Circle K - Yelm (Yelm & Killion), WA - Mechanical OTPA
A
B
B
22
11
8"Ø C
200
TYP 2
12"Ø A
450
TYP 2
10"Ø A
400
W/DAMPER
IN VERTICAL
12"x12"B
350
FF
2
FF
3
FF
1
WALK-IN FREEZER
WALK-IN COOLER
CASHIER
MEN'S
RESTROOM
WOMEN'S
RESTROOM
STORAGE ROOM
BACK ROOM
SALES FLOOR 2
COLD VAULT
SALES FLOOR 1
HALLWAY
1
2
2
2
CO
CO
4
5
5
6
7
RTU1
8
12"Ø A
450
W/DAMPER
IN VERTICAL
CO2
18"Ø
10
"
Ø
1" CD
3/4" CD
12"Ø
8"
Ø
8"
Ø
10"Ø
12"Ø A
450
TYP 2
S
DS
20
"
x
2
2
"
14"Ø
9
11
113/4" CD
3/4" CD
SALES FLOOR 3
RESTROOM ENTRY
12
"
Ø
18
"
x
2
4
"
18"Ø
12"Ø A
450
18"Ø
333
3
3/4" CD
CO
3
3/4" CD
CO
B501 B502
14
"
Ø
12"Ø
PREP AREA
2
12"x12"E
225
TYP 2
12
14"Ø
13
S14
10"Ø
10"Ø A
400
14"Ø
CO
CO
12"Ø
RTU1
14"Ø
OAU1
900
18
"
x
1
0
"
10"Ø A
400
12"Ø A
425
10"Ø
12"Ø
8"Ø A
75
12
"
Ø
18"Ø
14"Ø
14"Ø
18"Ø
2
.
.
2
2
14
0
15
12
"
Ø
8"Ø A
100
2
12"Ø
15
10"Ø
8"
Ø
10
12"x12"F
1
TYP 5
-
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.1
PROJECT NUMBER: 24212
MECHANICAL -
FLOOR PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
3/16" = 1'-0"
1 MECHANICAL FLOOR PLAN
A. EQUIPMENT SHALL COMPLY WITH ASHRAE
STANDARDS.
B. ALL WORK SHALL COMPLY WITH ALL APPLICABLE
FEDERAL, STATE, AND LOCAL CODES, LAWS, ACTS,
AND AUTHORITIES HAVING JURISDICTION.
C. THE COMPLETED INSTALLATION SHALL BE IN
ACCORDANCE WITH ALL APPLICABLE INDUSTRY
STANDARD OF GOOD PRACTICE AND SAFETY, AND
THE MANUFACTURER'S STRICTEST
RECOMMENDATIONS FOR EQUIPMENT AND
PRODUCT APPLICATION AND INSTALLATION.
D. ALL WORK SHALL BE LOCATED TO PROVIDE
ADEQUATE CLEARANCE FOR ARCHITECTURAL
DESIGN AND PROPER OPERATION AND SERVICE OF
EQUIPMENT.
E. ALL WORK SHALL BE LOCATED TO AVOID CONFLICTS
WITH OTHER TRADES. CLOSELY COORDINATE ALL
WORK WITH ALL OTHER TRADES. FAILURE OF THE
CONTRACTOR TO COORDINATE WITH ALL OTHER
TRADES SHALL RELIEVE THE OWNER/ENGINEER
FROM ANY ADDED COSTS.
KEYNOTES
1 PROGRAMMABLE THERMOSTAT WITH REMOTE
TEMPERATURE SENSORS. REF ENERGY MANAGEMENT
SYSTEM DRAWING.
2 ROUTE ALL DUCTWORK WITHIN THE JOISTS UNLESS
OTHERWISE SPECIFIED.
3 PROVIDE COPPER DRAIN LINES FROM COOLER/FREEZER
EVAPORATORS. VERIFY LOCATIONS WITH
REFRIGERATION PLANS (EVAPORATORS PROVIDED BY
CK/OTHERS). DRAIN LINES IN FREEZER SHALL BE
INSULATED AND HEAT TRACED. HEAT TRACE SHALL BE
SELF REGULATING 120V, 5 W/FT RAY-CHEM XL-TRACE OR
EQUIVALENT. REFER TO ELECTRICAL SHEETS FOR
POWER SUPPLY.
4 COPPER CONDENSATE DRAIN FROM COOLERS AND
FREEZER EVAPORATORS THRU WALL 12" AFF. ROUTE TO
GRASSY AREA. PROVIDE TRAP AT TERMINATION. HEAT
TRACE PIPING EXPOSED TO FREEZING.
5 MECHANICAL CONTRACTOR SHALL INSTALL A 6"
DIAMETER PVC PIPE, SCHEDULE 40, FROM TOP OF SLAB,
DOWN BELOW SLAB, OVER TO DELI CASE AND
TERMINATE AT SLAB WITH PULL STRING AS SHOWN. THE
REFRIGERANT PIPING WILL BE INSTALLED IN THIS PIPE
SLEEVE. CONTRACTOR SHALL PROVIDE LONG RADIUS
TYPE SWEEP ELBOWS AS REQUIRED. MECHANICAL
CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR THE TIMING OF THIS INSTALLATION.
PIPING SHALL BE CAPPED AT OPEN ENDS AS SOON AS IT
IS INSTALLED TO PREVENT DIRT, DEBRIS, AND WATER
FROM COLLECTING INSIDE OF PIPE. COORDINATE
TERMINATION POINT AT SLAB WITH DELI CASE
INSTALLATION INSTRUCTIONS. MECHANICAL
CONTRACTOR SHALL COORDINATE ELEVATION OF PIPE
BELOW SLAB WITH PLUMBING UTILITIES.
6 CO2 LOUVRED CABINET. SEE SHEET M1.4 FOR DETAIL.
7 ALL AIR GAPS TO BE MINIMUM TWICE THE DIAMETER OF
THE INDIRECT WASTE PIPE AS PER IPC 802.3.1.
8 SMOKE DETECTOR FOR UNIT SHUT-DOWN TO BE
FACTORY INSTALLED BY MANUFACTURER.
9 PROVIDE CO2 DETECTOR AND ALARM. SEE SHEET M1.5
FOR DETAIL OF CO2 DETECTOR AND ALARM SYSTEM.
10 EXTERIOR ROOF ACCESS.
11 MECHANICAL CONTRACTOR TO PROVIDE COPPER DRAIN
LINES FROM ROOFTOP EQUIPMENT.
12 PROVIDE RUNNING TRAP IN COOLER.
13 COPPER DRAIN LINE FROM COOLER AND FREEZER
EVAPORATORS DOWN IN WALL. TERMINATE AT FLOOR
SINK WITH MINIMUM 2" AIR GAP.
14 REMOTE TEMPERATURE SENSOR IN SUPPLY AND
RETURN AIR DUCT.
15 FULL SIZE SUPPLY & RETURN AIR DUCTS DOWN THRU
ROOF FROM ROOFTOP PACKAGE UNIT.
GENERAL NOTES
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
A
A
B
B
22
11
1
1
1
1
1
1
1
2
2
3
4
5
6
3
3
7
1
8
9
3
9
OAU1 RTU1 10
7
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.1.1
PROJECT NUMBER: 24212
MECHANICAL -
ROOF PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
MKE
JMS
SAG
JMS
3/16" = 1'-0"
1 MECHANICAL ROOF PLAN
A. EQUIPMENT SHALL COMPLY WITH ASHRAE
STANDARDS.
B. ALL WORK SHALL COMPLY WITH ALL APPLICABLE
FEDERAL, STATE, AND LOCAL CODES, LAWS, ACTS,
AND AUTHORITIES HAVING JURISDICTION.
C. THE COMPLETED INSTALLATION SHALL BE IN
ACCORDANCE WITH ALL APPLICABLE INDUSTRY
STANDARD OF GOOD PRACTICE AND SAFETY, AND
THE MANUFACTURER'S STRICTEST
RECOMMENDATIONS FOR EQUIPMENT AND
PRODUCT APPLICATION AND INSTALLATION.
D. ALL WORK SHALL BE LOCATED TO PROVIDE
ADEQUATE CLEARANCE FOR ARCHITECTURAL
DESIGN AND PROPER OPERATION AND SERVICE OF
EQUIPMENT.
E. ALL WORK SHALL BE LOCATED TO AVOID CONFLICTS
WITH OTHER TRADES. CLOSELY COORDINATE ALL
WORK WITH ALL OTHER TRADES. FAILURE OF THE
CONTRACTOR TO COORDINATE WITH ALL OTHER
TRADES SHALL RELIEVE THE OWNER/ENGINEER
FROM ANY ADDED COSTS.
GENERAL NOTES
KEYNOTES
1 CONDENSING UNIT FOR REFRIGERATION EQUIPMENT
BY VENDOR SHOWN FOR REFERENCE ONLY.
2 VTR'S SHOWN FOR REFERENCE ONLY, REFER TO
PLUMBING DRAWINGS FOR MORE INFORMATION.
PROVIDE MINIMUM 10'-0" SEPARATION FROM OUTSIDE
AIR INTAKES ON HVAC UNITS.
3 PIPE PORTAL FOR REFRIGERANT PIPING, ELECTRICAL
CONDUIT AND/OR CONDENSATE LINE AS REQUIRED,
REFER TO REFRIGERANT LINE GOOSENECK DETAIL.
4 3" GREASE TRAP VENT DOWN IN WALL AND CONNECT
TO GREASE TRAP.
5 SATELLITE DISH SHOWN FOR REFERENCE ONLY.
REFER TO ARCHITECTURAL DRAWINGS FOR INFO.
6 FREEZE LESS ROOF HYDRANT. REFERENCE PLUMBING
SHEETS.
7 MECHANICAL CONTRACTOR TO PROVIDE COPPER
DRAIN LINES FROM ROOFTOP EQUIPMENT.
8 EXTERIOR ROOF ACCESS SHOWN FOR REFERENCE
ONLY, REFER TO ARCHITECTURAL DRAWINGS FOR
MORE INFORMATION.
9 RUSKIN SD60 30'x20' SMOKE DAMPER INSTALLED IN
DRAFT STOP. DAMPER SHALL INCLUDE 24V NO FLOW
DUCT SMOKE DETECTOR AND 24V FAST ACTING
ACTUATOR. GC TO FIELD VERIFY EXACT LOCATION.
10 ROOFTOP HVAC UNIT INSTALLED ON FACTORY CURB
ON ROOF.
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
MANUFACTURERS
LABEL PER 2021
WSMC SECTION
301.9
IDENTIFICATION
LABEL PER 2021
WSMC SECTION
301.9
OUTSIDE AIR
INTAKE HOOD
LABEL TO BE
ENGRAVED UV
STABLE PLASTIC
SCREWED TO UNIT
FILTER ACCESS
PANEL
FLEX CONNECTION ON
SUPPLY & RETURN
ACOUSTICALLY LINED SUPPLY
AND RETURN AIR DUCTS, SAME
SIZE AS UNIT CONNECTION
REFER TO SPECS FOR
INSULATION REQUIREMENTS
CONDENSATE DRAIN,
SEE PLAN FOR
SIZING AND ROUTING
CLEAN OUT
4" THICK, 6 PCF DENSITY INSULATION INSIDE
CURB AROUND DUCT DROPS. INSULATION
INSTALLED FULLY INSIDE CURB PERIMETER.
14" HIGH FACTORY SUPPLIED CURB
SECURELY ANCHORED TO ROOF, FLASH AND
COUNTER-FLASH WATERTIGHT (SET UNIT
LEVEL). SECURE UNIT TO CURB; REF RTU
ANCHOR BRACKET DETAIL.
SECURE UNIT TO ROOF CURB,
CAULK WATERTIGHT.
PROVIDE ADEQUATE
CLEARANCE AROUND PIPING TO
REMOVE ACCESS PANEL ON
UNIT.
ROOFTOP UNIT
DUCT
HVAC
UNIT
POWER
SOURCE
NOTES:
TO FIRE DETECTION
OR ALARM SYSTEM
(IF PRESENT)
"LOW FLOW" TYPE DUCT SMOKE DETECTOR MOUNTED ON THE RETURN AIR DUCT WHERE SHOWN. FURNISHED,
INSTALLED, AND CONTROL WIRING BY MECHANICAL CONTRACTOR UNLESS FACTORY INSTALLED IN RTU. POWER
WIRING BY ELECTRICAL/FIRE ALARM CONTRACTOR. SEE PLANS FOR ALL LOCATIONS. PROVIDE REMOTE VISIBLE AND
AN AUDIBLE SIGNAL ALONG WITH LED BELOW CEILING AS REQUIRED PER 2021 WS MECH CODE AND NFPA.
MECHANICAL CONTRACTOR SHALL FURNISH, INSTALL, AND PROVIDE WIRING TO HVAC UNIT TO SHUT DOWN UNIT
UPON DETECTION OF SMOKE UNLESS FACTORY INSTALLED IN RTU. MECHANICAL CONTRACTOR SHALL PROVIDE ALL
NECESSARY RELAYS, CONTRACTORS, POWER MODULES, ETC. AS NECESSARY TO PROVIDE A COMPLETE
OPERATIONAL SYSTEM. COORDINATE WITH ELECTRICAL/FIRE ALARM CONTRACTOR TO VERIFY VOLTAGE
REQUIREMENTS, LOCATIONS, ETC.
ELECTRICAL/FIRE ALARM CONTRACTOR SHALL PROVIDE WIRING IF FIRE DETECTION OR ALARM SYSTEMS ARE
PROVIDED FOR THE BUILDING, THE SMOKE DETECTORS SHALL BE SUPERVISED BY SUCH SYSTEMS.
SMOKE DETECTORS REQUIRED BY 2021 WSMC SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72. DUCT SMOKE
DETECTORS REQUIRE A REMOTE LED INDICATOR THRU THE CEILING LEVEL. NFPA 72 3-8.3. DUCT SMOKE
DETECTORS SHALL ACTIVATE A VISIBLE AND AUDIBLE SIGNAL AT A NORMALLY OCCUPIED LOCATION AND SHALL BE
MONITORED BY THE FACP AND REPORT AS A SUPERVISORY SIGNAL PER NFPA 72 AND THE 2021 WS MECH CODE .
DUCT SMOKE DETECTORS TO PROVIDE SHUTDOWN IN 30 SECONDS OR LESS.
3
3
4 1 2
1
2
4
DS
INTERNAL DRAIN
PAN IN UNIT
CLEAN OUT
COIL
3"
3"
OPEN
6"
CONDENSATE
DRAIN LINE, SEE
PLAN FOR SIZE
NOTES:
~
1. CONDENSATE DRAIN LINES SHALL BE GRADED CONTINUOUSLY AND UNIFORMLY TO POINT OF DISCHARGE. MINIMUM
OF 1/8" PER FOOT.
2. CONDENSATE DRAIN LINES SHALL BE TYPE "M" HARD DRAWN COPPER TUBING ASTM B-88.
3. GENERAL CONTRACTOR TO SUPPLY AND INSTALL ALL CONDENSATE DRAINS PER MANUFACTURER'S
RECOMMENDATIONS.
4. INSULATE PRIMARY COIL CONDENSATE INSIDE BUILDING IN ACCORDANCE WITH SHEET SPECIFICATIONS
CENTERLINE
CE
N
T
E
R
L
I
N
E
CENTERLINE
RADIUS = 1.5W
W
R
NOTE: RADIUS ELBOWS
WITH MITERED THROAT
ARE NOT ALLOWED
RADIUS ELBOWMITERED ELBOW WITH
TURNING VANES
STRAP
SHEET METAL
SCREWS
NOTE: USE EITHER ANGLE OR STRAP
ANGLERODS
REFER TO SMACNA HVAC DUCT CONSTRUCTION STANDARDS TABLE 4-1
FOR "RECTANGULAR DUCT HANGERS MINIMUM SIZE".
SHEET METAL SCREW
OR POP RIVETS
ROD
STRAP
STRAP
1
1
/
2
"
STRAP
1/4" BOLT
REFER TO SMACNA HVAC DUCT CONSTRUCTION
STANDARDS TABLE 4-2 FOR "MINIMUM HANGER SIZES
FOR ROUND DUCT".
NOTE:
AIR FLOW
AI
R
F
L
O
W
BRANCH
DUCT
MAIN DUCT
1. FABRICATE PER SMACNA DUCT CONSTRUCTION STANDARDS FIGURE #2-8.
2. DO NOT USE EXTRACTORS IN BRANCH DUCTWORK.
3
0
°
W
W/
4
(
M
I
N
.
4
"
)
30°
3
0
°
45°
AIR FLOW
AIR FLOW
BRACKET ATTACHMENT
HVAC
UNIT
BRACKET
#12 TEK SCREWS
(TYP SIX PER
BRACKET)CURB
ROOF
∅3/16
SCREW HOLES
TWO PER ROW
EQ SPACED
TYP
BRACKETS ARE FURNISHED WITH RTU. BRACKET CONSTRUCTION, QUANTITIES, AND SPACING
SHOWN ON THIS DETAIL IS FOR GENERAL COORDINATION ONLY. INSTALL BRACKETS ACCORDING
TO MANUFACTURER'S INSTALLATION INSTRUCTIONS. COORDINATE FINAL BRACKET LOCATIONS
WITH EQUIPMENT. DO NOT OBSTRUCT OPENINGS OR UTILITY CONNECTIONS.
RTU BRACKET
16 GA
GALV TYP
BRACKET TYP
RTU BRACKET LAYOUT
∅3/16
SCREW HOLES
FOUR PER ROW
EQ SPACED
TYP
BRANCH DUCT
LAY-IN
CEILING
TYPICAL CEILING
DIFFUSER OR
RETURN GRILLE
SPIN-IN OR FLANGED FITTING WITH LOCKING
QUADRANT AND 2" STANDOFF. 13"DIA AND
LARGER TO HAVE SOLID ROD, NYLON
BUSHINGS LOCKING QUADRANT AND 2"
STANDOFF, REFERENCE SMACNA DETAIL
7-4, 2005 EDITION
1", 26 GA.
SUPPORT FROM
STRUCTURE @
MAX. 4'-0" O.C.
TAPE AROUND SNUGGLY Z WRAPS
PRIOR TO INSTALLING LINE STRAP
RIGID DUCT WHERE BRANCH DUCT
EXTENDS 4'-0" AND LONGER
THERMAFLEX TYPE M-KE FLEX DUCT
WITH CPE LINER & R=6.0 INSULATION,
CLASS 1 FLEXIBLE DUCT. DIAMETER
EQUAL TO DIFFUSER NECK SIZE
(MAX LENGTH 4'-0")
1" WIDE X 20 GA. STRAP W/
TIGHTENING SCREW -SECURE
STRAP W/ SHEET METAL
SCREWS 3" O.C. MAXIMUM
(TYPICAL)
PROVIDE MIAMI TECH #LJ10 OR EQUAL
4" OPENING
7" CLEARANCE
SEAL OPENING
WATERTIGHT
PROVIDE AIR-TIGHT FOAM SEAL
AROUND PIPING AND CONDUITS
PROVIDE INSULATION AT
ROOF INTERFACE
AROUND PIPING
EQUIVALENT TO ROOF
INSULATION AMOUNT
PROVIDE SHEET METAL
ENCLOSURE PANEL
WITH OPENINGS FOR
PIPING AND CONDUIT
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2
PROJECT NUMBER: 24212
MECHANICAL -
DETAILS (1 OF 3)
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
N.T.S.
1 ROOF-TOP PACKAGE UNIT DETAIL
N.T.S.
5 DUCT SMOKE DETECTOR CONNECTION DETAIL
N.T.S.
10 CONDENSATE DRAIN TRAP DETAIL
N.T.S.
7 DUCT ELBOW DETAILS
N.T.S.
9 RECTANGULAR DUCT HANGER DETAIL
N.T.S.
4 ROUND DUCT HANGER DETAIL
N.T.S.
6 DUCT CONNECTION
N.T.S.
2 RTU ANCHOR BRACKET DETAIL
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
N.T.S.
8 DIFFUSER/GRILLE CONNECTION DETAIL
N.T.S.
3 REFRIGERANT LINE GOOSENECK DETAIL
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2.1
PROJECT NUMBER: 24212
MECHANICAL -
DETAILS (2 OF 3)
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
OTP 11/12/24
FOR
INOFRMATION
ONLY
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2.2
PROJECT NUMBER: 24212
MECHANICAL -
DETAILS (3 OF 3)
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
OTP 11/12/24
FOR
INOFRMATION
ONLY
1. SIZE ALL UNITS ON SUMMER AMBIENT TEMPERATURE: 95° F.
2. VERIFY VOLTAGE/PHASE WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING.
3. COOLING CAPACITY, MINIMUM HEAT CAPACITY AND CFM ARE MINIMUM OUTPUT REQUIRED. ALL UNITS SHALL HAVE NO LESS THAN 98% OF THESE CAPACITIES.
COOLING CAPACITY IS GROSS COIL CAPACITY REQUIRED (FAN HEAT NOT DEDUCTED).
4. UNITS TO BE FURNISHED WITH FACTORY INSTALLED RETURN AIR SMOKE DETECTORS.
5. PROVIDE 14" ROOF MOUNTING CURB. VERIFY INSULATION HEIGHT. PROVIDE SEISMIC/WIND RESTRAINT BRACKETS.
6. PROGRAMMABLE THERMOSTAT WITH REMOTE SENSORS BY EMS SUPPLIER.
7. PROVIDE FACTORY INSTALLED ECONOMIZER WITH ENTHALPY SENSOR AND CONTROL ACCESSORIES.
8. PROVIDE WITH AUXILIARY HEATER.
9. PROVIDE WITH HAIL GUARDS
10. PROVIDE FACTORY INSTALLED DISCONNECT.
11. PROVIDE WITH UNPOWERED GFCI CONVENIENCE OUTLET.
12. PROVIDE COIL COATING.
13. PROVIDE CONDENSATE OVERFLOW SHUTDOWN SWITCH.
NOTES:
1. FIELD PAINT ALL DIFFUSERS AND GRILLES - COLOR WHITE
2. SA=SUPPLY AIR
3. EA=EXHAUST AIR
4. RA=RETURN AIR
5. TA=TRANSFER AIR
6. PROVIDE VOLUME / BALANCE DAMPERS WHERE INDICATED ON DRAWINGS.
a. ROUND (MANUFACTURER / MODEL): RUSKIN / MDRS25, DAYTON / 2TF (OR EQUIVALENT)
b. RECTANGULAR (MANUFACTURER / MODEL): RUSKIN / MD25, DAYTON / 22CV (OR EQUIVALENT)
7. PROVIDE DIFFUSER TO DUCT CONNECTION TRANSITION AS REQUIRED.
8. PROVIDE MANUFACTURERS SECTORIZING BAFFLES WHERE INDICATED BY FLOW ARROWS ON PLAN. USE A 4-
WAY THROW IF NO THROW ARROWS ARE SHOWN.
NOTE:
A. PROVIDE WALL MOUNTED CONTROL PANEL.
B. PROVIDE HARD-WIRED ROLLER TYPE MICROSWITCH AT DOOR/WINDOW. NO OTHER ON/OFF SWITCH IS TO BE
PROVIDE/INSTALLED.
C. PROVIDE INLET LOUVER AND FILTER.
D. PROVIDE WALL MOUNTING BRACKETS.
NOTES:
1. CALCULATIONS WERE PERFORMED WITH TRANE TRACE 700 SOFTWARE PROGRAM IN COMPLIANCE WITH ASHRAE
FUNDAMENTALS.
2. EQUIPMENT SIZING MEETS THE IECC 403.2.2 REQUIREMENTS
3. ALL MECHANICAL AIR CONDITIONING EQUIPMENT TO HAVE MINIMUM EFFICIENCY RATING PER 2021 WSEC, TABLE
C403.2.3. SUBMIT MECHANICAL AC EQUIPMENT TO OWNER OR ENGINEER FOR REVIEW AND APPROVAL PRIOR TO
ORDER.
NOTES:
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2.3
PROJECT NUMBER: 24212
MECHANICAL -
SCHEDULES
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
AIR DEVICE SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL FRAME
MATERIAL-
MODULE
A SA TITUS TMSA LAY-IN STEEL 24X24
B EA TITUS 23R LAY-IN STEEL 24X24
C SA TITUS TDC SURFACE MOUNT STEEL12X12
E EA TITUS 23R SURFACE MOUNT STEEL12X12
F RA TITUS 23R LAY-IN STEEL 24X24
AIR CURTAIN SCHEDULE
MARK LOCATION MANUFACTURER MODEL FPM
MOTOR
SONES WEIGHT NOTESPOWER VOLTAGE PH HZ MCA
FF 1 HALLWAY MARS AIR STD260-2U 3400 0.50 hp 115 V 1 60 Hz 12.75 A 68 90 lb A,B,C,D
FF 2 SALES FLOOR 2 MARS AIR STD236-1U 1800 0.50 hp 115 V 1 60 Hz 6.40 A 66 60 lb A,B,C,D
FF 3 SALES FLOOR 3 MARS AIR STD236-1U 1800 0.50 hp 115 V 1 60 Hz 6.40 A 66 60 lb A,B,C,D
ROOFTOP UNIT SCHEDULE
MARK MANUFACTURER MODEL
SUPPLY FAN
COOLING
CAPACITY
HEAT PUMP
HEAT RATING
OR NATURAL
GAS HEAT
OUTSIDE
AIR CFM
WEIGHT
(LBS)
ELECTRICAL DATA
AUXILIARY
ELEC HEAT
CFM
ESP
(IN.)HP BTU/HR VOLTS PH HZ MCA MOCP KW
RTU1 Carrier 50FCQ 4,000 10.0 ton 3 60 Hz
OUTSIDE AIR CALCULATION
OUTSIDE AIR REQUIREMENTS PER TABLE 403.3 AND 403.3.1.2, 2021 IMC
NAME
MINIMUM
EXHAUST AREA
# PEOPLE/
1000 FT²
NUMBER
OF
PEOPLE
OUTDOOR
AIR PER
PERSON
OUTDOOR
AIR PER
AREA
PEOPLE LOAD
REQUIRED (PLR)
OSA
BUILDING LOAD
REQUIRED (BLR)
OSA
SYSTEM
EFFICENCY
VALUE
TOTAL OSA REQUIRED
[(PLR+BLR)/SYSTEM
EFFICENCY]
CASHIER 0 226 SF 15 3 7.5 CFM 0.12 CFM/SF 25 CFM 27 CFM 0.8 66 CFM
HALLWAY 0 93 SF 15 1 7.5 CFM 0.12 CFM/SF 10 CFM 11 CFM 0.8 27 CFM
MEN'S
RESTROOM
200 222 SF 0 0.0 CFM 0.00 CFM/SF 0 CFM 0 CFM 0.8 0 CFM
REAR ENTRY
HALLWAY
0 49 SF 9 0 7.5 CFM 0.12 CFM/SF 3 CFM 6 CFM 0.8 12 CFM
RESTROOM
ENTRY
0 91 SF 0 0.0 CFM 0.00 CFM/SF 0 CFM 0 CFM 0.8 0 CFM
SALES FLOOR 1 0 633 SF 7 5 7.5 CFM 0.06 CFM/SF 35 CFM 38 CFM 0.8 92 CFM
SALES FLOOR 2 0 517 SF 7 4 7.5 CFM 0.06 CFM/SF 29 CFM 31 CFM 0.8 75 CFM
STORAGE
ROOM
0 87 SF 20 2 0.0 CFM 0.12 CFM/SF 0 CFM 10 CFM 0.8 13 CFM
WOMEN'S
RESTROOM
200 223 SF 0 0.0 CFM 0.00 CFM/SF 0 CFM 0 CFM 0.8 0 CFM
BACK ROOM 0 494 SF 20 10 0.0 CFM 0.12 CFM/SF 0 CFM 59 CFM 0.8 74 CFM
PREP AREA 0 224 SF 15 3 7.5 CFM 0.12 CFM/SF 25 CFM 27 CFM 0.8 65 CFM
SALES FLOOR 3 0 1315 SF 7 10 7.5 CFM 0.06 CFM/SF 73 CFM 79 CFM 0.8 190 CFM
TOTALS 4174 SF 39 202 CFM 289 CFM 613 CFM
AIR BALANCE SCHEDULE
MARK O.A. E.A. PRESSURE
OAU1 900 CFM 0 CFM 900 CFM
TOTAL EXHAUST: 1 900 CFM 900 CFM
2021 WSEC LOAD SUMMARY
AREA
COOLING LOAD CALCULATION
(MBH)
PROVIDED EQUIPMENT COOLING CAPACITY
(MBH)
SENSIBLE TOTAL SENSIBLE TOTAL
RTU1 100.1 110.6 93.4 125.3
SALES OSA RATE USES SUPERMARKET OCCUPANCY CLASSIFICATION
OTP 11/12/24
.75 2.4 115000 0 1293 208 133 150 24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
800 CFM 100 CFM
100 CFM800 CFM
T
~~
~~
~
~
~
~
~
~
~~
~
~
2021 WSEC COMPLIANCE NOTES
SECONDARY CONDENSATE DRAIN
PIPING FLOWSTREAM ID
PIPE FITTING SYMBOLS
TEE CONNECTION
CAPPED OUTLET
FLEX CONNECTION
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
STRAINER, FLANGED
ECCENTRIC REDUCER
SWITCH, PRESSURE
SWITCH, TEMPERATURE
TEST & PRESSURE (T&P) FITTING
PRESSURE GAUGE W/ COCK
PRESSURE GAGE W/O COCK
REDUCER OR INCREASER
DIRECTION OF FLOW
POINT OF NEW CONNECTION TO EXISTING
NEW PIPE CONNECTION TO EXISTING PIPING
SLOPE IN DIRECTION SHOWN (DOWN)
EXISTING PIPING TO BE REMOVED
EXISTING PIPING TO REMAIN
NEW PIPING
DN
F
P
T
UNION
ORIFICE UNION
THERMOMETER
FLANGED UNION
STRAINER
SWITCH, FLOW
FLEX PIPE
PIPE CAP
RISE IN PIPE
PIPE PLUG
PIPE GUIDES
DROP AT END
DROP AT MID
ANCHOR
ANCHOR, WALL
BLIND FLANGE
ABBREVIATIONS
CD
SCD
D
CONDENSATE DRAIN
DRAIN LINE
GENERAL NOTES
CODE INFORMATION
ANNOTATION SYMBOLS
HEX SYMBOL INDICATES NEW EQUIPMENT
NUMBER REFERS TO SPECIFIC EQUIPMENT
IDENTIFIED IN EQUIPMENT SCHEDULE
DUCTWORK SYMBOLS
XXX
CFM
MARK (AS SHOWN ON SCHEDULE)
NECK SIZE (Ø DIA. OR H" x W" RECTANG.)
NUMBER REFERS TO SPECIFIC EQUIPMENT
SYMBOL INDICATES NEW EQUIPMENT
OUTSIDE AIR CFM REQUIRED
POINT OF NEW CONNECTION TO EXISTING
NORTH ARROW
FLOW ARROWS
ROOM NUMBER
KEYED NOTE
DESCRIPTIONSYMBOL
AIR TERMINAL SYMBOLS
V12
X REVISION TRIANGLE
REVISION NUMBER
DETAIL NUMBER
DETAIL SYMBOL
DRAWING WHERE DETAIL APPEARS
OVAL SYMBOL INDICATES A CONTROL VALVE
V-NUMBER REFERS TO A SPECIFIC VALVE
IDENTIFIED IN THE CONTROL VALVE SCHEDULE
X
XXX
X SECTION CUT SYMBOL
SECTION LETTER
SECTION LETTER
SECTION CUT SYMBOL
DRAWING WHERE SECTION APPEARS
ACCESS DOOR
1-1/2 X BRANCH DUCT FROM SIDE OF MAIN
SQUARE ELBOW WITH TURNING VANES
DUCT TRANSITION
EXISTING DUCTWORK
RADIUS TYPE 90° ELBOW
ACCESS PANEL (AP)
NEW
EXISTING
RELOCATED
N
E
R
NEW/RELOCATED SUPPLY DIFFUSER, NECK SIZE, ANDBALANCE AIR AS INDICATED (MATCH EXISTING)
NEW/RELOCATED RETURN GRILLE WITH BOOT(MATCH EXISTING)
EXISTING SUPPLY DIFFUSER
EXISTING RETURN GRILLE WITH BOOT
RELOCATED EXISTING GRILLE OR DIFFUSER
RELOCATED ROOM THERMOSTAT, ELECTRICR
EXISTING ROOM THERMOSTAT, ELECTRICE
EXISTING DUCT TO BE REMOVED
DUCT TRANSITION FROM RECTANGULAR TO ROUND
DUCT OVER/UNDER ANOTHER DUCT
CONICAL TAP FITTING
SHOE TAP FITTING
POINT OF NEW CONNECTION TO EXISTING
SIDEWALL EXHAUST OR RETURN AIR GRILLE
EXHAUST CEILING REGISTER OR GRILLE
MANUAL VOLUME DAMPER (VD)
EXISTING DUCT TO BE REMOVED
30° RISE(R)/DROP(D) IN DUCTWORK IN DIRECTION
OF ARROW
FIRE/SMOKE DAMPER (FSD) THROUGH WALL/ FLOOR
CONNECT NEW DUCT TO EXISTING DUCT
FIRE DAMPER (FD) THROUGH WALL/ FLOOR
ECCENTRIC DUCT REDUCER
CONCENTRIC DUCT REDUCER
MOTOR OPERATED DAMPER
EXISTING DUCT
M
ROOM THERMOSTAT
DUCT SMOKE DETECTOR (DS)
ROOM TEMPERATURE SENSORS
DIFFUSER UNDER DUCT
SIDEWALL SUPPLY REGISTER
ROUND DIFFUSER
SMALL RADIUS ELBOW
LARGE RADIUS ELBOW
RETURN DUCT -SECTION/ END VIEW
SUPPLY DUCT -SECTION/ END VIEW
EXHAUST DUCT -SECTION/ END VIEW
RECTANGULAR DUCT, WIDTH x DEPTH (INCHES)
CROSS SECTION THROUGH ROUND DUCT
FLEXIBLE CONNECTION
12x8 W/1"AL
FLEXIBLE DUCT
ACOUSTICAL DUCT LINING
OVAL DUCT (INCHES)12x8Ø
ROUND DUCT (INCHES)
12x8
12Ø
LINEAR DIFFUSER
RETURN AIR CEILING GRILLE AND RETURN AIR CEILING
GRILLE WITH SOUND BOOT
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES
EXCEPT
TRANSFER AIR SOUND ELBOW)
CEILING DIFFUSERS (ARROWS DENOTE THROW
PATTERN
IF THROW IS SOMETHING OTHER THAN 4-WAY)
SYMBOL DESCRIPTION
SINGLE LINE DUCTWORK
SYMBOL DESCRIPTIONSYMBOLDESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
AD
BF
CI
CO
CONT.
DB
D
Db
DIA.
C
EFF
FB
FD
FD
FCU
ENT
EXH
FS
GA
GAL
FLEX
FT.
FT
HB
HORZ
HP
KW
IN
HR
F.G.
AC
AFF
AL
AMP
BHP
AP
BOD
BOP
BTU
BTUH
BD
CFM
DBT
DX
°F
FCO
FPM
FPS
GPH
FSD
GPM
HD
KWH
KVA
EMCS
NC.
MIN
LBS
MAX
OA
NTS
QTY
QUAD
RA
SA
S.DPR.
RM
REQ
SPEC
ST
TEMP
TSTAT
TYP
V
SQ
WB
Z
VEL
VERT
MA
MCC
N/A
NIC
#,NO.
NO
NC
OBD
PRV
PSI
PD
PSIG
RH
RPM
SCD
SDVV
VAC
VTR
WCO
WH
VAV
SP
TP
ZONE
TOTAL PRESSURE (INCHES OF WATER)
STATIC PRESSURE (INCHES OF WATER)
VARIABLE AIR VOLUME
WALL HYDRANT
WALL CLEANOUT
VENT THRU ROOF
VOLTS, ALTERNATING CURRENT
SINGLE DUCT VARIABLE VOLUME
SMOKE CONTROL DAMPER
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
POUNDS PER SQUARE INCH GAUGE
PRESSURE DROP
POUNDS PER SQUARE INCH
PRESSURE REDUCING VALVE
OPPOSED BLADE DAMPER
NORMALLY CLOSED
NORMALLY OPEN
NUMBER (QUANTITY)
NOT IN CONTRACT
NOT APPLICABLE
MOTOR CONTROL CENTER
MAIN AIR (CONTROLS)
VERTICAL
VELOCITY
WET BULB
SQUARE
VOLTS
TYPICAL
THERMOSTAT
TEMPERATURE
SOUND TRAP
SPECIFICATION
REQUIRED
ROOM
SMOKE DAMPER
SUPPLY AIR
RETURN AIR
QUADRANT
QUANTITY
NOT TO SCALE
OUTSIDE AIR
MAXIMUM
POUNDS
MINIMUM
NOISE CRITERIA
ENERGY MANAGEMENT CONTROL SYSTEM
KILOVOLT-AMPERE
KILOWATT HOUR
HAND DAMPER (VOLUME DAMPER)
GALLONS PER MINUTE
FIRE/SMOKE DAMPER
GALLONS PER HOUR
FEET PER SECOND
FEET PER MINUTE
FLOOR CLEANOUT
DEGREES FAHRENHEIT
DIRECT EXPANSION
DRY BULB TEMPERATURE
CUBIC FEET PER MINUTE
BACKDRAFT DAMPER
BTU PER HOUR
BRITISH THERMAL UNIT
BOTTOM OF PIPE
BOTTOM OF DUCT
ACCESS PANEL
BRAKE HORSE POWER
AMPERE (AMPS)
ACOUSTICAL LINING
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
FILTER GAUGE
HOUR(S)
INCHES
KILOWATT
HORSEPOWER
HORIZONTAL
HOSE BIBB
FLAT TOP
FEET
FLEXIBLE
GALLONS
GAUGE
FLOOR SINK
EXHAUST
ENTERING
FAN COIL UNIT
FIRE DAMPER
FLOOR DRAIN
FLAT BOTTOM
EFFICIENCY
CELSIUS
DIAMETER
DECIBEL
DRAIN
DRY BULB
CONTINUATION
CLEANOUT
CAST IRON
BELOW FLOOR
ACCESS DOOR
ABBREVIATION DESCRIPTION
XX
XX
X
*
*
FLEXIBLE DUCT
UC UNDERCUT
SYMBOLS LIST NOTES
A. DESIGN HEATING AND COOLING LOADS FOR THE BUILDING HAVE BEEN
CALCULATED USING CARRIER HAP USING PROCEDURES
RECOMMENDED BY ASHRAE.
B. ALL EQUIPMENT AND SYSTEMS HAVE BEEN SIZED TO BE NO GREATER
THAN NEEDED TO MEET CALCULATED LOADS.
C. HUMIDIFICATION SYSTEMS HAVE NOT BEEN PROVIDED ON THIS
PROJECT.
D. EACH HEATING OR COOLING SYSTEM ZONE HAS BEEN PROVIDED WITH
ITS OWN TEMPERATURE CONTROL DEVICE.
E. THE PROGRAMMABLE THERMOSTATS SHALL BE CAPABLE OF SETTING
BACK TEMPERATURE TO 55 DEGREES F DURING HEATING AND SETTING
UP TO 85 DEGREES F DURING COOLING, CAPABLE OF AUTOMATICALLY
SETTING BACK OR SHUTTING DOWN SYSTEMS DURING UNOCCUPIED
HOURS USING 7-DIFFERENT DAY SCHEDULES, HAVE A ACCESSIBLE
MANUAL 2-HOUR OVERRIDE THAT ALLOWS TEMPORARY OPERATION OF
THE SYSTEM FOR UP TO 2 HOURS, HAVE A BATTERY BACK-UP CAPABLE
OF MAINTAINING PROGRAMMED SETTINGS FOR AT LEAST 10 HOURS
WITHOUT POWER. A SETBACK OR SHUTOFF CONTROL IS NOT REQUIRED
ON THERMOSTATS THAT CONTROL SYSTEMS SERVING AREAS THAT
OPERATE CONTINUOUSLY SUCH AS THE ELEVATOR EQUIPMENT ROOM
AND ELECTRICAL ROOMS IF APPLICABLE.
F. OUTDOOR-AIR SUPPLY SYSTEMS WITH DESIGN AIRFLOW RATES
GREATER THAN 3000 CFM AND ALL EXHAUST SYSTEMS MUST HAVE
DAMPERS THAT ARE AUTOMATICALLY CLOSED WHILE EQUIPMENT IS
NOT OPERATING IF APPLICABLE.
G. OUTSIDE VENTILATION HAS BEEN DESIGNED PER 2021 WSMC.
H. ALL SUPPLY AND RETURN AIR DUCTS MUST BE INSULATED W ITH A
MINIMUM OF R-6 (2" MINIMUM THICKNESS DUCT WRAP OR 1-1/2" WHEN
DUCT IS LINED). ALL DUCTS LOCATED OUTSIDE THE BUILDING MUST BE
INSULATED WITH A MINIMUM OF R-8.
I. ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND
CONNECTIONS IN DUCTWORK MUST BE SECURELY SEALED USING
WELDMENTS, MECHANICAL FASTENERS WITH SEALS, GASKETS, OR
MASTICS, MESH AND MASTIC SEALING SYSTEMS, OR TAPES. TAPES AND
MASTICS MUST BE LISTED AND LABELED IN ACCORDANCE WITH UL 181A
OR UL 181B.
J. MECHANICAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST BE
USED WHEN CONNECTING DUCTS TO FANS AND OTHER AIR
DISTRIBUTION EQUIPMENT, INCLUDING MULTIPLE-ZONE TERMINAL
UNITS.
K. OPERATOR AND MAINTENANCE DOCUMENTATION MUST BE PROVIDED
TO THE OWNER THAT INCLUDES EQUIPMENT INPUT AND OUTPUT
CAPACITY AND REQUIRED MAINTENANCE ACTIONS, EQUIPMENT
OPERATION AND MAINTENANCE MANUALS, HVAC SYSTEM CONTROL
MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS, SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS.
DESIRED OR FIELD DETERMINED SET POINTS MUST BE PERMANENTLY
RECORDED ON THE CONTROL DRAWINGS, AT CONTROL DEVICES, OR,
FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS. A
COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO
OPERATE.
L. EACH SUPPLY AIR OUTLET OR DIFFUSER MUST HAVE ITS OW N
BALANCING DEVICE. ACCEPTABLE BALANCING DEVICES INCLUDE
ADJUSTABLE DAMPERS LOCATED WITHIN THE DUCTWORK AND SUPPLY
AIR DIFFUSERS.
M. WATER-HEATING EQUIPMENT AND HOT WATER STORAGE TANKS SHALL
MEET THE REQUIREMENTS OF TABLE 404.2 OF THE 2021 WSEC. THE
EFFICIENCY SHALL BE VERIFIED THROUGH DATA FURNISHED BY THE
MANUFACTURER OR THROUGH CERTIFICATION UNDER AN APPROVED
CERTIFICATION PROGRAM.
N. SERVICE WATER-HEATING EQUIPMENT MUST BE PROVIDED WITH
CONTROLS THAT ALLOW THE USER TO SET WATER TEMPERATURE TO
100 DEGREES F FOR DWELLING UNITS AND 90 DEGREES F FOR OTHER
OCCUPANCIES. CONTROL MUST LIMIT OUTPUT TEMPERATURES OF
LAVATORIES IN PUBLIC FACILITY REST ROOMS TO 110 DEG REES F.
O. WATER-HEATING EQUIPMENT NOT PROVIDED WITH INTEGRAL HEAT
TRAPS AND SERVING NON-CIRCULATING SYSTEMS SHALL BE PROVIDED
WITH HEAT TRAPS ON THE SUPPLY AND DISCHARGE PIPING
ASSOCIATED WITH THE EQUIPMENT.
P. FOR AUTOMATIC-CIRCULATING HOT WATER SYSTEMS, PIPING SHALL BE
INSULATED WITH 1" OF INSULATION HAVING A CONDUCTIVITY NOT
EXCEEDING 0.27 BTU-IN/(H xFT2x°F). THE FIRST 8'-0" OF PIPING IN NON-
CIRCULATING WATER HEATING SYSTEMS SERVED BY EQUIPMENT
WITHOUT INTEGRAL HEAT TRAPS SHALL BE INSULATED WITH 1/2" PIPE
INSULATION OF MATERIAL HAVING CONDUCTIVITY NOT EXCEEDING 0.27
BTU-IN/(H xFT2x°F).
DUCT SMOKE DETECTOR TESTING
T
T
DS
A
CFM
X
TYP #
TYPICAL OF NUMBER SHOWN ON
SYSTEM, OR INSTALL NOTE.
A. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS, UNLESS
OTHERWISE NOTED.
B. PROVIDE ACCESS PANELS OR DOORS IN UNACCESSIBLE CEILINGS
AND/OR CHASES FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS,
COILS, FANS, CONTROLS, ETC. ACCESS DOOR RATING SHALL MATCH
CLASSIFICATION OF WALL AND CEILING FIRE RATING.
C. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES,
REGISTERS, ACCESS DOORS, ETC., WITH THE ARCHITECTURAL
REFLECTED CEILING PLAN(S).
D. ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE
SAME NOMINAL SIZE AS THE SCHEDULED DIFFUSER NECK SIZE.
E. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE
SHOWN OR INDICATED. ALL DUCT SIZES SHOWN ON DRAWINGS ARE
NET INSIDE DIMENSIONS.
F. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS. EXCEPT
TRANSFER AIR SOUND ELBOWS.
G. THE CFM OF EACH DIFFUSER, REGISTER, ETC., IS INDICATED IN THE
SYMBOL DESIGNATION ON THE DRAWINGS.
H. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION
OF ALL FIRE RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES.
PROVIDE APPROVED FIRE AND FIRE/SMOKE DAMPERS IN ALL
REQUIRED PENETRATIONS FOR DUCTWORK, GRILLES, REGISTERS
AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF FIRE,
SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIG HT TO
THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE
PROOF CAULKING MATERIAL.
I. CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING,
PLUMBING AND FIRE PROTECTION PIPING WITH STRUCTURAL AND
ELECTRICAL SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO
AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND
SERVICEABILITY.
J. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES,
INSERTS, SLEEVES, AND HANGING DEVICES FOR INSTALLATION OF
MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING,
ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND
TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
K. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL
NECESSARY MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC.,
AS MAY BE REQUIRED TO ADEQUATELY SUPPORT THE MECHANICAL
PIPING, DUCTWORK, AND EQUIPMENT IN A MANNER APPROVED BY
THE ARCHITECT WHICH WILL NOT OVERLOAD THE BUILDING
STRUCTURAL SYSTEM.
L. CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR
OPENINGS IN FULL HEIGHT WALLS SIZED AT 500 FPM (UNLESS
OTHERWISE SPECIFICALLY SHOWN ON THE DRAWINGS) TO CREATE
AND/OR MAINTAIN A RETURN AIR PATH AS REQUIRED. FIRE DAMPERS
AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN SUCH OPENINGS
WHERE REQUIRED BY NOTE "H".
M. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL
PENETRATIONS AND FITTING CONNECTIONS ON ALL DUCT SYSTEMS.
2021 WASHINGTON STATE BUILDING CODE (WSBC), 2021 WASHINGTON
STATE MECHANICAL CODE (WSMC), 2021 WASHINGTON STATE ENERGY
CODE (WSEC) AND 2021 WASHINTON STATE PLUMBING CODE (WSPC).
ALL SYSTEMS SHALL BE IN COMPLIANCE WITH THE ABOVE CODES AS
ADOPTED BY THE CITY OF YELM, WA
OUTDOOR AIR VENTILATION PROVIDED AND BASED ON CHAPTER 4,
SECTION 403.2 AND TABLE 403.3.
SEE SHEET M1.2.2 FOR VENTILATION CALCULATIONS.
ALL ROOFTOP EQUIPMENT SHALL BE PERMANENTLY IDENTIFIED AS TO
THE AREA SERVED WITH A RUST-PROOF METAL NAMEPLATE PER 2021
WSMC.
DUCT SMOKE DETECTORS REQUIRED BY 2021 WSMC SECTION 606 SHALL
BE INSTALLED IN THE RETURN DUCTWORK AS SHOWN ON THE PLANS PER
WSMC 606.2.1, 606.2.2, 606.3, AND NFPA 72. IF A FIRE ALARM SYSTEM IS
AVAILABLE, THAT THE DUCT SMOKE DETECTOR(S) SHALL BE CONNECTED
TO THE FIRE ALARM SYSTEM (WSMC 606.4.1) AND IF A FIRE ALARM SYSTEM
IS NOT AVAILABLE, PROVIDE A VISIBLE AND AUDIBLE SUPERVISORY
SIGNAL AT A CONSTANTLY SUPERVISED LOCATION TRIGGERED BY THE
ACTIVATION OF A DUCT SMOKE DETECTOR. INCLUDE THE AIR DUCT
DETECTOR TROUBLE INDICATOR (LED AT THE CEILING BELOW THE DUCT
DETECTOR) AS REQUIRED BY WSMC 606.4.1, EXCEPTION 2.
EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE
TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF
THE LISTING, THE MANUFACTURERS INSTALLATION INSTRUCTIONS AND
THIS CODE. MANUFACTURERS INSTALLATION INSTRUCTIONS SHALL BE
AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION PER WSMC
SECTION 304.1.
ACCESS TO ROOF MOUNTED EQUIPMENT COMPLIES WITH 2021 WSMC.
SEE ARCHITECTURAL DRAWINGS FOR ROOF ACCESS DETAILS.
1. SYMBOLS LISTS, NOTES, ABBREVIATIONS, ETC. ARE FOR GENERAL
REFERENCE ONLY. THE PRESENCE OF SYMBOLS, NOTES,
ABBREVIATIONS, ETC. DOES NOT IMPLY ITS USE ON THIS PROJECT.
REFER TO DRAWINGS FOR SPECIFIC SYMBOLS, NOTES, ABBREVIATIONS,
ETC. USED.
TESTING AND INSPECTION OF SMOKE CONTROL DEVICES
A.PRIOR TO TESTING SMOKE CONTROL DEVICES:
1.VERIFY PROPER OPERATION OF EACH EXISTING SMOKE DETECTOR.
ACTIVATION TESTING SHALL BE PERFORMED USING "CANNED
SMOKE" ACCEPTABLE TO THE AUTHORITIES HAVING JURISDICTION.
2.VERIFY ACTIVATION OF THE EXISTING SMOKE DETECTOR SHUTS
DOWN THE APPROPRIATE AIR-MOVING SYSTEM(S). VERIFY
ACTIVATION OF THE SMOKE DETECTOR IS SHOWN BY THE FIRE
ALARM SYSTEM WHERE MONITORING IS REQUIRED.
B.INSPECTION & TESTING OF SMOKE CONTROL DEVICES:
1.TESTING OF FIRE/SMOKE DAMPERS AND SMOKE DETECTORS SHALL
BE ACCOMPANIED BY THE ELECTRICIAN AND/OR THE CONTROLS
SYSTEM SUPPLIER. IF THE BUILDING HAS A FIRE ALARM SYSTEM, A
REPRESENTATIVE OF THE MANUFACTURER MUST BE PRESENT
DURING THE TESTING.
AN AIR BALANCE REPORT SHOWING FRESH AIR COMPLIANCE IS REQUIRED
BY THE MECHANICAL INSPECTOR FOR FINAL INSPECTION APPROVAL.
VENTILATION SYSTEMS SHALL BE BALANCED BY AN APPROVED METHOD. A
BALANCE REPORT SHALL VERIFY THAT THE VENTILATION SYSTEM IS
CAPABLE OF SUPPLYING AIRFLOW RATES REQUIRED BY SECTION 403 (2021
WSMC SECTION 403.3).
VENTILATION VERIFICATION
?
-
---
H HUMIDISTAT
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2.4
PROJECT NUMBER: 24212
MECHANICAL -
NOTES
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
RTU1
T#
1
18/8
22/2 LOW
CAPACITANCE
COMM CABLE
VICONICS 8650 THERMOSTAT BY
EMS SUPPLIER.
EDGE
534
R
R
R
R
R
18/2
WALK-IN COOLER SENSOR
BEER CAVE SENSOR
WALK-IN DAIRY SENSOR
WALK-IN FREEZER SENSOR
REAR FREEZER SENSOR
INSIDE CPI PANEL
NETWORK
SWITCH
CAT5E
EMS CABLE SPECIFICATIONS
18/2 TSP -WINDY CITY #002352-S OR EQUAL
22/2 TSP -WINDY CITY #043004AL OR EQUAL
NOTE:ALL WIRING TO BE CONTINUOUS, WITH
NO SPLICES AND LABELED ON BOTH ENDS.
S#
1
RS
#
1
18/2
18/2
RETURN
SENSORS
SUPPLY
SENSORS
ROOFTOP
UNIT
RTU SETPOINTS COOLING HEATING HUMIDITY
RTU-1 74°F 68°F 55%RH
THERMOSTAT WIRING FROM RTU TO THERMOSTAT
LOCATION BY MECHANICAL CONTRACTOR. FINAL
CONNECTION TO THERMOSTAT BY EMS SUPPLIER.
OAU1
OAU1 IS INTENDED TO OPERATE
CONTINUOUSLY WHILE BUILDING IS
OCCUPIED TO MEET BOTH
VENTILATION AND EXHAUST
REQUIREMENTS. SUPPLY AIR SHALL
BE NEUTRAL (~70F DB, 55% RH)
COORDINATE FIELD INSTALLED
SENSOR REQUIREMENTS WITH EMS
SUPPLIER AND OWNER
1. REFERENCE MECHANICAL NOTES SHEET AND
MECHANICAL SPECIFICATIONS FOR CONTROLS
INFORMATION.
2. TERMINATIONS SHALL BE MADE IN ACCORDANCE
WITH EMS SUPPLIER INSTRUCTIONS. NO FOIL OR
UNUSED WIRE(S) SHALL BE EXPOSED AFTER
APPLICATION OF HEAT SHRINK.
3. MINOR CHANGES IN MATERIALS OR TERMINATION
POINTS SHALL NOT INCREASE CONTRACT COST.
4. ROUTE EMS CONDUITS CONCEALED IN SALES
AREA.
GENERAL EMS NOTES
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.2.5
PROJECT NUMBER: 24212
ENERGY
MANAGMENT
SYSTEM
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
N.T.S.
1 EMS RISER
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
MECHANICAL SPECIFICATIONSSECTION
1. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL VENTILATOR(S) AND/OR EXHAUST FAN(S) AS SHOWN AND
SCHEDULED. THE UNIT(S) SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS, AND
SHALL PERFORM AT THE CONDITIONS SCHEDULED.
2. INSTALL VENTILATOR(S) AND/OR EXHAUST FAN(S) WITH CLEARANCES FOR SERVICE AND MAINTENANCE.
3. THE MECHANICAL CONTRACTOR SHALL PROVIDE ONE (1) BACKDRAFT DAMPER FOR EACH VENTILATOR AND/OR EXHAUST
FAN, OR SHALL VERIFY A BACKDRAFT DAMPER HAS BEEN FACTORY INSTALLED.
4. THE MECHANICAL CONTRACTOR SHALL ADJUST DAMPER LINKAGES FOR PROPER OPERATION.
15853
POWERED
VENTILATORS
1. ALL DUCTWORK SHALL BE CONSTRUCTED FROM HOT NEW DIPPED GALVANIZED SHEET IRON OR STEEL, ASTM A-120, IN
COMPLIANCE WITH 2021 W.S.M.C. CHAPTER 6, AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS FOR GAGE AND
REINFORCEMENT. ALL DUCTWORK SHALL BE SEALED AND INSULATED IN ACCORDANCE WITH IECC.
2. ALL LOW VELOCITY AIR CONDITIONING SUPPLY AIR AND RETURN AIR DUCTWORK SHALL BE 2-INCH DUCT
CONSTRUCTION. CONSTRUCT AND ERECT DUCTWORK IN ACCORDANCE WITH THE CURRENT ISSUES OF THE WSMC,
SMACNA STANDARDS AND ASHRAE HANDBOOKS. DUCTS SHALL CONFORM TO DIMENSIONS ON THE DRAWINGS UNLESS
LOCATION OF STRUCTURAL MEMBERS PROHIBITS. IN CASE OF CHANGE IN DIMENSIONS, CROSS SECTIONAL AREAS
SHALL BE MAINTAINED.
3. ROUND FLEX DUCT SHALL BE USED FOR DIFFUSER-GRILL CONNECTIONS ABOVE LAY-IN CEILINGS. FLEXDUCT MAY BE
USED IN OTHER AREAS WHERE THE DUCT AND GRILLE ARE PERMANENTLY AND REASONABLY ACCESSIBLE. MAXIMUM
FLEX DUCT LENGTH IS 5'-0'' AND THE DUCTWORK SHALL BE PRE-LINED WITH 1" INSULATION. PERFORMANCE OF
FLEXIBLE DUCT SHALL MEET OR EXCEED THE RIGID DUCTWO RK.
4. FLEXIBLE DUCTS SHALL BE THERMAFLEX II TYPE M-KE, FACTORY FABRICATED ASSEMBLY, SPIRAL CONSTRUCTION,
FIBERGLASS BLANKET INSULATION (R=6.0), AND MYLAR SHEATH. FLEXIBLE DUCTS UL LISTED FOR CLASS 0 DUCT AND
COMPLY WITH NFPA-90A.
5. PAINT ALL DUCTWORK, TURNING VANES, INSULATION ECT., THAT IS VISIBLE THROUGH GRILLES, REGISTERS, OR
CEILING DIFFUSERS FLAT BLACK.
6. TAPE ALL JOINTS IN SHEET METAL DUCTWORK WITH ARABOL AND CANVAS OR EQUAL ADHESIVE.
7. FLEXIBLE CONNECTIONS SHALL BE 30 OUNCE, CLOSELY WOVEN, NEOPRENE COATED GLASS FABRIC THAT IS FIRE
RETARDENT, WEATHERPROOF AND AIRTIGHT, A MINIMUM OF 6" WIDTH.
8. FABRICATE ALL SHEET METAL DUCTS OF PRIME GRADE, LOCKING FORMING QUALITY GALVANIZED STEEL SHEETS
USING GAUGES OF METAL AND REINFORCING BETWEEN JOINTS AS FOLLOWS
A. 12" AND SMALLER (LONGEST SIDE)-24 GAUGE
B. 13"-18" (LONGEST SIDE) - 24 GAUGE.
C. 19"-30" (LONGEST SIDE) - 24 GAUGE, WITH 1"x1"x1/8" ANGLES AT 5 FT. ON CENTER
D. 31"-42" (LONGEST SIDE) - 22 GAUGE, WITH 1"x1"x1/8" ANGLES AT 5 FT. ON CENTER
9. DUCT LINER SHALL HAVE A FLAME SPREAD AND SMOKE DEVELOPMENT 25 OR LESS AND 50 OR LESS WHEN TESTED BY
ASTM E-84 (NFPA 255) METHOD.
10. INSULATE THE FIRST 10 FEET OF ALL RECTANGULAR SUPPLY AIR AND ALL RECTANGULAR RETURN AIR SHEET METAL
DUCTWORK INTERNALLY WITH JOHNS-MANVILLE LINACOUSTIC RC FIBERGLASS DUCT LINER WITH REINFORCED
COATING SYSTEM, THICKNESS 1" (R=6.0) AND DENSITY 1-1/2 PCF. ALL OTHER RECTANGULAR SUPPLY AIR AND RIGID
ROUND DUCTWORK SHALL BE INSULATED WITH 2" THICK (R=6.0) JOHNS-MANVILLE MICROLITE DUCT WRAP WITH FSK
VAPOR BARRIER.
15891
METAL
DUCTWORK
SYSTEMS
1. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING VOLUME DAMPERS, TURNING VANES,
ACCESS DOORS, VIBRATION ISOLATORS, ETC.
2. THE ACCESSORIES SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
15910
DUCT
ACCESSORIES
15975
TEMPERATURE
CONTROLS
1. THE MECHANICAL CONTRACTOR SHALL SUBCONTRACT AN AIR BALANCER TO BALANCE THE SYSTEMS DESCRIBED BELOW.
2. THE BALANCING SHALL BE COMPLETED BY AN INDEPENDENT AIR BALANCER WHO IS NOT AN EMPLOYEE OF THE MECHANICAL
CONTRACTOR.
3. THE BALANCING SHALL BE DONE BY A QUALIFIED AIR BALANCER THAT HAS AT LEAST (3) YEARS OF DOCUMENTED AIR
BALANCING EXPERIENCE.
4. PER COMPLIANCE WITH IECC, THE BALANCER SHALL SUBMIT AN AIR BALANCE REPORT TO THE ENGINEER AND CITY INSPECTOR.
5. THE BALANCE REPORT SHALL SHOW PROOF THAT THE SYSTEM HAS BEEN BALANCED TO +/- 5% OF THE DESIGNED AIRFLOW. IT IS
THE MECHANICAL CONTRACTOR AND AIR BALANCER'S DUTY TO PROVIDE ACCURATE DATA, SO AREAS OF INCORRECT FLOW MAY
BE DISCLOSED TO THE ENGINEER, INSPECTOR, AND OWNER.
6. ALL AIRSIDE SYSTEMS, COMPONENTS, ETC. INCLUDING SUPPLY, RETURN, OUTDOOR, AND EXHAUST AIR SYSTEMS SHALL BE
BALANCED. THE BALANCER SHALL PROVIDE SHEAVES AND BELTS AS NEEDED TO PROPERLY BALANCE EQUIPMENT TO +/- 5% OF
THE DESIGNED AIRFLOWS. ALL DIFFUSERS, REGISTERS, GRILLES, AND LOUVERS SHALL BE INDIVIDUALLY BALANCED AND LISTED
IN THE BALANCE REPORT. ALL AIRSIDE EQUIPMENT, SUPPLY, RETURN, AND OUTDOOR AIR FLOWRATES SHALL BE LISTED IN THE
BALANCE REPORT.
15990
TESTING,
ADJUSTING, AND
BALANCING
15010
BASIC
MECHANICAL
REQUIREMENTS
MECHANICAL SPECIFICATIONSSECTION
15140
SUPPORTS
AND
ANCHORS
1. FURNISH PIPE AND DUCT HANGERS, WHERE REQUIRED, FIRMLY SUPPORTED FROM BUILDING STEEL, CONCRETE OR MASONRY STRUCTURE.
2. SUPPORT PIPING SYSTEMS SECURELY WHILE ALLOWING FOR PIPE AND BUILDING EXPANSION AND CONTRACTION. PROVIDE COPPER PLATED
HANGERS FOR COPPER PIPE. USE ADJUSTABLE STEEL BAND HANGERS. MAXIMUM SPACING SHALL BE 5' FOR 1/2" PIPING, 7' FOR 3/4'' TO 1-1/4"
PIPING, AND 9' FOR 1-1/2" PIPING.
3. FURNISH MECHANICAL EQUIPMENT SUPPORTS AS DETAILED OR AS REQUIRED TO SAFELY AND PERMANENTLY CARRY THE WEIGHT OF THE
EQUIPMENT.
1. INSULATE ALL METAL SUPPLY AND RETURN DUCTWORK WITH 2'' FOIL BACKED FIBERGLASS INSULATION. IN UNHEATED ATTICS OR IN AREAS
LOCATED ABOVE THE LINE OF BUILDING INSULATION, INSULATE ALL DUCTWORK, INCLUDING RETURN AIR AND EXHAUST AIR DUCTWORK, WITH
3'' FOIL-BACKED INSULATION, AND REQUEST THAT GENERAL CONTRACTOR BLOW ATTIC INSULATION OVER THE TOP OF THE INSULATED
DUCTWORK, EXPOSED SPIRAL DUCTWORK, OR DUCTWORK LOCATED WITHIN A HEATED SPACE DOES NOT REQUIRE INSULATION.
2. LINE ALL SUPPLY AND RETURN DUCTWORK WITHIN FIFTEEN (15) FEET OF SUPPLY FAN WITH 1/2" DUCT LINER TO REDUCE SOUND.
3. ALL INSULATION MATERIALS TO HAVE A FLAME SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPMENT RATING OF 50 OR LESS AS TESTED
BY ASTM E-84, UL-723, NFPA 90A-90-B.
15250
MECHANICAL
INSULATION
1. THE OWNER SHALL FURNISH AND GENERAL CONTRACTOR SHALL INSTALL PACKAGED ROOF-TOP UNIT(S) AS SHOWN AND SCHEDULED. THE
UNIT(S) SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS, AND SHALL PERFORM AT THE CONDITIONS
SCHEDULED.
2. THE MECHANICAL CONTRACTOR SHALL PROVIDE TWO (2) SETS OF FILTERS FOR EACH UNIT AND SHALL BE RESPONSIBLE FOR CHANGING
FILTERS WITHIN TWO (2) WEEKS OF START-UP.
3. THE MECHANICAL CONTRACTOR SHALL PROVIDE A SINGLE POWER SOURCE CONNECTION DISCONNECT AND A 15 AMP DUPLEX,
WEATHERPROOF CONVENIENCE OUTLET BOX FOR EACH ROOF TOP UNIT INSTALLED.
15782
ROOF-TOP
UNITS
1. CONDENSATE DRAIN PIPING SHALL BE ASTM B-88, TYPE "M" HARD DRAWN COPPER WITH WROT COPPER FITTINGS AND SOLDERED JOINTS,
50/50 SOLDER. INSULATE WITH 1/2" THICK FLEXIBLE CLOSED CELL FOAMED PLASTIC PIPE INSULATION, ARMSTRONG ARAMFLEX, OR EQUAL
FOR ENTIRE LENGTH. FITTINGS FIELD FABRICATED OF NESTING SIZES, SECURED WITH ADHESIVE. REFRIGERANT SUCTION LINES SHALL BE
INSULATED TO 1" THICKNESS.
2. ALL PIPING SHALL CONFORM TO ASTM B88-72.
3. FITTINGS SHALL WROUGHT COPPER, DRAINAGE TYPE FOR LINES 1-1/4" AND LARGER. SOLDER WITH 50/50 SOLDER.
15783
CONDENSATE
AND COOLER
DRAINS
1. ALL WORK TO BE DONE AND MATERIALS FURNISHED COMPLYING WITH APPLICABLE LAWS, AND RESOLUTIONS, INCLUDING THE CURRENTLY
ENFORCED VERSIONS OF THE INTERNATIONAL MECHANICAL CODE (IMC), INTERNATIONAL PLUMBING CODE (IPC), INTERNATIONAL BUILDING CODE
(IBC), AND LOCAL, STATE, AND FEDERAL FIRE SAFETY CODES (NFPA).
2. ALL MATERIALS USED SHALL BE NEW AND UNDAMAGED.
3. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH CURRENT CONSTRUCTION INDUSTRY STANDARDS AND WORKMANSHIP.
4. PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY INSPECT ALL EXISTING CONDITIONS TO ENSURE
THAT THE WORK REPRESENTED ON THE DRAWINGS AND THESE SPECIFICATIONS CAN BE INSTALLED AS INDICATED.
5. AT SUBSTANTIAL COMPLETION OF THE CONSTRUCTION, FURNISH AS-BUILT PLANS TO ARCH/ENGINEER FOR APPROVAL BEFORE THEY ARE TURNED
OVER TO OWNER
6. ALL MANUFACTURED EQUIPMENT, ACCESSORIES AND MATERIALS SHALL BE USED AS INTENDED BY THE MANUFACTURER, IN STRICT ACCORDANCE
WITH THE MANUFACTURERS WRITTEN INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS.
7. THE MECHANICAL CONTRACTOR SHALL PROVIDE, IN ADDITION TO ANY OTHER WARRANTIES SPECIFIED, A ONE(1) YEAR FULL LABOR AND MATERIAL
WARRANTY ON ALL WORKMANSHIP, MATERIAL AND EQUIPMENT FURNISHED FOR THIS PROJECT. THE CONTRACTOR SHALL REPLACE ALL
DEFECTIVE WORKMANSHIP, EQUIPMENT, AND MATERIALS WITHOUT ADDITIONAL CHARGES, INCLUDING ALL REFRIGERANT CAUSED TO BE LOST BY
REPAIR OF DEFECTIVE WORK OR MATERIALS.
8. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR INSTRUCTING THE OWNER IN PROPER OPERATION AND MAINTENANCE OF THE EQUIPMENT.
A WIRING DIAGRAM WITH INSTRUCTIONS FOR THE OPERATIO N, INSTALLER'S NAME, PHONE NUMBER, MODEL, AND MAKE OF EQUIPMENT PROVIDED,
ETC., SHALL BE FURNISHED TO OWNER. AT A TIME DESIGNATED, PROVIDE AN ENGINEER OR MECHANIC TO GO OVER SYSTEM WITH OWNER'S
REPRESENTATIVE TO THOROUGHLY FAMILIARIZE HIM WITH THE OPERATION AND MAINTENANCE OF THE SYSTEM.
9. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL OPENINGS AND REQUIRED LINTELS NEEDED FOR GENERAL CONTRACTOR
FOR THE INSTALLATION OF MECHANICAL EQUIPMENT.
10. SAWCUTS, LINTELS, HEADERS, AND STRUCTURAL MODIFICATIONS TO THE BUILDING STRUCTURE NEEDED FOR THE INSTALLATION OF MECHANICAL
EQUIPMENT SHALL BE APPROVED BY THE GENERAL CONTRACTOR, BEFORE INSTALLATION.
11. IN GENERAL, OPENINGS AND REQUIRED LINTELS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR IS
RESPONSIBLE FOR PROVIDING DETAILS AND TEMPLATES OF ALL OPENINGS NECESSARY FOR MECHANICAL EQUIPMENT INSTALLATION INCLUDING:
HOUSING, ACCESS DOORS, INSPECTION DOORS, AND PASSAGE WAYS FOR MECHANICAL EQUIPMENT. THE MECHANICAL CONTRACTOR iS
RESPONSIBLE FOR SEALING CRACKS AND FINISHING ROUGH EDGES LEFT FOLLOWING MECHANICAL INSTALLATION.
12. THE USE OF THE MECHANICAL EQUIPMENT FOR HEATING, COOLING, OR DRYING DURING CONSTRUCTION IS PROHIBITED, UNLESS APPROVED BY
WRITTEN DOCUMENTATION BY THE OWNER.
13. ALL OTHER MANUFACTURERS BESIDES THE SPECIFIED PRODUCT MUST BE PRE-APPROVED PRIOR TO BIDDING. SUBMIT DETAILED EQUIPMENT CUT-
SHEETS AND CLEARLY IDENTIFY ANY DIFFERENCES FROM THE SPECIFIED PRODUCT. ANY EQUIPMENT SUBMITTED DURING THE REGULAR
SUBMITTAL PROCESS THAT WAS NOT PRE-APPROVED WILL BE AUTOMATICALLY BE REJECTED.
14. PERMITS AND INSPECTIONS: MECHANICAL CONTRACTOR IS RESPONSIBLE TO OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND LICENSES. WHEN
REQUIRED BY CODE, ALL WORK MUST BE INSPECTED AND APPROVED BY LOCAL AUTHORITIES. PRIOR TO FINAL APPROVAL, FURNISH THE
ARCHITECT/OWNER WITH CERTIFICATES OF INSPECTION AND APPROVALS BY LOCAL AUTHORITIES.
15. PRIOR TO SUBMITTING BID, THE MECHANICAL CONTRACTOR SHALL CAREFULLY EXAMINE THE PLANS FOR THE PROPER FITTING OF THE MATERIAL
AND APPARATUSES INTO THE BUILDING. ARRANGE WORK SCHEDULE FOR MINIMUM INTERFERENCE WITH THE WORK OF OTHER TRADES. SHOULD
THE PARTICULAR EQUIPMENT PROPOSED FOR INSTALLATION REQUIRE OTHER ARCHITECTURAL, STRUCTURAL, PLUMBING, OR ELECTRICAL
CONDITIONS THAT THOSE SHOWN, ARRANGE FOR SUCH SPACE BEFORE SUBMITTING BID. ALL CHANGES NECESSITATED BY THE FAILURE TO
COMPLY WITH THIS CLAUSE, SHALL BE MADE AT NO ADDED EXPENSE TO THE OWNER.
16. WITHIN 10 DAYS AFTER AWARD OF CONTRACT, SUBMIT (4) COPIES OF A COMPLETE WRITTEN LIST OF ALL MAJOR ITEMS OF EQUIPMENT AND
MATERIALS AS WELL AS ADDITIONAL COPIES, THAT THE CONTRACTOR MAY NEED RETURNED. THE SUBMITTAL SHALL DEFINITELY AND CLEARLY
STATE WHERE SUBMITTED EQUIPMENT DOES NOT AGREE WITH THE CONTRACT DOCUMENTS, AND LIST DEVIATIONS IN COLOR OTHER THAN RED.
SUBMIT ALL ITEMS AT ONE TIME AND IN A NEAT AND ORDERLY MANNER. PARTIAL LISTS WILL NOT BE ACCEPTABLE. SUBMITTALS SHALL INCLUDE
MANUFACTURER'S SPECIFICATIONS, PHYSICAL DIMENSIONS AND RATINGS OF ALL EQUIPMENT SUBMITTED. SUBMITTALS SHALL BE INDEXED,
SEPARATED BY DIVIDERS, AND BOUND IN LOOSE LEAF RING BINDERS.
1. THE OWNER SHALL FURNISH OR CONTRACT A TEMPERATURE CONTROL CONTRACTOR TO FURNISH ALL MOTORS, DRIVES,
CONTROLLERS INTEGRAL TO THE MECHANICAL EQUIPMENT SYSTEM, AND FACTORY MOUNTED CONTROLS FOR ALL
MECHANICAL EQUIPMENT.
2. THE MECHANICAL CONTRACTOR OR CONTRACTED TEMPERATURE CONTROL CONTRACTOR SHALL FURNISH AND INSTALL
ALL SWITCHES, FIRE STATS, FREEZE STATS, THERMOSTATS, RELAYS, TIMERS, CONTROL CABINETS, AND OTHER
SPECIALIZED EQUIPMENT PERTAINING TO MECHANICAL CONTROL.
3. THE ROOF MOUNTED UNITS (RTU#) SHALL BE CONTROLLED BY A PROGRAMMABLE THERMOSTAT WITH REMOTE
TEMPERATURE SENSORS.
A. THE TEMPERATURE CONTROLS SHALL BE ELECTRONIC, 7-DAY PROGRAMMABLE, WITH FUNCTION: AUTO, MANUAL, AND
FAN ONLY, UNLESS SPECIFICALLY REQUESTED BY THE OWNER, AND SHALL BE PROVIDED BY THE CONTRACTED
TEMPERATURE CONTROL CONTRACTOR.
B. DEHUMIDIFICATION SYSTEMS SHALL BE CONTROLLED BY MANUFACTURER'S HUMIDISTAT.
C. ALL CONTROL WIRING SHALL BE IN CONDUIT. CONDUIT SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. THE
MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR LOCATION FOR CONDUITS.
THE CONTRACTOR RESPONSIBLE TO INSTALL THE CONTROLS SHALL BE RESPONSIBLE TO PULL THE CONTROL WIRE.
D. THE ROOF TOP UNIT SHALL UTILIZE TEMPERATURE CONTROL SYSTEM FURNISHED AS PART OF THE UNIT, OR SPECIFIED
TO BE PROVIDED AS OPTIONS OR ACCESSORIES BY THE MANUFACTURER BY OF THE UNIT. ALL WIRING WILL BE DONE IN
ACCORDANCE WITH APPROVED SHOP DRAWINGS FURNISHED BY THE MANUFACTURER.
4. ELECTRICAL WIRING: ALL WIRING AND STARTERS ARE INCLUDED IN THE ELECTRICAL DIVISION OF THIS PROJECT, BUT ALL
CONTROLS, RELAYS, ETC., ARE INCLUDED UNDER THIS DIVISION. ROOM THERMOSTATS AND CONTROL SWITCHES SHALL BE
LOCATED AS SHOWN OR DIRECTED, AND ALL CONTROLS, RELAYS, STARTERS AND WIRING SHALL CONFORM TO THE
CURRENTLY ENFORCED VERSION OF THE NATIONAL ELECTRICAL CODE (NEC). ALL CONTROLS SHALL BE FURNISHED AND
PROPERLY IDENTIFIED, WITH INSTRUCTIONS FOR PROPER ELECTRICAL CONNECTIONS. RESPONSIBILITY FOR PROPER
CONNECTIONS AND OPERATION IS INCLUDED HEREIN.
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.3
PROJECT NUMBER: 24212
MECHANICAL -
SPECIFICATIONS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
A
A
B
B
22
11
B504
B603
B603
B603
B603
CASHIER
SALES FLOOR 2SALES FLOOR 1
BACK ROOMWALK-IN COOLER
COLD VAULT
STORAGE ROOMWALK-IN FREEZER
MEN'S
RESTROOM
WOMEN'S
RESTROOM
HALLWAY
STROBE ALARM
OVER BACK DOOR
18" BELOW CEILING
CONTROL PANEL IN CASHIER AREA. REF
ELECTRICAL FOR CONDUIT LOCATIONS FOR
ROUTING UNDER SLAB.
*B603
B503
D
AT 1' -0"
AFF
B503
N
AT 8'-0"
AFF
*B501
B502
B503
N
AT 8'-0"
AFF
PREP AREA
SALES FLOOR 3
1. PRESSURED RELIEF DEVICES SHALL BE PIPED TO THE
OUTDOORS WHERE THE DISCHARGE WILL NOT IMPINGE ON THE
STRUCTURE, PERSONNEL, OR MEANS OF EGRESS AND WILL NOT
CREATE A HAZARDOUS CONCENTRATION OF CARBON DIOXIDE.
(NFPA 55, 13.1.1.2). THE TERMINATION OF THE PRESSURE RELIEF
VENT DISCHARGE PIPING SHALL BE OUT DOORS AND A MINIMUM
OF 10 FEET FROM THE OPENING INTO THE BUILDING.
2. CONTAINERS, CYLINDERS, AND TANKS SHALL BE PROVIDED
WITH A PRESSURE GAUGE AND A LEVEL GAUGE OR DEVICE FOR
INDICATING THE QUANTITY OF LIQUID CARBON DIOXIDE. (NFPA
55, 13.1.2.1)
3. ROOMS OR AREAS WHERE CONTAINER SYSTEMS ARE FILLED
AND USED INDOORS OR IN ENCLOSED OUTDOOR LOCATIONS
SHALL BE PROVIDED WITH A GAS DETECTION AND ALARM
SYSTEM THAT IS CAPABLE OF DETECTING AND NOTIFYING THE
BUILDING OCCUPANTS OF A GAS RELEASE THAT CREATES
CARBON DIOXIDE VAPORS IN EXCESS OF ITS PEL. (NFPA 55,
13.2.2)
4. CARBON DIOXIDE GAS DETECTION SHALL BE AS FOLLOWS:
A. PRE-ALARM (1500 PPM) NOTIFYING AY INCLUDE, BUT NOT
LIMITED TO THE BUILDING OWNER, WORKING SUPERVISOR,
OR MAINTENANCE COMPANY.
B. ALARM (30,000 PPM) NOTIFICATION SHALL INCLUDE THE
COMPLETE AREA, OR BUILDING EVACUATION AND
ACTIVATION OF THE 911 SYSTEM, TO NOTIFY THE YELM FIRE
DEPARTMENT OF A CARBON DIOXIDE GAS DETECTION
ALARM. (PFD POLICY CARBON DIOXIDE 1.1)
5. CARBON DIOXIDE DETECTION SHALL BE LOCATED AT ALL
POINTS OF USE LOCATIONS INSIDE THE BUILDING. (R3000.1)
A. NOTE. THE DETECTION SHOULD BE PLACED AT A LEVEL
ACCEPTABLE BASED ON THE PROPERTIES OF THE GAS
(HEAVIER OR LIGHTER THAN AIR) 12-18 INCHES AFF OR BFC
6. ACTIVATION OF THE GAS DETECTION SYSTEM SHALL INITIATE AN
AUDIBLE ALARM WITHIN THE ROOM OR AREA IN WHICH THE
SYSTEM IS INSTALLED (NFPA 55, 13.2.2.1)
7. A WARNING SIGN SHALL BE POSTED AT THE ENTRANCE TO THE
BUILDING, ROOM, ENCLOSURE, OR CONFINED AREA WHERE THE
CONTAINER IS LOCATED. (NFPA 55, 13.2.3)
8. THE WARNING SIGN SHALL BE AT LEAST 8 IN. (200 MM) WIDE AND
6 IN. (150MM) HIGH AND STATE THE FOLLOWING:
A. CAUTION: CARBON DIOXIDE GAS. VENTILATE THE AREA
BEFORE ENTERING. A HIGH CARBON DIOXIDE (CO2) GAS
CONCENTRATION IN THIS AREA CAN CAUSE SUFFOCATION.
(NFPA 55, 13.2.3.1)
9. PROVIDE MINIMUM OF TWO NOTIFICATION DEVICES, ONE NEAR
THE AREA/ROOM WHERE CYLINDER IS LOCATED, ON IN COMMON
AREA WHERE THE PUBLIC GATHERS. DEVICES SHALL BE RATED
AT 100 CD FOR VISUAL EFFECT AND 75 DB FOR AUDIBLE EFFECT
UNLESS FULL FIRE ALARM IS PRESENT. (R3000.1)
A. *NOTE - IF THE BUILDING IS EQUIPPED WITH A FIRE ALARM
NOTIFICATION SYSTEM; THE USE OF THE SYSTEM IS
ACCEPTABLE, PROVIDED THE GAS DETECTION HAS AUDIBLE
AND VISIBLE CLEAR INDICATORS IN THE HAZARD AREA UPON
BOTH THE WARNING LEVEL AND ALARM LEVEL OF THE GAS.
10. GAS DETECTION SYSTEM SHALL BE TIED INTO THE MONITORING
SYSTEM IF PROVIDED (R3000.1)
11. PROVIDE LABEL ON PIPING TO INDICATE EXACT CONTENTS AND
DIRECTION OF FLOW. THESE LABELS SHALL BE PLACED EVERY
20 FEET, MAJOR CHANGE IN DIRECTION AND WHERE PIPING
ENTERS AND LEAVING WALLS.
NOTES
LEGEND
*
CO2 TANK TUBING
SHUT OFF VALVE LOCATION
B503
D
B501
B603
B502
B503
N
-POINT OF USE (BAG IN THE BOX)
-CO2 TANK CABINET
-DETECTION DEVICE
-NOTIFICATION DEVICE (REPEATER)
NOTE: SEE ALSO SHEET A1.5 & A3.2 FOR ADDITIONAL
INFORMATION
-CO2 CABINET
B504 -CO2 SIGN, SEE DETAIL 2/A9.1
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.4
PROJECT NUMBER: 24212
CO2 LAYOUT
PLAN AND NOTES
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
3/16" = 1'-0"
1 CO2 LAYOUT PLAN (FOR REFERENCE ONLY)
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
M1.5
PROJECT NUMBER: 24212
CO2 CUT SHEETS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
FOR
INFORMATION
ONLY
OTP 11/12/24
A
A
B
B
22
11
3" VTR
3" VTR
3" VTR
1
2
3
4
3
P417
5
2
P1.1
6
7
7
7
7
7
7
7
7
1
CD
CD
OAU1 RTU1
24
"
ROOF HYDRANT,
SEE SCHEDULES
DUAL CHECK BACKFLOW
BOOT COVER AND FLASHING
SECURE CASING TO TOP AND
BOTTOM CORDS OF BAR
JOIST. (OR WOOD TRUSS)
EXTEND DRAIN LINE FROM DRAIN
PORT ON CLOSURE VALVE TO MOP
SINK, FLOOR DRAIN OR OPEN
FIXTURE WASTE WITH AIR GAP
ROOF
BAR JOIST (OR WOOD TRUSS)
3/4" COLD WATER SUPPLY
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.1
PROJECT NUMBER: 24212
PLUMBING -
ROOF PLAN
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
KEYNOTES
1 ROOF DRAINAGE WITH 4" LEADER. SEE
DETAIL 9/A8.3. REFER TO ROOF DRAIN
CALCULATION FOR SIZING INFO.
2 3" GREASE TRAP VENT.
3 3" VTR. MAINTAIN 10'-0" FROM ALL
OUTDOOR AIR INTAKES.
4 3/4" CW UP FROM BELOW TO FREEZE
LESS ROOF HYDRANT.
5 SATELLITE DISH LOCATION. REFERENCE
THE ARCH ROOF PLAN FOR EXACT
LOCATION.
6 EXTERIOR ROOF ACCESS SHOWN FOR
REFERENCE ONLY, REFER TO
ARCHITECTURAL DRAWINGS FOR MORE
INFORMATION.
7 CONDENSING UNIT FOR REFRIGERATION
EQUIPMENT BY VENDOR SHOWN FOR
REFERENCE ONLY.
3/16" = 1'-0"
1 PLUMBING ROOF PLAN
N.T.S.
2 FREEZELESS ROOF HYDRANT
ROOF DRAIN CALCULATIONS
0.0104 = CONVERSION FACTOR - GPM/SQFT FOR 1"/HR RAINFALL.
AREA NAME
AREA
(A1)
PARAPET
AREA
1/2 PARAPET
WALL AREA
(A2)
RAIN FALL RATE
(R IN INCHES)
GPM=0.0104 x R x (A1+A2),
[EQ 11-1 WPC 1106.2.1]
2021 WASHINGTON PLUMBING
CODE:
MINIMUM VERTICAL PRIMARY
DRAIN SIZE PER TABLE 1106.3
LEFT SCUPPER 2599 ft² 342 ft² 171 ft² 1 29 2.5"
RIGHT SCUPPER 2612 ft² 399 ft² 200 ft² 1 29 2.5"
5211 ft² 371 ft²
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
~
~~
A
A
B
B
22
11
P201
P203 P001
P404
P403 P405
P405
P403
HD
TYP
4
HD
P204
P404
P204
P403
P403
P405
P403P404
P101
P404
P101
P101
P106
P106 P106
P106
P405
3" SS
3" SS
4" SS
4" SS
4" SS
4" SS
4" SS
3" SS
3" SS
4" SS
SALES FLOOR 2
CASHIER
SALES FLOOR 1
BACK ROOM
WALK-IN COOLER
COLD VAULT
STORAGE ROOM
WALK-IN FREEZER
MEN'S
RESTROOM WOMEN'S
RESTROOM
HALLWAY
1
2
3
4
5
65
7
P412
2" V
P101P103
P103
TYP
3
P1.3
WCO
P413
3" SS
8
P403
SALES FLOOR 3
FF = 353.50 FT
YCO
YCO
YCO
C001
TYP
3
B301
TYP
2
6" GW
9
WCO
H201
4 6
B001
TYP
3
YCO
YCO
YCO
YCO
M10210
P101 P101
P403
WCO
TYP
3
WCO
C002
C004 C202C005
B003
TYP
2
PREP AREA
4" SS SEE CIVIL
DRAWINGS FOR
CONTINUATION
(INV. 349.5 FT)
6" SS
4" SS
4" GW SEE CIVIL
DRAWINGS FOR
CONTINUATION
(INV. 349.5 FT)
4" H.D.
FLOOR SINK
4" H.D. 4" H.D.
FINISH FLOOR 2% MIN.
FLOOR SINK
4" H.D.
FINISH FLOOR
WALL
4" H.D.
BEVERAGE COUNTER
4" H.D.
BEVERAGE
COUNTER
FINISH FLOOR
WALL
WALL
FOUNTAIN MACHINE
COUNTER
FINISH FLOOR
2% MIN.
2"
2"
3"
3"
3"
3"
2"
2"
2" 2" 2"
2"
INSTALL HUB
DRAIN 24" AFFINSTALL HUB
DRAIN 24" AFF
4" AIR GAP4" AIR GAP
4" H.D.
2"
FLOW FLOW
COLD BEVERAGE STATIONFOUNTAIN MACHINE
4" H.D.
2"
4" H.D.
2"
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.1.1
PROJECT NUMBER: 24212
PLUMBING
FLOOR PLAN -
WASTE AND
VENT
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
3/16" = 1'-0"
1 PLUMBING FLOOR PLAN - WASTE AND VENT
KEYNOTES
1 PROVIDE 3-COMPARTMENT SINK DRAIN LINES WITH
FLOW CONTROL DEVICE AND RUN TO FLOOR SINK.
PROVIDE (3) 1 1/2" INDIRECT WASTE, 1 FOR EACH
COMPARTMENT OF SINK.
2 CONTRACTOR TO COORDINATE UNDERGROUND
SEWER PIPING WITH WALL FOOTING.
3 3" VTR. MAINTAIN 10'-0" FROM ALL OUTDOOR AIR
INTAKES.
4 PROVIDE WALL CLEANOUT. REFER TO SHEET P1.2
5 AIR GAP TO BE TWICE THE EFFECTIVE OPENING OF
THE INDIRECT WASTE PIPE.
6 REFER TO DETAIL 2/P1.1.1 FOR TYPICAL HUB DRAIN
INSTALLATION.
7 2" VTR. MAINTAIN 10'-0" FROM ALL OUTDOOR AIR
INTAKES.
8 ROUTE PIPING IN CHASE PROVIDED.
9 PROVIDE SAMPLING PORT WITH YCO AT GRADE PER
AHJ.
10 WATER DISPENSER IS EQUIPPED WITH A PUMPED
DRAIN. ROUTE 1/2" PUMPED DRAIN PIPING TO NEAREST
FLOOR SINK AND DISCHARGE WITH AN AIR GAP.
ROUTE PIPING CONCEALED IF ROUTED WITHIN
CUSTOMER AREA.
N.T.S.
2 HUB DRAIN DETAIL
SLOPE MINIMUM 1/8" PER FOOT
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
A
A
B
B
22
11
WALK-IN FREEZER STORAGE ROOM
COLD VAULT
WALK-IN COOLER
SALES FLOOR 1
SALES FLOOR 2
HALLWAY
MEN'S
RESTROOM
WOMEN'S
RESTROOM
BACK ROOM
CASHIER
1
P204
1" HW
3/4" HWR
1" HW
1" CW
1" HW
3/4" HWR
3/4" CW
2" CW
1" HW
1" HW
1/2" CW
1" CW
3/4" HW
P410
P410
3/4" CW
1/2" FDW
1/2" FW
2
B003
TYP
2
B301
TYP
2
C001
TYP
3
3
4
5P101
P101P101
P108
P108 P108
P108
P401
P201
P203
P001
P103
P103
P101
1
P1.3
4
P1.3
2
P1.3
3/4" HW
3/4" HW
P413
1/2" CW
6
P402
B603
TYP
5
2" MAIN DOMESTIC WATER
SERVICE FROM 2" METER AND
REDUCED PRESSURE
BACKFLOW PREVENTER. SEE
CIVIL PLAN FOR CONTINUATION.
7
8
WHA
H201
9
M102
B102
P101P101
TYP
2
P204
P414
C004
C005
C202
C002
B001
TYP
3
B101
TYP
2
1/2" FW
10FUTURE
CONNECTION
PREP AREA
11
SALES FLOOR 3
12
GENERAL NOTES
IF POST MIX IS INSTALLED A STAINLESS R.P.B.A. MUST BE
USED OR WILKINS 375X1 WITH NO COPPER INSTALLED
DOWNSTREAM OF R.P.B.A.
PLUMBING SYMBOLS
WALL CLEANOUT
HOSE BIBB
FREEZE PROOF WALL HYDRANT
YARD CLEANOUT
FLOOR SINK
ROOF DRAIN/OVERFLOW ROOF DRAIN
FLOOR DRAIN
T & P RELIEF VALVE
WATER HAMMER ARRESTOR
BACKFLOW PREVENTER
SHUT-OFF VALVE IN VERTICAL LINE
CHECK VALVE
PLUG VALVE
BALL VALVE
TEE - TURNED UP
TEE - TURNED DOWN
ELBOW - TURNED UP
ELBOW - TURNED DOWN
COMPRESSED AIR
NATURAL GAS
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER
OVERFLOW ROOF DRAIN LINE
ROOF DRAIN LINE
OIL WASTE
GREASE WASTE
SANITARY SEWER
110°F TEMPERED WATER
WATER METER
FILTERED WATER
STORM SEWER
IRRIGATION WATER
THERMOSTATIC MIXING VALVE
GAS COCK
GAS PRESSURE REGULATOR
PLUMBING VENT
REVERSE OSMOSIS WATER
CONDENSATE DRAIN
CONNECT TO EXISTING
EXISTING TO REMAIN
PLUMBING VACUUM
DEMO PIPE
AREA OF SLAB CUT
FLOW CONTROL VALVE
THERMOMETER
SS
GW
OW
ST
RD
ORD
IW
T
UNION
FW
G
A
CD
RO
V
VAC
M
WHA
TMV
FD
FS
YCO
FPWH
HB
WCO
ETR
RD
VENT BELOW FLOORVBF
FLOOR CLEANOUTFCO
?KEYNOTE CALLOUT SYMBOL
(? = NUMBER)
?PLUMBING FIXTURE CALLOUT SYMBOL
EF 1 MECHANICAL EQUIPMENT CALLOUT FOR
PLUMBING REFERENCE LOCATION
FILTERED + DESCALED WATERFDW
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.1.2
PROJECT NUMBER: 24212
PLUMBING
FLOOR
PLAN-DOMESTIC
WATER
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
3/16" = 1'-0"
1 PLUMBING FLOOR PLAN HOT AND COLD WATER
KEYNOTES
1 MAIN WATER SUPPLY LINE UP IN WALL TO ABOVE
CEILING. COORDINATE EXACT LOCATION.
2 1-1/2" CW TO WATER FILTER (OR SIZE AS REQUIRED BY
EQUIPMENT SUPPLIER). PROVIDE ACCESSIBLE
BACKFLOW PREVENTER AS REQUIRED BY A.H.J.
COORDINATE REQUIREMENTS WITH EQUIPMENT
SUPPLIER.
3 SHUT-OFF (BALL VALVE) ABOVE CEILING. PROVIDE
ACCESS (TYPICAL).
4 3/4" CW DOWN IN WALL/EXPOSED TO FREEZELESS HB.
5 CO2 LINE TO RUN UP WALL THEN OVERHEAD TO
CONNECT TO CARBONATORS. INSTALL PER
MANUFACTURERS' INSTALLATION INSTRUCTIONS.
6 ROUTE PIPING IN CHASE PROVIDED.
7 3/4" CW UP THROUGH ROOF TO FREEZELESS ROOF
HYDRANT.
8 PROVIDE TRAP PRIMER FOR FLOOR DRAIN, CONNECT
WITH NEAREST COLD WATER LINE.
9 FILTERED AND DESCALED WATER LINE ABOVE CEILING.
10 FILTERED WATER ABOVE CEILING.
11 HOSE BIBB ROUTED ABOVE CEILING AND DOWN
INTERIOR WALL THEN TURN OUT.
12 PROVIDE NORMALLY CLOSED BYPASS LINE WITH VALVES.
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
P403
P403
P403
P403
P404
P404
P404
P403
P204
P204
P403
P403
P201
P203
P404
P101
P101
P106
P106
P106
P106
P101
P405
P405
1 1/2" V3" VTR
3" VTR
3" VTR
P405 P405
3" SS
4" SS
4" SS
1 1/2" V
4" SS
4" SS
4" GW
4" GW
1 1/2" V
1 1/2" V
2" V
1 1/2" V
P412
3" V
H201
P103
P103
P101
2" V
WCO
3" SS
P413
3" SS
P001
WCO
2" V
YCO
YCO2" V
WCO
M102
WCO
YCO
TYP
6
4" GW
P101
P101
P204
P204
P201
P001
P203
P101
P101
P108
P108
P108
P108
P101
P410
P417
C001
TYP
3
B001
TYP
3
B003
TYP
2
B301
TYP
2
P401
P400
P410
1" HW
1" HW
1/2" CW
2" CW
2" CW
3/4" HWR
3/4" HW
1/2" CW
1" HW
2" CW
1" HW
1" CW
1" CW
1 1/2" CW
3/4" FDW
H201
3/4" CW
3/4" CW
P103
P103
3/4" CW
END CAP FOR FUTURE
CONNECTION TYP
END CAP FOR FUTURE
CONNECTION TYP
1/2" FW
1/2" FW
1/2" FDW
P406
2" CW
P413
1/2" CW
P418
TYP
P409
B101
TYP
2
B102
1/2" FDW
1/2" FDW
P402
WHA
P101
1" CW
P418
TYP
2
1
P1.3
P101
P101
1" HW
P414
1/2" FW
M102
C004
C005
C202
C002
3/4" CW
YELM, WA
48 PSI
110.9 (PREDOMINANTLY FLUSH VALVES) PER 2021 WPC
85.5
2" (VERIFY WITH WATER COMPANY)
48.0 PSI (PRESSURE IN MAIN)
-8.3 PSI (LOSS THROUGH 2" METER)
-2 PSI (LOSS THROUGH TAP)
-25 PSI (FIXTURE LOSS AT END, FLUSH VALVE)
-7 PSI (14 DROP FOR ELEVATION, 0.5 PSI LOSS PER FT)
-12 PSI (BACKFLOW PREVENTER)
22.9 PSI (BOOSTER PUMP)
16.6 PSI (AVAILABLE PRESSURE)
PIPE LENGTH (TAP TO METER) 38 FT
PIPE LENGTH (METER TO BUILDING)196 FT
PIPE LENGTH (BUILDING TO LAST FIXTURE)119 FT
VERTICAL LENGTH 20 FT
EQUIVALENT LENGTH OF FITTINGS 42 FT
TOTAL DEVELOPED LENGTH 415 FT
PRESSURE AVAILABLE 16.6 X 100 = 4.0 PSI/100 FT
TOTAL LENGTH 415
SITE LOCATION:
STATIC PRESSURE:
TOTAL WATER SUPPLY
FIXTURE UNIT:
GPM:
WATER MAIN:
MAX ALLOWABLE LOSS
(PER 100 FT OF PIPE):
A PRESSURE TEST IS TO BE PERFORMED IMMEDIATELY AFTER AWARDING OF BID. IF PRESSURE IS
LOWER THAN LISTED ABOVE, NOTIFY ENGINEER IMMEDIATELY.
1. PROVIDE IAPMO APPROVED BACKFLOW PREVENTER IN-
LINE TO EACH "NON-CARBONATED" KITCHEN
BEVERAGES EQUIPMENT.
2. PROVIDE IAPMO APPROVED REDUCED PRESSURE
BACKFLOW PREVENTER TO EACH "CARBONATED"
KITCHEN BEVERAGES EQUIPMENT (STAINLESS STEEL)
3. BEVERAGES LINES OF "CARBONATORS" SHALL NOT
HAVE ANY COPPER LINES DOWNSTREAM OF REDUCED
PRESSURE BACKFLOW PREVENTER.
4. BACKFLOW PREVENTERS SHALL HAVE PROPER DRAINS
AND ACCESSIBLE FOR MAINTENANCE.
NOTES:
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.2
PROJECT NUMBER: 24212
PLUMBING
RISERS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
N.T.S.
1 WASTE AND VENT PLUMBING RISER
N.T.S.
2 HOT AND COLD WATER RISER
GREASE INTERCEPTOR FIXTURES
TAG DESCRIPTION
DRAINAGE
PER COUNT
DRAINAGE
TOTAL (DFU)
P001 3-COMPARTMENT SINK W/ (2) 18" DRAIN
BOARDS
3 1 3
P201 MOP SERVICE SINK 3 1 3
P203 WALL MOUNTED HAND SINK 2 1 2
P403 FLOOR SINK 0.5 1 0.5
P404 FLOOR DRAIN WITH TRAP PRIMER 0 1 0
Grand total 5 8.5
PLUMBING LOADS
TAG DESCRIPTION CWFU HWFU
DRAINAGE
PER (DFU)COUNT
CW TOTAL
(CWFU)
HW TOTAL
(HWFU)
DRAINAGE
TOTAL (DFU)
TOTAL
WATER
(WSFU)
TOTAL
WATER
GPM
P001 3-COMPARTMENT SINK W/ (2) 18" DRAIN
BOARDS
3 3 3 1 3 3 3 6 3
P101 TOILET 10 0 10 6 60 0 60 60 30
P103 URINAL 10 0 4 2 20 0 8 20 10
P106 DROP-IN HAND SINK 0 0 3 4 0 0 12 0 0
P108 HAND SINK FAUCET - AUTOMATIC 2.25 2.25 0 4 9 9 0 18 9
P201 MOP SERVICE SINK 3 3 3 1 3 3 3 6 3
P203 WALL MOUNTED HAND SINK 2.25 2.25 2 1 2.25 2.25 2 4.5 2.25
P204 DROP-IN HAND SINK 2.25 2.25 3 2 4.5 4.5 6 9 4.5
P205 MANUAL SINK FAUCET 2.25 2.25 3 2 4.5 4.5 6 9 4.5
P402 WATER FILTER 1 0 0 0 0 0
P403 FLOOR SINK 0.5 7 0 0 3.5 0 0
P404 FLOOR DRAIN WITH TRAP PRIMER 0 0 0 4 0 0 0 0 0
P410 ENCASED NON-FREEZE HOSE BIB 1 0 0 2 2 0 0 2 1
P413 DRINKING FOUNTAIN 0.25 0 0.25 1 0.25 0 0.25 0.25 0.125
P417 FREEZELESS ROOF HYDRANT 1 0 0 1 1 0 0 1 0.5
Grand total 39 109.5 26.25 103.75 135.75 67.875
N.T.S.
3 WATER SUPPLY CALCULATION
P001 HAS 2 MINUTE DRAIN TIME
P403 ONLY RECIVES WASTE FROM P001
P404 IS EMERGENCY USE ONLY
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
85.5
1000 GAL GRAVITY GREASE
INTERCEPTOR TO BE USED.
8.5 DFU'S REQUIRES A 750
MIN GAL GRAVITY GREASE
INTERCEPTOR -WPC TABLE
1014.3.6
~
~
~~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
UNION
1/2"CW TUBING
SEAL WATERTIGHT
1/2"CW BELOW
FLOOR
STUD WALL
1/2"CW
1/2"CW TO TRAP,
CONNECT AS REQ'D.
FLOOR DRAIN
FINISHED FLOOR
STEEL ACCESS PANEL
LAVATORY
PROVIDE WITH
TRAP COVER
18
"
M
I
N
.
CONFIRM
LOCATION OF
DRAIN PIPE WHEN
AT SIP WALL.
B001
B001
B003
B003
B101
B102
C001
C001
C001
C004
C005
C002
P406
P406
H201
M102
WATER FILTER
ITEM # 52
3/4"
3/4"
3/4"
NO
NC
NO - NORMALLY OPEN
NC - NORMALLY CLOSED
NO
ROUTE FW LINES IN
CEILING
SPACE OVER TO
EQUIPMENT
ROUTE FW LINES IN CEILING
SPACE OVER TO
EQUIPMENT
FOUNTAIN
OUTLET 3/4"
FNPT
FILTERED + DESCALED
FILTERED ONLY
TYP
TYP
B001
CARBONATOR
INCLUDES BUILT-IN
ASSE 1022 BACKFLOW
PREVENTER
NO
B301
B301
B101
C202
BRASS CLEANOUT PLUG
W/COUNTER SUNK HEAD
6"
PVC WASTE
LINE
WASTE LINE
FINISHED GRADE 16"∅CONCRETE PAD
TROWEL SMOOTH & EDGE
WASTE LINE
3/4" T&P AND 1" DRAIN
FROM DRAIN PAN TO
MOP SINK
1-1/4" COLD WATER FEED
W/ VACUUM RELIEF VALVE
P400
INSTALL EWH IN GALV.
PAN 24 GAGE & 1-1/2"
MIN. RUN INDIRECT
DRAIN TO MOP SINK
ASME TEMPERATURE
AND PRESSURE
RELIEF VALVE.
3/4"
RECIRC
PUMP
1 1/4"
INSTALL MINIMUM 1"
INSULATION ON ALL HOT
WATER PIPING AND THE
FIRST 8' OF COLD WATER
PIPING AT THE TANK.
REFER TO DETAIL 1 ON A9.2. IN THE ARCHITECTURAL DWG. FOR WATER HEATER SHELF DETAIL.
REFER TO 1/A9.2 FOR
HOT WATER SUPPORT
AND WALL
CONSTRUCTION.
CHECK VALVE TYP
140° F.
1 1/4"
UNION TYP
PROVIDE BALANCING
VALVE SET TO 3 GPM
A. SLOPE SANITARY PIPING 2 1/2" AND SMALLER AND ALL GREASE WASTE PIPING AT 1/4"
PER FOOT FALL. SLOPE SANITARY SEWER PIPING 3" TO 6" AT 1/8" PER FOOT FALL.
COORDINATE BUILDING SEWER LOCATION AND INVERT ELEVATION WITH CIVIL
DRAWINGS.
B. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT, FEES, PERMITS, CERTIFICATE OF
INSPECTION, ETC. NECESSARY OR REASONABLE, REQUIRED FOR THE COMPLETE
INSTALLATION OF ALL PLUMBING WORK.
C. WORK SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL CODES, LAWS, ACTS,
ORDINANCES, REGULATIONS AND REQUIREMENTS OF AUTHORITIES HAVING
JURISDICTION.
D. THE COMPLETED INSTALLATION SHALL BE IN ACCORDANCE WITH ALL THE APPLICABLE
INDUSTRY STANDARDS OF GOOD PRACTICE, SAFETY, AND THE MANUFACTURERS
STRICTEST RECOMMENDATIONS FOR EQUIPMENT AND PRODUCT APPLICATION AND
INSTALLATION.
E. THESE DRAWINGS ARE DIAGRAMMATIC ONLY. CONTRACTOR SHALL MAKE
MODIFICATIONS INCLUDING OFFSETS, TURNS, AND RE-ROUTING REQUIRED TO
COMPLETE THE INSTALLATION. DO NOT SCALE LOCATION OF EQUIPMENT OR PIPING.
F. COORDINATE ALL PLUMBING WORK, INCLUDING EQUIPMENT AND PIPING, WITH OTHER
TRADES PRIOR TO WORK.
G. CONTRACTOR TO VERIFY LOCATION OF ALL EXISTING EQUIPMENT SO THAT NO
INTERFERENCES ARE ENCOUNTERED WITH OTHER EQUIPMENT OR WITH STRUCTURAL
ELEMENTS.
H. ALL PLUMBING WORK IS TO RUN IN A NEAT AND PROFESSIONAL MANNER, WITH THE
AESTHETICS OF THE FACILITY OF PARAMOUNT IMPORTANCE. ALL ROUGH-IN WORK TO
BE HIDDEN WITHIN WALLS AND ABOVE CEILING UNLESS OTHERWISE NOTED.
I. ALL WORK SHALL BE LOCATED TO AVOID CONFLICTS WITH OTHER TRADES. CLOSELY
COORDINATE ALL WORK WITH ALL OTHER TRADES. FAILURE OF THE CONTRACTOR TO
COORDINATE WITH ALL OTHER TRADES SHALL RELIEVE THE OWNER FROM ANY ADDED
COSTS.
J. THE CONTRACTOR SHALL DO ALL NECESSARY CUTTING OF WALLS AND CEILING. PATCH
AROUND ALL OPENINGS TO MATCH EXISTING CONSTRUCTION. NO STRUCTURAL
MEMBER SHALL BE CUT WITHOUT PERMISSION FROM THE ENGINEER.
K. THESE DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE LOCATIONS OF FIXTURES,
GENERAL NOTES
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.3
PROJECT NUMBER: 24212
PLUMBING-
SCHEDULES AND
DETAILS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
P001 3-COMPARTMENT SINK W/ (2) 18" DRAIN
BOARDS
ADVANCE TABCO 9-3-54-18RL 0" 0" 0" 0" 1 GC TO SUPPLY AND INSTALL SINK
P101 TOILET AMERICAN
STANDARD
3043.001 1" 4" 6 VALVE, SLOAN 111 ESS-1.25-TMO-HW - WATER CONSERVATION 1.28
GALLONS PER FLUSH. OPEN FRONT SEAT - OLSONITE #10CC.
P103 URINAL AMERICAN
STANDARD
6590.001 3/4" 2" 2 URINAL FLUSH VALVE SLONE 186-ESS-0.5-TMO-HW AUTOMATIC HARD
WIRED. WALL BRACKET SUPPORT SET AT ELEV. TO MEET ADA
P106 DROP-IN HAND SINK ROYSTON INTEGRATED 3/8" 3/8" 0" 1 1/4" 4 SLOAN#SF2400. PROVIDE WITH F FLOW CONTROL. PROVIDE WITH TRAP
COVER - TRUEBRO MODEL# 100 E-Z OR EQUAL CHROME STOPS 1/4
TURN, SUPPLIES INSUL SUPPLIES & TRAP PER ADA PROVIDE P408.
P108 HAND SINK FAUCET - AUTOMATIC SLOAN SF-2400 3/8" 3/8" 0" 0" 4 HARDWIRED; FULL MODEL NUMBER
SF-2400-4-PLG-TEE-CP-0.5GPM-MLM-IR-FCT PROVIDE P408.
P201 MOP SERVICE SINK MUSTEE 63M 3/4" 3/4" 0" 3" 1 AMERICAN STANDARD #8344.111 WALL MOUNT FAUCET TOP BRACE,
VACUUM BREAKER, STOPS
P203 WALL MOUNTED HAND SINK ADVANCE TABCO 7-PS-60 1/2" 1/2" 0" 1 1/2" 1 PROVIDE P408.
P204 DROP-IN HAND SINK ELKAY OR EQUAL K11515 3/8" 3/8" 0"2" 2 FAUCET BY G.C. CHROME STOPS 1/4 TURN SUPPLIES AND P-TRAP
PROVIDE P408.
P205 MANUAL SINK FAUCET CHICAGO
FAUCETS
895-317CP 3/8" 3/8" 0" 2" 2 FOR USE WITH P204.
P400 FIXED BLADDER TYPE EXPANSION
TANK.
AMTROL
FLEXCON
WATTS
WILKINS
ST-12
WH-18
PLT-12
XT-18
1 1/4" 0" 0" 0" 1 4.4 GALLON MINIMUM TOTAL CAPACITY, FACTORY STANDARD
PRECHARGE CAPACITY.
P401 ELECTRIC WATER HEATER A.O. SMITH DRE-52-24 1 1/4" 1 1/4" 1 3/4" P & T RELIEF VALVE. 52 GAL STORAGE. ELECTRICAL, 24 KW, 208V,
3PH.
P402 WATER FILTER PENTAIR
EVERPURE
EV9437-10 3/4" 0" 0" 3/4" 1 3/4" NPT CONNECTION, PROVIDED BY FACILITIES
P403 FLOOR SINK ZURN Z1901 7 1/2 GRATE WITH 12"X12" (6" DEEP) PORCELAIN SEDIMENT BUCKET
P404 FLOOR DRAIN WITH TRAP PRIMER WADE 1000-S-TD6.1 4 SATIN STRAINER
P405 FLOOR CLEANOUT J.R. SMITH 4100 SERIES 4 ADJUSTABLE FLOOR CLEANOUT, 5 IN ROUND NICKEL BRONZE TOP, 4 IN
PIPE, GAS TIGHT GASKETED BRASS PLUG, NO HUB OUTLET, MD LOAD
RATING.
P406 DUAL CHECK VALVE ATMOSPHERIC
PORT & STRAINER
WATTS SD-3 3/8" 0" 0" 0" 15 STAINLESS STEEL BODY CONSTRUCTION WITH INTERNAL RUBBER
COMPONENTS AND IS DESIGNED FOR CONTINUOUS OR INTERMITTENT
PRESSURE APPLICATIONS. WITH A WYE PATTERN STRAINER. MAXIMUM
WORKING PRESSURE: 150PSI (10 BAR)
P408 LEAD-FREE THERMOSTATIC MIXING
VALVE
ZURN WILKINS ZW3870XLT 7 3/8" COMPRESSION CONNECTIONS, CHROME PLATED ASSE 1070 SET TO
110°F
P409 RECIRCULATION PUMP TACO 003-BC4 3/4" 0" 0" 0" 1 HP: 1/40 - CONNECTION SIZES: 3/4” SWEAT
P410 ENCASED NON-FREEZE HOSE BIB MIFAB MHY-20 3/4" 0" 0" 0" 2 ANTI-SIPHON VACUUM BREAKER PROTECTED. VANDAL RESISTANT
VACUUM BREAKER.
P412 1000 GALLON GREASE INTERCEPTOR. JENSEN PRECAST JP1000EE-G 1 OR EQUIVALENT MAKE/MODEL. INTERCEPTOR DESIGN AND
INSTALLATION SHALL COMPLY WITH LOCAL AHJ REQUIREMENTS.
PROVIDE SAMPLING PORT AS REQUIRED BY AHJ. PROVIDE WITH H20
TRAFFIC RATED INSTALLATION.
P413 DRINKING FOUNTAIN OASIS PG8ACSLTM 3/8" 0" 1/2" 1 1/4"1
P414 WATER PRESSURE BOOSTER PUMP XYLEM 2AB310HME02 1 1/4" 0" 1 INTEGRATED VARIABLE SPEED CONSTANT PRESSURE SYSTEM. INSTALL
PER MANUFACTURER'S RECOMMENDATIONS. 2HP VARIABLE SPEED
CONTROLLER, PUMP, AND TANK INCLUDED.
P417 FREEZELESS ROOF HYDRANT WOODFORD RHY2-MS 3/4" 0" 0" 0" 1 PROVIDE MOUNTING SYSTEM AND DRAIN. ROUTE 1/8" DRAIN LINE TO
NEAREST APPROVED DRAIN WITH AIR GAP. HYDRANT TO BE PROVIDED
WITH A DOUBLE CHECK BACKFLOW PREVENTER.
P418 TRAP PRIMER SIOUX CHIEF SERIES 695 1/2" 0" 0" 0" 4 OR APPROVED EQUIVALENT. AMOUNTS AS REQUIRED
PLUMBING FIXTURE SCHEDULE
TAG DESCRIPTION MFG. MODEL
ROUGH-IN SIZE
COUNT TRIM/REMARKSCW HW FW SAN
B001 FOUNTAIN DRINK DISPENSER CORNELIUS ED-300 0" 0" 1/2"3/4" 3
B003 ICED TEA BREWER WILBURT CURTIS RSTB 0" 0" 1/4" 0" 2
B101 ICE MAKER FOLLETT HCD1810RHT 0" 0" 3/8" 3/4" 2 19" FOLLETT REMOTE CHEWBLET
B102 1 FOUNTAIN AND/OR BAGGER MANITOWOC IYF-1800C-161 0" 0" 3/8" 3/4" 1 30" MANITOWOC REMOTE ICE MAKER (1825LB)
B301 FOUR BARREL COUNTERTOP FCB CORNELIUS VIPER ELITE-4B 0" 0" 1/2" 0" 2
B603 3 WIDE BIB RACK PACKAGE CORNELIUS 3BIFJ 0" 0" 0" 0" 5
C001 3-HOPPER BEAN TO CUP BREWER SCHAERER 040381-00058 EUS 0" 0" 3/8" 0" 3
C002 5-HD CAPPUCCINO WILBURT CURTIS PCGT5 0" 0" 1/4" 0" 1
C004 COLD DRAFT COFFEE DISPENSER BUNN NITRON COLD DRAFT
C-TOP 4:1=12:1 WITH
REMOVABLE DOOR
GRAPHIC
0" 0" 3/8" 0" 1
C005 COLD BREW COFFEE DISPENSER BUNN NITRON COLD DRAFT
ALL-NITRO W RDG &
NGM
0" 0" 3/8" 0" 1
C202 ICE AND WATER DISPENSER FOLLETT 15CI100A-NW-NF-ST-00 -
15 SERIES CHEWBLET
ICE MACHINE AND
WATER
DISPENSER
0" 0" 1/4" 0" 1
H201 ELECTRIC COMBI OVEN UNOX XAVC-0511-EPR 0" 0" 3/4" 1 1/4" 1 OVEN REQUIRES FILTERED AND DESCALED WATER.
HD PVC HUB DRAIN --- ---7 SIZING PER P1.1.1
N.T.S.
1 TRAP PRIMER ASSEMBLY
N.T.S.
2 EVERPURE WATER FILTER SYSTEM
N.T.S.
3 2-WAY CLEANOUT DIAGRAM
N.T.S.
4 WALL MOUNTED WATER HEATER
M102 WATER DISPENSER GLACIER G21B 0" 0" 1/2" 0" 1 (1) 1/2" WATER LINE PER (3) MACHINES 15 PSI MINIMUM. EACH UNIT TO
HAVE DEDICATED BALL VALVE SHUTOFF. INDIRECT DRAIN.
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST
1. ALL WORK TO BE DONE AND MATERIALS FURNISHED COMPLYING WITH APPLICABLE
LAWS AND REGULATIONS, INCLUDING THE STATE OF WASHINGTON MECHANICAL,
PLUMBING AND FIRE SAFETY CODES. OBTAIN AND PAY FOR REQUIRED PERMITS AND
FEES.
2. ALL MATERIALS USED SHALL BE NEW AND UNDAMAGED.
3. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH CURRENT CONSTRUCTION
INDUSTRY STANDARDS AND WORKMANSHIP.
4. FURNISH SHOP DRAWINGS TO ARCH/ENGINEER FOR APPROVAL PRIOR TO PLACING
DELIVERY ORDERS. PROVIDE SHOP DRAWINGS OF ALL MANUFACTURED EQUIPMENT
AND MATERIALS EXCEPT PIPE, PIPE FITTINGS AND GALVANIZED DUCTWORK.
5. FURNISH ACCESS DOORS (RATED OR NON-RATED AS REQUIRED) WHERE VALVES OR
EQUIPMENT ARE CONCEALED BEHIND A NON ACCESSIBLE CEILING OR WALL. FURNISH
ACCESS DOORS TO GENERAL CONTRACTOR FOR INSTALLATION.
6. FURNISH STEEL PIPE SLEEVES WHERE PIPES PENETRATE RATED WALLS. PROVIDE
FIRESTOPPING MATERIALS AND SYSTEM TO MAINTAIN THE REQUIRED RATING OF THE
WALL PENETRATED. PROVIDE SHOP DRAWINGS SHOWING LISTING AND RATING OF
FIRESTOPPING MATERIALS.
7. ALL MANUFACTURED EQUIPMENT, ACCESSORIES AND MATERIALS SHALL BE USED AS
INTENDED BY THE MANUFACTURER IN STRICT ACCORDANCE W ITH THE
MANUFACTURER'S WRITTEN INSTALLATION, OPERATI0N AND MAINTENANCE
INSTRUCTIONS.
8. CONTRACTOR SHALL PROVIDE IN ADDITION TO ANY OTHER WARRANTIES SPECIFIED, A
ONE YEAR FULL LABOR AND MATERIAL WARRANTY ON ALL WORKMANSHIP, MATERIAL
AND EQUIPMENT FURNISHED FOR THIS PROJECT.
9. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL OPENINGS AND
REQUIRED LINTELS NEEDED FOR THE GENERAL CONTRACTOR FOR THE INSTALLATION
OF MECHANICAL EQUIPMENT.
10. SAWCUTS, LINTELS, HEADERS, AND STRUCTURAL MODIFICATIONS TO THE BUILDING
STRUCTURE NEEDED FOR THE INSTALLATION OF MECHANICAL EQUIPMENT SHALL BE
APPROVED BY THE GENERAL CONTRACTOR, BEFORE INSTALLATION.
11. IN GENERAL, OPENINGS AND REQUIRED LINTELS SHALL BE PROVIDED BY THE GENERAL
CONTRACTOR. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR PROVIDING DETAILS
AND TEMPLATES OF ALL OPENINGS NECESSARY FOR MECHANICAL EQUIPMENT
INSTALLATION INCLUDING: HOUSING, ACCESS DOORS, INSPECTION DOORS, AND
PASSAGEWAYS FOR MECHANICAL EQUIPMENT. THE PLUMBING CONTRACTOR IS
RESPONSIBLE FOR SEALING CRACKS AND FINISHING ROUGH EDGES LEFT FOLLOWING
MECHANICAL INSTALLATION.
12. APPROVAL EQUALS: PLUMBING ITEMS MANUFACTURED BY A COMPANY OTHER THAN
THAT WHICH WAS SPECIFIED IN THE SCHEDULE MAY BE SUBSTITUDED BY APPROVED
SHOP DRAWINGS CONTIGENT UPON MEETING THE DESIGN, APPEARANCE, AND
FUNCTIONAL STANDARDS ESTABLISHED BY THE ORIGINALLY SPECIFIED ITEM(S). THE
PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING DIMENSIONS,
CLEARANCES, ASSEMBLY, FIT, ETC. OF THE APPROVED EQUAL(S), AND THEIR AFFECT
ON OTHER EQUIPMENT FIT AND OPERATION. THE CONTRACTOR IS LIABLE FOR ANY
ADDED COSTS TO HIMSELF OR OTHERS CAUSED BY THE APPROVED EQUALS.
PLUMBING SPECIFICATIONSSECTION
15010
BASIC MECHANICAL
REQUIREMENTS
1. BALL VALVES SHALL BE CLASS 125 FOR WATER WITH ENDS AND MATERIALS TO MATCH
PIPING SYSTEMS.
2. BALL VALVES 2" AND SMALLER SHALL HAVE BRONZE BODY, STAINLESS STEEL BALL,
TEFLON SEATS, AND STUFFING BOX RING, LEVER HANDLE AND BALANCING STOPS,
ENDS TO MATCH PIPING SYSTEM.
PLUMBING SPECIFICATIONSSECTION
15100
VALVES
1. FURNISH PIPE AND DUCT HANGERS, WHERE REQUIRED, FIRMLY SUPPORTED FROM
BUILDING STEEL, CONCRETE OR MASONRY STRUCTURE. SUPPORT PIPING SYSTEMES
SECURELY WHILE ALLOWING FOR PIPE AND BUILDING EXPANSION AND CONTRACTION.
PROVIDE COPPER PLATED HANGERS, FOR COPPER PIPE. USE ADJUSTABLE CLEVIS
HANGERS OR ADJUSTABLE STEEL BAND HANGERS. MAXIMUM SPACING SHALL BE 5' FOR
1/2" PIPING, 7' FOR 3/4" TO 1/4" PIPING, 9' FOR 1-1/2" TO 2" PIPING. FURNISH PLUMBING
EQUIPMENT SUPPORTS AS DETAILED OR AS REQUIRED TO SAFELY AND PERMANENTLY
CARRY THE WEIGHT OF THE EQUIPMENT.
15140
SUPPORTS &
ANCHORS
1. INSULATE ABOVE FLOOR WATER PIPING WITH ELASTOMERIC PLACTIC PERFORMED PIPE
INSULATION WITHOUT JACKETING. ALL INSULATING MATERIALS TO HAVE FLAME SPREAD
RATING OF 25 OR LESS AND SMOKE DEVELOPMENT RATING O F 50 OR LESS AS TESTED
BY ANSI/ASTM E 84 (NFPA 233) METHOD. INSULATE ALL PIPING WITH SURFACE
TEMPERATURES BELOW 75 DEGREE F WITH 1/2" INSULATION. INSULATE ALL PIPING WITH
SURFACE TEMPERATURES 75 DEGREES F AND HIGHER WITH 1" THICK INSULATION.
INSTALL MINIMUM 1" INSULATION ON ALL HOT WATER PIPING AND THE FIRST 8' OF COLD
WATER PIPING AT THE TANK. JOINTS IN INSULATION SHALL BE GLUED, NOT TAPED.
WHERE PIPES ARE EXPOSED AND LESS THAN 8' ABOVE FLOOR, PROVIDE HEAVY DUTY
METAL JACKETING OVER INSULATION. INSULATE ABOVE FLO OR HORIZONTAL STORM
PIPING WITH 1" FIBERGLASS PERFORMED PIPE INSULATION WITH FACTORY APPLIED ALL
PURPOSE COVER.
15250
PLUMBING
INSULATION
15411
WATER
DISTRIBUTION
1. WITHIN BUILDING, SCHEDULE 40 PVC, DWV TYPE PIPE AND SOLVENT WELDED PIPE
FITTINGS, SCHEDULE 30 PVC PIPE MAY BE USED FOR VENT PIPING WHERE PERMITTED
BY CODE. HORIZONTAL PIPE SHALL BE SUPPORTED BY ADJUSTABLE RING HANGERS
EQUAL TO ITT-GRINNEL FIG. 97. VERTICAL PIPING SHALL BE SUPPORTED AT EACH FLOOR
OR ATTIC LEVEL BY RISER. INSTALL UNDERGROUND PVC PIPE ACCORDING TO ASTM
D2321.
15420
DRAINAGE & VENT
SYSTEMS
1. PROVIDE AIR CHAMBERS AT EACH FIXTURE CONNECTION. AIR CHAMBERS SHALL BE
ONE SIZE LARGER THAN SUPPLY PIPE AND SHALL BE 12" LONG. WHERE REQUIRED BY
PLUMBING CODE, FURNISH AND INSTALL MANUFACTURED WATER HAMMER
ARRESTORS.
2. PLUMBING FIXTURES SHALL BE INSTALLED WHERE SHOWN ON THE ARCHITECTURAL
DRAWINGS. INSTALL FIXTURES LEVEL AND PLUMB. FURNISH TRAPS WHERE REQUIRED.
FIXTURES SHALL BE EASILY REMOVABLE FOR SERVICE AND CLEANING.
3. PROVIDE CHROME PLATED RIGID OR FLEXIBLE SUPPLIES TO FIXTURES WITH STOP
VALVES, CHROME PLATED 17 GAUGE BRASS TRAPS WITH CHROME PLATED
ESCUTCHEONS.
4. SEAL ALL FIXTURES TO WALL AND FLOOR USING SILICO NE SEALANT. MATCH SEALANT
COLOR TO FIXTURE COLOR.
5. FIXTURES DESIGNATED BARRIER FREE SHALL BE INSTALLED IN COMPLIANCE WITH
AMERICAN'S WITH DISABILITIES ACT.
6. ALL CLEANOUT COVERS TO BE STAINLESS STEEL.
15440
PLUMBING
1. ABOVE GRADE: WATER PIPING SHALL BE CROSSLINKED PE (PEX) TUBING: PEX TUBE
SHALL BE TESTED AND CERTIFIED FOR POTABLE WATER SYSTEMS, AND SHALL COMPLY
WITH ANSI/NSF STANDARD 14, ANSI/NSF STANDARD 61, AND ASTM F876 AND/OR ASTM
F877. TUBE SHALL BE LABELED WITH THE ABOVE CERTIFICATIONS. PROVIDE PEX TUBING
SYSTEM BY ONE OF THE FOLLOWING: UPONOR, OR APPROVED PEX ALTERNATIVE.
FITTINGS AND CONNECTORS SHALL BE BY THE SAME MANUFACTURER AND ASSEMBLED
WITH THE MANUFACTURER’S APPROVED TOOLS. THE SAME CO NNECTION METHOD
SHALL BE USED THROUGHOUT THE INSTALLATION.
a. AT CONTRACTOR’S OPTION, IN LIEU OF PEX PIPING SYSTEM AS SPECIFIED ABOVE
TYPE L COPPER ASTM B 75, ASTM B 88, ASTM 251, ASTM B 447 WITH WROUGHT
COPPER SOLDER-JOINT FITTINGS ASME B 16.
2. BELOW GRADE: WATER PIPING SHALL BE PEX PIPING SYSTEM IN COMPLIANCE WITH THE
UPONOR PLUMBING DESIGN ASSISTANCE MANUAL (PDAM), CURRENT EDITION AND THE
UPONOR PIPING SYSTEMS INSTALLATION GUIDE, CURRENT EDITION (OR APPROVED
ALTERNATIVE). CROSSLINKED PE (PEX) TUBING, ASTM F876 WITHOUT JOINTS BENEATH
THE SLAB.
a. AT CONTRACTOR’S OPTION, IN LIEU OF PEX PIPING TYPE K COPPER WITH WROUGHT
COPPER SOLDER-JOINT FITTINGS. SOLDER SHALL BE 9596-396 TIN-ANTIMONY
ANSI/ASTM B 32 FOR HEATING SYSTEM PIPING.
3. THOROUGHLY FLUSH AND CLEAN ALL NEW AND EXISTING WATER PIPING SYSTEMS.
TEST ALL PIPING SYSTEMS PER REGULATIONS IN ITEM NO.1 OR AT 225 PSI FOR A
MINIMUM OF 2 HOURS WITH NO PRESSURE DROP INDICATED PRIOR TO INSULATING.
4. STERILIZE ALL DOMESTIC WATER PIPING PRE REQUIREMENTS OF LOCAL HEALTH
DEPARTMENT.
REVISION
ISSUE DATE
COPYRIGHT
This drawings is the property of the above
referenced Professional and is not to be
used for any purpose other than the specific
project and site named herein, and cannot be
reproduced in any manner without the
express written permission from the
professional
CIRCLE K STORE
PROFESSIONAL
PROJECT NAME
PROFESSIONAL IN CHARGE
PROJECT MANAGER
QUALITY CONTROL
DRAWN BY
P1.4
PROJECT NUMBER: 24212
PLUMBING-
SPECIFICATIONS
CIRCLE K
STORES, INC.
9548 KILLION RD SE,
YELM, WA 98597
YELM, WA
DBS
JMS
SAG
JMS
OTP 11/12/24
JOB NO.:
SUITE 5274 479-636-5004
ROGERS, AR 72756 DESIGNED BY: DBS
1805 N 2ND ST