Energy Code WorksheetWSU Code Compliance Calculator, WSEC 2018
Project Information Messages / Comments *
Plan 2385A
Review required for custom entries: - Doors
UA Reduction = 9.39, Proposed UA is better than baseline by 2.8%
Contact Information
Soundbuilt Homes LLC Window area is 12% of floor area
PO Box 73790 -
Puyallup, WA 98373 Whole House Mechanical Ventilation Airflow Rate: 40 CFM with Run Time Percent of 100%, Balanced, Distributed
253-848-0820 Maximum allowable total measured duct leakage: 191 CFM25
ANALYSIS SET UP
What code compliance pathway are you using?
Project Building Type?
Occupancy Type?
Code Version? WSEC-R Rev: Oct. 2023, https://www.sbcc.wa.gov/sites/default/files/2023-12/O
Classification:Medium Dwelling Unit -- 2385 sq. ft.
Baseline Description: Code Baseline - Baseline and proposed window areas are equal.
About Your Selection:Up to 15 sf exempt window and 24 sf exempt door allowable
RESULTS - Comparison of Baseline and Proposed Design **
Component Performance, R occupancies
U *Area UA Area UA
Doors U =0.300 86 25.7 86 19.9
Overhead Glazing U =0.500 0 0.0 0 0.0
Vertical Glazing U =0.300 295 88.5 295 88.5
Flat/Vaulted Ceilings U =0.024 1,469 35.3 1,469 36.7
Wall (above grade) U =0.056 2,535 142.0 2,535 136.9
Floors over Crawlspace U =0.029 1,469 42.6 1,469 42.6
Slab on Grade F =0.540 0 0.0 0 0.0
Below Grade Wall U =N/A 000.0
Below Grade Slab F =N/A 000.0
* Values from Table R402.1.2 (Oct 2023)
Baseline UA Total 334.1 Proposed UA Total 324.7
Required Credits 8.0 Proposed Credits 8.0 from Tables 406.2 and 406.
UA Percent Reduction 3%
UA Reduction 9.4
If the Proposed UA ≤ the Target UA, and the Proposed Credits from Table 406 are ≥ those required in Section R406, then the home meets the WSEC.
** Results assume your inputs are complete and correct. Results do not constitute an approval. Analysis should be reviewed by your AHJ.
Total Credits
(406.2 & 406.3)
8.0
* Results assume your inputs are complete and correct. Results do not constitute an approval. Analysis should be reviewed by your AHJ.
Air source ducted Heat Pump w/ Min HSPF2 of 10 (HSPF of
11). If htg design temp is 23F or below,a cold climate variable
capacity heat pump is required.
1.0
Table R406.2 Energy Equalization Credits
3.0Variable Refrigerant Heat Pump or Air-to-
Water Heat Pump
Select Options
Per Section R402.4.1.2 /1.5 ACH50 / For R-2, 0.20 cfm per ft2
at 50 Pa. / HRV with min SHR eff of 0.75 per IRC Section
M1505.3 or IMC Section 403.8
Table R406.3 Energy Credits
Option No.
2 Air Leakage Control and Efficient Ventilation
Efficient Building Envelope
3.1 -3.10
Energy Credits
(406.3)System No.
4
Option 2.2
Fuel Normalization
Credits (406.2)
1
Option 3.6
5.0
Full Description
For heating system using a heat pump that meets federal standards for the
equipment listed in Table C403.3.2(2) or Table C403.3.2(9) OR Air to Water heat
pump units that are configured to provide both heating and cooling and are rated in
accordance with AHRI 550/590
High Efficiency HVAC
Energy Credits
3.11 High Efficiency HVAC: Smart Thermostat 0.0
0.300
0.025
0.054
0.029
Proposed Design
U-Factor Compliance Path / Total UA Alternative
U
Baseline
New Construction
R3 Single family dwellings and townhouses
WSEC 2021
0.232
Brief Description of Selected Options*
1.5
Category
Select System Type
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Renewable Electric Energy kWh
Energy Credits
*Refer to WSEC 2015 Table R406.2 for complete option descriptions and requirements
Ducts/distribution system in conditioned space per R403.3.2
Electric resistance, hydronic, ductless and gas fired systems <
80% AFUE systems not permitted
0.0
Electric heat pump water heater meeting NEEA Tier 3.
0.5
0.0
5.0
7 Appliance Package
Efficient Water Heating: Drain Heat Recovery
Efficient Water Heating
Efficient Water Heating: Compact Hot Water Distribution
5.1
5.3-5.8
5.2
6
2.0
High Efficiency HVAC Distribution System
Option 5.6
0.0
0.0
4 Option 4.1
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
THERMAL ENVELOPE DETAILS - Proposed Design
Conditioned Floor Area, Proposed Design 2,385 sq. ft
Classification Medium Dwelling Unit
Exterior Doors
Plan Component Door
ID Description Ref. U Qt. Feet
Inch Feet Inch Area UA
Exempt 00.0
Fiberglass Door Custom 0.15 1 3 6
8 20 3.0 Refer to WSEC R402.1
Solid Core Door Custom 0.17 1 2
8 6 8 18 3.0 Refer to WSEC R402.1
Sliding Door Custom 0.29 1 6 8 48 13.9 Refer to WSEC R402.1
00.0
00.0
00.0
00.0
00.0
00.0
00.0
Sum of Area and UA 86 19.9
0 3
Exterior Doors Area Weighted U 0.232
Overhead Glazing
Plan Component Glazing
ID Description U Feet
Inch Feet Inch
-
-
-
-
-
0.0 0
0 0
Overhead Glazing Area Weighted U
Vertical Glazing Schedule Rows to Show 12
Plan Component Glazing
ID Description U Feet
Inch Feet Inch
Exempt - - -
1 U=0.30 (Code Baseline)Table 406.2 0.30 1 2 4 8.0 2.40
2 U=0.30 (Code Baseline)Table 406.2 0.30 1 5 5 25.0 7.50
3 U=0.30 (Code Baseline)Table 406.2 0.30 1 3 4 12.0 3.60
4 U=0.30 (Code Baseline)Table 406.2 0.30 3 6 2 36.0 10.80
5 U=0.30 (Code Baseline)Table 406.2 0.30 2 8 5 80.0 24.00
6 U=0.30 (Code Baseline)Table 406.2 0.30 4 4 4 64.0 19.20
7 U=0.30 (Code Baseline)Table 406.2 0.30 1 8 4 32.0 9.60
8 U=0.30 (Code Baseline)Table 406.2 0.30 1 4 2 8.0 2.40
9 U=0.30 (Code Baseline)Table 406.2 0.30 1 4 4
6 18.0 5.40
10 U=0.30 (Code Baseline)Table 406.2 0.30 2 2 3 12.0 3.60
11 - -
12 - -
Sum of Area and UA 295.0 88.5
0
Vertical Glazing Area Weighted U 0.300
Vertical Glazing and Doors Area Weighted U 0.285
Flat/Vaulted Ceilings
Plan Component Attic
ID Description U
R60 blown Attic STD baffled 10-7 0.025 1,469 36.7
1,469 36.7
0
Walls (Above Grade)
Width
Ref.
Ref.
Height
Notes
Height
Area
Width
Qt.
Sum of Area and UA
Qt. UAArea
HeightWidth
Sum of Area and UA
Ref.
UA
Area UA
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Plan Component Wall
ID Description Ref. U UA
R21 cavity+R0 foam INT 2X6W Lap (Code Baseline)10-5 0.054 2,535 137
2,535 137
0
Net Area
Sum of Area and UA
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Floor (over crawl or exterior)
Plan Component Floor UA
ID Description Ref. U
R30 vented Joist (Code Baseline)10-3 0.029 1,469 43
1,469 43
0
Slab on Grade (less than 2 feet below grade)
Plan Component Slab
ID Description Ref. F FP
00 0
Below Grade Walls and Slabs
Plan Component Slab Wall Wall Wall Slab
ID Description Depth Ref. U Area UA UA
Sum of Area, Length and UA 0 0.0 0 0
0
Links to Download Forms, Checklists and Other Resources
Compliance Certificate Instructions
Insulation Certificate for Residential New Construction
Duct Testing Affadavits
Existing Construction
New Construction
Prescriptive Checklist for 2018 WSEC
Alterations (Remodel) Worksheet
EER SEER2 COP HSPF2 Converter https://www.adicotengineering.com/eer-seer2-cop-hspf2-kwton-converter
Show
Ventilation Requirements
Conditioned Floor Area 2,385 sq. ft.
Number of Bedrooms 1
Run-Time Percent in Each 4-Hour Segment 100%
Is the system Balanced?Verify system meets definition of 'Balanced Whole-House Ventilation'
Is the system Distributed?Verify system meets definition of 'Distributed Whole-House Ventilation'
Ventilation Code Section IRC, Chapter 15
Whole House Mechanical Ventilation Airflow Rate 40 CFM
Show
HVAC Thermal Distribution System Download RS-33 (2018)
Is this a hydronic heating system?
Location of Ducts
Location of Air Handler
Is Duct Testing Required? Yes
Maximum Duct Leakage:
Maximum total measured duct leakage per square foot 0.08 CFM25 per sq. ft.
Maximum allowable total measured duct leakage 191 CFM25
A maximum of 10 feet of return ducts and 5 feet of supply ducts are allowed to be located outside of the building thermal envelope, if insulated and sealed per R403.3.7.
Show
Heating System Sizing - Proposed Design Try Out BetterBuiltNW's HVAC Sizing Tool:
Nearest Weather Station
Indoor Design Temperature 70 F
Outdoor Design Temperature 19 F
http://www.energy.wsu.edu/Documents/Duct%20Testing%20Standards%2
Conditioned Space
https://betterbuiltnw.com/resources/hvac-sizing-tool
Link
Prescriptive Checklist
Affidavit, Existing
Affidavit, New
Worksheet
No
Sum of Perimeter and FP
Slab
Perim
Compliance Certificate
Insulation Certificate
Sum of Area and UA
Distributed
Balanced
Show Distribution System Calculator?
Show Ventilation Calculator?
Slab Slab
Perim
Puyallup
Conditioned Space
Show Heating System Sizing?
Area
F
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Design Temperature Difference (∆T)51 F
Conditioned Floor Area, Proposed Design 2,385 ft2
Conditioned Volume 19,080 ft3 0.00
Leave blank to use default of 8.5 ft. ceiling height
HVAC System Type
Location of HVAC Distribution System Conditioned Space
Sum of UA, including exempt door and window 325
Envelope Heat Load 16,558 Btu / Hour
Sum of UA X ∆T
Air Leakage Heat Load 10,509 Btu / Hour
((Volume X 0.6) X ∆T) X .018))
Building Design Heat Load 27,067 Btu / Hour
Air Leakage + Envelope Heat Loss
Building and Duct Heat Load 27,067 Btu / Hour
For ducts located in unconditioned space: Sum of Building Heat Loss X 1.1
For ducts located in conditioned space or ductless: Sum of Building Heat Loss X 1
Maximum Heat Equipment Output 33,834 Btu / Hour
Building and Duct Heat Loss X 1.25 for heat pumps 9.9 kW
Building and Duct Heat Loss X 1.40 for all other systems
Heat Pump
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Project Information Messages / Comments *
Plan 2385B
Review required for custom entries: - Doors
UA Reduction = 9.41, Proposed UA is better than baseline by 2.8%
Contact Information
Soundbuilt Homes LLC Window area is 13% of floor area
PO Box 73790 -
Puyallup, WA 98373 Whole House Mechanical Ventilation Airflow Rate: 40 CFM with Run Time Percent of 100%, Balanced, Distributed
253-848-0820 Maximum allowable total measured duct leakage: 191 CFM25
ANALYSIS SET UP
What code compliance pathway are you using?
Project Building Type?
Occupancy Type?
Code Version? WSEC-R Rev: Oct. 2023, https://www.sbcc.wa.gov/sites/default/files/2023-12/O
Classification:Medium Dwelling Unit -- 2385 sq. ft.
Baseline Description: Code Baseline - Baseline and proposed window areas are equal.
About Your Selection:Up to 15 sf exempt window and 24 sf exempt door allowable
RESULTS - Comparison of Baseline and Proposed Design **
Component Performance, R occupancies
U *Area UA Area UA
Doors U =0.300 86 25.7 86 19.9
Overhead Glazing U =0.500 0 0.0 0 0.0
Vertical Glazing U =0.300 305 91.5 305 91.5
Flat/Vaulted Ceilings U =0.024 1,465 35.2 1,465 36.6
Wall (above grade) U =0.056 2,541 142.3 2,541 137.2
Floors over Crawlspace U =0.029 1,465 42.5 1,465 42.5
Slab on Grade F =0.540 0 0.0 0 0.0
Below Grade Wall U =N/A 000.0
Below Grade Slab F =N/A 000.0
* Values from Table R402.1.2 (Oct 2023)
Baseline UA Total 337.2 Proposed UA Total 327.8
Required Credits 8.0 Proposed Credits 8.0 from Tables 406.2 and 406.
UA Percent Reduction 3%
UA Reduction 9.4
If the Proposed UA ≤ the Target UA, and the Proposed Credits from Table 406 are ≥ those required in Section R406, then the home meets the WSEC.
** Results assume your inputs are complete and correct. Results do not constitute an approval. Analysis should be reviewed by your AHJ.
Total Credits
(406.2 & 406.3)
8.0
* Results assume your inputs are complete and correct. Results do not constitute an approval. Analysis should be reviewed by your AHJ.
Air source ducted Heat Pump w/ Min HSPF2 of 10 (HSPF of
11). If htg design temp is 23F or below,a cold climate variable
capacity heat pump is required.
1.0
Table R406.2 Energy Equalization Credits
3.0Variable Refrigerant Heat Pump or Air-to-
Water Heat Pump
Select Options
Per Section R402.4.1.2 /1.5 ACH50 / For R-2, 0.20 cfm per ft2
at 50 Pa. / HRV with min SHR eff of 0.75 per IRC Section
M1505.3 or IMC Section 403.8
Table R406.3 Energy Credits
Option No.
2 Air Leakage Control and Efficient Ventilation
Efficient Building Envelope
3.1 -3.10
Energy Credits
(406.3)System No.
4
Option 2.2
Fuel Normalization
Credits (406.2)
1
Option 3.6
5.0
Full Description
For heating system using a heat pump that meets federal standards for the
equipment listed in Table C403.3.2(2) or Table C403.3.2(9) OR Air to Water heat
pump units that are configured to provide both heating and cooling and are rated in
accordance with AHRI 550/590
High Efficiency HVAC
Energy Credits
3.11 High Efficiency HVAC: Smart Thermostat 0.0
0.300
0.025
0.054
0.029
Proposed Design
U-Factor Compliance Path / Total UA Alternative
U
Baseline
New Construction
R3 Single family dwellings and townhouses
WSEC 2021
0.232
Brief Description of Selected Options*
1.5
Category
Select System Type
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Renewable Electric Energy kWh
Energy Credits
*Refer to WSEC 2015 Table R406.2 for complete option descriptions and requirements
Ducts/distribution system in conditioned space per R403.3.2
Electric resistance, hydronic, ductless and gas fired systems <
80% AFUE systems not permitted
0.0
Electric heat pump water heater meeting NEEA Tier 3.
0.5
0.0
5.0
7 Appliance Package
Efficient Water Heating: Drain Heat Recovery
Efficient Water Heating
Efficient Water Heating: Compact Hot Water Distribution
5.1
5.3-5.8
5.2
6
2.0
High Efficiency HVAC Distribution System
Option 5.6
0.0
0.0
4 Option 4.1
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
THERMAL ENVELOPE DETAILS - Proposed Design
Conditioned Floor Area, Proposed Design 2,385 sq. ft
Classification Medium Dwelling Unit
Exterior Doors
Plan Component Door
ID Description Ref. U Qt. Feet
Inch Feet Inch Area UA
Exempt 00.0
Fiberglass Door Custom 0.15 1 3 6
8 20 3.0 Refer to WSEC R402.1
Solid Core Door Custom 0.17 1 2
8 6 8 18 3.0 Refer to WSEC R402.1
Sliding Door Custom 0.29 1 6 8 48 13.9 Refer to WSEC R402.1
00.0
00.0
00.0
00.0
00.0
00.0
00.0
Sum of Area and UA 86 19.9
0 3
Exterior Doors Area Weighted U 0.232
Overhead Glazing
Plan Component Glazing
ID Description U Feet
Inch Feet Inch
-
-
-
-
-
0.0 0
0 0
Overhead Glazing Area Weighted U
Vertical Glazing Schedule Rows to Show 12
Plan Component Glazing
ID Description U Feet
Inch Feet Inch
Exempt - - -
1 U=0.30 (Code Baseline)Table 406.2 0.30 1 2 4 8.0 2.40
2 U=0.30 (Code Baseline)Table 406.2 0.30 1 5 5 25.0 7.50
3 U=0.30 (Code Baseline)Table 406.2 0.30 1 3 4 12.0 3.60
4 U=0.30 (Code Baseline)Table 406.2 0.30 2 6 2 24.0 7.20
5 U=0.30 (Code Baseline)Table 406.2 0.30 2 8 5 80.0 24.00
6 U=0.30 (Code Baseline)Table 406.2 0.30 5 4 4 80.0 24.00
7 U=0.30 (Code Baseline)Table 406.2 0.30 1 8 4 32.0 9.60
8 U=0.30 (Code Baseline)Table 406.2 0.30 1 4 2 8.0 2.40
9 U=0.30 (Code Baseline)Table 406.2 0.30 1 6 4 24.0 7.20
10 U=0.30 (Code Baseline)Table 406.2 0.30 2 2 3 12.0 3.60
11 - -
12 - -
Sum of Area and UA 305.0 91.5
0
Vertical Glazing Area Weighted U 0.300
Vertical Glazing and Doors Area Weighted U 0.285
Flat/Vaulted Ceilings
Plan Component Attic
ID Description U
R60 blown Attic STD baffled 10-7 0.025 1,465 36.6
1,465 36.6
0
Walls (Above Grade)
Width
Ref.
Ref.
Height
Notes
Height
Area
Width
Qt.
Sum of Area and UA
Qt. UAArea
HeightWidth
Sum of Area and UA
Ref.
UA
Area UA
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Plan Component Wall
ID Description Ref. U UA
R21 cavity+R0 foam INT 2X6W Lap (Code Baseline)10-5 0.054 2,541 137
2,541 137
0
Net Area
Sum of Area and UA
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Floor (over crawl or exterior)
Plan Component Floor UA
ID Description Ref. U
R30 vented Joist (Code Baseline)10-3 0.029 1,465 42
1,465 42
0
Slab on Grade (less than 2 feet below grade)
Plan Component Slab
ID Description Ref. F FP
00 0
Below Grade Walls and Slabs
Plan Component Slab Wall Wall Wall Slab
ID Description Depth Ref. U Area UA UA
Sum of Area, Length and UA 0 0.0 0 0
0
Links to Download Forms, Checklists and Other Resources
Compliance Certificate Instructions
Insulation Certificate for Residential New Construction
Duct Testing Affadavits
Existing Construction
New Construction
Prescriptive Checklist for 2018 WSEC
Alterations (Remodel) Worksheet
EER SEER2 COP HSPF2 Converter https://www.adicotengineering.com/eer-seer2-cop-hspf2-kwton-converter
Show
Ventilation Requirements
Conditioned Floor Area 2,385 sq. ft.
Number of Bedrooms 1
Run-Time Percent in Each 4-Hour Segment 100%
Is the system Balanced?Verify system meets definition of 'Balanced Whole-House Ventilation'
Is the system Distributed?Verify system meets definition of 'Distributed Whole-House Ventilation'
Ventilation Code Section IRC, Chapter 15
Whole House Mechanical Ventilation Airflow Rate 40 CFM
Show
HVAC Thermal Distribution System Download RS-33 (2018)
Is this a hydronic heating system?
Location of Ducts
Location of Air Handler
Is Duct Testing Required? Yes
Maximum Duct Leakage:
Maximum total measured duct leakage per square foot 0.08 CFM25 per sq. ft.
Maximum allowable total measured duct leakage 191 CFM25
A maximum of 10 feet of return ducts and 5 feet of supply ducts are allowed to be located outside of the building thermal envelope, if insulated and sealed per R403.3.7.
Show
Heating System Sizing - Proposed Design Try Out BetterBuiltNW's HVAC Sizing Tool:
Nearest Weather Station
Indoor Design Temperature 70 F
Outdoor Design Temperature 19 F
http://www.energy.wsu.edu/Documents/Duct%20Testing%20Standards%2
Conditioned Space
https://betterbuiltnw.com/resources/hvac-sizing-tool
Link
Prescriptive Checklist
Affidavit, Existing
Affidavit, New
Worksheet
No
Sum of Perimeter and FP
Slab
Perim
Compliance Certificate
Insulation Certificate
Sum of Area and UA
Distributed
Balanced
Show Distribution System Calculator?
Show Ventilation Calculator?
Slab Slab
Perim
Puyallup
Conditioned Space
Show Heating System Sizing?
Area
F
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024
WSU Code Compliance Calculator, WSEC 2018
Design Temperature Difference (∆T)51 F
Conditioned Floor Area, Proposed Design 2,385 ft2
Conditioned Volume 19,080 ft3 0.00
Leave blank to use default of 8.5 ft. ceiling height
HVAC System Type
Location of HVAC Distribution System Conditioned Space
Sum of UA, including exempt door and window 328
Envelope Heat Load 16,716 Btu / Hour
Sum of UA X ∆T
Air Leakage Heat Load 10,509 Btu / Hour
((Volume X 0.6) X ∆T) X .018))
Building Design Heat Load 27,225 Btu / Hour
Air Leakage + Envelope Heat Loss
Building and Duct Heat Load 27,225 Btu / Hour
For ducts located in unconditioned space: Sum of Building Heat Loss X 1.1
For ducts located in conditioned space or ductless: Sum of Building Heat Loss X 1
Maximum Heat Equipment Output 34,032 Btu / Hour
Building and Duct Heat Loss X 1.25 for heat pumps 10.0 kW
Building and Duct Heat Loss X 1.40 for all other systems
Heat Pump
1/25/2024I:\2018 WSEC\2018 Compliance forms\2021\Code Compliance Calculator\WSU_C32021_20240325~Master.xlsm 3/26/2024