN - PRICE 10 6
3 10 FUEL CANOPY SIGN 20 A 1 1.20 0.96 1 20 A LTG. - MONUMENT SIGN - LOGO 10 4
1 10 FUEL CANOPY SIGN 20 A 1 1.20 0.96 1 20 A LTG. - MONUMENT SIGN - PRICE 10 2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Series Neutral Busbar:100%
A System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:225 A Main Rating Upstream:225 A Location:DIST. DP
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.00 0.00% 0.00 Spare Capacity Percent:43
9 Computer Outlets 0.00 0.00% 0.00 Spare Capacity:127 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 22.54 65.00% 14.65
4 Motors 0.21 100.00% 0.21 Total Est. Demand:98 A
3 Special Loads 9.90 100.00% 9.90 Total Conn.:120 A
2 Receptacles 10.21 98.97% 10.11 Total Est. Demand:35.19
1 Lighting - Continuous 0.26 125.00% 0.33 Total Conn. Load:43.12
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:134 A 104 A 127 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:15.75 12.51 14.85 kVA
41 2.17 0.26 1 20 A H002 / H005 HOT DOG ROLLER 5 42
39 2.17 0.32 1 20 A H101 / H002 SNEEZE GUARD 5 40
37
5 H211 UNOX SPEEDPRO OVEN
(OPTIONAL)8 20 A 3
2.17 -- 1 -- -- FILLER SPACE -- 38
35 2 B503 REC. CO2 DETECTION 3 20 A 1 0.18 1.54 1 20 A H001 HOT DOG ROLLER 5 36
33 5 H303 U.C. MICROWAVE 20 A 1 1.50 -- 1 -- -- FILLER SPACE -- 34
31 5 H303 U.C. MICROWAVE 20 A 1 1.50 1.54 1 20 A H001 / H005 HOT DOG ROLLER 5 32
29 2.17 -- 1 -- -- FILLER SPACE -- 30
27 2.17 -- 1 -- -- FILLER SPACE -- 28
25
5 H211 UNOX SPEEDPRO OVEN 20 A 3
2.17 -- 1 -- -- FILLER SPACE -- 26
23 2 C101 2 EA.-2 VALVE CREAMER 20 A 1 0.66 1.20 1 20 A B006 BEVERAGE COOLER 5 24
21 4 R306 SCA REFRG CASE FANS/HTRS 20 A 1 0.21 0.78 1 20 A C201 COUNTERTOP ICE MAKER 2 22
19 3 DUCT SMOKE DETECTORS 3,7 20 A 1 0.30 0.14 1 20 A R306 SCA REFRG CASE LIGHTS 1 20
17 5 R207 27" U.C. FRIDGE 20 A 1 0.48 0.18 1 20 A 4,8 WATER COOLERS 2 18
15 2 REC. BIB EQ B601, B602, B603 20 A 1 1.20 0.12 1 20 A RI FRZR & COLD VLT OVALS LED 1 16
13 2.40 2.40 14
11 3 B301 4-HEAD FROSTED VIPER 30 A 2
2.40 2.40 2 30 A B301 4-HEAD FROSTED VIPER 3
12
9 2 B003 ICE TEA CURTIS 20 A 1 1.65 1.65 1 20 A B003 ICE TEA CURTIS 2 10
7 2 RECS. GENERAL BACK RM 4 20 A 1 0.72 1.20 1 20 A B006 BEVERAGE COOLER 5 8
5 2 B001 12-HEAD SODA FOUNTAIN 20 A 1 0.62 0.60 1 20 A B101 ICE MAKER 2 6
3 2 B001 12-HEAD SODA FOUNTAIN 20 A 1 0.62 0.13 1 20 A B102 ICE MAKER 2 4
1 2 B001 12-HEAD SODA FOUNTAIN 20 A 1 0.62 0.60 1 20 A B101 ICE MAKER 2 2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Series Neutral Busbar:100%
B System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:225 A Main Rating Upstream:225 A Location:DIST. DP
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.00 0.00% 0.00 Spare Capacity Percent:39
9 Computer Outlets 0.00 0.00% 0.00 Spare Capacity:138 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 10.99 90.00% 9.89
4 Motors 2.80 100.00% 2.80 Total Est. Demand:87 A
3 Special Loads 0.00 0.00% 0.00 Total Conn.:112 A
2 Receptacles 26.15 69.12% 18.08 Total Est. Demand:31.45
1 Lighting - Continuous 0.00 0.00% 0.00 Total Conn. Load:40.49
0 Lighting - Non-Continuous 0.54 125.00% 0.68
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:117 A 101 A 123 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:13.83 12.14 14.52 kVA
41 2.28 0.36 1 20 A REC. POS 2 42
39 2.28 0.72 1 20 A REC. POS 2 40
37
5 H201 COMBI OVEN 25 A 3
2.28 0.36 1 20 A REC ISLAND POS 2 38
35 2 REC. AT PIZZA PREP. STATION 4 20 A 1 0.18 0.72 1 20 A RECS. CONVENIENCE OUTLET 2 36
33 2 H101,H102,H104 COLD WELL REC 20 A 1 0.54 0.36 1 20 A RECS. CONVENIENCE OUTLET 2 34
31 0 LTG. LED CONTROL / REC. 20 A 1 0.54 0.18 1 20 A REC. CONVENIENCE OUTLET 2 32
29 4 WATER / AIR FILL STATION 20 A 1 1.80 1.00 1 20 A RECIRC. PUMP / AQUA STAT 4 30
27 2 RECS. PREP CONVENIENCE 20 A 1 0.36 -- 1 -- -- FILLER SPACE -- 28
25 2 R401 6' NOVELTY CASE 20 A 1 1.80 1.35 26
23 5 H206 HATCO FSD-2 20 A 1 1.44 1.35 2 20 A 8 H209 FLEXESERVE 1000 (OPTIONAL) 5
24
21 2 WINE RACK RECEPTS 20 A 1 0.72 1.67 22
19 2 R201 WINE REFRIG 20 A 1 0.65 1.67 2 30 A R203 4DR REACH-IN FREEZER 2
20
17 2 HOT BOX - BACKFLOW PREVENTOR 8 20 A 1 1.20 -- 1 -- -- FILLER SPACE -- 18
15 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 16
13 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 14
11 2 C004 NITRO BREWER 20 A 1 0.72 0.72 1 20 A C005 NITRO BREWER 2 12
9 2 FROSTER, POLAR POP BACKGRND 20 A 1 0.36 1.80 1 20 A C002 5-HEAD CAPPUCCINO 2 10
7 -- SPARE -- 20 A 1 0.00 1.66 8
5 2 ROOF RECEPTACLES 20 A 1 1.08 1.66 2 20 A C001 COFFEE BREWER 2
6
3 1.66 1.66 4
1 2 C001 COFFEE BREWER 20 A 2
1.66 1.66 2 20 A C001 COFFEE BREWER 2
2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Series Neutral Busbar:100%
C System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:225 A Main Rating Upstream:225 A Location:DIST. DP
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.36 125.00% 0.45 Spare Capacity Percent:31
9 Computer Outlets 1.20 100.00% 1.20 Spare Capacity:155 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.50 100.00% 0.50
5 Kitchen (Commercial) 3.04 90.00% 2.74
4 Motors 7.75 100.00% 7.75 Total Est. Demand:70 A
3 Special Loads 1.84 100.00% 1.84 Total Conn.:72 A
2 Receptacles 11.27 94.36% 10.64 Total Est. Demand:25.12
1 Lighting - Continuous 0.00 0.00% 0.00 Total Conn. Load:25.97
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:67 A 72 A 78 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:8.07 8.57 9.32 kVA
41 3.84 1.20 1 20 A M104 LOTTERY VENDING MACHINE 2 42
39 2; 9 PANEL U VIA 6KVA POWER
CONDITIONER 9 40 A 2
2.22 1.35 40
37 3 WOMENS HAND DRYER 2 20 A 1 0.92 1.35 2 20 A 8 H209 FLEXESERVE 1000 (OPTIONAL) 5
38
35 3 MENS HAND DRYER 2 20 A 1 0.92 -- 1 -- -- FILLER SPACE -- 36
33 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 34
31 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 32
29 0.05 0.77 1 20 A 2,8 FF-3 AIR CURTAIN 4 30
27 5 H202 VENTLESS HOOD 20 A 2
0.05 0.77 1 20 A 2,8 FF-2 AIR CURTAIN 4 28
25 2 REC. GONDOLA FLOOR 20 A 1 0.36 1.53 1 20 A 2,8 FF-1 AIR CURTAIN 4 26
23 6; 2 WALK-IN FRZR DOOR HEAT 20 A 1 0.68 -- 1 -- -- FILLER SPACE -- 24
21 4 WALK IN COOLER EVAPS 20 A 1 1.44 -- 1 -- -- FILLER SPACE -- 22
19 2 M001 GONDLOA FLOOR RECS. 20 A 1 0.36 -- 1 -- -- FILLER SPACE -- 20
17 2 M001 GONDOLA FLOOR RECS. 20 A 1 0.72 -- 1 -- -- FILLER SPACE -- 18
15 2 GONDOLA FLOOR RECS. 20 A 1 0.36 0.18 1 20 A 4,8 M105 ICE MERCHANDISER 2 16
13 -- SPARE -- 20 A 1 0.00 0.18 1 20 A 4,8 M102 WATER DISPENSER 2 14
11 2 CEILING RECEPTACLES 20 A 1 0.18 0.36 1 20 A GONDOLA FLOOR RECS. 2 12
9 10 H401 EURO. BAKERY CASE 20 A 1 0.36 0.18 1 20 A FRONT WALL GONDOLA 2 10
7 2 REC. RESTROOMS 20 A 1 0.18 0.48 1 20 A COLD VAULT EVAP 4 8
5 2 REC. SHOW WINDOW 20 A 1 0.36 0.24 1 20 A R202 27" U.C. FREEZER 5 6
3 2 R206 UNDER COUNTER REFRIG 4 20 A 1 0.28 1.38 4
1 2 CIGARETTE BACK BAR RECS. 20 A 1 1.33 1.38 2 20 A BOOSTER PUMP 4
2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, Installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Series Neutral Busbar:100%
D System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:225 A Main Rating Upstream:225 A Location:DIST. DP
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.00 0.00% 0.00 Spare Capacity Percent:66
9 Computer Outlets 0.00 0.00% 0.00 Spare Capacity:76 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 0.00 0.00% 0.00
4 Motors 52.32 100.00% 52.32 Total Est. Demand:149 A
3 Special Loads 0.00 0.00% 0.00 Total Conn.:149 A
2 Receptacles 1.20 100.00% 1.20 Total Est. Demand:53.52
1 Lighting - Continuous 0.00 0.00% 0.00 Total Conn. Load:53.52
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:149 A 154 A 145 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:17.78 18.38 17.36 kVA
41 2 REC. BITCOIN ATM 20 A 1 0.24 0.36 1 20 A SELF CHECK DRN RECEPT 2 42
39 2 REC. ATM 20 A 1 0.24 0.36 1 20 A SELF CHECK DRN RECEPT 2 40
37 -- SPARE -- 20 A 1 0.00 -- 1 -- -- FILLER SPACE -- 38
35 -- SPARE -- 20 A 1 0.00 -- 1 -- -- FILLER SPACE -- 36
33 1.02 -- 1 -- -- FILLER SPACE -- 34
31 4 WALK-IN FREEZER EVAP 15 A 2
1.02 -- 1 -- -- FILLER SPACE -- 32
29 1.80 -- 1 -- -- FILLER SPACE -- 30
27 1.80 -- 1 -- -- FILLER SPACE -- 28
25
4 COLD VAULT CONDENSER 20 A 3
1.80 -- 1 -- -- FILLER SPACE -- 26
23 1.92 1.80 24
21 1.92 1.80 22
19
4 ZERO ZONE FRZR CONDENSER 20 A 3
1.92 1.80
3 20 A WALK-IN FREEZER CONDENSER 4
20
17 2.51 2.55 18
15 2.51 2.55 16
13
4 R306 REF. ISLAND MERCHDSR 30 A 3
2.51 2.55
3 50 A WALK-IN CLR 17DR CONDENSER 4
14
11 2.40 1.89 12
9 2.40 1.89 10
7
4 B202 ICE MACHINE CONDENSER 25 A 3
2.40 1.89
3 25 A B201 ICE MACHINE CONDENSER 4
8
5 -- FILLER SPACE -- -- 1 -- 1.89 6
3 -- FILLER SPACE -- -- 1 -- 1.89 4
1 -- FILLER SPACE -- -- 1 -- 1.89
3 25 A B201 ICE MACHINE CONDENSER 4
2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by GC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Fully Neutral Busbar:100%
E System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:225 A Main Rating Upstream:225 A Location:DIST. DP
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.00 0.00% 0.00 Spare Capacity Percent:39
9 Computer Outlets 0.00 0.00% 0.00 Spare Capacity:77 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 0.00 0.00% 0.00
4 Motors 13.75 100.00% 13.75 Total Est. Demand:48 A
3 Special Loads 2.37 100.00% 2.37 Total Conn.:48 A
2 Receptacles 1.26 100.00% 1.26 Total Est. Demand:17.38
1 Lighting - Continuous 0.00 0.00% 0.00 Total Conn. Load:17.38
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:55 A 45 A 47 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:6.53 5.46 5.64 kVA
41 2 DISTRIBUTION BOX (E3) 20 A 1 0.36 0.01 42
39 2 INTERCOM CONTROLLER (E2) 20 A 1 0.36 0.01 40
37 3 VEEDER ROOT (E1) 20 A 1 0.24 0.01
3 30 A 9 SPD 3
38
35 2 SPARE ELECTRONICS 20 A 1 0.36 -- 1 -- -- SWITCHED NEUTRAL -- 36
33 2 E-STOP CONTROL PWR 9 15 A 1 0.18 0.26 1 20 A MISC. - DIESEL DISPENSER #2 3 34
31 -- SWITCHED NEUTRAL -- -- 1 -- -- 1 -- -- SWITCHED NEUTRAL -- 32
29 -- FILLER SPACE -- -- 1 -- 0.26 1 20 A MISC. - DIESEL DISPENSER #1 3 30
27 -- FILLER SPACE -- -- 1 -- -- 1 -- -- SWITCHED NEUTRAL -- 28
25 -- FILLER SPACE -- -- 1 -- 0.26 1 20 A MISC. - DISPENSER #7 3 26
23 -- FILLER SPACE -- -- 1 -- -- 1 -- -- SWITCHED NEUTRAL -- 24
21 -- FILLER SPACE -- -- 1 -- 0.26 1 20 A MISC. - DISPENSER #6 3 22
19 1.38 -- 1 -- -- SWITCHED NEUTRAL -- 20
17 4 SUBMRG. 2HP PUMP DIESEL 20 A 2
1.38 0.26 1 20 A MISC. - DISPENSER #5 3 18
15 1.38 -- 1 -- -- SWITCHED NEUTRAL -- 16
13 4 SUBMRG. 2HP PUMP SUL 20 A 2
1.38 0.26 1 20 A MISC. - DISPENSER #4 3 14
11 1.38 -- 1 -- -- SWITCHED NEUTRAL -- 12
9 4 SUBMRG. 2HP PUMP CK CHOICE 20 A 2
1.38 0.26 1 20 A MISC. - DISPENSER #3 3 10
7 1.38 -- 1 -- -- SWITCHED NEUTRAL -- 8
5 4 SUBMRG. 2HP PUMP REGULAR 20 A 2
1.38 0.26 1 20 A MISC. - DISPENSER #2 3 6
3 1.38 -- 1 -- -- SWITCHED NEUTRAL -- 4
1 4 SUBMRG. 2HP PUMP REGULAR 20 A 2
1.38 0.26 1 20 A MISC. - DISPENSER #1 3 2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B C Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Fully Neutral Busbar:100%
G System:3Ø, 4W A.I.C. Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Mains Type:M.L.O.Busbar Material:CUPANELBOARD
Bus Rating:125 A Main Rating Upstream:225 A Location:DIST. DP
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST
FAULT CURRENT CALCULATIONS
THE FOLLOWING CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD WHERE:
Isc = Isc x M M= 1/(1+f)f =1.73 x L x I XFMR:IP(sca)= IP(sca)x Vp x%Z IS(sca)=Vp x M x IS(sca)
C x E x n 100,000 x KVA Vs(ALL CALCULATIONS UTILIZE COPPER CONDUCTORS)
Source
Fault Panel /(Fault Source I Conduit X'FMR X'FMR
Point Transformer Point)(amps)Type Wire/Bus Size 'C' value E (volts) L (length)KVA Z f M Isc
F1 SERVICE DISC 65,000
F2 DIST. DP F1 M 3 Set(s) of 400 KCM 20,566 208 5 0.037 0.96 53,308
F3 PANEL 'A' F2 1 Set(s) of 4/0 15,082 208 3
F4 PANEL 'B' F2 1 Set(s) of 4/0 208 5
F5 PANEL 'C' F2 1 Set(s) of 4/0 208
F6 PANEL 'D' F2 1 Set(s) of 4/0 208
F7
PANEL 'G' F2 1 Set(s) of 1 7,293 208F8
LTG. CONTACT F3 48,983 1 Set(s) of 12 617 208 8 5.289 0.16 7,789
PANEL 'U' F6 Set(s) of 8 1,557 208 3 0.786 0.56 27,427
F9
48,983
1F10
PANEL 'E' F2 208 0.921Set(s) of 4/0
M
M
M
M
M
M
M
M
55,298
55,298
0.088 0.92
0.147 0.87
0.92
0.92
46,470
0.85 45,077
48,983
15,082
15,082
15,082
15,082
3
3
3
3 0.183
U1 UTILITY XFRM 65,000 65,000
U1 M 3 Set(s) of 208 20 0.176 0.85400 KCM 20,566
53,308
0.088
0.088
0.088
48,983
48,983
48,983
53,308
53,308
53,308
53,308
53,308
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
E7.1
PROJECT NUMBER: 24212
PANEL
SCHEDULES
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
LHO
SAG
SAG
JCA
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 11.91 125.00% 14.89 Spare Capacity Percent:76
9 Computer Outlets 1.20 100.00% 1.20 Spare Capacity:243 A
7 Cooling 0.00 0.00% 0.00
6 Heating 0.50 100.00% 0.50
5 Kitchen (Commercial) 36.58 65.00% 23.78
4 Motors 156.10 100.00% 156.10 Total Est. Demand Current:757 A
3 Special Loads 38.44 100.00% 38.44 Total Conn. Current:838 A
2 Receptacles 51.66 59.68% 30.83 Total Est. Demand:272.60
1 Lighting - Continuous 4.95 125.00% 6.19 Total Conn. Load:301.88
0 Lighting - Non-Continuous 0.54 125.00% 0.68
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Circuit Numbering By Pole Position
Demand Loads May Vary From Connected Loads Because of Demand Factors 857 A 818 A 851 A Amps
102.38 98.18 101.56 kVA
10 3 SPD 9 30 A 3 0.01 0.01 0.01
9 -- FILLER SPACE -- 3 -- -- --
8 4 RTU 1 150 A 3 15.97 15.97 15.97
7 4 OAU 1 90 A 3 10.45 10.45 10.45
6 2; 4; 3 PANEL G 9 125 A 3 6.53 5.46 5.64
5 2; 4 PANEL E 9 225 A 3 17.78 18.38 17.36
4 6; 2; 4; 10; 5; 3; 9 PANEL D 9 225 A 3 8.07 8.57 9.32
3 2; 4; 5; 0 PANEL C 9 225 A 3 13.83 12.14 14.52
2 2; 4; 5; 1; 3 PANEL B 9 225 A 3 15.75 12.51 14.85
1 2; 10; 1; 3 PANEL A 9 225 A 3 13.98 14.69 13.44
CCT
No.Load Codes Load Description Notes
Brkr
Size Poles
A B C
Remarks
Furnished by Owner, installed by EC Feed Thru Lugs:No Terminations:75°C CU Sections:4
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-On IG Ground Busbar:No
Mounting:Cabinet Fully/Series:Fully Neutral Busbar:100%
DP System:3Ø, 4W Aic Rating:65,000 A Ground Busbar:Yes
Voltage:208Y/120 V Main Type:M.L.O.Busbar Material:CUSWITCHBOARD
Bus Rating:1000 A Main Rating Upstream:1000 A Location:DIST. DP
1. TERMINATE GROUND ON ISOLATED GROUND BUS.
2. INSTALL LOCKING DEVICE ON BREAKER PER NEC
(LOCK-OFF FOR MAINTENANCE).
3. INSTALL LOCKING DEVICE ON BREAKER PER NEC
(LOCK-ON FOR CRITICAL LOAD).
4. GFI BREAKER FOR PERSONNEL PROTECTION (5MA).
5. REFER TO ONE-LINE DIAGRAM FOR CONDUCTOR
SIZES.
6. PROVIDE LOCK-OFF DEVICE TO SIMULTANEOUSLY
DISCONNECT ALL UNGROUNDED CONDUCTORS PER
NEC.
7. FIRE ALARM CIRCUIT. PROVIDE RED MARKING AND
LABEL "FIRE ALARM CIRCUIT CONTROL" ON BREAKER.
8. OPTIONAL EQUIPMENT: REVISE TO FILLER SPACE IF
NOT USED ON SITE.
9. FACTORY INSTALLED WIRING IN UNITIZED
SWITCHGEAR.
PANELBOARD
CIRCUIT NOTESGROUND WIRE SIZING CHART
BRKR
AMPS
PHASE
WIRE SIZE
GROUND
12 10 8 6 4
15-20 12 10 8 6 4
PHASE
GROUND
10 8 6 4
25-30 10 8 6 4
PHASE
GROUND
8 6 4 3 2
35-50 10 8 4 4 4
PHASE
GROUND
6 4 3 2 1
60 10 6 6 4 4
PHASE
GROUND
6 4 3 2 1
70 8 4 4 3 2
PHASE
GROUND
4 3 2 1 1/0
80-90 8 6 4 4 3
PHASE
GROUND
3 2 1 1/0 2/0
100 8 6 4 4 3
PER NEC 250.122(B)
3
3
20A WIRE SIZING SCHEDULE
385 FT.
770 FT.
255 FT.
ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE
INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE.
THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
WIRE FOR 20 AMP CIRCUITS (120 VOLT). LENGTHS (IN
FEET) ARE INTENDED TO BE MAXIMUM.
6-10 AMPS
1-5 AMPS
120 VOLT
11-15 AMPS
325 FT.
110 FT.
160 FT.
#12
200 FT.
70 FT.
100 FT.
490 FT.
165 FT.
245 FT.
#10 #8 #6
12 Modular Furniture Outlets 0.00 0.00% 0.00
11 Miscellaneous - Continuous 0.00 0.00% 0.00
10 Exterior Lighting 0.00 0.00% 0.00
9 Computer Outlets 1.20 100.00% 1.20
7 Cooling 0.00 0.00% 0.00
6 Heating 0.00 0.00% 0.00
5 Kitchen (Commercial) 0.00 0.00% 0.00
4 Motors 0.00 0.00% 0.00 Total Est. Demand:25 A
3 Special Loads 0.00 0.00% 0.00 Total Conn.:25 A
2 Receptacles 4.86 100.00% 4.86 Total Est. Demand:6.06
1 Lighting - Continuous 0.00 0.00% 0.00 Total Conn. Load:6.06
0 Lighting - Non-Continuous 0.00 0.00% 0.00
Load Codes Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Demand Loads May Vary From Connected
Loads Because of Demand Factors
Total Amps:19 A 32 A Amps Circuit Numbering By Pole Position Circuit
Total Connect Load:2.22 3.84 kVA
15 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 16
13 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 14
11 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 12
9 -- FILLER SPACE -- -- 1 -- -- 1 -- -- FILLER SPACE -- 10
7 2 REC. DATA COMMUNICATIONS 20 A 1 0.36 0.96 1 20 A T101 SAFE REC 2 8
5 2 REC. SECONDARY COMMUNICATION 20 A 1 0.36 0.36 1 20 A RECS. LOTTO EQ 44 2 6
3 2 SELF CHECK POS SYSTEM 20 A 1 1.32 1.20 1 20 A REC. BACK OFFICE COMPUTER 9 4
1 2 SELF CHECK POS SYSTEM 20 A 1 1.32 0.18 1 20 A REC. CCTV SERVICE 2 2
CCT
No.
Load
Code Load Description Notes
Brkr
Size Poles A B Poles
Brkr
Size Notes Load Description
Load
Code
CCT
No.
Furnished by Owner, installed by EC. Feed Thru Lugs:No Terminations:75°C CU Sections:1
Nema Rating:1 Feed Type:Bottom Skirt Type:None
Status: New Trim:Door-In-Door Branch Breaker Type:Bolt-on IG Ground Busbar:No
Mounting:Cabinet Fully / Series:Series Neutral Busbar:100%
U System:1Ø, 3W A.I.C. Rating:35,000 A Ground Busbar:Yes
Voltage:120/240 V Mains Type:M.C.B.Busbar Material:CUPANELBOARD
Bus Rating:100 A Main Rating Upstream:40A Location:DIST. DP
1. CIRCUIT BREAKERS IN PANELBOARDS SHALL BE U.L.
LISTED SERIES RATED WITH SPECIFIED 65K AIC
UPSTREAM CIRCUIT BREAKER AND DOWNSTREAM
10K AMP RATED BRANCH CIRCUIT BREAKERS.
2. PROVIDE A PERMANENT LABEL READING "CAUTION -
SERIES RATED SYSTEM 65K, "X" AMPS AVAILABLE."
IDENTIFIED (LABELED) REPLACEMENT COMPONENTS
REQUIRED. (REFER TO SHORT CIRCUIT
CALCULATIONS FOR ACTUAL AMPS TO BE LABELED).
3. CIRCUIT BREAKERS SHALL BE A BOLT-ON TYPE, U.L.
LISTED SERIES-RATED COMBINATION FROM
PUBLISHED COMBINATION LISTINGS.
GENERAL PANELBOARD
NOTES
OTP 11/12/24
JOB NO.: 33080
SUITE 5268 479-636-5004
ROGERS, AR 72756 DESIGNED BY: LHO
1805 N 2ND ST