P pagesGENERAL NOTES 1. ALL WORK PERFORMED SHALL BE DONE IN STRICT ACCORDANCE TO ALL APPLICABLE MECHANICAL,BUILDING,ENERGY, FUEL GAS, AND LOCAL CODES, WITH AMENDMENTS. 2. COORDINATE MECHANICAL WORK WITH ELECTRICAL,ARCHITECTURAL, AND STRUCTURAL WORK SHOWN ON OTHER CONTRACT DOCUMENTS. PROVIDE ADDITIONAL OFFSETS FOR COORDINATED INSTALLATION WHERE REQUIRED. 3. COORDINATE HVAC,PLUMBING, AND FIRE PROTECTION WORK PRIOR TO INSTALLATION. DUCTWORK AND EQUIPMENT ACCESS TAKES PRECEDENCE OVER ALL PIPING EXCEPT GRAVITY SYSTEMS FOR AVAILABLE SPACE. 4. COORDINATE EQUIPMENT CONNECTIONS WITH MANUFACTURERSCERTIFIED DRAWINGS. COORDINATE AND PROVIDE DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE DUCT AND PIPING DIMENSIONS BEFORE FABRICATION. 5. LOCATIONS AND SIZES OF FLOOR WALL AND ROOF OPENINGS SHALL BE COORDINATED WITH OTHER TRADES INVOLVED. INCLUDE IN THE COST OF MECHANICAL WORK, CUTTING, CORING, PATCHING AND PAINTING OF EXISTING WALLS, CEILINGS, FLOOR$ AND ROOFS AS REQUIRED TO ACCOMMODATE WORK AS INDICATED IN THE MECHANICAL CONTRACT DOCUMENTS, UNLESS SPECIFICALLY SHOWN ON ARCHITECTURAL DRAWINGS. 6. MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE -DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 04 OR ILL 723. 7. PROVIDE COMMISSIONING FOR MECHANICAL SYSTEMS PER UN OF THE M21 WSEC. S. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 7B STANDARDS AND LOCAL REQUIREMENTS. 9. ALL FIELD WIRING SHALL REQUIRE AN ELECTRICAL PERMIT AND SHALL BE PERFORMED BY A LICENSED ELECTRICIAN. 10. LOCATE VALVES, DAMPERS, CONTROLS , AND SIMILAR COMPONENTS SO THAT THEY ARE ACCESSIBLE. HVACISHEET METAL: 1. ALL DUCTWORK TO BE CONSTRUCTED AND SEALED PER IMC AND SMACNA PRESSURE CUSS 2' (LOW PRESSURE) REQUIREMENTS. ALL DUCTS TO BE SEALED TO SMACNA SEAL CUSS A 2. CONSTRUCT DUCTWORKACCORDING TO WASHINGTON STATE ENERGY CODE. ALL DUCTWORK SHALL BE PRIMED GALVANIZED SHEET STEEL, LOCKFORMING QUALITY, FABRICATED IN ACCORDANCE TO SMACNA STANDARDS. 3. PROVIDE TURNING VANES IN ALL MITERED RECTANGULAR DUCT ELBOWS &TEES. 4. ALL SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED PER WASHINGTON STATE ENERGY CODE SECTION C403. SEE INSULATION SCHEDULE ON THIS SHEET FOR MORE INFORMATION. 5. PROVIDE TEMPORARY COVERS OVER OPEN ENDS OF EQUIPMENT AND DUCTWORK DURING CONSTRUCTION. 6. PROVIDE MANUAL VOLUME DAMPER FOR EACH DIFFUSER, REGISTER, AND GRILLE. 7. PROVIDED CT ACCESS DOORS AT DUCT SMOKE DETECTORS, BACKDRAFT DAMPERS, MOTORIZED CONTROL DAMPERS, DUCT AIRFLOW STATIONS, AND LOUVER PLENUMS. NONSTRUCTURAL MECHANICAL COMPONENTS: 1. HANGERS AND SEISMIC BRACING FOR THE MECHANICAL SYSTEMS SHALL BE DESIGNED AND PROVIDED BY THE MECHANICAL CONTRACTOR. REFER TO CONTRACTOR SHOP DRAWINGS FOR LOCATIONS OF EQUIPMENT AND HUNG MECHANICAL SYSTEMS. THE MECHANICAL CONTRACTOR SHALL COORDINATE THE SUPPORT SYSTEMS AND DESIGN LOADS FOR HUNG MECHANICAL SYSTEMS WITH THE GENERAL CONTRACTOR AND OTHER TRADES THAT MAYBE IMPACTED. DEMOLITION: 1. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED IN NEW SYSTEMS, EXCEPT WHERE INDICATED AS BEING RELOCATED. 2. CONTRACTOR SHALL REMOVE ALL PIPING, DUCTWORK. AND EQUIPMENT INCLUDING ALL ASSOCIATED INSULATION,HANGERS, VALVES, PLENUM WALLS, DAMPERS, WIREMOLD, WIRING, CONTROLS, AND APPURTENANCES ASSOCIATED WITH EACH PIECE OF EQUIPMENT, UNLESS OTHERWISE SHOWN TO ABANDON IN PLACE. 3. WHERE EXISTING ITEMS PENETRATE A WALL OR ROOF, CONTRACTOR SHALL PROVIDE INFILLAT(E) PENETRATIONS THROUGH WALL4ROOF WITH LIKE MATERIALS. PATCH & REPAIR TO MATCH SURROUNDING SURFACES INCLUDING PAINT. 4. MAINTAIN AND RESTORE (IF INTERRUPTED) ALL CONDUITS & CONDUCTORS, PIPING, & DUCTWORK PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS. 5. REMOVE ALL ABANDONED DUCTWORK,PIPING,CONTROLS,WIRING,ETC., WHERE ACCESSIBLE IN RENOVATED AREAS. 6. WHERE CONTROLS ARE DEMOLISHED, REMOVE WRING BACK TO NEAREST CONTROL PANEL OR JUNCTION BOX. 7. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL EQUIPMENT AND COMPONENTS REMOVED DURING CONSTRUCTION. MECHANICAL LEGEND HVAC SYMBOL DESCRIPTION SYMBOL DESCRIPTION SUPPLY DUCT UP I I I I I I D FLEXIBLE DUCT r.1 SUPPLY DUCT DOWN I I VOLUMEDAMPER(VD) RETURN, RELIEF, TRANSFER OSA DUCT UP MOTORIZED DAMPER / RETURN, RELIEF, TRANSFER OSA DUCT DOWN FLEXIBLE CONNECTION (DUCT) EXHAUST DUCT UP TURNING VANES (TV) R EXHAUST DUCT DOWN BACKDRAFTDAMPER(BD) RECTANGULAR OUCTSOUAREELBOWUP Q THERMOSTAT(T'STAT) RECTANGULAR DUCT, RADIUS ELBOW UP X0 ROUNDDUCT RECTANGULAR DUCT, SQUARE EL BOW DOWN s POINT OF CONNECTION BETWEEN NEW AND EXISTING RECTANGULAR DUCT, RADIUS ELBOW DOWN 3091FM AIR TERMINAL SIZE, TYPE &CFM ROUND DUCT ELBOW UP X)X SQUARE DUCT ROUND DUCT ELBOW DOWN ® CEILING AIR TERMINAL - SQUARE PLUMBING SYMBOL DESCRIPTION SYMBOL DESCRIPTION GATENALVE(GV) DOMESTIC COLD WATER(CW) GLOBEVALVE DOMESTIC HOT WATER(HW) BUTTERFLYVPLVE DOMESTIC HOT WATER RECIRCULATION(HWC) 2 I PRESSURE REDUCING VALVE(PRV) SOIL, WASTE(S,W) 7-� CHECKVALVE(CV) VENT IV), OR HIDDEN BELOW WASTE TEMP.I PRESS. RELIEF VALVE(T&PRV) 1—COND� CONDENSATE PIPING E­�j BALL VALVE t—G �j NATURALGASPIPING 7­� BALANCINGVALVE O WASTE OR VENT UP THERMOSTATIC BALANCING VALVE _ WALL CLEANOUT(WCO) Cyr PIPE DOWN 0— FLUSH CLEANOUT(FCO/SCO) O* ------- PIPE UP Il� CLBANOUT(CO) BRANCH -TOP CONNECTION IN LINE WASTE CONNECTION BRANCH -BOTTOM CONNECTION P-TRAP 7� BRANCHSIDE CONNECTION BRANCHPIPEDOWN 7­ FLOWDIRECTION 1—� BRANCH PIPE UP >C OR DON VALVE IN RISERI DROP TEE &UP 7­� PIPE ANCHOR TEE T— a PIPE GUIDE ELBOWS, 90'&45' E­� FLEXIBLE CONNECTION (PIPE) G� CAP E­� REDUCER PUMP 2--�y a STRAINER FREEZE RESISTANT WALL HYDRANT E— Fl---� UNION THERMOMETER - VACUUM BREAKER PRESSURE GAGE DRAIN VALVE ❑0 FLOORDRAIN TRAP PRIMER WITH ACCESS PANEL FLOOR FUNNEL DRAIN ME ABOVE FINISHED FLOOR !—�� CROSSING LINES, NON CONNECTING MC MECHANICAL CONTRACTOR PIPE CONTINUATION EC ELECTRICAL CONTRACTOR FLOORSINK GC GENERAL CONTRACTOR W SANITARY SEWER POC POINT OF CONNECTION BFF BELOW FINISHED FLOOR t—R— REFRIGERANT PIPING 1 V tP SINGLE LINE INDICATED ON PLANS DESIGNATES THE PROPOSED ROUTING FOR THE REFRIGERATION PIPING BETWEEN THE INDOOR AND OUTDOOR UNITS. THAT SINGLE LINE REPRESENTS ALL THE REQUIRED PIPING RUNS REQUIRED FOR THE SYSTEM DESIGNED. cmn�pm ©zOza Toran� Nan ai nq,n ��,�m G 1 0 1 1 on I I Q I I I I I I I PdIE) I T� /'4it I I E42 I I I I O _ _ O O S O O yllE) /4 1-G(E) 1 a I / �I 4--- --- / GI -- - — ------ ----- I TRIE 1 _ 1'2yE) 1 1'IE) 1 _ _ 2IE) 11 1 _ _ 1 11 1 a 1 - �� a tyN(EI 1 2 E) 3� 1Y (E) I I O O O s I n A4 i0iv. I anuu4 a I 1 1) 1 1 i 1 I I I I I I I I MECHANICAL DEMOLITION PLAN SCALE: 1)8'= 14' GENERAL NOTES 1. THIS DRAWING WAS CREATED FROMAS-BUILT DOCUMENTATION AND FIELD NOTES AND MAY NOT REPRESENTACTUPL CONDITIONS. CONTRACTOR TO FIELD VERIFY ACTUAL CONDITIONS AND REVIEW SCOPE PRIOR TO COMMENCING WORK. 2. ITEMS SHOWN DARK AND DASHED INDICATE EXISTING ITEMS TO BE REMOVED. ITEMS SHOWN LIGHT REPRESENT EXISTING TO REMAIN. DEMOLITION NOTES O REMOVE EXISTING GAS FIRED UNIT HEATER, DUCTWORK,HANGERS, AND APPURTENANCES. RETURN UNIT HEATER TO OWNER. TOVANI HART O2 REMOVE Yq GAS PIPING. CAP CONNECTION TO EXISTING GAS AT MAIN TO MAINTAIN SERVICEABILITY OF EXISTING SYSTEM. o 9 MCPOILAUMB✓IAA ST. SW. 98501 P.0.a39.02T4 F350.350.5614 O3 REMOVE EXISTING ELECTRIC UNIT HEATER, MOUNTING BRACKET, AND APPURTENANCES. RETAIN EQUIPMENT FOR REINSTALLATION. iI A Division of TM,Systems — ® EXISTING GAS FIRED WATER HEATER TO REMAIN. SEE DETAIL ON SHEET M6.01. fi021 121h Street East, Su0e 200Fife, W9shi0gto098424 T:253.922.04461 F: 253.922.0896 O REMOVE T-STATANDWIRING TO EXISTING GAS FURNACE. MAINTAIN TSTAT FOR REINSTALLATION. 1*1 12), 2026 r J O Z oO - � vvi z ::)0 c� 0) o VJ cm z dm cU G Q N J z z LLI N } 2024-010 �n7 09.1 61O0s4 BID SET UtMULI I IUN FLAN MD101 cro hl©— Tway Han ui yin Saa 1. IT rn n n ran ni 1 1 1 \ 1 1 1 IL L L ,L L 1 1 L 1 3 4A' 3'W 2 w 2"V 3"W 2A qyy 2"W Y'W© -- 3"W 2 4 2'W 1 1 �1 ,1 IL 11 1\ 1 �1 nl ll `1 _ 1 11 L 1\\I IA PLUMBING FOUNDATION PLAN SCALE 118"=1'-0" GENERALNOTES t. HATCHED AREA INDICATES AREA FOR SLAB CUT AND REMOVAL. CONSTRUCTION NOTES 0 WASTE SANITPIPING RUN WER 335.4). O INWAO.E. WASTE PIPING RUN INW FINISHED FLOOR. RCI-ARITMOV SHOWN ON THIG PLAN FOR CLARITY. SHOWN O3 DROP WASTE PIPE AT THIS LOCATION TO ACCOMMODATE INVERT DIFFERENCE FROM FINISHED TOVANI HART FLOOR TO OUTSIDE FINISHED GRADE. Od STRUCTURAL REINFORCED SLAB UNDER WALL. SEE 609 A COLUM61A ST, SW, O L Y M P I A W A360.9 6 5 0 1 SHEET S201 FOR SITAR CUTTING DETAILS. TERMINATE P360.339.02T4 F350.5614 SLAB CUT 1'43' FROM CENTER OF WALL. SCAN FLOOR FOR LOCATION OF STRUCTURAL REBAR AND REMOVE CONCRETE FOR PIPE PENETRATION WITHOUT Aff`C DAMAGING STRUCTURAL ELEMENTS. A Division of Tm,SyMems ({ 6021 121h St.. East, Suite 200 Fife, Washington 9g42d T:253.922.04461 F:253.922.0896 T.1=4 J r 0 Z o0 L z �0 ai o ^ cm U Z mm J � � z N } 2024-010 osn� av 09.19.2024 BID SET PLUMBING FOUNDATION PLAN M101 cro hl©--.ni HI Ni yin —1 ENLARGED PLUMBING PLAN scaLE: va=r-o 1 n PLUMBING FLOOR PLAN AND ENLARGED PLAN scaLE: Ire" , GENERALNOTES CONSTRUCTION NOTES 1. THIS DRAWING WAS CREATED FROM AS -BUILT Oj CONNECT 7yZ CW TOIXISTING CW AT MECHANICAL PLATFORM. DOCUMENTATION AND FIELD NOTES AND MAY NOT iYZ REPRESENT ACTUAL CONDITIONS. CONTRACTOR TO O EXISTING HOT WATER TANK ON MECHANICAL PLATFORM. SEE DETAIL ON FIELD VERIFY ACTUAL CONDITIONS AND REVIEW SCOPE SHEETMI PRIOR TO COMMENCING WORK. 2. ITEMS SHOWN DARK AND DASHED INDICATE EXISTING O FREEZE PROOF WALL HYDRANT, BALL VALVE, AND ASSOCIATED%ACW PIPING ITEMS TO BE REMOVED. ITEMS SHOWN LIGHT IS PART OF ALTERNATE BID. LOCATION PIPE ON WARM SIDE OF INSULATION. REPRESENT EXISTING TO REMAIN. © CONNECT%" CONDENSATE FROM ICU-2&II TO TAILPIECE OF KITCHEN SINK O TERMINATE Y"CONDENSATE FROM II &ICU-0, 2' ABOVE FLOOR RIM OF SERVICE SINK. © LOCATE IN CEILING SPACE. O CONNECT DISHWASHER TO ADJACENT SINK PER MANUFACTURERS RECOMMENDATIONS. GENERAL NOTES 1. THIS DRAWING WAS CREATED FROMAS-BUILT DOCUMENTATION PND FIELD NOTES AND MAY NOT REPRESENT ACTUAL CONDITIONS. CONTRACTOR TO FIELD VERIFY ACTUAL CONDITIONS AND REVIEW SCOPE PRIOR TO COMMENCING WORK. 2. ITEMS SHOWN DARK AND DASHED INDICATE EXISTINGITEMS TO BE REMOVED. ITEMS SHOWN LIGHT REPRESENT EXISTING TO REMAIN. CONSTRUCTION NOTES O O O O Ot 14114 DUCT UP THROUGH ROOF TO ROOF CAP IN T T EXISTING SKYLIGHT. TO VA N I HART Q BROWN BCSEK13OSS RANGE HOOD, 300 CFM(120V, 1 PH, 609 A COLUMBIA ST. SW. 0.65.4). OLYMPIA, WA 98501 O3 PROVIDE WALL CAP'WIRAFT DAMPER. REUSE IF 360.339.02T4 F 360.350.5614 � EXISTING WALL PENETRATION. ZrA e el / 0 EXISTING GAS FURNACE. A Division of TenSyMems 3 I 0� OS RELOCATE AS 6021 121h Street East, Su0e 200 MODA ELOVIDE CATION. REQUIRED TO ACCOMMODATE LOCATION. TO ACCOMMODATE Fife, Washington 98424 1 1 © REINSTALL EXISTING ELECTRIC UNIT HEATER AND T: 253.922,04461 F: 253.922,0896 1a10 10'10 EXISTING MOUNTING HARDWARE. COORDINATE `14 Wowan ® CONNECTION WITH EC. QQgBP 4V EWH m EWH 12/21 •_ — •��ac / z ICU= 8"0 y 3.26110 saO N 4 � c I 412]2ox 120 M O nn vJ -- 1 J 6 0 C L 14114 14I14 ICU13 1a10 a • O O ICU-2 ol _ T T V I I I `U C6Y' Z M O cc LZa G a Oc Z a'� m I I I Q y> a G > EXISTING ELECTRIC EXISTING ELECTRIC J Z E /111THEATER UNITHEATER� LLI N N I I I VVV ® p } N � Al I I n n I ,Da xo. zoz4am 09.1 61O0s4 BID SET MECHANICAL FLOOR PLAN SCALE: 141'=1'-0' M301 -m m©.. To —Han ui" .re..Nw MECHANICAL REFLECTED CEILING PLAN SCALE: 118'=1'A' GENERAL NOTES 1. THIS DRAWING WAS CREATED FROMASBUILT DOCUMENTATION AND FIELD NOTES AND MAY NOT REPRESENTACTUAL CONDITIONS. CONTRACTOR TO FIELD VERIFY ACTUAL CONDITIONS AND REVIEW SCOPE PRIOR TO COMMENCING WORK 2. ITEMS SHOWN DARN AND DASHED INDICATE EXISNNG ITEMS TO BE REMOVED. ITEMS SHOWN LIGHT REPRESENT EXISTING TO REMAIN. TOVANI HART 609 A COLUMBIA ST. SW. OLYMPIA, WA 96501 P 360.309.02T4 • F3So—.5614 AFrA V A Division of TenSyMems 6021 121h SOeet East, Suite 200 Fife, Washington 98424 T: 253.922,04461 F: 253.922,0896 1*112- J t— Oz o0 z ry ::)0 a 0— �Q o ^ cm U Z dO 2 Q a Jry 3 z LLI � N E N } 2024-010 'A T ev 09.11.2124 SET MECHANICAL REFLECTED CEILING PLAN M401 -m m © aaza>•o--u1" . re..Nw �1 1 1 �11 1 11 T T T T I I I I MECHANICAL ROOF PLAN SCALE: 118'=1'A' CONSTRUCTION NOTES O INTAKE AIR ROOF CAP. O EKHAUSTAIRROOFCAP. CLEANOUT ACCESS COVER, TOP OF COVER TO BE FLUSH WITH TOP OF FINISHED FLOOR. 1V SQUARE CONCRETE PAD TROWEL SMOOTH AND EDGE. BRASS CLEANOUT PLUG WITH COUNTERSINK SCREW HEAD. II III I _ 118 CASTIRON BEN D, 118 BEND BALANCEOFPIPINGSAME ASCLEANOUT TO GRADE. FLOOR CLEANOUT (FCO) TYPICAL BELOWGRADE_/ `W BEND IF CLEANOUT WASTE PIPE COUPLING, OCCURS ATENDOFUNE. CLEANOUT TO GRADE (SC0) n 1 EANOUT CLDETAIL � EXISTING HOT WATER TANK PIPING DIAGRAM SCALE: DIAGRAMMATIC MAY EXTEND AS A WASTE OR VENT WALL WALL a EGRADEWASTE AND VENT PIPE COUPLING EXTENDPIPINGAS REQUIRED WHEN INSTALLED IN BRICK STAINLESS STEEL WALL PLUGGED COVER AND SCREW. TEE WITH 1TORASNOTED— T CLEAMLIT BELOWGUIDE ] WASTE PIPE I COUPLING. 118, BALANCE, SAME AS CLEANOUT TO GRADE. - WALL CLEANOUT (WOO) n CLEANOUT DETAIL L6 WATER HEATER DEMOLITION NOTE: REMOVE EXISTINGy"HWC LINE AS REQUIRED TO ACCOMMODATE NEW Y4'HWC. RETAIN EXISTING CIRCULATION PUMPANDAQUASTAT. WATER HEATER CONSTRUCTION NOTES: 1O 4'HWC FROM NEW RESTROOMS. PROVIDE WITH NEW CHECK VALVE, BALANCING VALVE, AND BALL VALVE. BALANCE TO ] GPM. 2O CONNECTION TO EXISTING Y,'HWC. PROVIDE NEWy'CHECK VALVE, BALANCING VALVE, AND BALL VALVE. BALANCE TO GPM. O3 RECONNECT EXISTING 10 GPM CIRCULATION PUMP. CONNECT EXISTING AQUASTAT TO NEW Y4"CW PIPE AS INDICATED. 4Q PROVIDE NEW% CHECK VALVE AND BALANCING VALVE ON 4' CONNECTION TO EXISTING VOW. TOVANI HART 609 A COLUMBIA ST. SW. OLYMPIA, WA 96501 �LL A Division of TrenSystems 6021 121h SOeet East, Suite 200 Fife, Washington 98424 T: 253 922.04461 1: 253.922,0896 1*112- CW SIZE PER PLANS J O I HW SIZE I NOTES: PER PLAN—{�L1, ACCESS TO ILL z T O 1 BETION MA IT VIES MAINTAINED AT ALL TIME. I PLUMBING FIXTURE I I U c�nn REFER TOPS LAN FO MODELSRE MODELS i AND PIPE SONG I 2. ALL PIPES ARE TO BE I I ROUTEDWITHIN PLUMBING CHASE WHEN 7 I AVAILABLE. T// I r I I I I I 13, BALANCEVALVE IS TO BE SIT O ALLOW NO MORE ^' z I I THEN SFTISEC OF HOT HROUGH BRPNCH C O LINE LINE. cG G ; Q — — B. MAXIMUM. VJ cm FINISHED FLOOR U 7 L > 00 -0 TO BUPPLV STOPS REFER NOTE: HW PIPE MAXIMUM LENGTHS ARE m N5 TO SCHEDULE TO COMPLY WITH WSEC TABLE C404.3.1 W �> N E PUBLIC LAY. HOT WATER PIPING DETAIL SCALE: DIAGRAMMATIC N } I VIR MAY EXTEND ASA EXTERIOR 14" WASTE OR VENT WALL TO FIXTURE FINISHEDWALL MINIMUM ABOVE GRADE WASTE NEOPRENE ��VIR BOOT AND VENT PIPE COUPLING. EXTEND PIP GAS ACCESS DOOR WALL HYDRANT = REQUIRED WHEN SFRAME PER TRAP PRIMER PER INSTALLED IN BRICK SPECIFICATIONS. SPECIFICATIONS I ROOF STAINLESS STEEL WALL COVER AND SCREW. PLUGGED TRAP PRIMER TEE WITH DISTRIBUTOR. `\ 12'ORAS NOTED. CLEANOUT `C.W. SERVICE (MAY) FLOOR COOMINATETHIS REMOVABLE BE SERVED FROM r HEIGHT WITH ABOVE OR BELOW i�a BELOW GRADE WASTE q PRIMER BRANCH SURROUNDING LINES. FIXTURES. (SEE PLANS) PIPE COUPLING. FINISHED FLOOR VENT PIPE FROM 1I8 C.I. BEND TO FIRM BUILDING FIXTURES NOTE INSTALL @ 18' ABOVE FINISHED SURFACE. FREEZE PROTECTED VENT THROUGH ROOF DETAIL n WALL CLEANOUT DETAIL 3 n TRAP PRIMER PIPING DIAGRAM n WALL HYDRANT DETAIL SCALE: DIAGRAMMATIC SCALE: DAGRAMMATIC �J SCALE. DIAGRAMMATIC �i SCALE'. DIAGRAMMATIC 2024-010 oOA� sv0919.2024 BID SET PLUMBING DETAILS M601 cro hl©--.1i—ui yin —1 A GENERAL 1. SUPPLY AND EXHAUST FANS SHALL OPERATE VIA INTERNAL COWROLS. 2. MOTOMZEDDAMPERSATTHEINTAEMDEXHAUSTAIRLOUVERS OR ROOF HOODS SHALL OPEN WHEN FAN IS COMMANDED ON AND CLOSE WHEN FAN IS OFF. DAMPERS SHALL FAIL CLOSED. B. STANDALONE CONTROLLER SHALL LOG: • FAN OWOFF AND POWER • FAN RUNTIME • FAN FAILURE ALARM(I.E. NO CURRENT WHEN COMMANDED ON) • OAMPER POSITION(% COMMANDED OPEN) • DAMPER END SWITCH STATUS TOVANI HART 609 A COLUMBIA ST. SW. OLYMPIA. WA 98501 P 360.3311— • F 360.350.6614 ilrjrG A Division of TenSyMems 6021 121h Street East, Suite 200 Fife, Washington 98424 T: 253.922,04461 F: 253.922,0896 1*1112- V) J 0 0 U U } _H Z D c� G O cU G J LLI F— z _O Q ry 0 ` 0- /� C/ i z 2024-010 oOA� sv 09.19.2024 SET MECHANICAL DETAILS a; Q cm N M am U) Q Z N } M602 PLUMBING FIXTURE SCHEDULE UNITNO FIXTURE MOUNTING MANUFACTURER AND MODEL NUMBERS W V XW CIA, REMARKS WATER CLOSET TOILET: AMERICAN STANDARD AFWALL 3351.101 1.28 OFF, PROVIDE WITH HARD -WIRED SENSOR P-1 ELECTRONIC FLUSH WALL SEAT: CHURCH 95OCT 4' 2' - 1' RUSMOMETER& TRANSFORMER. COORDINATE WITH EC. VALVE FLUSH VALVE'. SUDAN ROYAL 111 ESS-1.28-TMO PROVIDE WITH BOLT CAP$. WATER CLOSET 1.28GPF,PROVIDE WITH HARD -WIRED SENSOR P-IA ADA WALL TOILET: SEAT: AMERICAN STANDARD AFWALL 3361.101 CHURCH 95DOGT 4' 2' - 1 FLUSHOMETER &TRANSFORMER. COORDINATE WITH EC. ELECTRONIC FLUSH VALVE RUSH VALVE ROAN SLOAN ROYAL 111 ESS-1.28-TMO FRO VIDE WITH BOLT CAPS. ADA COMPLIANT. INSTALL RIM HEIGHT AT 18-AFF URINAL P-2 ELECTRONIC WALL URINAL: AMERICAN STANDARD WASHBROOK 6590.001 2 1-1R _ L4 0.125 OFF, PROVIDE WITH HARD -WIRED SENSOR FLUSH VALVE RUSH VALVE: MOAN ROYAL 18MSSJD.125-DBP-TMbHW RUSHOMETER&TRANSFORMER. URINAL 0.125 OFF, PROVIDE WITH HARD -WIRED SENSOR P2A ADA WALL URINAL: AMERICAN STANDARD WASHBROOK 6590.001 2" 1-1N' - L4' RUSHOMETER&TRANSFORMER..AOA COMPLIANT.INSTALL OAT ELECTRONIC FLUSH VALVE FLUSH VALVE'. MOAN ROYAL 1884:5$-0.125-DBP-TMbHW RIM HEIGHT I6"AFF. SINK AMERICANSTANDARD LUCERNE 0356.028 Pa LAVATORY COUNTER FITTINGS: SUPPLIES: ROAN OPTIMA UF4104­BOX-BDTCP-0.5GPMMLM-FCT MCGUIRELFBV 2" 7-1n" 7f2' 1N' 0.5 GPM, PROVIDE WITH TRANSFORMER &INSTIMIONAL ADA INSULATOR KIT. ADD TMV&BRACKET. TRAP: MCGUIREMCT SINK. JUSTDLADA2133A55J KITCHEN SINK FITTINGS'. CHICAGO 7B6G6AE36XK-317AB FRO VIDE WITH 4 HOLE FAUCET DRILLING. 1.5 GPM FAUCET. PJ DOUBLE COMP ADA COUNTER MOUNT SUPPLIES: TRAP: MCGUIRE LFBV2165CC MCGUIRE MCT150 SERIES 2 110 17 10 PROVIDE WITH INSTITUTIONAL ADA INSULATOR WT. WASTE: JUSTJPDA-35 FLOOR FIXTURE: FLORESTOEN MSR-2424 PROW DE CHECK VALVE ON HW& CW SUPPLY. PROVIDE WI P5 MOP SINK FLOOR FITTINGS: CHICAGOENMSS42 CP 3' 2' 31d' yp• SERVICE SINK STRAINER TRAP: CAST IRON WALL MOUNT BARRIER FREE. PROVIDE WITH TRAP, SERVICE SUPPLY STOP, P6 DRINKING FOUNTAIN WALL HXTURE: ELKAYF S-FDFP2I71( 2' 1-112" - it? AND SUPPORT SYSTEM. (I 15V, 360W, MOM POWER -BOTTE FILLER CONNECTION) COORDINATE WITH EC. BARRIER FREE. PROVIDE WFH TRAP, SERVICE SUPPLY STOP, P$A WALL MOUNT WALL F-RE RNAY EZWSMOK 2' 1-1R' - 1/C ANDSUPPORT SYSTEM.(115V, 350W, MCA4i POWER BOTTLE FILLER CONNECTION) COORDINATE WITH EC. OF FREEZE PROOF P T WALL HYDRANT WALL FIXTURE: JR SMILH 5619-SAP - - 3N' - PROWDE WITH REMOVABLE HANDLE BOOSTER TANK SCHEDULE UNIT NO MANUFACTURER MODEL LOCATION -MUM TANKVOLUME (GAL) MAXIMUM ACCEPTANCE FACTOR ON TEMF MAX TEMP MA% PRESSURE (PSI) TANK CONFAB. REMARKS BT-1 AMTROL WX-200 ABOVE JANITOR 119 14 0.81 40 200 150 HORIZONTAL NOTES FOR EXPANSION TANK SCHEDULE TRAP PRIMER SCHEDULE UNITNO MANUFACTURER LOON TRAPS NUMBEROF ELECTRICAL REMARK MMS VOLTS W PH ETPA PRECISION PLUMBING PRODUCTS MEN 118 2 120 6 1 1 NOTES FOR ELECTRONIC TRAP PRIMER SCHEDULE 1. PROVIDE WITH CABINETANO ACCESS PANEL FOR SURFACE MUM INSTALLATIONS. PROVIDE WITH ACCESS PANEL WHEN INSTALLED RECESSED. TOVANI HART 609 A COLUMBIA ST. SW. OLYMPIA, WA 98501 P 36o. .02T4 ^ F 360.350.5614 ZrA V A Division of Tm,SyMems 6021 121h Street East, Suite 200 Fife, Washington 98424 T: 253.922,04461 F: 253.922,0896 1*11 2024 J r O Z O Z Ld_ ::)0 2i 0 o VJ c U Z mm 2 Q U) JLLJ 3 Z � � N E N } 2024-010 oeA� sv 09.19.2024 BID SET PLUMBING SCHEDULES M701 DEDICATED OUTDOOR AIR UNIT SCHEDULE SUPPLY FAN DATA EXHAUST FAN DATA SUMMER PERFORMANCE EFFECTIVENESS ELECTRICAL UNITNO MANUFACTURER MODEL LOCATIONOSA WEIGHT EXHAUST OSAPRE STARTER DISCONNECT REMARKS RETURN SUPPLY TOTAL CFM XP SHIP ESP RPM TOTAL ONXP SHIPESP RPM SUMMER% WINTER% MCA MOP FLA V PH (LBS) FILTERS FILTERS FURNISHED BY FURNISHED BY WB DB WB WB EAT EAT A EAT EAT A LAEAT DOAS1 SPADVANCING THORN 800V HALL 116 WO 0.50 0.40 0.8 2750 1 700 0.50 0.40 0.8 1 V60 85.0 1 65.0 1 75.0 62.0 78.7 63.0 1 62.0 602 3.9 20.0 1.i 200 1 510 MERV8 MERV8 MFR I EC 1 1,2 NOTES FOR DEDICATED OUTDOOR AIR UNIT SCHEDULE 1. PROVIDE WITH SINGLE POINT POWER CONNECTION 2 PROVIDE WITH MANUFACTURER'S VFD SPLIT SYSTEM INDOOR UNIT SCHEDULE UNITNO MANUFACTURER MODEL LOCATION INTERLOCKED WRH MOUNTING OEM HEATING COOLING ELECTRICAL STARTER FURNISHED BY DISCONNECT FURNISHED BY WEIGHT (CBS) REMARKS MEN TOTAL MBX MCA RUA MOP VOLTS PX ICU1 MITSUBISHI 7PKFYP004LM1408 HALL 116 OCU-1 WALL 124 2.3 2.8 208 1 MFR EC 25 1.2.3.4 CU-2 MITSUBISHI TPLFYPo30EM1/1A Ell KROOM120 OCU-1 CEILING 77/ 22.8 33.0 208 1 MFR EC 55 1,2,3,4 ICU3 MITSUBISHI TPLFYP03UEM142A BREAK ROOM 120 OCU-1 CEILING 777 22.6 33.0 MO.2 208 1 MFR EC 55 1.2.3.4 CU4 MITSUBISHI TPKFYP004LM14OB TOOLS STORGE 102 OCU-1 WALL 124 NIA 3.2 208 1 MFR EC 25 1,2,3,4,5 NOTES FORSPLIT SYSTEM INDOOR UNITSCHEDULE 1. EC TO PROVIDE SINGLE POINT POWER CONNECTION. CC TO INSTALL CONTROL WIRING BETWEEN INDOOR AND OUTDOOR 2. PROVIDE WITH MANUFACTURER'S INTERNAL CONDENSATE PUMP. 3. MOUNT UNIT ABOVE DOOR COORDINATE FINAL LOCATON WITH EC. 4. PROVIDEWITH MANUFACURER'S WIRED WALL MOUNTEDTHERMOSTAT. 5. COOLING ONLY. INTERLOCK WITH EXISTING GAS FURNACE. UNITS. SPLIT SYSTEM OUTDOOR HEAT PUMP SCHEDULE COOLNG I HEATING I ELECTRCAL UNIT NO MANUFACTURER MODEL LOCATION INTERLOCKED WITH TONS STARTER FURNISHED BY DISCONNECT FURNISHED BY WEIGHT (CBS) REMARKS COP MEN MENTOTAL MCA MOP VOLTS PH OHP-1 MRSUBISHI TUHYEI-ml NEXTERIOR ICU 6 72.2 4.1 11.9 BOA 320 50 1 COB 3 MFR EC 512 NOTES FORSPLIT SYSTEM CONDENSING UNIT SCHEDULE 1. EC TO PROVIDE SINGLE POINT POWER CONNECTION. CC TO INSTALL CONTROL AND POWER WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONDUIT WILL BE PROVIDED BY EC. 2. UNITUSES R410A REFRIGERANT. PROVIDE LONG LINE LENGTH KIT AND ADDITIONAL REFRIGERANT AS REQUIRED 3. PROVIDE LOW AMBIENT COOLING TO OF. 4. PROVIDE INVERTER DRIVEN COMPRESSORS FOR VARIABLE CAPACITY OPERATION. ELECTRIC WALL HEATER SCHEDULE UNITNO MANUFACTURER MODEL LOCATION WEIGHT (CBS) MOUNTING HEIGHT (', IN) ELECIPoCAL STARTER FURNISHED BY DISCONNECT FURNISHED BY REMARKS WATTS VOLTS PH EWH-1 KING PAW1215 WOMENS 117 10 1'E' SOO 120 1 MFR MFR 1,2 EWH-2 KING PAW1215 MEN$119 10 T-6' SOO 120 1 MFR MFR 12 NOTES POR ELECTRIC UNIT HEATER SCHEDULE 1. PROVIDEWITX$INOLE POLE INTEGRAL DISCONNECT SWITCH AND THERMOSTAT. 2. PROVIDE WITH RECESSED MOUNTING KIT. TOVANI HART 609 A COLUMB IA ST. SW. OLYMPIA, WA 98501 P 39o-.0274 • F3So-.5614 ZrA V A Division of TrenSystems 6021 121h Street East, Suite 200 Fife, Washington 98424 T: 253.922,04461 H 253.922,0896 1*112- 2024-010 oeA� sv 09.19.2024 BID SET MECHANICAL SCHEDULES M702