07-0276 Water #1 052208 From: Edward Smith
Sent: Thursday, May 22, 2008 4:32 PM
To: Tim Peterson
Cc: Jim Gibson; John Ivey; Kevin Ray; Karen Bennett; Steve Harrington; Deonne Hardy
Subject: Yelm Rv-Boat and Mini-Storage Plan Review Public Works.doc
Yelm Rv-Boat and Mini-Storage Plan Review form water department.
ry\Machine\Software\Classes\.htm\PersistentHandler City of Yelm Public Works Department
901 Rhoton Road
P.O. Box 479
Yelm, WA 98597
(360) 458-8406 Fax: (360) 458-8417
Public Works Inspection Report
Date: 22 May 2008 Page 1
Location: Yelm Rv/Boat and mini Storage Department: Water
Contractor: Rep:
1. The developer is responsible for the cost of the fire hydrant locks and the City of Yelm Water Department will order and install them. The project will not be final
until the City of Yelm has received the payment in full for the fire hydrant locks.
2. The existing water main should be a ten inch main (AC). This water main goes between Rhoton Road and Crystal Springs Road, May use a Hot Tap and saddle at station 10
+ 00.
3. Please use PVC pipe Class 150 /C- 900.
4. Why do we have a eight inch gate valve at each tee, at the fire hydrants runs? Can reduce this too eight inch gate valve at stations 10 +00, 14 + 22.82, 18 +85.73 and
21 + 28.47.
5. May use a hot tap and saddle at station 21 +28.47.
6. Will need to have Bollards around the fire hydrants to protect them.
7. I do not see a Potable water meter or an Irrigation meter and back flow assemblies on this print. Will the service lines come from the water main on Rhoton Road? Please
do not place them behind the fence or gate.
8. Jim is the city going to just Reduce Pressure Backflow Assemblies for commercial projects?
Reviewed by: Edward Smith, John I
Signed by: Edward Smith