02 Equipment Submittals
HVAC Submittals Indigo Urgent Care Tenant Improvement 937 W Yelm Ave Yelm, WA 98597 ASEI Job No. 4466 December 16, 2024 Prepared by: 3602 S. Pine St. Tacoma, WA 98409 Phone (253) 572-9484 Project Manager: Nick Rollins Table of Contents Energy Recovery Ventilator ...................................................................................Section 1 Lossnay Ductless Split System .............................................................................................Section 2 Mitsubishi Zone Dampers .........................................................................................................Section 3 Zonex Thermostat ..............................................................................................................Section 4 Honeywell Grilles, Registers, and Diffusers .............................................................................Section 5 Titus Section 1 Energy Recovery Ventilator Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Job Name: System Reference:Date: GENERAL FEATURES • Lossnay® cross-flow energy recovery core • Minimal cross contamination between entering and leaving air streams • Stand-alone remote controller (PZ-62DR-EA) • M-NET Connectivity • External input bypass damper control • Stand alone or interlocks connects with all Mitsubishi Electric products • Four fan speeds • High efficiency DC Motor • Standard MERV 7 non-woven fabric filter, washable fiber • Optional high-efficiency MERV 14 and MERV 16 filters Specifications System Unit Type LGH-F380RVX2-E Capacity CFM [m3/h]380 [646] Power source Voltage, Phase, Hertz 208/230V, 1-phase, 60 Hz Power Consumption kW 0.165 - 0.34 Current A 0.02 - 0.065 Starting Current A 6.1 MCA A 3.9 Maximum Overcurrent Protection (MOCP)A 15 Fan Air Volume CFM [m3/h]95-190-285-380 [161-323-484-646] External Static pressure in.WG 0.06–0.22–0.48–0.86 Exchange Efficiency Temperature %82-75-69.5-65 Enthalpy Cooling %68.0-60.0- 53.5- 49.0 Enthalpy Heating %78.0-71.0-65.5-61.0 External Finish Galvanized steel sheet External Dimensions In. [mm]39-13/32 x 42 x 15-29/32 [1,001 x 1,066 x 404] Net weight Lbs [kg]90 [41] Energy Transfer Mechanism Lossnay® Core Heat Exchange Material Partition, spacing plate-cellulose fiber membrane Heat Exchange System Air-to-air total heat (sensible heat + latent heat) exchange, no moving parts Blower Type 8-3/4 In. diameter centrifugal fan Motor Type EC Motor Entering Air Temperature Operation Range °F [°C]14 to 104 [-10 to 40] Sound pressure level dB(A)19.0–24.0–31.0-38.0 LGH-F380RVX2-EENERGY RECOVERY VENTILATION Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. ACCESSORIES: LGH-F380RVX2-E Wired Remote Controller Lossnay® ERV Remote Controller PZ-62DR-EA Control Interface Signal Output Terminal PZ-4GS-E Duct Accessories Duct Silencer PZ-200SS-E Filter MERV 14 Filter PZ-65RFP-E MERV 16 Filter PZ-65RFP2-E MERV 7 Filter (Included) PZ-65RF9-E Remote Sensor CO2 Sensor, Built-In PZ-70CSB-E CO2 Sensor, Wall Mount PZ-70CSW-E Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. FORM# LGH-F380RVX2-E - 202304 1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com UNIT SCALE inch(mm)N.T.S DIMENSIONS: LGH-F380RVX2-E Section 2 Ductless Split System Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Job Name: System Reference:Date: Indoor Unit PKA-A12LA Outdoor Unit PUZ-A12NKA7 INDOOR UNIT FEATURES • Selectable high sensible vs high latent capacity mode • UL 60335-2-40 compliant • Sleek, compact design • Simple installation • Airflow direction control • Auto fan mode • Suitable for: server rooms, daycare centers, classrooms, churches, small offices, and more • Multiple control options available: ○kumo cloud® smart device app for remote access ○Third-party interface options ○Wired or wireless controllers OUTDOOR UNIT FEATURES • Variable speed INVERTER-driven compressor • Pre-charged with refrigerant volume for piping length up to 70 ft • Low ambient cooling down to 0°F providing 100% capacity • 24-hour continuous operation (cooling mode) • High pressure protection • Fast restart • Superior energy and operational efficiency • Seacoast protection* ○External Outer Panel: Phosphate coating + Acrylic-Enamel coating ○Fan Motor Support: Epoxy resin coating (at edge face) ○Separator Assembly Valve Bed: Epoxy resin coating (at edge face) ○Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants. ○Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing *Seacoast protection standard from 2022 production PKA-A12LA & PUZ-A12NKA712,000 BTU/H WALL MOUNT12,000 BTU/H HEAT PUMP UNIVERSAL OUTDOOR Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. SPECIFICATIONS: PKA-A12LA & PUZ-A12NKA7 test Cooling at 95°F1 Maximum Capacity BTU/H 12,000 Rated Capacity BTU/H 12,000 Minimum Capacity BTU/H 4,400 Maximum Power Input W 900 Rated Power Input W 900 Moisture Removal Pints/h 2.7 Sensible Heat Factor 0.88 Power Factor [208V / 230V]%92.5 / 92.5 Heating at 47°F2 Maximum Capacity BTU/H 18,000 Rated Capacity BTU/H 14,000 Minimum Capacity BTU/H 4,400 Maximum Power Input W 1,600 Rated Power Input W 1,030 Power Factor [208V / 230V]%92.5 / 92.5 Heating at 17°F3 Maximum Capacity BTU/H 10,600 Rated Capacity BTU/H 10,600 Maximum Power Input W 1,190 Rated Power Input W 1,190 Efficiency SEER | SEER2 21.0 | 21.3 EER1 | EER21 13.3 | 13.3 HSPF [IV] | HSPF2 [IV]10.2 | 10.2 COP at 47°F2 3.9 COP at 17°F at Maximum Capacity3 2.6 Electrical Voltage, Phase, Frequency 208/230, 1, 60 Guaranteed Voltage Range V AC 198 - 253 Voltage: Indoor - Outdoor, S1-S2 V AC 208/230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Short-circuit Current Rating [SCCR]kA 5 Recommended Fuse/Breaker Size (Oudoor)A 15 Recommended Wire Size [Indoor - Outdoor]AWG 14 Power Supply Indoor unit is powered by the outdoor unit Indoor Unit MCA A 1.0 Fan Motor Full Load Amperage A 0.19 Fan Motor Type DC Motor Airflow Rate at Cooling, Dry CFM 265–310–385–455 Airflow Rate at Cooling, Wet CFM 215–255–320–375 Airflow Rate at Heating, Dry CFM 265–290–325–385 Sound Pressure Level [Cooling]dB[A]34–39–44–48 Sound Pressure Level [Heating]dB[A]34–37–40–43 Drain Pipe Size In. [mm]5/8 [16] Condensate Lift Mechanism, Maximum Distance In. [mm]19-11/16 [850] Coating on Heat Exchanger — External Finish Color White Munsell 0.7PB 9.2/0.4 Unit Dimensions W x D x H: In. [mm]35-23/64 x 9-11/32 x 11-25/32 [898 x 237 x 299] Package Dimensions W x D x H: In. [mm]38-3/16 x 13-25/64 x 14-11/64 [970 x 340 x 360] Unit Weight Lbs. [kg]28 [12.7] Package Weight Lbs. [kg]32 [14.5] Indoor Unit Operating Temperature Range Cooling Intake Air Temp [Maximum / Minimum]*°F 90 DB, 73 WB / 66 DB, 59 WB Heating Intake Air Temp [Maximum / Minimum]°F 82 DB / 50 DB NOTES: AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB Select high sensible versus high latent capacity mode via function setting mode 08, “Fan speed” (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): • ”High ceiling” mode = high sensible capacity »Mode 08, setting 3 (factory default) •”Standard” mode = high latent capacity »Mode 08, setting 2 *Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information. **Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. ***Blue Fin Coating Standard from 2022 production: • PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** • PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU***** SPECIFICATIONS: PKA-A12LA & PUZ-A12NKA7 test Outdoor Unit MCA A 11.0 MOCP A 28 Fan Motor Full Load Amperage A 0.5 Fan Motor Output W 46 Airflow Rate [Cooling / Heating]CFM 1590 / 1590 Refrigerant Control LEV Defrost Method Reverse Cycle Coating on Heat Exchanger Blue Fin Coating*** Sound Pressure Level, Cooling1 dB(A)44 Sound Pressure Level, Heating2 dB(A)46 Compressor Type INVERTER-driven twin rotary Compressor Model SNB092FQCMC Compressor Rated Load Amps A 7 Compressor Locked Rotor Amps A 12.0 Compressor Oil [Type // Charge]oz.FV50S // 12 External Finish Color Ivory Munsell 3Y 7.8/1.1 Base Pan Heater N/A Unit Dimensions W x D x H: In. [mm]31-13/16 (2+7/16) x 11-13/16 x 24-13/16 [809 (+62) x 300 x 630] Package Dimensions W x D x H: In. [mm]37-1/16 x 16-3/16 x 27-7/16 [941 x 411 x 697] Unit Weight Lbs. [kg]93 [42] Package Weight Lbs. [kg]104 [47] Outdoor Unit Operating Temperature Range Cooling Air Temp [Maximum / Minimum]*°F 115 DB / 0 DB Heating Air Temp [Maximum / Minimum]°F 70 DB, 59 WB / 12 DB, 14 WB Heating Thermal Lock-out / Re-start Temperatures**°F 8 / 12 Refrigerant Type R410A Pre-Charged Refrigerant Amount Lbs, oz 4.0, 7.0 Maximum Pre-Charged Piping Length Ft. [m]70.0 [21.0] Additional Refrigerant Charge Per Additional Piping Length oz./Ft. [g/m]0.2 [19] Piping Gas Pipe Size O.D. [Flared]In.[mm]1/2 [12.7] Liquid Pipe Size O.D. [Flared]In.[mm]1/4 [6.35] Maximum Piping Length Ft. [m]100 [30] Maximum Height Difference Ft. [m]100 [30] Maximum Number of Bends 15 NOTES: AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB Select high sensible versus high latent capacity mode via function setting mode 08, “Fan speed” (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): • ”High ceiling” mode = high sensible capacity »Mode 08, setting 3 (factory default) •”Standard” mode = high latent capacity »Mode 08, setting 2 *Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. • Refer to wind baffle documentation for further information. **Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. ***Blue Fin Coating Standard from 2022 production: • PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** • PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU***** Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. INDOOR UNIT ACCESSORIES: PKA-A12LA Control Interface 3-Pin Connector PAC-715AD BACnet® and Modbus® Interface PAC-UKPRC001-CN-1 IT Extender PAC-WHS01IE-E kumo station® for kumo cloud® PAC-WHS01HC-E Thermostat Interface PAC-US444CN-1 Thermostat Interface PAC-US445CN-1 USNAP Adapter PAC-WHS01UP-E Wireless Interface for kumo cloud® PAC-USWHS002-WF-2 Remote Sensor Flush Mount Remote Temperature Sensor PAC-USSEN002-FM-1 Flush Mount Temperature Sensor PAC-USSEN001-FM-1 Remote Temperature Sensor PAC-SE41TS-E Wireless temperature and humitity sensor for kumo cloud® PAC-USWHS003-TH-1 Wired Remote Controller Deluxe Wired MA Remote Controller† PAR-40MAAU Simple Ductless Wired Remote Controller PAC-SDW01RC-1 Simple MA Remote Controller† PAC-YT53CRAU-J Touch MA Controller† PAR-CT01MAU-SB Wireless Remote Controller kumo touch™ RedLINK™ Wireless Controller MHK2 Lockdown bracket for remote controller RCMKP1CB Wireless MA Remote Controller PAR-FL32MA-E Condensate Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] X87-721 Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H X86-003 Blue Diamond Sensor Extension Cable — 15 Ft. C13-103 Drain Pan Level Sensor/Control SS610E Fascia Kit for MicroBlue Pump, mounts the MicroBlue and sensor directly beneath indoor unit T18-016 Refco Condensate Pump (100-240 VAC) GOBI-II Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H COMBI Sauermann Condensate Pump SI30-230 Disconnect Switch (30A/600V/UL) [fits 2” X 4” utility box] - Black TAZ-MS303 (30A/600V/UL) [fits 2” X 4” utility box] - White TAZ-MS303W Lineset 100’ x 1/4” x 100’ / 1/2” Lineset (Twin-Tube Insulation) MLS141212T-100 15’ x 1/4” x 15’ / 1/2” Lineset (Twin-Tube Insulation) MLS141212T-15 30’ x 1/4” x 30’ / 1/2” Lineset (Twin-Tube Insulation) MLS141212T-30 50’ x 1/4” x 50’ / 1/2” Lineset (Twin-Tube Insulation) MLS141212T-50 65’ x 1/4” x 65’ / 1/2” Lineset (Twin-Tube Insulation) MLS141212T-65 Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. OUTDOOR UNIT ACCESSORIES: PUZ-A12NKA7 Air Outlet Guide Air Outlet Guide PAC-SJ07SG-E Centralized Drain Pan Centralized Drain Pan PAC-SG63DP-E Drain Pan PAC-SG64DP-E Control/Service Tool Control/Service Tool PAC-SK52ST M- & P-Series Maintenance Tool Cable Set M21EC0397 USB/UART Conversion Cable (Required for all laptop connection) M21EC1397 Drain Socket Drain Socket MAC-871DS Hail Guards Hail Guard HG-A5 M-NET Converter M-NET Converter PAC-SJ96MA-E Mini-Split Wire 14 Gauge, 4 wire MiniSplit Cable—250 ft. roll S144-250 14 Gauge, 4 wire MiniSplit Cable—50 ft. roll S144-50 16 Gauge, 4 wire MiniSplit Cable—250 ft. roll S164-250 16 Gauge, 4 wire MiniSplit Cable—50 ft. roll S164-50 Mounting Pad Condensing Unit Mounting Pad: 16” x 36” x 3” ULTRILITE1 Stand 18” Single Fan Stand QSMS1801M 24” Single Fan Stand QSMS2401M Condenser Wall Bracket QSWB2000M-1 Condenser Wall Bracket - Stainless Steel Finish QSWBSS Outdoor Unit Stand — 12” High QSMS1201M Wind Baffle Front Wind Baffle WB-PA4 Rear Wind Baffle WB-RE4 Side Advanced Wind Baffle WB-SD4 Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Unit: inch (mm) 19/32()15 0 4-59/64()125 6-1/2()165 9-1/8()231.7 10-51/64()274.2 12-41/64()321.2 13-25/32()350.2 14-21/64()364 19/32()15 4-59/64()125 6-1/2()165 () 10-51/64 231.7 11-15/64()285.2 12-41/64()321.2 13-25/32()350.2 14-21/64()364 9/ 3 2 ( ) 7.2 0 5/ 8 ( ) 16 1- 1 7 / 6 4 ( ) 32 . 2 2- 6 3 / 6 4 ( ) 76 4- 7 / 3 2 ( ) 10 7 . 2 5- 1 3 / 6 4 ( ) 13 2 . 2 6- 3 / 1 6 ( ) 15 7 . 2 9- 4 1 / 6 4 ( ) 24 4 . 7 10 - 1 / 8 ( ) 25 7 . 2 1- 4 9 / 6 4 ( ) 44 . 7 4- 2 3 / 3 2 ( ) 11 9 . 7 11-1/4()287.2 0 15-13/32()391.5 17-43/64()449 5-5/64()128.8 5-37/64()141.8 11-1/8()282.5 () 17-43/64 449 9- 1 / 1 6 ( ) 23 0 0 10 - 2 5 / 3 2 ( ) 27 4 63 / 6 4 () 25 2- 3 / 4 ( ) 69 . 7 4- 5 5 / 6 4 ( ) 12 3 . 5 6- 3 1 / 3 2 ( ) 17 7 . 2 2- 1 / 4 ( ) 57 . 2 3- 1 5 / 6 4 ( ) 82 . 2 7- 1 5 / 3 2 ( ) 18 9 . 7 13 / 6 4 ( 5 ) 20 - 6 3 / 6 4 ( 5 3 3 ) ( L I Q U I D P I P E ) 17 - 2 3 / 3 2 ( 4 5 0 ) ( G A S P I P E ) 1- 5 9 / 6 4 ( 4 9 ) 25 - 1 9 / 3 2 ( 6 5 0 ) 7- 5 3 / 6 4 ( 1 9 9 ) 35 - 2 3 / 6 4 ( 8 9 8 ) 7- 1 / 6 4 ( 1 7 8 ) 7- 9 / 1 6 ( 1 9 2 ) 11-25/32(299) 59 / 6 4 () 23 . 5 63 / 6 4 () 25 8-11/32()212 9-3/8()238 22 - 4 3 / 6 4 ( 5 7 6 ) 10 - 6 3 / 6 4 ( 2 7 9 ) 10 - 6 3 / 6 4 ( 2 7 9 ) 9- 1 1 / 3 2 ( 2 3 7 ) 6- 1 9 / 6 4 ( 1 6 0 ) (163) 6-27/64 10 - 1 5 / 6 4 ( 2 6 0 ) M I N . 5- 2 9 / 3 2 ( 1 5 0 ) M I N . 1- 3 1 / 3 2 ( 5 0 ) M I N . 1- 2 1 / 3 2 ( 5 0 ) 3- 2 7 / 6 4 ( 8 7 ) (67) 2-41/64 2- 9 / 1 6 ( 6 5 ) 25/64(10) (47) 1-27/32 (59) 2-21/64 (70) 2-3/4 (50) 1-31/32 25/64(10) 2- 9 / 1 6 ( 6 5 ) 3/ 4 ( 1 9 ) 2- 3 / 4 ( 7 0 ) 1- 6 1 / 6 4 ( 4 9 . 5 ) (67) 2-41/64 29×13/64(5.1HOLE) 5× 23/6 4 ( 9 HOLE ) 4× 11/64( 4.3H O L E ) () 15-29/64 392.5 F 5- 4 5 / 6 4 ( 1 4 5 ) 1-59/64(49) 1-31/32(50) MIN. (250) 9-27/32 MIN. E SL E E V E TH R O U G H H O L E 2- 6 1 / 6 4 ( 75 ) 2- 6 1 / 6 4 – 3- 5 / 3 2 ( 75 – 80 ) RE F R I G E R A N T PI P I N G LI Q U I D P I P E 1/ 4 ( 6. 3 5 ) GA S P I P E 1/ 2 ( 12 . 7 ) DR A I N H O S E CO N N E C T I O N 5/ 8 ( 16 ) IN S U L A T I O N 1- 9 / 6 4 ( 29 ) F WI T H O P T I O N A L DR A I N P U M P 2- 2 3 / 6 4 ( 6 0 ) OR L E S S MO R E T H A N 2- 2 3 / 6 4 ( 6 0 ) E MI N . 9/ 3 2 ( 7 ) MI N . 2- 2 3 / 6 4 ( 6 0 ) MI N . 9- 2 7 / 3 2 ( 2 5 0 ) A B C D IN D O O R U N I T IN S T A L L A T I O N P L A T E RE Q U I R E D S P A C E ( I N D O O R U N I T ) AI R I N L E T AI R O U T L E T IN S T A L L A T I O N P L A T E TE R M I N A L B L O C K F O R I N D O O R / O U T D O O R C O N N E C T I N G L I N E MA - R E M O T E C O N T R O L L E R T E R M I N A L B L O C K UN D E R P I P I N G C U T O U T A R E A UN D E R P I P I N G C U T O U T A R E A RE F R I G E R A N T P I P E , D R A I N P I P E RE F R I G E R A N T P I P E , D R A I N P I P E LE F T P I P I N G C U T O U T A R E A RE F R I G E R A N T P I P E , D R A I N P I P E RI G H T P I P I N G C U T O U T A R E A RE F R I G E R A N T P I P E , D R A I N P I P E RE C E I V E R OP E R A T I N G L A M P ( G R E E N ) ST A N D B Y L A M P ( O R A N G E ) AU T O V A N E S LO U V E R S ( M A N U A L ) TO P FR O N T FR O N T ( O P E N T H E G R I L L E ) BO T T O M LE F T RI G H T EM E R G E N C Y O P E R A T I O N S W I T C H ( H E A T ) EM E R G E N C Y O P E R A T I O N S W I T C H ( C O O L ) TE M P O R A R I L Y F I X I N G H O L E DR A I N H O S E B DE T A I L S O F C U T O U T FO R P I P I N G H O L E A D C IN CASE OF LEFT PIPING,LEFT BACK PIPING,2-11/64(55) MIN. OR OPTIONAL DRAIN PUMP INSTALLATION,2-61/64(75) MIN. IN C A S E O F O P T I O N A L DR A I N P U M P I N S T A L L A T I O N , 13 - 2 5 / 3 2 ( 3 5 0 ) M I N . 1. F O R C E I L I N G C O R N I C E : C O N S I D E R T H E D I M E N S I O N F O R I N S T A L L A T I O N . 2. M O U N T I N G B O L T F O R I N S T A L L A T I O N P L A T E : M 1 0 O R W 3 / 8 T A P P I N G S C R E W : N O M I N A L D I A M E T E R • • • 5 / 3 2 ( 4 ) L E N G T H • • • 6 3 / 6 4 ( 2 5 ) M I N SC R E W T I G H T A T I N S T A L L A T I O N P L A T E H O L E { 1 1 / 6 4 ( 4 . 3 ) } O N T H E U P P E R A N D L O W E R S I D E E V E N L Y . D O N O T S C R E W T I G H T O N L Y I N L I N E . 3. 4. L E F T P I P E : C O N N E C T D R A I N H O S E T O C O N N E C T I O N P O R T O N T H E L E F T S I D E O F D R A I N P A N . EX C H A N G E D R A I N H O S E A N D R U B B E R C A P A N D B U T T T H E M A G A I N S T D R A I N P O R T . 5. D R A I N P I P E E F F E C T I V E L E N G T H • • • 1 9 - 1 1 / 1 6 ( 5 0 0 ) WA L L H O L E 2- 6 1 / 6 4 ( 75 ) FO R R I G H T B A C K P I P I N G WA L L H O L E 2- 6 1 / 6 4 ( 75 ) FO R R I G H T B A C K C O N D I T C A B L E WA L L H O L E 2- 6 1 / 3 4 ( 75 ) FO R L E F T B A C K P I P I N G OP E R A T I N G R A N G E O F TH E H O R I Z O N T A L V A N E INDOOR UNIT DIMENSIONS: PKA-A12LA FORM# PKA-A12LA & PUZ-A12NKA7 - 202304 1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Unit: mm<in> Air discharge Air intake Air intake oval hole2-10×21 drain holeø42 2-U Shaped notched holes (Foundation Bolt M10<W 3/8>) (Foundation Bolt M10<W 3/8>) 33 0 <1 3 > 30 0 < 11 -1 3 / 1 6 > 40 <1-19/32> 404.5<15-15/16> 48 <1 - 2 9 / 3 2 > 36 0 < 1 4 - 3 / 1 6 > 32 . 5< 1- 9 / 3 2 > 500<19-11/16> Min.500mm<19-11/16>Min.100mm <3-15/16> Service port FLAREɹ 12.7 (1/2F)Connection forgas pipe FLAREɹø ø 6.35 (1/4F)Connection forliquid pipe Service panelfor charge plug Service panel Earth terminal Te rminal connectionLeft ... Power supply wiringRight ... Indoor/Outdoor wiring 23.2<15/16> 99 . 5 < 3 - 1 5 / 1 6 > 16 4 . 5< 6- 1 / 2 > 49 2 <1 9 - 3 / 8 > 185.5<7-5/16> 4 3 ° 3 5 ° 2-ø 22.2<7/8> 1/2 conduit hole Installation bolt pitch Handle for moving 22 <7/8> 32 0 <1 2 - 5 / 8 > 809 <31-7/8>62 <2-15/32> 154.5 <6-3/32> 310<12-7/32> 8. 5< 11 /3 2 > 22.3<29/32> 63 0 <2 4 - 1 3 / 1 6 > Min.100mm<3-15/16> Ba s i c a l l y o p e n Min.350mm <13-25/32> Ma x . <Foundation bolt height> 18 mm < 2 3 / 3 2 > Free space around the outdoor unit(basic example) 100mm<3-15/16> or more as long asno obstacle is placed on therear and right-and-left sidesof the unit 2 sides should be open in the right, left and rear side. Please secure the unit firmlywith 4 foundation (M10<W3/8>) bolts.(Bolts, washers and nut must be purchased locally). FOUNDAT ION BOLT S Piping and wiring connection can be made from the rear direction only. PIPING-WIRING DIRECTION FOUNDAT ION OUTDOOR UNIT DIMENSIONS: PUZ-A12NKA7 Job Name: System Reference:Date: Specifications are subject to change without notice. © 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Model: PAR-41MAAU Deluxe MA Remote Controller • ON/OFF -Switches between ON and OFF. •Operation mode switching -Switches between Cool/Dry/Fan/Auto/Setback/Heat. •Hold -Switches between enable and disable the Hold function. -If the Hold function is enable, the following functions will be prohibited. -ON/OFF timer/Schedule (Weekly timer) /Auto return/Auto-OFF timer •Temperature setting -Changes the set temperature. -Set temperature range varies depending on the indoor unit model. •Fan speed setting -Changes fan speed. -Available fan speeds vary depending on the model. •Air flow direction setting *1 -Changes airflow direction. -Available airflow directions vary depending on the model. •Louver setting *1 -Switches between louver ON/OFF. •Ventilation equipment control -Interlocked setting and interlocked operation setting with City Multi Lossnay units can be performed. -The Stop/Low/High settings of the ventilation equipment can be controlled. •Main display mode setting -The Main display can be displayed in two different modes: “Full” and “Basic.” •B&W inversion -The colors of the display can be inverted, turning white background to black and black characters to white. OPERATION/DISPLAY FULL VIEW BASIC VIEW •(NEW) View Energy Consumption Data for M- & P-Series *1 -Hourly: Displays the hourly energy consumption for the last 31-day period. -Daily/Monthly: Displays the Daily or Monthly energy consumption for the last 14-month period. •(NEW) MASS Save Function *1 -Select the outdoor air temperatures at which outdoor unit operation will be enabled and disabled: enable on rise, disable on fall. -Select the outdoor air temperatures at which backup heater operation will be enabled and disabled: enable on fall, disable on rise. •Clock *2 -Date (year/month/day) and time (hour/minute) can be set. -The set time as well as the day of the week will be displayed on the Main display. -It is also possible for the time to not display on the main display. -The clock can be displayed in 12-hour format (AM/PM before or after the time) and 24- hour format. •Daylight saving time -The start/end time for daylight saving time can be set. -The daylight saving time function will be activated based on the setting contents. •Room temp. display -The room temperature display can be enabled or disabled. •Error information -When an error occurs, an error code and the unit address appear. -The air-conditioning unit model, serial number, and contact number can be set to appear when an error occurs. (The above information needs to be entered in advance.) •Filter information -A filter sign will appear when it is time to clean the filter. •Remote controller information -The version of the remote controller can be checked. *1 This function is active only for the units that support the function. *2 The clock is accurate within 45 seconds per month (at the temperature of 77°F [25ºC]). The clock is backed up for 3 days. Specifications are subject to change without notice. © 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Model: PAR-41MAAU SYSTEM EXAMPLE *When a PAR-41MAAU is connected to a group, no other MA remote controllers can be connected to the same group. Deluxe MA remote controller Non-polarized2-wire Non-polarized2-wire Deluxe MA remote controller SCHEDULE AND TIMER SETTING • Timer -ON/OFF timer ◦Turns ON and OFF daily at a set time. ◦Time can be set in 5-minute increments. ◦It is also possible to set the ON time only or the OFF time only. -Auto-OFF timer ◦Turns off the unit after a certain period of operation. ◦Operation time can be set to a value from 30 to 240 minutes in 10-minute increments. • Weekly timer -Weekly ON/OFF times and set temperatures can be set. -Time can be set in 5-minute increments. Up to 8 schedule patterns can be set per day of the week. -Not valid when the ON/OFF timer is set. RESTRICTION SETTINGS • Allows/disallows local operation -The following operation can be prohibited by applying certain settings on the centralized controller: ON/OFF, operation mode, set temperature, filter sign reset, air direction, fan speed and timer. -While an operation is prohibited, the operation icon lights up (only on the Main display in the “Full” mode). • Operation lock -The following operations can be prohibited: Sensing Location, ON/OFF, Mode, Set temp., Menu, Fan, Louver, Vane, or Hold • Temperature range restriction -The room temperature range for each operation mode can be restricted. • Auto return -The units operate at the preset temperature after a designated period. ◦Time can be set to a value from 30 to 120 minutes in 10-minute increments. -Not valid when the temperature setting range is restricted. • Password -Administrator password (required for schedule setting etc.) and Maintenance password (required for test run and function setting etc.) can be set. MISCELLANEOUS ITEMS •Language Selection -Select the display language from the following 3 languages. ◦English, French, Spanish •Brightness Contrast -The brightness of the LCD can be adjusted. The contrast of the LCD can be adjusted. •Manual Vane Angle *1 -Fixes the vane position for each air outlet. •Service *1 -Contains Test run, Function setting, Request code, and Error history. •3D i-see Sensor® *1 -Settings for 3D i-see Sensor® can be made. ENERGY SAVING OPTIONS • No occupancy energy save -Requires 3D i-see Sensor® on applicable indoor units • Room Occupancy energy save -Requires 3D i-see Sensor® on applicable indoor units • No occupancy Auto-OFF -Requires 3D i-see Sensor® on applicable indoor units • Setback Mode *1 This function is active only for the units that support the function. *2 The clock is accurate within 45 seconds per month (at the temperature of 77°F [25ºC]). The clock is backed up for 3 days. 1340 Satellite Boulevard. Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com FORM# M_ Submittal_PAR-41MAAU - 202404 Specifications are subject to change without notice.© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Model: PAR-41MAAU DIMENSIONS SPECIFICATIONSCOMPATIBILITY CHART Product size (W x H x D) In. (mm) 4 3/4 x 4 3/4 x 0.57 (120 x 120 x 14.5) Net Weight Lbs. (kg) 9/16 (0.25) Rated Power Supply Voltage 12 VDC (supplied from indoor units) Power Consumption W 0.3 Usage Environment Temperature: 0 to 40º C (32 to 104º F) Humidity: 30 to 90%RH (with no condensation) Material Panel PMMA Main body PC + ABS Sound Pressure Level dB(A) <70 [A-weighted sound pressure level] CITY MULTI®M-Series P-Series PMFY-NBMU Yes MFZ-KA MAC-334IF-E PAA Yes PEFY-NMU Yes MFZ-KJ MAC-334IF-E PCA Yes PEFY-NMAU Yes MSZ/Y-A No PEA Yes PEFY-NMHSU Yes MSZ/Y-D NA: No NA-8: MAC-334IF-E PEAD Yes PEFY-NMLU Yes MS-WA No PKA Yes PEFY-NMSU Yes MSZ-FD No PLA Yes PLFY-NAMU Yes MSZ-FE 09(12)NA: No 09(12)NA-8: MAC-334IF-E 18NA: Yes1 PLFY-NBMU Yes MSZ/Y-GE 06(-18)NA: No NA-8: MAC-334IF-E NA-9: MAC-334IF-E GE24NA: MAC-334IF-E PLFY-NCMU Yes MSZ/Y-GL MAC-334IF-E PLFY-NEMU Yes MSZ/Y-GS MAC-334IF-E PLFY-NFMU Yes MSZ-FH MAC-334IF-E PLFY-NLMU Yes MSZ-FS MAC-334IF-E PCFY-VKM Yes MSZ-HE No PCFY-NGMU Yes MSZ-HM MAC-334IF-E PCFY-NKMU Yes MVZ-AA4 Yes PFFY-NEMU Yes MVZ-AA7 Yes PFFY-NRMU Yes SVZ-KP Yes PVFY-E00 Yes SEZ-KD No PVFY-NAMU Yes SEZ-KD4 Yes PKFY-NAMU Yes SLZ-KA Yes PKFY-NFMU Yes SLZ-KF Yes PKFY-NGMU Yes MLZ-KP MAC-334IF-E PKFY-NBMU Yes Note: MAC-334IF-E indicates that the unit requires a MAC-334IF-E Adapter in order to use the PAR-41MAAU. PKFY-NHMU Yes PKFY-NKMU Yes (Front view)(Side view)(Rear view)Unit: mm [in.]]46/73[ 5.41]23/32-4[ 021 ]2 3 / 3 2 - 4 [ 0 2 1 PVA Yes Section 3 Zone Dampers 5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802 Page 1 of 2 SUBMITTAL DESCRIPTION TECHNICAL DATA The STCD is a heavy duty modulating or power open / power close supply air damper, which is designed for applications on Zonex control systems. The dampers are available from 8” X 8” to 24” X 24” in 2” increments, and from 24” X 24” 48” X 48” in 4” increments. The STCD will operate with a maximum pressure differential of 1.75” W.C. STCD dampers feature parallel blade construction for height dimensions to 14” and opposed blade construction for height dimensions 16” through 48”. STCD dampers 8” in height use a single damper blade. The damper assembly is enclosed in a 16” long, 20 gauge galvanized steel sleeve, with standard slip and drive connections. Damper blades are bolted to a hexagonal damper shaft which rotates within stainless steel Oilite bushings. Damper blades close against steel blade stops. The damper linkage is non-adjustable and fully enclosed within the damper. Damper minimum and maximum positions are field adjustable on the actuator. For supply applications, the STCD is wired to a Zonex thermostat for modulating operation. Electrical: Supply Voltage: 24vac Power consumption: 2 VA maximum (1.5W) Environmental: Operating temperature: 20 to 125° F (-7 to 52° C) Operating humidity: 10-95% non-condensing Storage temperature: -20 to 130° F (-29 to 54° C) General: Shell: 20 gauge cold rolled galvanized steel Shaft: 1/2” dia. plated steel, hexagonal Blades: 16 gauge galvanized Bushings: Stainless steel oilite Actuator: Modulating or Power Open / Power Close Stroke: 90° REV 1/14/21 STCD Modulating Supply Damper STCD MODULATING SUPPLY DAMPER 5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802 Page 2 of 2 TYPICAL RECTANGULAR SUPPLY CAPACITY WIDTH IN INCHES 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 8 300 400 500 610 710 820 925 1050 1175 1250 1400 1500 1600 1725 1825 2000 2100 2200 2275 2400 2525 10 400 540 680 825 975 1125 1300 1400 1590 1750 1975 2100 2175 2400 2600 2775 2900 3000 3200 3400 3600 12 500 680 850 1000 1200 1400 1600 1850 2000 2300 2550 2700 2850 3100 3400 3600 3800 3975 4200 4450 5775 14 610 825 1000 1250 1500 1750 2000 2250 2500 2900 3150 3425 3625 3825 4200 4600 4800 5000 5300 5750 6000 16 710 975 1200 1500 1800 2100 2450 2700 3000 3600 3950 4200 4425 4650 5100 5600 5780 6025 6500 7000 7400 18 820 1125 1400 1750 2100 2500 2850 3080 3600 4400 4600 4950 5100 5600 6000 6500 7000 7150 7600 8100 8600 20 925 1300 1600 2000 2450 2850 3400 3775 4000 4800 5500 5700 6000 6600 7100 7900 8025 8500 9000 9600 10075 22 1050 1400 1850 2250 2700 3080 3775 4300 4800 5100 6000 6350 6800 7200 7800 8600 9000 9600 10000 11500 12500 24 1175 1590 2000 2500 3000 3600 4000 4800 5400 6100 7000 7150 7600 8600 9100 10000 10700 11500 12000 13050 14700 26 1250 1750 2300 2900 3600 4400 4800 5100 6100 6700 7800 8400 8900 10000 10900 11075 12050 13000 14000 15000 15900 28 1400 1975 2550 3150 3950 4600 5500 6000 7000 7800 8400 9150 10000 10700 11900 13000 13800 14900 15200 16500 17500 30 1500 2100 2700 3425 4200 4950 5700 6350 7150 8400 9150 10000 11000 11800 12400 13800 14200 15000 16000 17400 18500 32 1600 2175 2850 3625 4425 5100 6000 6800 7600 8900 10000 11000 11250 12700 13900 14900 15200 16900 17300 19000 20500 34 1725 2400 3100 3825 4650 5600 6600 7200 8600 10000 10700 11800 12700 14100 15000 16500 17200 18100 19200 20500 21900 36 1825 2600 3400 4200 5100 6000 7100 7800 9100 10900 11900 12400 13900 15000 16100 17400 18500 20000 21500 22900 24200 38 2000 2775 3600 4600 5600 6500 7900 8600 10000 11075 13000 13800 14900 16500 17400 17800 20000 21900 22600 24000 25100 40 2100 2900 3800 4800 5780 7000 8025 9000 10700 12050 13800 14200 15200 17200 18500 20000 21000 22200 24900 25000 27000 42 2200 3000 3975 5000 6025 7150 8500 9600 11500 13000 14900 15000 16900 18100 20000 21900 22200 22800 25100 26900 30000 44 2275 3200 4200 5300 6500 7600 9000 10000 12000 14000 15200 16000 17300 19200 21500 22600 24900 25100 26500 30000 32000 46 2400 3400 4450 5750 7000 8100 9600 11500 13050 15000 16500 17400 19000 20500 22900 24000 25000 26900 30000 30500 32800 48 2525 3600 5775 6000 7400 8600 1075 12500 14700 15900 17500 18500 20500 21900 24200 25100 27000 30000 32000 32800 35600 STCD MODULATING SUPPLY DAMPER These air quantities were derived from duct sizing chart .1” friction loss per 100’ of duct. All CFMs listed are approximate. For accurate selection, use duct sizing table or device. HE I G H T I N I N C H E S 5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802 Page 1 of 2 SUBMITTAL DESCRIPTION TECHNICAL DATA The Electronic Bypass Damper includes a factory mounted actuator and electronic static pressure controller used to control static pressure in zoned systems. The Electronic Static Pressure Control is adjustable, controlling a modulating bypass damper to maintain static pressure as zone dampers modulate. The bypass system reduces air noise from the supply outlets caused by excessive air velocity. When the system is satisfied, the bypass damper will remain 25% open, if intermittent fan is used. On systems utilizing continuous fan operation, bypass will modulate based on system static. Bypass controller is adjustable to maintain static pressure range from .15” - .95” W .C. The Integrated Static Pressure Control (IPC) includes a quick start option or may be field adjusted to specified static pressure. STCDBP dampers feature parallel blade construction for height dimensions to 14” and opposed blade construction for height dimensions 16” through 48”. STCDBP dampers 8” in height use a single damper blade. The damper assembly is enclosed in a 16” long, 20-gauge galvanized steel sleeve, with standard slip and drive connections. Damper blades are bolted to a hexagonal damper shaft, which rotate within a stainless steel Oilite bushing. Damper blades close against steel blade stops. Electronic Integrated Bypass Damper Electrical: Supply Voltage: 24vac Power consumption: 2 VA maximum (1.5 watt) Environmental: Operating temperature: 20 to 125° F (-7 to 52° C) Operating humidity: 10-95% non-condensing Storage temperature: -20 to 130° F (-29 to 54° C) General: Shell: 20 gauge cold rolled galvanized steel Shaft: 1/2” dia. plated steel, hexagonal Blades: 16 gauge galvanized Bushings: Stainless steel Oilite Actuator: Power open / Power close Stroke: 90° Rev 2/1/18 Rectangular Electronic Bypass Damper with Integrated Static Pressure Control (Part # STCDBP) STCDBP RECTANGULAR ELECTRONIC BYPASS DAMPER 5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802 Page 2 of 2 TYPICAL CAPACITIES* SENSOR LOCATION 8 10 12 14 16 18 20 22 24 28 32 36 40 44 48 8 667 833 1000 1167 1333 1500 1667 1833 2000 2333 2667 3000 3333 3667 4000 10 883 1042 1250 1458 1667 1875 2083 2292 2500 2917 3333 3750 4167 4583 5000 12 1000 1250 1500 1750 2000 2250 2500 2750 3000 3500 4000 4500 5000 5500 6000 14 1167 1458 1750 2042 2333 2625 2917 3208 3500 4083 4667 5250 5833 6417 7000 16 1333 1667 2000 2333 2667 3000 3333 3667 4000 4667 5333 6000 6667 7333 8000 18 1500 1875 2250 2625 3000 3375 3750 4125 4500 5250 6000 6750 7500 8250 9000 20 1667 2083 2500 2917 3333 3750 4167 4583 5000 5833 6667 7500 8333 9167 10000 22 1833 2292 2750 3208 3667 4125 4583 5042 5500 6417 7333 8250 9167 10083 11000 24 2000 2500 3000 3500 4000 4500 5000 5500 6000 7000 8000 9000 10000 11000 12000 28 2333 2917 3500 4083 4667 5250 5833 6417 7000 8167 9333 10500 11667 12833 14000 32 2667 3333 4000 4667 5333 6000 6667 7333 8000 9333 10667 12000 13333 14667 16000 36 3000 3750 4500 5250 6000 6750 7500 8250 9000 10500 12000 13500 15000 16500 18000 40 3333 4167 5000 5833 6667 7500 8333 9167 10000 11667 13333 15000 16667 18333 20000 44 3667 4583 5500 6417 7333 8250 9167 10083 11000 12833 14667 16500 18333 20167 22000 48 4000 5000 6000 7000 8000 9000 10000 11000 12000 14000 16000 18000 20000 22000 24000 * Capacities are for reference only at 1500 FPM. Duct friction rate should be established by use of ACCA Manual D, Manual Q, or equivalent. WIDTH IN INCHES HE I G H T I N I N C H E S STCDBP RECTANGULAR ELECTRONIC BYPASS DAMPER Section 4 Thermostat Wi-Fi VisionPRO® 8000 SUBMITTAL SHEET APPLICATION Wi-Fi VisionPRO allows remote access through a Smartphone, Tablet or Computer. It controls Up to 3H/2C Heat Pump systems or up to 2H/2C Conventional systems. Thermostat is selectable for Residential or Light Commercial applications. The thermostat have a Universal Relay to control humidification, humidification or ventilation. • The thermostat is equipped with a touchscreen display with a 2 line message center. • Provides Remote Access through Smartphone, Tablet or Computer when connected to Wi-Fi and registered to mytotalconnectcomfort.com • Provides lockout temperatures for auxiliary heat and/or compressor lockout in Heat Pump system using the wired outdoor sensor accessory or using the outdoor information from the cloud if no wired sensor is used, but the thermostat is connected to Wi-Fi and registered. SPECIFICATIONS Terminal Designations: TH8321WF Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K, U1 U1, S1 S1 Electrical Ratings (for VisionPRO and Equipment Interface Module): Terminal Voltage (50/60 Hz) Max. Current Rating W - O/B 18 to 30 VAC 1.00A Y (cooling)18 to 30 VAC 1.00A G (fan)18 to 30 VAC 0.50A W2 - Aux/E 18 to 30 VAC 0.60A Y2 (cooling)18 to 30 VAC 0.60A A-L/A (Output)18 to 30 VAC 1.00A U1, U1 30 VAC max.0.50A Power Consumption of TH8321WF Thermostat: Backlight on: 2.35 VA Backlight off: 1.40 VA Wi-Fi Communication Requirements: 802.11 b/g/n routers Android or IOS Smartphone, tablet or device Temperature Setting Range: Heating: 40 to 90 °F (4.5 to 32 °C) Cooling: 50 to 99 °F (10 to 37 °C) Temperature Sensor Accuracy: ± 1.5 °F at 70 °F (0.75 °C at 21.0 °C) Humidification Setting Range: 10% to 60% RH Dehumidification Setting Range: 40% to 80% RH Humidity Display Range: 0% to 99% Humidity Sensor Accuracy: ± 5% RH from 30% to 50% RH at 75 °F (24 °C) Cool Indication: Displays “Cool On” when the thermostat turns the cooling on. Heat Indication: Displays “Heat On” when the thermostat turns the heating on. Auxiliary Heat Indication: Displays “Aux Heat On” when the thermostat turns the auxiliary heat on. Interstage Differential: Comfort: The thermostat keeps the indoor temperature within 1 degree of the setpoint (droop less control). The thermostat turns on stage 2 when the capacity on stage 1 reaches 90%. When the interstage differential is set to 1.0 or higher, the thermostat stages the equipment based on how far the indoor temperature is from the setpoint. Clock Accuracy: If not connected to Wi-Fi: 1 minute per month at 77 °F (25 °C). ± 2 minutes per month over the operating ambient temperature range. If connected to Wi-Fi and registered to Total Connect Comfort: the current time is synced via the Internet. Mounting Means: Thermostat mounts directly on the wall in the living space using mounting screws and anchors provided. Fits a horizontal 2 x 4 in. junction box. Use a cover plate and its mounting bracket to mount the thermostat onto a vertical 2 x 4 in. junction box. 33-00072-01 Job Name Engineer Mechanical Contractor Contractor’s P.O. No. Representative Notes Model(s) TH8321WF1001 Qty. Notes Approval Service Tag No. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U.S. Registered Trademark © 2014 Honeywell International Inc. 33-00072—01 M.S. 12-14 Printed in United States Product Part Number Operating Ambient Temperature Operating Relative Humidity Shipping Temperature Physical Dimensions in in. (mm) Color(s) Thermostat TH8321WF1001 32 to 120 °F (0 to 48.9 °C) 5% to 90% Non-Condensing -20 to 120 °F (-28.9 to 48.9 °C) 4-15/16 x 4-5/8 x 1-1/8 (126 x 118 x 29) Arctic White Dimensions of thermostat in in. (mm). M34521 4-15/16 (126) 4-5/8 (118) 1-1/8 (29) 3-5/16 (84) Dimensions of VisionPRO cover plate in in. (mm). M34258 25/32 (20) 6-5/32(156) 1-1/2(38) 5-3/4 (146) Section 5 Grilles, Registers, and Diffusers Submittal Square Ceiling Diffusers Modular Core • Steel MCD • 1, 2, 3 or 4-Way Adjustable Discharge Pattern Border Type 1 (Surface Mount) Border Type 3 Lay-In)Border Type 4 (Spline) MCD 4-9-15 1/4"1" Duct Size Duct Size minus 1/4" Ceiling Opening = Duct Size plus 3" Duct Size plus 5 9/16" 2 1/8" Ceiling Module minus 1/4" Ceiling Module minus 1/4" Duct Size Border Type 6 (Beveled Drop Face) 3/8" Duct Sizeminus 1/4" Ceiling Module minus 1/16" 2 3/16" Duct Size minus 1/8" Duct Size minus 1/8" Duct Size minus 1/8" Available Duct Sizes Border Type 1, 6 Duct Size 6x6 14x14 22x22 8x8 16x16 24x24 10x10 18x18 12x12 20x20 Border Type 3, 4 Duct Size 24x24 Available Module Size 6x6 8x8 10x10 12x12 14x14 16x16 18x18 Note: All units have 4 individually adjustable cores. Duct size A *Note: Round duct sizes are available only in sizes shown. Border Type 3 24x24 Available Module Size Minimum A Available Round Duct Size 6x6 12x12 6 6, 8, 10, 12 MCD 4-9-15 Model AG-95 Opposed Blade Damper TRM TITUS Rapid Mount Frame For Surface Mounting Border Type 3 Accessories (Optional)Check if provided. Available in duct sizes 6 x 6 through 24 x 24. OperatorSlot 2 1/16" This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice. All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies. Border Type NT (Lay-In) Square Neck Duct Size A 23 3/8" Duct Size minus 1/8" 3/8" 24" 1 1/2" 2 1/8" Available Module Size Minimum Duct Size Maximum Duct Size 24 x 24 6 x 6 18 x 18 Note:Duct sizes are available in square 2” increments only. Border Type NT (Lay-In) Round Neck Available Module Size Dimension A Available Round Duct Size B 6 x 6 6 12 x 12 6, 8, 10, 1224 x 241 1/2"3/8" 24" 23 3/4" A Duct B-Diameter Duct Size minus 1/8" 1 3/8" 3 7/8" B Dimensions are in inches.Modular Core Adjustments 1-Way 2-Way Opposite 2-Way Corner 3-Way VERTICAL4-Way MCD 4-9-15 Model AG-95 Opposed Blade Damper TRM TITUS Rapid Mount Frame For Surface Mounting Border Type 3 Standard Finish: #26 White General Description • The Model MCD modular core diffuser is an extremely flexible diffuser. The model MCD can be adjusted for 1, 2, 3 or 4-way air patterns after being installed. Accessories (Optional)Check if provided. Available in square neck sizes 6 x 6 through 24 x 24. OperatorSlot 2 1/16" • Model MCD diffuser maintains a horizontal flow pattern from maximum to minimum CFM making it an excellent choice for variable air volume applications. • Optional AG-95 (square and rectangular) opposed blade damper is accessible from the face by removing a modular core. • MCD is shipped with the modular cores set for 4-way throw. • Material is steel. This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice. All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies. Damper Nominal Duct Size D" D minus 1/2" Optional Opposed Blade 1 1/4" D plus 1 3/4" D minus 3/4" J 3/16" K Duct plus 1/16" 1 1/2" Duct plus 2 3/8" Duct plus 1 7/8" 5/16" 1/4" 3/16" Duct Size 1 1/4" Duct Duct Size minus 3/4" 3/16" 1 Submittal Eggcrate Return Grilles • Aluminum Grid • Aluminum Border Border Type 1 (Surface Mount ) Available Sizes (D” x D”) Border Type 1 available in sizes 6” x 4” through 48 ” x 48 ” in one piece construction . Sizes larger than 48 ” x 48 ” are shipped in multiple sections. Odd and fractional sizes are available at additional cost. Wall or duct opening should be duct size ± 1/8. All dimensions are in inches. Fastenings Mounting Frames Type A • External Screw Type C • Concealed Screw PFAP • Aluminum Plaster Frame Recessed Mounted Example Note: Plaster frame can be installed as either surface mount or recessed. Dimensions are in inches. Wall or duct opening should be duct sizes + 1/8. Accessories (Optional)Standard Finish: #26 White Neck mounted opposed blade damper (galvanized steel) EQT • Earthquake Tabs General Description IS • Insect Screen (1/16 ” square mesh – galvanized steel) DS • Debris Screen (1/4” square mesh – galvanized steel) Other: ____________________ Other Finish: __________________ • #8 x 1 1/4 lg . Phillips flat head sheet metal screws painted white. • Insect and debris screens are not available when dampers are fitted. • Optional opposed blade damper has screwdriver adjustment accessible through face of grille. • Material is aluminum. • All dimensions are ± 1/16 " 50F – 1.0 10-17-17 Check One Dimension J K ½” x ½” x ½”½” x ½” x 1”1” x 1” x 1” 1 ¼”1 ¼”1 ¼” 2 ½”2 15/16”2 15/16” Check if provided. Available with Border Type 1 only. Type ‘C’ fastening not available on unit with damper . □ 50F • Code A • ½ x ½ x ½ Grid □ 50F • Code B • ½ x ½ x 1 Grid □ 50F • Code C • 1 x 1 x 1 Grid □ 50 F-NT • Code A • ½ x ½ x ½ Grid • Narrow Tee Border □ 50 F-NT • Code B • ½ x ½ x 1 Grid • Narrow Tee Border □ 50 F-NT • Code C • 1 x 1 x 1 Grid • Narrow Tee Border D - 1/4" H D - 1/4" Ceiling Module Size minus 1/4" 50F 2.0 10-17-17 Optional Border Types Available Border Type 3 (Lay-in ) Panel Mounted Border Type 8 (Core only) Available as panel-mounted in all standard module sizes with neck sizes up to module size minus 2”. Note: Module size minus 2" sizes do not require panel mounting. Available in sizes up to 48 ” x 48 ” Border Type 3 • Accessories & Options Border Type 7 and 8 • Accessories & Options Neck mounted opposed blade damper (galvanized steel) IS • Insect Screen (1/16 ” square mesh – galvanized steel ) DS • Debris Screen (1/4” square mesh – galvanized steel ) EQT • Earthquake tabs Other: _______________________ EQT • Earthquake tabs Standard Finish: #26 White Standard Finish: #26 White Check if provided.Border Type 7 (Channel) Available in sizes up to 48 ” x 48 ”. This submittal is meant to demonstrate general dimensions of this product . The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to make changes without written notice. All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies. 23 3/8" 23 3/4" D minus 3/4" D minus 1/2" 24" Blade Damper Opposed Optional Available Sizes (D” x D”) 6” x 4” through 22 ” x 22 ” in 1” increments. Dimensions are in inches . 5/16" 9/16" Standard Finish: #26 White Neck mounted opposed blade damper (galvanized steel) EQT • Earthquake Tabs IS • Insect Screen (1/16 ” square mesh – galvanized steel) DS • Debris Screen (1/4” square mesh – galvanized steel) Other Finish: __________________ Other: ____________________ Border Type NT (Lay-in ) Panel Mounted Border Type NT • Accessories & Options Other: _____________________ Other Finish: __________________ Note: Insect and Debris Screen are mutually exclusive options Other Finish: __________________ Check if provided. Note: Insect and Debris Screen are not available with Damper option Check if provided . Square to Round Adapter (SRG) Nominal Grille Size Nominal Round Inlet Size 6 8 10 12 14 16 18 20 22x22 24 X 24 Module Size Adapter interior is black and factory-mounted to grille