Tahoma Terra 2 Apts Bld C LayoutSITE
NITS
CPVC HANGER CHART
I&k�-11.1&=R f_1..I1.� AZf_lI—
0 5 20
SCALE IN FEET
13
T.
SYSTEM FDC PIPING TO FDC IN YARD AT SIDEWALK
v; 1.25" 1.25" /
SPARE HEAD BOX
N \CHECK VALVE
WATER FLOW
INDICATOR
N
DRAIN VALVE
N
Ut N
PRESSURE
GAUGE iv
14 N
DRAIN PIPED TO EXTERIOR
1.25" AMES 2000B-FP BACKFLOW
---PREVENTER
15
I 2
N
SPRINKLER RISER
General Notes
16 8" WATER MAIN
1. OWNER TO PROVIDE ADEQUATE HEAT (407. MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING.
2. CPVC PIPE SHALL HAVE HANGERS 6'-0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD.
3. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING. GARAGE LEVEL PIPING TO BE REVERSE TENTED TO PREVENT
FREEZING.
4. ALL PIPING TO BE 1" C.P.V.C. U.N.O.
5. FLOW SWITCH TO BE MONITORED BY OTHERS
6. A 8" BELL TO BE LOCATED ON THE FRONT APPROACH TO BUILDING.
Sprinkler Symbol Legend both sheets total
SYM SPRINKLER ORIFICE SIZE, TYPE & FINISH
RELIABLE F1 RES 49 16'x16'
RELIABLE F1 RES 49 16'x16'
Reliable F 3 QR DRY Sidewall
Reliable DH 56 DRY Sidewall 28'x10'
QUAN
TEMP
IK FA(
195
155°
4.9
24
175'
4.9
24
155-
5.6
6 155- 5.6
TOTAL 1 249
1.25" 1.257'
TO 3RD FLOOR/ 2N D FLOOR TO 3RD FLOOR/
FROM 1 st FLOOR FROM 1 st FLOOR
SCALE 1/e•— 10-0"
EVERGREEN RE PROTECTION INC.
PO BOX 998
Puyallup, WA 98371
EVERGFP967LZ
Phone: (253) 252-7942
Stamp
WASHINGTON STATE
CERTIFICATE OF COMPETENCY
FIRE SPRINKLER SYSTEMS
n Michael 0. Hutchinson
E 1166-0599-BG Level
Evergreen Fire Protection, Inc.
EVERGFP fi7LZ
Signature p
re dx,rs eararef ra feemu miu fars.f �...-------,
Sheet Title
NFPA 13R FIRE PLAN
Tchomc Terra 2 Apts. Ed C
itle 143 01 TAHOMA BLVD SIE
YELM9 WA 98597
DATE: 2/27/2025
REV:
DRAWN: MH
SHEET: 1 OF 2
S 1 TE
NTS
General Notes
1. OWNER TO PROVIDE ADEQUATE HEAT (40°F. MIN) TO PREVENT
SPRINKLER PIPES FROM FREEZING.
2. CPVC PIPE SHALL HAVE HANGERS 6'-0" c\c AND NOT MORE THAN
6" FROM ANY SPRINKLER HEAD.
3. ALL ATTIC PIPING TO BE TENTED WITH BATT INSULATION TO PREVENT
FREEZING. GARAGE LEVEL PIPING TO BE REVERSE TENTED TO PREVENT
FREEZING.
4. ALL PIPING TO BE 1" C.P.V.C. U.N.O.
5. FLOW SWITCH TO BE MONITORED BY OTHERS
6. A 8" BELL TO BE LOCATED ON THE FRONT APPROACH TO BUILDING.
0
0
Sprinkler Symbol Legend both sheets total
SYM SPRINKLER ORIFICE SIZE, TYPE & FINISH
RELIABLE F1 RES 49 16'x16'
RELIABLE F1 RES 49 16'x16'
Reliable F 3 QR DRY Sidewall
CPVC HANGER CHART
11V ULVVn nP111VL1[ VLIPIIL
ALL PIPE TO BE 1"CPVC
UNLESS OTHERWISE NOTED
PIPE
A%N�
INSULATION TENTING DETAIL
0
0
1.25" 3RD FLOOR 1.25"
TO 3RD FLOOR SCALE 1/8._ 10-00 TO 3RD FLOOR
FROM 1 st FLOOR FROM 1 st FLOOR
Sheet Title
Stamp
EXPt7C5 WASHINGTON STATE
OEC 31.25 CERTIFICATE OF COMPETENCY
FIRE SPRINKLER SYSTEMS 1
Michael 0. Hutchinson 1
1166-0599-BG Level i
Evergreen Fire Protection, Inc.
EVERGFP 67LZ
Signature Date
m ixmeimawmaremYmmaucmsmmemmw ��.�
QUAN TEMP KFACTOR EVERGREEN SIRE PROTECTION INCY NFPA 13R FIRE PLAN
245 155* 49 POyalOp,9WA 98371 Tchomc Terra 2 Apts. Ed C
EVERGFP967LZ
.1 /
Zq 15 ' 1 5.6
Phone: (253) 252-7942 Job Title 14301 TA HOMA BL VD r//Al rEl SE
Reliable DH 56 DRY Sidewall 28'x10' 6 155° 5.6
YELM, WA 98597
TOTAL 249 DATE: 2/27/2025 REV: DRAWN: MH SHEET: 2 0F 2 :]� I