Circle K - Yelm (Yelm & Killion), WA - USTSHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK001 CO V E R S H E E T CIRCLE K STORES, INC. KILLION RD SE & W YELM AVE YELM, WASHINGTON 98597 SYMBOLS LEGENDDESIGN CODES SHEET #SHEET NAME TK001 COVER TK006 EQUIPMENT LIST TK002 GENERAL NOTES TK301 UST PLAN AND SECTIONS TK500 TANK SUMP DETAILS TK102 SCHEMATIC WIRING, PIPING & DETAILS TK504 FUEL SYSTEM DETAILS TK201 STANDARD TANKS API AMERICAN PETROLEUM INSTITUTE N.C. NORMALLY CLOSED & AND NIP NIPPLE @ AT NO. NUMBER A.C. ASPHALT CONCRETE N.O. NORMALLY OPEN APPROX.APPROXIMATE N.T.S. NOT TO SCALE AUX. AUXILIARY N/A NOT APPLICABLE BLU. BLUE O.D. OUTSIDE DIAMETER BLK. BLACK P PRODUCT LINE ℄ CENTERLINE PVC POLYVINYL CHLORIDE COMB. COMBINATION PLC. PLACES CONN. CONNECTOR/CONNECTION ± PLUS OR MINUS CORP. CORPORATION # POUND OR NUMBER CSLD CONTINUOUS STATISTICAL LEAK DETECTION QTY. QUANTITY ø DIAMETER REF. REFERENCE DIM. DIMENSION REQD. REQUIRED D.C. DIRECT CURRENT RSG. RIGID STEEL GALVANIZED DWG. DRAWING SCH. SCHEDULE DBL. DOUBLE SCR'D. SCREWED (E) EXISTING SEC. SECTION ELECT. ELECTRICAL SPEC'S. SPECIFICATIONS E.S.O. EMERGENCY SHUT OFF S.T.P. SUBMERGED TURBINE PUMP EMT ELECTRICAL METALLIC TUBING TYP. TYPICAL ELL ELBOW U.L. UNDERWRITERS LABORATORY EMT ELECTRICAL METALLIC TUBING U.F.C. UNIFORM FIRE CODE FLEX. FLEXIBLE U.G. UNDER GROUND FRP FIBERGLASS REINFORCED PLASTIC U.S.T. UNDERGROUND STORAGE TANKS FNPT FEMALE NATIONAL PIPE THREAD UNL UNLEADED F.G. FIBERGLASS V VAPOR LINE ' FEET VAC VOLT AMP CURRENT ELD ENHANCED LEAK DETECTION VIO. VIOLET GAL. GALLON V.R. VAPOR RECOVERY GALV. GALVANIZED WHT WHITE HEX HEXAGON W/ WITH H.P. HORSEPOWER I.D. INSIDE DIAMETER " INCH J-BOX JUNCTION BOX MAX. MAXIMUM MFRS MANUFACTURERS MNPT MALE NATIONAL PIPE THREADS MIN. MINIMUM NPT NATIONAL PIPE THREAD (N) NEW TK502 TANK TOP HARDWARE DETAILS TK501 TANK SUMP DETAILS TK101 SITE PIPING PLAN TK007 EQUIPMENT LIST TK503 DISPENSER SUMP DETAILS TK503.1 DISPENSER SUMP DETAILS - HSD TK505 FUEL SYSTEM DETAILS ALL CONSTRUCTION SHALL COMPLY WITH: 2018 WASHINGTON STATE BUILDING CODE 2018 WASHING STATE FIRE CODE 2018 WASHINGTON STATE MECHANICAL CODE 2018 WASHINGTON STATE PLUMBING CODE 2020 NEC WITH WASHINGTON STATE AMENDMENTS NFPA 30 NFPA 30A LATEST EDITION OF API RECOMMENDED PRACTICES - 1615 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK002 GE N E R A L N O T E S GENERAL NOTE: A.CONTRACTORS MUST HAVE AT LEAST 5 YEARS EXPERIENCE INSTALLING RETAIL FUEL SYSTEMS AND COMPLY WITH THE FOLLOWING IN ORDER TO BID ON ANY CIRCLE K PROJECT OR BE INVOLVED ON ANY CONSTRUCTION: A.1.AMERON CERTIFICATION A.2.NUPI CERTIFICATION A.3.BRAVO CERTIFICATION A.4.FLEXING CERTIFICATION A.5.EMCO WHEATON CERTIFICATION A.6.GILBARCO/VEEDER-ROOT CERTIFICATION A.7.CONTAINMENT SOLUTIONS/XERXES/MODERN WELDING CERTIFICATION & COMPLY WITH INSTALLATION INSTRUCTIONS A.8.HAZWOPPER & TRENCH EXCAVATION TRAINING B.IT IS REQUIRED THAT ONLY "CERTIFIED INSTALLERS" BE USED FOR INSTALLATION OF THE PIPING SYSTEM TO INSURE THAT PROPER PIPE FABRICATION, COUPLING AND INSTALLATION PERFORMED. "CERTIFIED INSTALLERS" ARE EQUIPPED WITH FACTORY MANUFACTURED COUPLING EQUIPMENT AND INSTALLATION TOOLS AND HAVE RECEIVED FACTORY TRAINING BY AMERON AND NUPI REPRESENTATIVES ON THE PROPER INSTALLATION AND TESTING PROCEDURES. THIS ENVIRONMENTALLY SAFE, FLEXIBLE UNDERGROUND PIPING SYSTEM PROVIDES PIPING RUNS BETWEEN USTS AND THE PRODUCT DISPENSERS C.ALL PRODUCT PIPING IS TO BE PRIMARY FUEL OF SPECIFIED DIAMETER IN SECONDARY PIPING OF SPECIFIED DIAMETER. PIPING TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. D.WHERE FLEX CONNECTORS ARE COMPLETELY CONTAINED (NOT IN CONTACT WITH GROUND WATER, NATIVE SOIL OR BACKFILL MATERIAL), STAINLESS STEEL CONNECTORS ARE ACCEPTABLE. WHERE FLEX CONNECTORS ARE NOT COMPLETELY CONTAINED ISOLATION BOOTS OR PRIME AND WARP SHALL BE USED TO SEPARATE CONNECTOR FROM COMING INTO CONTACT WITH GROUND WATER, NATIVE SOIL OR BACKFILL MATERIAL. ALL FLEX CONNECTORS SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE. E.THE GENERAL CONTRACTOR ACCEPTS FULL RESPONSIBILITY FOR PROPER HANDLING AND INSTALLATION OF PIPING SYSTEM. THE GENERAL CONTRACTOR SHALL INSURE THAT GOOD WORKMANSHIP AND CONSTRUCTION PROCEDURES ARE FOLLOWED THROUGHOUT THE INSTALLATION, REGARDLESS OF INCLUSION OR OMISSION OF ANY APPLICABLE SUGGESTION IN THESE INSTRUCTIONS OR ON THE DRAWINGS. F.UNKNOWN SITUATIONS OR CONDITIONS NOT COVERED IN THESE INSTRUCTIONS ARE THE RESPONSIBILITY OF THE CONTRACTOR. MANUFACTURERS SPECIALISTS ARE AVAILABLE FOR CONSULTATION. THE PRESENCE OF THE OWNER'S OR MANUFACTURER'S REPRESENTATIVE AT AN INSTALLATION SITE DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FOR A PROPER INSTALLATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER SAFEGUARDING OF THE INSTALLATION AND MATERIALS AND EQUIPMENT STORED ON THE SITE TO PREVENT THEFT, VANDALISM OR DAMAGE. RESPONSIBILITY NOTE: PETROLEUM SYSTEM ELECTRICIAN IS RESPONSIBLE FOR ALL POWER WIRING, LOW VOLTAGE WIRING, ATG SENSOR/PROBE WIRING, AND SETUP. PETROLEUM CONTRACTOR IS RESPONSIBLE FOR DISPENSER/SYSTEM START-UP AND CALIBRATION. ON DAY OF SYSTEM STARTUP, DATA/NETWORK SUPPLIER, PETROLEUM CONTRACTOR, PETROLEUM ELECTRICIAN, AND CK CONSTRUCTION MANAGER MUST BE ON SITE. PETROLEUM CONTRACTOR IS REQUIRED TO BE ON SITE FOR THE ENTIRETY OF THE FIRST DAY OF STORE OPERATION (7AM - 6PM) CONCRETE NOTE: UPON INSTALLATION & APPROVALS OF NEW PIPING, CONDUIT, PLUMBING, ETC. FOR THE TANK INSTALLATION, BACKFILL EXCAVATION AREAS WITH APPROVED BACKFILL, AND PROVIDE CONCRETE PAVING PER CIVIL. NOTE: MINIMUM REQUIREMENTS. 8" THICK, 4000 P.S.I. MIN. REQ'D @ TANK AREAS W/ NO. 4 BARS @ 12" O.C.E.W. (TYP). PROVIDE 6" THICK MIN. CONC W/ NO. 4'S 18" O.C.E.W. REINFORCING AT PIPING TRENCHES. FINISH SHALL BE WOOD FLOAT WITH MEDIUM BROOM FINISH. A MEDIUM BROOM FINISH IS REQUIRED ON THE CONCRETE PAVING LOCATED BETWEEN THE GASOLINE ISLANDS AND THE SIDEWALK IN FRONT OF THE CIRCLE K BUILDING. CONTRACTOR TO PROVIDE TEST AREA FOR CIRCLE K REPRESENTATIVE APPROVAL. SETTLEMENT NOTE: CAUTION TANK SETTLEMENT, TANK DISTORTION, OR MOVEMENT IN CONCRETE COVER SLAB CANNOT BE TOLERATED AND IF SPECIFIED MATERIALS ARE USED AND SPECIFIED PROCEDURES ARE FOLLOWED, NO INSTALLATION FAILURE SHOULD OCCUR, IT WILL BE PRESUMED THE CONTRACTOR HAS NOT FOLLOWED THE SPECIFIED INSTRUCTIONS AND PROCEDURES AND THE CONTRACTOR SHALL IMMEDIATLY UNDERTAKE, AT HIS SOLE EXPENSE, ANY NECESSARY CORRECTIVE MEASURES, AS MAY BE APPROVED BY THE CIRCLE K FIELD REPRESENTATIVE, UP TO AND INCLUDING COMPLETE REMOVAL AND RESETTING OF ALL UNDERGROUND TANKAGE AT THE SITE. IF IT IS DETERMINED THAT MOVEMENT, SETTLEMENT OR DISTORTION HAS BEEN CAUSED BY FACTORS BEYOND THE CONTRACTOR'S CONTROL, THE COST OF REMEDIAL MEASURES WILL BE BORNE BY OTHERS. THE GAS INSTALLATION CONTRACTOR DOES HEREBY AGREE TO GUARANTEE THE UNDERGROUND TANKAGE INSTALLATION AGAINST FAILURE AS OUTLINED HEREIN ABOVE, FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. TANK BACKFILL REQUIREMENTS UNDERGROUND STORAGE TANK BACKFILL MUST ADHERE TO MANUFACTURER MATERIAL REQUIREMENTS AND COMPLIANCE TO STANDARDS POLICY IN ORDER TO ASSURE COMPLIANCE TO UST MANUFACTURER'S REQUIREMENTS FOR UST BACKFILL MATERIALS, PROCEDURES WILL BE FOLLOWED TO MONITOR APPROVAL BY MANUFACTURER, VERIFICATION THAT APPROVED MATERIAL HAS BEEN DELIVERED TO THE SITE, AND DOCUMENTATION ON THE CONSISTENCY OF MATERIAL PLACED IN THE UST EXCAVATION. PROCEDURE SPECIFICATIONS FOR ACCEPTABLE MATERIALS TO BE USED AS STRUCTURAL SUPPORT FOR FIBERGLASS USTS. ROUNDED GRAVEL WHEN USING ROUNDED GRAVEL, THE MATERIAL IS THE BE A MIX OF ROUNDED PARTICLES, SIZES BETWEEN 1/8" AND 3/4". THE ROUNDED GRAVEL MUST CONFORM TO THE SPECIFICATIONS OF ASTM C-33, PARAGRAPH 9.1, SIZES 6, 67, OR 7. NO MORE THAN 5% (BY WEIGHT) OF THE BACKFILL MAY PASS THROUGH A #8 SIEVE. THE MATERIAL IS TO BE WASHED, FREE-FLOWING, AND FREE OF ICE, SNOW, AND DEBRIS. CRUSHED STONE WHEN USING CRUSHED STONE, THE MATERIAL IS TO BE A MIX OF ANGULAR PARTICLES, SIZES BETWEEN 1/8" AND 1/2". THE CRUSHED STONE MUST CONFORM TO THE SPECIFICATIONS OF ASTM C-33, PARAGRAPH 9.1, SIZES 7 OR 8. NO MORE THAN 5% (BY WEIGHT) OF THE BACKFILL MAY PASS THROUGH A #8 SIEVE. THE MATERIAL IS TO BE WASHED, FREE-FLOWING, AND FREE OF ICE, SNOW, AND DEBRIS. APPROVAL PROCESS ROUNDED GRAVEL A SAMPLE CONSISTING OF THREE (3) SEPARATE RANDOM INTERIOR STOCKPILE SAMPLES SHALL BE TAKEN AT THE QUARRY BY THE MATERIALS TESTING COMPANY. CLEAN ONE GALLON SIZED BUCKETS (APPROXIMATE) CAN BE USED FOR SAMPLING. THE MATERIALS TESTING COMPANY SHALL COMPLETE A SIEVE ANALYSIS ON THIS MATERIAL AS IT HAS BEEN COMBINED. IF THIS MATERIAL MEETS THE ASTM C-33 SPECIFICATIONS, THE ANALYSIS SHALL BE SUBMITTED TO THE TANK MANUFACTURER FOR APPROVAL. THE TANK MANUFACTURER WILL ISSUE AN APPROVAL ON THAT SAMPLE AS REFERENCED TO A SPECIFIC QUARRY. THIS PROCESS SHOULD TAKE ABOUT TWO DAYS. WITH ROUNDED GRAVEL ONLY, IT WILL BE NECESSARY TO OBTAIN A NEW SAMPLE ON EACH INSTALLATION AS LONG AS THE QUARRY REMAINS THE SAME. AN APPROVAL FROM THE TANK MANUFACTURER WILL ONLY BE NEEDED ONCE TO DOCUMENT THE APPROVAL OF THE ROCK. IT WILL NOT BE NECESSARY TO ASK FOR APPROVAL ON ADDITIONAL INSTALLATIONS, UNLESS THE QUARRY LOCATION CHANGES. IT WILL BE THE TANK INSTALLATION CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT ANY MATERIAL THAT HAS BEEN APPROVED BY THE TANK MANUFACTURER ALWAYS COMES FROM THE SAME QUARRY AND REMAINS CONSISTENT. CRUSHED STONE A SAMPLE CONSISTING THREE (3) SEPARATE RANDOM INTERIOR STOCKPILE SAMPLES SHALL BE TAKEN AT THE QUARRY BY THE MATERIALS TESTING COMPANY. CLEAN ONE GALLON (APPROXIMATE) SIZED BUCKETS CAN BE USED FOR SAMPLING. THE MATERIALS TESTING COMPANY SHALL COMPLETE A SIEVE ANALYSIS ON THIS MATERIAL AS IS HAS BEEN COMBINED. IF THIS MATERIAL MEETS THE ASTM C-33 SPECIFICATIONS WITH NO VARIATION, IT WILL NOT BE NECESSARY TO SUBMIT A SIEVE ANALYSIS FOR APPROVAL BY THE TANK MANUFACTURER. IT IS NOT UNCOMMON TO RECEIVE AN ANALYSIS THAT INDICATES MATERIAL SIZES OUTSIDE OF THE ASTM-33 STANDARD. THESE VARIABLE REPORTS WILL NEED TO BE SUBMITTED TO THE TANK MANUFACTURER FOR APPROVAL. THIS PROCESS SHOULD TAKE ABOUT TWO DAYS. A NEW SAMPLE AND SIEVE ANALYSIS WILL BE REQUIRED FOR EVERY LOCATION AS WELL AS AN APPROVAL FROM THE TANK MANUFACTURER. ON CRUSHED STONE ONLY, CIRCLE K WILL REQUIRE AN ON-SITE INSPECTION AND DOCUMENTATION BY THE TESTING COMPANY AS TO THE CONSISTENCY OF THE MATERIAL DELIVERED TO THE SITE AND ITS SIMILARITY TO THE MATERIAL APPROVED BY THE TANK MANUFACTURER. CIRCLE K WILL ALSO REQUIRE TESTING COMPANY DOCUMENTATION TO VERIFY THAT THE MATERIAL PLACED IN THE TANK EXCAVATION REMAINS CONSISTENT THROUGHOUT THE BACKFILL PROCESS. MATERIAL DISCOVERED ON SITE THAT DOES NOT MEET THE ASTM C-33 SPECIFICATION, FOR ANY REASON, WILL BE REMOVED AND REPLACED AT THE UST INSTALLERS EXPENSE. TANK AND DISPENSER NOTE: A.THE SPECIFIC SITE PLAN AND SPECIFICATIONS WILL GOVERN THE EXACT LOCATION, NUMBER, SIZE, AND TYPE OF EQUIPMENT TO BE INSTALLED AND INSTALLATION TO BE FOLLOWED. B.PLANS AND SPECIFICATIONS REPRESENT MINIMUM REQUIREMENTS. CONTRACTOR SHALL MAKE THE INSTALLATION IN ACCORDANCE WITH MANUFACTURER'S, FEDERAL, STATE, AND LOCAL ORDINANCES WHEN SUCH ORDINANCES EXCEED THESE MINIMUMS. C.CONTRACTOR SHALL SECURE, ARRANGE FOR AND PAY FOR ALL NECESSARY PERMITS, INSPECTIONS, AND TESTS AND INCLUDE THE COST IN THEIR BID (UNLESS SPECIFIED DIFFERENTLY IN SCOPE OF WORK). D.THE SCOPE OF WORK OR SPECIFICATIONS WILL LIST MATERIAL AND EQUIPMENT TO BE FURNISHED BY CIRCLE K. CONTRACTOR SHALL STORE, SAFEGUARD AND FURNISH ALL OTHER MATERIALS REQUIRED TO COMPLETE THE INSTALLATION. E.MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION AND OPERATIONAL TESTING OF ALL TANKS, PIPING, DISPENSERS, AND MONITORING EQUIPMENT SHALL BE FOLLOWED TO AVOID POSSIBILITY OF DAMAGE TO EQUIPMENT. F.ALL INSTALLATIONS SHALL INCLUDE THE INSTALLATION OF STAGE I VAPOR RECOVERY. G.CONTRACTOR SHALL PLACE ALL UNDERGROUND PIPING WHERE SHOWN WITH A MINIMUM NUMBER OF BENDS AND CONTINUOUSLY PITCHED TO PROVIDE MAXIMUM SLOPE FROM RISER TO THE LOW POINT AT THE CONNECTION. MINIMUM SLOPE OF 1/8" PER FOOT. INSTALL ALL PRODUCT AND VENT LINES IN A COMMON TRENCH. H.ALL PRODUCT LINES SHALL BE DOUBLE WALL FLEX PIPE. ALL VENT LINES (UNDERGROUND) SHALL BE FIBERGLASS UNLESS OTHERWISE NOTED. ALL PRODUCT LINES SHALL BE NUPI SMARTFLEX. ALL VENT LINES SHALL BE AMERON DUALOY 3000/L. I.CONTRACTOR SHALL IDENTIFY UNDERGROUND PIPING, AND VENT PIPING ONCE IT HAS BEEN BACKFILLED AND COVERED UP SO FINISH GRADING AND CONCRETE CONTRACTOR KNOW WHERE UNDERGROUND PIPING IS LOCATED. PIPE TRENCH NOTE: PIPING TRENCH LINERS SHALL BE 6oz NON-WOVEN GEOTECH FABRIC - OVERLAP TOP COURSE. CONTACT LOCAL CIRCLE K REPRESENTATIVE FOR LOCAL REQUIREMENTS. FINISH NOTE: (ALL PRODUCTS ARE SHERWIN-WILLIAMS) A.BOLLARDS:N/A - SLEEVED PER ARCH. ISLAND FORMS (IF REQUIRED BY AHJ): AMARILLO WHITE VENT PIPE:AMARILLO WHITE CANOPY NOTE: CANOPY IS A PREFAB STEEL STRUCTURE, CONTACT CIRCLE K REPRESENTATIVE FOR NAME OF MANUFACTURER, SEE MANUFACTURER'S DRAWING FOR STRUCTURAL DESIGN AND INSTALLATION INFORMATION. SEE ARCHITECTURAL SITE FOR LOCATION OF CANOPY AND GAS ISLANDS. THE GASOLINE CANOPY STRUCTURE IS FURNISHED AND INSTALLED BY CIRCLE K. INSTALLATION NOTE: CANOPY TANKS AND BUILDING TO BE INSTALLED AT THE SAME TIME. THESE PLANS MUST BE USED IN COORDINATION WITH SEPARATE SITE, BUILDING AND CANOPY PLANS. CONTRACTOR NOTE: A.IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONS ASSOCIATED WITH THIS PROJECT WORK SCOPE PRIOR TO THE INITIATION OF CONSTRUCTION. SHOULD THE CONTRACTOR FIND A CONFLICT WITH THE DOCUMENTS RELATIVE TO THE SPECIFICATIONS OR APPLICABLE CODES, IT IS THE CONTRACTOR'S RESPOSIBILITY TO NOTIFY THE PROJECT ENGINEER OF RECORD IN WRITING PRIOR TO THE START OF CONSTRUCTION. FAILURE BY THE CONTRACTOR TO NOTIFY THE PROJECT ENGINEER SHALL CONSTITUTE ACCEPTANCE OF FULL RESPONSIBILITY BY THE CONTRACTOR TO COMPLETE THE SCOPE OF WORK AS DEFINED BY THE DRAWINGS AND IN FULL CONFORMANCE WITH LOCAL REGULATIONS AND CODES. B.THE CONTRACTOR ACCEPTS FULL RESPONSIBILITY FOR PROPER HANDLING AND INSTALLATION OF THE GASOLINE USTS AND SHALL INSURE THAT GOOD WORKMANSHIP PRACTICES AND CONSTRUCTION PROCEDURES ARE FOLLOWED REGARDLESS OF THE INCLUSION OR OMISSION OF ANY INSTRUCTION. C.UNKNOWN SITUATIONS OR CONDITIONS NOT COVERED IN THESE AND THE MANUFACTURER'S INSTRUCTIONS ARE THE RESPONSIBILITY OF THE CONTRACTOR. MANUFACTURER'S SPECIALISTS ARE AVAILABLE FOR CONSULTATION. THE PRESENCE OF THE MANUFACTURER OR OBSERVER AT AN INSTALLATION SITE DOES NOT RELIVE THE CONTRACTOR OF HIS RESPONSIBILITY FOR THE PROPER INSTALLATION OF THE TANKS. D.QUESTIONS REGARDING INSTALLATION PROCEDURES OR TANK REPAIRS SHOULD BE DIRECTED TO THE CIRCLE K FIELD REPRESENTATIVE. E.GASOLINE UNDERGROUND TANKS MUST BE INSTALLED ACCORDING TO THESE INSTRUCTIONS, THE MANUFACTURER'S INSTRUCTIONS AND NFPA 30 AND 30A UL971. LOCAL CODES MAY APPLY AND MUST BE ADHERED TO. FAILURE TO FOLLOW THESE INSTALLATIONS INSTRUCTIONS WILL VOID THE WARRANTY AND WILL RESULT IN TANK FAILURE. PROPER INSTALLATION OF GASOLINE USTS HELP PREVENT TANK DAMAGE AND SHOULD INSURE LONG-TERM CORROSION-PROOF SERVICE. IT IS IMPERATIVE TO READ, UNDERSTAND AND FOLLOW THESE INSTRUCTIONS. F.THESE SPECIFICATIONS ARE SUPPLEMENTED BY THE RESPECTIVE TANK MANUFACTURER'S SPECIFICATIONS. THE INSTALLATION PROCEDURE SHALL COMPLY WITH BOTH SETS OF INSTRUCTIONS AND SPECIFICATIONS. IF, IN THE CONTRACTOR'S JUDGEMENT, THERE APPEARS TO BE A CONFLICT IN THESE SPECIFICATIONS AND THE TANK MANUFACTURER'S INSTRUCTIONS, CONTACT THE LOCAL CIRCLE K REPRESENTATIVE FOR CLARIFICATION AND GUIDANCE. G.CONTRACTOR SHALL INSPECT AND CONFIRM ALL PIPING TO BE CLEAR OF ALL BEDDING MATERIAL, TRASH, ANY TYPE OF LIQUID OR DEBRIS PRIOR TO AND AFTER INSTALLATION. I.TANK AND PRODUCT LINE TESTING AND REPORTING REQUIRED. COORDINATE REQUIREMENTS WITH CIRCLE K REPRESENTATIVE. J.TANK TIGHTNESS TESTING PROCEDURES SHALL BE FOLLOWED FOR ALL TANKS BEING INSTALLED. TESTING DATA LOG SHALL BE COMPLETED BY THE CONTRACTOR AND SUBMITTED TO THE CIRCLE K REPRESENTATIVE AFTER TESTING IS COMPLETE. CONTRACTOR SHALL ALSO RETAIN A COPY AS PART OF THE TANK RECORDS THAT MAY BE REQUIRED BY FEDERAL, STATE AND/OR LOCAL REGULATIONS AND CODES. K.CONTRACTOR SHALL PROVIDE TANK EXCAVATION HOLE PROTECTION AT AL TIMES UNTIL PAVING IS IN PLACE PER OSHA STANDARD 1910. COVERS AND/OR GUARDRAILS SHALL BE PROVIDED TO PROTECT PERSONNEL FROM THE HAZARDS OF OPEN PITS, TANK VATS, DITCHES, ETC. L.ALL TANK, TRANSITION, AND DISPENSER SUMPS SHALL BE COVERED DURING CONSTRUCTION TO PREVENT DEBRIS AND WATER FROM ACCUMULATING. ANY ACCUMULATION SHALL BE REMOVED AND SUMPS KEPT CLEAN. SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK006 EQ U I P M E N T L I S T EQUIPMENT LIST #PART DESCRIPTION MANUFACTURER MODEL NUMBER FURN.INST.REMARKS PRODUCT TANKS 1 DOUBLEWALL FIBERGLASS UNDERGROUND STORAGE TANK CONTAINMENT SOLUTIONS 20K - 10' DIA. 20K (12K/8K SPLIT) - 10' DIA 12K - 8' DIA - DIESEL CK GC COMPLETE WITH FIBERGLASS TANK SUMPS, CONTAINMENT COLLARS AND MISCELLANIOUS PARTS INCLUDING FIBERGLASS STRAPS, GALVANIZED TIE-DOWNS, AND DEADMEN. HYDROSTATIC INTERSTITIAL FOR ALL TANKS. NO EXCEPTIONS. 2 3 4 5 PRODUCT AND VENT PIPING 6 2" DOUBLE WALL FLEXIBLE PIPING NUPI SMARTFLEX 19TSMAXPD63R75 CK GC 246' COIL 7 2" SINGLE WALL FIBERGLASS PIPING (VENT PIPING ONLY)AMERON AMERON-DUALOY 3000/L CK GC 33' STICK LENGTH, USE GLUE KIT FOR 100% ALCOHOL COMPATIBILITY. PROTECTIVE MESH IS REQUIRED FOR L PIPING 8 9 TANK TOP PACKAGES, CONTAINMENT SUMPS, HARDWARE, AND MANHOLES 10 FILL SPILL BUCKET EMCO WHEATON A1004EVR-317S CK GC NO DRAIN VALVES. 11 VAPOR BUCKET EMCO WHEATON A1004EVR-317A CK GC NO DRAIN VALVES. 12 SWIVEL FILL ADAPTOR EMCO WHEATON A0030-124S CK GC 13 4" FILL CAP EMCO WHEATON A0097-005 CK GC 14 SWIVEL VAPOR ADAPTOR EMCO WHEATON A0076-124S CK GC DO NOT INSTALL SWIVEL VAPOR ADAPTOR AT DIESEL. 15 VAPOR CAP EMCO WHEATON A0099-002 CK GC INSTALL A0099-002 CAP AT DIESEL VAPOR ONLY. INSTALL A0097-005 AT ALL OTHER PRODUCTS 16 EXTRACTOR VALVE 4x4x2 (NO CAGE)EMCO WHEATON A0079-150 CK GC 17 COMPOSITE 42" MANHOLE W/CAM LOCK EMCO WHEATON A0716-042C CK GC 18 15' OVERFILL DROP TUBE EMCO WHEATON A1100EVR-056CF CK GC 19 4" x 16' SLOTTED SCH 40 PVC W/ PLUG TITAN INDUSTRIES MF-4X16WS GC GC 20 12" X 16' SLOTTED SCH 40 PVC W/ PLUG TITAN INDUSTRIES TI-PVC12X16WELL GC GC 21 12" MONITOR WELL MANHOLE EMCO WHEATON A0721-101 CK GC Steel Skirt, White Lid 22 18" MONITOR WELL MANHOLE EMCO WHEATON A0721-018 CK GC 23 18" RAINTITE BOLTED MANHOLE EMCO WHEATON A0717-018B CK GC 24 4" WELL CAP EMCO WHEATON A0720-001 CK GC 25 12" WELL CAP TITAN INDUSTRIES EM-P4120BTMPLUG CK GC 26 UNITED SIGN FILL PIPE ID TAG, DIESEL UNITED SIGN US-FPI-125D CK GC 27 UNITED SIGN FILL PIPE ID TAG, UNLEADED UNITED SIGN US-FPI-125U CK GC 28 UNITED SIGN FILL PIPE ID TAG, PREMIUM UNITED SIGN US-FPI-125P CK GC 29 UNITED SIGN FILL PIPE ID TAG, E0 UNITED SIGN US-FPI-E0 CK GC 30 UNITED SIGN VAPOR RECOVERY ID TAG UNITED SIGN US-FPI-22 CK GC 31 32 33 34 35 36 37 38 39 TURBINE 40 FE PETRO 2 HP FIXED SPEED W/ MAG SHELL FRANKLIN FUELING FE-STPM200-VL2 CK GC REFER TO TK101 FOR PUMP QTY & SIZING CHART, ORDER RISER WITH PUMP 41 4" x 24" RISER - NPT THREADED 304L STAINLESS STEEL FRANKLIN FUELING CK GC ORDER PRE-THREADED FROM MNFR. 42 4" x 24" RISER - NPT THREADED EPOXY COATED (DIESEL ONLY)FRANKLIN FUELING FE-400168424 CK GC 43 44 45 46 47 48 49 50 51 52 53 54 TURBINE SUMP FITTINGS, PIPING, AND VENT HARDWARE 55 BRAVO 3/4 FIBERGLASS CONDUIT ENTRY 10 PACK W/ GLUE BRAVO BR-F-07-FF/BR-F-07R-FF CK GC USE BR-F-07R-FF WHEN PVC COATED CONDUIT IS USED 56 2.5" ID FIBERGLASS SUMP ENTRY FITTING FOR 2" NUPI SMARTFLEX NUPI 19SEBEFM75A CK GC 57 58 3" PIPE CLAMP BRAVO BR-T-FF-CLAMP-3 CK GC 59 ENTRY FITTING ADHESIVE KIT 7 OZ - 1 KIT PER FITTING BRAVO BR-ADHESIVE-EPOXY-KIT CK GC 60 2" X 1-1/2" F ADAPTER - SS NUPI 19SAF63112SSNPT CK GC 61 2" M ADAPTER - SS NUPI 19SAM632SSNPT CK GC 62 2" F ADAPTER - SS NUPI 19SAF632SSNPT CK GC 63 FLEX CONN 2"x24" MxM SWIVEL END OMEGAFLEX OF-2X24MMS CK GC 64 ISOLATION BOOT 3x30"CRUSHPROOF CTC-450036 CK GC 65 2" THREAD,3" WC PRESSURE VACUUM VENT HUSKY A0084-038 CK GC 66 2" ALUMINUM OPEN TANK VENT (DIESEL ONLY)HUSKY A4103-002 CK GC 67 2" BALL VALVE - STAINLESS STEEL JOMAR JI-T100-2SS CK GC 68 2" BALL VALVE - BRASS JOMAR JI-T100-2PC CK GC 69 2" STEEL PIPING & FITTINGS - 304L STAINLESS STEEL - NPT THREADED GC GC 70 2" STEEL PIPING & FITTINGS - SCH 40 BLACK STEEL - NPT THREADED (DIESEL ONLY)GC GC 71 2" STEEL PIPING & FITTINGS - SCH 40 GALVANIZED - NPT THREADED (VENT RISER ONLY)GC GC 72 2" 90 - SINGLE WALL NUPI 19SGE63 CK GC 73 2" 45 - SINGLE WALL NUPI 19SCE63 CK GC 74 2" TEE - SINGLE WALL NUPI 19STE63 CK GC 75 2" COUPLING - SINGLE WALL NUPI 19SME63 CK GC 76 2" 90 - DOUBLE WALL NUPI 19SGEDW63 CK GC WITHOUT TEST PORT 77 2" 45 - DOUBLE WALL NUPI 19SCEDW63 CK GC WITHOUT TEST PORT 78 2" TEE - DOUBLE WALL NUPI 19STEDW63 CK GC WITHOUT TEST PORT 79 2" COUPLING - DOUBLE WALL NUPI 19SMEDW63 CK GC WITHOUT TEST PORT 80 2" TERMINATION FITTING NUPI 19SETFCV63 CK GC WITH TEST PORT #PART DESCRIPTION MANUFACTURER MODEL NUMBER FURN.INST.REMARKS DISPENSER & DISPENSER HARDWARE 81 MULTI-PRODUCT DISPENSER GILBARCO ENCORE 700S CK GC REFER TO TK101 FOR PRODUCT QTY AND TYPE (3+1+1, 3+1, 3+0, ETC.) 82 HUSKY 3/4" UL2586 UNL W/CLP BLK W/SPLSH HUSKY HN-N10SUF-UL CK GC 83 3/4" X 8" FS FUT HOSE - BLACK CONTINENTAL/CONTITECH CT-WHP3408 CK GC 84 3/4" X 9' FS FUT HOSE - BLACK CONTINENTAL/CONTITECH CT-3409 CK GC 85 3/4" MAGNETIC BREAKAWAY HUSKY HS-8330 CK GC 86 1+6 3/4 X 3/4 MULTIPLANE SWVL HUSKY HS-0350 CK GC 87 3/4" NEW UL2586 LFD W/CLP GRN W/SPLSH HUSKY HN-N10SLF-UL CK GC 88 3/4" X 8" FS FUT HOSE - BLACK CONTINENTAL/CONTITECH CT-WHP3408 CK GC 89 3/4" X 9' FS FUT HOSE - BLACK CONTINENTAL/CONTITECH CT-3409 CK GC 90 BRAVO 1000E FIBERGLASS SUMP FOR ENCORE DISPENSER BRAVO BR-B1000-ENC CK GC ECONOMY STYLE 91 BRAVO STABILIZER BAR BRAVO BR-BRKT-1000-ENC CK GC 92 SHEAR VALVE - OPW 10 PLUS DOUBLE POPPET OPW 10P-0152 CK GC 93 FLEX CONN 1.5" x 18" MxM SWIVEL END OMEGAFLEX OF-112X18MMS CK GC 94 3/4" UNLEADED HOSE KIT HUSKY HN-011154 CK GC ORDERING OPTION - INCLUDES PARTS 82, 83, 84, 85, 86 95 3/4" DIESEL HOSE KIT HUSKY HN-011463 CK GC ORDERING OPTION - INCLUDES PARTS 85, 86, 87, 88, 89 96 97 98 99 100 101 102 103 104 MISCELLANEOUS 105 6" BOLLARD COVER POST-GUARD GREY - 48"CK GC 106 6" x 72" BOLLARDS GC GC 107 3' x 5' x 13" DISPENSER ISLAND FORMS RIVERSIDE STEEL RS-3X5X13 CK GC USE ONLY IF REQUIRED BY AUTHORITY HAVING JURISDICTION. USE STAINLESS STEEL ISLAND FORMS IN SNOW SITES. 108 20 CHANNEL INTERCOM SYSTEM-TRADEMARK ESCO ES-941-0114 CK GC 109 CONTAINMENT LINER MPC PETROGARD X GC GC FOR PIPING AND TANK HOLES THAT REQUIRE "TERTIARY CONTAINMENT". VERIFY WITH CK REP AT TIME OF BIDDING 110 FILTER FABRIC GSE 8 OZ GSE NW8 GC GC FOR STANDARD INSTALLATION IN TANK HOLES AND PIPING TRENCHES 111 FILTER FABRIC GSE 16 OZ GSE NW16 GC GC FOR USE WITH ROCK HOLES. INCLUDE IN BID IF ROCK EXISTS. 112 113 114 115 116 117 118 119 120 121 122 123 124 MONITORING 125 TLS450PLUS W/ TCH DISPLAY & PRINT - CK VEEDER-ROOT VR-860091-301CK CK GC 126 TLS450PLUS APPLICATION SOFTWARE - CK VEEDER-ROOT VR-333545-001CK CK GC 127 RISK MGMT LEAK DETECTION DPLLD VEEDER-ROOT VR-332972-008CK CK GC 128 UNIVERSAL SENSOR PROBE 16 INPUT MOD VEEDER-ROOT VR-332812-001CK CK GC 129 UNIVERSAL INPUT/OUTPUT INTERFACE MOD VEEDER-ROOT VR-332813-001CK CK GC 130 CSLD SOFTWARE ENHANCEMENT VEEDER-ROOT VR-332972-006CK CK GC 131 DPLLD WITHOUT SWIFTCHECK VEEDER-ROOT VR-859080-001CK CK GC 132 8' MAG PLUS TANK PROBE VEEDER-ROOT VR-846396-107CK CK GC 133 10' MAG PLUS TANK PROBE VEEDER-ROOT VR-846396-109CK CK GC 134 PHASE SEPARATION 4" GAS FLOAT KIT - 10' CABLE VEEDER-ROOT VR-886100-010CK CK GC 135 4" NEW STYLE DIESEL FLOAT KIT - 10'CABLE VEEDER-ROOT VR-846400-011CK CK GC 136 4" CAP AND RING KIT VEEDER-ROOT VR-312020-952CK CK GC 137 PIPING SUMP SENSOR VEEDER-ROOT VR-794380-208CK CK GC 138 SENSOR HOLDER FOR UDC BRAVO BR-SH-UDC CK GC 139 SENSOR HOLDER FOR TANK SUMP BRAVO BR-SH-TS CK GC 140 HYDROSTATIC RESERVOIR SENSOR WITH VENTED CAP VEEDER-ROOT VR-794380-303CK CK GC 141 EMERGENCY SHUT OFF SIGN UNITED SIGN US-MS76 GC GC 142 EMERGENCY SHUT OFF SWITCH POWER INTEGRITY PI-IA-ESOCA/T GC GC 143 OVERFILL ALARM VEEDER-ROOT VR-790091-001CK CK GC 144 OVERFILL ALARM ACKNOWLEDGEMENT SWITCH VEEDER-ROOT VR-790095-001CK CK GC 145 146 147 148 149 150 151 152 153 154 155 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK007 EQ U I P M E N T L I S T EQUIPMENT LIST #PART DESCRIPTION MANUFACTURER MODEL NUMBER FURN.INST.REMARKS HIGH SPEED DIESEL/DEF - DISPENSERS, CONTAINMENT, AND HANGING HARDWARE 156 ULTRA HI FLOW DISPENSER GILBARCO ENCORE 700S CK GC SEE SITE PLAN AND VERIFY NUMBER OF MASTER/SATELLITES WITH CK CONSTRUCTION REP 157 ULTRA HI FLOW DISPENSER WITH DEF GILBARCO ENCORE 700S CK GC SEE SITE PLAN AND VERIFY NUMBER OF MASTER/SATELLITES WITH DEF WITH CK CONSTRUCTION REP 158 UNITED SIGN FILL PIPE ID TAG, DEF UNITED SIGN FPI-XXXX CK GC 159 SHEAR VALVE - 2" SINGLE POPPET OPW 10RF-2001 CK GC FOR USE AT SATELLITE FEEDS ONLY 160 SHEAR VALVE - 2" DOUBLE POPPET OPW 10RF-2002 CK GC FOR USE AT MAINFEED ONLY 161 SHEAR VALVE - 1" DEF OPW 60V-DEF CK GC FOR DEF ONLY. USE BSPP/NPT ADAPTORS PART #'s 205900/205899 FOR FINAL CONNECTIONS 162 ENCORE DIESEL/DEF UNDER DISPENSER SUMP BRAVO B1385-S30 CK GC FOR USE AT DISPENSERS WITH DEF. INSTALL B1000-ENC (REF. TK006) FOR DISPENSERS WITHOUT DEF. 163 1" DEF HOSE - BLUE OPW 21GU-H12 CK GC 12' HOSE 164 STAINLESS STEEL DEF SWIVEL/RECONNECTABLE BREAKAWAY OPW 21GU-SSB CK GC COMES WITH 21GU-BCS SWIVEL COVER SLEEVE 165 1" DEF NOZZLE - BLUE OPW 21GU-040G CK GC NO MIS-FILLING DEVICE. CONFIRM WITH CK WHEN MIS-FILLING DEVICE WILL BE NEEDED. 166 1" x 8" WHIP HOSE - BLACK CONTINENTAL 20022010 CK GC 167 1" MAGNETIC BREAKAWAY DEVICE CATLOW CAM TWIST CTM100-HD CK GC 168 1" x 10' DIESEL HOSE - BLACK CONTINENTAL 20021982 CK GC 169 1" SWIVEL HUSKY 0087 CK GC 170 1" HIGH VOLUME NOZZLE - GREEN HUSKY 177610-03 CK GC 171 FLEX CONN 1" x 18" MxM SWIVEL END FRANKLIN FF10X18HMXM346 CK GC 172 1" STAINLESS STEEL BALL VALVE JOMAR T100-965 CK GC 173 174 175 176 177 178 179 180 HIGH SPEED DIESEL SERVICE ISLAND EQUIPMENT 181 ADA APPROVED FREEZE PROOF WATER HYDRANT W/ 3/4" CONNECTION MERRIL R103 CK GC 3/4" OUTLET 1" INLET X 70 - 1/2" HYDRANT 182 5HP ELECTRIC AIR COMPRESSOR CHAMPION VR5-8 - VERT/HR5-8 - HORIZONTAL CK GC INSTALL IN CK SUPPLIED CABINET AT REAR OF BUILDING OR DUMPSTER ENCLOSURE. REFER TO TK101. 183 AIR HOSE REEL REELCRAFT D8650 ELP CK GC ORDER SIDE WIND OPTION FOR COLUMN MOUNTING 184 1/2" X 18" STAINLESS STEEL FLEX CONNECTOR GC GC 185 1/2" STAINLESS STEEL BALL VALVE GC GC 186 3/4" SCH 40 PVC GC GC FOR USE WITH WATER ONLY. REFER TO CIVIL 187 1/2" TYPE K COPPER LINE GC GC FOR USE WITH AIR ONLY 188 1/2" BRASS BALL VALVE GC GC 189 AIR COMPRESSOR FILTER CHAMPION CFL SERIES CK GC 190 AIR COMPRESSOR REGULATOR CHAMPION CK GC 191 ANGLED AIR CHUCK WESTWARD 2HKY2 CK GC ANGLED AIR CHUCK, 1/4" FEMALE NPT, 150PSI RATING 192 WATER SPOUT MILTON JE 8647 CK GC WATER SPOUT, 1/4" FEMALE NPT 193 WATER HOSE CK GC 20' LENGTH X 3/4", RED 194 195 DEF TANK HARDWARE AND COMPONENTS 196 DEF SUBMERSIBLE PUMP KIT FE PETRO FE-STP-DEF-VL2 CK GC FOR 8' DIA TANK 197 2" STAINLESS STEEL CHECK VALVE CSVE200 CK GC 198 DEF FILL BUCKET EMCO WHEATON A1005-518GW2DEF CK GC USE ONLY WHEN DIRECT BURY FILL IS SPECIFIED 199 SS 4" X 3" FILL REDUCER ADAPTER SS 64143040 CK GC USE ONLY WHEN DIRECT BURY FILL IS SPECIFIED 200 SS 3" DUST CAP SS 1401130 CK GC USE ONLY WHEN DIRECT BURY FILL IS SPECIFIED 201 DEF REMOTE FILL BOX MORRISON BROS 515SD-0200 AC CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 202 DEF OVERFILL DEVICE MORRISON BROS 9095SS-9800AV CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 203 2" DEF DRY DISCONNECT ADAPTER MORRISON BROS 927S-0200 1A CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 204 2" DEF DUST CAP MORRISON BROS 9284-0200 1C CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 205 2" STAINLESS STEEL BALL VALVE MORRISON BROS 691BSS0800 1V CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 206 2" LINE STRAINER MORRISON BROS 284S-3100 1S CK GC USE ONLY WHEN REMOTE FILL APPLICATION IS SPECIFIED 207 208 209 210 CIRCLE-K STORE 5,200 S.F. 1 100'- 0 " 13 100' - 0 " 13 16 11 12 16 16 14 11 12 16 7 8 10 5 17 18 15 2 4 3 14 20 19 TR A N S F O R M E R PA D ( A P P R O X ) W 16 11 12 16 14 16 11 12 16 14 16 11 12 16 14 16 11 12 16 14 16 14 11 12 16 20 19 100'-0" 21 22 KEY SCHEDULE: 1.CIRCLE K STORE; REF. ARCH 2.REGULAR UL DOUBLE WALL UNDERGROUND STORAGE TANK; REF. TK301 3.PREMIUM UL/CK CHOICE DUAL COMPARTMENT DOUBLE WALL UNDERGROUND STORAGE TANK; REF. TK301 4.DIESEL DOUBLE WALL UNDERGROUND STORAGE TANK; REF. TK301 5.TANK PAD ; REF. TK301 6.NOT USED. 7.OBSERVATION WELL (4"); REF. DTL. 1/TK502 8.OBSERVATION WELL (12"); REF. DTL . 2/TK502 9.2" DOUBLE WALL NUPI SMART FLEX PRODUCT PIPING 10.2" SINGLE WALL FIBERGLASS VENT PIPING. PIPE TO SLOPE AT MINIMUM SLOPE OF 1/8" PER FOOT BACK TO TANK 11.UNDER DISPENSER CONTAINMENT SUMP; REF. TK503 12.DISPENSER; REF. TK504 13.EMERGENCY STOP BUTTON PLACED 20' MINIMUM/100' MAXIMUM FROM DISPENSER PER NFPA 30A/LOCAL FIRE CODE; REF ELECTRICAL DWGS. 14.CANOPY COLUMN; REF. ARCH 15.VENT STACK; REF. TK504 16.BOLLARD; REF TK504 17.CANOPY; REF. ARCH 18.CANOPY APRON; REF. CIVIL 19.HSD UNDER DISPENSER CONTAINMENT SUMP; REF. TK503.1 20.HSD DISPENSER; REF. TK505.1 21.EMERGENCY STOP BUTTON PLACED 20' MINIMUM/100' MAXIMUM FROM DISPENSER PER NFPA 30A 22.EMERGENCY STOP BUTTON PEDESTAL; REF. DTL 3/TK505 LEGEND REGULAR UNLEADED CIRCLE K CHOICE DIESEL PREMIUM UNLEADED VENT SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK101 SI T E P I P I N G P L A N 1 SITE PIPING PLAN SCALE: 1" = 20'-0" D CKC P U DI S P E N S E R 1 L E A K D E T E C T O R DI S P E N S E R 2 L E A K D E T E C T O R DI S P E N S E R 3 L E A K D E T E C T O R DI S P E N S E R 4 L E A K D E T E C T O R DI S P E N S E R 5 L E A K D E T E C T O R DI S P E N S E R 6 L E A K D E T E C T O R DI S P E N S E R 7 L E A K D E T E C T O R 3/ 4 " C DI S P E N S E R 1 I N T E R C O M T O C A S H I E R DI S P E N S E R 2 I N T E R C O M T O C A S H I E R DI S P E N S E R 3 I N T E R C O M T O C A S H I E R DI S P E N S E R 4 I N T E R C O M T O C A S H I E R DI S P E N S E R 5 I N T E R C O M T O C A S H I E R DI S P E N S E R 6 I N T E R C O M T O C A S H I E R DI S P E N S E R 7 I N T E R C O M T O C A S H I E R DI S P E N S E R 1 P O W E R CK STORE 12 K D I E S E L ( 1 0 ' D I A . ) 8K CKC12K SUL 20K REGULAR I V S F V S STP T T F V I STP V F I 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C FSTPT 3/ 4 " C DI S P E N S E R 1 C R I N D 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C DI S P E N S E R 2 C R I N D DI S P E N S E R 3 C R I N D DI S P E N S E R 4 C R I N D DI S P E N S E R 5 C R I N D DI S P E N S E R 6 C R I N D DI S P E N S E R 7 C R I N D NOTE: CONDUITS REQUIRED PER DISPENSER: ·(1) 3/4" FOR INTERCOM ·(1) 3/4" FOR POWER ·(1) 3/4" FOR VEEDER ROOT SENSOR IN DISPENSER SUMP ·(1) 3/4" FOR CRIND POWER CONDUIT REQUIRED PER SUB PUMP: ·(1) 3/4" CONDUIT LV CONDUIT REQUIRED PER TANK : ·(1) 3/4" CONDUIT TO EACH TANK AND ADJACENT PROBES CANOPY LIGHTS, SPEAKERS, AND SIGNS: ·(4) 3/4" CONDUIT FOR LIGHTS ·(1) 3/4" CONDUIT FOR SPEAKERS CANOPY SECURITY CAMERAS: ·(3) 1" CONDUIT NUMBER WILL VARY BASED ON NUMBER OF DISPENSERS AND SUB PUMPS. REFER TO TK101 FOR TYPE AND QUANTITY OF DISPENSERS. PRODUCT PIPING SLOPED AT 1/8" PER FOOT TO TANKS. PRODUCT PIPING SLOPED AT 1/8" PER FOOT TO TANKS. PR O D U C T P I P I N G SL O P E D A T 1 / 8 " P E R FO O T T O T A N K S . PR O D 1 B S T P P O W E R PR O D 2 S T P P O W E R PR O D 3 S T P P O W E R PR O D 4 S T P P O W E R 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C TA N K 1 M O N I T O R I N G TA N K 2 M O N I T O R I N G TA N K 3 M O N I T O R I N G 3/4" CONDUIT LOOPED AS SHOWN AT ALL TANKS (TYP.) 3/ 4 " C 3/ 4 " C 3/ 4 " C DI S P E N S E R 2 P O W E R DI S P E N S E R 3 P O W E R DI S P E N S E R 4 P O W E R DI S P E N S E R 5 P O W E R DI S P E N S E R 6 P O W E R DI S P E N S E R 7 P O W E R PR O D 1 A S T P P O W E R 3/ 4 " C Xref .\XREF\xr-site.dwg 3+1+1 3+1+13+1 3+1+1 OR VARIES 3+1 3+1+1 OR VARIES 3+1 3+1+1 OR VARIES 3+1 3+1+1 OR VARIES 3+1 3+1+1 OR VARIES STORE ELECTRICIAN TO ROUGH IN CONDUIT AT ELECTRICAL ROOM AND RUN TO PETROLEUM ELECTRICIAN'S POINT OF INTERCEPTION 30' FROM FRONT OF STORE. ELECTRICIAN RESPONSIBILITY DELINIATION PETROLEUM ELECTRICIAN TO INTERCEPT CONDUIT 30' FROM FRONT OF STORE AND COMPLETE RUNS TO DISPENSERS, CANOPY, AND TANKS. PETROLEUM ELECTRICIAN RESPONSIBLE FOR ALL WIRING. REFER TO PETROLEUM ELECTRICAL DRAWINGS FOR WIRE TYPES. NOTE: CONDUIT ROUTING SHOWN ON THIS PLAN IS DIAGRAMMATIC. ELECTRICIAN TO USE BEST EFFORT TO ELIMINATE BENDS WHEN INSTALLING CONDUIT. 1" C 1" C SE C U R I T Y SE C U R I T Y SE C U R I T Y CA N O P Y L I G H T I N G CA N O P Y L I G H T I N G CA N O P Y L I G H T I N G CA N O P Y S P E A K E R S CA N O P Y L I G H T I N G 1" C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C COORDINATE WITH CK CONSTRUCTION MANAGER TO VERIFY WHICH COLUMNS RECEIVE CONDUITS STP (2) U - UNLEADED D - DIESEL I - INTERSTITIAL SPACE C - ELECT. CONDUIT T - TANK LEVEL MONITOR X - EXTRA TANK OPENING STP - SUBMERSIBLE TURBINE PUMP F - FILL V - VENT P - PREMIUM UNLEADED LEGEND U CKC D P V - VAPOR VCKC - CIRCLE K CHOICE S - SPARE SEE SERVICE ISLAND DETAIL ON SHEET TK505 CANOPY ABOVE; REF. ARCH CK PREFERENCE FOR DISPENSERS TO BE INSTALLED ON GRADE. ONLY INSTALL ON ISLAND IF REQUIRED BY LOCAL AHJ. CANOPY APRON BELOW; REF. CIVIL SEE SERVICE ISLAND DETAIL ON SHEET TK504 3/ 4 " C 3/ 4 " C 3/ 4 " C 3/ 4 " C DI S P E N S E R 8 I N T E R C O M T O C A S H I E R DI S P E N S E R 8 L E A K D E T E C T O R DI S P E N S E R 8 P O W E R DI S P E N S E R 8 C R I N D HSD SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK102 SC H E M A T I C W I R I N G , P I P I N G & D E T A I L S 1 SCHEMATIC SITE PLAN SCALE: N.T.S. wv 1'-41 2" (TYP) 37'-83 4" 4'-61 2"5'-6"5'-6"6'-8"5'-6"5'-6" 1'-2" NOTES: 1.TANK INTERSTICE IS FACTORY BRINE FILLED. 2.NOMINAL TANK WEIGHT : 11,300 lbs 0' - 4 " 3' - 0 " Ø1 0 ' - 0 " Ø1 0 ' - 4 " wv 1'-41 2" (TYP) NOTES: 1.TANK INTERSTICE IS FACTORY BRINE FILLED. 2.SERVICE FITTING ON FLAT #11 IS FOR A VENT ONLY. 3.NOMINAL TANK WEIGHT : 12,700 lbs Ø1 0 ' - 0 " Ø1 0 ' - 4 " 37'-91 4" 5'-11"5'-6"2'-9"4'-11 2"2'-9"4'-11 2"5'-6"2'-7" 1'-21 2" 2'-9" 0' - 4 " ( T Y P ) 3' - 0 " (T Y P ) C OPTIONAL 22' PREFABRICATED CONCRETE DEADMAN2D LIFTING LUG A B C HOLD DOWN STRAP LOCATION ITEM QTY C 1 2 3 4 6 7 8 10 DESCRIPTION 1 1 2 4 5 9 24'-01 4" A B OPTIONAL 18" DIA. HYDROSTATIC MONITORING RESERVOIR WITH 4" NPT FITTING 4" NPT MONITOR FITTING 22' D 0' - 4 " 3' - 0 " A A 10 ' - 4 " 10 ' - 0 " 1'-21 2"1'-41 2" (TYP.) 5'-11"4'-11 2"3'-111 2"4'-11 2" SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK201 ST A N D A R D T A N K S 12K GALLON UNDERGROUND STORAGE TANK (10' DIAMETER)4320K GALLON DUAL COMPARTMENT UNDERGROUND STORAGE TANK (12K/8K SPLIT)SCALE: NTS SCALE: NTS20K GALLON UNDERGROUND STORAGE TANK (10' DIAMETER)2112K GALLON UNDERGROUND STORAGE TANK (10' DIAMETER)SCALE: NTS SCALE: NTS 1' - 0 " 10 ' - 0 " O. D . 3' M I N . 6' M A X UNDISTURBED SOIL TK500 2 TK502 6 TK502 5 TK502 4 TK502 4 TANK MANUFACTURER PROVIDED PRECAST CONCRETE DEADMAN SYSTEM WITH HOLD DOWN STRAPS TANK MANUFACTURER PROVIDED PRECAST CONCRETE DEADMAN SYSTEM WITH HOLD DOWN STRAPS PEA GRAVEL BACKFILL SLOPE AROUND ALL MANWAYS (SEE DETAILS) TIE DOWN STRAP (TYP) REFER TO MANUFACTURER'S DRAWINGS FOR TIE DOWN STRAP LOCATION, SPACING, AND QUANTITY OPTIONAL EXTENDED SLAB FOR ASPHALT SITES OPTIONAL EXTENDED SLAB FOR ASPHALT SITES ADJACENT PAVEMENT; REF. CIVL ADJACENT PAVEMENT; REF. CIVL TIE DOWN STRAP (TYP.) SHORE HOLE AS REQUIRED PER GEOTECH OR SITE LIMITATIONS FILTER FABRIC (TYP. AT ALL SIDES) SEE TK006 NO SLOPE ON TANK UNDERGROUND STORAGE TANK UNDERGROUND STORAGE TANK TK502 3 TK501 4 NOTE: INSTALL TANK LEVEL PROBE IN STP SUMP OF ALL TANKS EXCEPT 20K SINGLE COMP. 5" RE B A R O N 3" C H A I R S TK502 2 TK502 1 NOTE: VERIFY DEADMAN PLACEMENT REQUIREMENTS WITH TANK MANUFACTURER SPECIFICATIONS 1' - 0 " BE D D I N G , T Y P . 3'-0" MIN. TYP. 3'-0" MIN. TYP. 10'-0" #4 BARS @ 12" O.C.E.W. (TYP.) W/ DOUBLE MAT REINFORCING PER DTL. 2/TK301 8" THICK 4,000 PSI CONCRETE TANK SLAB; REF. CIVIL/GEOTECH REPORT 37'-9" 3' - 0 " MI N . 3' - 0 " MI N . 3' - 0 " MI N . 3'-0" MIN. 3'-0" MIN. 35 ' - 1 0 " M I N . EX T E N D T A N K P A D A S R E Q . T O F I L L A R E A B E T W E E N C A N O P Y A N D S T R E E T S I D E C U R B 57'-1"15'-0" OPTIONAL EXTENDED TANK PAD FOR ASPHALT SITES 15'-0" OPTIONAL EXTENDED TANK PAD FOR ASPHALT SITES 8' - 6 " MI N . O F F C U R B 4'-0"3'-0"2'-6"3'-0"1'-10"3'-0"2'-8"2'-4"3'-0"3'-0"2'-4" 3'-0"4'-8"4'-8"3'-7"2'-6"4'-4"2'-10"3'-11" 4' - 0 " 2' - 6 " 3' - 0 " 2' - 9 " 3' - 5 " 4' - 3 " 1' - 0 " 1' - 0 " 4' - 3 " 1' - 0 " 1' - 0 " 4'-3"1'-0"1'-0" DI E S E L ( 1 0 ' D I A . ) CK CHOICESUPER UL REGULAR UL ST P VA P O R STP VA P O R SP A R E FI L L ST P ST P OB S E R V A T I O N WE L L ( 1 2 " ) OB S E R V A T I O N WE L L ( 4 " ) TA N K LE V E L MO N I T O R FI L L IN T E R S T I T I A L VAPOR FILL INTERSTITIAL TANK LEVEL MONITOR #4 BARS @ 12" O.C.E.W. (TYP.) 8" THICK 4,000 PSI CONCRETE TANK SLAB, SEE SECTION ABOVE. PROVIDE CONTROL JOINTS AT 20' MAX. SPACING EACH WAY. REF. PLAN FOR CJ SPACING IN T E R S T I T I A L TA N K LE V E L MO N I T O R SP A R E FI L L VA P O R #4 BARS FOR ADDITIONAL REINFORCING AT MANWAYS CANOPY SIDE STREET SIDE 8' - 2 " 24 ' - 0 " 16'-4" 3' - 8 " 37'-9" 12" OBSERVATION WELL ALWAYS ON STREET SIDE 19'-0"19'-1"19'-0" 3'-0" MIN. 17 ' - 1 1 " 17 ' - 1 1 " C. J . C. J . C.J. SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK301 TY P I C A L U S T P L A N A N D S E C T I O N S 1 UNDERGROUND STORAGE TANK PROFILE SCALE: NONE 2 UNDERGROUND STORAGE TANK PLAN SCALE: NONE PRESSURE LINE LEAK DETECTOR 48"Ø FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER 2" NIPPLE 2" NIPPLE 2" 90° ELBOW TURBINE PUMP 4" RISER TANK MAG SUMP SENSOR W/ SENSOR MOUNTING KIT 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" TERMINATION FITTING WITH TEST PORT SEAL OFF (ONE FITTING FOR EACH CONDUIT) JUNCTION BOX 2" ENTRY FITTING 3/4" CONDUIT BONDED ENTRY FITTING 3/4" RIGID STEEL CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 2" FULL PORT BALL VALVE FRP ENCLOSURE TOP W/ ROUND BODY EXTENSIONFIELD BONDED ADHESIVE JOINT (TYP.) 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 3/4" RIGID STEEL CONDUIT FOR PUMP POWER 3/4" CONDUIT BONDED ENTRY FITTING 3/4" CONDUIT BONDED ENTRY FITTING DEEP BURIAL POLYGON FRP SUMP BODY 3/4" RIGID STEEL CONDUIT TO INTRINSICALLY SAFE GUTTER AT MONITOR CONTROL PANEL TOP OF FIBERGLASS OVERLAY STEEL PLATE 5" SECTION 2" TEE NOTE: ·FOR ALL FUEL TYPES EXCEPT FOR DIESEL, ALL COMPONENTS MUST BE SCH. 40 STAINLESS STEEL. ·FOR DIESEL, ALL COMPONENTS MUST BE BLACK IRON. ·PRODUCT PIPING CONFIGURATION AND EXIT POINTS MAY VARY. REFER TO TK101. 4" MI N . PEA GRAVEL BACKFILL 42"Ø MANHOLE W/ FRAME AND COVER CONCRETE TANK SLAB 34"Ø WATERTIGHT FRP LID 12"12" 72 7069 131 40 41 42 6867 7069 7069 7069 137 139 6 80 2" UNION 56 PLAN VIEW AT MANWAY 2" ENTRY FITTING PRESSURE LINE LEAK DETECTOR (AB0VE, ONE STP ONLY) ℄ TANK 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" TERMINATION FITTING WITH TEST PORT 2" SS MALE NPT ADAPTER FITTING 2" NIPPLE 2" 90° ELBOW TURBINE PUMP 4" RISER 48"Ø FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER FRP ENCLOSURE TOP W/ ROUND BODY EXTENSION (TRIM FROM BOTTOM FOR FIELD ADJUSTMENT) 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 8"R DEEP BURIAL POLYGON FRP SUMP BODY 2" TEE DISPENSERS TURBINE PUMP WITH SWIFT CHECK VALVE 40 131 80 61 7069 7069 7069 40 56 6 41 42 2" DOUBLE WALL NUPI SMARTFLEX PIPE6 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK500 TA N K S U M P D E T A I L S TANK SUMP DETAIL - PROFILE2 SCALE: NTS TANK SUMP DETAIL - PLAN1 SCALE: NTS TOP OF FIBERGLASS OVERLAY STEEL PLATE PRESSURE LINE LEAK DETECTOR 42"Ø FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER 2" NIPPLE 2" 90° ELBOW TURBINE PUMP 4" RISER TANK MAG SUMP SENSOR W/ SENSOR MOUNTING KIT SEAL OFF (ONE FITTING FOR EACH CONDUIT) EXPLOSION PROOF JUNCTION BOX 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" TERMINATION FITTING WITH TEST PORT 3/4" CONDUIT DOUBLE ENTRY BONDED FITTING 2" FULL PORT BALL VALVE FRP ENCLOSURE TOP W/ ROUND BODY EXTENSION (TRIM FROM BOTTOM FOR FIELD ADJUSTMENT) FIELD BONDED ADHESIVE JOINT (TYP.) PEA GRAVEL BACKFILL 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 3/4" CONDUIT DOUBLE ENTRY BONDED FITTING DEEP BURIAL POLYGON FRP SUMP BODY 3/4" RIGID STEEL CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 5" 3/4" RIGID STEEL CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 2" NIPPLE 42"Ø MANHOLE W/ FRAME AND COVER CONCRETE TANK SLAB 34"Ø WATERTIGHT FRP LID 12"12" 4" MI N . 72 131 40 7069 6867 7069 7069 80 6 139137 4241 TANK LEVEL MONITOR 69 70 133 NOTE: ·FOR ALL FUEL TYPES EXCEPT FOR DIESEL, ALL COMPONENTS MUST BE SCH. 40 STAINLESS STEEL. ·FOR DIESEL, ALL COMPONENTS MUST BE BLACK IRON. ·PRODUCT PIPING CONFIGURATION AND EXIT POINTS MAY VARY. REFER TO TK101. 3/4" RIGID STEEL CONDUIT FOR PUMP POWER 2" UNION 2" TERMINATION FITTING WITH TEST PORT 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" ENTRY FITTING 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" ELBOW TANK LEVEL MONITORPRESSURE LINE LEAK DETECTOR (ABOVE) ℄ TANK TURBINE PUMP DEEP BURIAL POLYGON FRP SUMP BODY 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 42"Ø DOUBLE WALL FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER FRP ENCLOSURE TOP W/ ROUND BODY EXTENSION (TRIM FROM BOTTOM FOR FIELD ADJUSTMENT) TO D I S P E N S E R S 8"R2" SS MALE NPT ADAPTER FITTING 1 61 40 131 69 70 69 70 133 80 56 6 NOTE: ·FOR ALL FUEL TYPES EXCEPT FOR DIESEL, ALL COMPONENTS MUST BE SCH. 40 STAINLESS STEEL. ·FOR DIESEL, ALL COMPONENTS MUST BE BLACK IRON. ·PRODUCT PIPING CONFIGURATION AND EXIT POINTS MAY VARY. REFER TO TK101. 6 2" TERMINATION FITTING WITH TEST PORT 2" ENTRY FITTING PRESSURE LINE LEAK DETECTOR (AB0VE) 2" 90° ELBOW ℄ TANK 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" NIPPLE 2" 90° ELBOW TURBINE PUMP 4" RISER 42"Ø FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER FRP ENCLOSURE TOP W/ ROUND BODY EXTENSION (TRIM FROM BOTTOM FOR FIELD ADJUSTMENT) TO DISPENSERS 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 8"R DEEP BURIAL POLYGON FRP SUMP BODY 80 6 56 6 7069 7069 40 131 4241 NOTE: ·FOR ALL FUEL TYPES EXCEPT FOR DIESEL, ALL COMPONENTS MUST BE SCH. 40 STAINLESS STEEL. ·FOR DIESEL, ALL COMPONENTS MUST BE BLACK IRON. ·PRODUCT PIPING CONFIGURATION AND EXIT POINTS MAY VARY. REFER TO TK101. 2" SS MALE NPT ADAPTER FITTING61 PRESSURE LINE LEAK DETECTOR 42"Ø FRP CONTAINMENT COLLAR, BY TANK MANUFACTURER 2" NIPPLE 2" NIPPLE 2" 90° ELBOW TURBINE PUMP 4" RISER TANK MAG SUMP SENSOR W/ SENSOR MOUNTING KIT SEAL OFF (ONE FITTING FOR EACH CONDUIT) JUNCTION BOX TO DISPENSERS 42"Ø MANHOLE W/ FRAME AND COVER 3/4" CONDUIT DOUBLE ENTRY BONDED FITTING 3/4" RIGID STEEL CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 2" FULL PORT BALL VALVE CONCRETE TANK SLAB 4" MI N . FRP ENCLOSURE TOP W/ ROUND BODY EXTENSION FIELD BONDED ADHESIVE JOINT (TYP.) PEA GRAVEL BACKFILL 22"Ø MANWAY AND COVER W/ (4) 4" NPT TANK FITTING (PLUG UNUSED FITTINGS) 34"Ø WATERTIGHT FRP LID 3/4" RIGID STEEL CONDUIT FOR PUMP POWER 3/4" CONDUIT DOUBLE ENTRY BONDED FITTING 3/4" CONDUIT DOUBLE ENTRY BONDED FITTING DEEP BURIAL POLYGON FRP SUMP BODY 3/4" RIGID STEEL CONDUIT TO INTRINSICALLY SAFE GUTTER AT MONITOR CONTROL PANEL TOP OF FIBERGLASS OVERLAY STEEL PLATE 5" 12" 7069 55 7069 6867 4241 7069 40 131 55 55 55 139137 NOTE: ·FOR ALL FUEL TYPES EXCEPT FOR DIESEL, ALL COMPONENTS MUST BE SCH. 40 STAINLESS STEEL. ·FOR DIESEL, ALL COMPONENTS MUST BE BLACK IRON. ·PRODUCT PIPING CONFIGURATION AND EXIT POINTS MAY VARY. REFER TO TK101. 2" UNION 2" SS MALE NPT ADAPTER FITTING 2" ENTRY FITTING 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" DOUBLE WALL NUPI SMARTFLEX PIPE 61 6 56 6 2" TERMINATION FITTING WITH TEST PORT80 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK501 TA N K S U M P D E T A I L S TANK SUMP DETAIL - PROFILE4 SCALE: NTS TANK SUMP DETAIL - PLAN3 SCALE: NTS TANK SUMP DETAIL - PROFILE2 SCALE: NTS TANK SUMP DETAIL - PLAN1 SCALE: NTS 12 " MI N . MIN. 2' - 0 " 2'-0" TANK BOTTOM TA N K E D G E 12 " 8" WELL CAP KIT SKIRT PEA GRAVEL BACKFILL 24"Ø SONOTUBE 12" BENTONITE SEAL 4" SCH. 40 FACTORY SLOTTED P.V.C. WELL SCREENS (MAXIMUM 0.05" - 0.02" HORIZONTAL SLOTS) PVC CAP 12"Ø MONITORING/ OBSERVATION WELL MANHOLE CONCRETE WARPED UP 1" ABOVE FINISH GRADE CONCRETE SLAB CONCRETE 24 21 19 19 21 12 " MI N . MIN. 2' - 0 " 2'-0" TANK BOTTOM TA N K E D G E 12 " 8" WELL CAP KIT SKIRT PEA GRAVEL BACKFILL 36"Ø SONOTUBE 12" BENTONITE SEAL 12" SCH. 40 FACTORY SLOTTED P.V.C. WELL SCREENS (MAXIMUM 0.05" - 0.02" HORIZONTAL SLOTS) PVC CAP 18"Ø MONITORING/ OBSERVATION WELL MANHOLE CONCRETE WARPED UP 1" ABOVE FINISH GRADE CONCRETE SLAB CONCRETE 22 25 20 20 22 8" MONITORING PROBE CAP ALUMINUM ADAPTOR KIT FACE SEAL ADAPTOR SENSOR LEAD CABLE SPLICED IN JUNCTION BOX 18"Ø MANWAY W/ COVER PAINTED BLACK INSIDE OF TANK FLOAT KIT TOP OF FIBERGLASS OVERLAY STEEL PLATE WARNING WARNING NO FILL NO FILL TANK LEVEL PROBE INSTALLATION KIT TOP CAP 3/8" NPT WEATHERPROOF CORD GRIP 4" ALUMINUM ADAPTER 5' CHAIN W/SPLIT RINGS SPLIT RING ATTACH TO TANK LEVEL MONITOR EXPLOSION PROOF JUNCTION BOX PEA GRAVEL BACKFILL SEAL OFF (ONE FITTING FOR EACH CONDUIT) 3/4" RIGID CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 4" TANK FITTING 3/4" RIGID CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE 4" RISER CONCRETE WARPED UP 1" ABOVE FINISH GRADE CONCRETE SLAB MAG PLUS PROBE FLOAT KIT 22 133132 135134 135134 136 4241 SST CLOSE NIPPLE POWDER COATED FITTING PRODUCT COVER I.D. TAG 4" TANK FITTING STEEL PLATE INSIDE OF TANK 4" RISER PIPE WRAPPED W/ MASTIC TAPE 8" CONC. WARPED UP 1" ABOVE FINISH GRADE PEA GRAVEL BACKFILL DOUBLE WALL SPILL CONTAINER CONC. SLAB VAPOR TOP-SEAL CAP 2" FRP BELL x FEMALE NPT THREADED ADAPTER SWIVEL ADAPTOR 3" FLEXIBLE CONNECTOR ISOLATION JACKET (SHRINK TO FIT) 2" MALE x 2" MALE FLEXIBLE CONNECTOR 2" FRP VENT LINE PRODUCT BUCKET I.D. TAG 11 12 7 15 63 64 7 30 4241 11 11 EXTRACTOR FITTING 16 NOTE: INSTALL THREADED CAP PLUG AT DIESEL COMPARTMENTS ONLY PER TK006 NOTE: USE FIBERGLASS PIPING FOR UG VENT ONLY - FIBERGLASS VENT PIPING USED FOR TO AVOID PIPE "BELLYING" AS TO MITIGATE TRAPPING OF LIQUID IN LINE. SST CLOSE NIPPLE POWDER COATED FITTING PRODUCT COVER I.D. TAG 4" OPEN TELESCOPIC DROP TUBE DIFFUSER 4" TANK FITTING TOP OF FIBERGLASS OVERLAY STEEL PLATE OVERFILL PREVENTION VALVE ASSEMBLY 4" DROP TUBE INSIDE OF TANK DOUBLE WALL FIBERGLASS TANK 4" RISER PIPE WRAPPED W/ MASTIC TAPE 8" CONC. WARPED UP 1" ABOVE FINISH GRADE PEA GRAVEL BACKFILL DOUBLE WALL SPILL CONTAINER CONC. SLAB FILL TOP-SEAL CAP PRODUCT BUCKET I.D. TAG 15 18 4241 2726 2928 18 18 15 15 8" 18" DIA. MANWAY W/ COVER SENSOR LEAD CABLE SPLICED IN JUNCTION BOX DOUBLE WALL FIBERGLASS TANK HYDROSTATIC RESERVOIR SENSOR INTEGRAL RESERVOIR FOR HYDROSTATIC LEAK DETECTION SYSTEM PEA GRAVEL BACKFILL 4" TANK FITTING EXPLOSION PROOF JUNCTION BOX RISER PIPE CAP VENT TUBE ADJUSTABLE LEAD CABLE 4" RISER W/ MASTIC WRAP CONCRETE SLAB CONCRETE WARPED UP 1" ABOVE FINISH GRADE THE MONITORING LIQUID SHALL BE ANTI FREEZE SALT SOLUTION PROVIDED BY TANK MANUFACTURER 3/4" RIGID CONDUIT LOOPED TO JUNCTION BOX OF ADJACENT SENSOR/PROBE SEAL FITTING (ONE FITTING FOR EACH CONDUIT) 4241 23 140 140 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK502 TA N K T O P H A R D W A R E D E T A I L S 1 OBSERVATION WELL DETAIL (4")SCALE: NONE 2 OBSERVATION WELL DETAIL (12")SCALE: NONE 3 TANK LEVEL MONITOR DETAIL SCALE: NONE 4 INTERSTITIAL MONITOR DETAIL SCALE: NONE 5 VAPOR RISER DETAIL SCALE: NONE 6 FILL RISER DETAIL SCALE: NONE 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" TERMINATION FITTING W/ TEST PORT DISPENSER SUMP STABILIZER BAR W/ MOUNTING BRACKET (TYP.) TK 5 0 3 3 90 2" ENTRY FITTING 80 6 56 91 NOTE: ·PROVIDE FLEXIBLE CONNECTORS AND SHEAR VALVE ASSEMBLIES AT PRODUCT CONNECTIONS TO DISPENSERS. ·QUANTITY AND LOCATION OF PRODUCT PIPING MAY VARY. REFER TO TK101 FOR EXACT CONFIGURATION *IF DISPENSER IS NOT 3+1+1* PLUG CKC PRODUCT LINE AT ADAPTER FITTING WITH NPT THREADED PLUG TO ALLOW FOR FUTURE USE. 2" SW 9072 DISPENSER TOP OF CONCRETE, SLOPE AWAY FROM DISPENSER 1" OVER 1'. REF. DTL. 6/TK504 PRODUCT SHEAR VALVE BOLTED TO STABILIZER BAR ASSEMBLY DISPENSER SUMP PEA GRAVEL BACKFILL 1-1/2" x 18" FLEX CONNECTOR MALE SWIVEL x MALE COMPACTED SOIL UNDISTURBED SOIL JUNCTION BOX DISPENSER MAG SUMP SENSOR AT EACH DISPENSER. SPLICE SENSOR LEAD CABLE IN JUNCTION BOX. INSTALL AT LOWEST POINT IN SUMP SEAL FITTING (ONE FITTING FOR EACH CONDUIT) 3/4" RIGID STEEL C0NDUIT LOOPED TO J-BOX AT ADJACENT DISPENSER SUMP (FOR SUMP SENSOR) 92 81 90 93 137 NUPI 2" SW TEE74 NOTE: ·PROVIDE FLEXIBLE CONNECTORS AND SHEAR VALVE ASSEMBLIES AT PRODUCT CONNECTIONS TO DISPENSERS. ·QUANTITY AND LOCATION OF PRODUCT PIPING MAY VARY. REFER TO TK101 FOR EXACT CONFIGURATION *IF DISPENSER IS NOT 3+1+1* PLUG CKC PRODUCT LINE AT ADAPTER FITTING WITH NPT THREADED PLUG TO ALLOW FOR FUTURE USE. NUPI 2" X 1.5" ADAPTER FITTING 60 DISPENSER TOP OF CONCRETE, SLOPE AWAY FROM DISPENSER 1" OVER 1'. REF. DTL. 6/TK504 PRODUCT SHEAR VALVE BOLTED TO STABILIZER BAR ASSEMBLY DISPENSER SUMP PEA GRAVEL BACKFILL 1-1/2" x 18" FLEX CONNECTOR MALE SWIVEL x MALE COMPACTED SOIL UNDISTURBED SOIL JUNCTION BOX DISPENSER MAG SUMP SENSOR AT EACH DISPENSER. SPLICE SENSOR LEAD CABLE IN JUNCTION BOX. INSTALL AT LOWEST POINT IN SUMP SEAL FITTING (ONE FITTING FOR EACH CONDUIT) 3/4" RIGID STEEL C0NDUIT LOOPED TO J-BOX AT ADJACENT DISPENSER SUMP (FOR SUMP SENSOR) 92 81 90 93 137 NUPI 2" SW 9072 NOTE: ·PROVIDE FLEXIBLE CONNECTORS AND SHEAR VALVE ASSEMBLIES AT PRODUCT CONNECTIONS TO DISPENSERS. ·QUANTITY AND LOCATION OF PRODUCT PIPING MAY VARY. REFER TO TK101 FOR EXACT CONFIGURATION *IF DISPENSER IS NOT 3+1+1* PLUG CKC PRODUCT LINE AT ADAPTER FITTING WITH NPT THREADED PLUG TO ALLOW FOR FUTURE USE. NUPI 2" X 1.5" ADAPTER FITTING 60 2" DOUBLE WALL NUPI SMARTFLEX PIPE 2" TERMINATION FITTING W/ TEST PORT DISPENSER SUMP STABILIZER BAR W/ MOUNTING BRACKET (TYP.) TK 5 0 3 4 90 2" ENTRY FITTING 80 6 56 91 NOTE: ·PROVIDE FLEXIBLE CONNECTORS AND SHEAR VALVE ASSEMBLIES AT PRODUCT CONNECTIONS TO DISPENSERS. ·QUANTITY AND LOCATION OF PRODUCT PIPING MAY VARY. REFER TO TK101 FOR EXACT CONFIGURATION *IF DISPENSER IS NOT 3+1+1* PLUG CKC PRODUCT LINE AT ADAPTER FITTING WITH NPT THREADED PLUG TO ALLOW FOR FUTURE USE. 2" SW TEE74 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK503 DI S P E N S E R S U M P D E T A I L S DISPENSER SUMP SECTION (THRU & THRU)43DISPENSER SUMP SECTION (TERMINATION)SCALE: NTS SCALE: NTSDISPENSER SUMP DETAIL (THRU & THRU)21DISPENSER SUMP DETAIL (TERMINATION)SCALE: NTS SCALE: NTS TK 5 0 3 . 1 3 STABILIZER BAR W/ MOUNTING BRACKET (TYP.) PRODUCT PIPING SUMP 2" TERMINATION SECONDARY CONTAINMENT FITTING W/ TEST PORT 90 91 6 60 FROM TANK FRP 90 2" BONDED ENTRY FITTING56 RIGID FRP DOUBLE WALL PRODUCT PIPING TO ADJ DISP. TK 5 0 3 . 1 4 STABILIZER BAR W/ MOUNTING BRACKET (TYP.) PRODUCT PIPING SUMP 2" TERMINATION SECONDARY CONTAINMENT FITTING W/ TEST PORT 90 91 6 60 FROM TANK FRP 90 2" BONDED ENTRY FITTING56 RIGID FRP DOUBLE WALL PRODUCT PIPING PEA GRAVEL BACKFILL COMPACTED SOIL UNDISTURBED SOIL 156 JUNCTION BOX DISPENSER MAG SUMP SENSOR AT EACH DISPENSER. SPLICE SENSOR LEAD CABLE IN JUNCTION BOX SEAL FITTING (ONE FITTING FOR EACH CONDUIT) 3/4" RIGID STEEL C0NDUIT LOOPED TO J-BOX AT ADJACENT DISPENSER SUMP (FOR SUMP SENSOR) DISPENSER SUMP 2" x 18" FLEX CONNECTOR MALE SWIVEL x MALE DISPENSER 90 62 137 2" DOUBLE POPPET SHEAR VALVE PRODUCT PIPE TO DISPENSER (TYP.) 2" STL. UNION (TYP.) 2" FRP TEE NOTE: SET SHEAR POINT OF VALVES TO BE EVEN WITH TOP OF SUMP. SECURE SHEAR VALVES TO SUMP WITH STABILIZER BAR KIT AND U-BOLT PER MANUFACTURER SPECIFICATIONS TOP OF CONCRETE, SLOPE AWAY FROM DISPENSER 1" OVER 1'. REF. DTL. 2/TK505.1 PEA GRAVEL BACKFILL COMPACTED SOIL UNDISTURBED SOIL 156 JUNCTION BOX DISPENSER MAG SUMP SENSOR AT EACH DISPENSER. SPLICE SENSOR LEAD CABLE IN JUNCTION BOX SEAL FITTING (ONE FITTING FOR EACH CONDUIT) 3/4" RIGID STEEL C0NDUIT LOOPED TO J-BOX AT ADJACENT DISPENSER SUMP (FOR SUMP SENSOR) DISPENSER SUMP 2" x 18" FLEX CONNECTOR MALE SWIVEL x MALE DISPENSER 90 62 137 2" DOUBLE POPPET SHEAR VALVE PRODUCT PIPE TO DISPENSER (TYP.) 2" STL. UNION (TYP.) 2" FRP 90 NOTE: SET SHEAR POINT OF VALVES TO BE EVEN WITH TOP OF SUMP. SECURE SHEAR VALVES TO SUMP WITH STABILIZER BAR KIT AND U-BOLT PER MANUFACTURER SPECIFICATIONS TOP OF CONCRETE, SLOPE AWAY FROM DISPENSER 1" OVER 1'. REF. DTL. 2/TK505.1 SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK503.1 DI S P E N S E R S U M P D E T A I L S HSD DISPENSER SUMP DETAIL (TERMINATION)43HSD DISPENSER SUMP DETAIL (THROUGH & THROUGH)SCALE: NTS SCALE: NTSHSD DISPENSER SUMP DETAIL (TERMINATION)21HSD DISPENSER SUMP DETAIL (THROUGH & THROUGH)SCALE: NTS SCALE: NTS Unleaded Price per gallon, All taxes included Plus Price per gallon, All taxes included Premium Price per gallon, All taxes included CK Choice Price per gallon, All taxes included Diesel Price per gallon, All taxes included STRAIGHTENING HOSE BREAKAWAY DEVICE 3/4" HOSE NOZZLE 3/4" SWIVEL CONCRETE DRIVE SLAB RAISED CONCRETE SLAB (SLOPE 1" OVER 1') 88 85 89 87 86 FUEL DISPENSER81 STRAIGHTENING HOSE BREAKAWAY DEVICE 3/4" HOSE NOZZLE 3/4" SWIVEL 83 85 84 82 86 CL STREET SIDE 3'-6" 14 ' - 0 " 3' - 1 1 2"5' - 0 " 3' - 1 1 2" STORE SIDE SE E C A N O P Y P L A N S 5' - 0 " 4' - 0 " 6" PIPE BOLLARD; REF. DTL. 4/TK505 1'-9"1'-9" LIMITS OF TYPICAL FUEL DISPENSER FOOTING (VARIES), VERIFY SIZE PRIOR TO SETTING DISPENSER SUMP BEGIN SLOPING AWAY FROM DISPENSER 2" OUTSIDE LIMITS OF CABINET TO ENSURE NO GAPS BETWEEN DISPENSER AND DRIVE SLAB CL 2" 2" END SLOPED CONCRETE AROUND DISPENSER 3' - 9 " SLOPE UP 1" OVER 1' AROUND DISPENSER 101 76 CANOPY FASCIA ABOVE OPTIONAL MASONRY FINISH, REF. ARCH. STRUCTURAL COLUMN REF. ARCH/CANOPY PLANS (2) 1'-4" Ø CONCRETE FOOTING 2"Ø VENT RISER (TYPICAL), PAINT WHITE STEEL GALVANIZED POSTS SECURED TO 1/4"x3"x4" 2" UNISTRUT TO BE 12 ' - 0 " AB O V E A D J A C E N T P A V E M E N T 2"X2" GALV. UNISTRUT POSTS W/ THREADED CAPS (TYPICAL) ℄℄℄℄ FLEXIBLE BOOTS (TYP.) 2" Ø x 24" FLEX CONNECTOR ASSEMBLY (TYP.) 2" TEE WITH 2" TEST PLUG (TYP. ALL VENT RISERS) 1'-4" 6" 2"Ø FIBERGLASS VENT LINES WITH PROTECTIVE MESH COVERING (TYP.) 1' - 6 " 9' - 6 " 7 63 VARIES1'-4" 1'-4" 9" TYP. 2' - 0 " 3' - 0 " PAINT ALL RISER SUPPORTS, HARDWARE, AND VENT PIPING WHITE 64 VENT CAPS, DO NOT PAINT 71 71 6665 NOTE: ·REFER TO TK101 FOR QUANTITY AND PLACEMENT OF VENT PIPING ON RISER. ·DO NOT MANIFOLD VENTS. EACH TANK TO HAVE A DEDICATED VENT LINE ℄ CAP BOTH SUPPORTS TANK LEVEL STICK UPPER SUPPORT. SECURE 4" U BOLT TO UNISTRUT. 2"x2' PVC FILL STICK HOLDER SECURED TO UNISTRUT. CAP PVC PIPE AT BOTTOM AND DRILL 1/4" HOLE FOR DRAIN. TANK LEVEL STICK MOUNTED TO VENT STACK WHEN NOT IN USE 6" MIN. 9" MIN. 9" MIN. 9" MIN. 2 Ø DOUBLE WALL PIPES 18" MIN. PEA GRAVEL BACKFILL ABOVE PIPES. (VARIES BASED ON PIPE RUNS AND SLOPES) 3'-6" MIN. 6" MIN. BEARING TYP. BOTH SIDES OF TRENCH 6" 6" MIN. PEA GRAVEL BED UNDER PIPES REF. CIVIL FOR PAVEMENT DESIGN 4'-6" VARIES BASED ON WIDTH OF TRENCH WHICH IS DETERMINED BY NUMBER OF PRODUCT PIPES KEYWAYKEYWAY NOTE: MIN. SPACING MUST BE ADHERED TO PIPE. (MANUFACTURERS REQUIREMENT) FILTER FABRIC (TYP FOR ALL TRENCHES) WIDTH OF TRENCH FOR (4) PRODUCT LINES 6" MIN. 6" DIA. STEEL PIPE GUARD (FILL WITH CONCRETE) 6" 3' - 0 " 4" 24" DIA. 3' - 1 1 1 2" 6" 4' - 0 " GRAY BOLLARD COVER; REF. ARCH CONCRETE BASE ROUNDED CONCRETE TOP 4' - 2 " 7'-0" MIN. VARIES BASED ON QTY. OF VENTS 1'-0"4'-11" MIN. VARIES BASED ON QTY. OF VENTS 1'-0" 1' - 0 " 2' - 2 " 1' - 0 " RISER POST & FOUNDATION (TYP, 2) 6" CONCRETE PAD 1'-0"5'-0" MIN. VARIES BASED ON QTY. OF VENTS 1'-0" 6" BOLLARD; REF DTL. 4/TK504 VENT RISERS; REF ELEVATION VIEW 6" CURB; REF. CIVIL PLAN VIEW 9" TYP. 1'-4"1'-4" REGULAR E0 UNLEADED: LID PAINTED WHITE WITH "0" PAINTED IN BLACK MIDGRADE E0 UNLEADED: LID PAINTED BLUE WITH "0" PAINTED IN BLACK 0 0 PREMIUM E0 UNLEADED: LID PAINTED RED WITH "0" PAINTED IN BLACK0 REGULAR E10 UNLEADED: LID PAINTED WHITE MIDGRADE E10 UNLEADED: LID PAINTED BLUE PREMIUM E10 UNLEADED: LID PAINTED RED E15 FUEL: LID PAINTED BROWN WITH "E15" PAINTED IN BLACKE15 E85 FUEL: LID PAINTED BROWN WITH "E85" PAINTED IN BLACKE85 ON-ROAD ULTRA LOW SULFUR DIESEL: LID PAINTED YELLOW ON-ROAD ULTRA LOW SULFUR DIESEL B20% BIODEISEL: LID PAINTED YELLOW WITH "B20" PAINTED IN BLACKB20 OFF-ROAD ULTRA LOW SULFUR DIESEL: LID PAINTED YELLOW WITH "OFF" PAINTED IN REDOFF OFF-ROAD ULTRA LOW SULFUR DIESEL: LID PAINTED YELLOW WITH "OFF" PAINTED IN RED AND "B20" PAINTED IN BLACK OFFB20 BIODIESEL B100/B99.9: LID PAINTED LIGHT BLUE DIESEL EXHAUST FLUID: PAINT DARK BLUE MONITORING WELL: LID PAINTED WHITE WITH BLACK TRIANGLE VAPOR RECOVERY: LID PAINTED ORANGE FUEL OIL #2: LID PAINTED GREEN WITH "2" PAINTED IN BLACK2 KEROSENE: LID PAINTED BROWN USED OIL: LID PAINTED GRAY SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK504 FU E L S Y S T E M D E T A I L S PIPE TRENCH5 SCALE: 1/4" = 1'-0"DISPENSER ISLAND DETAIL6 SCALE: 1/2" = 1'-0"3 DISPENSER ELEVATION 1 TYPICAL FREE STANDING VENT RISER SCALE: 1/2" = 1'-0" API COLOR CODES FOR MANWAYS2 SCALE: 1/2" = 1'-0"PIPE BOLLARD DETAIL4 SCALE: 3/4" = 1'-0" CONCRETE DRIVE SLAB RAISED CONCRETE SLAB (SLOPE 1" OVER 1') STRAIGHTENING HOSE BREAKAWAY DEVICE 1" HOSE DIESEL NOZZLE 1" SWIVEL169 170 168 167 166 DIESEL Price per gallon, All taxes included Unleaded Gasoline HIGH FLO DIESEL DISPENSER 156 LIMITS OF TYPICAL FUEL DISPENSER FOOTING (VARIES), VERIFY SIZE PRIOR TO SETTING DISPENSER SUMP BEGIN SLOPING AWAY FROM DISPENSER 2" OUTSIDE LIMITS OF CABINET TO ENSURE NO GAPS BETWEEN DISPENSER AND DRIVE SLAB 2" 2" END SLOPED CONCRETE AROUND DISPENSER SLOPE UP 1" OVER 1' AROUND DISPENSER 76 OPTIONAL MASONRY FINISH, REF. ARCH. STRUCTURAL COLUMN REF. ARCH/CANOPY PLANS 6" PIPE BOLLARD; REF. DTL. 4/TK504 CL 3'-6" 20 ' - 0 " 3' - 1 1 2"5' - 0 " 3' - 1 " 5' - 0 " CL 3' - 9 " CANOPY FASCIA ABOVE STREET SIDE 3' - 1 1 2" 5' - 0 " 3' - 1 " 5' - 0 " 3' - 9 " CL CL 2" 2" SE E C A N O P Y P L A N S STORE SIDE 6" 1'-4" 3' - 6 " 1'-4" x 1'-4" x 3'-6" CONCRETE FOOTING 2" x 2" GALVANIZED STEEL PIPE SUPPORT LIFT HERE TO SHUT DOWN FUELING SYSTEM STOP FUEL PUMPSHUT DOWN LIFT COVER PUSH BUTTON 3/4" CONDUIT SEAL OFF FITTING CAP 4' - 0 " EMERGENCY STOP BUTTON TO BE MOUNTED BETWEEN 42-48 INCHES ABOVE GRADE NATURAL GROUND SHEET NO. 1130 WEST WARNER ROAD SUITE B TEMPE, AZ 85284 602-728-8000 REVISIONS DATE KI L L I O N R D S E & W Y E L M A V E YE L M , W A 9 8 5 9 7 Drawn Checked TLH SW PROTOTYPE VERSION # CI R C L E K S T O R E PR O J E C T : # PROJECT #:A24-117 FGA22.01.24 06/22/2022 SH E E T T I T L E : DATE Documents prepared by The Dimension Group are to be used only for the specific project and specific use for which they are intended. Any extension of use to other projects, by owner or any other party, without the expressed, written consent of The Dimension Group is done at the user's own risk. If used in a way other than that specifically intended, user will hold The Dimension Group harmless from all claims and losses. AR C H I T E C T U R E C I V I L E N G I N E E R I N G M E P E N G I N E E R I N G 10 7 5 5 S A N D H I L L R O A D , D A L L A S , T E X A S 7 5 2 3 8 TE L : 2 1 4 - 3 4 3 - 9 4 0 0 ww w . d i m e n s i o n g r p . c o m 09/04/24 TK505 FU E L S Y S T E M D E T A I L S SCALE: 1/4" = 1'-0"SG HSD DISPENSER ISLAND DETAIL1 2 HSD DISPENSER DETAIL SCALE: 1/2" = 1'-0"3 SCALE: 1/2" = 1'-0"EMERGENCY STOP BUTTON PEDESTAL